LED fluorescent and - Bernlite · voltage LED boards (50-250V DC) - check with the Philips...

18
Emergency components for LED, fluorescent and auxiliary purpose OEM Emergency Portfolio Product Guide

Transcript of LED fluorescent and - Bernlite · voltage LED boards (50-250V DC) - check with the Philips...

Emergency components for LED, fluorescent and auxiliary purpose

OEM Emergency Portfolio

Product Guide

Hazel
Typewritten Text

ContentsIntroduction to this guide 3

LED Modules 4

PHL-EL3PHL-EL3-80PHL-EL3-DPHL-EL3-D80PHL-EL3-4PHL-EL3-S3W PHL-EL3-3W

Fluorescent Modules 9

PHF-EL3-L6PHF-EL3-3PHF-EL3-4PHF-EL3-5PHF-EL3-6 PHF-EL3-3/14PHF-EL3-4/14-24PHF-EL3-6/35-49PHF-EL3-6/28-54

PHF-EL3-6/55

Batteries 13

PHB-EL3-C3-SPHB-EL3-C3-FLPHB-EL3-C4-SPHB-EL3-C5-SPHB-EL3-C6-TSPHB-EL3-M3-SPHB-EL3-M3-TPHB-EL3-M4-TSPHB-EL3-M5-TSPHB-EL3-M6-TS

LED Auxilary, LED Indicators and Accessories 14

PHI-EL3-24PHI-EL3-30PPHI-EL3-LI PHI-EL3-L1D PHI-EL3-SR

Range Overview 16

Lamp Compatibility Chart 17

2

Introduction to this guideThe Philips OEM Emergency Portfolio offers a wide range of emergency lighting conversion components, required for the manufacture of emergency luminaires. The range supports the installation of emergency lighting schemes which comply with current regulations.

Thank you for choosing the Philips OEM Emergency Portfolio. In this guide you will find the specification information for the portfolio. For installation information please refer to the Installation Guide. As technology is continuously improving, we advise you to visit our website: www.philips.co.uk/oememergency for the latest details.

The Philips OEM Emergency Portfolio is the ideal choice for emergency lighting needs in a broad range of new construction and retrofit applications within the commercial sector, including offices, warehouses, schools, hospitals, public buildings, industrial and retail applications.

3

PHL-EL3 PHL-EL3-8012NC 919913998246 919913998247

Voltage Range 6-55 Volts 6-80 Volts

LED Current Limit 320mA 320mA

Battery Current Limit 1100mA 1100mA

Mains Supply Voltage 230-240V AC 230-240V AC

Mains Power 5 Watts 5 Watts

Mains Frequency 50/60Hz 50/60Hz

Power Factor 0.9 0.9

Charge Current 200mA 200mA

Recharge Time 24-Hours 24-Hours

Module Dimensions 165mm x 45mm x 29mm 165mm x 45m x 29mm

Module Weight 285g 285g

The units are suitable for use with the following Philips Emergency Batteries:

919913998263 PHB-EL3-C3-S 3.6V 4Ah NiCd BATTERY IN STICK FORMATION

919913998276 PHB-EL3-C3-FL 3.6V 4Ah NiCd BATTERY IN FLEXIBLE FORMATION

919913998267 PHB-EL3-M3-S 3.6V 4Ah NiMH BATTERY IN STICK FORMATION

919913998268 PHB-EL3-M3-T 3.6V 4Ah NiMH BATTERY IN TRIANGULAR FORMATION

The Emergency PHL-EL3 & PHL-EL3-80 are 3 hour emergency lighting converters designed to suit a wide range of LED types and circuits. The converter automatically adjust the output LED current to provide the best match between the battery and the load, providing maximum illumination whilst ensuring battery duration.

