Renuka Sagar HaldiaDate: 15-03-2011Customer: RENUKA SAGAR HALDIA
Description: THE DESIGN IS AS PER REQUIREMENT OF THE CLIENT.
LIST OF DEVIATIONS :
1> ARRANGEMENT OF POLE = TWIN CENTRAL
2> CONSIDERED HEIGHT OF POLE = 7.5M
3> POLE TO POLE SPACING = 15M
4> AVARAGE ILLUMINANCE LEVEL ACHIEVED= 16.8 LUX
CalcuLuX Road 7.5.0.1
7 J C M ROAD,KOLKATA-700 020PHILIPS ELECTRONICS INDIA LIMITED
The nominal values shown in this report are the result of precision calculations, based upon precisely positioned luminaires in a fixed relationship to each other and to the area under examination. In practice the values may vary due to tolerances on luminaires, luminairepositioning, reflection properties and electrical supply.
PDF created with pdfFactory trial version www.pdffactory.com
![Page 2: Light Illumination Calculation](https://reader036.fdocuments.us/reader036/viewer/2022080506/577cc9a31a28aba711a4443a/html5/thumbnails/2.jpg)
Renuka Sagar Haldia PHILIPS ELECTRONICS INDIA LIMITEDDate: 15-03-2011
Table of Contents
1. Project Description 3
1.1 3-D Project Overview 31.2 Top Project Overview 41.3 Front Project Overview 5
2. Overview of Schemes 6
3. Summary 7
3.1 Main Road 7
4. Calculation Results 8
4.1 Main Eh: Textual Table 84.2 Main Eh: Graphical Table 94.3 Main Eh: Iso Contour 104.4 Main Eh: Filled Iso Contour 114.5 Main Eh: Mountain Plot 12
5. Luminaire Details 13
5.1 Project Luminaires 13
Philips Lighting B.V. - CalcuLuX Road 7.5.0.1 Page: 2/13
PDF created with pdfFactory trial version www.pdffactory.com
![Page 3: Light Illumination Calculation](https://reader036.fdocuments.us/reader036/viewer/2022080506/577cc9a31a28aba711a4443a/html5/thumbnails/3.jpg)
Renuka Sagar Haldia PHILIPS ELECTRONICS INDIA LIMITEDDate: 15-03-2011
1. Project Description
1.1 3-D Project Overview
B BRP320 1X24LED-HP/CW PS
B
B
BBBBBBB
B
B
BBBBBBB
X
YZ
Philips Lighting B.V. - CalcuLuX Road 7.5.0.1 Page: 3/13
PDF created with pdfFactory trial version www.pdffactory.com
![Page 4: Light Illumination Calculation](https://reader036.fdocuments.us/reader036/viewer/2022080506/577cc9a31a28aba711a4443a/html5/thumbnails/4.jpg)
Renuka Sagar Haldia PHILIPS ELECTRONICS INDIA LIMITEDDate: 15-03-2011
1.2 Top Project Overview
B BRP320 1X24LED-HP/CW PS
-2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
X(m)
-2-1
01
23
45
67
89
1011
1213
1415
1617
Y(m
)
B
B
B
B
Scale1:100
Philips Lighting B.V. - CalcuLuX Road 7.5.0.1 Page: 4/13
PDF created with pdfFactory trial version www.pdffactory.com
![Page 5: Light Illumination Calculation](https://reader036.fdocuments.us/reader036/viewer/2022080506/577cc9a31a28aba711a4443a/html5/thumbnails/5.jpg)
Renuka Sagar Haldia PHILIPS ELECTRONICS INDIA LIMITEDDate: 15-03-2011
1.3 Front Project Overview
B BRP320 1X24LED-HP/CW PS
-2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
X(m)
-5-4
-3-2
-10
12
34
56
78
910
1112
13Z(
m)
BBBBBBBBBBBBB BBBBBBBBBBBBB
Scale1:100
Philips Lighting B.V. - CalcuLuX Road 7.5.0.1 Page: 5/13
PDF created with pdfFactory trial version www.pdffactory.com
![Page 6: Light Illumination Calculation](https://reader036.fdocuments.us/reader036/viewer/2022080506/577cc9a31a28aba711a4443a/html5/thumbnails/6.jpg)
Renuka Sagar Haldia PHILIPS ELECTRONICS INDIA LIMITEDDate: 15-03-2011
2. Overview of Schemes
The overall maintenance factor used for this project is 0.70.
