LINE CURRENT DIFFERENTIAL SYSTEM - BELMET · 2011. 11. 7. · relay operating signals thus...
Transcript of LINE CURRENT DIFFERENTIAL SYSTEM - BELMET · 2011. 11. 7. · relay operating signals thus...
201
Tran
smis
sion
Lin
e Pr
otec
tion
g Digital Energy
• Phasesegregateddifferentialprotectionensuressecurehigh-speedsinglepoletripping
• CompleteIEC61850ProcessBussolutionprovidingresourceoptimizationandminimizingtotalP&Clifecyclecosts
• Reliableandsecureprotectiononlinesequippedwithseriescompensation
• Increasedsensitivitythroughdynamicchargingcurrentcompensationandcommunicationchannelasymmetrycompensation
• Advancedfaultanddisturbancerecording,includinginternalrelayoperatingsignalsthuseliminatingtheneedforexternalrecordingdevices
• PhasorMeasurementUnit-SynchronizedphasorinformationaccordingtoIEEEC37.118standard
• RobustnetworksecurityenablingCriticalInfrastructureProtectionthroughusercommandlogging,anddualpermissionaccesscontrol
• Ambienttemperaturemonitoringwithalarmingwhenoutsidetemperatureexceedsupperthresholds
• Overheadlinesincludingseriescompensatedlinesandundergroundcablesofdifferentvoltagelevels
• Circuitswithtappedtransformerfeeders• Suitableforthreeterminallineconfigurations,withchannel
redundancyanddirecttransfertripping(DTT)
• Wideareasystemmonitoringandcontrolandusingintegratedprotectionandsynchrophasormeasurement
• Singleanddual-breakercircuitsrequiringsinglepole/three-poleautoreclosingandindependentsynchrochecksupervision
• Distributedbusbarprotection
• Realtimemonitoringofremote,localanddifferentialperphasecurrents
• Oscillography-64samples/cycle,upto64records• EventRecorder-1024timetaggedevents,with0.5msscan
ofdigitalinputs• DataLogger-Upto16channelswithuserselectable
samplingrate• Synchronisedmeasurementofvoltage¤tand
sequencecomponentphasors-1to60phasors/sec• Multi-endedfaultlocationconsistentlyproviding2%
accuracy
Monitoring and Metering
Protection and Control• Phasesegregatedlinecurrentdifferentialwithadaptive
restraint&Grounddifferential,stubbusprotection• Thermalprotection,under/overfrequency,brokenconductor• PhaseDistance(threeZones)withindependentcompensation
settingsforin-zonepowertransformers• Grounddistance(threezones)withindependentselfand
mutualzerosequencecompensation,reversepower• Reversepower,OutofSteptrippingandpowerswingblocking• Thermaloverload,phase,neutralandnegativesequence
directionalovercurrent;andbrokenconductor• Over,UnderandrateofchangeofFrecuency,Synchronism
checkfordualbreakerapplications
Communications• Networkinginterfaces–100MbitFiberOpticEthernet,RS485,
RS232,RS422,G.703,C37.94• MultipleProtocols-IEC61850,DNP3.0Level2,ModbusRTU,
ModbusTCP/IP,IEC60870-5-104,EthernetGlobalData(EGD)• DirectI/O–secure,high-speedexchangeofdatabetween
L90sforDirectTransferTripapplications• EmbeddedManagedEthernetSwitchwith4-100MbitFiber
opticportsand2copperports
FEATURES
APPLICATIONS
KEY BENEFITS
EnerVista™ Software• GraphicalLogicDesignerandLogicMonitortosimplify
designingandtestingprocedures• Documentandsoftwarearchivingtoolsettoensure
referencematerialanddeviceutilitiesareup-to-date• EnerVista™Integratorprovidingeasyintegrationofdatain
theL90intoneworexistingmonitoringandcontrolsystems
• Robustcommunicationswithupto8HardFiberBricks• SeamlessintegrationwithexistingL90functions• Redundantarchitecturefordependabilityandsecurity
IEC 61850 Process Bus Interface
L90Multilin™
LINE CURRENT DIFFERENTIAL SYSTEM
Phasesegregatedlinecurrentdifferentialanddistanceprotection
202202
L90Line Differential SystemTr
ansm
issi
on L
ine
Prot
ectio
n
www.GEDigitalEnergy.com
Protection and ControlThe L90 is a high-end cost effectiveline current differential protection relayintendedfortransmissionlinesandcablesof different voltages levels providingreliableandsecureoperationevenundertheworstcasepowersystemconditions.The L90 provides high-speed phase-segregated fault clearance suitable forsingleandthree-poletrippingapplications.PartoftheUniversalRelayfamily,theL90comeswithavarietyofversatilefeaturestruly integrating protection, monitoring,metering, communicationandcontrol inoneeasy-to-usedevice.TheUniversalRelayfamilyoffersahighdegreeofmodularityin its design and functionality providingsuperior performance in protection andcontrolmeetingthetoughestrequirementsofthemarketplace.