• PHL-EL3 for 2-20 LEDs in series (6-55V)

• PHL-EL3-80 for 2-30 LEDs in series (6-80V)

• Additional 3rd pole relay• Deep discharge protection• Compact enclosure• Constant current charger

PHL-EL3 & PHL-EL3-803 Hour EM Converter for 6-55V and 6-80V LED Loads

Technical Details

Emergency Portfolio

LED Components

4

The units are suitable for use with the following Philips Emergency Batteries:

919913998263 PHB-EL3-C3-S 3.6V 4Ah NiCd BATTERY IN STICK FORMATION

919913998276 PHB-EL3-C3-FL 3.6V 4Ah NiCd BATTERY IN FLEXIBLE FORMATION

PHL-EL3-D PHL-EL3-D8012NC 919913998248 919913998249

Voltage Range 6-55V 6-80V

LED Current Limit 320mA 320mA

Battery Current Limit 1100mA 1100mA

Mains Supply Voltage 230-240V AC 230-240V AC

Mains Power 5W 5W

Mains Frequency 50/60Hz 50/60Hz

Power Factor 0.9 0.9

Charge Current 200mA Nominal 200mA Nominal

Recharge Time 24-Hours 24-Hours

Module Dimensions 165mm x 45mm x 29mm 165mm x 45mm x 29mm

Module Weight 300g 300g

A 3Hr emergency lighting converter with DALI interface and automatic test function, designed to suit an extremely wide range of LED types and circuits. The DALI converter automatically adjusts the output LED current to provide the best match between the battery and the load, providing maximum illumination whilst ensuring full battery duration.

• PHL-EL3-D for 2-20 LEDs in series (6-55V)

• PHL-EL3-D80 for 2-30 LEDs in series (6-80V)

• 2-pole changeover relay• Additional 3rd pole relay• Deep discharge protection• Compact enclosure• Constant current charger

PHL-EL3-D & PHL-EL3-D80 3 Hour EM DALI Converter for 6-55V and 6-80V LED Loads

Technical Details

Emergency Portfolio

LED Components

5

The units are suitable for use with the following Philips Emergency Batteries:

919913998264 PHB-EL3-C4-S 4.8V 4Ah NiCd BATTERY IN STICK FORMATION

919913998269 PHB-EL3-M4-TS 4.8V NiMH BATTERY IN TWIN STICK FORMATION

The PHL-EL3-4 is a 3 hour emergency lighting conversion module designed to power suitable mains lamps (e.g. some GU10 & T8 LED tubes) and high voltage LED boards (50-250V DC) - check with the Philips technical team for compatibility. The PHL-EL3-4 automatically adjusts the output LED current to provide the best match between the battery and the load, providing maximum illumination whilst ensuring full battery duration.

PHL-EL3-43 Hour EM Converter for 50-250V LED Loads

• 2-pole changeover relay• Additional 3rd pole relay• Deep discharge protection• Compact enclosure• Constant current charger

12NC Mains supply Voltage

Battery Current Limit

Mains Power

Mains Frequency

Power Factor

Charge Current

Recharge Period Dimensions Module

weight

919913998250 230-240v AC 1100mA 5 Watts 50/60Hz 0.9200mA Nominal

24 Hours165mm x 45mm x 29mm

296g

Technical Details PHL-EL3-4

Emergency Portfolio

LED Components

6

The units are suitable for use with the following Philips Emergency Batteries:

919913998263 PHB-EL3-C3-S 3.6V 4Ah NiCd BATTERY IN STICK FORMATION

919913998276 PHB-EL3-C3-FL 3.6V 4Ah NiCd BATTERY IN FLEXIBLE FORMATION

919913998267 PHB-EL3-M3-S 3.6V 4Ah NiMH BATTERY IN STICK FORMATION

919913998268 PHB-EL3-M3-T 3.6V 4Ah NiMH BATTERY IN TRIANGULAR FORMATION

Technical Details PHL-EL3-S3W

The PHL-EL3-S3W is a complete quick & easy solution for LED mains/emergency applications. The unit is available to operate 3 Watt (700mA) constant current devices. The unit is designed to be used as a standalone unit and is able to pass through a 40mm cut out. The module is connected to the mains, battery and LED with simple irreversible plug & socket arrangements, for ease of installation.

