LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 1 DOCUMENT 009113.01 – ADDENDUM 01 1.1 PROJECT INFORMATION A. Project Name: LCCC Crossroads Renovation. 1. Owner: Laramie County Community College. 2. Architect: Hord Coplan Macht (HCM). 3. Architect Project Number: 11738.001 1.2 NOTICE TO BIDDERS A. This Addendum is issued to all registered plan holders pursuant to the Instructions to Bidders and Conditions of the Contract. B. Incorporate the following modifications, corrections, additions and /or deletions into the Drawings, Specifications and Construction Documents issued for this project. C. This Addendum is dated January 30, 2018 and will be attached to and become part of the Contract Documents dated January 4, 2018 and submitted with the Contract. D. There have been occasions when the failure of a Contractor to acknowledge receipt of Addenda has cost him/her the award of a Contract. Please acknowledge receipt of this Addendum on the Bid Form. 1.3 CONTRACTOR QUESTIONS A. Refer to “ATTACHMENTS’ for responses to all contractor questions. 1.4 SUBSTITUTION REQUESTS A. Insight – PLC series shall be acceptable as a substitute for type “C1” luminaires. B. Prescolite – LBS series IS NOT an acceptable substitute for “D3” luminaires. Lighting is powered form 277V circuit. C. Dual-Lite – EVOD series IS NOT an acceptable substitute for “ED” luminaires. Fixture does not have cover. Cut sheet does not indicate actual dimensions of product. D. Finelite – HP series shall be acceptable as a substitute for type “P2” luminaires. E. Columbia – LCL series IS NOT an acceptable substitute for “S1” luminaires. Fixture is not within 10% of the operating characteristics specified F. Dual-Lite – EVC series shall be acceptable as a substitute for type “X3” luminaires. G. Bock Lighting – Beretto series shall be acceptable as a substitute for type “L1” luminaires, in regards to electrical characteristics. Confirm aesthetics with Architect prior to submitting bid.

Transcript of LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job...

Page 1: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

LCCC Crossroads Renovation HCM Job No.11738.001

ADDENDUM 01 009113.01 - 1

DOCUMENT 009113.01 – ADDENDUM 01

1.1 PROJECT INFORMATION

A. Project Name: LCCC Crossroads Renovation.

1. Owner: Laramie County Community College. 2. Architect: Hord Coplan Macht (HCM). 3. Architect Project Number: 11738.001

1.2 NOTICE TO BIDDERS

A. This Addendum is issued to all registered plan holders pursuant to the Instructions to Bidders and Conditions of the Contract.

B. Incorporate the following modifications, corrections, additions and /or deletions into the Drawings, Specifications and Construction Documents issued for this project.

C. This Addendum is dated January 30, 2018 and will be attached to and become part of the Contract Documents dated January 4, 2018 and submitted with the Contract.

D. There have been occasions when the failure of a Contractor to acknowledge receipt of Addenda has cost him/her the award of a Contract. Please acknowledge receipt of this Addendum on the Bid Form.

1.3 CONTRACTOR QUESTIONS

A. Refer to “ATTACHMENTS’ for responses to all contractor questions.

1.4 SUBSTITUTION REQUESTS

A. Insight – PLC series shall be acceptable as a substitute for type “C1” luminaires.

B. Prescolite – LBS series IS NOT an acceptable substitute for “D3” luminaires. Lighting is powered form 277V circuit.

C. Dual-Lite – EVOD series IS NOT an acceptable substitute for “ED” luminaires. Fixture does not have cover. Cut sheet does not indicate actual dimensions of product.

D. Finelite – HP series shall be acceptable as a substitute for type “P2” luminaires.

E. Columbia – LCL series IS NOT an acceptable substitute for “S1” luminaires. Fixture is not within 10% of the operating characteristics specified

F. Dual-Lite – EVC series shall be acceptable as a substitute for type “X3” luminaires.

G. Bock Lighting – Beretto series shall be acceptable as a substitute for type “L1” luminaires, in regards to electrical characteristics. Confirm aesthetics with Architect prior to submitting bid.

Page 2: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

LCCC Crossroads Renovation HCM Job No.11738.001

ADDENDUM 01 009113.01 - 2

H. Tech Lighting – 700 series shall be acceptable as a substitute for type “L2” luminaires in regards to electrical characteristics. Confirm aesthetics with Architect prior to submitting bid.

I. Plastic Laminate Cabinets Spec Section 064116 – JBD, Inc is an acceptable manufacturer.

1.5 ATTACHMENTS

A. This Addendum includes the following attached Sheets:

1. G-101, AD-111, AD-121, A-100, A-111, A-121, A-141, A-150, A-300, A-420, A-522, A-610, P-001, P-111, E-121, E-301, E-302

1.6 REVISIONS TO DIVISIONS 02-49 SPECIFICATION SECTIONS

A. Revision to Section 095113

1. Paragraph 2.4.B.10. change size to 24x48 inch.

B. Revision to Section 097723

1. Omit spec section in its entirety.

C. Revision to Section 262200

1. CLARIFY: Only General Electric transformers will be considered per Owner Quality standards.

D. Revision to Section 262416

1. CLARIFY: Only General Electric panelboards will be considered per Owner Quality standards.

E. Revision to Section 283112

1. ADD: Section 283112 for Fire Detection and Alarm requirements. See Attached.

1.7 REVISIONS TO DRAWING SHEETS

A. Revision to sheet G-101

1. Revise Plumbing Counts Note No 3.

B. Revision to sheet AD-111

1. Revise Keynote #14.

2. Add keynote #17.

3. Demo existing wallpaper as noted with keynote #17 and extent of dash line. Existing walls are to be skim coated and prepped for new paint.

Page 3: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

LCCC Crossroads Renovation HCM Job No.11738.001

ADDENDUM 01 009113.01 - 3

C. Revision to sheet AD-121

1. Revise Keynote #6 to the following: “DEMO EXISTING CONCRETE CEILING IN ITS ENTIRETY: RE: DEMO DETAILS.”

D. Addition of sheet A-100

1. Add sheet to indicate extent of campus buildings and restroom distances.

E. Revision to sheet A-111:

1. Existing recessed walk off mat to be removed, slab to be filled with self-leveling concrete flush to existing elevation.

2. Add keynote #6

3. Window at Specialist's Office tagged type "A"

4. Revise wall types at Study Computer Room 110C.

F. Revision to sheet A-121:

1. (2) Lights at south end of metal grid tagged type "L1"

2. Ceiling type in restrooms changed to "C-2"

3. Ceiling types C-2, C-3, C-4 updated

G. Revision to sheet A-141:

1. Updated carpet and rubber base added to Entries 121, 122 & Corridors 123 & 124.

2. CPT-1, CPT-2, CPT-3 specs updated

3. P-4 spec updated

H. Revision to sheet A-150:

1. Furniture layout updated throughout

I. Revision to sheet A-300:

1. Revise wall section D1 to demo all existing CMU walls and entire existing concrete ceiling.

J. Revision to sheet A-420:

1. Locker specs updated: 5 high, CFCI

K. Revision to sheet A-522:

Page 4: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

LCCC Crossroads Renovation HCM Job No.11738.001

ADDENDUM 01 009113.01 - 4

1. Revise details E1 & E3 to demo all existing CMU walls and entire existing concrete ceiling.

L. Revision to sheet A-610:

1. Revise details A3 & A4 to demo all existing CMU walls and revise stud wall size.

M. Revision to sheet P-001:

1. Electric instantaneous water heater has been replaced with a point-of-use 6-gal

tank electric water heater

N. Revision to sheet P-111:

1. Graphical change for tank type water heater.

O. Revision to sheet E-121:

1. Add circuit of convenience receptacles in Study Room #110C. Provide five (5) duplex receptacles and connect to spare breaker in Panel LA, circuit #72. See attached revised plan.

2. 3-phase disconnect serving EWH-1 changed to single phase fused switch. Circuit shown on plan updated to ‘LA-69’.

P. Revision to sheet E-301:

1. LIGHTING CONTROL MATRIX: TYPE LC2: Fixtures shall be programmed for automatic ON in lieu of manual ON as shown. See attached revised plan.

2. LUMINAIRE SCHEDULE: See above for accepted equals.

3. MECHANICAL EQUIPMENT SCHEDULE: Revised load and means of disconnect for EWH-

Q. Revision to sheet E-302:

1. PANEL ‘LA’ SCHEDULE: Breaker #72 shall indicate Study Room 110C Receptacles.

2. PANEL ‘PA’ SCHEDULE: 100/3 breaker for new transformer shall be a new device provided by the contractor. See attached revised plan.

3. PANEL ‘PA’ SCHEDULE: Breaker #22,24,26 shall be marked as spare.

4. PANEL ‘LA’ SCHEDULE: Breaker #69 shall indicate EQ - EWH-1.

END OF DOCUMENT 009113.01

Page 5: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

LCCC

Crossroads Renovation

Bidding Questions/Repsonses

SHT/SPEC DTL/Para.Date

Review Comment

Responsible

Party Responses Addendum Issuance

A-420 D5 1/17/2018

The drawing shows six high and the specs state five high. What should we quote? HCM Lockers shall be 5-tier per spec, 5-wide for a total of 15

lockers. "OFCI" shall be removed from text note. These

lockers shall be provided and installed by the contractor.

Update will be provided

in Addendum No.1

A-111 A1 1/17/2018

On sheet A-111 in specialist office 105B there appears to be a window, but it does not have a tag on it. Is this supposed to be window type

A?

HCM

Window at Specialist Office 105B shall be window type A

Update will be provided

in Addendum No.1

AD-121 & A-121

Notes,

Legend,

A1

1/18/2018

Sheet note #1 on AD-121 reads ‘Demo existing ceiling and grid’. Sheet note #1 on A-121 reads ‘New grid, ceiling tiles…’. However, A-121

Ceiling Type Legend, C-2 calls for ‘New 2X4 ACT, Existing Grid’. Please clarify weather new grid is to be installed or existing grid is to be

reused.

HCM Sheet note #1 on sheet AD-121 is correct. On sheet A-121

toilet rooms 113 & 114 shall be changed to ceiling type C-2. On

sheet A-121 Ceiling Type Legend shall be updated as follows:

C-2 shall be "NEW 2x4 ACT, NEW GRID", ceiling types C-3 &

C-4 shall be omitted.

Update will be provided

in Addendum No.1

AD-121 Notes,

Legend

1/27/2018 Sheet AD 121 indicates that all existing ACT is to be removed.

On sheet A 121 ceiling C2 indicates new 2 x 4 tiles in existing grid.

HCM See response above

General 1/29/2018 After reviewing the documents it looks like they are requesting just one roller screen shade for one room, the Specialist Office, but they do

not provide any sizes for it. There are sizes for four other windows but it does not appear that they need roller screen shades for those.

HCMThe roller shade size shall be 4'-0" x 4'-2" and is only required

at the Specialist Office

Spec 095113 1/27/2018 Specification Section 095113-3 2.4 B.1 indicates 2 x 2 Armstrong # 1810. HCM Size shall be changed to 2x4

A-610 Door

Types

1/26/2018 Sheet A6.10 of the drawings call out a type E glass door that isn’t addressed in the storefront spec section. The storefront section (084113)

page 6 under entrance doors calls out as basis-of-design Kawneer heavy wall doors. This does not match the glass door that is called out in

the drawings. If these are to be glass doors , please provide an All-Glass Entrances spec section calling out all the necessary requirements

for this specific project such as glass thickness, patch fiitings or door rails, concealed overhead or floor closers etc. The hardware schedule

for these openings only list a lock and cylinder.

