Liner Integrity Survey- Electrical Leak Location MWEA Lagoon Conference February 17, 2015 Presented by: Tammy Perkins Weaver Consultants Group

Transcript of Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey...

Page 1: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

Liner Integrity Survey- Electrical Leak Location

MWEA Lagoon Conference

February 17, 2015

Presented by:

Tammy Perkins

Weaver Consultants Group

Page 2: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

What is a Liner Integrity Survey?

or

Leak Location Survey?

Page 3: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

Liner integrity / Leak location survey is a

means used for locating leak paths (holes)

in installed geomembranes through the

use of electrical methods.

Page 4: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

When would this survey be performed?

• Immediately after construction before being placed into service (Integrity Survey)

• After being placed into service and an issue has surfaced. (Leak Location)

Page 5: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

The function of a geomembrane at a

WWTP is to prevent liquid flow into the

environment.

Page 6: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

73% of damage occurs during cover

soil placement

24% occurs during geomembrane

installation,

2% occurs during post construction

Geomembrane Hole Statistics (Nosko, 1996)

Page 7: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

Cover soil placement damage

Page 8: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

Wastewater leakage through the

geomembrane creates a

microbiological reaction creating gas

followed by the common whale.

Page 9: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical
Page 10: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

History This is a time-tested technology

• Early 80’s development started (USEPA)

• Mid 80’s first commercial surveys on soil

and water covered geomembranes

• Mid 90’s first exposed geomembrane

surveys

• Early 2000 first ASTM method published

• Technology continues to emerge and its

use is more common

Page 11: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical
Page 12: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

CHARACTERISTIC LEAK SIGNAL

Page 13: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

SIGNAL OVER AND BESIDE LEAK

Page 14: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

MAPPED VOLTAGE READINGS

Page 15: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

Leak Location Methods

D6747-04 Standard Guide for Selection of Techniques for Electrical detection of potential Leak Paths in Geomembranes

– Water Puddle System

– Water Lance System

– Di-Pole System

– Conductive Geomembrane Spark Test

– Arc Testing System

Page 16: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

Water Puddle Method (exposed geomembranes)

D7002-10 Standard Practice for Leak location on Exposed Geomembrane using Water Puddle System

Page 17: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

Water Lance Method (exposed geomembranes)

D7703-11 Standard Practice for leak Location on Exposed

Geomembranes Using the Water Lance System

Page 18: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

Water Covered Method (Di-pole)

D7007-09 Standard Practice for Electrical methods for Locating Leaks in Geomembrane Covered with Water or Earth Material (Di-pole)

Page 19: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

Soil Covered Method (di-pole)

D7007-09 Standard Practice for Electrical methods for Locating Leaks in Geomembrane Covered with Water or Earth Material (Di-pole)

Page 20: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

Spark Test

D7240-11 Standard Practice for Leak Location using Geomembranes with an Insulating Layer in Intimate Contact with a Conductive Layer via Electrical Capacitance Technique (Conductive Geomembrane Spark Test)

Page 21: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

Arc Test

D7953-14 Standard Practice for Leak Location on Exposed Geomembranes Using the Arc Testing Method

Page 22: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

Holes found utilizing this technology

Page 23: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical
Page 24: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical
Page 25: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical
Page 26: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical
Page 27: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical
Page 28: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical
Page 29: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical
Page 30: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

Boundary Conditions • A conductive medium above the

geomembrane;

• A conductive medium through the holes;

• A conductive medium directly under the geomembrane;

• No contact between the medium above and below the geomembrane other than the holes being sought.

Page 31: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical
Page 32: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

Limitations

Dry soils/frozen soils

Type of boundary soils

Multiple geosynthetic layers

Wrinkles / Waves

Other electrical interference

Page 33: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

Edmore WWTP Lagoon Liner Integrity Survey Project

Page 34: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

Storage Lagoon #3

5.8 acres

Storage Lagoon #2

5.2 acres

Primary Lagoon #1

1 acre

Page 35: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

Edmore WWTP Lagoon Project Lagoon Cross-Section (from bottom up)

• Prepared subgrade

• Geosynthetic Clay Liner

• 40-mil PVC geomembrane

• 12-inch thick protective cover layer (sand)

• Erosion control ballast on sideslopes

Page 36: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

Edmore Lagoon #3

Page 37: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

Edmore Lagoon #3

Page 38: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

Edmore Lagoon #3

Page 39: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

Edmore Lagoon #3

Page 40: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

Edmore Lagoon #1

Page 41: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

Edmore Lagoon #1

Page 42: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

Edmore Lagoon #2

Page 43: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

Edmore Lagoon #2

Page 44: Liner Integrity Survey- Electrical Leak Location Leak Location - Perkins.pdfLeak location survey after an operational issue has been identified is the quickest and most economical

Conclusions

Liner integrity survey immediately

after construction is the best means for a comprehensive evaluation of the complete installation

Leak location survey after an operational issue has been identified is the quickest and most economical means to find a hole.