Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of...

34
FLUORESCENT LIGHTING FOR ZONE 2 AND 22 LIGHTING THE WAY PROCESS AUTOMATION PROCESS AUTOMATION

Transcript of Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of...

Page 1: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

FLUORESCENT LIGHTINGFOR ZONE 2 AND 22

LIGHTING THE WAY

PROCESS AUTOMATIONPROCESS AUTOMATION

Page 2: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

2

ABOUT PEPPERL+FUCHS

OUR VALUES, OUR GOALS, OUR FOCUS – YOUR BENEFITS

Pepperl+Fuchs the world’s leading manufacturer of intrinsically safe explosion protection and electronic

sensors acquired UK based Walsall Ltd to expand the Process Automation Division with significant

expertise in the development and manufacture of installation equipment for use in hazardous areas and

harsh environments.

Walsall Ltd has over one hundred years of UK heritage dating back to the early days of Walsall Conduits PLC, which

once dominated the world of mechanical explosion protection equipment. In addition to the hazardous area approved

lighting suitable for Zone 2 and 22 installation shown in this brochure, Pepperl+Fuchs has a wide range of complementary

products also available. These include:

Lighting for Zone 1 Applications

A range of general purpose and emergency lighting products suitable for installation in Zone 1 hazardous area locations.

Enclosures and Terminal Boxes

High quality terminal junction box enclosures in the increased safety, intrinsic safety and flameproof protection classes

available in a wide range of sizes and materials such as GRP and Stainless Steel.

Local Control

A comprehensive range of standard and customised multi function local control stations and control panels are available

in GRP, Stainless steel, and Cast Iron Enclosures.

Hazardous Area Enclosure Solutions

UK based design and build service offering a fully customised explosion proof panel assembly and wiring service using a

variety of explosion proof (Exd) and increased safety (Exe) enclosures to house non certified electrical components.

Page 3: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

3

HAZARDOUS AREA FLUORESCENT LIGHTING

FLUORESCENT LIGHTING FOR ZONE 2 AND 22 APPLICATIONS

Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22

hazardous area locations. The Elenor product range covers applications for general purpose and emergency

lighting with a wide range of single and twin fittings using a design which is simple to install and maintain.

The products are ideally suited to a range of applications and industries including:

■ Oil & Gas

■ Petrochemical

■ Pharmaceutical

■ Distilleries

■ Water Pumping and Sewerage Treatment

■ Agricultural

■ Food and Beverage

P. 04

P. 16

P. 28

P. 30

STANDARD FLUORESCENT

ESCAPE ROUTE

EMERGENCY FLUORESCENT

BULKHEAD

3

Elenor Range

Page 4: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-09

-04 2

2:54

Date

of iss

ue 2

012-

09-0

723

9113

_eng

_175

7376

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 4

VIPET-N-118HFEx nA Fluorescent Light Fitting

Dimensions (mm)

Technical dataElectrical specificationsOperating voltage 220 ... 240 V 50Hz / 60HzOperating current 0.09 ATerminal capacity 2.5 mm2 Connection block suitable for through wiringControl gear high frequency electronic ballastFitting type Ceiling light fittingLamps T26 bi-pin fluorescent tube

Number of lamps 1Length 600 mm ( 2 ft )Power 18 W

Mechanical specificationsCover fixing stainless steel snap shut fastenersProtection degree IP66Cable entry

Number of cable entries 2 x M20 1 at each endMaterial

Housing PolycarbonateLamp cover PolycarbonateReflector 0.6 mm Mild steelFinish Body: as moulded

reflector: epoxy powder coated, whiteSeal polyurethane foam

Mass approx. 1.7 kgDimensions

A 685 mmB 119 mmC 110 mmD 176 mm

Features

• Power 18 W• Installation in Zone 2 and Zone 22• Electronic HF control gear• Suitable for 220-240V AC 50/60Hz

operation• Multiple locking points on diffuser that

can be hinged from both sides• Fast opening and closing of fitting via

snap shut fasteners• Anti-glare diffuser cover• Stainless steel surface mounting

brackets supplied as standard

A

FE

C

DB

Page 5: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-09

-04 2

2:54

Date

of iss

ue 2

012-

09-0

723

9113

_eng

_175

7376

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 5

VIPET-N-118HFEx nA Fluorescent Light Fitting

F 340 mmMounting 2 x stainless steel removable mounting bracketsGrounding Internal connectionAmbient conditionsAmbient temperature -20 ... 40 °C (-4 ... 104 °F)Data for application in connection with Ex-areasEC-Type Examination Certificate FTZU 02 ATEX 0313X

Group, category, type of protection, temperature class

¬ II 3 GD Ex nA tD A II T5 T82°C

International approvalsGOST-R approval GOST-R B02432ConformityProtection degree EN 60529General informationSupplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of

Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

AccessoriesDesignation 1 x nylon non-armoured Ex e cable gland

1 x nylon Ex e sealing plug

Page 6: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-09

-04 2

2:55

Date

of iss

ue 2

012-

09-0

723

9114

_eng

_175

7377

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 6

VIPET-N-218HFEx nA Fluorescent Light Fitting

Dimensions (mm)

Technical dataElectrical specificationsOperating voltage 220 ... 240 V 50Hz / 60HzOperating current 0.18 ATerminal capacity 2.5 mm2 Connection block suitable for through wiringControl gear high frequency electronic ballastFitting type Ceiling light fittingLamps T26 bi-pin fluorescent tube

Number of lamps 2Length 600 mm ( 2 ft )Power 2 x 18 W

Mechanical specificationsCover fixing stainless steel snap shut fastenersProtection degree IP66Cable entry

Number of cable entries 4 x M20 2 at each endMaterial

Housing PolycarbonateLamp cover PolycarbonateReflector 0.6 mm Mild steelFinish Body: as moulded

reflector: epoxy powder coated, whiteSeal polyurethane foam

Mass approx. 2.2 kgDimensions

A 685 mmB 173 mmC 110 mmD 230 mm

Features

• Power 2 x 18 W• Installation in Zone 2 and Zone 22• Electronic HF control gear• Suitable for 220-240V AC 50/60Hz

operation• Multiple locking points on diffuser that

can be hinged from both sides• Fast opening and closing of fitting via

snap shut fasteners• Anti-glare diffuser cover• Stainless steel surface mounting

brackets supplied as standard

C

DB

A

FE

Page 7: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-09

-04 2

2:55

Date

of iss

ue 2

012-

09-0

723

9114

_eng

_175

7377

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 7

VIPET-N-218HFEx nA Fluorescent Light Fitting

F 340 mmMounting 2 x stainless steel removable mounting bracketsGrounding Internal connectionAmbient conditionsAmbient temperature -20 ... 40 °C (-4 ... 104 °F)Data for application in connection with Ex-areasEC-Type Examination Certificate FTZU 02 ATEX 0313X

Group, category, type of protection, temperature class

¬ II 3 GD Ex nA tD A II T5 T82°C

International approvalsGOST-R approval GOST-R B02432ConformityProtection degree EN 60529General informationSupplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of

Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

AccessoriesDesignation 1 x nylon non-armoured Ex e cable gland

1 x nylon Ex e sealing plug

Page 8: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-09

-04 2

2:54

Date

of iss

ue 2

012-

09-0

723

9115

_eng

_175

7378

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 8

VIPET-N-136HFEx nA Fluorescent Light Fitting

Dimensions (mm)

Technical dataElectrical specificationsOperating voltage 220 ... 240 V 50Hz / 60HzOperating current 0.16 ATerminal capacity 2.5 mm2 Connection block suitable for through wiringControl gear high frequency electronic ballastFitting type Ceiling light fittingLamps T26 bi-pin fluorescent tube

Number of lamps 1Length 1200 mm ( 4 ft )Power 36 W

Mechanical specificationsCover fixing stainless steel snap shut fastenersProtection degree IP66Cable entry

Number of cable entries 2 x M20 1 at each endMaterial

Housing PolycarbonateLamp cover PolycarbonateReflector 0.6 mm Mild steelFinish Body: as moulded

reflector: epoxy powder coated, whiteSeal polyurethane foam

Mass approx. 3 kgDimensions

A 1290 mmB 119 mmC 110 mmD 176 mm

Features

• Power 36 W• Installation in Zone 2 and Zone 22• Electronic HF control gear• Suitable for 220-240V AC 50/60Hz

operation• Multiple locking points on diffuser that

can be hinged from both sides• Fast opening and closing of fitting via

snap shut fasteners• Anti-glare diffuser cover• Stainless steel surface mounting

brackets supplied as standard

A

FE

C

DB

Page 9: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-09

-04 2

2:54

Date

of iss

ue 2

012-

09-0

723

9115

_eng

_175

7378

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 9

VIPET-N-136HFEx nA Fluorescent Light Fitting

F 700 mmMounting 2 x stainless steel removable mounting bracketsGrounding Internal connectionAmbient conditionsAmbient temperature -20 ... 40 °C (-4 ... 104 °F)Data for application in connection with Ex-areasEC-Type Examination Certificate FTZU 02 ATEX 0313X

Group, category, type of protection, temperature class

¬ II 3 GD Ex nA tD A II T5 T86°C

International approvalsGOST-R approval GOST-R B02432ConformityProtection degree EN 60529General informationSupplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of

Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

AccessoriesDesignation 1 x nylon non-armoured Ex e cable gland

1 x nylon Ex e sealing plug

Page 10: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-09

-04 2

2:55

Date

of iss

ue 2

012-

09-0

723

9117

_eng

_175

7379

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 10

VIPET-N-236HFEx nA Fluorescent Light Fitting

Dimensions (mm)

