    Lighting Desing for Electrical Engineering Seminar Room

    Partner for Contact:Order No.: Assignment 01Company: EE DepartmentCustomer No.: 001

    Date: 28.05.2012Operator: P.A.T.I.Jayanatha

  • 8/13/2019 lightening design

    2/15

    Lighting Desing for Electrical Engineering Seminar Ro

    28.05.2012

    University of Moratuwa

    Katubedda

    Operator P.A.T.I.JayanathaTelephone 0712383303

    Faxe-Mail [email protected]

    Table of contents

    Lighting Desing for Electrical Engineering Seminar RoomProject Cover 1Table of contents 2Luminaire parts list 3EAE 41288 JR2 4*C6T-WL/DF

    Luminaire Data Sheet 4OSRAM 4050300774237 72086 LUMILUX DUO EL-F/P 2x36W

    Luminaire Data Sheet 5Seminar Room with flourescent

    Input Protocol 6Luminaires (layout plan) 7

    Photometric Results 83D Rendering 9Room Surfaces

    WorkplaneIsolines (E) 10

    Seminar Room with LEDInput Protocol 11Luminaires (layout plan) 12Photometric Results 133D Rendering 14Room Surfaces

    WorkplaneIsolines (E) 15

    Page 2

    Discussion 16

  • 8/13/2019 lightening design

    3/15

    Lighting Desing for Electrical Engineering Seminar Ro

    28.05.2012

    University of Moratuwa

    Katubedda

    Operator P.A.T.I.JayanathaTelephone 0712383303

    Faxe-Mail [email protected]

    Lighting Desing for Electrical Engineering Seminar Room / Luminaire parts list

    20 Pieces EAE 41288 JR2 4*C6T-WL/DFArticle No.: 41288Luminous flux (Luminaire): 2205 lmLuminous flux (Lamps): 2475 lmLuminaire Wattage: 28.0 WLuminaire classification according to CIE: 100CIE flux code: 52 82 96 100 89Fitting: 450 x SMD LED (Correction Factor1.000).

    15 Pieces OSRAM 4050300774237 72086 LUMILUX DUO

    EL-F/P 2x36WArticle No.: 4050300774237Luminous flux (Luminaire): 3419 lmLuminous flux (Lamps): 6700 lmLuminaire Wattage: 72.0 WLuminaire classification according to CIE: 88CIE flux code: 43 72 90 88 51Fitting: 2 x L36W/830 (Correction Factor 1.000).

    Page 3

  • 8/13/2019 lightening design

    4/15

    Lighting Desing for Electrical Engineering Seminar Ro

    28.05.2012

    University of Moratuwa

    Katubedda

    Operator P.A.T.I.JayanathaTelephone 0712383303

    Faxe-Mail [email protected]

    EAE 41288 JR2 4*C6T-WL/DF / Luminaire Data Sheet

    Luminous emittance 1:

    200

    300

    400

    cd/klm 89%C0 - C180 C90 - C270

    0 15 30

    45

    60

    75

    90

    105105

    90

    75

    60

    45

    30 15 0

    Luminaire classification according to CIE: 100CIE flux code: 52 82 96 100 89

    Luminous emittance 1:

