Lecture 17
Transcript of Lecture 17
SYNCHRONOUS MACHINE MODELS – 1
ByProf. C. Radhakrishna
10/17/2010 10:19 AM 2
CONTENTSSYNCHRONOUS MACHINE MODELS – 1
Synchronous Machine Theory and Modelling
Direct and Quadrature Axes
Mathematical Description of a Synchronous Machine
Representation in System Studies
Typical values of standard parameters
Simplifications essential for large-scale studies
Neglect of Stator pψ Terms
Neglecting the Effect of Speed Variations on Stator Voltages
Simplified model with Amortisseurs NeglectedConstant Flux Linkage ModelClassical ModelConstant Flux Linkage Model Including the Effects of Subtransient CircuitsSummary of Simple Models for Different Time Frames
10/17/2010 10:19 AM 3
SYNCHRONOUS MACHINE MODELS – 1Synchronous Machine Theory and Modelling
• The power system stability problem is largely one of keepinginterconnected synchronous machines in synchronism.
• An understanding of their characteristics and accuratemodeling of their dynamic performance are of fundamentalimportance to the study of power system stability.
Direct and Quadrature Axes• Magnetic circuits and all rotor windings are symmetrical with
respect to both polar axis and the inter-polar axis.• The direct (d) axis, centred magnetically in the centre of
the north pole;• The quadrature (q) axis, 90 electrical degrees ahead of the
d-axis.• The position of the rotor relative to the stator is measured
by the angle θ between the d-axis and the magnetic axis ofphase 'a' winding.
10/17/2010 10:19 AM 4
10/17/2010 10:19 AM 5
10/17/2010 10:19 AM 6
10/17/2010 10:19 AM 7
10/17/2010 10:19 AM 8
10/17/2010 10:19 AM 9
In developing equations of a synchronous machine,assumptions are made
Representation in System Studies
Mathematical Description of a Synchronous Machine
The swing equation, expressed as two first order differentialequations, becomes
1 ( )2
rm e D r
d T T Kdt H
0 rddt
In the above equations, time t is in seconds, rotor angle δ is inelectrical radians, and ω0 is equal to 2πf. We will assume thevariables ∆ωr, Tm and Te to be in per unit. However, t will beexpressed in seconds and ω0 in electrical radians per second.
10/17/2010 10:19 AM 10
10/17/2010 10:19 AM 11
Typical values of standard parameters
Table 1
d q q d q dX X X X X X
0 0d d d d kdT T T T T
0 0q q q qT T T T
10/17/2010 10:19 AM 12
Table 1
Parameter Hydraulic Units Thermal Units
Synchronous ReactanceXd 0.6 – 1.5 1.0 – 2.3
Xq 0.4 – 1.0 1.0 – 2.3
Transient Reactance
0.2 - 0.5 0.15 – 0.4
- 0.3 – 1.0
Subtransient Reactance
0.15 – 0.35 0.12 – 0.25
0.2 – 0.45 0.12 – 0.25
Transient OC Time Constant
1.5 – 9.0 s 3.0 – 10.0 s
- 0.5 – 2.0 s
Subtransient OC Time Constant
0.01 – 0.05 s 0.02 – 0.05 s
0.01 – 0.09 s 0.02 – 0.05 s
Stator Leakage Inductance X1 0.1 – 0.2 0.1 – 0.2
Stator Resistance Ra 0.002 – 0.02 0.0015 – 0.005
dX
qX
dX
qX
0dT
0qT
0dT
0qT
10/17/2010 10:19 AM 13
Simplifications essential for large-scale studiesFor stability analysis of large systems, it is necessary to
neglect the following for stator voltage:• The transformer voltage terms, pψd and pψq• The effect of speed variations.
Neglect of Stator pψ Terms• The pψd and pψq terms represent the stator transients.• With these terms neglected, the stator quantities contain
only fundamental frequency components and the statorvoltage equations appear as algebraic equations.
• This allows the use of steady-state relationships forrepresenting the interconnecting transmission network.
Neglecting the Effect of Speed Variations on Stator Voltages• The assumption of per unit ωr = 1.0 (i.e., ωr = ω0 rad/s) in the
stator voltage equations does not contribute to computationalsimplicity in itself.
• The primary reason for making this assumption is that itcounterbalances the effect of neglecting pψd, pψq terms so far asthe low-frequency rotor oscillations are concerned.
10/17/2010 10:19 AM 14
• The first order of simplification to the synchronous machinemodel is to neglect the amortisseur effects.• It may contribute to reduction in computational effort byreducing the order of the model and allowing larger integrationsteps in time-domain simulations.
Simplified model with Amortisseurs Neglected
For studies in which the period of analysis is small incomparison to , the machine model is often simplified byassuming (or ψfd) constant throughout the study period.This assumption eliminates the only differential equationassociated with the electrical characteristics of the machine.A further approximation, which simplifies the machine modelsignificantly, is to ignore transient saliency byassuming , and to assume that the flux linkage ψ1qalso remains constant. With these assumptions, the voltagebehind the transient impendencehas a constant magnitude.
Constant Flux Linkage Model:Classical Model
0dT
qE
d qX X
a dR jX
10/17/2010 10:19 AM 15
This model offers considerable computational simplicity; it allowsthe transient electrical performance of the machine to berepresented by a simple voltage source of fixed magnitudebehind an effective reactance. It is commonly referred to as theclassical model, since it was used extensively in early stabilitystudies.
Constant Flux Linkage Model Including the Effects of Subtransient Circuits
Figure 1 Simplified transient model
This model is used in short-circuit programs for computing theinitial value of the fundamental frequency component of short-circuit currents. As the rotor flux linkages cannot changeinstantaneously, the value is equal to its prefault value. Such aconstant flux linkage model would not be generally acceptable forstability studies.
10/17/2010 10:19 AM 16
Summary of Simple Models for Different Time Frames
• Simple models of the synchronous machine applicable to the three timeframes; subtransient, transient, and steady state.
• The subtransient and transient models assume constant rotor fluxlinkages, and the steady-state model assumes constant field current.
• These models neglect saliency effects and stator resistance and offerconsiderable structural and computational simplicity.
Figure 2 Simplified model for subtransient period
10/17/2010 10:19 AM 17
is the predisturbance value of internal voltage given by
(a) Subtransient model
0E
0 0 0t tE E jX I
is the internal voltage
(b) Transient model
0E
0 0 0t tE E jX I
10/17/2010 10:19 AM 18
(c) Steady-state model
Figure 3: Simple Synchronous Machine Models
0 0q t s tE E jX I
q ad fd IE X i E
REFERENCES :[ 1 ] P.M. Anderson & A.A. Fouad : “Power System Control and Stability” , 2nd edition, IEEE Press
Power Engineering Series, Wiley-Interscience, 2003.[ 2 ] K.R. Padiyar : “Power System Dynamics : Stability and Control” , 2nd edition, BS
Publications, 2002.
10/17/2010 10:19 AM 19
CONCLUSIONS
10/17/2010 10:19 AM 20
THANK YOU