Linear motion system LMS IndraLogic Interface Manual
Transcript of Linear motion system LMS IndraLogic Interface Manual
NYCe 4000
Linear motion systemLMS IndraLogic Interface Manual
ReferenceR911347216
Edition 04
NYCe 4000Linear motion systemLMS IndraLogic Interface Manual
Reference
DOK-NY4000-IND*LOG*V45-RE04-EN-E
RS-7896ea8d5b38d2a80a347ea5007b4340-4-en-US-6
Edition Release Date Notes
DOK-NY4000-IND*LOG*V45-RE01-EN-E 02/2015 First edition 45V02DOK-NY4000-IND*LOG*V45-RE02-EN-E 06/2016 2nd edition 45V08DOK-NY4000-IND*LOG*V45-RE03-EN-E 12/2017 3rd edition 45V13DOK-NY4000-IND*LOG*V45-RE04-EN-E 03/2018 4th edition 45V14
List of trademarks Microsoft®, Windows 7® and Windows 10® are either registered trademarksor trademarks of Microsoft® Corporation in the United States and/or othercountries.Products in this publication are referred to by their general trade names. Inmost, if not all cases, these designations are claimed as trademarks orregistered trademarks of their respective companies.
Copyright © Bosch Rexroth AG 2018All rights reserved, also regarding any disposal, exploitation, reproduction,editing, distribution, as well as in the event of applications for industrialproperty rights.
Liability The specified data is intended for product description purposes only and shallnot be deemed to be a guaranteed characteristic unless expressly stipulatedin the contract. All rights are reserved with respect to the content of thisdocumentation and the availability of the product.
Published by Bosch Rexroth AGP.O. Box 7170 ■ 5605 JD Eindhoven ■ The Netherlandshttp://www.boschrexroth.com
Title
Type of Documentation
Document Typecode
Internal File Reference
Record of Revision
Bosch Rexroth AG DOK-NY4000-IND*LOG*V45-RE04-EN-ENYCe 4000 Linear motion system LMS IndraLogic Interface Manual
Table of ContentsPage
1 LMS IndraLogic Interface............................................................................................... 31.1 Introduction............................................................................................................................................. 31.2 Overview................................................................................................................................................. 31.3 Used abbreviations in this manual.......................................................................................................... 5
2 CM Function Block library.............................................................................................. 72.1 Introduction............................................................................................................................................. 72.2 Data types............................................................................................................................................... 72.2.1 NYCE_STATUS................................................................................................................................... 72.2.2 CM_MOVE_PARS............................................................................................................................... 72.3 Function Blocks...................................................................................................................................... 72.3.1 Common information........................................................................................................................... 72.3.2 Edge-controlled FB: CmInitialize......................................................................................................... 82.3.3 Edge-controlled FB: CmMoveToPosition............................................................................................ 92.3.4 State-controlled FB: CmReadSystemVariable.................................................................................. 11
3 How to use the IndraLogic interface............................................................................ 15
4 NYCeCMSocketServer................................................................................................ 17
5 Notes on use of NYCe 4000 LMS with IndraLogic....................................................... 195.1 Configuration........................................................................................................................................ 195.2 Start-up sequence................................................................................................................................ 195.3 PLC application..................................................................................................................................... 20
DOK-NY4000-IND*LOG*V45-RE04-EN-E Bosch Rexroth AG I/21NYCe 4000 Linear motion system LMS IndraLogic Interface Manual
Table of Contents
Bosch Rexroth AG DOK-NY4000-IND*LOG*V45-RE04-EN-EII/21NYCe 4000 Linear motion system LMS IndraLogic Interface Manual
1 LMS IndraLogic Interface1.1 Introduction
NYCe 4000 Software LMS supports the PLC programming tool IndraLogic2G using socket communication. Bosch Rexroth IndraControl L25, L45, andL65 with the IndraMotion software package are supported. The PLC canexecute all CM functions and a subset of the NYCe 4000 standardfunctionality. The PLC uses the n4kcmsocketclient library (supplied byRexroth) that communicates with the CM Socket Server on the PC. Thisn4kcmsocketclient library uses IndraLogic-specific PLC libraries to accessthe socket interface.The PLC can also be from another manufacturer, but you have to implementthe n4kcmsocketclient library which interfaces with the CM Function Blocklibrary and the PLC manufacturer supplied socket communication interfaces.See for more information the NYCe 4000 LMS Generic PLC InterfaceManual.This manual describes the CM Function Block interface.