HCM

Door Type 'E' is a demountable partition system with all

hardware and accessories provided by manufacturer

Spec 097200 1.1 B #2 1/26/2018 This section references 'Panel Signage', is the signage by Owner or contractor? HCM Signage is by Owner

A-420 D5 1/26/2018 This detail calls for Owner furnished and contractor installed lockers and references the division 10 spec. In the specifications it appears that

the contractor is furnishing and installing the lockers. Please confirm who is responsible for furnishing the lockers.

HCM The lockers shall be CFCI Update will be provided

in Addendum No.1

AD-111 Gen Note

19

1/26/2018 Based on past experience this item can vary greatly in cost depending on conditions of existing doors, amount of finish, etc. Would it be

possilbe to consider an allowance for this scope of work so all contractors are bidding the same thing? Or bid doors as new, depending on

condition, this may be less expensive and a better end product.

HCM Only the existing doors that are to remain is applicable to this

note.

AD-121 Room

113/114

1/26/2018

Note 1 has us demolishing ceiling tile and grid. New reflected ceiling plan states to re-use existing grid in the 'Ceiling type legend'. Please

confirm which approach is correct.

HCM This has been updated, see Addendum #1 Update will be provided

in Addendum No.1

E-121 Power 1/26/2018 Demo plan has removing the ceiling and grid. New plan shows existing to remain. Please coordinate. HCM This has been updated, see Addendum #1 Update will be provided

in Addendum No.1

E-121 Power 1/26/2018 In locations where new power/data is going on an existing wall is surface mounted conduit acceptable? HCM New power/data in existing walls shall be run within wall cavity

at all locations possible

Update will be provided

in Addendum No.1

E-121 Power 1/26/2018 If surface mounted conduit is unacceptable and it must be concealed, please provide a drawing which shows the types of existing walls

(gyp/masonry).

HCM Existing masonry walls are now removed from room 110C so

there should not be a need to coordinate with masonry/power

locations

Division 28 Fire Alarm 1/26/2018 Please confirm the existing slab is on grade in all new floor box locations. HCM Correct, existing slab is on grade. No saw cutting is required

for electrical boxes lcoations

A-141 ACT 1/26/2018 Please confirm that Armstrong #895 is the correct product (1 Hour Rated Panel). The same pattern panel that is non-rated Class A is #755. HCM #895 is Owner standard

Spec 097723 AWP 1/26/2018 Fabric Wrapped Acoustical Wall Panels appears in the specifications, but none appear on the drawings. Please remove specification section

if not applicable.

HCM Will be removed.

Spec 062023 2.3.A.1.a 1/26/2018 Is there an artist the school has in mind for this scope of work? Or an allowance that could be allotted for this scope of work? HCM Coordination with local artist will need to be considered

following award of bid

General 1/25/2018 Our vinyl wall covering subcontractors are requesting a copy of the intended graphics to be used so they can properly quote their portion of

the project. Will this be available prior to the bid date?

HCM Final graphics have not been selected yet.

M-001 Mech

Pricing

Notes

1/22/2018 Mechanical: Add Alternate #2 Is it the intent with the DDC Upgrade (Alt #2) to also replace the valves or will only the actuator be replaced? Cator Ruma The intent is to maintain the existing control valves and only

replace the valve actuators with the DDC Upgrade

Architectural: Wall

Covering

1/22/2018 Please advise of the extent of wall covering area in Room 110C. Is it the intent to have the wall cover extend along the entire west wall of

110C. The arrow indicating WC-1 stops short of the existing window.

HCM See revised finish plan A-141, wall covering will extend to

corner of existing wall.

Page 6: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

LCCC

Crossroads Renovation

Bidding Questions/Repsonses

SHT/SPEC DTL/Para.Date

Review Comment

Responsible

Party Responses Addendum Issuance

Architectural:

Storefront &

Demountable

Partition

1/22/2018 Please advise if alum storefront F.1, F.2 & F.3 is a component of the Steelcase demountable partition or if it is a standalone system. HCM This is a stand-alone system having to consider additional

manufacturers listed as an equal

Temp Partitions-

Student Access

1/25/2018 During the site walk it was stated that there will need to be temporary partition(s) installed to maintain the corridor between ARP and CCC.

Please advise of the temporary partitions construction and locations to maintain public traffic / egress.

HCM Contractor shall provide standard proper temporary partition to

meet safety and access requirements

Wall Coverings

along west wall

1/25/2018 Please advise of the finish along the west wall of room 109, 110A, 110C. Currently the vinyl wall covering is peeling off and rippled. The

room finish schedule calls for paint and wall covering (WC-1). If the vinyl is to be removed, please advise any substrate prep.

HCM Existing wall covering shall be removed and wall surface shall

be skim coated for prep of new paint or new wall covering

Flooring

replacement for

waste floor demo

1/25/2018 With the slab demo that is required for the waste line, please advise of the new floor finish that is to be install in Corridor 111. HCM New carpet will be installed.

Abatement report 1/25/2018 Per note 9 on AD-111 it states “GC to coordinate abatement consultant for any contaminated materials to be removed before work to begin

in this area.” Please provide abatement report to obtain a demolition permit by DEQ.

HCM We do not have access to abatement report

Wood Doors 1/25/2018 Per note 19 on AD-111 it states the sand doors smooth and refinish. Please clarify the doors that are to be refinished. Please also advise if

the door hardware will need to be modified or replaced on the refinished doors.

HCM All existing wood doors that are existing to remain shall be

included in this scope. No hardware modifications unless

specifically identified

Wyoming

Caseworker

1/25/2018 Per the casework specification (064116) there are no Wyoming contractors listed. Please advise of any Wyoming Casework manufactures

that will be qualified on this project.

HCM See substitution requests

OSHA 10 1/25/2018 It was stated at the pre-bid that the Project Manager’s OHSA 10 card must be submitted with the bid. These is no reference of this

requirement in the bidding documents. Please clarify.

LCCC A new revised bid will be issued with OSHA 10 requirement.

License Plate Wall 1/25/2018 Per Spec section 062023 – 2.3, it calls for contracting with a local artist having 5 years of similar experience with this type of installation.

Can an allowance be specified for the art installation?

HCM Contractor shall bid scope as currently spec'd and detailed.

Bid Submission 1/25/2018 Per the Pre-Bid meeting agenda, it states bids are turned in at Room CCC-178, however per section 3 of the invitation to bid it states the

bids turn in at Room AM-108 (Page 1 of 24) and AM-104 (page 18 of 24). Please clarify which room the bids turn in at.

LCCC A new revised bid will be issued with CCC-178 bid opening

Bid Form Does the CSI Exhibit E need to be submitted at the time of bid. Per Section 5, Exhibit E is not listed in the Required Submittals, however per

Section 6 it is listed. A new revised bid will be issued with CSI Division requirement. If Exhibit E is required can it be turned in 24 hours after

bid submission. No, CSI is due at time of bid opening

Please advise how the Unit Cost #1 (Slab Cutting and Patching) is to be noted on the bid form.

Please advise how the alternates are to be noted on the bid form.

Please advise how to list several different subcontractors within one division line item. I.e. Division 9- Metal Stud Framing, Paint, Flooring,

Ceilings, etc.

LCCC A new revised bid will be issued with CSI Division requirement.

No, CSI is due at time of bid opening

Windows 1/25/2018 Per note 4 on AD-111 it states to demo wall and windows. However currently there are no windows in this location. Please clarify note, and

provide framing detail for the window attachment to metal framing. Please provide finish detail of hall side regarding window installation.

HCM If referring to keynote #4 near existing Electrical room this note

should refer to demo existing partition

Spec Section

084113 Aluminum

Entrances and

Storefront

1/25/2018 The Project Manual include aluminum entrances and storefront. Specs reference Entry Doors and associated hardware. Please advise of

the locations that apply to this spec section.

HCM Storefront spec is applicable to the single storefront exterior

window. Demountable partitions are shown elsewhere at

interior space.

Demountable

Partitions

1/25/2018 The Demountable Partition Specs include door hardware to be included with the partition system, however the Door Schedule calls for

hardware groups in the 087100 hardware spec. Please clarify the hardware requirements of the demountable partitions. The hardware listed

in the demountable partitions references (2) lock cylinders, one calls for Tumbler Type, BHMA 156.5 Grade 1 and the other references spec

section 087100. Please clarify.

HCM All hardware shall be by demountable partition manufacturer.

The cores and any other required hardware not already

supplied shall be by others

Page 7: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

Laramie County Community College

Crossroads Renovation

Cheyenne, WY

HCM Project No 11738.001

FIRE DETECTION AND ALARM 283112 - 1

SECTION 283112 – FIRE DETECTION AND ALARM - EXPANSION / REMODEL

PART 1 - GENERAL

1.1 SUMMARY:

A. Drawings indicate general design intent and do not indicate all equipment or devices or the full extent of the System. Provide complete design of the Fire Alarm System for review by local fire authority including layouts and deferred submittals. There is an existing fire control panel installed in the facility. Any references to the existing control operation equipment, etc., are for information on system operation. All existing devices such as call boxes, connections, shall remain as existing U.O.N. on drawings.

B. Provide system component devices compatible with the existing system with changes required for proper operation on the new, upgraded equipment.

C. Provide additions and modifications to existing system suitable for occupancy group as defined by local Authority Having Jurisdiction (AHJ)

1.2 QUALITY ASSURANCE:

A. Manufacturer's Qualifications: Firms regularly engaged in manufacture of fire alarm systems of types, sizes, and electrical characteristics required, and whose products have been in satisfactory use in similar service for not less than 5 years.

B. Installer's Qualifications: Firm with at least 5 years of successful installation experience on projects with fire alarm systems work similar to that required for this project.

1. Firm with manufacturer's factory trained personnel. 2. Firm with factory authorized service organization and spare parts stock within 200 miles

of the project and with a 24 hour response time. 3. Installation shall be accomplished by or supervised by NICET II or higher.

C. Codes and Standards:

1. The complete installation shall conform to the applicable sections of NFPA 72, Local Code Requirements, and the National Electrical Code; with particular attention to article 760. All control equipment must have transient protection to comply with UL 864 requirements or Standard #497B as applicable.

2. UL Compliance and Labeling: Comply with provisions of UL safety standards pertaining to fire alarm systems; and provide products and components which are UL-listed and labeled.

3. FM Compliance: Provide fire alarm components and accessories which are FM-approved.

4. The fire alarm system and devices shall comply with ADA 1990 and UL 1971 requirements.

5. International Building Code, International Fire Code, and other applicable local codes and standards.

1.3 SUBMITTALS:

A. See Section 26 05 00 Common Work Results for Electrical for Submittal requirements. Supplemental information is listed within this section.

Page 8: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

Laramie County Community College

Crossroads Renovation

Cheyenne, WY

HCM Project No 11738.001

FIRE DETECTION AND ALARM 283112 - 2

B. Product Data: Submit manufacturer's technical product data, including specifications, data sheets, wiring diagrams, equipment ratings, dimensions, finishes and descriptions of system operation. Submit manufacturer's installation instructions, including outlet or back box requirements for each piece of equipment.

