Limitamp AR, Arc Resistant Medium Voltage Motor Control
Transcript of Limitamp AR, Arc Resistant Medium Voltage Motor Control
Limitamp* ARArc Resistant Medium Voltage Motor Control
Application Guide
GEIndustrial Solutions
Limitamp* AR - Arc Resistant
IntroductionLimitamp AR is the Arc Resistant version of the Limitamp, providing a solution for flash conditions, increasing the safety and protection defined in the applicable IEEE standards. The new Limitamp AR Medium Voltage Motor Controllers meet the safety requirements of the market, offering more reliable operation and control of Medium Voltage installations. This new construction includes a complete product offering of 400A/800A starters and other controllers.
The Limitamp AR is designed to provide a reliable solution to the growing demand for Arc Resistant equipment in the market place.
The uniquely designed Limitamp AR products have passed a rigorous testing program as specified by the IEEE/ANSI C37.20.7-2007 Type 2B safety standard. They are designed to provide personnel protection on the front, rear and sides of the enclosure in the event of an arc flash occurrence. This means that when the medium voltage doors are properly secured, the service technician can access the interior of the low voltage compartment, and the Limitamp AR provides the protection from a potential arc flash event.
Limitamp AR keeps the same basic design, features and general applications of the CR194 Limitamp control and the vacuum contactor, meeting UL347 and all other requirements.
Technical Data• System voltage: up to 7.2kV• Main bus: 1200A, 2000A, 3000A• 50kA short circuit at 0.5 seconds• Enclosure type: Indoor NEMA 1 gasketed
• Arc Resistant Type 2B per IEEE/ANSI C37.20.7-2007 standard
Product Offering• 1-high and 2-high 400A FVNR (full voltage non-reversing starters)• 1-high 800A FVNR (full voltage non-reversing starters)• 1-high 800A FVR (full voltage reversing starters)• 1-high 400A FVR (full voltage reversing starters)• RVAT (reduced voltage autotransformer starters)• RVPR (reduced voltage primary reactor starters)• 2S1W (two speed, single winding starters)• 2S2W (two speed, dual winding starters)• 400A MVSS (medium voltage solid-state starters)• IC-1074 load break switches• SYNC excitation starters• Main, Feeder and Tie sections• Incoming line cable sections• Auxiliary sections
Front view Limitamp AR
2-High Limitamp AR with medium voltage door open
ConstructionThe low voltage door on the front of each unit includes pilot lights, switches and relays. This compartment provides easy access to the secondary devices while the main medium voltage front door is closed. It is isolated from the live parts of the unit, providing increased safety under arc flash conditions.
Detail of low voltage compartment when medium voltage door is closed
Front view Limitamp 2-High with extension main bus and extension of the duct/plenum
Arc Duct / Plenum showing exhaust cap at the last segment.
When the main door is open, an extra glass-reinforced polyester barrier is provided in the back of the low voltage compartment for protection, as shown in photo below.
Each cubicle is provided with reinforced doors that incorpo-rate special hinges, gaskets, handles and latches to ensure proper sealing in front of the section.
The Limitamp AR – Arc Resistant Medium Voltage Motor Controls are manufactured using heavy duty rein-forced side panels in a 1/8” thick (11 gauge) welded steel construction which, in conjunction with other mechanical features and special bolted pieces provide additional safety for arc flash conditions.
In the case of an internal arc fault inside the vertical section, all the gases and other materials produced as result of the fault are directed to the upper part of the vertical section.
The robust design of the enclosure, bottom plate and medium voltage doors prevents front, bottom and side exhaust. Particles and gases are directed to the upper part of the vertical section, through the vent flaps and plenum to an external area determined by the customer, away from the gear and personnel.
Every vertical section includes a plenum fabricated of 0.105” thick (12 gauge) sheet steel, and along with others in adjacent sections, form a duct along the top of the Limitamp AR.
The plenum system is not installed at the factory. It is supplied for field installation. Extra segments can be ordered, depending on the particular characteristics of the installation site.
The last segment of the duct is provided with a cap to direct the arc flash particles and gases away from the gear and the operator.
2-High Limitamp AR with low voltage door open
Rear of low voltage box with medium voltage door open
Special lock system in the medium voltage door to ensure protection
Limitamp AR Medium Votage Motor Control CR194 AR 400A, Stationary or Draw-out, Outline Dimensions 2400-7200 Volts, One-High, Bottom Cable Entry
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
L.H.SIDE VIEW
C
7.5
68.8
52.0
6.5
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
32.0G
42.0
D
BTM CABLE ENTRY
-1700 lbs771 Kg
FRO
NT
6.5 7.5
10.8
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
19.3
11.7
6.8
C
7.5
68.8
52.0
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
36.0G
1-HI
UPPER UNIT
40.042.0
D
BTM CABLE ENTRY
-2000 lbs907 Kg
FRO
NT
90.0
24.0
6.5 7.52
10.8
64.2
15.2
D
B
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
M
P
6.8
17.4
2.6 6.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
M
P
6.8
17.4
2.6 10.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