Segregated Current Differential ProtectionThe L90 is a phase segregated currentdifferential protection relay, which usessuperior and patented algorithms toaddress the challenges of bandwidth ,security,dependabilityand sensitivity incurrentdifferentialrelaying.Bandwidth requirements are effectivelyaddressedbymeansofapatentednewdata consolidation technique called“phaselets”.Thispermitsapplicationwithinacommunicationsbandwidthof64Kbps,
andcandetect faultswithinahalfcyclepluschanneldelay.The L90 innovative dual slope adaptiverestraint characteristic, based onestimates ofmeasurement errors, allowtherelaytobesecureonsevereexternalfaults while maintaining sensitivity forinternal faults. The estimate of errors intheinputcurrentspermitsmoresensitivesettingsthanthoseusedinthetraditionalpercentdifferentialschemes.TheL90approachtoclocksynchronizationrel ies upon precise distr ibuted
synchronization. Clocks are phasesynchronized to each other andfrequency synchronized to the powersystem frequency.Each relaycomparesitsclocktothephaseoftheotherclocksandmakesappropriateadjustments.Thisallows forgreater transient ride-throughfor power system and communicationsdisturbances.
Enhancedadditionalsecurity isprovidedby a sensitive current disturbancedetector,whichcanbeusedtosupervisethecurrentdifferentialelement.
The L90 is the single point for protection, control, metering, and monitoring in one integrated device that can easily be connected directly into DCS or SCADA monitoring and control systems like Viewpoint Monitoring as shown.
831706AS.CDR
L90 Line Differential System
52
Monitoring CLOSE TRIP
Data From/To Remote End(via Dedicated Communications)
MeteringFlexElementTM Transducer
Inputs
50DD 51N50N67P87L 21P 68 7850BF51_251P50_2
32 49
79
50P 21G67N/G
81U/O
27P
27X59N
59X
59P
25
51G50G
DEVICENUMBER
21G21P2527P27X50BF50DD
50G50N50P50_251G51N51P51_25259N59P59X67N67P67_268787987L
Ground DistancePhase DistanceSynchrocheckPhase UndervoltageAuxiliary UndervoltageBreaker FailureAdaptive Fault Detector
Ground Instantaneous OvercurrentNeutral Instantaneous OvercurrentPhase Instantaneous OvercurrentNegative Sequence Instantaneous OvercurrentGround Time OvercurrentNeutral Time OvercurrentPhase Time OvercurrentNegative Sequence Time OvercurrentAC Circuit BreakerNeutral OvervoltagePhase OvervoltageAuxiliary OvervoltageNeutral Directional OvercurrentPhase Directional OvercurrentNegative Sequence Directional OvercurrentPower Swing BlockingOut-of-Step TrippingAutomatic RecloserSegregated Line Current Differential
FUNCTION
ANSI DEVICE NUMBERS AND FUNCTIONS
(senstive current disturbance detector)
Functional Block Diagram
L90 - Protection, Metering, Monitoring and Control
DeviceNumber Function21G GroundDistance21P PhaseDistance25 SynchronismCheck27P PhaseUndervoltage27X AuxiliaryUndervoltage32 SensitiveReversePower49 ThermalOverload50BF BreakerFailure50DD CurrentDisturbanceDetector50G GroundInstantaneousOvercurrent50N NeutralInstantaneousOvercurrent50P PhaseInstantaneousOvercurrent50_2 NegativeSequenceInstantaneousOvercurrent51G GroundTimeOvercurrent51N NeutralTimeOvercurrent51P PhaseTimeOvercurrent51_2 NegativeSequenceTimeOvercurrent52 ACCircuitBreaker59N NeutralOvervoltage59P PhaseOvervoltage59X AuxiliaryOvervoltage67_2 NegativeSequenceDirectionalOvercurrent67N NeutralDirectionalOvercurrent67P PhaseDirectionalOvercurrent68 PowerSwingBlocking78 Out-of-stepTripping79 AutomaticRecloser81U/O Under/OverFrequency,df/dt87L SegregatedLineCurrentDifferential
ANSIDeviceNumbers&Functions
203203
L90Line Differential System
Tran
smis
sion
Lin
e Pr
otec
tion
www.GEDigitalEnergy.com
Ground Differential “87G”
The Ground Differential function “87G”protects against low-current single line-to-ground faults. It has a single slopecharacteristicandusesthevectorialsumofall in-zonephasecurrentstocalculatetheNeutraldifferentialcurrent. with themaximum value of phase current beingusedas restraint . This function togetherwith the phase differential deliversenhancedsensibilityandselectivitytotheprotectionscheme.