C. Shop Drawings: Provide shop drawing submittal for approval by the local Fire Department and/or The Authority having jurisdiction. The Contractor shall arrange to have the Fire Alarm System shop drawing submittal prepared, sealed, and signed by a professional fire protection engineer and NICET III or NICET IV in Fire Alarm Systems. Preparer shall assume the duty of Engineer of Record for the Fire Alarm System design. Provide shop drawings showing system components, including panels and cabinets, locations, quantities, and full schematic of system wiring showing conductor routings and quantities, and connection details. All conduit routing must be submitted to, and accepted by, the Architect/Engineer. Shop drawing documents must be submitted simultaneously with sprinkler system documents and prior to installation.

1. This information shall be submitted on 1/8" = 1'-0" scale building floor plans. No other systems shall be included on these plans. Reproduction of contract drawing will not be acceptable. The following information shall be included in the shop drawings:

a. Occupancy group and use. b. Include brief description of scope of work c. Indicate extent of building sprinkler system. d. Indicate addition to/modifications of existing system. e. One-line diagram showing/indicating number of devices and appliances per

zone/circuit. f. Submit Zone schedule g. Wire sizes, color coding, type(s) and voltage drop calculations. h. Back-up battery calculations i. Indicate annunciation method and include graphic zone map. j. Addition to or modification of the system shall be distinguishable from the existing

and be identified on the floor plans as well as the one-line diagram(s). k. Include wiring diagrams for all fire alarm junction boxes (new and existing)

impacted by this project. Include wiring numbers on all connections. l. Proposed conduit routing, specifically if exposed conduit or wiremold is being

proposed. All surface mounted conduit and wiremold routing must be submitted to, and accepted by, the Architect/Engineer.

m. Connection details for new and existing devices/equipment. n. Provide updated room names and numbers that match the names and numbers as

labeled at the building. Room names and numbers shown on the contract documents are not necessarily those that are currently being used in the building. The fire alarm manufacturer shall coordinate with the contractor and owner on existing and new work and survey the site on existing work to identify the proper names and numbers.

o. Submit graphic annunciator and/or map layouts for review by the Architect/Engineer prior to fabrication

p. Submit sequence of operation and verification of system operation by manufacturer or his authorized representative

D. Quality Assurance Documentation:

1. Submit manufacturer's certificate that system meets or exceeds specified requirements. 2. All shop drawings, battery and voltage drop calculations shall be submitted to the

authority having jurisdiction for review after review by the Architect/Engineer.

Page 9: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

Laramie County Community College

Crossroads Renovation

Cheyenne, WY

HCM Project No 11738.001

FIRE DETECTION AND ALARM 283112 - 3

E. Field Quality Control Test Reports: Submit record of testing as described below. Refer to Section 26 05 00 – Common Work Results for additional requirements.

1.4 DELIVERY, STORAGE, AND HANDLING:

A. Handle fire alarm equipment carefully to prevent damage, breaking, and scoring. Do not install damaged equipment or components; replace with new.

B. Store fire alarm equipment in clean, dry place. Protect from weather, dirt, fumes, water, construction debris, and physical damage.

1.5 EXTRA MATERIALS:

A. General: Provide extra materials as listed below in addition to that required to complete the work. The additional stock shall not be used unless specifically authorized by the owner’s representative.

B. Lamps: Furnish spare/replacement lamps and LED’s amounting to not less than three (3) lamps of each type and of each color.

C. Devices:

1. Furnish spare/replacement detection bases amounting to 5 percent of the quantity installed by this work, but not less than two (2) of each type, including duct detector housings.

2. Furnish spare/replacement detectors amounting to 5 percent of the quantity installed by this work, but not less than two (2) of each type.

3. Furnish spare/replacement adaptor modules and relays amounting to 5 percent of the quantity installed by this work, but not less than one (1) of each type.

4. Furnish spare/replacement speakers, speakers/horns, combination speaker/horn/strobe units, and strobe units amounting to 5 percent of the quantity installed by this work but not less than one (1) of each type.

5. Furnish spare/replacement AIM’s, and AOM’s or systems similar components amounting to 5 percent of the quantity installed by this work but not less than one (1) of each type.

1.6 OPERATION:

A. The system alarm operation subsequent to the alarm activation of any manual station, automatic detection device, and monitoring device serving the “alarm” status of an air sampling smoke detector, or sprinkler flow switch shall be unchanged from the existing system operation. When owner has agreed to or asked for revisions to the evacuation plan, all new operational sequences shall be documented and approved in writing.

B. Provide alterations to the existing systems that incorporate the following additional functions (if not already present:

1. All audible alarm indicating appliances shall sound a distinctive and continuous fire alarm signal until silenced by the alarm silence switch at the control panel or at the remote annunciator.

2. All visible alarm indicating appliances shall flash continuously until the system is reset. Visual alarm devices shall continue to operate when audible devices are silenced, when allowed by the AHJ. Any subsequent zone alarm shall reactivate the alarm indicating appliances.

3. All doors normally held open by door control devices shall release.

Page 10: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

Laramie County Community College

Crossroads Renovation

Cheyenne, WY

HCM Project No 11738.001

FIRE DETECTION AND ALARM 283112 - 4

4. A supervised signal to notify the monitoring center shall be activated. 5. Activation of a sprinkler flow device shall cause the exterior horn/light to operate

continuously until the flow has ceased. 6. Activation of a duct detector shall alarm the system and shut down the associated air

handling unit.

C. The activation of any system smoke detector shall initiate an Alarm Verification operation whereby the panel will reset the activated detector and wait for a second alarm activation. If within one (1) minute after resetting, a second alarm is reported from the same or any other smoke detector, the system shall process the alarm as described previously. If no second alarm occurs within one minute the system shall resume normal operation. The Alarm Verification shall operate only on smoke detector alarms. Other activated initiating devices shall be processed immediately. The alarm verification operation shall be selectable by zone.

1. The control panel shall have the capability to display the number of times (tally) a zone has gone into a verification mode. Should this mode verification tally reach a pre-programmed number, a trouble condition shall occur.

D. A manual evacuation (drill) switch shall operate the alarm indicating appliances without causing other control circuits to be activated. However, should a true alarm occur, all alarm functions would occur as described previously.

1.7 SUPERVISION:

A. Supervision shall be unchanged from the existing system. Supervision of additional devices shall be as follows:

1. Provide independently supervised and independently fused indicating appliance circuits for alarm speakers and flashing alarm lamps. Disarrangement conditions of any circuit shall not affect the operation of other circuits.

2. Auxiliary manual control shall be supervised so that an "off normal" position of any switch shall cause an "off normal" system trouble.

3. Each independently supervised circuit shall include a discrete LCD readout to indicate disarrangement conditions per circuit.

4. The System Modules shall be electrically supervised for module placement. Should a module become disconnected the system trouble indicator shall illuminate and the audible trouble signal shall sound.

5. The system shall have provisions for disabling and enabling all circuits individually for maintenance or testing purposes.

PART 2 - PRODUCTS

2.1 ACCEPTABLE MANUFACTURERS:

A. Manufacturers: Provide materials that mate and match with existing system components. Subject to compliance with requirements, provide fire alarm system components manufactured by the same manufacturer of the existing system.

1. Notifier – Field Verify Series prior to quotation.

2.2 FIRE ALARM AND DETECTION SYSTEMS:

A. General: Provide complete fire alarm products of types, sizes and capacities indicated, which comply with manufacturer's standard design, materials, components; construct in accordance

Page 11: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

Laramie County Community College

Crossroads Renovation

Cheyenne, WY

HCM Project No 11738.001

FIRE DETECTION AND ALARM 283112 - 5

with published product information, and as required for complete installation. Provide fire alarm and detection systems for applications indicated.

B. Wiring System Materials: Provide basic wiring materials which comply with Division 26 sections; "Raceways", “Wires and Cables” and "Electrical Boxes and Fittings".

1. Provide wire and cable in accordance with requirements of manufacturer. Wire insulation shall comply with NEC Article 760.

2. Provide individual solid copper conductor sizes AWG #14, or larger. 3. Provide multi-conductor cables for wire sizes smaller than AWG #16. 4. Provide conductors which are UL listed for the installation and location, and approved for

fire alarm usage. 5. Initiating circuits shall be color coded red for positive, red with black strip for negative.

Indicating circuits shall be color coded red with yellow stipe for positive, red with brown stripe for negative.

6. All conductors shall be numbered and their numbers shall correspond to the terminal block numbering they are connected to. Provide conductor wiring and terminal block numbering.

C. Power Supplies: Existing system operates on 120 VAC power supply. Provide additional power supplies and other equipment necessary to accommodate new or modified existing devices.

1. Provide battery back-up and increase battery back-up to system as required. Design battery back-up to take over supply to system within 30 seconds of loss of primary system to 85 percent voltage. Provide battery system capable of operation of system for 24 hours under normal conditions and then for 15 minutes under alarm conditions.

D. Provide Control of additional auxiliary services as follows:

1. Interior flashing strobe lights 2. Fire/Smoke damper releases 3. Remote annunciators

2.3 FIRE ALARM CONTROL PANEL:

A. Connect additional devices to existing fire alarm control panel. Modify and upgrade panel for compatibility with current codes and current UL requirements and as required for the additional features or equipment. Provide all necessary reprogramming and recertification.

2.4 ADDRESSABLE COMMUNICATION NETWORK:

A. Extend or modify existing communications network as required for the additional equipment.

2.5 ADDRESSABLE DEVICE TYPES:

A. General: Devices will be located as shown on the drawings. The location of addressable devices will be selected to optimize the system layout in order to provide the level of protection, zone identification and control as shown on the drawings.

B. Addressable Detector Bases: All addressable smoke and heat detector heads will plug into their bases. The base will contain electronics that communicate the detector status (normal, alarm, trouble) to the control panel over two wires. The same two wires shall also provide

Page 12: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

Laramie County Community College

Crossroads Renovation

Cheyenne, WY

HCM Project No 11738.001

FIRE DETECTION AND ALARM 283112 - 6

power to the base and detector. Detector heads (smoke or heat) must be interchangeable. Upon removal of the head, a trouble signal will be transmitted to the control panel.

C. Photoelectric Detector Head: Photoelectric type detectors shall be of the solid state photoelectric type and shall contain no radioactive material. They will use a pulsed infrared LED light source and be sealed against rear air flow entry. The detector shall fit into an addressable base that is common with both the heat and photoelectric type detectors.

D. Pull Stations: Pull stations shall contain electronics that communicate the station’s status (alarm, normal) to the control panel over two wires which also provide power to the pull station. The address will be set on the station. They will be manufactured from high impact red Lexan. Station will mechanically latch upon operation and remain so until manually reset by opening with a key common to all system locks. Pull stations will be double action. The front of the station is to be hinged to a back-plate assembly and must be opened with a key to reset the station. The key shall be common with the control panels. The addressable manual station shall be Underwriters' Laboratories Inc. listed for operation with the control panel.

E. Adaptor Module: Adapter Modules shall be used for monitoring of water flow, valve tamper, non-addressable detectors, and for control of smoke dampers, door holders, and other output control functions. Adapter Modules will be capable of mounting in a standard electric outlet box. Adapter Modules will include cover plates to allow surface or flush mounting. Adapter Modules will receive their 24VDC power from a separate two wire pair running from an appropriate power supply. There shall be two types of devices: Type 1; Monitor Adapter Modules - for conventional 2-wire thermal detector and/or contact device monitoring with Class B or Class A wiring supervision. Type 2; Control Adapter Modules - for signals, speakers, fire fighter phone jacks and other device control with Class B or Class A wiring supervision.