Technical dataElectrical specificationsOperating voltage 220 ... 240 V 50Hz / 60HzOperating current 0.32 ATerminal capacity 2.5 mm2 Connection block suitable for through wiringControl gear high frequency electronic ballastFitting type Ceiling light fittingLamps T26 bi-pin fluorescent tube

Number of lamps 2Length 1200 mm ( 4 ft )Power 2 x 36 W

Mechanical specificationsCover fixing stainless steel snap shut fastenersProtection degree IP66Cable entry

Number of cable entries 4 x M20 2 at each endMaterial

Housing PolycarbonateLamp cover PolycarbonateReflector 0.6 mm Mild steelFinish Body: as moulded

reflector: epoxy powder coated, whiteSeal polyurethane foam

Mass approx. 3.6 kgDimensions

A 1290 mmB 173 mmC 110 mmD 230 mm

Features

• Power 2 x 36 W• Installation in Zone 2 and Zone 22• Electronic HF control gear• Suitable for 220-240V AC 50/60Hz

operation• Multiple locking points on diffuser that

can be hinged from both sides• Fast opening and closing of fitting via

snap shut fasteners• Anti-glare diffuser cover• Stainless steel surface mounting

brackets supplied as standard

C

DB

A

FE

Page 11: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-09

-04 2

2:55

Date

of iss

ue 2

012-

09-0

723

9117

_eng

_175

7379

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 11

VIPET-N-236HFEx nA Fluorescent Light Fitting

F 700 mmMounting 2 x stainless steel removable mounting bracketsGrounding Internal connectionAmbient conditionsAmbient temperature -20 ... 40 °C (-4 ... 104 °F)Data for application in connection with Ex-areasEC-Type Examination Certificate FTZU 02 ATEX 0313X

Group, category, type of protection, temperature class

¬ II 3 GD Ex nA tD A II T5 T86°C

International approvalsGOST-R approval GOST-R B02432ConformityProtection degree EN 60529General informationSupplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of

Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

AccessoriesDesignation 1 x nylon non-armoured Ex e cable gland

3 x nylon Ex e sealing plugs

Page 12: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-09

-04 2

2:55

Date

of iss

ue 2

012-

09-0

723

9118

_eng

_175

7380

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 12

VIPET-N-158HFEx nA Fluorescent Light Fitting

Dimensions (mm)

Technical dataElectrical specificationsOperating voltage 220 ... 240 V 50Hz / 60HzOperating current 0.27 ATerminal capacity 2.5 mm2 Connection block suitable for through wiringControl gear high frequency electronic ballastFitting type Ceiling light fittingLamps T26 bi-pin fluorescent tube

Number of lamps 1Length 1500 mm ( 5 ft )Power 58 W

Mechanical specificationsCover fixing stainless steel snap shut fastenersProtection degree IP66Cable entry

Number of cable entries 2 x M20 1 at each endMaterial

Housing PolycarbonateLamp cover PolycarbonateReflector 0.6 mm Mild steelFinish Body: as moulded

reflector: epoxy powder coated, whiteSeal polyurethane foam

Mass approx. 3.3 kgDimensions

A 1590 mmB 119 mmC 110 mmD 176 mm

Features

• Power 58 W• Installation in Zone 2 and Zone 22• Electronic HF control gear• Suitable for 220-240V AC 50/60Hz

operation• Multiple locking points on diffuser that

can be hinged from both sides• Fast opening and closing of fitting via

snap shut fasteners• Anti-glare diffuser cover• Stainless steel surface mounting

brackets supplied as standard

A

FE

C

DB

Page 13: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-09

-04 2

2:55

Date

of iss

ue 2

012-

09-0

723

9118

_eng

_175

7380

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 13

VIPET-N-158HFEx nA Fluorescent Light Fitting

F 1000 mmMounting 2 x stainless steel removable mounting bracketsGrounding Internal connectionAmbient conditionsAmbient temperature -20 ... 40 °C (-4 ... 104 °F)Data for application in connection with Ex-areasEC-Type Examination Certificate FTZU 02 ATEX 0313X

Group, category, type of protection, temperature class

¬ II 3 GD Ex nA tD A II T5 T92°C

International approvalsGOST-R approval GOST-R B02432ConformityProtection degree EN 60529General informationSupplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of

Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

AccessoriesDesignation 1 x nylon non-armoured Ex e cable gland

1 x nylon Ex e sealing plug

Page 14: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-09

-04 2

2:55

Date

of iss

ue 2

012-

09-0

723

9119

_eng

_175

7381

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 14

VIPET-N-258HFEx nA Fluorescent Light Fitting

Dimensions (mm)

Technical dataElectrical specificationsOperating voltage 220 ... 240 V 50Hz / 60HzOperating current 0.51 ATerminal capacity 2.5 mm2 Connection block suitable for through wiringControl gear high frequency electronic ballastFitting type Ceiling light fittingLamps T26 bi-pin fluorescent tube

Number of lamps 2Length 1500 mm ( 5 ft )Power 2 x 58 W

Mechanical specificationsCover fixing stainless steel snap shut fastenersProtection degree IP66Cable entry