Charging Current Compensation
For long transmission l ines andundergroundcables,thechargingcurrentmaybelargeandresultinexcessivelyhighpickupsettings.TheL90candynamicallycompensate the charging current thusincreasingitssensitivitytothefaultcurrentonlongtransmissionlines.
Enhanced Monitoring Features
TheL90usesanadvancederrordetectionand supervising functions to secure theL90againstmisoperationduetoerroneousdata. High bit errors are addressed bymeansofcomputinga32bitCRCchecksumseffectivelyaddressingtheconcernsofmultiplebiterrorsduetohighchannelnoise.On multiplexed channels, channelasymmetrymaybeexpectedduetopathswitching spurious differential currents,which can endanger the security of thedifferential system. By using GPS timesynchronization, up to 10ms of channelasymmetrycanbecompensatedfor.ExtrasecurityhasbeenimplementedintheL90toensureproperoperationontheeventofIRIG-Bsignalfailure.Integrated channel monitoring providesreal-time diagnostic data on the healthof the L90. Communications channeldeterioration or failure will activate analarm,andcanbeusedtoenablebackupprotection. Channel propagation delayismonitored and adjusted according tovariationsincommunicationpaths.
Communication Topologies
Relays can communicate through directfiber,RS422,G.703,IEEEC37.94interfacesat 64Kbps, with extensive channelmonitoringanddiagnosticsare included.Inacurrentdifferentialscheme,theL90sexchange data via the communication
functions in L90 comewith three zonesof phase and ground distance (mho orquad). The phase distance elementscome with built-in in-zone transformercompensation. The L90 also providesa load encroachment element , whichsupervises the distance elements underheavylineloadingconditions.
Overvoltage and undervoltage protection
Longlinesunderlightlyloadedconditionsor no-load may experience voltagesexceeding rated per unit voltage levelof the line. Use the phase overvoltageelementoftheL90toinitiatealocaltripaswellasaremotetripusingdirecttransfertrip.
Overcurrent Functions
TTheL90providesthermaloverload,timeand instantaneousovercurrentelementsfor phase, neutral, ground, negativesequence,phaseandneutraldirectional.Any of them can run in parallel withprimarydifferentialprotectionorcanbeprogrammedtorunwhenthedifferentialelementisnotavailable.
Typical two and three terminal application of L90. L90 supports a variety of media cards for signalling between L90’s including direct multimode or single mode fibre, RS422, G.703 and IEEE C37.94.
Typical Applications
link, acting either as master collectingdata, making calculations and makingall relevant trip and restraint decisions,or as slave only transmitting currentdatatotheoneactingasmaster.Fortwoterminalapplications,usetheredundantcommunicationscapabilityoftheL90foroptimalreliabilityofthecurrentdifferentialline protection. For this scheme, datais continuously transmitted over bothchannels, so if a failure occurs, the L90willcontinuetoprovidecurrentdifferentialprotection.Forthreeterminalapplications,advancedinter-relay communication featureseliminate the need for redundantcommunicationchannelsduetotheabilityoftheL90toautomaticallyswitchbetweenmaster and slave mode, maintaining adependablesystemevenwithafailureofoneofthecommunicationchannels.
