TESTS ON TRANSFORMER
1. Open Circuit Test or No Load Test
2. Short Circuit Test
3. Polarity Test
-
Open Circuit Test or No - load Test
The low voltage side is supplied with rated voltage while the high voltage side is left open. Electrical measurements are done on the low voltage side.
-
occoreloss PP
oc
ocm
P
ER
2
oc
ocm
Q
EX
2
ocococ IES
22
ocococ PSQ
where:
Poc = reading of the wattmeter during the test (watt)Eoc = reading of the voltmeter during the test (volt)I oc = reading of the ammeter during the test (ampere)
-
Example:
The no - load current of a transformer is 4A at 0.25 pf when supplied at 250 V, 60 Hz. Determine the
a. core lossb. resistance representing the core
lossc. magnetizing reactance
-
wattspfIEP
PP
A
ocococ
occoreloss
25025.04250
.
250250
250
.
22
oc
ocm
P
ER
B
55.6424.968
250
24.9682501000
10004250
.
22
2222
oc
ocm
ocococ
ocococ
Q
EX
VARPSQ
VAIES
C
-
Short Circuit Test
The low voltage side is short circuited while the high voltage side is supplied with voltage adjusted so that the high side will draw rated high side current. Electrical measurements are done on the high voltage side.