Liebert TVSS: The First Line of Defense - Product Overvie · Liebert TVSS: The First Line of...
Transcript of Liebert TVSS: The First Line of Defense - Product Overvie · Liebert TVSS: The First Line of...
Liebert TVSS: The First Liebert TVSS: The First Line of Defense Line of Defense --Product OverviewProduct OverviewJim Tiesi
3Company ConfidentialJanuary 21, 2005
Board Meeting
True modular design
Low impedance copper conduction plates
Best in class performance
Real-time status
Built-in test capability
Stringent third party testing
Warranty: 10 year
Overall DesignOverall DesignOverall Design
4Company ConfidentialJanuary 21, 2005
Board Meeting
NEMA 4 w/status mounted behind protected window
Black, textured paint, silk-screened
Status label includes pushbutton to operate Audible, Push to Test, BIT, and Counter Reset
EnclosureEnclosureEnclosure
5Company ConfidentialJanuary 21, 2005
Board Meeting
Copper InteriorCopper InteriorCopper InteriorLow impedance copper
conduction plates
Copper back plane
Maximizes surface area
High mechanical strength
Heavy duty tin plated copper lugs
Conductor sizes to # 1/0AWG
6Company ConfidentialJanuary 21, 2005
Board Meeting
Rotary Disconnect (Fused)Rotary Disconnect (Fused)Rotary Disconnect (Fused)Lock off-able safety feature
Extremely low impedance
Heavy duty industrial quality
Tin plated copper lugs and conductor surfaces
True “through door” disconnect for NEMA 4 rating
7Company ConfidentialJanuary 21, 2005
Board Meeting
CapacitorsCapacitorsCapacitors30 microfarad total capacitance;
highest in industry
Great ring-wave attenuation
EMI / RFI filtering
–100kHz: 41 dB
–10MHz: 35 dB
–1 MHz: 31 dB
–100MHz: 53 dB
8Company ConfidentialJanuary 21, 2005
Board Meeting
Surge ModuleSurge ModuleSurge ModuleMOV
Custom, Durez coated, 25 mm MOVs
– MOV surge capability 18 kA
Array of 7 MOVs per module matchedto +/- 1 volt
Fusing
Component level, coordinated fusing
99.9% pure, silver link fuse
200 kAIC rating
individual fuse links w/ monitoring on all modes
9Company ConfidentialJanuary 21, 2005
Board Meeting
Protection RedundancyProtection RedundancyProtection Redundancy
Industry Typical Phase Conductor
NEUTRAL / GROUND
30 kA 18 kA 18 18 18 18 18 18 kA
Reality 30 kA 125 kA Reality
18 18 18 18 18 18 18 kA 18 18 18 18 18 18 18 kA
Fuse Link
MOV
WEAK
No Weak Links
10Company ConfidentialJanuary 21, 2005
Board Meeting
Surge ModuleSurge ModuleSurge ModuleSurge Ratings
80 kA, 100 kA, and 125 kA modules
Independent surge current testing by R&B Labs
Flexible per phase kA ratings from 160 kA to 1000 kA
Endurance testing / 15,000 category C3 impulses < 1.5% degradation
Approved for direct bus connections
11Company ConfidentialJanuary 21, 2005
Board Meeting
Internal and external LEDsAudible alarmForm C contactsBuilt-in-Test feature
Self check logic bussTests each fuse/MOV in every
module L-N, L-G, N-G% protection per phase
Undervoltage detectionPhase loss monitoring
Unit StatusUnit StatusUnit Status
12Company ConfidentialJanuary 21, 2005
Board Meeting
NEMA LS 1 Test PackageNEMA LS 1 Test PackageNEMA LS 1 Test PackageHigh current abnormal over-voltage test (AIC Rating)
Maximum continuous operating voltage (MCOV)
Surge current test
UL 1449 suppressed voltage rating (SVR)
Frequency response curve
UL 1449 authorization
Endurance testing
13Company ConfidentialJanuary 21, 2005
Board Meeting
SIxxxyyyYARSE
Surge Rating016 (160kA)025 (250kA)032 (320kA)040 (400kA)050 (500kA)060 (600kA)075 (750kA)
100 (1000kA)
N = Single Phase L-NL = Single Phase L-LS = Split PhaseD = 3-Phase DeltaY = 3-Phase WyeH = 3-Ph Delta Hi-leg