Distance
Separate high-speed phase and grounddistanceelementsareprovidedforoptionalsupervisionwithtappedtransformersandas a back-up during channel failures orunavailability. The back-up distance the
204204
L90Line Differential SystemTr
ansm
issi
on L
ine
Prot
ectio
n
www.GEDigitalEnergy.com
Single-Pole Tripping
TheL90relayusesastate-of-the-artdualphase selection algorithm that providesfastandaccuratefaulttypeidentificationevenunderweak-infeedconditions.
Direct transfer trip (DTT)
UsethedirecttransfertripfeatureofL90to trip remote breaker. Both single poleand three pole direct transfer trips aresupported. Up to eight signals can besentoverpilotcommunicationschannelsselectable through user configurablelogic.
Autoreclosing
TheL90providesmulti-shotautoreclosingforsinglepoleorthreepoleautorelcoseonall typesof faultswith independentlysettable dead time for each shot . Auto-reclose can be dynamically blocked byuser programmable logic. Four differentauto-relcosemodesareavailableenablingtheuserstoselectthereclosingmodetosuitspecificapplications.
Synchronism Check
The L90 monitors voltage difference,phaseangledifferenceandslipfrequencyto ensure proper breaker closure as peruser requirements. The L90 providesadditionalenhancementsinsynchronizingby allowing synchrocheck verificationbetween local and remote line terminalvoltages.
Breaker Failure
TheL90isabletoprovidefullyindependentbreakerfailureprotectionforthebreakersassociatedtothelinewhenconnectedtoasubstationwithabreaker-and-a-halforringbusarrangement. TheL90providesthe required elements to perform twoindependentbreakerfailurefunctions.
Multiple Breaker Configurations
The L90 supports multi-breaker busbarconfigurationssuchasbreaker-and-a-halforringbusarrangements,providingdualbreaker auto reclose, dual synch-checkelements,anddual independentBreakerFailure elements. The design providessecure operation during external faultswithpossibleCTsaturation
Special Applications - Distributed Busbar
Use the L90’s capability of supportingup to 4 directly connected CTs forapplicationswheretheuseofconventionalbus differential relaying is not practicalor economically feasible. The L90 canbe used to protect both line and busesby measuring currents from the feederCTsasshown.TheL90providesprimaryprotection for both the buses and thecircuitconnectingthem.
IEC 61850 Process BusThe IEC 61850 Process Bus moduleis designed to interface with theMultilin HardFiber™ System, allowing
bi-directional IEC 61850 fiber opticcommunications. The HardFiber Systemisdesigned to integrate seamlesslywiththeexistingUniversalRelayapplications,includingprotection functions,FlexLogic,meteringandcommunications.HardFiberSystembenefits:
• CommunicatesusingopenstandardIEC61850messaging
• DrasticallyreducesP&Cdesign,installationandtestinglaborbyeliminatingindividualcopperterminations
• IntegrateswithexistingC70’sbyreplacingtraditionalCT/VTinputswithIEC61850ProcessBusmodule
• DoesnotintroducenewCyberSecurityconcerns
Advanced AutomationTheL90incorporatesadvancedautomationfeatures including powerful FlexLogic™programmablelogic,communication,andSCADAcapabilitiesthatfarsurpasswhatisfoundintheaveragelinerelay.TheL90integratesseamlesslywithotherURrelaysforcompletesystemprotection.
FlexLogic™
FlexLogic™ is the powerful UR-platformprogramming logic engine thatprovidestheabilitytocreatecustomizedprotectionandcontrolschemestherebyminimizingtheneed,andassociatedcosts,ofauxiliarycomponentsandwiring.Using FlexLogic, the L90 can providerequiredtrippingandcustomschemelogicfor line breaker control and interlockinganddynamicsettinggroupchanges.
Scalable HardwareThe L90 is available with a multitudeof I/O configurations to suit the mostdemanding application needs. Theexpandable modular design allows foreasyconfigurationandfutureupgrades.
• Flexible,modularI/Ocoveringabroadrangeofinputsignalsandtrippingschemes
• Mechanicallylatchingoutputscanbeusedtodevelopsecureinterlockingapplicationsandreplaceelectromechanicallockoutrelays
FlexLogicTM Designer
Flexlogic™ allows for customizing the L90 to operate and control the breakers and other auxiliary devices needed to fit most line protection schemes and applications.
