Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011...

32
LiebertHPW -- PD -- 273136 -- 05.05.2011 Liebert HPW Outdoor Package Cooling System for Mobile Network Access Nodes Precision Cooling for Business -Critical Continuity PRODUCT DOCUMENTATION

Transcript of Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011...

Page 1: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

LiebertH

PW--PD--273136

--05.05.2011

Liebert HPWOutdoor Package Cooling System for Mobile Network Access Nodes

Precision Cooling forBusiness--Critical Continuity

PRODUCT DOCUMENTATION

Page 2: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

Liebert HPW 05--15

Liebert HPW---PD---273136---05.05.2011

Liebert HPW 05--- 15

Reliability, Flexibility and TCOLiebert HPW is the newest high performancewall ---mount outdoor packagecooling system,de-signed to assure proper environmental conditions inside technological environments, especiallyBTS or Node B for mobile telecom networks.It’s reliable: mechanical design ideal for managing high sensible heat load in harsh environ-ments.It’s flexible: available in upflow or downflow air delivery versionswith the same compact cabinetdimension, Liebert HPW can configured with different main options as free cooling, emergencycooling 48 Vdc and heating.It’s designed tominimise the Total Cost of Ownership (TCO) thanks to high efficiency (EER),high effectiveness (displacement like, cooling process), low installation and maintainance costs.

One Liebert HPW cooling unit can handle up to 15 kW sensible heat load site, with efficiency(EER) higher than 3, in environments temperature range from ---30_Cup tomore than 50_C, sav-ing in 10years lifetime 50%of Total cost ofOwnership if comparedwith traditional air conditioningsystem!

Front view Rear view

Page 3: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

Index of Contents

Liebert HPW---PD---273136---05.05.2011

Index of Contents

Contents 1 Features and Benefits

2Model Description andSelection

3 Mechanical Specifications

4 Control

5 Options

6 Accessories

7 Test andReferenceNorms

8 Technical Data

9 Overall Dimensions

10 Installation

The product conforms to European Uniondirectives 2006/42/EC; 2004/108/EC;2006/95/EC and 97/23/EC.

Units are supplied complete with a testcertificate and conformity declaration andcontrol component list.

Liebert HPW units are CE marked as theycomply with the European directivesconcerning mechanical, electrical andelectromagnetic safety.

The Quality ManagementSystem of Emerson Network

Power S.r.l. High PerformanceAir Conditioning has been

approved by Lloyd's RegisterQuality Assurance to the

quality management systemstandard ISO 9001:2008.

Page 4: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

Features and Benefits1

Liebert HPW---PD---273136---05.05.2011 1 - 1

Features and Benefits

Use the most adaptive and suitable wall mount solution!Liebert HPW can be configured in over flow (Liebert HPW ---O) or down flow (Liebert HPW ---D)version, resulting as extremely adaptive to different site layout; whatever is the chosen deliveryair version wall cuts are the same, the condenser section is always positioned on the top part ofthe unit reducing critical environment impact on condenser efficiency and permitting easier andmore effective maintenance activities.

Distribute the air in the best way!Use theLiebertHPW ---D version toget efficiency andeffectivenessat same time:LiebertHPW ---D delivers the cold air straight down, close to the racks suction area and intakes the hot air out-coming from the heat sources in the top part of the room. In this way the mixing effect betweencooling unit cold air and the electronic equipment hot air is denied resulting in a doublebeneficialeffect: the racks are fed by cold air where it is needed and the air conditioner treats only the hotair maximising its efficiency.Proper temperature inside the racks, high efficiency of the cooling equipment, hot spot absencein the site: distributing the air in a smart way is very effective.

Save energy!The use of the freecooling gives the possibility to stop the compressor and condenser fan, usingthe external fresh air to cool the site: the annual energy absorption, requested to cool the site,goes sensibly down. The0---100% finemodulation allows to keepconstantly thedesired set pointinside the site. Thanks to its own air distribution (only hot air is exhausted), Liebert HPWdownflowversion, extends the yearly freecooling use, increasing the energy saving.

Maximize site reliability!Liebert HPW, equippedwithe the Emergency Cooling feature, does not stop the operation evenin case of mains failure: fed by 48 V DC emergency supply from back up systems, Liebert HPWautosets its parameters to ventilate andmaximise the freecooling to keep the indoor temperaturebelow the shut down limit, reliablity of the site means also reliability of the unit. Downflow modelallows tostart theEmergengy Freecooling at a higher external temperature, reducing the siteshutdown risks.

Fast installation and start---up!No piping or refrigeration work is requested on site: just prepare cut---outs in the wall, accordingto the template, andmake power available. As soon the unit is fixed and sealed on the wall, placethe remote display in a suitable position and feed the unit.Installation canbe further speededupusing the fast plug connector option (available on request):no wiring is requested on site and the connection can be performed even by non skilled person-nel. In case of unit replacement, the fast plugs allow replacement ina few minutes.

S Two versions:DownfloworOver

S Onesitepreparation:samewall cuts

S CoolingeffectivenessS CoolingEfficiency

S EnhancedFreecooling

S Continuerevenuefromsite

S Nopiping, fastelectricalconnections

Page 5: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

2 Model Description and Selections

Liebert HPW---PD---273136---05.05.2011 2 - 1

Model Description and Selections

3 54 10987

Cooling Capacity “kW”(Nominal cooling capacity)

1 2

Model Nomenclature / Digit Numbers

_ _ _ _ _ _ _

Wall Mounted Unit

6

0 6 MWCabinet Size(Small, Medium)

M

Liebert HPW WM05---06SO/SD --- HPW WM06---15MO/MDBASE UNIT: DIGITS 1, 2, 3, 4, 5Packaged outdoor wall mounted air conditioner, direct expansion(R407C) with built--- in air cooled condenser

Digit 6 --- Airflow pathD = DownflowO = Over

Digit 7 --- Emergency cooling (EFC)0 = No emergency cooling1 = Emergency cooling through 48Vdc fan (*)

2 = Emergency cooling through 230Vac (*)

A = No emergency cooling + Alarm boardB = Emergency cooling through 48Vdc fan + Alarm board (*)

C = Emergency cooling through 230Vac + Alarm board (*)

(*) Option possible only if digit 9 = 1, 2, A, or B

Digit 8 --- Main power supply and electric heating0 = 230V / 1Ph / 50Hz, no electric heating, for 4 --- 6kW

400V / 3Ph / 50Hz, no electric heating, for 8 --- 16kW1 = 230V / 1Ph / 50Hz, with electric heating, for 4 --- 6kW

400V / 3Ph / 50Hz, with electric heating, for 8 --- 16kW

Digit 9 --- Fresh air freecooling (FC)0 = No freecooling1 = Freecooling with modulating damper2 = Freecooling with fast return damperA = Freecooling with modulating damper and HumitempB = Freecooling with fast return damper and Humitemp

Digit 10 ---Microprocessor control1 = Control without display2 = Control with remote display (cable included)

With Hiromatic Evolution (Graphic display)(inclusive of RS422 with RJ connectors)

5 = Languages Set 1, temperature control(GB, F, I, D, E, P, NL, S)

6 = Languages Set 2, temperature control(GB, PL, CZ, H, RUS, TK)