Number of cable entries 4 x M20 2 at each endMaterial

Housing PolycarbonateLamp cover PolycarbonateReflector 0.6 mm Mild steelFinish Body: as moulded

reflector: epoxy powder coated, whiteSeal polyurethane foam

Mass approx. 4.8 kgDimensions

A 1590 mmB 173 mmC 110 mmD 230 mm

Features

• Power 2 x 58 W• Installation in Zone 2 and Zone 22• Electronic HF control gear• Suitable for 220-240V AC 50/60Hz

operation• Multiple locking points on diffuser that

can be hinged from both sides• Fast opening and closing of fitting via

snap shut fasteners• Anti-glare diffuser cover• Stainless steel surface mounting

brackets supplied as standard

C

DB

A

FE

Page 15: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-09

-04 2

2:55

Date

of iss

ue 2

012-

09-0

723

9119

_eng

_175

7381

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 15

VIPET-N-258HFEx nA Fluorescent Light Fitting

F 1000 mmMounting 2 x stainless steel removable mounting bracketsGrounding Internal connectionAmbient conditionsAmbient temperature -20 ... 40 °C (-4 ... 104 °F)Data for application in connection with Ex-areasEC-Type Examination Certificate FTZU 02 ATEX 0313X

Group, category, type of protection, temperature class

¬ II 3 GD Ex nA tD A II T5 T93°C

International approvalsGOST-R approval GOST-R B02432ConformityProtection degree EN 60529General informationSupplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of

Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

AccessoriesDesignation 1 x nylon non-armoured Ex e cable gland

3 x nylon Ex e sealing plugs

Page 16: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-09

-04 2

2:54

Date

of iss

ue 2

012-

09-0

723

9120

_eng

_175

7382

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 16

VIPET-N-EM-118HF-3HEx nA Emergency Fluorescent Light Fitting

Dimensions (mm)

Technical dataElectrical specificationsOperating voltage 220 ... 240 V 50Hz / 60HzOperating current 0.09 ATerminal capacity 2.5 mm2 Connection block suitable for through wiringControl gear high frequency electronic ballastFitting type Ceiling light fittingLamps T26 bi-pin fluorescent tube

Number of lamps 1Length 600 mm ( 2 ft )Power 18 W

Emergency operation non-maintainedOperation time 3 h

Mechanical specificationsCover fixing stainless steel snap shut fastenersProtection degree IP66Cable entry

Number of cable entries 2 x M20 1 at each endMaterial

Housing PolycarbonateLamp cover PolycarbonateReflector 0.6 mm Mild steelFinish Body: as moulded

reflector: epoxy powder coated, whiteSeal polyurethane foam

Mass approx. 2.3 kgDimensions

A 685 mmB 119 mm

Features

• Power 18 W• Installation in Zone 2 and Zone 22• Electronic HF control gear• Multiple locking points on diffuser that

can be hinged from both sides• Fast opening and closing of fitting via

snap shut fasteners• Anti-glare diffuser cover• Stainless steel surface mounting

brackets supplied as standard• Minimum of 3 hour duration in

emergency mode

A

FE

C

DB

Page 17: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-09

-04 2

2:54

Date

of iss

ue 2

012-

09-0

723

9120

_eng

_175

7382

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 17

VIPET-N-EM-118HF-3HEx nA Emergency Fluorescent Light Fitting

C 110 mmD 176 mmF 340 mm

Mounting 2 x stainless steel removable mounting bracketsGrounding Internal connectionAmbient conditionsAmbient temperature 0 ... 30 °C (32 ... 86 °F)Data for application in connection with Ex-areasEC-Type Examination Certificate FTZU 05 ATEX 0200X

Group, category, type of protection, temperature class

¬ II 3 GD Ex nA tD A II T5 T42°C

International approvalsGOST-R approval GOST-R B02432ConformityProtection degree EN 60529General informationSupplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of

Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

AccessoriesDesignation 1 x nylon non-armoured Ex e cable gland

1 x nylon Ex e sealing plug

Page 18: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-09

-04 2

2:54

Date

of iss

ue 2

012-

09-0

723

9121

_eng

_175

7383

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 18

MULTIVIPET-N-EM-218HF-3HEx nA Emergency Fluorescent Light Fitting

Dimensions (mm)

Technical dataElectrical specificationsOperating voltage 220 ... 240 V 50Hz / 60HzOperating current 0.18 ATerminal capacity 2.5 mm2 Connection block suitable for through wiringControl gear high frequency electronic ballastFitting type Ceiling light fittingLamps T26 bi-pin fluorescent tube

Number of lamps 2Length 600 mm ( 2 ft )Power 2 x 18 W

Emergency operation maintainedOperation time 3 h

Mechanical specificationsCover fixing stainless steel snap shut fastenersProtection degree IP66Cable entry