205205
L90Line Differential System
Tran
smis
sion
Lin
e Pr
otec
tion
www.GEDigitalEnergy.com
Monitoring and MeteringTheL90includeshighaccuracymeteringand recording forallACsignals.Voltage,current,andpowermeteringarebuiltintothe relay as a standard feature. CurrentandvoltageparametersareavailableastotalRMSmagnitude,andasfundamentalfrequencymagnitudeandangle.
Fault and Disturbance Recording
The advanced disturbance and eventrecording features within the L90 cansignificantly reduce the timeneeded forpostmortem analysis of power systemeventsandcreationofregulatoryreports.Recordingfunctionsinclude:
• SequenceofEvent(SOE)-1024timestampedevents
• Oscillography,
-64digital&upto40Analogchannels
• DataLogger,disturbancerecording–16channelsupto1sample/cycle/channel
• FaultReports
-Powerfulsummaryreportofpre-faultandfaultvalues
• Multi-endedfaultlocation
-calculatingfaultlocationontwoorthreeterminallineswith2%accuracy
The very high sampling rate and largeamount of storage space available fordata recording in the L90 can eliminatetheneed for installingcostlystandalonerecordingequipment.
CB1
CT1
CB2
CT2
CB3
CT3
CB4
BUS1
CT4
L90-2
Com
mun
icat
ion
chan
nel
CB5
CT5
CB6
CT6
CB7
CT7
BUS2
L90-1
831783A1.CDR
PROTECTEDLINE
VT3
VT21PH
CT2CB2CB1CT1
VT11PH
L90
Example of Distributed Bus Differential Protection Application. L90 Breaker-and-a-Half Application example.
Advanced Device Health Diagnostics
TheL90performscomprehensivedevicehealth diagnostic tests during startupand continuously at runtime to testits own major functions and criticalhardware.Thesediagnostictestsmonitorforconditionsthatcould impactsecurityandavailabilityofprotection,andpresentdevicestatusviaSCADAcommunicationsand front panel display. Providingcontinuousmonitoringandearlydetectionof possible issueshelps improve systemuptime.
• Comprehensivedevicehealthdiagnosticperformedduringstartup
• MonitorstheCT/VTinputcircuitrytovalidatetheintegrityofallsignals
CommunicationsTheL90providesforsecureremotedataand engineering access,making it easyand flexible to use and integrate intonew and existing infrastructures. Fiberoptic Ethernet provides high-bandwidthcommunicationsallowingforlow-latencycontrolsandhigh-speed file transfersofrelayfaultandeventrecord information.Theavailable redundantEthernetoptionand the embedded managed Ethernetswitchprovidethemeansofcreatingfaulttolerant communicationarchitectures inaneasy,cost-effectivemanner.TheL90supportsthemostpopularindustrystandardprotocolsenablingeasy,directintegration into monitoring and SCADAsystems.
• IEC61850
• DNP3.0
• IEC60870-5-104
• ModbusRTU,ModbusTCP/IP
Interoperability with Embedded IEC 61850
TheL90with integrated IEC61850canbeused to lower costs associated with lineprotection, control and automation. GEEnergy’s leadership in IEC 61850 comesfrom thousands of installed devices andfollowsonMultilin’sextensivedevelopmentexperiencewithUCA2.0.
• ReplaceexpensivecopperwiringbetweendeviceswithdirecttransferofdatausingGOOSEmessaging
• ConfiguresystemsbasedonIEC61850andalsomonitorandtroubleshoottheminreal-timewithEnerVista™ViewpointEngineer
• IntegrateMultilinIEDsandgenericIEC61850-compliantdevicesseamlesslyinEnerVista™ViewpointMonitoring
Multi-Language
TheL90supportsEnglish,French,Russian,andChineselanguagesonthefrontpanel,EnerVista™ setup software, andproductmanual. Easily switch between Englishandanadditional languageon the localdisplayswithoutuploadingnewfirmware.
206206
L90Line Differential SystemTr
ansm
issi
on L
ine
Prot
ectio
n
www.GEDigitalEnergy.com
EnerVistaTM SoftwareThe EnerVista™ Suite is an industry-leading set of software programs thatsimplifies everyaspect of using the L90relay.TheEnerVista™suiteprovidesallthetoolstomonitorthestatusoftheprotectedasset,maintain the relay, and integrateinformation measured by the L90 intoDCS or SCADA monitoring systems.Convenient COMTRADE and Sequenceof Events viewers are an integral partof the UR Setup software includedwitheveryURrelay,tocarryoutpostmortemeventanalysistoensureproperprotectionsystemoperation.