1.2 OverviewThe IndraLogic PLC architecture to the CM Socket Server architecture areshown in fig. 1-1 "IndraLogic PLC architecture" on page 4.
DOK-NY4000-IND*LOG*V45-RE04-EN-E Bosch Rexroth AG 3/21NYCe 4000 Linear motion system LMS IndraLogic Interface Manual
LMS IndraLogic Interface
application
PLC
NYCe 4000 API
IEEE 1394bor Ethernet
to NYCe 4000 nodes
“NYCe4000" PC
CM Socket Server
N4kCall N4kLoggerN4kCommunication
System libraries
n4kcmsocketclient library
n4kcmapi.libraryCM Function Blocks
CmMoveToPositionCmReadSystemVariable
Fig. 1-1: IndraLogic PLC architecture The IndraLogic PLC - CM Socket Server interface uses a client-server model.The CM Socket Server executes on the "NYCe4000" PC and handles thecommunication with the IndraLogic PLC. The CM Socket Server interpretsthe function call messages from the IndraLogic PLC, invokes thecorresponding NYCe 4000 function and returns the output arguments to theIndraLogic PLC. The CM Socket Server also supports logging error anddebug messages from the IndraLogic PLC.The IndraLogic PLC is the client and can execute CM functions. Then4kcmsocketclient library (n4kcmsocketclient.library supplied byRexroth) includes the interface with the CM Function Blocks(n4kcmapi.library) and the IndraLogic-specific libraries used toimplement the TCP/IP and UDP/IP socket communication.This manual describes the following information.● n4kcmsocketclient library, see chapter 2 "CM Function Block library" on
page 7.● NYCeCMSocketServer, see chapter 4 "NYCeCMSocketServer" on
page 17.
Bosch Rexroth AG DOK-NY4000-IND*LOG*V45-RE04-EN-E4/21NYCe 4000 Linear motion system LMS IndraLogic Interface Manual
LMS IndraLogic Interface
● PLC application, see chapter 5 "Notes on use of NYCe 4000 LMS withIndraLogic" on page 19.
1.3 Used abbreviations in this manualThe following table gives a summary of abbreviations used in this manual.
Abbreviation Description
API Application Programming Interface
CM Carrier Management
FB Function Block
IP Internet Protocol
LMS Linear Motion System
PLC Programmable Logic Controller
TCP Transmission Control Protocol
UDP User Datagram Protocol
Tab. 1-1: Summary of used abbreviations
DOK-NY4000-IND*LOG*V45-RE04-EN-E Bosch Rexroth AG 5/21NYCe 4000 Linear motion system LMS IndraLogic Interface Manual
LMS IndraLogic Interface
Bosch Rexroth AG DOK-NY4000-IND*LOG*V45-RE04-EN-E6/21NYCe 4000 Linear motion system LMS IndraLogic Interface Manual
2 CM Function Block library2.1 Introduction
The task of each CM Function Block is to execute a single CM function. EachCM Function Block executes its task according to the processing mode"terminating processing", because the functionality of a CM function iscompleted when it returns.Most CM Function Blocks execute their task according to the controllingmode "edge controlled", because the functionality of a CM function needs tobe executed only once. An example is CmMoveToPosition. Some of theCM Function Blocks execute their task according to the controlling mode"state controlled", because the functionality of a CM function can be executedrepeatedly. An example is CmReadSystemVariable.The description of the interface of the CM Function blocks uses a graphic forthe CM Function Block and a table that describes the purpose of the FunctionBlock along with a description of each input and output variable. Theinterface behavior is described in a signal-time diagram.
2.2 Data types2.2.1 NYCE_STATUS
This data type maps to the type NYCE_STATUS.
NYCe 4000 definition PLC definition Description
NYCE_STATUS UDINT The return type for allNYCe 4000 API functions.
Tab. 2-1: NYCE_STATUS mapping
2.2.2 CM_MOVE_PARSThis data type maps to the structure CM_MOVE_PARS.
NYCe 4000 definition PLC definition Description
struct CM_MOVE_PARS CM_MOVE_PARS
endPosition LREAL End position in pu.
maxVelocity LREAL Maximum velocity in pu/s.
maxAcceleration LREAL Maximum acceleration in pu/s2.
maxJerk LREAL Maximum jerk in pu/s3.
Tab. 2-2: CM_MOVE_PARS mapping
2.3 Function Blocks2.3.1 Common information
The variable ErrorID only contains a valid value when the variable Erroris TRUE. If the variable Done is TRUE, the variable ErrorID does not containa valid value.