2.6 ALARM SIGNAL DEVICES:

A. Fire Alarm Horn/Strobe Combination: Provide high impact resistant red LEXAN Horn/Strobe combination devices as shown on the plans. Each assembly shall consist of two independent devices which are manufactured as compatible with each other and with the control equipment. Each assembly shall provide a terminal strip or wire leads for true in-out wiring connections. The strobe unit shall have a candela-second rating in compliance with ADA requirements and be rated at 24 VDC. Strobes shall be clear with red letters "FIRE" on two sides.

1. Provide wall mounting as shown on the plans. Verify manufacturer mounting requirements prior to rough in.

B. Individual Strobe Unit: Provide strobe units mounted where shown. Units shall match those used in the Speakers/Horns devices specified.

C. Where multiple strobe units are visible from a single location and the potential visible flash rate is 5 hz or more, provide synchronizing modules and strobes compatible for synchronizing as required. Provide additional wiring, conduit, and power supplies as necessary.

D. Speakers/Horns have been located on the drawings. It is the Contractor's responsibility to provide adequate coverage to achieve the required 15 dBA above ambient at all locations throughout the building. If locations shown are inadequate, show additional devices on shop drawing submittal. Additional devices will be added at no additional cost to the contract including conduit wiring, power supplies, etc. System shall meet NFPA 72 Intelligibility Standards required by AHJ.

Page 13: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

Laramie County Community College

Crossroads Renovation

Cheyenne, WY

HCM Project No 11738.001

FIRE DETECTION AND ALARM 283112 - 7

2.7 REMOTE ANNUNCIATOR:

A. Update/replace existing building annunciator. Annunciator shall include two lines of 40 character LCD display, alarm silence, system reset, programmable control switches, and be supervised from the FACP panel.

1. Annunciator shall indicate each alarm initiating device by address and description. Alarm conditions shall be indicated for each alarm initiating device.

2. The annunciator shall communicate with the control panel over one twisted shielded pair of wires. Operating power shall be 24 VDC and shall be fused at the control panel.

PART 3 - EXECUTION

3.1 EXAMINATION:

A. Examine areas and conditions under which fire alarm systems are to be installed. Do not proceed with work until unsatisfactory conditions have been corrected in manner acceptable to Installer.

3.2 IDENTIFICATION:

A. Provide electrical identification in accordance with Division 26 "Electrical Identification". SLC and NAC Devices shall be labeled with System Device Address and EOL locations shall be identified at each EOL device.

3.3 INSTALLATION OF BASIC WIRING SYSTEM MATERIALS:

A. Provide raceways and supports per code.

B. Install wiring, raceways, and electrical boxes and fittings in accordance with Division 26 sections; "Raceways", "Wires and Cables", and "Electrical Boxes and Fittings".

C. Install wiring in exposed ivory colored surface metal raceway only where specifically noted as allowed on wall or ceilings.

D. Install wires and cables without splices. Make connections at terminal strips in cabinets or at equipment terminals. Make soldered splices in electronic circuits in control cabinets.

3.4 INSTALLATION OF FIRE ALARM SYSTEMS:

A. Install fire alarm system components as indicated, in accordance with equipment manufacturer's written instructions and complying with applicable portions of NEC and NECA's "Standard of Installation."

B. Wiring: Wiring of fire alarm system is work of this section, but is not specifically detailed on drawings. Refer to the manufacturer's shop drawings for detailed wiring and connection information.

1. Complete wiring in accordance with manufacturer's requirements. Provide Striped Color coded wiring and install per manufacturer's point-to-point wiring diagram. Determine exact number of wires for each fire area zone from number and types of devices installed. Connect each device with sufficient wiring to complete its intended operation.

2. Where there are a number of additional power requiring devices such as smoke detectors, fan relays, door holders and smoke damper operators installed in a circuit,

Page 14: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

Laramie County Community College

Crossroads Renovation

Cheyenne, WY

HCM Project No 11738.001

FIRE DETECTION AND ALARM 283112 - 8

group in numbers so power required does not exceed 80 percent of manufacturer's power supply rating. Provide extra wiring, or extra power supplies required to fulfill that requirement. In addition, provide extra or larger size wiring to alleviate voltage drops which makes device operate beyond voltage limits for which it was designed. Determine above with manufacturer’s representative while equipment is being installed.

C. Mount audible and visual devices per Americans with disabilities Act (ADA) 1990 requirements.

D. The existing system shall remain in operation while the new devices are being installed, tested, and accepted. Make provisions to keep F.A. System active and/or provide fire watch as acceptable to the AHJ and owner so that existing wiring can be reused as practical.

3.5 FIELD QUALITY CONTROL:

A. Connection and Supervision: Make connections to panel under manufacturer's supervision. Complete connections from this cabinet to panel utilizing Manufacturer's technicians.

B. Prior to starting work, establish that the existing system is in proper working order. If condition exists which prevents normal operation of specified additions and extensions, bring this fact to Architect/Engineer's attention prior to doing work affecting existing system. Where work is done without such notification, it is assumed that connections have been made to a working system, and performance requirements and guarantee will apply to entire system.

C. System Test and Approval: Submit shop drawings for function and operation only, pre-approved by authority having local jurisdiction.

1. Prior to final acceptance of system, manufacturer shall, in presence of Contractor and Owner's Representative, test each additional sensing or detection and alarm device including devices and equipment interlocks such as equipment shutdown and smoke dampers. Schedule test with Owner.

2. The completed fire alarm system shall be fully tested in accordance with NFPA 72 by the contractor in the presence of the Owner's representative and the Local Fire Marshal. The contractor shall coordinate the testing of each fire alarm detector added or relocated under this project with the fire department and forward a completed checklist showing each detector operated properly and that proper indication of detector operation occurred at all control panels, annunciator panels, remote indicators, remote test switches, etc.

3. In addition, proper interlocks, door release, etc. shall be documented with specific equipment affected listed by identifier.

4. Upon completion of a successful test, the contractor shall so certify in writing to the Owner and General Contractor.

5. Submit copy of test results in duplicate after signed by Owner's Representative to Architect/Engineer, Owner, and Local Fire Protection Authority. Mount copy of inspection record in lexan enclosed frame assembly on control panel.

6. Provide Record of Completion Documentation per NFPA 72.

3.6 MAINTENANCE CONTRACT:

A. Where a maintenance contract exists, the maintenance contractor shall make available to the owner a maintenance contract proposal to increase the scope of the maintenance agreement to provide a minimum of two (2) inspections and tests per year in compliance with NFPA 72 guidelines.

Page 15: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

Laramie County Community College

Crossroads Renovation

Cheyenne, WY

HCM Project No 11738.001

FIRE DETECTION AND ALARM 283112 - 9

3.7 WARRANTY:

A. The Contractor shall guarantee all equipment and wiring provided under this contract free from inherent mechanical and electrical defects for a period of one year from the date of acceptance as set forth in the general conditions. If sections of the project are phased the acceptance and warranty should start and end at one time unless the project is phased and phased acceptance has been accepted by the owner.

3.8 OPERATING AND MAINTENANCE INSTRUCTIONS:

A. Provide three (3) copies of Operating and Maintenance Instructions in hardback, three-ring binders covering all equipment furnished. Manuals shall include the following information:

1. Name, address and telephone number of authorized service organization to be contacted for each equipment item. The local fire alarm supplier shall have a 24 hour telephone response service. An answering machine shall not be considered acceptable.

2. Parts list and wiring diagram, operating and maintenance instructions for each piece of equipment.

3. Record Set of Shop Drawings: Shop drawings corrected to show as-built conditions. Transfer modifications from field set.

4. Record of voltage sensitivity for each ionization detector head as recorded during final calibration.

5. All wiring diagrams shall show color coding of all connections and mounting dimensions of equipment.

3.9 DEMOLITION:

A. Upon completion of new fire alarm system, after final connections have been made, this contractor shall carefully remove all existing fire alarm apparatus where indicated, including fire alarm control panel, manual stations, audible signals, etc., and turn all such equipment over to Owner.

3.10 PAINTING AND PATCHING:

A. Contractor shall paint all exposed conduit to match adjacent surfaces. All surfaces or finishes damaged as a result of this work shall be properly patched, painted and/or repaired by trained craftsmen of the trade involved.

B. Contractor shall patch and paint where old devices are removed unless the old devices are in block walls or in concrete, where the Contractor shall provide blank plates on boxes. Blank plates shall be painted to match adjacent surfaces.

END OF SECTION 283112

Page 16: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

Laramie County Community College

Crossroads Renovation

Cheyenne, WY

HCM Project No 11738.001

FIRE DETECTION AND ALARM 283112 - 10

Page 17: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

UP

DN

UP

DN

100 SFSTORAGE

1 OCC

300 SF /OCC70 SFELEC

1 OCC

300 SF /OCC

121 SFOFFICE

2 OCC

100 SF /OCC

123 SFOFFICE

2 OCC

100 SF /OCC

128 SFOFFICE

2 OCC

100 SF /OCC

116 SFOFFICE

2 OCC

100 SF /OCC

118 SFOFFICE

2 OCC

100 SF /OCC

216 SFOFFICE

3 OCC

100 SF /OCC60 SF

STORAGE

1 OCC

100 SF /OCC

183 SFCONF

13 OCC

15 SF /OCC

165 SF

VESTIBULE

100

545 SFMECH

2 OCC

300 SF /OCC

375 SFSTORAGE

2 OCC

300 SF /OCC

22 SF

FIRESERVICE

102A

204 SFCONF

14 OCC

15 SF /OCC

501 SFRECEPTION

5 OCC

100 SF /OCC

20 SFJAN

1 OCC

300 SF /OCC

3942 SFPUBLIC AREA

40 OCC

100 SF /OCC

180 SF

WOMEN'STOILET

114

188 SF

MEN'STOILET

113

99 SF

CORR.

111

541 SFCONF

36 OCC

15 SF /OCC

OCCUPANCY TYPE

Accessory storage areas, Mechanicalequipment room

Assembly without fixed seatsUnconcentrated (tables and chairs)

Business areas

Non-Occupied space (Circulation,Toilet Rms, Etc.)

Calculating...