EnerVista™ Launchpad
EnerVista™ Launchpad is a powerfulsoftwarepackagethatprovidesuserswithallofthesetupandsupporttoolsneededfor configuringandmaintainingMultilinproducts. The setup software withinLaunchpadallowsconfiguringdevicesinreal-timebycommunicatingusingserial,Ethernet , or modem connections, orofflinebycreatingsettingfilestobesenttodevicesatalatertime.Included in Launchpad is a documentarchiving and management systemthat ensures critical documentation isup-to-date and availablewhen needed.Documentsmadeavailableinclude:
• Manuals&Brochures
• ApplicationNotes
• GuideformSpecifications
• WiringDiagrams
• FAQ’s
• ServiceBulletins
Viewpoint Monitoring
Viewpoint Monitoring is a simple-to-useand full-featured monitoring and datarecording software package for smallsystems.ViewpointMonitoringprovidesacompleteHMIpackagewiththefollowingfunctionality:
• Plug-&-PlayDeviceMonitoring
• SystemSingle-LineMonitoring&Control
• AnnunciatorAlarmScreens
• TrendingReports
• AutomaticEventRetrieval
• AutomaticWaveformRetrieval
Viewpoint Engineer
ViewpointEngineerisasetofpowerfultoolsthatwillallowtheconfigurationandtestingofURrelaysatasystemlevelinaneasy-to-usegraphicaldrag-and-dropenvironment.ViewpointEngineerprovidesthefollowingconfigurationandcommissioningutilities:
• GraphicalLogicDesigner
• GraphicalSystemDesigner
• GraphicalLogicMonitor
• GraphicalSystemMonitor
Viewpoint Maintenance
ViewpointMaintenanceprovidestoolsthatwillcreatereportsontheoperatingstatusoftherelay,simplifythestepstodownloadfaultandeventdata,andreducetheworkrequired for cyber-security complianceaudits. Tools available in ViewpointMaintenanceinclude:
• SettingsSecurityAuditReport
• DeviceHealthReport
• SingleClickFaultDataRetrieval
EnerVista™ Integrator
EnerVista™ Integrator is a toolkit thatallows seamless integration of Multilindevices into new or existing automationsystems.IncludedinEnerVista™Integratoris:
• OPC/DDEServer
• MultilinDrivers
• AutomaticEventRetrieval
• AutomaticWaveformRetrieval
User InterfaceThe L90 front panel provides extensivelocal HMI capabilities. The local displayisusedformonitoring,statusmessaging,faultdiagnosis,anddeviceconfiguration.Userconfigurablemessagesthatcombinetextwithlivedata,canbedisplayedwhenuser-definedconditionsaremet.
Record the operation of the internal L90 elements and external connected devices with 1ms time-stamped accuracy to identify the Sequence of Operation of station devices during line faults and disturbances.
Power System Troubleshooting
Graphically view zone settings for ground phase distance elements for the selected zones and the power swing detection element.
Analyze line faults using both analog and digital power system quantities that are measured and recorded up to a rate of 64 samples per cycle.