Main Field grid is based on the CEN Luminance grid method.
CodeB
Luminaire TypeLuminaire TypeBRP320 1X24LED-HP/CW PSU
Lamp TypeLamp Type1 * 24 LED
Power (W)Power (W) 43.1
Flux (lm)Flux (lm)1 * 3493
UnitCarriagewayCentral Reserve mRoad Width mNumber of LanesReflection TableQ0 of TableMaintenance FactorLuminaire CodeInstallationHeight mSpacing mOverhang mTilt90 degEh ave luxEh min luxEh max luxEh min/maxEh min/ave
Scheme 1Scheme 1Dual Carriageway
0.756.001
CIE C20.0700.70
BTwin Central
7.5015.000.505.0
16.8 13.2 21.6
0.610.79
Philips Lighting B.V. - CalcuLuX Road 7.5.0.1 Page: 6/13
PDF created with pdfFactory trial version www.pdffactory.com
![Page 7: Light Illumination Calculation](https://reader036.fdocuments.us/reader036/viewer/2022080506/577cc9a31a28aba711a4443a/html5/thumbnails/7.jpg)
Renuka Sagar Haldia PHILIPS ELECTRONICS INDIA LIMITEDDate: 15-03-2011
3. Summary
3.1 Main Road
Luminaire Type : BRP320 1X24LED-HP/CW PSULamp Type : 1 * 24 LEDLamp Flux : 3493 lumenTilt90 (T) : 5.0 degGrid Method : CEN LuminanceProject Maintenance Factor : 0.70
T
O
H
WW C
S
Carriageway : Dual CarriagewayCentral Reserve (C) : 0.75 mRoad Width (W) : 6.00 mNumber of Lanes : 1Reflection Table : CIE C2Q0 of Table : 0.070Maintenance Factor : 0.70Installation : Twin CentralHeight (H) : 7.50 mSpacing (S) : 15.00 mOverhang (O) : 0.50 m
Overall quality figures for the above road scheme.
Horizontal IlluminanceAverage = 16.8 luxMinimum = 13.2 luxMaximum = 21.6 luxMinimum/Maximum = 0.61Minimum/Average = 0.79
Philips Lighting B.V. - CalcuLuX Road 7.5.0.1 Page: 7/13
PDF created with pdfFactory trial version www.pdffactory.com
![Page 8: Light Illumination Calculation](https://reader036.fdocuments.us/reader036/viewer/2022080506/577cc9a31a28aba711a4443a/html5/thumbnails/8.jpg)
Renuka Sagar Haldia PHILIPS ELECTRONICS INDIA LIMITEDDate: 15-03-2011
4. Calculation Results
4.1 Main Eh: Textual Table
Grid : Main at Z = -0.00 mCalculation : Horizontal Illuminance (lux)
Average Minimum Maximum Min/Ave Min/Max Project maintenance factor 16.8 13.2 21.6 0.79 0.61 0.70
X (m) 1.00 3.00 5.00 Y (m)
14.25 16 19 21
12.75 16 18 21
11.25 15 17 19
9.75 14 15 17
8.25 13 14 16
6.75 13< 14 16
5.25 14 15 17
3.75 15 17 18
2.25 16 19 21
0.75 16 19 22>
Philips Lighting B.V. - CalcuLuX Road 7.5.0.1 Page: 8/13
PDF created with pdfFactory trial version www.pdffactory.com
![Page 9: Light Illumination Calculation](https://reader036.fdocuments.us/reader036/viewer/2022080506/577cc9a31a28aba711a4443a/html5/thumbnails/9.jpg)
Renuka Sagar Haldia PHILIPS ELECTRONICS INDIA LIMITEDDate: 15-03-2011
4.2 Main Eh: Graphical Table
Grid : Main at Z = -0.00 mCalculation : Horizontal Illuminance (lux)
Average Minimum Maximum Min/Ave Min/Max Project maintenance factor 16.8 13.2 21.6 0.79 0.61 0.70
B BRP320 1X24LED-HP/CW PS
-5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11
X(m)
-10
12
34
56
78
910
1112
1314
1516
Y(m
)
B
B
B
B
21
21