Number of cable entries 4 x M20 2 at each endMaterial

Housing PolycarbonateLamp cover PolycarbonateReflector 0.6 mm Mild steelFinish Body: as moulded

reflector: epoxy powder coated, whiteSeal polyurethane foam

Mass approx. 2.9 kgDimensions

A 685 mmB 173 mm

Features

• Power 2 x 18 W• Installation in Zone 2 and Zone 22• Electronic HF control gear• Suitable for 220-240V AC 50/60Hz

operation• Multiple locking points on diffuser that

can be hinged from both sides• Fast opening and closing of fitting via

snap shut fasteners• Anti-glare diffuser cover• Stainless steel surface mounting

brackets supplied as standard• Minimum of 3 hour duration in

emergency mode

C

DB

A

FE

Page 19: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-09

-04 2

2:54

Date

of iss

ue 2

012-

09-0

723

9121

_eng

_175

7383

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 19

MULTIVIPET-N-EM-218HF-3HEx nA Emergency Fluorescent Light Fitting

C 110 mmD 230 mmF 340 mm

Mounting 2 x stainless steel removable mounting bracketsGrounding Internal connectionAmbient conditionsAmbient temperature 0 ... 30 °C (32 ... 86 °F)Data for application in connection with Ex-areasEC-Type Examination Certificate FTZU 05 ATEX 0200X

Group, category, type of protection, temperature class

¬ II 3 GD Ex nA tD A II T5 T75°C

International approvalsGOST-R approval GOST-R B02432ConformityProtection degree EN 60529General informationSupplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of

Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

AccessoriesDesignation 1 x nylon non-armoured Ex e cable gland

3 x nylon Ex e sealing plugs

Page 20: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-09

-04 2

2:54

Date

of iss

ue 2

012-

09-0

723

9122

_eng

_175

7385

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 20

MULTIVIPET-N-EM-136HF-3HEx nA Emergency Fluorescent Light Fitting

Dimensions (mm)

Technical dataElectrical specificationsOperating voltage 220 ... 240 V 50Hz / 60HzOperating current 0.16 ATerminal capacity 2.5 mm2 Connection block suitable for through wiringControl gear high frequency electronic ballastFitting type Ceiling light fittingLamps T26 bi-pin fluorescent tube

Number of lamps 1Length 1200 mm ( 4 ft )Power 36 W

Emergency operation maintainedOperation time 3 h

Mechanical specificationsCover fixing stainless steel snap shut fastenersProtection degree IP66Cable entry

Number of cable entries 4 x M20 2 at each endMaterial

Housing PolycarbonateLamp cover PolycarbonateReflector 0.6 mm Mild steelFinish Body: as moulded

reflector: epoxy powder coated, whiteSeal polyurethane foam

Mass approx. 3.4 kgDimensions

A 1290 mmB 119 mm

Features

• Power 36 W• Installation in Zone 2 and Zone 22• Electronic HF control gear• Suitable for 220-240V AC 50/60Hz

operation• Multiple locking points on diffuser that

can be hinged from both sides• Fast opening and closing of fitting via

snap shut fasteners• Anti-glare diffuser cover• Stainless steel surface mounting

brackets supplied as standard• Minimum of 3 hour duration in

emergency mode

A

FE

C

DB

Page 21: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-09

-04 2

2:54

Date

of iss

ue 2

012-

09-0

723

9122

_eng

_175

7385

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 21

MULTIVIPET-N-EM-136HF-3HEx nA Emergency Fluorescent Light Fitting

C 110 mmD 176 mmF 700 mm

Mounting 2 x stainless steel removable mounting bracketsGrounding Internal connectionAmbient conditionsAmbient temperature 0 ... 30 °C (32 ... 86 °F)Data for application in connection with Ex-areasEC-Type Examination Certificate FTZU 05 ATEX 0200X

Group, category, type of protection, temperature class

¬ II 3 GD Ex nA tD A II T5 T75°C

International approvalsGOST-R approval GOST-R B02432ConformityProtection degree EN 60529General informationSupplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of

Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

AccessoriesDesignation 1 x nylon non-armoured Ex e cable gland

1 x nylon Ex e sealing plug

Page 22: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-09

-04 2

2:54

Date

of iss

ue 2

012-

09-0

723

9123

_eng

_175

7386

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 22

MULTIVIPET-N-EM-236HF-3HEx nA Emergency Fluorescent Light Fitting

Dimensions (mm)

Technical dataElectrical specificationsOperating voltage 220 ... 240 V 50Hz / 60HzOperating current 0.32 ATerminal capacity 2.5 mm2 Connection block suitable for through wiringControl gear high frequency electronic ballastFitting type Ceiling light fittingLamps T26 bi-pin fluorescent tube

Number of lamps 2Length 1200 mm ( 4 ft )Power 2 x 36 W

Emergency operation maintainedOperation time 3 h

Mechanical specificationsCover fixing stainless steel snap shut fastenersProtection degree IP66Cable entry