DOK-NY4000-IND*LOG*V45-RE04-EN-E Bosch Rexroth AG 7/21NYCe 4000 Linear motion system LMS IndraLogic Interface Manual
CM Function Block library
If the value of the variable ErrorID is in the range of NYCE_STATUS codesCUSTOM_ERROR_BASE thru CUSTOM_WARNING_BASE, it means that acommunication error occurred during processing of the task. If the variableErrorID contains another value, it means that a NYCe 4000 error orwarning is returned by the executed CM function. The error codes are listedin the NYCe 4000 LMS Generic PLC Interface Manual (table 2-5).If a CM function returns a NYCe 4000 warning, the CM Function Blockprocesses it as a NYCe 4000 error. The variable Error is set to TRUE andthe variable ErrorID contains the NYCe 4000 warning code.
2.3.2 Edge-controlled FB: CmInitializeThe Function Block CmInitialize calls the CM function CmInitialize.
Execute
MachineData
Done
Active
Error
ErrorId
CmInitialize
BOOL
STRING
BOOL
BOOL
BOOL
NYCE_STATUS
Fig. 2-1: Function Block CmInitialize The following table describes the interface of the Function Block CmInitialize.
Name CmInitialize
Purpose Initializes the LMS. State: CM_SYSTEM_POWERUP Trans.: CM_SYSTEM_POWER_UP → CM_SYSTEM_INITIALIZED, All tracks: CM_TRACK_POWER_UP → CM_TRACK_IDLE
VAR_INPUT
Execute BOOL Start the command at the rising edge.
MachineData STRING Name of the machine data file. The filemust be specified using an absolute path.
VAR_OUTPUT
Done BOOL Command completed successfully.
Active BOOL Command is executing.
Error BOOL Command completed with an error.
ErrorId NYCE_STATUS Error code of the error.
Tab. 2-3: Interface description of the FB CmInitialize The signal-time diagrams of this Function Block are in the following figures.
Bosch Rexroth AG DOK-NY4000-IND*LOG*V45-RE04-EN-E8/21NYCe 4000 Linear motion system LMS IndraLogic Interface Manual
CM Function Block library
Execute
Active
Error
Done
1 PLC cyle1 2
Fig. 2-2: Signal-time diagram of an edge-controlled terminating FB, success‐fully completed
The Function Block becomes active when the variable Execute is set TRUE.This status is visible in the next PLC cycle as the variable Active is nowTRUE. In situation ①, the requested function is active during 2 PLC cycles,and in the subsequent PLC cycle the variable Done is set TRUE. As long asthe variable Execute has the value TRUE, the variable Done remainsTRUE. After the variable Execute is set to FALSE, the variable Done alsochanges to FALSE. In situation ②, the variable Execute is set TRUE andreset to FALSE in the next PLC cycle. This can be done, because theFunction Block is edge-controlled. The requested function is active during 3PLC cycles, and in the subsequent PLC cycle the variable Done is set TRUE.As the variable Execute is already set to FALSE, the variable Done changesto FALSE in the following PLC cycle.
Execute
Active
Error
Done
1 PLC cyle1 2
Fig. 2-3: Signal-time diagram of an edge-controlled terminating FB, completedwith an error
If the Function Block completes with an error, the status variables behaveidentical as in the successful completion condition, except that the variableDone remains FALSE and the variable Error changes to TRUE.
2.3.3 Edge-controlled FB: CmMoveToPositionThe Function Block CmMoveToPosition calls the CM functionCmMoveToPosition.
Execute
CarrierId
Done
Active
Error
ErrorId
CmMoveToPosition
BOOL
INT
BOOL
BOOL
BOOL
NYCE_STATUSMoveParsCM_MOVE_PARS
Fig. 2-4: Function Block CmMoveToPosition
DOK-NY4000-IND*LOG*V45-RE04-EN-E Bosch Rexroth AG 9/21NYCe 4000 Linear motion system LMS IndraLogic Interface Manual
CM Function Block library
The following table describes the interface of the Function BlockCmMoveToPosition.