PHL-EL3-S3W3 hour maintained driver for single 700mA LED with strain relief

12NC Voltage Range Power Rating - Non-Maintained

Power Rating - Maintained

Emergency Duration Charger Recharge

TimeBallast Lumen

output

919913998251220-240 Volts AC

50/60 Hz3.0 Watts 7.1 Watts 3 Hours 200mA 24 Hours 100%

Discharge Current Tc Max Operation Mode Output Load Output Current Mounting Hole

SizeModule Size L x

W x H Weight

1000mA70°C Module / 50°C Battery

Switchable Maintained/Non

Maintained3 Watt 700mA

Designed to fit through 40mm

Aperture

152mm x 26.5mm x 28.5mm (FC

144mm)163g

Emergency Portfolio

LED Components

7

The units are suitable for use with the following Philips Emergency Batteries:

919913998263 PHB-EL3-C3-S 3.6V 4Ah NiCd BATTERY IN STICK FORMATION

919913998276 PHB-EL3-C3-FL 3.6V 4Ah NiCd BATTERY IN FLEXIBLE FORMATION

919913998267 PHB-EL3-M3-S 3.6V 4Ah NiMH BATTERY IN STICK FORMATION

919913998268 PHB-EL3-M3-T 3.6V 4Ah NiMH BATTERY IN TRIANGULAR FORMATION

The emergency PHL-EL3-3W is a combined switchable mains & emergency LED converter. The unit is available to operate 3 Watt (700mA) constant current devices.

PHL-EL3-3W 3 hour maintained driver for single 700mA LED

12NC Input Voltage Power Rating - Non-Maintained

Power Rating - Maintained

Emergency Duration Charger Recharge

TimeBallast Lumen

output

919913998252220-240 Volts AC

50/60 Hz3.0 Watts 7.1 Watts 3 Hours 200mA 24 Hours 100%

Discharge Current Tc Max Operation Mode Output Load Output Current Module Size

L x W x H Weight

1000mA70°C Module / 50°C Battery

Switchable Maintained/ Non Maintained

1 x 3 Watt 700mA152mm x 26.5mm x

28.5mm (FC 144mm)

85g

Technical Details PHL-EL3-3W

Emergency Portfolio

LED Components

8

The units are suitable for use with the following Philips Emergency Batteries:

919913998266 PHB-EL3-C6-TS 7.2V 4Ah NiCd BATTERY IN TWIN STICK FORMATION

The PHF-EL3-L6 low line 3 hour duration emergency lighting single ended inverter is specifically designed to fit in low line and T5 Luminaire profiles and to ensure complete performance compatibility with all types of fluorescent 4 pin lamps and their associated control gear. The inverter employs cathode pre heating and continuous heating to optimise lamp performance. The specified circuit and operation are selected at the time of installation by the method of wiring and connection.

Features• 4 Pole changeover relay - for total isolation of the control

gear from the emergency inverter in the event of a test or emergency condition.

• Additional 5th pole HF relay• Low profile metal case to suit low line luminaire profiles.• Cathode Pre Heating • Constant Cathode Heating • Constant Current Emergency operation• Open Circuit Lamp detect • Deep discharge protection

PHF-EL3-L6 3 Hour Slimline EM Inverter Multi Watt

Technical Details PHF-EL3-L6

12NC Input Voltage

Power Rating Watts

Emergency Duration

Charge Current

Recharge Time

Cut-Off Voltage

Discharge Current

Ambient Temp.

TC Point

TC Max. Temp.

IP Rating

Module Size L x W x H

Overall Weight

919913998253

220-240 Volts AC – 50/60

Hz

5.3 Watts

3 Hours 200mA 24 Hours 6.0 Volts 1.05 Amp0°C to +50°C

Case Side

(Centre)70°C IP20

300mm x 31.5mm x 21mm

FC = 285mm

265g

Emergency Portfolio

Fluorescent Components

9

PHF-EL3-3 PHF-EL3-4 PHF-EL3-5 PHF-EL3-612NC 919913998254 919913998255 919913998256 919913998257

Input Voltage 220-240 Volts AC – 50/60 Hz

Power Rating Watts 4.7 Watts

Emergency Duration 3 Hours

Battery Voltage 3.6 Volts 4.8 Volts 6.0 Volts 7.2 Volts

Charge Current 200mA

Recharge Time 24 Hours

Cut-Off Voltage 3.0 Volts 4.0 Volts 5.0 Volts 6.0 Volts

Discharge Current 1.05 Amp

Ambient Temperature 0°C to +50°C

TC Point Case Side (Centre)

TC Max. Temperature 70°C

IP Rating IP20

Dimensions 165mm x 45mm x 29mm (FC 155mm)