Number of cable entries 2 x M20 1 at each endMaterial

Housing PolycarbonateLamp cover PolycarbonateReflector 0.6 mm Mild steelFinish Body: as moulded

reflector: epoxy powder coated, whiteSeal polyurethane foam

Mass approx. 4.4 kgDimensions

A 1290 mmB 173 mm

Features

• Power 2 x 36 W• Installation in Zone 2 and Zone 22• Electronic HF control gear• Suitable for 220-240V AC 50/60Hz

operation• Multiple locking points on diffuser that

can be hinged from both sides• Fast opening and closing of fitting via

snap shut fasteners• Anti-glare diffuser cover• Stainless steel surface mounting

brackets supplied as standard• Minimum of 3 hour duration in

emergency mode

C

DB

A

FE

Page 23: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-09

-04 2

2:54

Date

of iss

ue 2

012-

09-0

723

9123

_eng

_175

7386

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 23

MULTIVIPET-N-EM-236HF-3HEx nA Emergency Fluorescent Light Fitting

C 110 mmD 230 mmF 700 mm

Mounting 2 x stainless steel removable mounting bracketsGrounding Internal connectionAmbient conditionsAmbient temperature 0 ... 30 °C (32 ... 86 °F)Data for application in connection with Ex-areasEC-Type Examination Certificate FTZU 05 ATEX 0200X

Group, category, type of protection, temperature class

¬ II 3 GD Ex nA tD A II T5 T75°C

International approvalsGOST-R approval GOST-R B02432ConformityProtection degree EN 60529General informationSupplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of

Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

AccessoriesDesignation 1 x nylon non-armoured Ex e cable gland

3 x nylon Ex e sealing plugs

Page 24: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-09

-04 2

2:54

Date

of iss

ue 2

012-

09-0

723

9124

_eng

_175

7387

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 24

MULTIVIPET-N-EM-158HF-3HEx nA Emergency Fluorescent Light Fitting

Dimensions (mm)

Technical dataElectrical specificationsOperating voltage 220 ... 240 V 50Hz / 60HzOperating current 0.27 ATerminal capacity 2.5 mm2 Connection block suitable for through wiringControl gear high frequency electronic ballastFitting type Ceiling light fittingLamps T26 bi-pin fluorescent tube

Number of lamps 1Length 1500 mm ( 5 ft )Power 58 W

Emergency operation maintainedOperation time 3 h

Mechanical specificationsCover fixing stainless steel snap shut fastenersProtection degree IP66Cable entry

Number of cable entries 4 x M20 2 at each endMaterial

Housing PolycarbonateLamp cover PolycarbonateReflector 0.6 mm Mild steelFinish Body: as moulded

reflector: epoxy powder coated, whiteSeal polyurethane foam

Mass approx. 3.7 kgDimensions

A 1590 mmB 119 mm

Features

• Power 58 W• Installation in Zone 2 and Zone 22• Electronic HF control gear• Suitable for 220-240V AC 50/60Hz

operation• Multiple locking points on diffuser that

can be hinged from both sides• Fast opening and closing of fitting via

snap shut fasteners• Anti-glare diffuser cover• Stainless steel surface mounting

brackets supplied as standard• Minimum of 3 hour duration in

emergency mode

A

FE

C

DB

Page 25: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-09

-04 2

2:54

Date

of iss

ue 2

012-

09-0

723

9124

_eng

_175

7387

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 25

MULTIVIPET-N-EM-158HF-3HEx nA Emergency Fluorescent Light Fitting

C 110 mmD 176 mmF 1000 mm

Mounting 2 x stainless steel removable mounting bracketsGrounding Internal connectionAmbient conditionsAmbient temperature 0 ... 30 °C (32 ... 86 °F)Data for application in connection with Ex-areasEC-Type Examination Certificate FTZU 05 ATEX 0200X

Group, category, type of protection, temperature class

¬ II 3 GD Ex nA tD A II T5 T75°C

International approvalsGOST-R approval GOST-R B02432ConformityProtection degree EN 60529General informationSupplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of

Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

AccessoriesDesignation 1 x nylon non-armoured Ex e cable gland

1 x nylon Ex e sealing plug

Page 26: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-09

-04 2

2:54

Date

of iss

ue 2

012-

09-0

723

9125

_eng

_175

7388

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 26

MULTIVIPET-N-EM-258HF-3HEx nA Emergency Fluorescent Light Fitting

Dimensions (mm)

Technical dataElectrical specificationsOperating voltage 220 ... 240 V 50Hz / 60HzOperating current 0.51 ATerminal capacity 2.5 mm2 Connection block suitable for through wiringControl gear high frequency electronic ballastFitting type Ceiling light fittingLamps T26 bi-pin fluorescent tube

Number of lamps 2Length 1500 mm ( 5 ft )Power 2 x 58 W

Emergency operation maintainedOperation time 3 h

Mechanical specificationsCover fixing stainless steel snap shut fastenersProtection degree IP66Cable entry