B
B
L3
L2
L1
4.2
6.5
L.H.SIDE VIEW
C
68.8
52.0
6.5
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
32.0G
42.0
TOP CABLE ENTRY
-1700 lbs771 Kg
FRO
NT
B
M
P
6.8
17.4
2.6 6.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
7.5
PLENUM
FRONT VIEW
L.H.SIDE VIEW
CC
7.5
68.8
52.0
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
36.0G
1-HI
UPPER UNIT
40.042.0
TOP CABLE ENTRY
-2000 lbs907 Kg
FRO
NT
90.0
24.0
64.2
15.2
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
M
P
6.8
17.4
2.6 10.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
B BL3
L2
5.7
6.5L1
H48.0
H48.0
H48.0
H48.0
D
18.0
17.418.1
D
18.0
17.4
18.1
D
18.726.5
34.47.0
6.7
4.5
T1
T2
T3 T1
T2
T3 T1-T3
T2
T1
T2
T3
T1
T2
T3
T1
T2
T3
* *
*
PLENUM
FRONT VIEW
C
19.3
11.7
6.8
D
1-HI
36.0
90.0
24.0
64.2
11.2
B
L3
L2
L1
4.2
T1-T3
T2
*
*
* *
*
*
*
***
PLENUM
FRONT VIEW
C
1-HI
36.0
90.0
24.0
64.2
11.2
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
BL3
L2
L1
4.2
D
18.726.5
34.4
4.5
6.7
7.0
T1
T2
T3
***
***
***
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 36" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 40" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 36" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 40" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
L.H.SIDE VIEW
C
7.5
68.8
52.0
6.5
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
32.0G
42.0
D
BTM CABLE ENTRY
-1700 lbs771 Kg
FRO
NT
6.5 7.5
10.8
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
19.3
11.7
6.8
C
7.5
68.8
52.0
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
36.0G
1-HI
UPPER UNIT
40.042.0
D
BTM CABLE ENTRY
-2000 lbs907 Kg
FRO
NT
90.0
24.0
6.5 7.52
10.8
64.2
15.2
D
B
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
M
P
6.8
17.4
2.6 6.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
M
P
6.8
17.4
2.6 10.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
B
B
L3
L2
L1
4.2
6.5
L.H.SIDE VIEW
C
68.8
52.0
6.5
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
32.0G
42.0
TOP CABLE ENTRY
-1700 lbs771 Kg
FRO
NT
B
M
P
6.8
17.4
2.6 6.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
7.5
PLENUM
FRONT VIEW
L.H.SIDE VIEW
CC
7.5
68.8
52.0
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
36.0G
1-HI
UPPER UNIT
40.042.0
TOP CABLE ENTRY
-2000 lbs907 Kg
FRO
NT
90.0
24.0
64.2
15.2
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
M
P
6.8
17.4
2.6 10.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
B BL3
L2
5.7
6.5L1
H48.0
H48.0
H48.0
H48.0
D
18.0
17.418.1
D
18.0
17.4
18.1
D
18.726.5
34.47.0
6.7
4.5
T1
T2
T3 T1
T2
T3 T1-T3
T2
T1
T2
T3
T1
T2
T3
T1
T2
T3
* *
*
PLENUM
FRONT VIEW
C
19.3
11.7
6.8
D
1-HI
36.0
90.0
24.0
64.2
11.2
B
L3
L2
L1
4.2
T1-T3
T2
*
*
* *
*
*
*
***
PLENUM
FRONT VIEW
C
1-HI
36.0
90.0
24.0
64.2
11.2
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
BL3
L2
L1
4.2
D
18.726.5
34.4
4.5
6.7
7.0
T1
T2
T3
***
***
***
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 36" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 40" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 36" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 40" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
L.H.SIDE VIEW
C
7.5
68.8
52.0
6.5
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
32.0G
42.0
D
BTM CABLE ENTRY
-1700 lbs771 Kg
FRO
NT
6.5 7.5
10.8
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
19.3
11.7
6.8
C
7.5
68.8
52.0
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
36.0G
1-HI
UPPER UNIT
40.042.0
D
BTM CABLE ENTRY
-2000 lbs907 Kg
FRO
NT
90.0
24.0
6.5 7.52
10.8
64.2
15.2
D
B
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
M
P
6.8
17.4
2.6 6.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
M
P
6.8
17.4
2.6 10.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
B
B
L3
L2
L1
4.2
6.5
L.H.SIDE VIEW
C
68.8
52.0
6.5
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
32.0G
42.0
TOP CABLE ENTRY
-1700 lbs771 Kg
FRO
NT
B
M
P
6.8
17.4
2.6 6.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
7.5
PLENUM
FRONT VIEW
L.H.SIDE VIEW
CC
7.5
68.8
52.0
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
36.0G
1-HI
UPPER UNIT
40.042.0
TOP CABLE ENTRY
-2000 lbs907 Kg
FRO
NT
90.0
24.0
64.2
15.2
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
M
P
6.8
17.4
2.6 10.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
B BL3
L2
5.7
6.5L1
H48.0
H48.0
H48.0
H48.0
D
18.0
17.418.1
D
18.0
17.4
18.1
D
18.726.5
34.47.0
6.7
4.5
T1
T2
T3 T1
T2
T3 T1-T3
T2
T1
T2
T3
T1
T2
T3
T1
T2
T3
* *
*
PLENUM
FRONT VIEW
C
19.3
11.7
6.8
D
1-HI
36.0
90.0
24.0
64.2
11.2
B
L3
L2
L1
4.2
T1-T3
T2
*
*
* *
*
*
*
***
PLENUM
FRONT VIEW
C
1-HI
36.0
90.0
24.0
64.2
11.2
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
BL3
L2
L1
4.2
D
18.726.5
34.4
4.5
6.7
7.0
T1
T2
T3
***
***
***
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 36" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 40" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 36" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 40" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
L.H.SIDE VIEW
C
7.5
68.8
52.0
6.5
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
32.0G
42.0
D
BTM CABLE ENTRY
-1700 lbs771 Kg
FRO
NT
6.5 7.5
10.8
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
19.3
11.7
6.8
C
7.5
68.8
52.0
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
36.0G
1-HI
UPPER UNIT
40.042.0
D
BTM CABLE ENTRY
-2000 lbs907 Kg
FRO
NT
90.0
24.0
6.5 7.52
10.8
64.2
15.2
D
B
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
M
P
6.8
17.4
2.6 6.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