Digit 11 ---Air filters0 = G31 = G42 = G3 + clogged filter pressure switch on internal air3 = G4 + clogged filter pressure switch on internal air

Digit 12 ---PackingP = PLP and palletC = Cardboard and wooden crateS = Seaworthy

Digit 13 ---Condensing control0 = Condensing control ON---OFF1 = Modulating condenser fan speed control (Variex)

Digit 14 ---Coils0 = Standard aluminium fins1 = Standard evaporator fins and epoxy coated condenser fins2 = Epoxy evaporator fins and standard coated condenser fins3 = Epoxy coated evaporator and condenser fins

Digit 15 ---Grills0 = No grill (only HPW---O version)1 = Simple (not adjustable) intake and delivery (only HPW---D

version)2 = Simple (not adjustable) intake and double adjustable on

delivery (only HPW---D version)Finned (not adjustable) intake and double adjustable ondelivery (only HPW---O version)

Digit 16 ---Free0 = Free option always

Digit 17 ---Special requirements0 = NoneX = Special

Page 6: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

3 Mechanical Specifications

Liebert HPW---PD---273136---05.05.2011 3 - 1

Mechanical Specifications

CabinetThe unit is designed to be installed outdoor, coping with the worst weather conditions.The self ---supporting cabinet is made of heavy gauge galvanised steel panels, painted on bothsideswith RAL7035 polyester powder, insulated with polyurethane foam, fire---proof class 1. Thebackpanel (wall side) includes integral spigots, 50mmdeep. Fixedpanels aresecuredbywater---tight, aluminum rivets.All external screws are anti ---vandalism type, to be opened with a special tool supplied with theunit. Metal safety grids rated IP20 --- protect the machine and prevent contact with sensitive/dan-gerous components.

Refrigerant circuitThe refrigeration compressor is a hermetic, scroll type, complete with internal protection againstover heating. A crankcase heater maintains a minimum refrigerant temperature to allow reliablestart---up and operation even in very cold climate.The circuit is pre---charged with refrigerant and includes a thermostatic expansion valve, filterdryer and sight glass, low pressure and high pressure switches and two access valves.The compressor is housed in a compartment separated from the air flow and protected by aninsulated panel closed with anti ---vandalism screws, accessible from the front side for completemaintenance.

Evaporating sectionA single coil with copper tubes and aluminum fins, having a large heat exchange surface to re-duce humidity removal and increase efficiency.A galvanized steel condensate drain tray (10/10 mm thick) is provided.

Evaporator fanEvaporator fans are centrifugal type, with backward curved blades (plug--- type), direct driven byintegral electric motors.Fans are statically and dynamically balancedwith self --- lubricatedbearings, equippedwith anairflow sensor as standard to provide an alarm in case of low air flow.

Condenser sectionA wide surface condensing coil (L or U shape) is provided. It is designed in copper tubes withaluminium fins and sized to allow operations at least up to up to 50_C outdoor air temperature.

Condenser fanThe condenser fan is of the axial type, with integral IP54 motor and internal thermal protection,statically and dynamically balanced, including sealed--- for--- life bearings. Blades, impeller andcasing are made from corrosion---proof materials.It is protected by metal safety grids, rated IP20.

Air filterThe filtering system is composedby two filters, one for the indoor air and one for the fresh air (eas-ily removable from the front outdoor side of the unit). Filters are pleated type (except indoor airfilter on over version) with a synthetic fiber surface and metal frame, giving G3 class efficiency(CEN---EN) as standard.

Electrical panelThe electrical board is housed in a compartment isolated from the air stream and closed by ascrewed on panel. It is built in accordance with EN 60204---1 recommendations.

S Designedtoworkwithworstweatherconditions

S Scroll compressorS CrankcaseheaterS Filterdryerandsightglass

S BackwardcurvedbladesS 230VACor48VDC(option)

S Latentheatexchangeatminimum

S LorU---shapecoilS Upto50° Cexternaltemperature

S Axial typeS Highefficiency

S Indoor filterS Freshair filter

S Insulatedfromairstream

Page 7: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

Mechanical Specifications

Liebert HPW---PD---273136---05.05.2011 3 - 2

PLP packingLiebert HPW unit is packed as standard on awooden pallet with shock---proof angle pieces anda top cover made of pressed cardboard/polystyrene sandwich, protected by flexible polythenefilm.

ConnectivityLAN (Local Area Networking) among several units is allowed as standard; sharing setting para-meters, rotating the units during their operation, keeping units in stand---by and re---activatingthem when required.

Operational limitsLiebert HPW models “DC emergency freecooling version”

HPW WM05SD WM05SO WM06SD WM06SO

Power supply voltage 230V ±10% / 1Ph / 50Hz

Outdoorworking conditions

from10° C (1)

---30° C (2)

to 49° C (3) 49.5° C (3) 47° C (3) 47.5° C (3)

Indoorworking conditions (4)

from 20° C, 30---80% RH 21° C, 30---80% RH 21° C, 30---80% RH 22° C, 30---80% RH

to 35° C, 40% R.H.

Storage conditions---40° C, 5% R.H.

55° C, 90% R.H.

HPW WM06MD WM06MO WM08MD WM08MO WM10MD WM10MO

Power supply voltage 230V ±10% / 1Ph / 50Hz 400V ±10% / 3Ph+N+PE / 50Hz

Outdoorworking conditions

from10° C (1)

---30° C (2)

to 52° C (3) 50.5° C (3) 50° C (3)

Indoorworking conditions (4)

from 21° C, 30---80% RH

22° C, 30---80% RH 20° C, 30%---80% R.H. 21° C, 30%---80% R.H.

to 35° C, 40% R.H. 34° C,40% R.H.

33° C,40% R.H.

35° C,40% R.H.

33° C,40% R.H.

Storage conditions---40° C, 5% R.H.

55° C, 90% R.H.

HPW WM13MD WM13MO WM15MD WM15MO

Power supply voltage 400V ±10% / 3Ph+N+PE / 50Hz

Outdoorworking conditions

from10° C (1)

---30° C (2)

to 51° C (3) 48.5° C (3)

Indoorworking conditions (4)

from 22° C, 30%---80% R.H. 24° C, 30%---80% R.H.

to 32° C, 40% R.H.

Storage conditions---40° C, 5% R.H.

55° C, 90% R.H.

Notes:(1) – If ON/OFF condensing fan control option has been chosen.(2) – If modulating condensing fan control (Variex) option has been chosen.(3) --- Maximum external air temperature id referred to:

• 30°C / 39.5% R.H. at the evaporating suction side, for WM05 ---15D models;• 27°C / 47% R.H. at the evaporating suction side, for WM05 ---15O models.

(4) --- Conditions referred to the evaporating suction side; the min. indoor temperature is referred to 30% of indoor relative humidity and to the min.outdoo temperature; for higher relative humidity and/or outdoor temperatures, the min. indoor temperature is lower than the table data.The max. indoor temperature is referred to outdoor temperature of 35° C; for higher indoor relative humidities and/or outdoor temperatures, themax indoor temperature is lower than the table data.