113 SFOFFICE

2 OCC

100 SF /OCC

170 SFRECEPTION

2 OCC

100 SF /OCC

155 SF

CORRIDOR104C

170 SF

CORRIDOR

104K

113 SFOFFICE

2 OCC

100 SF /OCC

EXISTING 2-HOUR AREA SEPARATION RATING

EXISTING 1-HOUR FIRE RATED WALL

EXIT WIDTHREQ'D = 71 OCCUPANTS x 0.2 = 14.2"PROVIDED = 68"

EXIT WIDTHREQ'D = 56 OCCUPANTS x 0.2 = 11.2"PROVIDED = 68"

EXIT WIDTHREQ'D = 56 OCCUPANTS x 0.2 = 11.2"

PROVIDED = 68"

HATCHED AREA IS NOT IN SCOPE OF RENOVATION BUT HAS BEEN SHOWN FOR EGRESS PURPOSES

CODE SYMBOL LEGEND

GOVERNING CODES: 2015 INTERNATIONAL BUILDING CODE2015 INTERNATIONAL EXISTING BUILDING CODE2015 INTERNATIONAL FIRE CODE2015 INTERNATION MECHANICAL CODE2015 INTERNATIONAL ENERGY CODE2015 INTERNATIONAL PLUMBING CODE2015 INTERNATIONAL FUEL CODE2017 NATIONAL ELECTRICAL CODE2009 ICC/ANSI A117.1 ACCESAIBILITY CODECHEYENNE CITY CODE

THIS IS A 10,349 SF RENOVATION INSIDE OF THE EXISTING 14,950 GSF CROSSROADS BUILDING. THE EXISTING BUILDING STRUCTURE IS CONCRETE POST AND BEAM WITH PRECAST CONCRETE DOUBLE TEE ROOF SLABS. THE RENOVATION WILL CONSIST OF NEW PARTITION WALLS, INTERIOR FINISH REPLACEMENT, NEW FIRE PROTECTION THROUGHOUT SPACE, AND MECHANICAL AND ELECTRICAL UPGRADES TO THE PROGRAM SPACE.

CONSTRUCTION TYPE: II-B, EXISTING BUILDING PARTIAL SPRINKLERED (NEW SCOPE WILL SPRINKLER REMAINING BUILDING AND FULLY DETECTED)NUMBER OF STORIES: 1OCCUPANCY: B

EXITING: PER TABLE 1020.1 CORRIDOR FIRE-RESISTANCE RATING FOR BUSINESS SPACES 0 HR WITH SPRINKLERS

AREA SEPARATION: EXISTING 2 HOUR AREA SEPARATION BETWEEN CROSSROADS BUILDING AND ADJACENT BUILDINGS TO THE WEST AND EAST

PER 2015 IBC TABLE 504.3 AND 504.4, AND 506.2: ALLOWABLE AREA, HEIGHT AND NUMBER OF STORIES AS FOLLOWS:

OCCUPANCY GROUP: TYPE: HEIGHT STORIES: ALLOWABLE AREA:B II-B 75 FEET 4 108,560 SF

ACTUAL: 14,950 GSF = IN COMPLIANCE

PER SECTION 303.1.1 AND 303.1.2 SMALL ASSEMBLY SPACES SHALL BE CLASSIFIED AS GROUP B OCCUPANCY .

TOTAL BUILDING OCCUPANTS = 198

EXISTING 2-HOUR AREA SEPARATION RATING

TO REMAIN

EXISTING 2-HOUR AREA SEPARATION RATING TO REMAIN

EXISTING 1-HOUR FIRE RATING WILL BE ABANDONED DUE TO ADDITION OF FIRE SPRINKLERS

EXISTING 1-HOUR FIRE RATING WILL BE ABANDONED DUE TO ADDITION OF FIRE SPRINKLERS

94 SF

ENTRY

121

94 SF

ENTRY

122

494 SF

CORRIDOR

123

527 SF

CORRIDOR

124

685 SFPUBLIC AREA

12 OCC

100 SF /OCC

304 SFCONF

16 OCC

15 SF /OCC

103 SFOFFICE

2 OCC

100 SF /OCC102 SFOFFICE

2 OCC

100 SF /OCC

CODE SUMMARY

1596 SFWAITING AREA

16 OCC

100 SF /OCC

87 SFOFFICE

1 OCC

100 SF /OCC104 SFOFFICE

2 OCC

100 SF /OCC139 SFOFFICE

2 OCC

100 SF /OCC

119 SFOFFICE

2 OCC

100 SF /OCC

115 SFOFFICE

2 OCC

100 SF /OCC

111 SF

VESTIBULE

128

297 SFSTORAGE

1 OCC

300 SF /OCC155 SFOFFICE

2 OCC

100 SF /OCC

FEC

126 SFOFFICE

2 OCC

100 SF /OCC

FEC

FEC

DEF

(E)

(E)

(E)

(E)

HATCHED AREA SCOPE INCLUDES NEW SPRINKLER UPGRADE

HATCHED AREA SCOPE INCLUDES NEW SPRINKLER, CEILING & LIGHT FIXTURE UPGRADE

HATCHED AREA SCOPE INCLUDES NEW SPRINKLER, CEILING & LIGHT FIXTURE UPGRADE

TRAVEL DISTANCE = 134'-6"

TRAVEL DISTANCE = 92'-6"

FIRE SPRINKLERS ADDED TO SPACE UNDER 2013 REMODEL

EXIT WIDTHREQ'D = 15 OCCUPANTS x 0.2 = 3"

PROVIDED = 68"15

15

PLUMBING COUNTS ARE BASED ON BUILDING OCCUPANCY:

** FOR THE PURPOSE OF PLUMBING CALCULATION, WE PROPOSE THE FOLLOWING OCCUPANT LOAD AND FIXTURE COUNTS BASED ON ACTUAL BUILDING USAGE. WE PROPOSE THESE FOLLOWING ASSUMPTIONS:

1. NON-OCCUPIED SPACES (VESTIBULES, STAIRS, ELEVATORS, TOILET ROOMS, SHAFTS, CLOSETS) WILL NOT BE COUNTED TOWARDS OCCUPANT LOAD FOR EXISTING OR FIXTURE COUNT, BECAUSE THE SAME OCCUPANTS ARE IN EITHER OR SCENARIO OR THOSE SPACES ARE NON-OCCUPIABLE.

2. BECAUSE SOME CIRCULATION SPACES SERVES AS PUBLIC AREAS FOR LOUNGING AND WAITING, THOSE SPECIFIC AREAS HAVE BEEN INCLUDED IN THE OCCUPANT LOAD COUNT FOR PLUMBING AND EXITING.

3. PER INTERNATIONAL PLUMBING CODE SECTION 403.3.3: IN OCCUPANCIES OTHER THAN MALLS TOILET FACILITIES SHALL BE LOCATED NOT MORE THAN ONE STORY ABOVE OR BELOW SPACE AND PATH OF TRAVEL TO STUCH FACILITIES SHALL NOT EXCEED DISTANCE OF 500 FEET. INCLUDING FIXTURES IN CROSSROADS BUILDING PLUS ADDITIONAL FIXTURES IN ADAJCENT CONNECTED ARP BUILDING RESTROOMS, MINIMUM FIXTURE COUNTS REQUIRED HAVE BEEN MET.

WC (MALE) WC (FEMALE) LAVS DF OTHERGROUP 'B'1:25 FOR 50 1:25 FOR 50 1:40 FOR 80 1:100 1 SVC SINK1:50 1:50 1:80

WC / URINAL LAVS DF SVC SINK

FIXTURES REQUIRED 3 3 - -(MALE)

FIXTURES REQUIRED 3 3 - -(FEMALE)

TOTAL REQUIRED 6 6 2 1

FIXTURE PROVIDED 14 8 2 1

PLUMBING COUNTS

CONSULTANT:

ISSUE:

OWNER:

PROJECT:

DRAWING INFORMATION:

DRAWN BY:

PROJECT NO:

SHEET TITLE:

APPROVED BY:

CHECKED BY:

SHEET OF

1 2 3 4 5 6

A

B

C

D

E

1 2 3 4 5 6

P 303.607.0977www.hcm2.com

1331 Nineteenth StreetDenver, CO. 80202

hord|coplan|macht

1/2

9/2

01

8 9

:05:4

5 P

M

C:\R

evit L

ocal F

iles\1

17

38.0

01

_LC

CC

SE

_C

CR

_C

entr

al_

twe

llner@

hcm

2.c

om

.rvt

G-101

FIRST FLOOR CODEPLAN

LARAMIE COUNTYCOMMUNITYCOLLEGE

CROSSROADSBUILDINGRENOVATION

MP

TW

11738.001

MP

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

1.4.2018 CONTRACT DOCUMENTS

1/8" = 1'-0"A1FIRST FLOOR CODE PLAN

OCCUPANCY SCHEDULE

Number Name Code Plan Name Area

Area PerOccupantCalculated Occupancy Classification Occupancy

101 MECHANICAL MECH 545 SF 100 SF Business areas 2

102 FOOD PANTRY STORAGE 375 SF 300 SF Accessory storage areas, Mechanical equipment room 2

102A FIRE SERVICE MECH 22 SF 300 SF Accessory storage areas, Mechanical equipment room 1

103 COLLABORATION PUBLIC AREA 3942 SF 100 SF Business areas 40

104A RECEPTION/WAITING RECEPTION 170 SF 100 SF Business areas 2

104B CONFERENCE ROOM CONF 183 SF 15 SF Assembly without fixed seats Unconcentrated (tables and chairs) 13

104C CORRIDOR CONF 155 SF 100 SF Business areas 0

104D STORAGE STORAGE 60 SF 100 SF Business areas 1

104E OFFICE OFFICE 216 SF 100 SF Business areas 3

104F OFFICE OFFICE 118 SF 100 SF Business areas 2

104G OFFICE OFFICE 116 SF 100 SF Business areas 2

104H OFFICE OFFICE 128 SF 100 SF Business areas 2

104J OFFICE OFFICE 123 SF 100 SF Business areas 2

104K CORRIDOR CIRC 170 SF 100 SF Business areas 0

104L OFFICE OFFICE 113 SF 100 SF Business areas 2

104M OFFICE OFFICE 113 SF 100 SF Business areas 2

105A IT/HELP DESK OFFICE 103 SF 100 SF Business areas 2

105B SPECIALIST OFFICE OFFICE 121 SF 100 SF Business areas 2

105C STORAGE STORAGE 100 SF 300 SF Accessory storage areas, Mechanical equipment room 1

106 ELEC. ELEC 70 SF 300 SF Accessory storage areas, Mechanical equipment room 1

107 COMPUTER STATIONS PUBLIC AREA 685 SF 100 SF Business areas 12

108 COMMUNITY CAFE CONF 304 SF 15 SF Assembly without fixed seats Unconcentrated (tables and chairs) 16

109 CONF ROOM CONF 541 SF 15 SF Assembly without fixed seats Unconcentrated (tables and chairs) 36

110A STUDENT VETERANSLOUNGE

RECEPTION 501 SF 100 SF Business areas 5

110B SVA OFFICE OFFICE 102 SF 100 SF Business areas 2

110C STUDY / COMPUTER CONF 204 SF 15 SF Assembly without fixed seats Unconcentrated (tables and chairs) 14

112 JAN. JAN 20 SF 300 SF Accessory storage areas, Mechanical equipment room 1

118 WAITING AREA WAITING AREA 1596 SF 100 SF Business areas 16

119 OFFICE OFFICE 87 SF 100 SF Business areas 1

120 OFFICE OFFICE 104 SF 100 SF Business areas 2

125 OFFICE OFFICE 139 SF 100 SF Business areas 2

126 OFFICE OFFICE 119 SF 100 SF Business areas 2

127 OFFICE OFFICE 115 SF 100 SF Business areas 2

129 BREAK ROOM STORAGE 297 SF 300 SF Accessory storage areas, Mechanical equipment room 1

130 OFFICE OFFICE 155 SF 100 SF Business areas 2

131 OFFICE OFFICE 126 SF 100 SF Business areas 2

Grand total 12040 SF 198

1023.7 EXTERIOR WALLS OF INTERIOR EXITS THAT ARE NOT PROTECTED AND AT AN ANGLE LESS THAN 180 DEGREES SHALL BEPROTECTED 10' HORIZONTALLY BY A 1 HR RATING WITH OPENING PROTECTION OF NOT LESS THAN 45 MIN.