Suitable Batteries 919913998263919913998276

919913998264 919913998265 919913998266

Module Weight 320g 320g 320g 320g

These 3 hour duration emergency lighting inverters are designed to suit multiple 4-pin fluorescent lamp wattages & circuits. The unit has the benefit of a 4 Pole changeover relay - for total isolation of the control gear from the emergency inverter in the event of a test or emergency condition. An additional 5th pole HF relay offers built in time delay to ensure the interconnected HF ballast does not see an open circuit condition when the fluorescent lamp is used in the emergency

condition. The deep discharge protection circuit on the battery completely cuts off the battery load when fully discharged. The constant current charger circuit maintains the battery at peak condition to provide 3 hours emergency duration. The changeover operation from mains to emergency operation occurs between 60 and 85% of mains voltage in accordance with BS-EN 61347-2-7.

PHL-EL3-3, PHL-EL3-4, PHL-EL3-5 & PHL-EL3-63 Hour EM Inverter 4-36W, 4-58W, 4-70W, 4-100W CFL & T8

Technical Details

Emergency Portfolio

Fluorescent Components

10

PHF-EL3-3/14PHF-

EL3-4/14-24PHF-

EL3-6/28-54PHF-

EL3-6/35-4912NC 919913998258 919913998259 919913998261 919913998260

Input Voltage 220-240 Volts AC – 50/60 Hz

Power Rating Watts 4.7 Watts

Emergency Duration 3 Hours

Battery Type 4.5Ah Nickel Cadmium

Battery Voltage 3.6 Volts 4.8 Volts 7.2 Volts

Charge Current 200mA

Recharge Time 24 Hours

Cut-Off Voltage 3.0 Volts 4.0 Volts 6.0 Volts

Discharge Current 1.05 Amp

Ambient Temperature 0°C to +50°C

TC Point Case Side (Centre)

TC Max. Temperature 70°C

IP Rating IP20

Module Size L x W x H 165mm x 45mm x 29mm (FC 155mm)

Suitable Batteries 919913998263919913998276

919913998264 919913998265 919913998266

Module Weight 320g 320g 320g 320g

These 3 hour duration emergency lighting inverters are designed to suit T5 (T16) fluorescent lamps. The unit has the benefit of a 4 Pole changeover relay - for total isolation of the control gear from the emergency inverter in the event of a test or emergency condition. An additional 5th pole HF relay offers built in time delay to ensure the interconnected HF ballast does not see an open circuit condition when the fluorescent lamp is used in the emergency condition. The deep discharge

protection circuit on the battery completely cuts off the battery load when fully discharged. The constant current charger circuit maintains the battery at peak condition to provide 3 hours emergency duration. The changeover operation from mains to emergency operation occurs between 60 and 85% of mains voltage in accordance with BS EN 60598-2-22.

PHF-EL3-3/14, PHF-EL3-4/14-24, PHF-EL3-6/35-49 & PHF-EL3-6/28-54 3 Hour EM Inverter for 14W, 14 & 24W, 35 & 49W, 28 & 54W T5 Lamps

Technical Details

Emergency Portfolio

Fluorescent Components

11

The units are suitable for use with the following Philips Emergency Batteries:

919913998266 PHB-EL3-C6-TS 7.2V 4Ah NiCd BATTERY IN TWIN STICK FORMATION

The PHF-EL3-6/55 3 hour duration emergency lighting inverter are designed for low mercury/amalgam type fluorescent lamps and is also suitable for use with free mercury type lamps (see lamp compatibility chart on page 17). The unit provides continuous lamp cathode heating and has the benefits of a 4 Pole changeover relay - for total isolation of the control gear from the emergency inverter in the event of a test or emergency condition. An additional 5th pole HF relay offers built in time delay to ensure the interconnected HF ballast does not see an open circuit condition

when the fluorescent lamp is used in the emergency condition. The deep discharge protection circuit on the battery completely cuts off the battery load when fully discharged. The constant current charger circuit maintains the battery at peak condition to provide 3 hours emergency duration. The changeover operation from mains to emergency operation occurs between 60 and 85% of mains voltage in accordance with BS EN 60598-2-22.

