Page 1: #LEAN!GENT&3 # 3YSTEM - · PDF file• IMO guidelines MSC/Circ. 776, 848 ... • Tested and approved according to MSC/circ.848. • Approved by a number of authorities for filling
Page 2: #LEAN!GENT&3 # 3YSTEM - · PDF file• IMO guidelines MSC/Circ. 776, 848 ... • Tested and approved according to MSC/circ.848. • Approved by a number of authorities for filling
Page 3: #LEAN!GENT&3 # 3YSTEM - · PDF file• IMO guidelines MSC/Circ. 776, 848 ... • Tested and approved according to MSC/circ.848. • Approved by a number of authorities for filling
Page 4: #LEAN!GENT&3 # 3YSTEM - · PDF file• IMO guidelines MSC/Circ. 776, 848 ... • Tested and approved according to MSC/circ.848. • Approved by a number of authorities for filling

Brassbell ASNye Vakåsvei 78 VV1395 Hvalstad, Norway

TelTT +47 66 85 33 80Fax +47 66 85 33 81

[email protected]

total f ire protection one supplier

tehcnologyfire

Physical Properties of Clean Agent FS 49 C2®

Commonly used name Clean Agent FS 49 C2Trade name FS 49 C2Technical denominationTT HFC 3-4-9 C2/(R866)Application Total flooding systemsTT

Environmental PropertiesOzone Depleting Potential (ODP) 0Global Warming Potential (HGWP) 0,35

Physical PropertiesMolecular Weight 99,49Boiling Point °C Lowest –78,5Liquid Density @ 20°C kg/dm3 1,19Vapour Pressure @ 20°C bar 14,9

Extinguishing Concentrationsn-heptane, cup burner % by vol. 8,5REMP value, agent/fuel ratio 10 – 13Inerting Concentration % by vol. 12 - 14(Flammability limit, propane)

Acute ToxicityALC LC50 4 hrs % by vol. >50NOAL % by vol. >13LOAL % by vol. >15

Approved/Accepted and/or Tested by• Swedish Maritime Administration

• Norwegian Maritime Directorate

• Finnish Maritime Directorate

• Danish Maritime Authority

• American Bureau of Shipping – ABS

• Maritime & Port Authority of Singapore

• Marine Administration, Isle of Man

• Swedish Armed Forces

• Norwegian Armed Forces

• Institute of Science and TechnologyTTDepartment of Fire Safety Engineering,University of Lund, Sweden

• SP, Swedish National Testing & ReseaTT rch Institute

• ISO norms by SP

• CEA norms by SP

• IMO guidelines MSC/Circ. 776, 848

Clean Agent FS 49 C2® SystemHalon 1301 Replacement Systems

• M.E.D - Marine Equipment Directive 96/98/EC

• Germanischer Lloyd

• Bureau Veritas

• Maritime and Coastguard Agency (MCA)

Page 5: #LEAN!GENT&3 # 3YSTEM - · PDF file• IMO guidelines MSC/Circ. 776, 848 ... • Tested and approved according to MSC/circ.848. • Approved by a number of authorities for filling

Brassbell ASNye Vakåsvei 78VV1395 Hvalstad, Norway

TelTT +47 66 85 33 80Fax +47 66 85 33 81

[email protected]

total f ire protection one supplier

??????????????

TECHNICAL CONTAINER DATADATAA ATT SPECIFICATIONAA NOTES

Norm 1999/36/EEC (TPED) Pi ( ) marked

Material 34CrMo4

Finish RAL 3000 Red

Test PTT ressure 250 bar

Approval By a Notified Body

Outlet Connection 3/4” BSP

Supplied With CylinderSiphon tube, 20 mmValve 18 DSafety Burst Disc,190 barFilling ValvePressure SwitchPressure Gauge, 0 – 100 barSafety Outlet Plug

CE approved and BAM tested

Optional

Actuators Electrical

Pneumatic

Mechanical

Pyrotechnical or Solenoid Valve

Single Pneumatic, Combined Pneumatic

Hand Knob Release, Wire Pull deviceCombined release devices

BS 2,7 - 4,0Steel Containers with Differential Pressure Valve

for the CLEAN AGENT FS 49 C2® Extinguishing Agent

FEATURES• All components comply fully with international

regulations for land and marine use.