SourceConfiguration
ProtectionModesA = All
Connection OptionsR = With DisconnectN = Wire Lug
Voltage120208220230240277480
Monitoring OptionsS = StdC = 1 CounterD = Dual Counter
Enclosure OptionsE = NEMA 4(Std)N = Caseless
Liebert Interceptor II Series Model NumberLiebert Interceptor II Series Model Liebert Interceptor II Series Model NumberNumber
14Company ConfidentialJanuary 21, 2005
Board Meeting
UL 1449, UL 1283, CE, and CUL
UL rated 200kAIC fuse network
160 kA to 1,000 kA /Phase surge capacity
Independent Test Pkg. Nema LS1
Unmatched levels of redundancy
Summary: Liebert Interceptor II Series Summary: Liebert Interceptor II Series Summary: Liebert Interceptor II Series
Ideal protection for service entrance and distribution
15Company ConfidentialJanuary 21, 2005
Board Meeting
Protection for service entrances less than 1200 amperes and distribution
panelsUL 1449, UL 1283, OWHX and CUL Listed
ACV models offer 65 kA per mode/ 130kA/ phase surge current capacity
ACVII models offer 80 kA per mode/ 160kA/ phase surge current capacity
UL Rated 200 kAIC fuse network
NEMA LS 1
Liebert AccuVar SeriesLiebertLiebert AccuVarAccuVar SeriesSeries
16Company ConfidentialJanuary 21, 2005
Board Meeting
Life cycle rating Category C3 Impulses ACV 6,000 per mode/12,000/ phase ACVII 8,000 per mode/16,000/ phase
Compact module design - easily retrofits on panelboards
Flush mount kit
On-line monitoring in all modes
EMI/RFI filtering option
Any modes of protection available
Enclosure NEMA 4X
Warranty: 10 year
Liebert AccuVar SeriesLiebertLiebert AccuVarAccuVar SeriesSeries
17Company ConfidentialJanuary 21, 2005
Board Meeting
ACVxxxY101RKE
ACV = 65 kA ModulesACVII = 80 kA Modules
Voltage120240277208480
N = Single PhaseS = Split PhaseD = 3-Phase DeltaY = 3-Phase Wye
SourceConfiguration
Surge Protection Modes1xx = L-L or L-Nx1x = L-Gxx1 = N-GAnd Number of Modulese.g. 201
OptionsR = Red/Green LEDK = Form C ContactE = EMI Filter
Liebert AccuVar Series Model NumberLiebert Liebert AccuVarAccuVar Series Model NumberSeries Model Number
Note: Note: New RatingsNew Ratings
18Company ConfidentialJanuary 21, 2005
Board Meeting
Designed specifically for the needs of the telecommunications
industryTrue hybrid - integrates response time of SAD’s
with the high-energy capability of the Interceptor MOV design
Industry’s only Active Disconnect System Surge
Surge current ratings from 50 kA to 750 kA per phase
Liebert Interceptor Hybrid AdvantageLiebert Interceptor Hybrid AdvantageLiebert Interceptor Hybrid Advantage
19Company ConfidentialJanuary 21, 2005
Board Meeting
Interceptor Hybrid AdvantageInterceptor Hybrid AdvantageInterceptor Hybrid Advantage
Source Load
Ground Neutral
Control Circuit
Control Circuit
Current Diverter Module
Current Diverter Module
ElectronicDisconnectElectronicDisconnect
Current Diverter Module
Current Diverter Module
Current Diverter Module
Current Diverter Module
SADSAD
ImpedanceImpedance
20Company ConfidentialJanuary 21, 2005
Board Meeting
MOV & SAD Clamping Characteristics
0.0
100.0
200.0
300.0
400.0
500.0
600.0
0 2500 5000 7500 10000
Surge Current (Amperes)
Cla
mpi
ng V
olta
ge (V
olts
)
MOV
SAD
MOV & SAD CLAMPING CHARACTERISTICSMOV & SAD CLAMPING CHARACTERISTICSMOV & SAD CLAMPING CHARACTERISTICS
21Company ConfidentialJanuary 21, 2005
Board Meeting
SAD Hybrid Interceptor Surge Current Sharing DataH2120Y222R-01
0.010.020.030.040.050.060.070.080.090.0
100.0
0 5000 10000 15000 20000 25000 30000
Total Surge Current (Amperes)
Perc
enta
ge o