M
P
6.8
17.4
2.6 10.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
B
B
L3
L2
L1
4.2
6.5
L.H.SIDE VIEW
C
68.8
52.0
6.5
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
32.0G
42.0
TOP CABLE ENTRY
-1700 lbs771 Kg
FRO
NT
B
M
P
6.8
17.4
2.6 6.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
7.5
PLENUM
FRONT VIEW
L.H.SIDE VIEW
CC
7.5
68.8
52.0
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
36.0G
1-HI
UPPER UNIT
40.042.0
TOP CABLE ENTRY
-2000 lbs907 Kg
FRO
NT
90.0
24.0
64.2
15.2
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
M
P
6.8
17.4
2.6 10.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
B BL3
L2
5.7
6.5L1
H48.0
H48.0
H48.0
H48.0
D
18.0
17.418.1
D
18.0
17.4
18.1
D
18.726.5
34.47.0
6.7
4.5
T1
T2
T3 T1
T2
T3 T1-T3
T2
T1
T2
T3
T1
T2
T3
T1
T2
T3
* *
*
PLENUM
FRONT VIEW
C
19.3
11.7
6.8
D
1-HI
36.0
90.0
24.0
64.2
11.2
B
L3
L2
L1
4.2
T1-T3
T2
*
*
* *
*
*
*
***
PLENUM
FRONT VIEW
C
1-HI
36.0
90.0
24.0
64.2
11.2
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
BL3
L2
L1
4.2
D
18.726.5
34.4
4.5
6.7
7.0
T1
T2
T3
***
***
***
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 36" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 40" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 36" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 40" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
1 High, 40” Wide
1 High, 36” Wide
Limitamp AR Medium Votage Motor Control CR194 AR 400A, Stationary or Draw-out, Outline Dimensions 2400-7200 Volts, One-High, Top Cable Entry
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
L.H.SIDE VIEW
C
7.5
68.8
52.0
6.5
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
32.0G
42.0
D
BTM CABLE ENTRY
-1700 lbs771 Kg
FRO
NT
6.5 7.5
10.8
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
19.3
11.7
6.8
C
7.5
68.8
52.0
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
36.0G
1-HI
UPPER UNIT
40.042.0
D
BTM CABLE ENTRY
-2000 lbs907 Kg
FRO
NT
90.0
24.0
6.5 7.52
10.8
64.2
15.2
D
B
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
M
P
6.8
17.4
2.6 6.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
M
P
6.8
17.4
2.6 10.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
B
B
L3
L2
L1
4.2
6.5
L.H.SIDE VIEW
C
68.8
52.0
6.5
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
32.0G
42.0
TOP CABLE ENTRY
-1700 lbs771 Kg
FRO
NT
B
M
P
6.8
17.4
2.6 6.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
7.5
PLENUM
FRONT VIEW
L.H.SIDE VIEW
CC
7.5
68.8
52.0
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
36.0G
1-HI
UPPER UNIT
40.042.0
TOP CABLE ENTRY
-2000 lbs907 Kg
FRO
NT
90.0
24.0
64.2
15.2
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
M
P
6.8
17.4
2.6 10.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
B BL3
L2
5.7
6.5L1
H48.0
H48.0
H48.0
H48.0
D
18.0
17.418.1
D
18.0
17.4
18.1
D
18.726.5
34.47.0
6.7
4.5
T1
T2
T3 T1
T2
T3 T1-T3
T2
T1
T2
T3
T1
T2
T3
T1
T2
T3
* *
*
PLENUM
FRONT VIEW
C
19.3
11.7
6.8
D
1-HI
36.0
90.0
24.0
64.2
11.2
B
L3
L2
L1
4.2
T1-T3
T2
*
*
* *
*
*
*
***
PLENUM
FRONT VIEW
C
1-HI
36.0
90.0
24.0
64.2
11.2
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
BL3
L2
L1
4.2
D
18.726.5
34.4
4.5
6.7
7.0
T1
T2
T3
***
***
***
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 36" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 40" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 36" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 40" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
L.H.SIDE VIEW
C
7.5
68.8
52.0
6.5
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
32.0G
42.0
D
BTM CABLE ENTRY
-1700 lbs771 Kg
FRO
NT
6.5 7.5
10.8
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
19.3
11.7
6.8
C
7.5
68.8
52.0
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
36.0G
1-HI
UPPER UNIT
40.042.0
D
BTM CABLE ENTRY
-2000 lbs907 Kg
FRO
NT
90.0
24.0
6.5 7.52
10.8
64.2
15.2
D
B
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
M
P
6.8
17.4
2.6 6.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
M
P
6.8
17.4
2.6 10.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
B
B
L3
L2
L1
4.2
6.5
L.H.SIDE VIEW
C
68.8
52.0
6.5
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
32.0G
42.0
TOP CABLE ENTRY
-1700 lbs771 Kg
FRO
NT
B
M
P
6.8
17.4
2.6 6.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
7.5
PLENUM
FRONT VIEW
L.H.SIDE VIEW
CC
7.5
68.8
52.0
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
36.0G
1-HI
UPPER UNIT
40.042.0
TOP CABLE ENTRY
-2000 lbs907 Kg
FRO
NT
90.0
24.0
64.2
15.2
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
M
P
6.8
17.4
2.6 10.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
B BL3
L2
5.7
6.5L1
H48.0
H48.0
H48.0
H48.0
D
18.0
17.418.1
D
18.0
17.4
18.1
D
18.726.5
34.47.0
6.7
4.5
T1
T2
T3 T1
T2
T3 T1-T3
T2
T1
T2
T3
T1
T2
T3
T1
T2
T3
* *
*
PLENUM
FRONT VIEW
C
19.3
11.7
6.8
D
1-HI
36.0
90.0
24.0
64.2
11.2
B
L3
L2
L1
4.2
T1-T3
T2
*
*
* *
*
*
*
***
PLENUM
FRONT VIEW
C
1-HI
36.0
90.0
24.0
64.2
11.2
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
BL3
L2
L1
4.2
D
18.726.5
34.4
4.5
6.7
7.0
T1
T2
T3
***
***
***
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 36" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 40" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 36" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 40" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
L.H.SIDE VIEW
C
7.5
68.8
52.0
6.5
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
32.0G
42.0
D
BTM CABLE ENTRY
-1700 lbs771 Kg
FRO
NT
6.5 7.5
10.8
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
19.3
11.7
6.8
C