S Cardboard,polystyreneandwoodstandardpacking

S LANavailabilityasstandard

Page 8: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

Mechanical Specifications

Liebert HPW---PD---273136---05.05.2011 3 - 3

Liebert HPW models “No freecooling, freecooling and AC emergency freecooling version”HPW WM05SD WM05SO WM06SD WM06SO

Power supply voltage 230V ±10% / 1Ph / 50Hz

Outdoorworking conditions

from10° C (1)

---30° C (2)

to 49° C (3) 49.5° C (3) 47° C (3) 47.5° C (3)

Indoorworking conditions (4)

from 20° C, 30---80% RH 21° C, 30---80% RH 21° C, 30---80% RH 22° C, 30---80% RH

to 35° C, 40% R.H.

Storage conditions---40° C, 5% R.H.

55° C, 90% R.H.

HPW WM06MD WM06MO WM08MD WM08MO WM10MD WM10MO

Power supply voltage 230V ±10% / 1Ph / 50Hz 400V ±10% / 3Ph+N+PE / 50Hz

Outdoorworking conditions

from10° C (1)

---30° C (2)

to 52° C (3) 50.5° C (3) 50° C (3)

Indoorworking conditions (4)

from 21° C, 30---80% RH

22° C, 30---80% RH 20° C, 30%---80% R.H. 22° C, 30%---80% R.H.

to 35° C, 40% R.H. 33° C, 40% R.H. 35° C,40% R.H.

33° C,40% R.H.

Storage conditions---40° C, 5% R.H.

55° C, 90% R.H.

HPW WM13MD WM13MO WM15MD WM15MO

Power supply voltage 400V ±10% / 3Ph+N+PE / 50Hz

Outdoorworking conditions

from10° C (1)

---30° C (2)

to 51° C (3) 48.5° C (3)

Indoorworking conditions (4)

from 23° C, 30%---80% R.H. 25° C, 30%---80% R.H.

to 33° C, 40% R.H.

Storage conditions---40° C, 5% R.H.

55° C, 90% R.H.

Notes:(1) – If ON/OFF condensing fan control option has been chosen.(2) – If modulating condensing fan control (Variex) option has been chosen.(3) --- Maximum external air temperature id referred to:

• 30°C / 39.5% R.H. at the evaporating suction side, for WM05 ---15D models;• 27°C / 47% R.H. at the evaporating suction side, for WM05 ---15O models.

(4) --- Conditions referred to the evaporating suction side; the min. indoor temperature is referred to 30% of indoor relative humidity and to the min.outdoo temperature; for higher relative humidity and/or outdoor temperatures, the min. indoor temperature is higher than the table data.The max. indoor temperature is referred to outdoor temperature of 35° C; for higher indoor relative humidities and/or outdoor temperatures, themax indoor temperature is lower than the table data.

Page 9: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

Mechanical Specifications

Liebert HPW---PD---273136---05.05.2011 3 - 4

Fig. 1 --- Air flow operating diagram --- Liebert HPW models WM05---06SO/SD

Freecooling Compressor cooling

OUTSIDE OUTSIDE

INSIDEINSIDE

OUTSIDE

INSIDE

OUTSIDE

INSIDE

Exhaust air outletfrom left lateralpanel

Upflow version

Downflow version

Freecooling Compressor cooling

Page 10: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

Mechanical Specifications

Liebert HPW---PD---273136---05.05.2011 3 - 5

Fig. 2 --- Air flow operating diagram --- Liebert HPW models WM06---08---10---13---15MO/MD

Upflow version

Downflow version

OUTSIDE

Freecooling

OUTSIDE

OUTSIDE OUTSIDE

Exhaust air outletfrom left lateralpanel

INSIDE INSIDE

INSIDEINSIDE

Freecooling Compressor cooling

Compressor cooling

Page 11: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

4 Control

Liebert HPW---PD---273136---05.05.2011 4 - 1

Control

Main featuresThemain board is housed in the electrical paneland can be connected to the remote display, tobe installed in the container/room (connectioncable is included in the remote display option).

The user interface (option) is the 3---digit back---lit display showing parameter values and rel-evant symbols/codes in a tree menu. It featuresnavigation push buttons and status leds.General warning and general alarm signals areavailable: both of them activate a visual indicator in the optional display.Input for remoteOn---Off and volt --- free contacts for simple remotemonitoringof generalwarningand alarms are available.

The self --- test function automatically activates / deactivates the main components (evaporatorfan, compressor, free cooling damper, heaters, alarms) without changing the pre---set para-meters, to easily start ---up and commission the unit.No skilled personnel are requested (*).

All settings are protected through a 3---Level password system (*).

Automatic restart is provided after a power failure.

(*) The Remote display is required to activate the function.

Technical dataD Power supply: 24 Vac / 24 Vdc / 48 Vdc. . . . . . . . . . . . . . . . . .

D E2prom: 64 Kbit. . . . . . . . . . . . . . . . . . . . . . .D Eprom / Flash memory: 2 or 4 Mbit. . . . . . . . . .

D RAM memory space: 256 Kbit. . . . . . . . . . .D Analogue Input: 1 x Analogue 0---10V. . . . . . . . . . . . . .

2 x Analogue 0---5V

D Digital Input: 3 x PTC input. . . . . . . . . . . . . . . . . . .5 x Flexible Digital multi input

D Analogue Output: 2 x Analogue 0---10VD Digital output: 3 x relay high power output. . . . . . . . . . . . . . . . . .

2 x relay 24Vac / 48Vdc output2 x relay low power output1 x open collector 12Vdc output

D Time and date function buffered by LI ---battery.D Hirobus LAN connectors (optional): 3 RJ45 sockets (to and from LAN connected units,

remote display)

D Hironet connectors: 1 RJ9 socket for RS485 (direct connection to . . . . .. . . . . . . . . . . . .proprietary supervision)

D Hiromatic E display (optional).D SMM mobile phones communications via SMS (optional).

Page 12: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

5 Options

Liebert HPW---PD---273136---05.05.2011 5 - 1

Options

Emergency coolingThe unit is optionally equipped with an emergency cooling system that allows to ventilate or tocool through external fresh air the site in case of main electrical supply fault.For this purpose the evaporating fan section, the control, and the free cooling damper are sup-plied in 48 VDCpower supply (from rectifier in normalmode, from batteries in emergencymode).This option guarantees the air circulation inside the site and if the control recognizes the properexternal temperature to run the freecooling mode, the damper will open to fresh the site and getthe required set point. The emergency cooling system is also available in 230 VAC.

The compressor and the condenser fan are supplied by standard AC power.

HeatingThe heating option includes electric heaters (1.5 kW on models 05 and 06, 3 kW on models 08to15) located in the top indoor unit area, one stage andON---OFF regulation. A safety thermostat,with manual reset, prevents from reaching dangerous temperatures.

FreecoolingThe optional, innovative rotary freecooling system consists of a rotary damper controlled andmoved from AC servomotor (48VDC supplied in the emergency version). The system allows a0---100% modulating free--- cooling in order to respect the desired set point. The exhaust air isdischarged through the unit without any additional external damper.The control allows the unit to run in freecooling mode when the difference between the indoorand outdoor air temperature reaches the required value to get the nominal cooling capacity. Inemergency situation, the freecooling is allowed at a lower difference between the indoor andout-door air temperature, in order to use the external fresh air as much as possible.A combined humidity and temperature sensor (Humitemp) can be fitted, in order to avoid highindoor humidity levels in freecooling mode, acting on the freecooling damper.Fast return damper option is available to close automatically the damper in case of AC powerfailure (DC power failure in the 48VDC emergency cooling version).Combined operation, mechanical cooling and freecooling is available on request.