SECTION 1023: INTERIOR EXIT STAIRWAYS AND RAMPS

1020.4 DEAD ENDS, WHERE MORE THAN ONE EXIT OR EXIT ACCESS DOORWAY IS REQUIRED, THE EXIT ACCESS SHALL BEARRANGED SUCH THAT THERE ARE NO DEAD ENDS IN CORRIDORS MORE THAN 20 FEET IN LENGTH. EXCEPTION 2: INOCCUPANCIES IN GROUP B, WHERE THE BUILDING IS EQUIPPED THROUGHOUT WITH AN AUTOMATIC SPRINKLERSYSTEM IN ACCORDANCE WITH 903.3.1.1, THE LENGTH OF THE DEAD-END CORRIDORS SHALL NOT EXCEED 50 FEET.

ASSEMBLY, BUSINESS: 44 INCHES CLEAR (MIN)

T1020.2 MINIMUM CORRIDOR WIDTH:

STORAGE SPACES: 0 HR (SPRINKLERS)

BUSINESS SPACES: 0 HR (SPRINKLERS)

T1020.1 CORRIDOR FIRE-RESISTANCE RATING:

SECTION 1020: CORRIDORS:

B 300 FEET (SPRINKLERS)

OCCUPANCY: MAX TRAVEL DISTANCE:

T1017.2 EXIT ACCESS TRAVEL DISTANCE:

SECTION 1017: EXIT ACCESS TRAVEL DISTANCE:

1016.2 EGRESS THROUGH INTERVENING SPACES: EGRESS THROUGH INTERVENING SPACE IS PERMITTED WHERE SUCHADJOINING SPACES ARE ACCESSORY AND PROVIDE A DISCERNIBLE PATH OF EGRESS TO AN EXIT

SECTION 1016: EXIT ACCESS:

1015.2 WHERE REQUIRED: OPEN-SIDES OF WALKING SURFACES AND BALCONIES THAT ARE LOCATED MORE THAN 30 INCHESVERTICALLY ABOVE GRADE

SECTION 1015: GUARDS:

1013.1 WHERE REQUIRED: EXIT SIGN PLACEMENT SHALL BE SUCH THAT NO POINT IN AN EXIT ACCESS CORRIDOR IS MORETHAN 100 FEET FROM EXIT ACESS OR EXIT SIGN

SECTION 1013: EXIT SIGNS:

1011.4 WIDTH: REQUIRED WIDTH SHALL BE DETERMINED BY OCCUPANT LOAD BUT SHALL NOT BE LESS THAN 44 INCHES.

1011.3.1.2 FIRE-RESISTANCE RATING: STAIRWAY ENCLOSURES CONNECTING FOUR OR MORE STORIES SHALL HAVE AFIRE-RESISTANCE RATING NOT LESS THAN TWO HOURS.

SECTION 1011: STAIRWAYS:

1010.1.9.8 ACCESS-CONTROLLED EGRESS DOORS: EGRESS DOORS w/ APPROVED ACCESS CONTROL SYSTEMS SHALL DISENGAGEw/ SIGNAL OR LOSS OF POWER, MANUAL UNLOCKING DEVICES, ACTIVATION OF BUILDING FIRE ALARM SYSTEM AND/ORACTIVATION OF BUILDING AUTOMATIC SPRINKLER SYSTEM

1010.1.1 SIZE OF DOORS: MINIMUM WIDTH OF DOOR OPENING SHALL BE AS REQUIRED FOR OCCUPANT LOAD AND SHALLPROVIDE A MINIMUM 32 INCH CLEAR WIDTH

SECTION 1010: DOORS, GATES AND TURNSTILES:

1009.8 TWO-WAY COMMUNICATION SYSTEM COMPLYING WITH SECTIONS 1009.8.1 AND 1009.8.2 SHALL BE PROVIDED AT THELANDING SERVING EACH ELEVATOR OR BANK OF ELEVATORS ON EACH ACCESSIBLE FLOOR THAT IS ONE OR MORESTORIES ABOVE OR BELOW THE LEVEL OF EXIT DISCHARGE

1009.1 ACCESSIBLE MEANS OF EGRESS REQUIRED: WHERE MORE THAN ONE MEANS OF EGRESS IS REQUIRED FROM ANACCESSIBLE SPACE, THE ACCESSIBLE SPACE SHALL BE SERVED BY NO LESS THAN TWO ACCESSIBLE MEANS OF...

SECTION 1009: ACCESSIBLE MEANS OF EGRESS:

501-1000 3

1-500 2

OCCUPANT LOAD PER STORY MIN. NUMBER OF EXITS FROM STORY

T1006.3.1 MINIMUM NUMBER OF EXITS OR ACCESS TO EXITS PER STORY

'B' 100' (SPRINKLED)

OCCUPANCY MAX CPET DISTANCE

T1006.2.1 SPACES WITH ONE EXIT OR EXIT ACCESS DOORWAY

1006.2.1 EGRESS BASED ON OCCUPANT LOAD AND COMMON PATH OF EGRESS TRAVEL DISTANCE (CPET): TWO EXITS OR EXITACCESS DOORWAYS FROM ANY SPACE SHALL BE PROVIDED WHERE THE DESIGN OCCUPANT LOAD OR THE COMMONPATH OF EGRESS TRAVEL DISTANCE EXCEEDS THE VALUES LISTED IN TABLE 1006.2.1.

SECTION 1006: NUMBER OF EXITS AND EXIT ACCESS DOORWAYS:

1005.7.1 ENCROACHMENT (DOORS): WHEN FULLY OPEN SHALL NOT REDUCE REQUIRED WIDTH MORE THAN 7 INCHES IN ANYPOSITION, DOOR SHALL NOT REDUCE REQUIRED WIDTH MORE THAN HALF

1005.3.2 OTHER EGRESS COMPONENTS: CAPACITY SHALL BE DETERMINED BY MULTIPLYING CALCULATED OCCUPANT LOAD PERFLOOR BY 0.2 INCH PER OCCUPANT

1005.3.1 STAIRWAYS: CAPACITY SHALL BE DETERMINED BY MULTIPLYING CALCULATED OCCUPANT LOAD PER FLOOR BY 0.3 INCHPER OCCUPANT

SECTION 1005: MEANS OF EGRESS SIZING:

IBC CHAPTER 10: MEANS OF EGRESS:

1 1/29/18 Addendum 1

1

ADD-1

1

ADD-1

SUCH

Page 18: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

CROSSROADS BUILDING

ARP BUILDING

COLLEGE COMMUNITY

CTR

LUDDEN LIBRARY

FINE ARTS

EDUCATION & ENRICHMENT CTR

BUSINESS & TECHNOLOGY AUTO TECH

PATHFINDER BUILDING

TOTAL DISTANCE BETWEEN RESTROOMS 334'

N

KEY PLAN

CONSULTANT:

ISSUE:

OWNER:

PROJECT:

DRAWING INFORMATION:

DRAWN BY:

PROJECT NO:

SHEET TITLE:

APPROVED BY:

CHECKED BY:

SHEET OF

1 2 3 4 5 6

A

B

C

D

E

1 2 3 4 5 6

P 303.607.0977www.hcm2.com

1331 Nineteenth StreetDenver, CO. 80202

hord|coplan|macht

1/3

0/2

01

8 1

2:2

3:4

6 P

M

C:\R

evit L

ocal F

iles\1

17

38.0

01

_LC

CC

SE

_C

CR

_C

entr

al_

twe

llner@

hcm

2.c

om

.rvt

A-100

SITE PLAN

LARAMIE COUNTYCOMMUNITYCOLLEGE

CROSSROADSBUILDINGRENOVATION

MP

TW

11738.001

MP

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

1.4.2018 CONTRACT DOCUMENTS

1 1/29/18 Addendum 1

1" = 40'-0"1SITE PLAN

1

ADD-1

Page 19: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

T45

UP UP

DN DN

DEMOLITION GENERAL

NOTES

GENERAL CONTRACTOR TO COORDINATE SCHEDULING ALL WORK WITH OWNER.

WORK LABELED (NIC), OR OTHERWISE NOT NOTED IS NOT IN CONTRACT FOR ANY ARCHITECTURAL IMPROVEMENTS.

THE GENERAL CONTRACTOR & THEIR SUBCONTRACTORS SHALL VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS WITH CONDITIONS SHOWN IN THE CONTRACT DOCUMENTS AND SHALL REPORT ANY DEVIATIONS, DISCREPANCIES AND/OR CONFLICTS TO ARCHITECT.

THE GENERAL CONTRACTOR & SUBCONTRACTOR SHALL TAKE EXTREME CARE DURING DEMOLITION NOT TO DAMAGE OR DISTURB ANY EXISTING CONDITIONS THAT ARE TO REMAIN. GENERAL CONTRACTOR OR SUBCONTRACTOR SHALL REPAIR ANY DAMAGE OR DISTURBANCE TO EXISTING CONDITIONS AT NO COST TO THE OWNER.

PROVIDE PROTECTION FOR FLOORS, WALLS, & CEILING AT ALL EXISTING CONDITIONS TO REMAIN, INCLUDING TRAFFIC AREA FOR DEMOLITION REMOVAL IN COMMON BUILDING AREAS & FREIGHT ELEVATORS. DAMAGED FLOORS WILL BE REPLACED @ NO COST TO OWNER.

REMOVE ALL WALLS, DOORS (AND OTHER ITEMS) SHOWN DASHED - FIELD VERIFY CONSTRUCTION OF ALL WALLS TO BE REMOVED - PROVIDE SHORING AND BRACING AS REQUIRED.

ALL ITEMS WITHIN WALLS TO BE REMOVED ARE NOT SHOWN -FIELD VERIFY EXISTING CONDITIONS AND TEMPORARILY OR PERMANENTLY REMOVE ITEMS AS NECESSARY FOR NEW CONSTRUCTION.

REMOVE ALL EXISTING POWER AND ASSOCIATED CONDUIT (AND OTHER MISCELLANEOUS ITEMS WHERE INDICATED) ON EXISTING WALLS TO BE REUSED. IF REMOVAL WILL DISRUPT PERFORMANCE OF ANY ITEM NOT INCLUDED IN THIS SCOPE, RELOCATE AND ENSURE PROPER FUNCTION IS RESTORED.

GENERAL CONTRACTOR TO COORDINATE ABATEMENT CONSULTANT FOR ANY CONTAMINATED MATERIALS TO BE REMOVED BEFORE WORK TO BEGIN IN THIS AREA.

REFER TO SPECIFICATIONS REGARDING; EXISTING CONDITIONS, CUTTING AND PATCHING AND SELECTIVE DEMOLITION REQUIREMENTS THAT APPLY TO ALL WORK KEY NOTES DESCRIBED ON THIS SHEET.

REFER TO (ELECTRICAL, MECHANICAL, STRUCTURAL, LANDSCAPE, ETC.) DEMOLITION DRAWINGS FOR ADDITIONAL ITEMS.

COORDINATE W/BUILDING OWNER DURING DEMOLITION TO DETERMINE WHETHER EXISTING FIRE & SMOKE DETECTION SYSTEMS ARE TO BE BAGGED, PROTECTED & REMAIN IN OPERATION OR TO BE TAKEN OFF LINE.

