leak_calc

3

Click here to load reader

Transcript of leak_calc

Page 1: leak_calc

Diameter of Round Hole (In Inches) 2.00

Gauge Pressure (psig) 75.0

Number of Minutes Released 1.0

Liquid Flow Rate (lb/min) 5802.86

Total Liquid Relased (lb) 5803

Area of Leak (In Square Inches) 3.14

Gauge Pressure (psig) 75.0

Number of Minutes Released 1.0

Liquid Flow Rate (lb/min) 5802.43

Total Liquid Relased (lb) 5802

Radius

Diameter of Round Hole (In Inches) 2.00 1

Gauge Pressure (psig) 75.0

Number of Minutes Released 1.0

Gas Flow Rate (lb/min) 246.19 246.1867

Total Vapor Relased (lb) 246 246.1867

Area of Leak (In Square Inches) 3.14

Gauge Pressure (psig) 75.0

Number of Minutes Released 1.0

Refrigerant Gas Temperature (Degrees Fahrenheit) 50.00

Gas Flow Rate (lb/min) 246.19 246.1898

Total Vapor Relased (lb) 246 246.1898

Formulas for above calculations are adapted from the September 1993 second edition

of the Chemical Exposure Index Guide published by the Dow Chemical Company.

Formula for Liquid Release, Round Opening: L=26.81(D squared) * Square Root of Pg*Pl

Formula for Liquid Release, Irregular Opening: L=34.133A * Square Root of Pg*Pl

Where: L=Liquid Flow Rate Lb./min.

D=Diameter round hole, inches

Pg=Gauge pressure, psig

Pl= Density of liquid at operating temperature, Lb./cu. Ft.

Length x Height x Width x PPM/1,000,000 x vapor

density @ specific temp = total NH3 in lbs

Length x Height x Width = volume in feet3

Gas Release--Round Opening

Gas Release--Irregular Opening

Parts per million of NH3

Liquid Release--Irregular OpeningTotal room volume in ft3

Vapor density

Total NH3 in lbs

Liquid Release--Round Opening Room Level--PPM to lbs

Length of room (in feet)

Height of room (in feet)

Width of room (in feet)

Room temperature (F)

Page 2: leak_calc

A=Area of leak, square inches

Formula for Gas Release, Round Opening: AQ=(15.48*(D Squared)*Pa)/Square Root (Tr+459)

Formula for Gas Release, Irregular Opening: AQ=(19.71*A*Pa)/Square Root (Tr+459)

Where: AQ=Gas Flow Rate, Lb./min.

D=Diameter of round hole, inches

Pa=Gauge pressure plus 14.7, psi

Tr=Refrigerant gas temperature, °F

A=Area of leak, square inches

Page 3: leak_calc

0

0

0

0

0

0

0.1094

0

R^2 Area

1 3.141593

Formula for Gas Release, Round Opening:AQ=(15.48*(D Squared)*Pa)/Square Root (Tr+459)

Formula for Gas Release, Irregular Opening:AQ=(19.71*A*Pa)/Square Root (Tr+459)

Where: AQ=Gas Flow Rate, Lb./min.

D=Diameter of round hole, inches

Pa=Gauge pressure plus 14.7, psi

Tr=Refrigerant gas temperature, °F

A=Area of leak, square inches

=

Length x Height x Width x PPM/1,000,000 x vapor

density @ specific temp = total NH3 in lbs

Length x Height x Width = volume in feet3

Parts per million of NH3

Total room volume in ft3

Vapor density

Total NH3 in lbs

Room Level--PPM to lbs

Length of room (in feet)

Height of room (in feet)

Width of room (in feet)

Room temperature (F)