Control”No Display” option let just authorized people to change main parameters set, using a ”servicedisplay”.Graphic display is available featuring a 24h graphic record of controlled parameters as well asthe last 200 events occurred. A back---up battery keeps the data stored in the memory (graphicdata record, alarms).

Special filtrationOptional high--- level filtration can be reached.A clogged filter system can be supplied to advise when the indoor air filter is dirty.

GrillsWhile fix intake air grill is efficient solution, optional delivery air double adjustable grill could benecessary to address the cold air where it is really needed.

PackageStandard packing consists of a wooden pallet and cardboard box. Polythene foam protects theunit painted surfaces. On request, a cardboard box with an additional wooden crate or woodencase for sea transport can be supplied.

S UninterruptibleventilationS 48VDCFreecoolingS Customizedalarmsonboard

S ON---OFFcontrolS Safety thermostat

S InnovativerotarysystemS 0---100%modulationS Fast returndamperS Prevention fromhighhumidity

S G4filterS Freshairclogged filter

S Different typeof intakeanddeliverygrills

S SafetyoptionS Graphicdisplay

S WoodencrateS Woodencase

Page 13: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

Options

Liebert HPW---PD---273136---05.05.2011 5 - 2

Condenser fan speed controlTheoptional pressure---actuated speed regulatormaintains theminimum speedneeded to rejectheat load from the condenser, reducing compressor cycling and outdoor noise, allowing oper-ations down ---30 ° C external temperature.

Corrosive environments protectionThe condenser coil and/or evaporator coils are available with aluminium fins coated by epoxyfilm, to protect from aggressive environmental conditions.

S Epoxycoatedcoils

S Pressurespeedcontrol

Page 14: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

6 Accessories

Liebert HPW---PD---273136---05.05.2011 6 - 1

Accessories

Lifting eyeboltsSupports on unit top side to lift the unit and help the installation (available on heavy units, sizeM).

Installation template (paper scale 1:1)Wall cut and fixing points position/dimensions in a 1:1 scale drawn to prepare the site for unit in-stallation.

Support bracketsMade of galvanized steel RAL 7035 color, support the unit during the installation.

Hirobus cables8 poles shielded cables, either 3 or 5 or 20 meters long for LAN creation (Local Area Network).

Page 15: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

7 Test and Reference Norms

Liebert HPW---PD---273136---05.05.2011 7 - 1

Test and Reference Norms

SafetyLiebert HPW units are designed,manufactured and tested according to the European Union di-rectives:

D 2006/42/EC;D 2004/108/EC;

D 2006/95/EC;D 97/23/EC.

Electrical BoardDesign and manufacturing is compliant with EN 60204---1.

Electro---Magnetic compatibility (EMC)Liebert HPW complies with the following EMC standards:D EN 50081---1, Emission (“Generic emission standard, Part 1: Residential, commercial andlight industry, Jan 1992”)

D EN 50082---2, Immunity (“Generic immunity standard, Part 2: Industrial environment, Mar1995”).

MarkEach unit is supplied complete with individual test certificate and a declar-ation of conformity to the EuropeanUnion directives. The units aremarked“CE”.

QualityTheQuality Management System ofEmersonNetworkPower S.r.l. HighPerformance Air Conditioning has been approved by Lloyd’s RegisterQuality Assurance to the quality management system standard ISO9001:2008.

Page 16: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

Technical Data8

Liebert HPW---PD---273136---05.05.2011 8 -- 1

Technical Data

Tab. 1 --- Liebert HPW models WM05---06S (DC emergency freecooling version)MODEL: HPW WM05SD WM05SO WM06SD WM06SOAir supply --- Downflow Upflow Downflow Upflow

Main power supply --- 230V ±10% / 1Ph / 50Hz

Emergency power supply --- 48 Vdc ±17%

PERFORMANCETotal cooling capacity (1)Sensible cooling capacity (1)Compressor --- AC power input (1)Compressor --- AC operative current (OA) (1)Compressor --- AC max current (FLA)Compressor --- AC starting current (LRA)Condenser fan --- AC power input (1)Condenser fan --- AC max. power inputCondenser fan --- AC operative current (OA) (1)Condenser fan --- AC max. current (FLA)Condenser fan --- AC start ---up current (LRA)Evaporator fan --- DC power input (1)Evaporator fan --- DC operative current (OA) (1)Evaporator fan --- DC max. current (FLA) (2)Evaporator fan --- DC start ---up current (LRA)Evaporator air flowFreecooling air flowCondenser max. air flowOutdoor sound pressure level (3)Indoor sound pressure level (3)Max. ambient temperature (4)

kWkWkWAAAkWkWAAAkWAAAm3/hm3/hm3/hdB(A)dB(A)_C

5.55.51.265.810.035.00.240.241.11.41.60.102.62.60.111101310292552.557.049.0

5.34.61.255.710.035.00.240.241.11.41.60.102.62.60.110601090292552.557.049.5

6.35.81.637.611.447.00.240.241.11.41.60.102.62.60.111101310292554.057.047.0

6.05.01.637.611.447.00.240.241.11.41.60.102.62.60.110601090292554.057.047.5

REFRIGERATION CIRCUITCompressor --- type / quantityRefrigerantExpansion deviceEvaporator coil --- tubes / fins materialCondenser coil --- tubes / fins material

---------------

Scroll / 1R407C

Thermostatic valveCopper / AluminiumCopper / Aluminium

AIR FILTRATIONMain air filter --- quantity / typeEfficiency (CEN---EU)Filter dimension (DX side)Filter dimension (FC side)

------mmmm

1 / PleatedG3

705 x 428 x 40705 x 428 x 40

EVAPORATOR FANQuantity / Type / Poles --- 1 / Plug / ---

Driven / Motor protection --- Direct / IP42

CONDENSER FANQuantity / Type / Poles --- 1 / Axial / 6

Driven / Motor protection --- Direct / IP54

Control system --- Single speed or continually variable speed, depending on condensingfan control chosen option

ELECTRIC HEATINGType / Steps --- Wires / 1

Heating capacity kW 1.5

Heating --- max. current A 6.5

CABINETFrame --- Galvanized steel

Painting --- Polyester --- RAL7035

DIMENSIONSWidth x Height x Depth mm 800 x 1690 x 450

Weight kg 170 175

Notes:(1) – Values are referred to 35°C outdoor temperature, to nominal power supply and to the following Indoor conditions:

• 30°C / 39.5% R.H. at the evaporating suction side, for WM05 ---06SD models;• 27°C / 47% R.H. at the evaporating suction side, for WM05 ---06SO models.

(2) – Value is referred to nominal speed (factory set).(3) --- Measured with 35°C outdoor temperature, at 2 m from the unit, in free field conditions.(4) --- Maximum outdoor temperature referred to:

• 30°C / 39.5% R.H. at the evaporating suction side, for WM05 ---06SD models;• 27°C / 47% R.H. at the evaporating suction side, for WM05 ---06SO models.