AREAS OF DEMOLITION SHALL BE FREE OF (FURNITURE AND MOBILE EQUIPMENT AND ACCESSORIES) PRIOR TO START OF WORK.

REMOVE (STAPLES, NAILS AND SCREWS) FROM WALLS TO REMAIN, TYPICAL THROUGHOUT.

REMOVE AND SALVAGE (ALL SIGNAGE, CLOCKS, EMERGENCY KITS, PENCIL SHARPENERS AND PHONES) FROM WALLS, (INSIDE CLASSROOMS AND IN LOBBY AREAS). PATCH AND REPAIR WALLS WHERE DAMAGED BY REMOVAL. (SALVAGE AND RETURN TO OWNER) (OR) (SALVAGE FOR NEW LOCATION)

REMOVE AND REPLACE ALL EXISTING SWITCH PLATES AND OUTLET COVERS FROM EXISTING WALLS AND REPLACE WITH NEW PLATES PER SPEC.

REMOVE ALL EXISTING WALL MOUNTED DOOR STOPPERS. PATCH AND REPAIR WALLS WHERE DAMAGED BY REMOVAL.

REMOVE ALL FLOORING (INCLUDING ADHESIVES, SETTING MATERIALS, TRANSITION MATERIALS, ETC.) AND (RUBBER) WALL BASE. PROTECT WALLS FROM DAMAGE.

REMOVE ALL WOOD DOORS. SAND DOORS SMOOTH & REFINISH TO ORIGINAL LUSTER.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

A B C D

1

2013 REMODEL NOT IN SCOPE

1

2

1

2

2

2

2

3

444 4

5

6

7

45

6

9

1011

12

13

4

214

12

2' - 8 1/2"

4' - 0"

2' - 8 1/4"

4' - 0"

2' - 8 1/4"

4' - 0" 3' - 4 1/2" 4' - 0"

5' - 0" 3' - 4"

15

16

16

12

ALTERNATE NO. 4

9' -

8 1

/2"

3' -

0"

17

17

17

17

1

ADD-1

1

ADD-1

17 17

17

N

KEY PLAN

CONSULTANT:

ISSUE:

OWNER:

PROJECT:

DRAWING INFORMATION:

DRAWN BY:

PROJECT NO:

SHEET TITLE:

APPROVED BY:

CHECKED BY:

SHEET OF

1 2 3 4 5 6

A

B

C

D

E

1 2 3 4 5 6

P 303.607.0977www.hcm2.com

1331 Nineteenth StreetDenver, CO. 80202

hord|coplan|macht

1/3

0/2

01

8 7

:31:0

2 A

M

C:\R

evit L

ocal F

iles\1

17

38.0

01

_LC

CC

SE

_C

CR

_C

entr

al_

twe

llner@

hcm

2.c

om

.rvt

AD-111

FIRST FLOORDEMOLITION PLAN

LARAMIE COUNTYCOMMUNITYCOLLEGE

CROSSROADSBUILDINGRENOVATION

Checker

Author

11738.001

Approver

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

1.4.2018 CONTRACT DOCUMENTS

SHEET NOTES - DEMOLITIONPLANS

NOTE # NOTE1 DEMO EXISTING CARPET THRU-OUT

2 DEMO EXISTING DEMOUNTABLE PARTITIONS, DOOR FRAMES, DOORS& HARDWARE

3 DEMO EXISTING CERAMIC TILE

4 DEMO EXISTING WALL AND WINDOW

5 DEMO EXISTING TRANSACTION COUNTER

6 DEMO EXISTING SLIDING SECURITY GRILLE

7 DEMO EXISTING POWER POLE WOOD POST

9 DEMO EXISTING CASEWORK AND COUNTER TOP IN ITS ENTIRETY

10 DEMO EXISTING WALL FOR NEW DOOR

11 DEMO EXISTING GYP. BOARD SOFFIT ABOVE

12 DEMO EXISTING WALL

13 DEMO EXISTING DOOR

14 DEMO EXISTING VAULT DOOR AND LINTEL ABOVE DOOR AND CMUWALLS IN THEIR ENTIRETY

15 REMOVE EXISTING DEFLIBERATOR AND REINSTALL AS NOTED

16 REMOVE EXISTING FIRE EXTINGUISHER AND CABINET ANDREINSTALL AS NOTED

17 DEMO EXISTING WALLPAPER FLOOR TO CEILING, SKIM COAT WALLSAND PREP FOR NEW PAINT

1/8" = 1'-0"A1DEMOLITION FLOOR PLAN

1 1/29/18 Addendum 1

1

ADD-1

1

ADD-1

1

ADD-1

1

ADD-1

1

ADD-1

Page 20: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

A B C D

1

1

2

3

1

1

1

1

1

11

1 1

1

1

11

1

1

2

4

4

5

5

5

1

1

1

6

1

1

D1

A-300

E3

A-522

2013 REMODEL NOT IN SCOPE

A4

A-610

1

1

1

ADD-1

DEMOLITION RCP GENERAL NOTES

GENERAL CONTRACTOR TO COORDINATE SCHEDULING ALL WORK WITH OWNER.

WORK LABELED (NIC), OR OTHERWISE NOT NOTED IS NOT IN CONTRACT FOR ANY ARCHITECTURAL IMPROVEMENTS.

THE GENERAL CONTRACTOR & THEIR SUBCONTRACTORS SHALL VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS WITH CONDITIONS SHOWN IN THE CONTRACT DOCUMENTS AND SHALL REPORT ANY DEVIATIONS, DISCREPANCIES AND/OR CONFLICTS TO ARCHITECT.

THE GENERAL CONTRACTOR & SUBCONTRACTOR SHALL TAKE EXTREME CARE DURING DEMOLITION NOT TO DAMAGE OR DISTURB ANY EXISTING CONDITIONS THAT ARE TO REMAIN. GENERAL CONTRACTOR OR SUBCONTRACTOR SHALL REPAIR ANY DAMAGE OR DISTURBANCE TO EXISTING CONDITIONS AT NO COST TO THE OWNER.

PROVIDE PROTECTION FOR FLOORS, WALLS, & CEILING AT ALL EXISTING CONDITIONS TO REMAIN, INCLUDING TRAFFIC AREA FOR DEMOLITION REMOVAL IN COMMON BUILDING AREAS & FREIGHT ELEVATORS. DAMAGED FLOORS WILL BE REPLACED @ NO COST TO OWNER.

REMOVE ALL WALLS, DOORS (AND OTHER ITEMS) SHOWN DASHED - FIELD VERIFY CONSTRUCTION OF ALL WALLS TO BE REMOVED - PROVIDE SHORING AND BRACING AS REQUIRED.

ALL ITEMS WITHIN WALLS TO BE REMOVED ARE NOT SHOWN -FIELD VERIFY EXISTING CONDITIONS AND TEMPORARILY OR PERMANENTLY REMOVE ITEMS AS NECESSARY FOR NEW CONSTRUCTION.

REMOVE ALL EXISTING POWER AND ASSOCIATED CONDUIT (AND OTHER MISCELLANEOUS ITEMS WHERE INDICATED) ON EXISTING WALLS TO BE REUSED. IF REMOVAL WILL DISRUPT PERFORMANCE OF ANY ITEM NOT INCLUDED IN THIS SCOPE, RELOCATE AND ENSURE PROPER FUNCTION IS RESTORED.

GENERAL CONTRACTOR TO COORDINATE ABATEMENT CONSULTANT FOR ANY CONTAMINATED MATERIALS TO BE REMOVED BEFORE WORK TO BEGIN IN THIS AREA.

REFER TO SPECIFICATIONS REGARDING; EXISTING CONDITIONS, CUTTING AND PATCHING AND SELECTIVE DEMOLITION REQUIREMENTS THAT APPLY TO ALL WORK KEY NOTES DESCRIBED ON THIS SHEET.

REFER TO (ELECTRICAL, MECHANICAL, ETC.) DEMOLITION DRAWINGS FOR ADDITIONAL ITEMS.

COORDINATE W/ BUILDING OWNER DURING DEMOLITION TO DETERMINE WHETHER EXISTING FIRE & SMOKE DETECTION SYSTEMS ARE TO BE BAGGED, PROTECTED & REMAIN IN OPERATION OR TO BE TAKEN OFF LINE.

AREAS OF DEMOLITION SHALL BE FREE OF (FURNITURE AND MOBILE EQUIPMENT AND ACCESSORIES) PRIOR TO START OF WORK.

REMOVE (STAPLES, NAILS AND SCREWS) FROM WALLS TO REMAIN, TYPICAL THROUGHOUT.

REMOVE AND SALVAGE (ALL SIGNAGE, CLOCKS, EMERGENCY KITS, PENCIL SHARPENERS AND PHONES) FROM WALLS. PATCH AND REPAIR WALLS WHERE DAMAGED BY REMOVAL. (SALVAGE AND RETURN TO OWNER, U.O.N.

REMOVE AND REPLACE ALL EXISTING SWITCH PLATES AND OUTLET COVERS FROM EXISTING WALLS AND REPLACE WITH NEW PLATES PER SPEC.

REMOVE ALL EXISTING WALL MOUNTED DOOR STOPPERS. PATCH AND REPAIR WALLS WHERE DAMAGED BY REMOVAL.

REMOVE ALL FLOORING (INCLUDING ADHESIVES, SETTING MATERIALS, TRANSITION MATERIALS, ETC.) AND (RUBBER) WALL BASE. PROTECT WALLS FROM DAMAGE.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

N

KEY PLAN

CONSULTANT:

ISSUE:

OWNER:

PROJECT:

DRAWING INFORMATION:

DRAWN BY:

PROJECT NO:

SHEET TITLE:

APPROVED BY:

CHECKED BY:

SHEET OF

1 2 3 4 5 6

A

B

C

D

E

1 2 3 4 5 6

P 303.607.0977www.hcm2.com

1331 Nineteenth StreetDenver, CO. 80202

hord|coplan|macht

1/2

9/2

01

8 9

:05:3

9 P

M

C:\R

evit L

ocal F

iles\1

17

38.0

01

_LC

CC

SE

_C

CR

_C

entr

al_

twe

llner@

hcm

2.c

om

.rvt

AD-121

FIRST FLOORREFLECTED CEILINGDEMOLITION PLAN

LARAMIE COUNTYCOMMUNITYCOLLEGE

CROSSROADSBUILDINGRENOVATION

Checker

Author

11738.001

Approver

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

1.4.2018 CONTRACT DOCUMENTS

1/8" = 1'-0"A1DEMOLITION REFLECTED CEILING PLAN

SHEET NOTES - DEMOLITIONREFLECTED CEILING PLANS

NOTE # NOTE1 DEMO EXISTING CEILING AND GRID

2 DEMO EXISTING BULKHEAD

3 DEMO EXISTING WOOD CEILING

4 DEMO EXISTING OPERABLE PARTITIONS AND HOUSING

5 DEMO EXISTING SOFFIT

6 DEMO EXISTING CONCRETE CEILING IN ITS ENTIRETY. RE: DEMODETAILS

1 1/29/18 Addendum 1

1

ADD-1

Page 21: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

UP

UP

UP

FLOOR PLAN GENERAL NOTES

DIMENSIONS INDICATED ARE TO FACE OF FINISH MATERIAL OF PARTITION OR WALL AND GRID LINES, UON

REFER TO FINISH PLANS FOR INTERIOR ELEVATION CALLOUTS, ENLARGED PLAN CALLOUTS AND FLOOR PATTERNS.