Name CmMoveToPosition
Purpose Starts the movement of a carrier to a specified end position. When the command is successfully completed, the carrier hasstarted to move, unless the movement is suspended, due to thefact that the feed override is zero. State: CM_TRACK_ACTIVE, any carrier state, except CM_CARRIER_POWERUP Trans.: CM_CARRIER_STOPPED → CM_CARRIER_SUSPENDED (if feed override equals 0),
CM_CARRIER_STOPPED → CM_CARRIER_MOVING, CM_CARRIER_JOGGING → CM_CARRIER_MOVING, CM_CARRIER_MOVING → CM_CARRIER_STOPPED (after completion of movement)
VAR_INPUT
Execute BOOL Start the command at the rising edge.
CarrierId STRING Identification of the carrier.
MovePars CM_MOVE_PARS Movement parameters.
VAR_OUTPUT
Done BOOL Command completed successfully.
Active BOOL Command is executing.
Error BOOL Command completed with an error.
ErrorId NYCE_STATUS Error code of the error.
Tab. 2-4: Interface description of the FB CmMoveToPosition See fig. 2-2 "Signal-time diagram of an edge-controlled terminating FB,successfully completed" on page 9 and fig. 2-3 "Signal-time diagram of anedge-controlled terminating FB, completed with an error" on page 9 for thesignal-time diagrams of this Function Block.The following listed CM Function Blocks are of the same type.
CmActivateTrack CmAddCarrier
CmAddFirstCoil CmAddLastCoil
CmAddMovingCarrier CmAssignCarrierIds
CmCancelAddMovingCarrier CmCancelMoveAcrossTrackBounds
CmClearWarning CmDeactivateTrack
Bosch Rexroth AG DOK-NY4000-IND*LOG*V45-RE04-EN-E10/21NYCe 4000 Linear motion system LMS IndraLogic Interface Manual
CM Function Block library
CmDefineSyncGroup CmDeleteSyncGroup
CmDownloadCpaTable CmEnableBumper
CmEnableCpa CmEnableSensorDetection
CmEnableStartTrigger CmFreeArea
CmLinkCpaTable CmMoveAcrossTrackBounds
CmMoveAdjacent CmMoveProfile
CmMoveToTrack CmRemoveCarrier
CmRemoveFirstCoil CmRemoveLastCoil
CmRemoveMovingCarrier CmResetError
CmSelectFirstCoilAlternative CmSelectLastCoilAlternative
CmSelectSpecialControllerPars CmSetFeedOverride
CmSetTrackStateToIdle CmShutdown
CmStartSyncGroup CmStartVelocityMode
CmStopCarrier CmStopCarriers
CmStopVelocityMode CmSynchronize
CmUnlinkCpaTable CmWriteCarrierPars
CmWriteHomePars CmWriteSpecialControllerPars
Tab. 2-5: Edge-controlled Function Blocks
2.3.4 State-controlled FB: CmReadSystemVariableThe Function Block CmReadSystemVariable calls the CM functionCmReadSystemVariable.
Enable
VarId
Done
Active
Error
ErrorId
CmReadSystemVariable
BOOL
STRING
BOOL
BOOL
BOOL
NYCE_STATUS
Value LREAL
Fig. 2-5: Function Block CmReadSystemVariable The following table describes the interface of the Function BlockCmReadSystemVariable.
DOK-NY4000-IND*LOG*V45-RE04-EN-E Bosch Rexroth AG 11/21NYCe 4000 Linear motion system LMS IndraLogic Interface Manual
CM Function Block library
Name CmReadSystemVariable
Purpose Reads the value of the specified system variable. State: - Trans.: -
VAR_INPUT
Enable BOOL Execute the command continuously whileenabled.
VarId STRING Identification of variable.
VAR_OUTPUT
Done BOOL Command completed successfully.
Active BOOL Command is executing.
Error BOOL Command completed with an error.
ErrorId NYCE_STATUS Error code of the error.
Value LREAL Value of the variable.
Tab. 2-6: Interface description of the FB CmReadSystemVariable The signal-time diagrams of this Function Block are in the following figures.
Enable
Active
Error
Done
Fig. 2-6: Signal-time diagram of an state-controlled terminating FB, success‐fully completed
The Function Block becomes active when the variable Enable is set TRUE.This status is visible in the next PLC cycle as the variable Active is nowTRUE. The requested function is active during 2 PLC cycles, and in thesubsequent PLC cycle the variable Done is set TRUE. In the following PLCcycle the variable Done is reset to FALSE. As long as the variable Enablehas the value TRUE, the function is executed again. After 2 subsequent PLCcycles the variable Done changes again to TRUE. This cyclic behaviorrepeats as long as the variable Enable is TRUE. After the variable Enableis set to FALSE, the variable Active also changes to FALSE. Note that thevariable Done does not change to TRUE.