    Glare Evaluation According to UGR

    Ceiling 70 70 50 50 30 70 70 50 50 30

    Walls 50 30 50 30 30 50 30 50 30 30

    Floor 20 20 20 20 20 20 20 20 20 20

    Room SizeX Y

    Viewing direction at right anglesto lamp axis

    Viewing direction parallelto lamp axis

    2H 2H 14.8 16.0 15.1 16.3 16.5 15.1 16.4 15.4 16.6 16.9

    3H 16.3 17.4 16.6 17.7 18.0 16.7 17.8 17.0 18.1 18.3

    4H 16.9 18.0 17.2 18.2 18.5 17.2 18.3 17.5 18.6 18.9

    6H 17.3 18.3 17.7 18.6 18.9 17.6 18.6 18.0 18.9 19.2

    8H 17.5 18.5 17.9 18.8 19.1 17.8 18.7 18.1 19.0 19.3

    12H 17.7 18.6 18.1 18.9 19.3 17.9 18.8 18.2 19.1 19.4

    4H 2H 15.3 16.4 15.6 16.7 16.9 15.6 16.7 15.9 17.0 17.2

    3H 17.1 18.0 17.4 18.3 18.6 17.3 18.3 17.7 18.6 18.9

    4H 17.8 18.6 18.2 18.9 19.3 18.1 18.9 18.5 19.2 19.6

    6H 18.4 19.1 18.8 19.5 19.9 18.6 19.3 19.0 19.7 20.1

    8H 18.7 19.3 19.1 19.7 20.1 18.8 19.4 19.2 19.8 20.3

    12H 18.9 19.5 19.3 19.9 20.3 19.0 19.5 19.4 19.9 20.4

    8H 4H 18.1 18.7 18.5 19.1 19.5 18.3 19.0 18.7 19.4 19.8

    6H 18.8 19.4 19.3 19.8 20.2 19.0 19.5 19.5 20.0 20.4

    8H 19.2 19.7 19.7 20.1 20.6 19.3 19.8 19.8 20.2 20.7

    12H 19.5 19.9 20.0 20.4 20.9 19.5 19.9 20.0 20.4 20.9

    12H 4H 18.1 18.7 18.5 19.1 19.5 18.3 18.9 18.8 19.3 19.86H 18.9 19.4 19.4 19.8 20.3 19.1 19.5 19.5 20.0 20.5

    8H 19.3 19.7 19.8 20.2 20.7 19.4 19.8 19.9 20.3 20.8

    Variation of the observer position for the luminaire distances S

    S = 1.0H +0.1 / -0.2 +0.1 / -0.2

    S = 1.5H +0.3 / -0.5 +0.2 / -0.4

    S = 2.0H +0.5 / -0.8 +0.5 / -0.8

    Standard table BK05 BK05

    CorrectionSummand

    -1.8 -1.6

    Corrected Glare Indices referring to 2475lm Total Luminous F lux

    Page 4

  • 8/13/2019 lightening design

    5/15

    Lighting Desing for Electrical Engineering Seminar Ro

    28.05.2012

    University of Moratuwa

    Katubedda

    Operator P.A.T.I.JayanathaTelephone 0712383303

    Faxe-Mail [email protected]

    OSRAM 4050300774237 72086 LUMILUX DUO EL-F/P 2x36W / Luminaire Data Sheet

    Luminous emittance 1:

    80

    120

    160

    cd/klm 51%C0 - C180 C90 - C270

    0 15 30 45

    60

    75

    90

    105

    120

    135150165180165150135

    120

    105

    90

    75

    60

    45 30 15 0

    Luminaire classification according to CIE: 88CIE flux code: 43 72 90 88 51

    LUMILUX DUO EL-F/P;LUMILUX DUO EL-F/P are electronic surface-mounted luminaires with an extremely low profile. The two-lamp designmakes them suitable for applications that require high lightinglevels.;Extremely low-profile luminaire for fixed connection;High-qualityluminaire casing made from anodized aluminum;With prismatic lamp coverfor uniform light;With QTP Electronic Control Gear;Equipped with twoLUMILUX T8 830 fluorescent lamps; IP20, IK05, Light color 830, 230-240 V,50-60 Hz, G13 base

    Due to missing symmetry properties, no UGR tablecan be displayed for this luminaire.

    Page 5

  • 8/13/2019 lightening design

    6/15

    Lighting Desing for Electrical Engineering Seminar Ro

    28.05.2012

    University of Moratuwa

    Katubedda

    Operator P.A.T.I.JayanathaTelephone 0712383303

    Faxe-Mail [email protected]

    Seminar Room with flourescent / Input Protocol

    Height of working plane: 0.760 mBoundary Zone: 0.500 m

    Maintenance factor: 0.80

    Height of Room: 4.000 mGround area: 128.00 m

    1 2

    34

    Surface Rho [%] from ( [m] | [m] ) towards ( [m] | [m] ) Length [m]

    Floor 52 / / /

    Ceiling 83 / / /

    Wall 1 21 ( 0.000 | 0.000 ) ( 16.000 | 0.000 ) 16.000

    Wall 2 45 ( 16.000 | 0.000 ) ( 16.000 | 8.000 ) 8.000

    Wall 3 78 ( 16.000 | 8.000 ) ( 0.000 | 8.000 ) 16.000

    Wall 4 21 ( 0.000 | 8.000 ) ( 0.000 | 0.000 ) 8.000

    Page 6

  • 8/13/2019 lightening design

    7/15

    Lighting Desing for Electrical Engineering Seminar Ro

    28.05.2012

    University of Moratuwa

    Katubedda

    Operator P.A.T.I.JayanathaTelephone 0712383303

    Faxe-Mail [email protected]

    Seminar Room with flourescent / Luminaires (layout plan)

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    16.00 m0.00 1.60 4.80 8.00 11.20 14.40

    8.00 m

    0.00

    1.33

    4.00

    6.67

    Scale 1 : 115

    Luminaire Parts List

    No. Pieces Designation

    1 15 OSRAM 4050300774237 72086 LUMILUX DUO EL-F/P 2x36W

    Page 7

  • 8/13/2019 lightening design

    8/15

    Lighting Desing for Electrical Engineering Seminar Ro

    28.05.2012

    University of Moratuwa

    Katubedda

    Operator P.A.T.I.JayanathaTelephone 0712383303

    Faxe-Mail [email protected]

    Seminar Room with flourescent / Photometric Results

    Total Luminous Flux: 51288 lmTotal Load: 1080.0 WMaintenance factor: 0.80Boundary Zone: 0.500 m

    Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m]direct indirect total

    Workplane 168 96 264 / /

    Floor 139 95 234 52 39

    Ceiling 0.00 108 108 83 29

    Wall 1 108 107 216 21 14

    Wall 2 73 106 179 45 26

    Wall 3 109 99 208 78 52

    Wall 4 68 103 171 21 11

    Uniformity on the working planeu0: 0.625 (1:2)Emin/ Emax: 0.531 (1:2)

    Illuminance Quotient (according to LG7): Walls / Working Plane: 0.779, Ceiling / Working Plane: 0.410.

