Lightning Protection Sizing

download Lightning Protection Sizing

of 1

Transcript of Lightning Protection Sizing

  • 7/29/2019 Lightning Protection Sizing

    1/1

    PROJECT : -

    CLIENT :-

    CLIENT'S CONSULTANT :-

    CONTRACTOR :-

    i) Input Data :-a) Dimensions of Building / StructureLength of the Building L = 60.00 m

    Width of the Building W = 28.00 m

    Height of the Building H = 23.00 m

    b) Lightning Flash Density & Weighing FactorsNumber of Thunderstorm Days / Year N = 100 No. of Days / Year

    Li htnin Flash Densit (Flashes to Ground /km2/ ear) Ng = 9.2 Nos./km

    2/ ear

    Weighting Factor A ( Use of Structure ) A ( Refer Table 1A of IS 2309 ) = 1

    Weighting Factor B ( Type of Construction ) B ( Refer Table 1B of IS 2309 ) = 0.8

    Weighting Factor C ( Content of Consequential Effects ) C ( Refer Table 1C of IS 2309 ) = 1

    Weighting Factor D ( Degree of Isolation ) D ( Refer Table 1D of IS 2309 ) = 0.4

    Weighting Factor E ( Type of Country ) E ( Refer Table 1E of IS 2309 ) = 0.3

    ii) Calculations :-

    Overall Multiplying Factor = AxBxCxDxE = 0.096000

    = 0.006526

    ie 6.5260E-03

    iii) Maximum Acceptable Overall Risk Factor:-

    = 0.000001ie 1.000E-06

    iv) Result / Conclusion :-

    >

    Calculations (As per Clause 12.2.3 of IS-2309):-

    Base Area of Structure Ab = = 1680 Meter2

    Perimeter of Structure P = = 176 Meter

    i) For Base Area (Ab) < 100m2

    a) Number of Down Conductors Required = = 1 Nos

    ii) For Base Area (Ab) > 100m2

    b) Based on Base Area of Structure:-

    = = 6 Nos

    c) Based on Parimeter of Structure:-

    = = 6 Nos.

    Hence, Required Number of Down Conductors = 6 Nos.

    Rev. Date Drg/Doc. No. Reviewed ApprovedR0

    A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION

    PACKAGE4 INDOOR SUBSTATIONS-NEW & MODIFICATIONS

    OCP

    Uhde

    Spie Maroc

    LIGHTNING PROTECTION CALCULATION FOR PJ-TPP BUILDING

    ( REFERENCE : IS 2309 )

    Description / ParameterSymbol / Formulae /

    ReferencesValue Unit

    ( Refer the Relevant Layout

    Drawings of the Building /

    Structure )

    ( Refer Fig. 1 of IS 2309 )

    ( Refer Clause 8.1.2 of

    Collection Area ( Refer Clause 8.1.2 of IS 2309 ) Ac =(L x W) + 2 (L x H) +

    2(W x H) + 3.14 H

    2 = 7389.06 Meter2

    Probable Number of Strikes to Building / Structure per Year (

    Refer Clause 8.1.2 of IS 2309 )P = Ac x Ng x 10

    -6times/year = 0.067979 Times per year

    ( L x W )

    Overall Risk Factor Calculated Rf-C =Overall Multiplying

    Factor x P

    Maximum Acceptable Overall Risk Factor Rf-A( Refer Clauses 8.1.3 &

    8.1.6 of IS 2309 )

    Since Overall Risk Factor Calculated Maximum Acceptable Overall Risk Factor

    Hence, Lightning Protection is Required.

    B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS

    2(L+W)

    For Ab < 100m2

    Number of Down Conductors Required 1+(Ab-100)/300

    Number of Down Conductors Required P/30

    Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309)

    REVISION

    DETAILS Remarks Prepared

    First Submission