19
17
16
16
17
18
21
22
19
18
17
15
14
14
15
17
19
19
16
16
15
14
13
13
14
15
16
16
Scale1:100
Philips Lighting B.V. - CalcuLuX Road 7.5.0.1 Page: 9/13
PDF created with pdfFactory trial version www.pdffactory.com
![Page 10: Light Illumination Calculation](https://reader036.fdocuments.us/reader036/viewer/2022080506/577cc9a31a28aba711a4443a/html5/thumbnails/10.jpg)
Renuka Sagar Haldia PHILIPS ELECTRONICS INDIA LIMITEDDate: 15-03-2011
4.3 Main Eh: Iso Contour
Grid : Main at Z = -0.00 mCalculation : Horizontal Illuminance (lux)
Average Minimum Maximum Min/Ave Min/Max Project maintenance factor 16.8 13.2 21.6 0.79 0.61 0.70
B BRP320 1X24LED-HP/CW PS
-5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11
X(m)
-10
12
34
56
78
910
1112
1314
1516
Y(m
)
14
16
16
16
18
18
20
20
B
B
B
B
Scale1:100
Philips Lighting B.V. - CalcuLuX Road 7.5.0.1 Page: 10/13
PDF created with pdfFactory trial version www.pdffactory.com
![Page 11: Light Illumination Calculation](https://reader036.fdocuments.us/reader036/viewer/2022080506/577cc9a31a28aba711a4443a/html5/thumbnails/11.jpg)
Renuka Sagar Haldia PHILIPS ELECTRONICS INDIA LIMITEDDate: 15-03-2011
4.4 Main Eh: Filled Iso Contour
Grid : Main at Z = -0.00 mCalculation : Horizontal Illuminance (lux)
Average Minimum Maximum Min/Ave Min/Max Project maintenance factor 16.8 13.2 21.6 0.79 0.61 0.70
B BRP320 1X24LED-HP/CW PS
20
18
16
14
-3 -2 -1 0 1 2 3 4 5 6 7 8 9
X(m)
-10
12
34
56
78
910
1112
1314
1516
Y(m
)
B
B
B
B
Scale1:100
Philips Lighting B.V. - CalcuLuX Road 7.5.0.1 Page: 11/13
PDF created with pdfFactory trial version www.pdffactory.com
![Page 12: Light Illumination Calculation](https://reader036.fdocuments.us/reader036/viewer/2022080506/577cc9a31a28aba711a4443a/html5/thumbnails/12.jpg)
Renuka Sagar Haldia PHILIPS ELECTRONICS INDIA LIMITEDDate: 15-03-2011
4.5 Main Eh: Mountain Plot
Grid : Main at Z = -0.00 mCalculation : Horizontal Illuminance (lux)
Average Minimum Maximum Min/Ave Min/Max Project maintenance factor 16.8 13.2 21.6 0.79 0.61 0.70
-0
2
4
6
X(m)
0
2
4
6
8
10
12
14
16
Y(m)
Philips Lighting B.V. - CalcuLuX Road 7.5.0.1 Page: 12/13
PDF created with pdfFactory trial version www.pdffactory.com
![Page 13: Light Illumination Calculation](https://reader036.fdocuments.us/reader036/viewer/2022080506/577cc9a31a28aba711a4443a/html5/thumbnails/13.jpg)
Renuka Sagar Haldia PHILIPS ELECTRONICS INDIA LIMITEDDate: 15-03-2011
5. Luminaire Details
5.1 Project Luminaires
BRP320 1X24LED-HP PSU 1x24 LED
Light output ratios DLOR : 1.00 ULOR : 0.00 TLOR : 1.00Lamp flux : 3493 lmLuminaire wattage : 43.1 WMeasurement code : LVNS198
Note: Luminaire data not from database.
750
0o 30o30o
60o 60o
90o 90o
120o 120o150o 150o180o
C = 180o C = 0o C = 270o C = 90o C = 340o Imax C = 160o
Luminous Intensity Diagram (candela/1000 lumen)
Philips Lighting B.V. - CalcuLuX Road 7.5.0.1 Page: 13/13
PDF created with pdfFactory trial version www.pdffactory.com