Number of cable entries 4 x M20 2 at each endMaterial

Housing PolycarbonateLamp cover PolycarbonateReflector 0.6 mm Mild steelFinish Body: as moulded

reflector: epoxy powder coated, whiteSeal polyurethane foam

Mass approx. 5.3 kgDimensions

A 1590 mmB 173 mm

Features

• Power 2 x 58 W• Installation in Zone 2 and Zone 22• Electronic HF control gear• Suitable for 220-240V AC 50/60Hz

operation• Multiple locking points on diffuser that

can be hinged from both sides• Fast opening and closing of fitting via

snap shut fasteners• Anti-glare diffuser cover• Stainless steel surface mounting

brackets supplied as standard• Minimum of 3 hour duration in

emergency mode

C

DB

A

FE

Page 27: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-09

-04 2

2:54

Date

of iss

ue 2

012-

09-0

723

9125

_eng

_175

7388

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 27

MULTIVIPET-N-EM-258HF-3HEx nA Emergency Fluorescent Light Fitting

C 110 mmD 230 mmF 1000 mm

Mounting 2 x stainless steel removable mounting bracketsGrounding Internal connectionAmbient conditionsAmbient temperature 0 ... 30 °C (32 ... 86 °F)Data for application in connection with Ex-areasEC-Type Examination Certificate FTZU 05 ATEX 0200X

Group, category, type of protection, temperature class

¬ II 3 GD Ex nA tD A II T5 T75°C

International approvalsGOST-R approval GOST-R B02432ConformityProtection degree EN 60529General informationSupplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of

Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

AccessoriesDesignation 1 x nylon non-armoured Ex e cable gland

3 x nylon Ex e sealing plugs

Page 28: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-09

-04 2

2:54

Date

of iss

ue 2

012-

09-0

723

9126

_eng

_175

7389

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 28

POINTER-N-I-PC-WR-EP-211Ex nA Compact Fluorescent Bulkhead Light Fitting

Dimensions (mm)

Technical dataElectrical specificationsOperating voltage 220 ... 240 V 50Hz / 60HzOperating current 0.08 ATerminal capacity 3 x 2.5 mm2 Connection block suitable for through wiringControl gear high frequency electronic ballastFitting type Bulkhead light fittingLamps compact fluorescent lamp

Number of lamps 2Power 2 x 11 W

Mechanical specificationsCover fixing stainless steel snap shut fastenersProtection degree IP66Cable entry

Number of cable entries 4 x M20 2 at each endMaterial

Housing PolycarbonateLamp cover PolycarbonateReflector 0.6 mm Mild steelFinish Body: as moulded

reflector: epoxy powder coated, whiteSeal polyurethane foam

Mass approx. 1.2 kgDimensions

A 385 mmB 173 mmC 105 mmD 230 mmF 100 mm

Features

• Power 2 x 11 W• Installation in Zone 2 and Zone 22• Electronic HF control gear• Multiple locking points on diffuser that

can be hinged from both sides• Fast opening and closing of fitting via

snap shut fasteners• Anti-glare diffuser cover• Stainless steel surface mounting

brackets supplied as standard

C

DB

A

FE

Page 29: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-09

-04 2

2:54

Date

of iss

ue 2

012-

09-0

723

9126

_eng

_175

7389

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 29

POINTER-N-I-PC-WR-EP-211Ex nA Compact Fluorescent Bulkhead Light Fitting

Mounting 2 x stainless steel removable mounting bracketsGrounding Internal connectionAmbient conditionsAmbient temperature -20 ... 40 °C (-4 ... 104 °F)Data for application in connection with Ex-areasEC-Type Examination Certificate FTZU 02 ATEX 0144X

Group, category, type of protection, temperature class

¬ II 3 GD Ex nA tD A II T4 T87°C

ConformityProtection degree EN 60529General informationSupplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of

Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

AccessoriesDesignation 1 x nylon non-armoured Ex e cable gland

3 x nylon Ex e sealing plugs

Page 30: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-09

-04 2

2:53

Date

of iss

ue 2

012-

09-0

723

9127

_eng

_175

7390

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 30

BASET-N-I-PC-WR-111-3HEx nR Compact Fluorescent Emergency Exit Fitting

Dimensions (mm)

Technical dataElectrical specificationsOperating voltage 230 V 50HzOperating current 0.08 ATerminal capacity 3 x 2.5 mm2 Connection block suitable for through wiringControl gear high frequency electronic ballastFitting type Bulkhead light fittingLamps compact fluorescent lamp

Number of lamps 1Power 11 W

Emergency operation non-maintainedOperation time 3 h

Mechanical specificationsCover fixing stainless steel snap shut fastenersProtection degree IP66Cable entry