7.5
68.8
52.0
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
36.0G
1-HI
UPPER UNIT
40.042.0
D
BTM CABLE ENTRY
-2000 lbs907 Kg
FRO
NT
90.0
24.0
6.5 7.52
10.8
64.2
15.2
D
B
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
M
P
6.8
17.4
2.6 6.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
M
P
6.8
17.4
2.6 10.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
B
B
L3
L2
L1
4.2
6.5
L.H.SIDE VIEW
C
68.8
52.0
6.5
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
32.0G
42.0
TOP CABLE ENTRY
-1700 lbs771 Kg
FRO
NT
B
M
P
6.8
17.4
2.6 6.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
7.5
PLENUM
FRONT VIEW
L.H.SIDE VIEW
CC
7.5
68.8
52.0
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
36.0G
1-HI
UPPER UNIT
40.042.0
TOP CABLE ENTRY
-2000 lbs907 Kg
FRO
NT
90.0
24.0
64.2
15.2
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
M
P
6.8
17.4
2.6 10.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
B BL3
L2
5.7
6.5L1
H48.0
H48.0
H48.0
H48.0
D
18.0
17.418.1
D
18.0
17.4
18.1
D
18.726.5
34.47.0
6.7
4.5
T1
T2
T3 T1
T2
T3 T1-T3
T2
T1
T2
T3
T1
T2
T3
T1
T2
T3
* *
*
PLENUM
FRONT VIEW
C
19.3
11.7
6.8
D
1-HI
36.0
90.0
24.0
64.2
11.2
B
L3
L2
L1
4.2
T1-T3
T2
*
*
* *
*
*
*
***
PLENUM
FRONT VIEW
C
1-HI
36.0
90.0
24.0
64.2
11.2
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
BL3
L2
L1
4.2
D
18.726.5
34.4
4.5
6.7
7.0
T1
T2
T3
***
***
***
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 36" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 40" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 36" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 40" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
L.H.SIDE VIEW
C
7.5
68.8
52.0
6.5
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
32.0G
42.0
D
BTM CABLE ENTRY
-1700 lbs771 Kg
FRO
NT
6.5 7.5
10.8
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
19.3
11.7
6.8
C
7.5
68.8
52.0
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
36.0G
1-HI
UPPER UNIT
40.042.0
D
BTM CABLE ENTRY
-2000 lbs907 Kg
FRO
NT
90.0
24.0
6.5 7.52
10.8
64.2
15.2
D
B
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
M
P
6.8
17.4
2.6 6.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
M
P
6.8
17.4
2.6 10.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
B
B
L3
L2
L1
4.2
6.5
L.H.SIDE VIEW
C
68.8
52.0
6.5
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
32.0G
42.0
TOP CABLE ENTRY
-1700 lbs771 Kg
FRO
NT
B
M
P
6.8
17.4
2.6 6.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
7.5
PLENUM
FRONT VIEW
L.H.SIDE VIEW
CC
7.5
68.8
52.0
6.5
14.2
12.8EB1
L3
L2
L1
PLENUM
36.0G
1-HI
UPPER UNIT
40.042.0
TOP CABLE ENTRY
-2000 lbs907 Kg
FRO
NT
90.0
24.0
64.2
15.2
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
M
P
6.8
17.4
2.6 10.0
6.0
6.0
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
B BL3
L2
5.7
6.5L1
H48.0
H48.0
H48.0
H48.0
D
18.0
17.418.1
D
18.0
17.4
18.1
D
18.726.5
34.47.0
6.7
4.5
T1
T2
T3 T1
T2
T3 T1-T3
T2
T1
T2
T3
T1
T2
T3
T1
T2
T3
* *
*
PLENUM
FRONT VIEW
C
19.3
11.7
6.8
D
1-HI
36.0
90.0
24.0
64.2
11.2
B
L3
L2
L1
4.2
T1-T3
T2
*
*
* *
*
*
*
***
PLENUM
FRONT VIEW
C
1-HI
36.0
90.0
24.0
64.2
11.2
FRONT
TOP VIEW
P
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
BL3
L2
L1
4.2
D
18.726.5
34.4
4.5
6.7
7.0
T1
T2
T3
***
***
***
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 36" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 40" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 36" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 1 High, 40" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
1 High, 40” Wide
1 High, 36” Wide
Limitamp AR Medium Votage Motor Control CR194 AR 400A, Stationary or Draw-out, Outline Dimensions 2400-7200 Volts, Two-High, Bottom Cable Entry
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
11.2
19.3
11.7
6.8C
C
20.9
43.3
4.5
6.7
7.0
61.969.0
76.8
7.5
68.852.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
D
PLENUM
D
D
18.2
18.1
16.5
32.0G
2-HI
LOWER UNIT
UPPER UNIT
36.042.0
D
BTM CABLE ENTRY
-2200 lbs998 Kg
FRO
NT
90.0
24.0
C
6.5 7.5
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
M
M
6.8
17.4
2.6 6.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J10.8
*
H48.0
T1
T2
T3
T1
T2
T3
T1
T2
T3
T1-T3
T2
**
* *
*
***
*
*
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
15.2
19.3
11.7
6.8C
C
20.9
43.3
4.5
6.7
7.0
61.969.0
76.8
7.5
68.8
52.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
D
PLENUM
D
D
18.2
18.1
16.5
36.0G
2-HI
LOWER UNIT
UPPER UNIT
40.042.0
D
BTM CABLE ENTRY
-2450 lbs1112 Kg
FRO
NT
90.0
24.0
C
6.5 7.5
10.8
H48.0
T1
T2
T3
T1
T2
T3
T1
T2
T3
T1-T3
T2
***
* *
*
***
*
*
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
11.2
C
C
20.9
43.3
7.5
68.852.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
PLENUM
32.0G
2-HI
LOWER UNIT
UPPER UNIT
36.042.0
TOP CABLE ENTRY
-2200 lbs998 Kg
FRO
NT
90.0
24.0
C
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
M
M
6.8
17.4
2.6 6.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
D D
D
D
18.726.5
34.4
63.9
75.6
6.8
4.5
6.7
7.0
10.8
7.56.5
18.0
17.418.1
H48.0
T1
T2
T3
T1
T2
T3
T1-T3
T2
T1
T2
T3
* *
*
***
*
*
***
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
15.2
C
C
20.9
43.3
7.5
68.8
52.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
PLENUM
36.0G
2-HI
LOWER UNIT
UPPER UNIT
40.042.0
TOP CABLE ENTRY
-2450 lbs1112 Kg
FRO
NT
90.0
24.0
C
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
M
M
6.8
17.4
2.6 10.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
D
D
6.5 7.5
10.8
18.0
17.4
18.1
D
D
18.726.5
34.4
63.9
75.6
7.0
6.7
4.5
6.8
H48.0
T1
T2
T3
T1