PHF-EL3-6/553 Hour EM Inverter for Amalgam and 2D Lamps up to 55W

Technical Details PHF-EL3-6/55

12NC Input Voltage Power Rating Watts

Emergency Duration Battery Type Battery

VoltageCharge Current Recharge Time

919913998262220-240 Volts AC – 50/60 Hz

4.7 Watts 3 Hours4.5Ah Nickel

Cadmium7.2 Volts 200mA 24 Hours

Cut-Off Voltage Discharge Current Ambient Temp. TC Point TC Max. Temp. IP Rating Module Size

L x W x HModule Weight

6.0 Volts 1.05 Amp 0°C to +50°C Case Side (Centre) 70°C IP20165mm x 45mm x

29mm (FC 155mm)370g

Emergency Portfolio

Fluorescent Components

12

919913998263 PHB-EL3-C3-S 3.6V 4Ah NiCd BATTERY IN STICK FORMATION 220mm long x 37mm diameter f/c 205mm – 382g

919913998276 PHB-EL3-C3-FL 3.6V 4Ah NiCd BATTERY IN FLEXIBLE FORMATION 270mm long x 38mm – 399g

919913998264 PHB-EL3-C4-S 4.8V 4Ah NiCd BATTERY IN STICK FORMATION 280mm long x 37mm diameter f/c 265mm – 506g

919913998265 PHB-EL3-C5-S 6V 4Ah NiCd BATTERY IN STICK FORMATION 340mm long x 37mm diameter f/c 325mm – 633g

919913998266 PHB-EL3-C6-TS 7.2V 4Ah NiCd BATTERY IN TWIN STICK FORMATION 2 x 220mm long x 37mm diameter

f/c 205mm each – 756g

919913998267 PHB-EL3-M3-S 3.6V 4Ah NiMH BATTERY IN STICK FORMATION243mm long x 21mm high x 22mm wide

f/c 230mm – 198g

919913998268 PHB-EL3-M3-T3.6V 4Ah NiMH BATTERY

IN TRIANGULAR FORMATION70.5mm long x 37.5mm diameter – 210g

919913998269 PHB-EL3-M4-TS 4.8V NiMH BATTERY IN TWIN STICK FORMATION2x 170mm long x 21mm high x 22mm wide

f/c 160mm each – 273g

919913998270 PHB-EL3-M5-TS 6V NiMH BATTERY IN TWIN STICK FORMATION1 x 170mm long x 21mm high x 22mm wide

& 1 x 243mm long x 21mm high x 22mm f/c 160mm & 230mm – 331g

919913998271 PHB-EL3-M6-TS 7.2V NiMH BATTERY IN TWIN STICK FORMATION2 x 243mm long x 21mm high x 22mm wide

f/c 230mm each – 399g

Philips Emergency Lighting range of batteries are available in both nickel cadmium (NiCd) and nickel metal hydride (NiMH) compositions and in varying configurations to meet the needs of a wide range of luminaire dimensions. The 4Ah capacity of the batteries provides 3 hours duration when used in conjunction with Philips emergency lighting modules. It is recommended by the British Standards that emergency lighting batteries are changed every four years. The NiCd batteries have a temperature limit of 55°C and the NiMH batteries have a temperature limit of 50°C. All the batteries are supplied with an irreversible plug and socket arrangement.

The dimensions and weights of the batteries is as follows:

Philips Emergency Batteries

Emergency Portfolio

Batteries

13

The PHI-EL3-24 is a constant current 110° wide beam 3W LED complete with bi-colour charge LED. The unit is designed to fit in a variety of louvered luminaires.

PHI-EL3-24 Single Point 700mA Device for Downlight Applications

Mounting To Wall Between Fittings

Height 0.5 1.0 0.5 1.0

2.5 3.3 2.9 7.0 6.4

3.0 3.7 3.1 8.0 7.2

4.0 4.3 3.2 9.8 8.4

5.0 4.5 3.3 11.2 8.8

6.0 4.6 2.8 12.1 9.0

8.0 4.4 - 12.7 6.1

Spacing Table (in metres)

Technical Information

Input Voltage

Power Rating

Max. Forward Current

Beam Angle Cut Out

Light Source Colour

Colour Temp.

Emitter Luminous

Flux

General CRI Tc Max Wiring

Method Dimensions Weight

4V DC Max 3 watts 700mA 110°48mm x 12.5mm

Cool White

6800K 114 Lumens 72.380°C LED Backplate

Series connection

only via C4201

Series Plug

50mm x 16mm x

18mm (22mm inc. lead)

24g

Emergency Portfolio

Auxiliary

14

The PHI-EL3-30P is a constant current 110° wide beam 3W LED complete with bi-colour charge LED for use in downlighters.