Page 17: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

Technical Data

Liebert HPW---PD---273136---05.05.2011 8 -- 2

Tab. 2 --- Liebert HPW models WM06---08---10M (DC emergency freecooling version)MODEL: HPW WM06MD WM06MO WM08MD WM08MO WM10MD WM10MO

Air supply --- Downflow Upflow Downflow Upflow Downflow Upflow

Main power supply --- 230V ±10% / 1Ph / 50Hz 400V ±10% / 3Ph+N+PE / 50Hz

Emergency power supply --- 48 Vdc ±17%PERFORMANCETotal cooling capacity (1)Sensible cooling capacity (1)Compressor --- AC power input (1)Compressor --- AC operative current (OA) (1)Compressor --- AC max current (FLA)Compressor --- AC starting current (LRA)Condenser fan --- AC power input (1)Condenser fan --- AC max. power inputCondenser fan --- AC operative current (OA) (1)Condenser fan --- AC max. current (FLA)Condenser fan --- AC start ---up current (LRA)Evaporator fan --- DC power input (1)Evaporator fan --- DC operative current (OA) (1)Evaporator fan --- DC max. current (FLA) (2)Evaporator fan --- DC start ---up current (LRA)Evaporator air flowFreecooling air flowCondenser max. air flowOutdoor Sound Pressure Level (3)Indoor Sound Pressure Level (3)Max. ambient temperature (4)

kWkWkWAAAkWkWAAAkWAAAm3/hm3/hm3/hdB(A)dB(A)_C

6.56.21.466.811.447.00.200.231.11.41.60.102.62.60.113001440371050.057.052.0

5.75.41.497.011.447.00.200.231.11.41.60.102.62.60.113601360371049.557.052.0

8.98.91.903.55.132.00.220.231.11.41.60.285.89.60.119502420371052.060.050.5

8.28.01.933.55.132.00.220.231.11.41.60.459.49.60.121302400371052.064.050.0

11.710.92.664.87.046.00.720.783.53.57.40.459.59.60.123002420566055.064.050.0

11.19.52.684.97.046.00.720.783.53.57.40.459.59.60.123002400566055.064.050.0

REFRIGERATION CIRCUITCompressor --- type / quantityRefrigerantExpansion deviceEvaporator coil --- tubes / fins materialCondenser coil --- tubes / fins material

---------------

Scroll / 1R407C

Thermostatic valveCopper / AluminiumCopper / Aluminium

AIR FILTRATIONMain air filter --- quantity / typeEfficiency (CEN---EU)Filter dimension (DX side)Filter dimension (FC side)

------mmmm

1 / PleatedG3

840 x 601 x 100840 x 601 x 100

EVAPORATOR FANQuantity / Type / Poles --- 1 / Plug / ---

Driven / Motor protection --- Direct / IP42 Direct / IP20

CONDENSER FANQuantity / Type / Poles --- 1 / Axial / 6 1 / Axial / 4

Driven / Motor protection --- Direct / IP54

Control system --- Single speed or continually variable speed, depending on condensingfan control chosen option

ELECTRIC HEATINGType / Steps --- Wires / 1

Heating capacity kW 1.5 3.0

Heating --- max. current A 6.5

CABINETFrame --- Galvanized steel

Painting --- Polyester --- RAL7035

DIMENSIONSWidth x Height x Depth mm 932 x 1901 x 640

Weight kg 195 195 205 205 220 220

Notes:(1) – Values are referred to 35°C outdoor temperature, to nominal power supply and to the following Indoor conditions:

• 30°C / 39.5% R.H. at the evaporating suction side, for WM06 ---08 ---10MD models;• 27°C / 47% R.H. at the evaporating suction side, for WM06 ---08 ---10MO models.

(2) – Value is referred to nominal speed (factory set).(3) --- Measured with 35°C outdoor temperature, at 2 m from the unit, in free field conditions.(4) --- Maximum outdoor temperature referred to:

• 30°C / 39.5% R.H. at the evaporating suction side, for WM06 ---08 ---10MD models;• 27°C / 47% R.H. at the evaporating suction side, for WM06 ---08 ---10MO models.

Page 18: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

Technical Data

Liebert HPW---PD---273136---05.05.2011 8 -- 3

Tab. 3 --- Liebert HPW models WM13---15M (DC emergency freecooling version)MODEL: HPW WM13MD WM13MO WM15MD WM15MOAir supply --- Downflow Upflow Downflow Upflow

Main power supply --- 400V ±10% / 3Ph+N+PE / 50Hz

Emergency power supply --- 48 Vdc ±17%

PERFORMANCETotal cooling capacity (1)Sensible cooling capacity (1)Compressor --- AC power input (1)Compressor --- AC operative current (OA) (1)Compressor --- AC max current (FLA)Compressor --- AC starting current (LRA)Condenser fan --- AC power input (1)Condenser fan --- AC max. power inputCondenser fan --- AC operative current (OA) (1)Condenser fan --- AC max. current (FLA)Condenser fan --- AC start ---up current (LRA)Evaporator fan --- DC power input (1)Evaporator fan --- DC operative current (OA) (1)Evaporator fan --- DC max. current (FLA) (2)Evaporator fan --- DC start ---up current (LRA)Evaporator air flowFreecooling air flowCondenser max. air flowOutdoor sound pressure level (3)Indoor sound pressure level (3)Max. ambient temperature (4)

kWkWkWAAAkWkWAAAkWAAAm3/hm3/hm3/hdB(A)dB(A)_C

13.013.02.564.87.046.00.680.783.43.57.40.459.59.60.126152850588055.059.051.0

12.010.22.604.97.046.00.680.783.43.57.40.459.59.60.123002700588055.064.051.0

14.914.03.296.110.050.00.690.783.33.57.40.8217.219.20.128203000588058.063.048.5

13.811.23.306.110.050.00.720.783.53.57.40.7816.319.20.124502840588058.067.048.5

REFRIGERATION CIRCUITCompressor --- type / quantityRefrigerantExpansion deviceEvaporator coil --- tubes / fins materialCondenser coil --- tubes / fins material

---------------

Scroll / 1R407C

Thermostatic valveCopper / AluminiumCopper / Aluminium

AIR FILTRATIONMain air filter --- quantity / typeEfficiency (CEN---EU)Filter dimension (DX side)Filter dimension (FC side)

------mmmm

1 / PleatedG3

840 x 601 x 100840 x 601 x 100

EVAPORATOR FANQuantity / Type / Poles --- 1 / Plug / --- 2 / Plug / ---

Driven / Motor protection --- Direct / IP20

CONDENSER FANQuantity / Type / Poles --- 1 / Axial / 4

Driven / Motor protection --- Direct / IP54

Control system --- Single speed or continually variable speed, depending on condensingfan control chosen option

ELECTRIC HEATINGType / Steps --- Wires / 1

Heating capacity kW 3.0 6.0

Heating --- max. current A 6.5 13.0

CABINETFrame --- Galvanized steel

Painting --- Polyester --- RAL7035

DIMENSIONSWidth x Height x Depth mm 932 x 1901 x 640

Weight kg 250 250 260 260

Notes:(1) – Values are referred to 35°C outdoor temperature, to nominal power supply and to the following Indoor conditions:

• 30°C / 39.5% R.H. at the evaporating suction side, for WM13 ---15MD models;• 27°C / 47% R.H. at the evaporating suction side, for WM13 ---15MO models.