T2
T3
T1-T3
T2
T1
T2
T3
* *
*
***
*
*
***
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 36" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 36" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 40" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 40" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
M
M
6.8
17.4
2.6 10.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
11.2
19.3
11.7
6.8C
C
20.9
43.3
4.5
6.7
7.0
61.969.0
76.8
7.5
68.852.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
D
PLENUM
D
D
18.2
18.1
16.5
32.0G
2-HI
LOWER UNIT
UPPER UNIT
36.042.0
D
BTM CABLE ENTRY
-2200 lbs998 Kg
FRO
NT
90.0
24.0
C
6.5 7.5
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
M
M
6.8
17.4
2.6 6.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J10.8
*
H48.0
T1
T2
T3
T1
T2
T3
T1
T2
T3
T1-T3
T2
**
* *
*
***
*
*
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
15.2
19.3
11.7
6.8C
C
20.9
43.3
4.5
6.7
7.0
61.969.0
76.8
7.5
68.8
52.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
D
PLENUM
D
D
18.2
18.1
16.5
36.0G
2-HI
LOWER UNIT
UPPER UNIT
40.042.0
D
BTM CABLE ENTRY
-2450 lbs1112 Kg
FRO
NT
90.0
24.0
C
6.5 7.5
10.8
H48.0
T1
T2
T3
T1
T2
T3
T1
T2
T3
T1-T3
T2
***
* *
*
***
*
*
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
11.2
C
C
20.9
43.3
7.5
68.852.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
PLENUM
32.0G
2-HI
LOWER UNIT
UPPER UNIT
36.042.0
TOP CABLE ENTRY
-2200 lbs998 Kg
FRO
NT
90.0
24.0
C
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
M
M
6.8
17.4
2.6 6.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
D D
D
D
18.726.5
34.4
63.9
75.6
6.8
4.5
6.7
7.0
10.8
7.56.5
18.0
17.418.1
H48.0
T1
T2
T3
T1
T2
T3
T1-T3
T2
T1
T2
T3
* *
*
***
*
*
***
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
15.2
C
C
20.9
43.3
7.5
68.8
52.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
PLENUM
36.0G
2-HI
LOWER UNIT
UPPER UNIT
40.042.0
TOP CABLE ENTRY
-2450 lbs1112 Kg
FRO
NT
90.0
24.0
C
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
M
M
6.8
17.4
2.6 10.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
D
D
6.5 7.5
10.8
18.0
17.4
18.1
D
D
18.726.5
34.4
63.9
75.6
7.0
6.7
4.5
6.8
H48.0
T1
T2
T3
T1
T2
T3
T1-T3
T2
T1
T2
T3
* *
*
***
*
*
***
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 36" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 36" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 40" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 40" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
M
M
6.8
17.4
2.6 10.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
11.2
19.3
11.7
6.8C
C
20.9
43.3
4.5
6.7
7.0
61.969.0
76.8
7.5
68.852.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
D
PLENUM
D
D
18.2
18.1
16.5
32.0G
2-HI
LOWER UNIT
UPPER UNIT
36.042.0
D
BTM CABLE ENTRY
-2200 lbs998 Kg
FRO
NT
90.0
24.0
C
6.5 7.5
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
M
M
6.8
17.4
2.6 6.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J10.8
*
H48.0
T1
T2
T3
T1
T2
T3
T1
T2
T3
T1-T3
T2
**
* *
*
***
*
*
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
15.2
19.3
11.7
6.8C
C
20.9
43.3
4.5
6.7
7.0
61.969.0
76.8
7.5
68.8
52.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
D
PLENUM
D
D
18.2
18.1
16.5
36.0G
2-HI
LOWER UNIT
UPPER UNIT
40.042.0
D
BTM CABLE ENTRY
-2450 lbs1112 Kg
FRO
NT
90.0
24.0
C
6.5 7.5
10.8
H48.0
T1
T2
T3
T1
T2
T3
T1
T2
T3
T1-T3
T2
***
* *
*
***
*
*
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
11.2
C
C
20.9
43.3
7.5
68.852.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
PLENUM
32.0G
2-HI
LOWER UNIT
UPPER UNIT
36.042.0
TOP CABLE ENTRY
-2200 lbs998 Kg
FRO
NT
90.0
24.0
C
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
M
M
6.8
17.4
2.6 6.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
D D
D
D
18.726.5
34.4
63.9
75.6
6.8
4.5
6.7
7.0
10.8
7.56.5
18.0
17.418.1
H48.0
T1
T2
T3
T1
T2
T3
T1-T3
T2
T1
T2
T3
* *
*
***
*
*
***
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
15.2
C
C
20.9
43.3
7.5
68.8
52.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
PLENUM
36.0G
2-HI
LOWER UNIT
UPPER UNIT
40.042.0
TOP CABLE ENTRY
-2450 lbs1112 Kg
FRO
NT
90.0
24.0
C
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
M
M
6.8
17.4
2.6 10.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
D
D
6.5 7.5
10.8
18.0
17.4
18.1
D
D
18.726.5
34.4
63.9
75.6
7.0
6.7
4.5
6.8
H48.0
T1
T2
T3
T1
T2
T3
T1-T3
T2
T1
T2
T3
* *
*
***
*
*
***
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 36" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 36" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 40" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 40" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
M
M
6.8
17.4
2.6 10.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
11.2
19.3
11.7
6.8C
C
20.9
43.3
4.5
6.7
7.0
61.969.0
76.8
7.5
68.852.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
D
PLENUM
D
D
18.2
18.1
16.5
32.0G
2-HI
LOWER UNIT
UPPER UNIT
36.042.0
D
BTM CABLE ENTRY
-2200 lbs998 Kg
FRO
NT
90.0
24.0
C
6.5 7.5
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
M
M
6.8
17.4
2.6 6.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J10.8
*
H48.0
T1
T2
T3
T1
T2
T3
T1
T2
T3
T1-T3
T2
**
* *
*
***
*
*
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
15.2
19.3
11.7
6.8C
C
20.9
43.3
4.5
6.7
7.0
61.969.0
76.8
7.5
68.8
52.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
D
PLENUM
D
D
18.2
18.1
16.5
36.0G
2-HI
LOWER UNIT
UPPER UNIT
40.042.0
D
BTM CABLE ENTRY
-2450 lbs1112 Kg
FRO
NT
90.0
24.0
C
6.5 7.5
10.8
H48.0
T1
T2
T3
T1
T2
T3
T1
T2
T3
T1-T3