Bosch Rexroth AG DOK-NY4000-IND*LOG*V45-RE04-EN-E12/21NYCe 4000 Linear motion system LMS IndraLogic Interface Manual
CM Function Block library
Enable
Active
Error
Done
Fig. 2-7: Signal-time diagram of an state-controlled terminating FB, completedwith an error
If the active function completes with an error, the variable Error changes toTRUE and the function is not called again even though the variable Enableremains TRUE. In this condition the variable Error remains TRUE until thevariable Enable is reset to FALSE.The following listed CM Function Blocks are of the same type.
CmCheckArea CmGetAxisIdOfCoil
CmGetAxisIdOfCoil CmGetCarriersOnTrack
CmGetFeedOverride CmGetSyncGroup
CmGetTracks CmReadBumperPars
CmReadCarrierData CmReadCarrierPars
CmReadCarrierState CmReadCarrierVariable
CmReadCoilVariable CmReadEndstopPositions
CmReadErrorCode CmReadHomePars
CmReadPosition CmReadServerState
CmReadSingleCarrierData CmReadSpecialControllerPars
CmReadSystemVariable CmReadTrackData
CmReadTrackState CmReadTrackVariable
Tab. 2-7: State-controlled Function Blocks
DOK-NY4000-IND*LOG*V45-RE04-EN-E Bosch Rexroth AG 13/21NYCe 4000 Linear motion system LMS IndraLogic Interface Manual
CM Function Block library
Bosch Rexroth AG DOK-NY4000-IND*LOG*V45-RE04-EN-E14/21NYCe 4000 Linear motion system LMS IndraLogic Interface Manual
3 How to use the IndraLogic interfaceThe PLC application can use one or more instances of the N4kCall FunctionBlock to communicate with CM, see chapter 2 "CM Function Block library"on page 7. The actual communication with CM is performed by theN4kCommunication Function Block. The PLC application is responsible tocreate a communication program which calls an instance of theN4kCommunication Function Block, see fig. 3-1 "Example of acommunication program" on page 15.
Fig. 3-1: Example of a communication program The communication program must run as a separate task with high priorityand an interval time of 1 ms, see fig. 3-2 "Communication task configuration"on page 16.
DOK-NY4000-IND*LOG*V45-RE04-EN-E Bosch Rexroth AG 15/21NYCe 4000 Linear motion system LMS IndraLogic Interface Manual
How to use the IndraLogic interface
Fig. 3-2: Communication task configuration
Bosch Rexroth AG DOK-NY4000-IND*LOG*V45-RE04-EN-E16/21NYCe 4000 Linear motion system LMS IndraLogic Interface Manual
How to use the IndraLogic interface
4 NYCeCMSocketServerNYCeCMSocketServer is a tool in the Windows System Tray. The tool offersan LMS interface to which PLC applications can connect using sockets.When you start NYCeCMSocketServer from the Start Menu, the tool starts inthe System Tray.
Fig. 4-1: NYCeCMSocketServer started in the System Tray A notification text shows the number of active connections toNYCeCMSocketServer when you hoover the mouse over the icon in theSystem Tray.Right-click on the icon in the System Tray to open the pop-up menu of thetool. With the menu entry "Open" you can see the IP address and the portnumbers used by NYCeCMSocketServer and number of active connections.
Fig. 4-2: NYCeCMSocketServer dialog With the menu entry "Exit" you can close the communication with the PLCapplication and terminate NYCeCMSocketServer.
When NYCeCMSocketServer is started the socket server binds toINADDR_ANY (0.0.0.0), thus to all available network interfaces of the PC.This default behavior can be overruled by specifying a specific IP address inthe registry to which the socket server must connect. If the registry entry isnot available or the registry entry holds an invalid IP address, the socketserver will bind to INADDR_ANY.Both TCP and UDP connection use port 4242. NYCeCmSocketServer will notstart if the TCP port cannot be opened. If the UDP port cannot be opened,NYCeCmSocketServer logs the error and continues without logging support.The used port numbers can be configured in the registry of Windows (ifnecessary). The path of the registry entry isHKEY_LOCAL_MACHINE\Software\Rexroth\NYCe4000\Cmwith the following keys● IP address key = ServerIPAddress (type is String)
The string is a decimal-dotted IPv4 address.● TCP port key = TCPServerPort (type is DWORD)● UDP port key = UDPLoggerPort (type is DWORD)
DOK-NY4000-IND*LOG*V45-RE04-EN-E Bosch Rexroth AG 17/21NYCe 4000 Linear motion system LMS IndraLogic Interface Manual
NYCeCMSocketServer
Bosch Rexroth AG DOK-NY4000-IND*LOG*V45-RE04-EN-E18/21NYCe 4000 Linear motion system LMS IndraLogic Interface Manual
5 Notes on use of NYCe 4000 LMS with IndraLogic5.1 Configuration
To configure the communication between CM and your PLC application youmust set and specify IP address settings.