(2) – Value is referred to nominal speed (factory set).(3) --- Measured with 35°C outdoor temperature, at 2 m from the unit, in free field conditions.(4) --- Maximum outdoor temperature referred to:

• 30°C / 39.5% R.H. at the evaporating suction side, for WM13 ---15MD models;• 27°C / 47% R.H. at the evaporating suction side, for WM13 ---15MO models.

Page 19: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

Technical Data

Liebert HPW---PD---273136---05.05.2011 8 -- 4

Tab. 4 --- Liebert HPW models WM05---06S(No freecooling, freecooling and AC emergency freecooling version)

MODEL: HPW WM05SD WM05SO WM06SD WM06SOAir supply --- Downflow Upflow Downflow UpflowMain power supply --- 230V ±10% / 1Ph / 50HzEmergency power supply --- 230V ±10% / 1Ph / 50Hz

PERFORMANCETotal cooling capacity (1)Sensible cooling capacity (1)Compressor --- AC power input (2)Compressor --- AC operative current (OA) (1)Compressor --- AC max current (FLA)Compressor --- AC starting current (LRA)Condenser fan --- AC power input (1)Condenser fan --- AC max. power inputCondenser fan --- AC operative current (OA) (1)Condenser fan --- AC max. current (FLA)Condenser fan --- AC start ---up current (LRA)Evaporator fan --- AC power input (1)Evaporator fan --- AC operative current (OA) (1)Evaporator fan --- AC max. current (FLA) (2)Evaporator fan --- AC start ---up current (LRA)Evaporator air flowFreecooling air flowCondenser max. air flowOutdoor Sound Pressure Level (3)Indoor Sound Pressure Level (3)Max. ambient temperature (4)

kWkWkWAAAkWkWAAAkWAAAm3/hm3/hm3/hdB(A)dB(A)_C

5.55.51.265.810.035.00.240.241.11.41.60.140.70.71.211101310292552.556.049.0

5.34.61.255.710.035.00.240.241.11.41.60.140.70.71.210601090292552.556.049.5

6.35.81.637.611.447.00.240.241.11.41.60.140.70.71.211101310292554.056.047.0

6.05.01.637.611.447.00.240.241.11.41.60.140.70.71.210601090292554.056.047.5

REFRIGERATION CIRCUITSCompressor --- type / quantityRefrigerantExpansion deviceEvaporator coil --- tubes / fins materialCondenser coil --- tubes / fins material

---------------

Scroll / 1R407C

Thermostatic valveCopper / AluminiumCopper / Aluminium

AIR FILTRATIONMain air filter --- quantity / typeEfficiency (CEN---EU)Filter dimension (DX side)Filter dimension (FC side)

------mmmm

1 / PleatedG3

705 x 428 x 40705 x 428 x 40

EVAPORATOR FANQuantity / Type / Poles --- 1 / Plug / 4Driven / Motor protection --- Direct / IP44

CONDENSER FANQuantity / Type / Poles --- 1 / Axial / 6Driven / Motor protection --- Direct / IP54

Control system --- Single speed or continually variable speed, depending on condensingfan control chosen option

ELECTRIC HEATINGType / Steps --- Wires / 1Heating capacity kW 1.5Heating --- max. current A 6.5

CABINETFrame --- Galvanized steelPainting --- Polyester --- RAL7035

OVERALL DIMENSIONSWidth x Height x Depth mm 800 x 1690 x 450Weight kg 170 175

Notes:(1) – Values are referred to 35°C outdoor temperature, to nominal power supply and to the following Indoor conditions:

• 30°C / 39.5% R.H. at the evaporating suction side, for WM05 ---06SD models;• 27°C / 47% R.H. at the evaporating suction side, for WM05 ---06SO models.

(2) – Value is referred to nominal speed (factory set).(3) --- Measured with 35°C outdoor temperature, at 2 m from the unit, in free field conditions.(4) --- Maximum outdoor temperature referred to:

• 30°C / 39.5% R.H. at the evaporating suction side, for WM05 ---06SD models;• 27°C / 47% R.H. at the evaporating suction side, for WM05 ---06SO models.

Page 20: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

Technical Data

Liebert HPW---PD---273136---05.05.2011 8 -- 5

Tab. 5 --- Liebert HPW models WM06---08---10M(No freecooling, freecooling and AC emergency freecooling version)

MODEL: HPW WM06MD WM06MO WM08MD WM08MO WM10MD WM10MOAir supply --- Downflow Upflow Downflow Upflow Downflow Upflow

Main power supply --- 230V ±10% / 1Ph / 50Hz 400V ±10% / 3Ph+N+PE / 50Hz

Emergency power supply --- 230V ±10% / 1Ph / 50Hz

PERFORMANCETotal cooling capacity (1)Sensible cooling capacity (1)Compressor --- AC power input (2)Compressor --- AC operative current (OA) (1)Compressor --- AC max current (FLA)Compressor --- AC starting current (LRA)Condenser fan --- AC power input (1)Condenser fan --- AC max. power inputCondenser fan --- AC operative current (OA) (1)Condenser fan --- AC max. current (FLA)Condenser fan --- AC start ---up current (LRA)Evaporator fan --- AC power input (1)Evaporator fan --- AC operative current (OA) (1)Evaporator fan --- AC max. current (FLA) (2)Evaporator fan --- AC start ---up current (LRA)Evaporator air flowFreecooling air flowCondenser max. air flowOutdoor Sound Pressure Level (3)Indoor Sound Pressure Level (3)Max. ambient temperature (4)

kWkWkWAAAkWkWAAAkWAAAm3/hm3/hm3/hdB(A)dB(A)_C

6.56.21.466.811.447.00.200.231.11.41.60.150.70.71.213001440371050.056.052.0

5.75.41.497.011.447.00.200.231.11.41.60.150.70.71.213601360371049.556.052.0

8.98.91.903.55.132.00.220.231.11.41.60.462.32.45.319502240371052.063.050.5

8.28.01.933.55.132.00.220.231.11.41.60.472.42.45.321302150371052.063.050.0

11.610.52.664.77.046.00.710.783.53.57.40.462.32.45.321302240566055.063.050.0

11.09.12.674.87.046.00.710.783.53.57.40.472.42.45.321402150566055.063.050.0

REFRIGERATION CIRCUITSCompressor --- type / quantityRefrigerantExpansion deviceEvaporator coil --- tubes / fins materialCondenser coil --- tubes / fins material

---------------

Scroll / 1R407C

Thermostatic valveCopper / AluminiumCopper / Aluminium

AIR FILTRATIONMain air filter --- quantity / typeEfficiency (CEN---EU)Filter dimension (DX side)Filter dimension (FC side)

------mmmm

1 / PleatedG3

840 x 601 x 100840 x 601 x 100

EVAPORATOR FANQuantity / Type / Poles --- 1 / Plug / 4

Driven / Motor protection --- Direct / IP44 Direct / IP54

CONDENSER FANQuantity / Type / Poles --- 1 / Axial / 6 1 / Axial / 4

Driven / Motor protection --- Direct / IP54

Control system --- Single speed or continually variable speed, depending on condensingfan control chosen option

ELECTRIC HEATINGType / Steps --- Wires / 1

Heating capacity kW 1.5 3.0

Heating --- max. current A 6.5

CABINETFrame --- Galvanized steel

Painting --- Polyester --- RAL7035

OVERALL DIMENSIONSWidth x Height x Depth mm 932 x 1901 x 640

Weight kg 195 195 205 205 220 220

Notes:(1) – Values are referred to 35°C outdoor temperature, to nominal power supply and to the following Indoor conditions:

• 30°C / 39.5% R.H. at the evaporating suction side, for WM06 ---08 ---10MD models;• 27°C / 47% R.H. at the evaporating suction side, for WM06 ---08 ---10MO models.