f Sur
ge C
urre
nt (%
)
Interceptor MOV ModuleHybrid SAD Module
Interceptor Hybrid AdvantageInterceptor Hybrid AdvantageInterceptor Hybrid Advantage
22Company ConfidentialJanuary 21, 2005
Board Meeting
All components are computer tested and matched
SAD’s within ± 1%, MOVs within 1 volt
Matched low impedance buss system for SAD and MOV modules
Primary stage joule ratings:
“H1” modules 250 joules
“H2” modules 500 joules
UL rated 200 kAIC fuse network
Options audible alarm, transient counters, test set, NEMA 3R, 4, 4X enclosures
Warranty: 10 Year
Interceptor Hybrid AdvantageInterceptor Hybrid AdvantageInterceptor Hybrid Advantage
23Company ConfidentialJanuary 21, 2005
Board Meeting
H1xxxY111R
H1 = 250 Joule SADH2 = 500 Joule SAD
Surge Current Ratings111 Series 250kA/Phase222 Series 320kA/Phase333 Series 400kA/Phase444 Series 750kA/Phase
R = With Disconnect
Voltage120240277208480
S = Split PhaseD = 3-Phase DeltaY = 3-Phase Wye
SourceConfiguration
Interceptor Hybrid Advantage Model NumberInterceptor Hybrid Advantage Model Interceptor Hybrid Advantage Model NumberNumber
24Company ConfidentialJanuary 21, 2005
Board Meeting
Motorola R56 Standards & Guidelines for Communication Sites
CompetitionTranstectorA-C DataNorthern Tech
Motorola R56 Version Interceptor & Hybrid AdvantageMotorola R56 Version Motorola R56 Version Interceptor & Hybrid AdvantageInterceptor & Hybrid Advantage
25Company ConfidentialJanuary 21, 2005
Board Meeting
Source Load
Normal Mode (L-N, L-L) Neutral
MOVCurrent Diverter
Module
MOVCurrent Diverter
Module
MotorolaInterceptor Hybrid Advantage Type 1 & 1AMotorolaMotorolaInterceptor Hybrid Advantage Type 1 & 1AInterceptor Hybrid Advantage Type 1 & 1A
SADSAD
ImpedanceImpedance
26Company ConfidentialJanuary 21, 2005
Board Meeting
Type 1A– Protection for facilities located
where the level of exposure is high
Primary SAD module: 500 J / phaseSecondary MOV module: 5000 J / phaseL-N suppression only330 volt protection levelPulse life requirements
(40) 20 kV / 10 kA(360) 6 kV / 3 kA
NEMA 4XWarranty: 10 Year
Motorola R56 Version Hybrid AdvantageMotorola R56 Version Hybrid AdvantageMotorola R56 Version Hybrid Advantage
27Company ConfidentialJanuary 21, 2005
Board Meeting
Type 2
– Protection for specific applications
MOV modules: 5000 J / phase
L-N suppression only
400 volt protection level
6 kV / 3 kA per UL 1449 Edition 2
Pulse life requirements
(400) 6 kV / 3 kA
NEMA 4X
Warranty: 10 Year
Motorola R56 Version InterceptorMotorola R56 Version InterceptorMotorola R56 Version Interceptor
28Company ConfidentialJanuary 21, 2005
Board Meeting
Transmits transients generated by lightning and switching
Minimal voltage drops
Patented coaxial cables
Minimizes inductance through a reduced coaxial aspect ratio
Extremely low impedance (2-10 Ω)
Losses are under 4.2 V / ft / kA
Especially valuable in cases where SPD cannot be installed close to the point of protection (> 5 ft)
Liebert AccuGuideLiebertLiebert AccuGuideAccuGuide
29Company ConfidentialJanuary 21, 2005
Board Meeting
JacketOuter BraidInner Braid
Primary & SecondaryInsulation
Conductor
l Conventional conductor voltage losses exceed 16V/ft/kA
l AccuGuide coax voltage losses are less than 4.2V/ft/kA
l AccuGuide provides 400% improved performance
AccuGuide Coax ConstructionAccuGuideAccuGuide Coax ConstructionCoax Construction
30Company ConfidentialJanuary 21, 2005
Board Meeting
0
500
1000
1500
2000
2500
3000
3500
0 7.5 16.5 26 33 43
Distance Feet
Cla
mpi
ng V
olta
ge
AccuGuide 3kA PerformanceAccuGuideAccuGuide 3kA Performance3kA Performance#10 AWGAccuGuide