123
Nodenr: 0NodeName: Y
123
PC
LMS node
IP address“PLC”
IP address“CM”
ethernet CM
LAN
IEEE1394b or ethernet
NY4110 or NY4112
PLC
Fig. 5-1: Network configuration of the CM PC and the PLC connection ● The network adapter of the PC (on which CM runs) that connects to the
PLC must have a fixed IP address, IP address "CM". The PC must notuse DHCP to obtain an IP address from a DHCP server for this networkadapter.
● The IP address of the PC must be specified in the N4kCommunicationFunction Block.
● Note that the PC must have up to 3 ethernet network adapters.– Connection to the PLC.– Connection to the NYCe 4000 node, if the NY4112 MCU is used.– Connection to a LAN (optional).
Make sure that the IP address of the PC and the IP address ofthe PLC are in the same subnet.
5.2 Start-up sequenceCM starts the communication with all nodes when CM receives theCmInitialize command. Therefore, the start-up procedure for the systemis as follows.
1. Start PC and NYCe 4000 nodes2. Start NYCeCMSocketServer3. Start PLC application4. Start any additional Windows CM applications.
If a restart is needed, the mentioned start-up sequence must be followed.This means that you must close the additional applications, stop the PLCapplication, close NYCeCMSocketServer, and power cycle the PC and allnodes.NYCeCMSocketServer starts the UDP log server and the TCP server. TheUDP server binds itself to the configured UDP port (default 4242) and waitsfor data. Received data is logged in shared memory for the DEH subsystem.The TCP server binds itself to the configured TCP port (default 4242) andwaits for data. When data is received, the data is checked. If the data isinvalid, the error N4K_INVALID_REQUEST is returned, a quick stop on allaxes is executed and the TCP connection is closed. If the data is valid, the
DOK-NY4000-IND*LOG*V45-RE04-EN-E Bosch Rexroth AG 19/21NYCe 4000 Linear motion system LMS IndraLogic Interface Manual
Notes on use of NYCe 4000 LMS with IndraLogic
specified CM function is executed and the return status of the executedfunction is returned to the application.
5.3 PLC applicationThe PLC application can use an "unlimited" number of N4kCall FunctionBlocks, but only 40 N4kCall Function Blocks can be active. If too manyN4kCall Function Blocks are active, the return statusN4K_STATUS_OUT_OF_RESOURCES is returned. An N4kCall Function Blockis active from the moment that the Function Block is enabled until the reply isretrieved by the Function Block. In case of a timeout the call remains activeuntil the message is received by the N4kCommunication Function Block.The PLC application is responsible to call the N4kCommunication FunctionBlock every 1 ms in a separate task. To initialize the communication with theNYCeCMSocketServer the PLC application must callN4kCommunication() with the Enable flag set TRUE. When theInOperation flag of N4kCommunication is set, N4kCall requests can besubmitted.By default a connection to 192.168.0.1:4242 is made. To change this defaultsetting, you must specify the new IP address and/or port number in the firstcall to the N4kCommunication Function Block with the Enable flag set TRUE.The PLC application should call N4kLogMsg() in the main application eachPLC cycle. When there is no data to log, the call returns immediately. Bydefault the logger logs to 192.168.0.1:4242. To change this default setting,you must specify the new IP address and/or port number in the first call toN4kLogMsg().The N4kLogger has a flag that indicates the status. The N4kLogger isintended to log errors in the N4kCommunication process, not intended to loguser messages.
Bosch Rexroth AG DOK-NY4000-IND*LOG*V45-RE04-EN-E20/21NYCe 4000 Linear motion system LMS IndraLogic Interface Manual
Notes on use of NYCe 4000 LMS with IndraLogic
Notes
DOK-NY4000-IND*LOG*V45-RE04-EN-E Bosch Rexroth AG 21/21NYCe 4000 Linear motion system LMS IndraLogic Interface Manual