(2) – Value is referred to nominal speed (factory set).(3) --- Measured with 35°C outdoor temperature, at 2 m from the unit, in free field conditions.(4) --- Maximum outdoor temperature referred to:

• 30°C / 39.5% R.H. at the evaporating suction side, for WM06 ---08 ---10MD models;• 27°C / 47% R.H. at the evaporating suction side, for WM06 ---08 ---10MO models.

Page 21: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

Technical Data

Liebert HPW---PD---273136---05.05.2011 8 -- 6

Tab. 6 --- Liebert HPW models WM13---15M(No freecooling, freecooling and AC emergency freecooling version)

MODEL: HPW WM13MD WM13MO WM15MD WM15MOAir supply --- Downflow Upflow Downflow UpflowMain power supply --- 400V ±10% / 3Ph+N+PE / 50HzEmergency power supply --- 230V ±10% / 1Ph / 50Hz

PERFORMANCETotal cooling capacity (1)Sensible cooling capacity (1)Compressor --- AC power input (2)Compressor --- AC operative current (OA) (1)Compressor --- AC max current (FLA)Compressor --- AC starting current (LRA)Condenser fan --- AC power input (1)Condenser fan --- AC max. power inputCondenser fan --- AC operative current (OA) (1)Condenser fan --- AC max. current (FLA)Condenser fan --- AC start ---up current (LRA)Evaporator fan --- AC power input (1)Evaporator fan --- AC operative current (OA) (1)Evaporator fan --- AC max. current (FLA) (2)Evaporator fan --- AC start ---up current (LRA)Evaporator air flowFreecooling air flowCondenser max. air flowOutdoor Sound Pressure Level (3)Indoor Sound Pressure Level (3)Max. ambient temperature (4)

kWkWkWAAAkWkWAAAkWAAAm3/hm3/hm3/hdB(A)dB(A)_C

12.712.02.564.87.046.00.680.783.53.57.40.482.42.45.323202530588055.059.051.0

12.010.22.604.97.046.00.680.783.53.57.40.482.42.45.323002700588055.063.051.0

14.512.73.276.110.050.00.690.783.33.57.40.834.34.810.624002550588058.062.048.5

13.811.23.306.110.050.00.720.783.53.57.40.794.24.810.624502840588057.066.048.5

REFRIGERATION CIRCUITSCompressor --- type / quantityRefrigerantExpansion deviceEvaporator coil --- tubes / fins materialCondenser coil --- tubes / fins material

---------------

Scroll / 1R407C

Thermostatic valveCopper / AluminiumCopper / Aluminium

AIR FILTRATIONMain air filter --- quantity / typeEfficiency (CEN---EU)Filter dimension (DX side)Filter dimension (FC side)

------mmmm

1 / PleatedG3

840 x 601 x 100840 x 601 x 100

EVAPORATOR FANQuantity / Type / Poles --- 1 / Plug / 4 2 / Plug / 4Driven / Motor protection --- Direct / IP54

CONDENSER FANQuantity / Type / Poles --- 1 / Axial / 4Driven / Motor protection --- Direct / IP54

Control system --- Single speed or continually variable speed, depending on condensingfan control chosen option

ELECTRIC HEATINGType / Steps --- Wires / 1Heating capacity kW 3.0 6.0Heating --- max. current A 6.5 13.0

CABINETFrame --- Galvanized steelPainting --- Polyester --- RAL7035

OVERALL DIMENSIONSWidth x Height x Depth mm 932 x 1901 x 640Weight kg 250 250 260 260

Notes:(1) – Values are referred to 35°C outdoor temperature, to nominal power supply and to the following Indoor conditions:

• 30°C / 39.5% R.H. at the evaporating suction side, for WM13 ---15MD models;• 27°C / 47% R.H. at the evaporating suction side, for WM13 ---15MO models.

(2) – Value is referred to nominal speed (factory set).(3) --- Measured with 35°C outdoor temperature, at 2 m from the unit, in free field conditions.(4) --- Maximum outdoor temperature referred to:

• 30°C / 39.5% R.H. at the evaporating suction side, for WM13 ---15MD models;• 27°C / 47% R.H. at the evaporating suction side, for WM13 ---15MO models.