PHI-EL3-30P Single Point 700mA Device for Louvre Applications

Mounting To Wall Between Fittings

Height 0.5 1.0 0.5 1.0

2.5 3.8 3.1 9.2 7.4

3.0 4.1 3.2 10.0 8.0

4.0 4.5 3.1 11.0 8.8

5.0 4.6 2.2 12.0 9.0

6.0 4.2 n/a 12.6 8.3

8.0 1.0 n/a 12.3 1.4

Spacing Table (in metres)

Input Voltage

Power Rating

Max. Forward Current

Beam Angle

Light Source Colour

Colour Temp.

Luminaire Output

General CRI Tc Max Wiring Method Dimensions Weight

4V DC Max 3 watts 700mA 110°Cool

White6000K

123 Lumens

78.980°C LED Backplate

Series connection only via C4201

Series Plug

Ø 23mm x 50mm

42g

Technical Information

Emergency Portfolio

Auxiliary

15

12NC Product Code Product Description

LED Modules

919913998246 PHL-EL3 3 HOUR EM CONVERTER FOR 6-55V LED LOADS

919913998247 PHL-EL3-80 3 HOUR EM CONVERTER FOR 15-80V LED LOADS

919913998248 PHL-EL3-D 3 HOUR EM DALI CONVERTER FOR 6-55V LED LOADS

919913998249 PHL-EL3-D80 3 HOUR EM DALI CONVERTER FOR 15-80V LED LOADS

919913998250 PHL-EL3-4 3 HOUR EM CONVERTER FOR 50-250V LED LOADS

919913998251 PHL-EL3-S3W 3 HOUR MAINTAINED DRIVER FOR SINGLE 700mA LED WITH STRAIN RELIEF

919913998252 PHL-EL3-3W 3 HOUR MAINTAINED DRIVER FOR SINGLE 700mA LED

Flourescent Modules

919913998253 PHF-EL3-L6 3 HOUR SLIMLINE EM INVERTER MULTI WATT

919913998254 PHF-EL3-3 3 HOUR EM INVERTER 4-36W CFL & T8

919913998255 PHF-EL3-4 3 HOUR EM INVERTER 4-58W CFL & T8

919913998256 PHF-EL3-5 3 HOUR EM INVERTER 4-70W CFL & T8

919913998257 PHF-EL3-6 3 HOUR EM INVERTER 4-100W CFL & T8

919913998258 PHF-EL3-3/14 3 HOUR EM INVERTER FOR 14W T5 LAMPS

919913998259 PHF-EL3-4/14-24 3 HOUR EM INVERTER FOR 14 & 24W T5 LAMPS

919913998260 PHF-EL3-6/35-49 3 HOUR EM INVERTER FOR 35 & 49W T5 LAMPS

919913998261 PHF-EL3-6/28-54 3 HOUR EM INVERTER FOR 28 & 54W T5 lamps

919913998262 PHF-EL3-6/55 3 HOUR EM INVERTER FOR AMALGAM & 2D / PLQ LAMPS UP TO 55W

Batteries

919913998263 PHB-EL3-C3-S 3.6V 4Ah NiCd BATTERY IN STICK FORMATION

919913998276 PHB-EL3-C3-FL 3.6V 4Ah NiCd BATTERY IN FLEXIBLE FORMATION

919913998264 PHB-EL3-C4-S 4.8V 4Ah NiCd BATTERY IN STICK FORMATION

919913998265 PHB-EL3-C5-S 6V 4Ah NiCd BATTERY IN STICK FORMATION

919913998266 PHB-EL3-C6-TS 7.2V 4Ah NiCd BATTERY IN TWIN STICK FORMATION

919913998267 PHB-EL3-M3-S 3.6V 4Ah NiMH BATTERY IN STICK FORMATION

919913998268 PHB-EL3-M3-T 3.6V 4Ah NiMH BATTERY IN TRIANGULAR FORMATION

919913998269 PHB-EL3-M4-TS 4.8V NiMH BATTERY IN TWIN STICK FORMATION

919913998270 PHB-EL3-M5-TS 6V NiMH BATTERY IN TWIN STICK FORMATION

919913998271 PHB-EL3-M6-TS 7.2V NiMH BATTERY IN TWIN STICK FORMATION

LED Auxiliary919913998272 PHI-EL3-24 SINGLE POINT 700mA DEVICE FOR DOWNLIGHT APPLICATIONS

919913998273 PHI-EL3-30P SINGLE POINT 700mA DEVICE FOR LOUVRE APPLICATIONS

