Lightning Protection Sizing
Transcript of Lightning Protection Sizing
-
7/29/2019 Lightning Protection Sizing
1/1
PROJECT : -
CLIENT :-
CLIENT'S CONSULTANT :-
CONTRACTOR :-
i) Input Data :-a) Dimensions of Building / StructureLength of the Building L = 60.00 m
Width of the Building W = 28.00 m
Height of the Building H = 23.00 m
b) Lightning Flash Density & Weighing FactorsNumber of Thunderstorm Days / Year N = 100 No. of Days / Year
Li htnin Flash Densit (Flashes to Ground /km2/ ear) Ng = 9.2 Nos./km
2/ ear
Weighting Factor A ( Use of Structure ) A ( Refer Table 1A of IS 2309 ) = 1
Weighting Factor B ( Type of Construction ) B ( Refer Table 1B of IS 2309 ) = 0.8
Weighting Factor C ( Content of Consequential Effects ) C ( Refer Table 1C of IS 2309 ) = 1
Weighting Factor D ( Degree of Isolation ) D ( Refer Table 1D of IS 2309 ) = 0.4
Weighting Factor E ( Type of Country ) E ( Refer Table 1E of IS 2309 ) = 0.3
ii) Calculations :-
Overall Multiplying Factor = AxBxCxDxE = 0.096000
= 0.006526
ie 6.5260E-03
iii) Maximum Acceptable Overall Risk Factor:-
= 0.000001ie 1.000E-06
iv) Result / Conclusion :-
>
Calculations (As per Clause 12.2.3 of IS-2309):-
Base Area of Structure Ab = = 1680 Meter2
Perimeter of Structure P = = 176 Meter
i) For Base Area (Ab) < 100m2
a) Number of Down Conductors Required = = 1 Nos
ii) For Base Area (Ab) > 100m2
b) Based on Base Area of Structure:-
= = 6 Nos
c) Based on Parimeter of Structure:-
= = 6 Nos.
Hence, Required Number of Down Conductors = 6 Nos.
Rev. Date Drg/Doc. No. Reviewed ApprovedR0
A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION
PACKAGE4 INDOOR SUBSTATIONS-NEW & MODIFICATIONS
OCP
Uhde
Spie Maroc
LIGHTNING PROTECTION CALCULATION FOR PJ-TPP BUILDING
( REFERENCE : IS 2309 )
Description / ParameterSymbol / Formulae /
ReferencesValue Unit
( Refer the Relevant Layout
Drawings of the Building /
Structure )
( Refer Fig. 1 of IS 2309 )
( Refer Clause 8.1.2 of
Collection Area ( Refer Clause 8.1.2 of IS 2309 ) Ac =(L x W) + 2 (L x H) +
2(W x H) + 3.14 H
2 = 7389.06 Meter2
Probable Number of Strikes to Building / Structure per Year (
Refer Clause 8.1.2 of IS 2309 )P = Ac x Ng x 10
-6times/year = 0.067979 Times per year
( L x W )
Overall Risk Factor Calculated Rf-C =Overall Multiplying
Factor x P
Maximum Acceptable Overall Risk Factor Rf-A( Refer Clauses 8.1.3 &
8.1.6 of IS 2309 )
Since Overall Risk Factor Calculated Maximum Acceptable Overall Risk Factor
Hence, Lightning Protection is Required.
B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS
2(L+W)
For Ab < 100m2
Number of Down Conductors Required 1+(Ab-100)/300
Number of Down Conductors Required P/30
Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309)
REVISION
DETAILS Remarks Prepared
First Submission