• Approved according to SOLAS by a variety of shipping and offshore authorities.

• Tested and appTT roved according to MSC/circ.848.

• Approved by a number of authorities for filling density up to 1,01 kg/litre and 52 bar.

• Allows functionary test without loss of extinguishing agent.

• The discharge valve 18-D series B04670000 has beensubjected to extensive laboratory testing.

• Certified by Lloyds Register.

Page 6: #LEAN!GENT&3 # 3YSTEM - · PDF file• IMO guidelines MSC/Circ. 776, 848 ... • Tested and approved according to MSC/circ.848. • Approved by a number of authorities for filling
Page 7: #LEAN!GENT&3 # 3YSTEM - · PDF file• IMO guidelines MSC/Circ. 776, 848 ... • Tested and approved according to MSC/circ.848. • Approved by a number of authorities for filling

Brassbell ASNye Vakåsvei 78 1395 Hvalstad, Norway

Tel +47 66 85 33 80Fax +47 66 85 33 81

[email protected]

total f ire protection one supplier

TECHNICAL CONTAINER DATADATA SPECIFICATION NOTES

Norm 1999/36/EEC (TPED) Pi ( ) marked

Material 34CrMo4

Finish RAL 3000 Red

Test Pressure 250 bar

Approval By a Notified Body

Outlet Connection 3/4” BSP

Supplied With CylinderSiphon tube, 20 mmValve 18 D Safety Burst Disc,190 barFilling ValvePressure SwitchPressure Gauge, 0 – 100 barSafety Outlet Plug

CE approved and BAM tested

Optional

Actuators Electrical

Pneumatic

Mechanical

Pyrotechnical or Solenoid Valve

Single Pneumatic, Combined Pneumatic

Hand Knob Release, Wire Pull deviceCombined release devices

BS 13,4 - 30Steel Containers with Differential Pressure Valve

for the CLEAN AGENT FS 49 C2® Extinguishing Agent

FEATURES• All components comply fully with international regulations for land and marine use.

• Approved according to SOLAS by a variety of shipping and offshore authorities.

• Tested and approved according to MSC/circ.848.

• Approved by a number of authorities for filling density up to 1,01 kg/litre and 52 bar.

• Allows functionary test without loss of extinguishing agent.

• The discharge valve 18-D series B04670000 has been subjected to extensive laboratory testing.

• Type approved by among others GL (Germanischer Lloyd)

Page 8: #LEAN!GENT&3 # 3YSTEM - · PDF file• IMO guidelines MSC/Circ. 776, 848 ... • Tested and approved according to MSC/circ.848. • Approved by a number of authorities for filling
Page 9: #LEAN!GENT&3 # 3YSTEM - · PDF file• IMO guidelines MSC/Circ. 776, 848 ... • Tested and approved according to MSC/circ.848. • Approved by a number of authorities for filling

B 0431 810

,0 B 0431 1 20 8 1020 2

B 0431 1 2 1370

Page 10: #LEAN!GENT&3 # 3YSTEM - · PDF file• IMO guidelines MSC/Circ. 776, 848 ... • Tested and approved according to MSC/circ.848. • Approved by a number of authorities for filling

Brassbell ASNye Vakåsvei 78VV1395 Hvalstad, Norway

TelTT +47 66 85 33 80Fax +47 66 85 33 81

[email protected]

total f ire protection one supplier

technologyfire

TECHNICAL CONTAINER DATADATAA ATT SPECIFICATIONAA NOTES

Norm 1999/36/EEC (TPED) Pi ( ) marked

Material 34CrMo4

Finish RAL 3000 Red

Test PTT ressure 250 bar

Approval By a Notified Body

Outlet Connection 1 1/2” BSP

Supplied With CylinderSiphon tube, 38 mmValve 38 D Safety Burst Disc,190 barFilling ValvePressure SwitchPressure Gauge, 0 – 100 barSafety Outlet Plug

CE approved and BAM tested

Optional

Actuators Electrical

Pneumatic

Mechanical

Pyrotechnical or Solenoid Valve

Single Pneumatic, Combined Pneumatic

Hand Knob Release, Wire Pull deviceCombined release devices

BS 45,0-80,0Steel Containers with Differential Pressure Valve

for the CLEAN AGENT FS 49 C2® Extinguishing Agent

FEATURESAll components comply fully with internationalregulations for land and marine use.