T2
***
* *
*
***
*
*
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
11.2
C
C
20.9
43.3
7.5
68.852.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
PLENUM
32.0G
2-HI
LOWER UNIT
UPPER UNIT
36.042.0
TOP CABLE ENTRY
-2200 lbs998 Kg
FRO
NT
90.0
24.0
C
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
M
M
6.8
17.4
2.6 6.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
D D
D
D
18.726.5
34.4
63.9
75.6
6.8
4.5
6.7
7.0
10.8
7.56.5
18.0
17.418.1
H48.0
T1
T2
T3
T1
T2
T3
T1-T3
T2
T1
T2
T3
* *
*
***
*
*
***
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
15.2
C
C
20.9
43.3
7.5
68.8
52.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
PLENUM
36.0G
2-HI
LOWER UNIT
UPPER UNIT
40.042.0
TOP CABLE ENTRY
-2450 lbs1112 Kg
FRO
NT
90.0
24.0
C
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
M
M
6.8
17.4
2.6 10.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
D
D
6.5 7.5
10.8
18.0
17.4
18.1
D
D
18.726.5
34.4
63.9
75.6
7.0
6.7
4.5
6.8
H48.0
T1
T2
T3
T1
T2
T3
T1-T3
T2
T1
T2
T3
* *
*
***
*
*
***
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 36" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 36" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 40" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 40" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
M
M
6.8
17.4
2.6 10.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
2 High, 40” Wide
2 High, 36” Wide
Limitamp AR Medium Votage Motor Control CR194 AR 400A, Stationary or Draw-out, Outline Dimensions 2400-7200 Volts, Two-High, Top Cable Entry
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
11.2
19.3
11.7
6.8C
C
20.9
43.3
4.5
6.7
7.0
61.969.0
76.8
7.5
68.852.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
D
PLENUM
D
D
18.2
18.1
16.5
32.0G
2-HI
LOWER UNIT
UPPER UNIT
36.042.0
D
BTM CABLE ENTRY
-2200 lbs998 Kg
FRO
NT
90.0
24.0
C
6.5 7.5
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
M
M
6.8
17.4
2.6 6.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J10.8
*
H48.0
T1
T2
T3
T1
T2
T3
T1
T2
T3
T1-T3
T2
**
* *
*
***
*
*
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
15.2
19.3
11.7
6.8C
C
20.9
43.3
4.5
6.7
7.0
61.969.0
76.8
7.5
68.8
52.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
D
PLENUM
D
D
18.2
18.1
16.5
36.0G
2-HI
LOWER UNIT
UPPER UNIT
40.042.0
D
BTM CABLE ENTRY
-2450 lbs1112 Kg
FRO
NT
90.0
24.0
C
6.5 7.5
10.8
H48.0
T1
T2
T3
T1
T2
T3
T1
T2
T3
T1-T3
T2
***
* *
*
***
*
*
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
11.2
C
C
20.9
43.3
7.5
68.852.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
PLENUM
32.0G
2-HI
LOWER UNIT
UPPER UNIT
36.042.0
TOP CABLE ENTRY
-2200 lbs998 Kg
FRO
NT
90.0
24.0
C
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
M
M
6.8
17.4
2.6 6.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
D D
D
D
18.726.5
34.4
63.9
75.6
6.8
4.5
6.7
7.0
10.8
7.56.5
18.0
17.418.1
H48.0
T1
T2
T3
T1
T2
T3
T1-T3
T2
T1
T2
T3
* *
*
***
*
*
***
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
15.2
C
C
20.9
43.3
7.5
68.8
52.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
PLENUM
36.0G
2-HI
LOWER UNIT
UPPER UNIT
40.042.0
TOP CABLE ENTRY
-2450 lbs1112 Kg
FRO
NT
90.0
24.0
C
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
M
M
6.8
17.4
2.6 10.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
D
D
6.5 7.5
10.8
18.0
17.4
18.1
D
D
18.726.5
34.4
63.9
75.6
7.0
6.7
4.5
6.8
H48.0
T1
T2
T3
T1
T2
T3
T1-T3
T2
T1
T2
T3
* *
*
***
*
*
***
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 36" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 36" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 40" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 40" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
M
M
6.8
17.4
2.6 10.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
11.2
19.3
11.7
6.8C
C
20.9
43.3
4.5
6.7
7.0
61.969.0
76.8
7.5
68.852.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
D
PLENUM
D
D
18.2
18.1
16.5
32.0G
2-HI
LOWER UNIT
UPPER UNIT
36.042.0
D
BTM CABLE ENTRY
-2200 lbs998 Kg
FRO
NT
90.0
24.0
C
6.5 7.5
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
M
M
6.8
17.4
2.6 6.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J10.8
*
H48.0
T1
T2
T3
T1
T2
T3
T1
T2
T3
T1-T3
T2
**
* *
*
***
*
*
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
15.2
19.3
11.7
6.8C
C
20.9
43.3
4.5
6.7
7.0
61.969.0
76.8
7.5
68.8
52.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
D
PLENUM
D
D
18.2
18.1
16.5
36.0G
2-HI
LOWER UNIT
UPPER UNIT
40.042.0
D
BTM CABLE ENTRY
-2450 lbs1112 Kg
FRO
NT
90.0
24.0
C
6.5 7.5
10.8
H48.0
T1
T2
T3
T1
T2
T3
T1
T2
T3
T1-T3
T2
***
* *
*
***
*
*
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
11.2
C
C
20.9
43.3
7.5
68.852.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
PLENUM
32.0G
2-HI
LOWER UNIT
UPPER UNIT
36.042.0
TOP CABLE ENTRY
-2200 lbs998 Kg
FRO
NT
90.0
24.0
C
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
M
M
6.8
17.4
2.6 6.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
D D
D
D
18.726.5
34.4
63.9
75.6
6.8
4.5
6.7
7.0
10.8
7.56.5
18.0
17.418.1
H48.0
T1
T2
T3
T1
T2
T3
T1-T3
T2
T1
T2
T3
* *
*
***
*
*
***
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
15.2
C
C
20.9
43.3
7.5
68.8
52.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
PLENUM
36.0G
2-HI
LOWER UNIT
UPPER UNIT
40.042.0
TOP CABLE ENTRY
-2450 lbs1112 Kg
FRO
NT
90.0
24.0
C
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
M
M
6.8
17.4
2.6 10.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
D
D
6.5 7.5
10.8
18.0
17.4
18.1
D
D
18.726.5
34.4
63.9
75.6
7.0
6.7
4.5
6.8