Page 22: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

OverallDimensions

9

9--1

LiebertHPW---PD---273136---05.05.2011

OverallDimensions

Fig.1---Overalldimensions---LiebertHPWmodelsWM05---06SD

4601230

6050

15828

15

858

10038038038038070

50

800

1690

791370118

50450

60740

60370 45

TOPVIEW

FRONTVIEW

REARVIEW

SXSIDEVIEW

DXSIDEVIEW

450

N.5+5

holesø8forconditionerfixing

Electrical

supply

Conditionedairinlet

Conditionedairoutlet

Condensingairinlet

Freecoolingairoutlet

Freecoolingairinlet

Condensingairoutlet

Page 23: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

OverallDimensions

9--2

LiebertHPW---PD---273136---05.05.2011

Fig.2---Overalldimensions---LiebertHPWmodelsWM05---06SO

15828

15

858

6050

4601230

10038038038038070

50

800

1690

60740

60

50450

45370791370118

450

FRONTVIEW

REARVIEW

SXSIDEVIEW

DXSIDEVIEW

N.5+5

holesø8forconditionerfixing

TOPVIEW

Conditionedairinlet

Conditionedairoutlet

Condensingairinlet

Freecoolingairoutlet

Freecoolingairinlet

Condensingairoutlet

Electrical

supply

Page 24: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

OverallDimensions

9--3

LiebertHPW---PD---273136---05.05.2011

Fig.3---Overalldimensions---LiebertHPWmodelsWM06---08---10MD

FRONTVIEW

REARVIEW

SXSIDEVIEW

DXSIDEVIEW

TOPVIEW

Conditionedairinlet

Conditionedairoutlet

Condensingairinlet

Freecoolingairoutlet

Freecoolingairinlet

Condensingairoutlet

640

1901

932

640

960

1515

50

990

870

889

990

970 370370

1401 500

43148

241 390 390 390 390 100

470 11560

525 606060

60 2525

445

445

5050

N.5+5

holesø8forconditionerfixing

Electrical

supply

Liftwith

eyebolts

Page 25: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

OverallDimensions

9--4

LiebertHPW---PD---273136---05.05.2011

Fig.4---Overalldimensions---LiebertHPWmodelsWM06---08---10MO

FRONTVIEW

REARVIEW

SXSIDEVIEW

DXSIDEVIEW

TOPVIEW

Conditionedairinlet

Conditionedairoutlet

Condensingairinlet

Freecoolingairoutlet

Freecoolingairinlet

Condensingairoutlet

640

932

640

960

1515

50

990

1901

970 370370 43148

1401 500

241 390 390 390 390 100

445

445

5050

990

870

889

470 11560

525 606060

60 2525

N.5+5

holesø8forconditionerfixing

Electrical

supply

Liftwith

eyebolts

Page 26: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

OverallDimensions

9--5

LiebertHPW---PD---273136---05.05.2011

Fig.5---Overalldimensions---LiebertHPWmodelsWM13---15MD

FRONTVIEW

REARVIEW

SXSIDEVIEW

DXSIDEVIEW

TOPVIEW

Conditionedairinlet

Conditionedairoutlet

Condensingairinlet

Freecoolingairoutlet

Freecoolingairinlet

Condensingairoutlet

640

1901

932

43370965370153

49640

60870

60

990

58 525 60

25889

25

5501351

50445

44550Electrical

supplyø23

Liftwith

M10

eyebolts

N.5+5

holesø8forconditionerfixing

1515

960

990

390390 390 390241 100

Page 27: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

OverallDimensions

9--6

LiebertHPW---PD---273136---05.05.2011

Fig.6---Overalldimensions---LiebertHPWmodelsWM13---15MO

FRONTVIEW

REARVIEW

SXSIDEVIEW

DXSIDEVIEW

TOPVIEW

Conditionedairinlet

Conditionedairoutlet

Condensingairinlet

Freecoolingairoutlet

Freecoolingairinlet

Condensingairoutlet

640

1901

932

43370965370153

60870

60

990

6052558

25889

25

640

5015

960

15

990

5501351

100390390390390241

445

5050

445

Electrical

supply

N.5+5

holesø8forconditionerfixing

Liftwith

M10

eyebolts

Page 28: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

Installation10

Liebert HPW---PD---273136---05.05.2011 10 -- 1

Installation

Fig. 7 --- Service area --- Liebert HPW

HPW

A

B

Maintenance (A) and Operational (B), (E) areas

90o

= =

DA

C

E

HPW

Shelter

(PROTECTIVE ROOF)

F

HPW A (mm) B (mm) C (mm) D (mm) E (mm) F (*) (mm)

S---Models min. 900 min. 3500 800 450 min. 500 0

M---Models min. 900 min. 900 932 640 min. 2000 0

(*) No minimum distance from floor is required outside. Check internal needs.

Page 29: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

Installation

Liebert HPW---PD---273136---05.05.2011 10 -- 2

Fig. 8 --- Holes on the wall --- Liebert HPW models WM05---06SO/SD

min. 200 mm

33390

1740

40 140

49 760 49

390

770

390

Fig. 9 --- Installation of 1 unit

SECTION

Installation of 2 units

Page 30: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

Installation

Liebert HPW---PD---273136---05.05.2011 10 -- 3

Fig. 10 --- Holes on the wall --- Liebert HPW models WM06---08---10---13---15MO/MD

min. 200 mm

50 890 50

390

950

390

33390

40

350 190 350107(W

M13--15)

57(W

M06--08--10)

Installation of 1 unit

Installation of 2 units

SECTION

Page 31: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

Prin

ted

inIta

lyby

Lieb

ertH

IRO

SS

S.p

A.

Issu

edby

T.D

.Ser

vice

Since the Liebert HIROSS Company has a policy of continuousproduct improvement, it reserves the right to change design andspecifications without previous notice.

Il Fabbricante dichiara che questo prodotto è conforme alle direttive Europee:The Manufacturer hereby declares that this product conforms to the European Union directives:Der Hersteller erklärt hiermit, dass dieses Produkt den Anforderungen der Europäischen Richtlinien gerecht wird:Le Fabricant déclare que ce produit est conforme aux directives Européennes:El Fabricante declara que este producto es conforme a las directivas Europeas:O Fabricante declara que este produto está em conformidade com as directivas Europeias:Tillverkare försäkrar härmed att denna produkt överensstämmer med Europeiska Uniones direktiv:De Fabrikant verklaart dat dit produkt conform de Europese richtlijnen is:Vaimistaja vakuuttaa täten, että tämä tuote täyättää seuraavien EU---direktiivien vaatimukset:Produsent erklærer herved at dette produktet er i samsvar med EU---direktiver:Fabrikant erklærer herved, at dette produkt opfylder kravene i EU direktiverne:

Ο ΚατασÀευαστÞj δηλþνει üτι το παÃüν πÃοΪüν εßναι ÀατασÀευασmÝνο αýmφωνα mε τιj οδηγßεj τηj Ε.Ε.:

2006/42/EC; 2004/108/EC; 2006/95/EC; 97/23/EC

Page 32: Liebert HPW - Dataromskjøling€¦ · Index of Contents Liebert HPW---PD---273136---05.05.2011 Index of Contents Contents 1 Features and Benefits 2 Model Description and Selection

Surge Protection

AC Power

Connectivity

DC Power

Embedded Power

Monitoring

Outside Plant

Precision Cooling

Rack & Integrated Cabinets

Services

Emerson Network Power and the Emerson Network Power Iogo are trademarks and service marks of Emerson Electric Co. 2008 Emerson Electric Co.

Emerson Network Power

The global leader in Business--Critical Continuityt

Ensuring the High AvailabilityOf Mission--Critical Data and Applications

Emerson Network Power, a business of Emerson (NYSE:EMR), isthe global leader in enabling Business--Critical Continuitytfrom grid to chip for telecommunication networks, data centers,health care and industrial facilities. Emerson Network Powerprovides innovative solutions and expertise in areas includingAC and DC power and precision cooling systems, embeddedcomputing and power, integrated racks and enclosures, powerswitching and controls, monitoring, and connectivity. All solutionsare supported globally by local Emerson Network Power servicetechnicians. Liebert power, precision cooling and monitoringproducts and services from Emerson Network Power improve theutilization and management of data center and networktechnologies by increasing IT system availability, flexibility andefficiency. For more information, visit www.liebert.com,www.emersonnetworkpower.com orwww.eu.emersonnetworkpower.com

While every precaution has been taken to ensure the accuracyand completeness of this literature, Liebert Corporation assumesno responsibility and accepts no liability for damages resultingfrom use of this information or for any errors or omissions.E2008 Liebert Corporation.All rights reserved throughout the world. Specifications subject tochange without notice.Liebert and the Liebert logo are registered trademarks of LiebertCorporation. All names referred to are trademarks or registeredtrademarks of their respective owners.

Locations

Emerson Network Power -- Headquarters EMEAVia Leonardo Da Vinci 16/18

Zona Industriale Tognana35028 Piove di Sacco (PD) Italy

Tel: +39 049 9719 111Fax: +39 049 5841 257

[email protected]

Emerson Network Power -- Service EMEAVia Leonardo Da Vinci 16/18

Zona Industriale Tognana35028 Piove di Sacco (PD) Italy

Tel: +39 049 9719 111Fax: +39 049 9719 045

[email protected]

United States1050 Dearborn Drive

P.O. Box 29186Columbus, OH 43229Tel: +1 6148880246

Asia29/F The Orient Square Building

F. Ortigas Jr. Road, Ortigas CentrePasig City 1605 Philippines

Tel: +63 2 620 3600Fax: +63 2 730 9572

Embedded Computing

Power Switching & Control