• Approved according to SOLAS by a variety of shipping and offshore authorities.

• Tested and appTT roved according to MSC/circ.848.

• Approved by a number of authorities for filling density up to 1,01 kg/litre and 52 bar.

• Allows functionary test without loss of extinguishing agent.

• The discharge valve 38-D series B04680000 has been subjected to extensive laboratory testing.

• Type approved by among others GL (Germanischer Lloyd)

Page 11: #LEAN!GENT&3 # 3YSTEM - · PDF file• IMO guidelines MSC/Circ. 776, 848 ... • Tested and approved according to MSC/circ.848. • Approved by a number of authorities for filling

Brassbell ASNye Vakåsvei 78 VV1395 Hvalstad, Norway

TelTT +47 66 85 33 80Fax +47 66 85 33 81

[email protected]

total f ire protection one supplier

technologyfire

RELEASE DEVICES AND ACCESSORIES

Solenoid valve with adapter. Delivered with steel tube complete including adapters for connection between solenoid valve and pneumatic release device.

Pre bent tube set for release of master container. Con-necting Solenoid valve with the release device.

Electrically operated pyrotechnical release plunger.Operates with all fire alarm and release cabinets

Pneumatic Release Plunger operating with pressurefrom solenoid valve or pilot, slave or master cylinder.

Strike Knob Release Device. Pull the safety ring and strike the knob to release the valve.

Wire Release Device operated by pulling on wire.

Pressure Switch to monitor the pressure in the container to avoid leakage of the extinguishing agent. Complete with o-ring and sintered metal filter.

Pilot Release Hose. Stainless steel high pressure tubeComplete including adapters.

Volume (Litre) TypeTT Filling weight (kg) D (mm) H1 (mm) H2(mm) TaTT re (kg)*

45,0 BS45,0-38 D 30,0 - 45,0 267 1045 1220 52-58

67,5 BS67,5-38 D 45,0 - 68,0 267 1490 1665 69-76

80,0 BS80,0-38 D 68,0 - 80,0 267 1755 1930 97-102

* Excluding release devices

WARNING!The safety cap must be installed on the discharge outlet whenever a charged cylinder/valve assembly is not connected to the system piping.

Failure to install the safety cap could result in violent movement of the container in the event of inadvertentactuation. Failure to follow these instructions could result in serious injury to personnel and damage to property.

Page 12: #LEAN!GENT&3 # 3YSTEM - · PDF file• IMO guidelines MSC/Circ. 776, 848 ... • Tested and approved according to MSC/circ.848. • Approved by a number of authorities for filling

Brassbell ASNye Vakåsvei 78 1395 Hvalstad, Norway

Tel +47 66 85 33 80Fax +47 66 85 33 81

[email protected]

total f ire protection one supplier

Sigma XTExtinguishant Control Panel

History

Until recently, the design and function-ality of one of the most important piec-

protection extinguishing systems (the

by a commonstandard.This changed in 2003 with the publication of EN12094-

(Components for gas extinguishing systems, requirements and test meth-ods for electrical automatic control and

the functionality and test methods for the control equipment thus enabling

-tion.Now, BS7273-1:2006 the Code of

-tion measures (Electrical actuation of

systems), contains direct references to control and indicating equipment stan-dard EN12094-1:2003.

Extinguishant Control Panel

Sigma XT is a new generation extin-guishant releasing panel which is fully compliant with European standard BS EN12094-1.