LED Indicator919913998274 PHI-EL3-LI GREEN CHARGE INDICATING LED WITH HOLDER

919913998237 PHI-EL3-L1D BI COLOUR CHARGE INDICATING LED WITH HOLDER FOR DALI MODULES

Accessory 919913998275 PHI-EL3-SR CEILING RECESSABLE CHARGE LED HOLDER

Range Overview

Philips charge indicators are available in two formats. The PHI-EL3-LI has a green lens and is compatible with most of our modules. The PLI-EL3-LI-D is bi colour and would be compatible with the PHL-EL3-D and PHL-EL3-D80 modules. This version is lit green in standard operation and flashes red to indicate a fault. All charge LEDs are supplied with a 500mm lead for connection to the module and a mounting collar. If there is no space to mount the indicator to the body of a luminaire, then the PHI-EL3-SR can be used to recess the indicator into the ceiling adjacent to the fitting.

PHI-EL3-LI, PHI-EL3-L1D and PHI-EL3-SRGreen Charge Indicating LED With HolderBi Colour Charge Indicating LED With Holder For DALI ModulesCeiling Recessable Charge LED Holder

16

*Recommended option in bold

Auxiliary

Wat

tage

Lam

p t

ype

PH

F-E

L3-3

PH

F-E

L3-4

PH

F-E

L3-5

PH

F-E

L3-3

/14

PH

F-E

L3-4

/14-

24

PH

F-E

L3-6

/28-

54

PH

F-E

L3-6

/35-

49

PH

F-E

L3-6

/55

PH

F-E

L3-L

6

4 T5 28 33 39

5 TC-EL 25 29 35

7 TC-EL 20 24 28

8 T5 18 21 25

9 TC-EL 19 22 26

10 TC-DEL 15 18 21

11 TC-EL 18 21 26

13 TC-DEL 16 18 22

14 T5 15 21 34

14 PL-R 34

16 TC-DD 13 15 18

17 PL-R 28

18 TC-L 12 14 16 5

18 TC-F 12 14 16 5 23

18 TC-DEL 12 14 17 9

18 TC-TEL 13 15 18 9

18 T8 12 14 16

21 T5 23

22 T5-CIR 19

24 T5 15 20

24 TC-L 11 12 15 7 18

24 TC-F 11 12 15 7 18

26 TC-DEL 10 12 14 8 15

26 TC-TEL 6 11 13 9 14

28 T5 20 17

28 TC-DD 10 11 13 10 15

32 TC-TEL 7 11

34 TC-L 8 9 11 5 12

35 T5 17 14

36 TC-L 8 9 11 5 12

36 T8 8 9 11 12

36 TC-F 8 9 11 6 12

38 TC-DD 8 10 6 11

39 T5 12

40 T5-CIR 8 9

40 TC-L 9 11 11

42 TC-TEL 9 9

49 T5 13 10

54 T5 12 9

55 T5-CIR 6 7

55 TC-L 7

55 TC-DD 3 8

57 TC-TEL 6

58 T8 7 8 7

70 T8 7 6

80 T5 6

80 TC-L 5

Lamp compatibility chart and BLF%

17

Contact details:

Guildford

Philips Lighting, Philips Centre, Guildford Business

Park, Guildford, GU2 8XH

Tel: 0845 601 1283

Dublin

Philips Electronics Ireland Ltd, Philips House, South

County Business Park, Leopardstown, Dublin 18

Tel: +353 1 764 0000

Email: [email protected]

www.philips.co.uk/lighting

www.philips.com/fortimo

www.philips.com/technology

© 2014 Royal Philips N.V. All rights reserved. Philips reserves the right to make changes inspecifcations and/or to discontinue any product at any time without notice or obligation andwill not be liable for any consequences resulting from the use of this publication.08/2014