207207
L90Line Differential System
Tran
smis
sion
Lin
e Pr
otec
tion
www.GEDigitalEnergy.com
Typical Wiring
L90-H00-HCL-F8F-H6G-L6D-N6K-S6C-U6H-W7A
L90
A B C
52
1
Powersupply
9
CPU
7
COM
8
CT/VT
6Inputs/outputs
*
6Inputs/outputs
*
6Inputs/outputs
*
6
Inputs/outputs
6Inputs/outputs
*
JU MX LW KV BHT DN GS FPR
RS-232
DB-9
(front)
UR COMPUTER
1
TXD RXD
RXD TXD
SGND SGND
1 832
207645
22
CONNECTOR
PERSONALCOMPUTER
CONNECTOR
2 23 34 45 56 67 78 89 9
DC
TOREMOTE
L90
OPTIONAL
TC
TC
N
2
1H1a
H2b
H1cH1b
H2c
H2a
H4a
H4c
H3bH3a
H4b
H3c
SURGE
H6a
H8a
H5b
H7b
H8b
H5a
H7a
H6c
H8c
H5c
H7c
H1
H2
H3
H4
I
V
I
V
I
V
I
V
6G
U8a
U7b
U7a
U8c
U7c U1b
U2b
U3b
U4b
U5b
U6b
U1a
U2a
U3a
U4a
U5a
U6a
U1c
U2c
U3c
U4c
U5c
U6c
SURGEU8b
U1
U5
U2
U6
U3
U4
6H I
V
I
V
I
V
I
V
I
V
I
V
N7a
N1a
N2b
N7c
N1c
N7b
N1b
N8cN8b
N2c
N8a
N2a
N4a
N5b
N4c
N6b
N3bN3a
N6a
N4b
N5c
N5a
N3c
N6c
6K N1
N5
N2
N6
N3
N7
N4
N8
CRITICALFAILURE
OUTPUT
CONTROLPOWER
HILO
1
FILTERSURGE
B3a
B1b
B8a
B6b
B8b
B6a
B3b
B1aB2b
B5b
Tx1 Rx1
Tx2 Rx2
INTE
R-RE
LAY
CO
MM
S.W
7A
FIBER
FIBER
6C
S1
S5
S2
S6
S3
S7
S4
S8
S7a
S1a
S2b
S7c
S1c
S7b
S1b
S8cS8b
S2c
S8a
S2a
S4a
S5b
S4c
S6b
S3bS3a
S6a
S4b
S5c
S5a
S3c
S6c
L6a
L8a
L5b
L7b
L5a
L7a
L6c
L8c
L5c
L7c
SURGE
L1a
L8b
L4c
L2c
L3aL3c
L1c
L3b
L1b
L4a
L2a
6D
minimum
PROVIDED
8L
F1c
F4a
F3c
F2c
F4c
F1a
F4b
F1b
F2a
F3a
F2b
F3b
IA IB IC IGIA5
IA1
IB5
IC5
IG5
IB1
IC1
IG1
F8c
F8a
F5a
F5c
F7c
F6a
F7a
F6c
VX
VA VB
VC VX
VA VB
VC
Multilin
com
10BaseFL
10BaseFL
10BaseT
D1aD2a
D4bD3a
D4a IRIG-BInput
IRIG-BOutput
COM1
RS485
ALTERNATE
NORMAL
Tx2Rx2
Tx1Rx1
BNC
BNC
FibreOptic
*
RemoteDevice
Shielded
Co-axial
Co-axial
com
10BaseFL
10BaseFL
10BaseT
D1aD2a
D4bD3a
D4a IRIG-BInput
IRIG-BOutput
COM1
RS485
ALTERNATE
NORMAL
Tx2Rx2
Tx1Rx1
BNC
BNC
FibreOptic
*
RemoteDevice
Shielded
Co-axial
Co-axial
208208
L90Line Differential SystemTr
ansm
issi
on L
ine
Prot
ectio
n
www.GEDigitalEnergy.com
Ordering Notes:1-Forverticalmountingordercodes,pleasevisitouronlinestore2-ToviewthelatestoptionsavailablefortheL90,ortoordertheURClassicFrontPanel,pleasevisitouronlinestoreformoredetails.
• URApplicationsILearningCD TRCD-URA1-C-S-1
• MultilinkEthernetSwitch ML2400-F-HI-HI-A2-A2-A6-G1
• ViewpointEngineer VPE-1
• ViewpointMaintenance VPM-1
• ViewpointMonitoringIEC61850 VP-1-61850
Accessories for the L90 • ViewGuideformspecifications
• Downloadtheinstructionmanual
• Reviewapplicationsnotesandsupportdocuments
• BuyaL90online
• ViewtheURFamilybrochure
Visit www.GEMultilin.com/L90 to:
Ordering