-nents for gasextinguishing systems).

options and easy to install construction make Sigma XT panels the ideal choice for small to medium sized systems us-ing all extinguishant agents.

Page 13: #LEAN!GENT&3 # 3YSTEM - · PDF file• IMO guidelines MSC/Circ. 776, 848 ... • Tested and approved according to MSC/circ.848. • Approved by a number of authorities for filling

Brassbell ASNye Vakåsvei 78 1395 Hvalstad, Norway

Tel +47 66 85 33 80Fax +47 66 85 33 81

[email protected]

total f ire protection one supplier

FEATURES

lease

delays

option

latching zone inputoption to receive signals from other systems such as aspirating equipment

up to 60 seconds in 5 second steps

up to 5 minutes in 5 second steps

ing until release

PRODUCT OVERVIEW

highest standards in a quality con-trolled environment and with European EN12094-1 approvals, the Sigma XT extinguishant releasing panel offers out-standing value and performance for all

-tions.

to activate from any combination of detec-tion zone inputs to allow (among other combinations) any two from three type activations such as would be required for detection in ceiling void, room and

the Sigma XT allow the functionality of the

still complying with the requirements of the controlling standard for the equipment (EN12094-1).

which also displays the time remaining until extinguishant release for added user safety.

to seven remote status units to provide lo-cal indication of the extinguishant system status.

single, easily removable, steel plate Sig-ma XT panels are both robust and easy to install.Sigma XT is supplied in an enclo-sure that matches the design and colour of the Sigma CP range.

Page 14: #LEAN!GENT&3 # 3YSTEM - · PDF file• IMO guidelines MSC/Circ. 776, 848 ... • Tested and approved according to MSC/circ.848. • Approved by a number of authorities for filling

Brassbell ASNye Vakåsvei 78 1395 Hvalstad, Norway

Tel +47 66 85 33 80Fax +47 66 85 33 81

[email protected]

total f ire protection one supplier

FEATURES

when used with Sigma XTcontrol equip ment.

control panel.

until release.

mode select key switch option.

switch option

indication with buzzer

(monitored)

Sigma SIExtinguishant Status Indicator

indication andcontrol for Sigma XT and Sigma XT+ extinguishant control sys-tems.

fault indications there are models to cover the requirements for all types of system.

-nection is all that is required to connect up to seven status units to a control

cabling for most systems.

PRODUCT OVERVIEW

-tors provide detailed status information

control equipment.

-

and a common fault indicator.

extinguishant release control are required, -

ted.

which shows a countdown of the time re-maining until the extinguishant is released in seconds.

Page 15: #LEAN!GENT&3 # 3YSTEM - · PDF file• IMO guidelines MSC/Circ. 776, 848 ... • Tested and approved according to MSC/circ.848. • Approved by a number of authorities for filling

Brassbell ASNye Vakåsvei 78 1395 Hvalstad, Norway

Tel +47 66 85 33 80Fax +47 66 85 33 81

[email protected]

total f ire protection one supplier

- Sigma XT+ control panels are multi-area extinguishant control panels complying with EN12094-1.- Up t o 8 zones of conventional detection with up to 4 extinguishant areas are avail- able. Stand a lone extinguishant c ontrol units are also available with 2 monitored inputs to receive initiating signals from remote

able modules.- Each extinguishant area has a compre hensive set of inputs and outputs and is

interface.

serially connected Sigma Si status indi- cation and control units or ancillary relay boards connected via a simple 4 core cable.- The versatility of the control panel can be

Sigma CP Sounder boards (S461) to the

- For compatible s tatus units see Sigma Si

- Complies with EN12094-1- 2, 4 or 8 detection zones- 1 to 4 extinguishant areas

- First and second stage sounder outputs for each area- First and second stage volt free change over contacts for each area

- Fault volt free contact per area- Programmable extinguishant delays- Programmable output duration- Extract fan control- Countdown indicator shows time until release in seconds

trols per area

(door interlock) input

switch input

switch input- Serial connection for Sigma Si status units and ancillary boards. (S588)

Sigma XT+Multi-Area Extinguishant

Control Panel