Number of cable entries 4 x M20 2 at each endMaterial

Housing PolycarbonateLamp cover PolycarbonateReflector 0.6 mm Mild steelFinish Body: as moulded

reflector: epoxy powder coated, whiteSeal polyurethane foam

Mass approx. 1.8 kgDimensions

A 385 mmB 173 mmC 105 mm

Features

• Power 11 W• Installation in Zone 2 and Zone 22• Electronic HF control gear• Multiple locking points on diffuser that

can be hinged from both sides• Fast opening and closing of fitting via

snap shut fasteners• Anti-glare diffuser cover• Stainless steel surface mounting

brackets supplied as standard• Minimum of 3 hour duration in

emergency mode• LED status indication

C

DB

A

FE

Page 31: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-09

-04 2

2:53

Date

of iss

ue 2

012-

09-0

723

9127

_eng

_175

7390

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 31

BASET-N-I-PC-WR-111-3HEx nR Compact Fluorescent Emergency Exit Fitting

D 230 mmF 100 mm

Mounting 2 x stainless steel removable mounting bracketsGrounding Internal connectionAmbient conditionsAmbient temperature 0 ... 30 °C (32 ... 86 °F)Data for application in connection with Ex-areasEC-Type Examination Certificate FTZU 04 ATEX 0219X

Group, category, type of protection, temperature class

¬ II 3 GD Ex nR tD A II T6 T45°C

ConformityProtection degree EN 60529General informationSupplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of

Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

AccessoriesDesignation 1 x nylon non-armoured Ex e cable gland

3 x nylon Ex e sealing plugs

Page 32: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-08

-15 1

8:41

Date

of iss

ue 2

012-

09-0

7t15

4633

_eng

_175

7391

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 32

BASET-N-I-PC-WR-109-3HEx nR Compact Fluorescent Emergency Exit Fitting

Dimensions (mm)

Technical dataElectrical specificationsOperating voltage 230 V 50HzOperating current 0.08 ATerminal capacity 3 x 2.5 mm2 Connection block suitable for through wiringControl gear high frequency electronic ballastFitting type Bulkhead light fittingLamps compact fluorescent lamp

Number of lamps 1Power 9 W

Emergency operation non-maintainedOperation time 3 h

Mechanical specificationsCover fixing stainless steel snap shut fastenersProtection degree IP66Cable entry

Number of cable entries 4 x M20 2 at each endMaterial

Housing PolycarbonateLamp cover PolycarbonateReflector 0.6 mm Mild steelFinish Body: as moulded

reflector: epoxy powder coated, whiteSeal polyurethane foam

Mass approx. 1.8 kgDimensions

A 385 mmB 173 mmC 105 mm

Features

• Power 9 W• Installation in Zone 2 and Zone 22• Electronic HF control gear• Multiple locking points on diffuser that

can be hinged from both sides• Fast opening and closing of fitting via

snap shut fasteners• Anti-glare diffuser cover• Stainless steel surface mounting

brackets supplied as standard• Minimum of 3 hour duration in

emergency mode• LED status indication

C

DB

A

FE

Page 33: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Relea

se da

te 20

12-08

-15 1

8:41

Date

of iss

ue 2

012-

09-0

7t15

4633

_eng

_175

7391

.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 33

BASET-N-I-PC-WR-109-3HEx nR Compact Fluorescent Emergency Exit Fitting

D 230 mmF 100 mm

Mounting 2 x stainless steel removable mounting bracketsGrounding Internal connectionAmbient conditionsAmbient temperature 0 ... 30 °C (32 ... 86 °F)Data for application in connection with Ex-areasEC-Type Examination Certificate FTZU 04 ATEX 0219X

Group, category, type of protection, temperature class

¬ II 3 GD Ex nR tD A II T6 T45°C

ConformityProtection degree EN 60529General informationSupplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of

Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

AccessoriesDesignation 1 x nylon non-armoured Ex e cable gland

3 x nylon Ex e sealing plugs

Page 34: Lighting The Way - Fluorescent Lighting For Zone 2 And 22 · Pepperl+Fuchs offers a wide range of fluorescent lighting suitable for installation in Zone 2 and 22 hazardous area locations.

Subject to modificationsCopyright Pepperl+Fuchs

www.pepperl-fuchs.com

Northern Europe HeadquartersPepperl+Fuchs GB Ltd. Oldham · EnglandTel. +44 161 6336431E-Mail: [email protected]

For the Pepperl+Fuchs representative closest to you check www.pepperl-fuchs.com/pfcontact

PROCESS AUTOMATION – PROTECTING YOUR PROCESS

For over a half century, Pepperl+Fuchs has been continually providing new concepts for the world of process automation. Our company sets standards in quality and innovative technology. We develop, produce and distribute electronic interfacemodules, Human-Machine Interfaces and hazardous location protection equipment on a global scale, meeting the most deman-ding needs of industry. Resulting from our world-wide presence and our high flexibility in production and customer service, we are able to individually offer complete solutions – wherever and whenever you need us. We are the recognized experts in our technologies – Pepperl+Fuchs has earned a strong reputation by supplying the world’s largest process industry companies with the broadest line of proven components for a diverse range of applications.