H48.0
T1
T2
T3
T1
T2
T3
T1-T3
T2
T1
T2
T3
* *
*
***
*
*
***
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 36" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 36" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 40" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 40" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
M
M
6.8
17.4
2.6 10.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
11.2
19.3
11.7
6.8C
C
20.9
43.3
4.5
6.7
7.0
61.969.0
76.8
7.5
68.852.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
D
PLENUM
D
D
18.2
18.1
16.5
32.0G
2-HI
LOWER UNIT
UPPER UNIT
36.042.0
D
BTM CABLE ENTRY
-2200 lbs998 Kg
FRO
NT
90.0
24.0
C
6.5 7.5
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
M
M
6.8
17.4
2.6 6.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J10.8
*
H48.0
T1
T2
T3
T1
T2
T3
T1
T2
T3
T1-T3
T2
**
* *
*
***
*
*
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
15.2
19.3
11.7
6.8C
C
20.9
43.3
4.5
6.7
7.0
61.969.0
76.8
7.5
68.8
52.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
D
PLENUM
D
D
18.2
18.1
16.5
36.0G
2-HI
LOWER UNIT
UPPER UNIT
40.042.0
D
BTM CABLE ENTRY
-2450 lbs1112 Kg
FRO
NT
90.0
24.0
C
6.5 7.5
10.8
H48.0
T1
T2
T3
T1
T2
T3
T1
T2
T3
T1-T3
T2
***
* *
*
***
*
*
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
11.2
C
C
20.9
43.3
7.5
68.852.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
PLENUM
32.0G
2-HI
LOWER UNIT
UPPER UNIT
36.042.0
TOP CABLE ENTRY
-2200 lbs998 Kg
FRO
NT
90.0
24.0
C
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
M
M
6.8
17.4
2.6 6.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
D D
D
D
18.726.5
34.4
63.9
75.6
6.8
4.5
6.7
7.0
10.8
7.56.5
18.0
17.418.1
H48.0
T1
T2
T3
T1
T2
T3
T1-T3
T2
T1
T2
T3
* *
*
***
*
*
***
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
15.2
C
C
20.9
43.3
7.5
68.8
52.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
PLENUM
36.0G
2-HI
LOWER UNIT
UPPER UNIT
40.042.0
TOP CABLE ENTRY
-2450 lbs1112 Kg
FRO
NT
90.0
24.0
C
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
M
M
6.8
17.4
2.6 10.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
D
D
6.5 7.5
10.8
18.0
17.4
18.1
D
D
18.726.5
34.4
63.9
75.6
7.0
6.7
4.5
6.8
H48.0
T1
T2
T3
T1
T2
T3
T1-T3
T2
T1
T2
T3
* *
*
***
*
*
***
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 36" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 36" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 40" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 40" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
M
M
6.8
17.4
2.6 10.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Notes:B1 — AC Power BusC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
11.2
19.3
11.7
6.8C
C
20.9
43.3
4.5
6.7
7.0
61.969.0
76.8
7.5
68.852.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
D
PLENUM
D
D
18.2
18.1
16.5
32.0G
2-HI
LOWER UNIT
UPPER UNIT
36.042.0
D
BTM CABLE ENTRY
-2200 lbs998 Kg
FRO
NT
90.0
24.0
C
6.5 7.5
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
M
M
6.8
17.4
2.6 6.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J10.8
*
H48.0
T1
T2
T3
T1
T2
T3
T1
T2
T3
T1-T3
T2
**
* *
*
***
*
*
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
15.2
19.3
11.7
6.8C
C
20.9
43.3
4.5
6.7
7.0
61.969.0
76.8
7.5
68.8
52.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
D
PLENUM
D
D
18.2
18.1
16.5
36.0G
2-HI
LOWER UNIT
UPPER UNIT
40.042.0
D
BTM CABLE ENTRY
-2450 lbs1112 Kg
FRO
NT
90.0
24.0
C
6.5 7.5
10.8
H48.0
T1
T2
T3
T1
T2
T3
T1
T2
T3
T1-T3
T2
***
* *
*
***
*
*
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
11.2
C
C
20.9
43.3
7.5
68.852.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
PLENUM
32.0G
2-HI
LOWER UNIT
UPPER UNIT
36.042.0
TOP CABLE ENTRY
-2200 lbs998 Kg
FRO
NT
90.0
24.0
C
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 6.0
6.0
2.62.3
2.5
6.0
6.0
N
M
M
6.8
17.4
2.6 6.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
D D
D
D
18.726.5
34.4
63.9
75.6
6.8
4.5
6.7
7.0
10.8
7.56.5
18.0
17.418.1
H48.0
T1
T2
T3
T1
T2
T3
T1-T3
T2
T1
T2
T3
* *
*
***
*
*
***
PLENUM
FRONT VIEW
L.H.SIDE VIEW
C
15.2
C
C
20.9
43.3
7.5
68.8
52.0
6.5
6.5
14.2
12.8E
B1L3
L2
L1
PLENUM
36.0G
2-HI
LOWER UNIT
UPPER UNIT
40.042.0
TOP CABLE ENTRY
-2450 lbs1112 Kg
FRO
NT
90.0
24.0
C
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
M
M
6.8
17.4
2.6 10.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
D
D
6.5 7.5
10.8
18.0
17.4
18.1
D
D
18.726.5
34.4
63.9
75.6
7.0
6.7
4.5
6.8
H48.0
T1
T2
T3
T1
T2
T3
T1-T3
T2
T1
T2
T3
* *
*
***
*
*
***
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 36" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 36" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 40" Wide (Stationary or Draw-out)– TOP CABLE ENTRY
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 40" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
M
M
6.8
17.4
2.6 10.0
6.0
6.0
LOWER UNIT
UPPER UNIT
N
FLOOR PLAN
2.5
2.3 0.75TYP.
6.06.0
2.0TYP.
1.5
FRONT
1.5
J
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
6.8
17.4
2.6 10.0
6.0
2.62.3
2.5
10.0
6.0
N
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
add 0.12” for welded bottom plate
2 High, 40” Wide
2 High, 36” Wide
PLENUM
FRONT VIEWL.H.SIDE VIEW
C
15 316
C
C
201516
4314
712
681316
52
612
612
14 316
121316
E
B1
PLENUM
36G
2-HI
LOWER UNIT
UPPER UNIT
4042
TOP CABLE ENTRY
-2450 lbs1112 Kg
FRO
NT
90
24
C
Enclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 40" Wide (Stationary or Draw-out)-TOP CABLE ENTRY
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
61316
1738
6
258
2 51621
210
6
N
FLOOR PLAN
34
TYP.
66
2TYP.