    Specific connected load: 8.44 W/m = 3.20 W/m/100 lx (Ground area: 128.00 m)

    Page 8

  • 8/13/2019 lightening design

    9/15

    Lighting Desing for Electrical Engineering Seminar Ro

    28.05.2012

    University of Moratuwa

    Katubedda

    Operator P.A.T.I.JayanathaTelephone 0712383303

    Faxe-Mail [email protected]

    Seminar Room with flourescent / 3D Rendering

    Page 9

  • 8/13/2019 lightening design

    10/15

    Lighting Desing for Electrical Engineering Seminar Ro

    28.05.2012

    University of Moratuwa

    Katubedda

    Operator P.A.T.I.JayanathaTelephone 0712383303

    Faxe-Mail [email protected]

    Seminar Room with flourescent / Workplane / Isolines (E)

    210

    240

    240

    240 240

    240

    240

    240

    240

    270

    270 270 270 270

    270

    270270

    300

    300

    300

    300

    300

    300300

    300

    300 300

    300

    300300

    16.00 m0.00

    8.00 m

    0.00

    0.50

    7.50

    Values in Lux, Scale 1 : 115Position of surface in room:Working plane with 0.500 m

    Boundary ZoneMarked point:(0.500 m, 0.500 m, 0.760 m)

    Grid: 128 x 64 Points

    Eav[lx] Emin[lx] Emax[lx] u0 Emin/ Emax264 165 310 0.625 0.531

    Page 10

  • 8/13/2019 lightening design

    11/15

    Lighting Desing for Electrical Engineering Seminar Ro

    28.05.2012

    University of Moratuwa

    Katubedda

    Operator P.A.T.I.JayanathaTelephone 0712383303

    Faxe-Mail [email protected]

    Seminar Room with LED / Input Protocol

    Height of working plane: 0.760 mBoundary Zone: 0.500 m

    Maintenance factor: 0.80

    Height of Room: 4.000 mGround area: 128.00 m

    1 2

    34

    Surface Rho [%] from ( [m] | [m] ) towards ( [m] | [m] ) Length [m]

    Floor 52 / / /

    Ceiling 83 / / /

    Wall 1 21 ( 0.000 | 0.000 ) ( 16.000 | 0.000 ) 16.000

    Wall 2 72 ( 16.000 | 0.000 ) ( 16.000 | 8.000 ) 8.000

    Wall 3 78 ( 16.000 | 8.000 ) ( 0.000 | 8.000 ) 16.000

    Wall 4 21 ( 0.000 | 8.000 ) ( 0.000 | 0.000 ) 8.000

    Page 11

  • 8/13/2019 lightening design

    12/15

    Lighting Desing for Electrical Engineering Seminar Ro

    28.05.2012

    University of Moratuwa

    Katubedda

    Operator P.A.T.I.JayanathaTelephone 0712383303

    Faxe-Mail [email protected]

    Seminar Room with LED / Luminaires (layout plan)

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    16.00 m0.00 1.60 4.80 8.00 11.20 14.40

    8.00 m

    0.00

    1.00

    3.00

    5.00

    7.00

    Scale 1 : 115

    Luminaire Parts List

    No. Pieces Designation

    1 20 EAE 41288 JR2 4*C6T-WL/DF

    Page 12

  • 8/13/2019 lightening design

    13/15

  • 8/13/2019 lightening design

    14/15

  • 8/13/2019 lightening design

    15/15

    Lighting Desing for Electrical Engineering Seminar Ro

    28.05.2012

    University of Moratuwa

    Katubedda

    Operator P.A.T.I.JayanathaTelephone 0712383303

    Faxe-Mail [email protected]

    Seminar Room with LED / Workplane / Isolines (E)

    240

    280

    280

    280280 280

    280

    320

    320

    320 320320

    320

    320

    320320320

    320

    16.00 m0.00

    8.00 m

    0.00

    0.50

    7.50

    Values in Lux, Scale 1 : 115Position of surface in room:Working plane with 0.500 m

    Boundary ZoneMarked point:(0.500 m, 0.500 m, 0.760 m)

    Grid: 64 x 32 Points

    Eav[lx] Emin[lx] Emax[lx] u0 Emin/ Emax297 181 346 0.610 0.522

    P 15