L90 - * 00 - H * * - F ** - H ** - L ** - N ** - S ** - U ** - W/X ** For Horizontal MountBaseUnit L90 BaseUnitCPU E RS485+RS485(IEC61850optionnotavailable) G RS485+Multi-modeST10BaseF H RS485+Mutli-modeSTRedundant10BaseF J RS485+Multi-modeST100BaseFX K RS485+Multi-modeSTRedundant100BaseFX N RS485+10/100BaseT S RS485+6port,100Mbps,ManagedEthernetSwitchSoftware 00 NoSoftwareOptions 02 BreakerandHalfsoftware 03 IEC61850 05 BreakerandHalf+IEC61850 06 PhasorMeasurementUnit(PMU) 07 IEC61850+PhasorMeasurementUnit(PMU) 08 Breaker&Half+PhasorMeasurementUnit(PMU) 09 Breaker&Half+IEC61850+PhasorMeasurementUnit(PMU)Mount/Coating H Horizontal(19"rack)-Standard A Horizontal(19"rack)-HarshChemicalEnvironmentOption V Vertical(3/4size)-Standard B Vertical(3/4size)-HarshChemicalEnvironmentOptionUserInterface K EnhancedEnglishFrontPanel L EnhancedEnglishFrontPanelwithUser-ProgrammablePushbuttons M EnhancedFrenchFrontPanel N EnhancedFrenchFrontPanelwithUser-ProgrammablePushbuttons Q EnhancedRussianFrontPanel T EnhancedRussianFrontPanelwithUser-ProgrammablePushbuttons U EnhancedChineseFrontPanel V EnhancedChineseFrontPanelwithUser-ProgrammablePushbuttons F VerticalFrontPanelwithEnglishdisplayPowerSupply H 125/250VAC/DC H RH 125/250VAC/DCwithredundant125/250VAC/DC L 24-48V(DConly)CT/VTDSP 8L 8L Standard4CT/4VTw/enhanceddiagnostics 8N 8N Standard8CTw/enhanceddiagnosticsIEC61850ProcessBus 81 8PortIEC61850ProcessBusModuleDigitalI/O XX XX XX XX XX NoModule 4A 4A 4A 4A 4A 4SolidState(NoMonitoring)MOSFETOutputs 4C 4C 4C 4C 4C 4SolidState(Currentw/optVoltage)MOSFETOutputs 4D 4D 4D 4D 4D 16DigitalInputswithAuto-Burnish 4L 4L 4L 4L 4L 14Form-A(NoMonitoring)LatchableOutputs 67 67 67 67 67 8Form-A(NoMonitoring)Outputs 6C 6C 6C 6C 6C 8Form-COutputs 6D 6D 6D 6D 6D 16DigitalInputs 6E 6E 6E 6E 6E 4Form-COutputs,8DigitalInputs 6F 6F 6F 6F 6F 8FastForm-COutputs 6K 6K 6K 6K 6K 4Form-C&4FastForm-COutputs 6L 6L 6L 6L 6L 2Form-A(Currentw/optVoltage)&2Form-COutputs,8DigitalInputs 6M 6M 6M 6M 6M 2Form-A(Currentw/optVoltage)&4Form-COutputs,4DigitalInputs 6N 6N 6N 6N 6N 4Form-A(Currentw/optVoltage)Outputs,8DigitalInputs 6P 6P 6P 6P 6P 6Form-A(Currentw/optVoltage)Outputs,4DigitalInputs 6R 6R 6R 6R 6R 2Form-A(NoMonitoring)&2Form-COutputs,8DigitalInputs 6S 6S 6S 6S 6S 2Form-A(NoMonitoring)&4Form-COutputs,4DigitalInputs 6T 6T 6T 6T 6T 4Form-A(NoMonitoring)Outputs,8DigitalInputs 6U 6U 6U 6U 6U 6Form-A(NoMonitoring)Outputs,4DigitalInputs 6V 6V 6V 6V 6V 2Form-A(Curw/optVolt)1Form-COutput,2LatchingOutputs,8DigitalInputsTransducerI/O 5A 5A 5A 5A 5A 4dcmAInputs,4dcmAOutputs 5F 5F 5F 5F 5F 8dcmAInputsInter-RelayCommunications 7A 820nm,multi-mode,LED,1Channel 7B 1300nm,multi-mode,LED,1Channel 7C 1300nm,single-mode,ELED,1Channel 7H 820nm,multi-mode,LED,2Channels 7I 1300nm,multi-mode,LED,2Channels 7J 1300nm,single-mode,ELED,2Channels 7S G.703,2Channels 7W RS422,2Channels 7V RS422,2Channels,DualClock 73 1550nm,single-mode,LASER,2Channel 76 IEEEC37.94,820nm,multimode,LED,1Channel 77 IEEEC37.94,820nm,multimode,LED,2Channel 2B C37.94SM,1300nmSinglemode,ELED,2ChannelSinglemode 2S 6port,100Mbps,ManagedEthernetSwitch,HI(125/250VAC/DC) 2T 6port,100Mbps,ManagedEthernetSwitch,LO(24-48Vdc)