112
FRONT
112
J
GE Limitamp® AR Medium Voltage Motor ControlEnclosures
D
D
612
1034
18
1738
18 116
D
D
181116
26 916
3438
6378
7558
7
634
4 916
61316
H48
T1
T2
T3
T1
T2
T3
T1-T3
T2
T1
T2
T3
* *
*
***
*
*
***
4278
51316
B2
11
11
L1
L3
L2
L1
L2
L3
712
Notes:B1 — AC Power Bus, 1200AB2 — AC Power Bus, 3000AC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
PLENUM
FRONT VIEWL.H.SIDE VIEW
C
11 316
C
C
201516
4314
712
681316
52
612
612
14 316
121316
E
B1
PLENUM
32G
2-HI
LOWER UNIT
UPPER UNIT
3642
TOP CABLE ENTRY
-2200 lbs998 Kg
FRO
NT
90
24
C
Enclosure Outline dimensions 2400-7200 VoltsCR194 AR 400A, 2 High, 36" Wide (Stationary or Draw-out)-TOP CABLE ENTRY
LOWER UNIT
UPPER UNIT
FRONT
TOP VIEW
M
M
61316
1738
6
258
2 51621
26
6
N
FLOOR PLAN
34
TYP.
66
2TYP.
112
FRONT
112
J
GE Limitamp® AR Medium Voltage Motor ControlEnclosures
D D
D
D
181116
26 916
3438
6378
7558
61316
412
634
7
1034
612
18
1738
18 116
H48
T1
T2
T3
T1
T2
T3
T1-T3
T2
T1
T2
T3
* *
*
***
*
*
***
4278
51316
B2
11
11
L1
L3
L2
L1
L2
L3
712
Notes:B1 — AC Power Bus, 1200AB2 — AC Power Bus, 3000AC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionG — Space Required to Open Doors 135°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
4
E
68-4/5
B114-3/16
52
6-1/2
6-1/2L1
L2
L3
10
11-1/2
6
1726
10-1/2
T1
T2
T3
D
72
5-1/2
6-1/2
42
L.H.SIDE VIEW
X
C
F
48
17-5/8
- 1800 LBS.
HFRO
NT
G
L3
L2
L1
D
12-1/2
10-5/8
5-3/4 12-3/4
4-3/16
C
T2
T1,T36
90
B
X
48FRONT VIEW
13-1/2
F
E
16-3/427-3/4
9
*
7
PLENUM
24
4-1/2
2-3/4
- 816 KG.
6P
M
N
K6
7-9/16
6
1-1/2
42
3/4
2
10-1/2
2-5/16
10-1/2
FRONT
26
31-5/16
2
14
J
K
FLOOR PLAN
1-1/2
6
8-7/16
9
8-7/166P
M
10-1/22-9/16
6
14
TOP VIEW
FRONT2-1/2
K
3-1/2N7-9/16
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power Bus, 800AC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 90°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control ConduitP — Recommended Position for Incoming Power Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 800A, 1 High, 48" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
add 0.12” for welded bottom plate
4
E
68-4/5
B114-3/16
52
6-1/2
6-1/2L1
L2
L3
10
11-1/2
6
1726
10-1/2
T1
T2
T3
D
72
5-1/2
6-1/2
42
L.H.SIDE VIEW
X
C
F
48
17-5/8
- 1800 LBS.
HFRO
NT
G
L3
L2
L1
D
12-1/2
10-5/8
5-3/4 12-3/4
4-3/16
C
T2
T1,T36
90
B
X
48FRONT VIEW
13-1/2
F
E
16-3/427-3/4
9
*
7
PLENUM
24
4-1/2
2-3/4
- 816 KG.
6P
M
N
K6
7-9/16
6
1-1/2
42
3/4
2
10-1/2
2-5/16
10-1/2
FRONT
26
31-5/16
2
14
J
K
FLOOR PLAN
1-1/2
6
8-7/16
9
8-7/166P
M
10-1/22-9/16
6
14
TOP VIEW
FRONT2-1/2
K
3-1/2N7-9/16
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power Bus, 800AC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 90°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control ConduitP — Recommended Position for Incoming Power Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 800A, 1 High, 48" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
add 0.12” for welded bottom plate
4
E
68-4/5
B114-3/16
52
6-1/2
6-1/2L1
L2
L3
10
11-1/2
6
1726
10-1/2
T1
T2
T3
D
72
5-1/2
6-1/2
42
L.H.SIDE VIEW
X
C
F
48
17-5/8
- 1800 LBS.
HFRO
NT
G
L3
L2
L1
D
12-1/2
10-5/8
5-3/4 12-3/4
4-3/16
C
T2
T1,T36
90
B
X
48FRONT VIEW
13-1/2
F
E
16-3/427-3/4
9
*
7
PLENUM
24
4-1/2
2-3/4
- 816 KG.
6P
M
N
K6
7-9/16
6
1-1/2
42
3/4
2
10-1/2
2-5/16
10-1/2
FRONT
26
31-5/16
2
14
J
K
FLOOR PLAN
1-1/2
6
8-7/16
9
8-7/166P
M
10-1/22-9/16
6
14
TOP VIEW
FRONT2-1/2
K
3-1/2N7-9/16
Notes:B — Incoming Power Terminal ConnectionB1 — AC Power Bus, 800AC — Control Lead Terminal BoardD — Motor Lead Terminal ConnectionE — Ground Bus Terminal ConnectionF — Ground Terminal Connection (If Ordered)G — Space Required to Open Doors 90°H — Four-foot Aisle for Contactor RemovalJ — Mounting Holes for 1/2" Diameter Anchor BoltsM — Recommended Position for Incoming Motor ConduitN — Recommended Position for Incoming Control ConduitP — Recommended Position for Incoming Power Conduit* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
GE Limitamp AR Medium Voltage Motor Control EnclosuresEnclosure Outline dimensions 2400-7200 VoltsCR194 AR 800A, 1 High, 48" Wide (Stationary or Draw-out)– BTM CABLE ENTRY
add 0.12” for welded bottom plate
Limitamp AR Medium Voltage Motor Control CR194 AR 800A, Stationary or Draw-out, Outline Dimensions 2400-7200 Volts, One-High, Top/Bottom Cable Entry
1 High, 48” Wide
Reference PublicationsStandard, non-Arc Resistant LimitampVacuum Contactors GEH-5306Installation Instructions GEH-6263Application and Selection Guide GET-6840 Load-Break Switches Installation Instructions GEH-4268 Vacuum Contactors, Renewal Parts Bulletin GEF-8016
Limitamp ARLimitamp AR Product Flyer DEA-527Limitamp AR Installation Instructions DEH-6790
Information provided is subject to change without notice. Please verify all details with GE. All values are design or typical values when measured under laboratory conditions, and GE makes no warranty or guarantee, express or implied, that such performance will be obtained under end-use conditions. DET-745B 10/14
GE Industrial Solutions 41 Woodford AvenuePlainville, CT 06062www.geindustrial.com
© 2014 General Electric Company