31Company ConfidentialJanuary 21, 2005
Board Meeting
Liebert LM Series®Liebert LM SeriesLiebert LM Series®®
“Competitive Grade” product for competitor controlled specifications
Modular design
120 kA to 500 kA per phase surge current capacity
UL rated 200kAIC fuse network
All modes of protection
Internal and external LEDs, Form C Contacts, & Audible Alarm
Service entrances and distribution panel applications
32Company ConfidentialJanuary 21, 2005
Board Meeting
Liebert LM Series®Liebert LM SeriesLiebert LM Series®®
EMI / RFI filtering
Complete Testing/Certifications:
UL 1449, UL 1283, and CSA Listed
NEMA LS1 (up to LM200)
5 year parts warranty
Options: disconnect, counter, test set, enclosures - NEMA 3r, 4 & 4X
33Company ConfidentialJanuary 21, 2005
Board Meeting
LM 1 - 2 - 3 - 4 - 5- 6 - 7
1 Surge Level per Mode : 060, 080, 100, 125, 150, 200, 225, 250, 300
2 Voltage: 120, 208, 220, 230, 240, 277, 347, 480, 600
3 Phase Configuration: N (1 ph L-N), L (1 ph L-L), S (split), Y (Wye), D (Delta), H (Delta Hi-Leg), X (Wye no neutral)
4 Modes of Protection: A (All)
5 Disconnect: N (no disconnect), R (disconnect)
6 Options: S (standard: LEDs, form C, AA), C (Counter)
7 Enclosure: E (standard 12), R (3R), T (4), X (4X)
Ex: LM080120YARSEModel # designation - LM SeriesModel # designation Model # designation -- LM SeriesLM Series
34Company ConfidentialJanuary 21, 2005
Board Meeting
Liebert PowerSure Medium Exposure
Non modular TVSS
Ideal for 800 Amp panels or less
Surge Current Ratings: 100kA, 160kA
Fault tested to 65 kAICDimensions:
100kA - 6.0”x4.0”x3.0” , 160kA-8.0”x6.0”x4.0”
EMI/RFI Noise Attenuation
Status Indication: LED, Form CCertifications: UL 1449, CUL
Warranty: 5 Years
35Company ConfidentialJanuary 21, 2005
Board Meeting
LPM - 1 - 2 - 3 EX: LPM277Y160
1 - Voltage: 120, 208, 240, 277, 480
2 - Phase Configuration: N (1 ph L-N), L (1 ph L-L), S (split), Y (Wye), D (Delta), H (Delta Hi-Leg), X (Wye no neutral)
3 - Surge Capacity:
160 (160 kA per ph/ 80 kA per mode)
100-2 (100 kA L-N, N-G)
Model # designation - PowerSure Medium ExposureModel # designation Model # designation -- PowerSurePowerSure Medium Medium ExposureExposure
36Company ConfidentialJanuary 21, 2005
Board Meeting
Non modular TVSSIdeal for 400 Amp panels or less
Surge Current Ratings: 25kA, 50kA, 100kA
Fault Tested to 14 kAIC
Dimensions: 4.72”x4.72”x2.36”EMI/RFI Noise Attenuation
Status Indication: LED, Form C Contacts
Certifications: UL 1449, CUL
Warranty: 5 Years
Liebert PowerSure Low Exposure
37Company ConfidentialJanuary 21, 2005
Board Meeting
LPL - 1 - 2 - 3 Ex: LPL120S25-21 - Voltage: 120, 208, 240, 277, 480
2 - Phase Configuration: N (1 ph L-N), L (1 ph L-L), S (split), Y (Wye), D (Delta), H (Delta Hi-Leg), X (Wye no neutral)
3 - Surge Capacity:
100 (100 kA per ph/ 50 kA per mode)
50 (50 kA per ph/25 kA per mode)
25-2 (25 kA L-N, N-G)
Model # designation - PowerSure Low ExposureModel # designation Model # designation -- PowerSurePowerSure Low Low ExposureExposure
38Company ConfidentialJanuary 21, 2005
Board Meeting
l MOV / SAD Matching - Every MOV / SAD is voltage matched to allow complete current sharing
l Component Level Fusing - Every MOV/SAD is individually fused and monitored
l 200 kAIC Silver Fuse Network - Allows rated surge current to pass without fuse operation
l NEMA LS 1 complete documentation package
l Modular and non-modular devices/power, data, and telecom
l Broadest range of ratings 25 kA to 1000 kA
Why LIEBERT TVSS?Why LIEBERT TVSS?Why LIEBERT TVSS?