REFER TO FINISH PLANS FOR MARKER/TACK/LCD SCREEN SIZES AND LOCATIONS.

PROVIDE BLOCKING AT ALL WALL-MOUNTED ACCESSORIES HARDWARE WHERE REQUIRED AND WALL-HUNG CABINETS.

VERIFY & COORDINATE ALL REQUIREMENTS FOR OWNER FURNISHED ITEMS PRIOR TO PERFORMANCE OF WORK THAT MAY INTERFACE WITH SUCH ITEMS.

PROVIDE PAINTED ACCESS PANELS IN WALLS & CEILINGS AT CONCEALED ITEMS, SUCH AS VALVES, CONTROLS, SWITCHES OR ANY OTHER ITEMS THAT REQUIRES ACCESS. GC TO DETERMINE ACCESS PANEL LOCATION W/ ARCHITECT PRIOR TO INSTALLATION.

1.

2.

3.

4.

5.

6.

A B C D

1

100 SF

STORAGE

105C

121 SF

SPECIALISTOFFICE

105B

123 SF

OFFICE

104J

128 SF

OFFICE

104H

116 SF

OFFICE

104G

118 SF

OFFICE

104F

216 SF

OFFICE

104E60 SF

STORAGE

104D

183 SF

CONFERENCEROOM

104B

165 SF

VESTIBULE

100

545 SF

MECHANICAL

101

375 SF

FOODPANTRY

102

FIRESERVICE

102A

204 SF

STUDY /COMPUTER

110C

501 SF

STUDENTVETERANSLOUNGE

110A

20 SF

JAN.

112

3942 SF

COLLABORATION

103

180 SF

WOMEN'STOILET

114

188 SF

MEN'STOILET

11399 SF

CORR.

111

C1

A-300

541 SF

CONFROOM

109

IDFRACK

2013 REMODEL NOT IN SCOPE

113 SF

OFFICE

104L

170 SF

CORRIDOR

104K

155 SF

CORRIDOR

104C

170 SF

RECEPTION/WAITING

104A

113 SF

OFFICE

104M

A1

A-300

304 SF

COMMUNITYCAFE

108

103 SF

IT/HELPDESK

105A

102 SF

SVAOFFICE

110B

685 SF

COMPUTERSTATIONS

107

70 SF

ELEC.

106

104A

104M

104B

109

110B

110A 104K

104L

110C

105A

2-3A

2-3A

2-3F

2-3A

2-3F

2-3A

2-3A

2-3A

2-3A

2-3A

3-3A

3-3A3-3A

2-3A

10' - 0" 4' - 9"

10

' -

0"

10

' -

3 1

/2"

2-3A

15

' -

3 1

/4"

5' - 4 1/2"

ALIGN

75.0°

ALIG

N

SKYLIGHT ABOVE, TYP

3' - 1

0 3

/4" 1

3' - 4

1/2

"

11' - 6" 9' - 0"

2' -

9"

16

' -

7"

EQ EQ

A A A

A

105C

105B

104J

104H

104G

104F

104E

104D

A-521

E6

2-3A

F.3

F.2

F.1

ALTERNATE NO. 1

D1

A-300

2-3A

2-3A

1-3A

1-3A

4' - 8"

2-3A

1

5' - 0" 3' - 4"

2

3

3

105D

103

105D

103

2-6A

A-520

B4

96.0°

8' - 9 1/2"

3' -

0"

5' -

0"

11' - 8" 8' - 1 1/4"

11' - 9 1/2" 2' - 5" 2' - 5" 6' - 5" 2' - 5" 2' - 5"

16

' -

1 1

/4"

2' -

4"

11' - 7 1/4"

10

' - 1

1 1

/2"

3' -

5"

6' -

4 1

/2"

10' - 4" 11' - 0 1/2"

ALIGN

1' -

5 3

/4"

2' - 0"

1-3F

1-3F

1-3F

A-610

A3

F.4

3' -

0"

10

' -

4"

4

7' - 8 1/4" 5' - 10 1/4"

5' - 2 3/4"

TYP. OF 3

2-6A

3' -

1"

2' -

10

"7

' -

4 1

/2"

5' - 1 1/2" 11 1/4"

5' -

0 1

/2"

9' -

2 1

/4"

1' -

0 1

/4"

8' - 4"

8' -

2 1

/4"

2-3A ABOVE

A4

A-610

5

A1

ADD-1

6

94 SF

ENTRY

122

494 SF

CORRIDOR

123

527 SF

CORRIDOR

124

94 SF

ENTRY

121

1

ADD-1

1

ADD-1

NO

M.

1/4

"

NO

M.

1/4

"

1"

PARTITION

PARTITION

PARTITION

PARTITION

PARTITION

PARTITION

PARTITION

PARTITION

PARTITION

1-HR

1-2-

1-3-

1-6-

1-8-

2-X-

2-8-

2-6-

2-3-

2-2-

NON-RATED PARTITION HEAD---F

PLAN DETAIL @ PARTITION INTERSECTION

ASSEMBLY

RATED WALL

PLAN DETAIL - NON-RATED CONTROL JOINT

1/2"

PARTITION TYPES LEGEND

2-6A

2-6A1HR

PARTITION TYPES NOTES

NO

M.

1/4

"

PARTITION

PARTITION

PARTITION

PARTITION

PARTITION

1-HR

3-X-

3-8-

3-6-

3-3-

3-2-

GYP BD

METAL STUD

BASE- RE: FINISH PLAN

RUNNER CHANNEL

SEALANT

GYP BD- BOTH SIDES

METAL STUD

BASE- RE: FINISH PLAN

RUNNER CHANNEL

SEALANT- BOTH SIDES

FLOOR OR ROOF DECK

DEEP LEG TOP TRACK

METAL STUD

GYP BD- BOTH SIDES

CEILING

WITH 2-1/2" METAL STUD PARTITION WIDTH = 3-1/8"

WITH 3-5/8" METAL STUD PARTITION WIDTH = 4-1/4"

WITH 6" METAL STUD PARTITION WIDTH = 6-5/8"

WITH 8" METAL STUD PARTITION WIDTH = 8-5/8"

WITH 2-1/2" METAL STUD PARTITION WIDTH = 3-3/4"

WITH 3-5/8" METAL STUD PARTITION WIDTH = 4-7/8"STC: 45

WITH 6" METAL STUD PARTITION WIDTH = 7-1/4"STC: 45

WITH 8" METAL STUD PARTITION WIDTH = 9-1/4"STC: 45

WITH STUD AS INDICATEDU.L. DESIGN = U419

SEE GENERAL PARTITION TYPE FOR REQUIRED STUD SIZE AND LAYERS OF GYP. BD. (2 LAYERS SHOWN)

RE: PLANS FOR SCHEDULED PARTITION

TYPES

RE: PLANS FOR SCHEDULED PARTITION

TYPES

GYP. BD. ACCESSORY -CONTROL JOINT - BOTH

SIDES

SEALANT - BOTH SIDES

PARTITION TYPE -FIRST POSITION INIDCATES GENERALPARTITION TYPE

PARTITION TYPE -SECOND POSITION INDICATESRELATIVE WIDTH OF PARTITION

LETTER INDICATES CONDITION AT HEAD OF PARTITION

FIRE RATING IS CALLED OUT BELOW TAG

1. PARTITION TYPES ARE INDICATED ON THE FLOOR PLANS.

2. ALL PARTITIONS SHALL EXTEND STRUCTURE TO STRUCTURE UNLESS NOTED OTHERWISE.

3. CONSTRUCTION OF FIRE-RATED PARTITIONS, INCLUDING TAPING AND FINISHING OF GYP. BD. FOR FULL HEIGHT TO STRUCTURE ABOVE, SHALL BE IN ACCORDANCE WITH MANUFACTURER'S DIRECTIONS TO ACHIEVE THE RATING INDICATED.

4. SOUND ISOLATION PARTITIONS SHALL BE SEALED AIRTIGHT FOR FULL HEIGHT TO PREVENT PASSAGE OF AIRBORNE SOUND. TAPE AND FINISH ALL GYP. BD. JOINTS AND FASTENERS, PROVIDE SEALANT AT PERIMETER AND AT ALL PENETRATIONS.

5. PROVIDE FIRE-RETARDANT TREATED WOOD BLOCKING FOR PARTITION MOUNTED EQUIPMENT AND CASEWORK.

6. PARTITION TYPES DESCRIBE THE PRIMARY MEMBER AND SHEATHING. REFER TO FINISH SCHEDULE FOR ALL PARTITION FINISH DESIGNATIONS.

7. PROVIDE TYPE 'WR' WATER RESISTANT GYP. BD. IN ALL WET AREAS SUCH AS TOILET, LOCKER, AND SHOWER ROOMS. PROVIDE 5/8" CONCRETE BACKER BOARD AT ALL CERAMIC TILE FINISHES TO ALIGN WITH 5/8" TYPE 'WR' GYP. BD. ABOVE.

8. PROVIDE SLIP JOINT CONNECTIONS AT THE TOPS OF ALL PARTITIONS WHICH INTERSECT THE STRUCTURE ABOVE. PROVIDE FIRE SAFING AT ALL SLIP JOINT CONNECTIONS IN FIRE RATED PARTITIONS.

9. ALL PARTITIONS TO BE PARTITION TYPE (3-5/8" METAL STUD WITH SOUND ATTENUATION INSULATION AND (1) LAYER OF 5/8" GYP. BD. ON BOTH SIDES) AND SHALL EXTEND STRUCTURE TO STRUCTURE, UNLESS NOTED OTHERWISE WITH A PARTITION TYPE TAG. THIS DEFAULT PARTITION TYPE IS NON-RATED. THIS SAME PARTITION TYPE IN A RATED CONDITION IS TAGGED ON THE FLOOR PLANS.

10. PROVIDE GYP. BD. CONTROL JOINTS WHERE DESIGNATED ON THE INTERIOR ELEVATIONS (A-420 SHEETS) AND ANYWHERE THERE IS A CONTINUOUS RUN OF GYP. BD. THAT IS GREATER THAN 30'-0" IN LENGTH. CONFIRM THE LOCATION OF ADDITIONAL CONTROL JOINTS WITH THE ARCHITECT PRIOR TO INSTALLATION.

FLOOR LINE FLOOR LINE

GYP BD- BOTH SIDES

METAL STUD

BASE- RE: FINISH PLAN

RUNNER CHANNEL

SEALANT- BOTH SIDES

WITH 2-1/2" METAL STUD PARTITION WIDTH = 4-3/8"

WITH 3-5/8" METAL STUD PARTITION WIDTH = 5-1/2"STC: 50

WITH 6" METAL STUD PARTITION WIDTH = 7-7/8"STC: 50

WITH 8" METAL STUD PARTITION WIDTH = 9-7/8"STC: 50

WITH STUD AS INDICATEDU.L. DESIGN = U419

FLOOR LINE

1"

NON-RATED PARTITION HEAD---A

FLOOR OR ROOF DECK

DEEP LEG TOP TRACK

METAL STUD

GYP BD- BOTH SIDES

CEILING

SEE GENERAL PARTITION TYPE FOR REQUIRED STUD SIZE AND LAYERS OF GYP. BD. (2 LAYERS SHOWN)

SOUND ATTENTUATION BLANKET

TYPE 'X' GYP. BOARD

SOUND ATTENTUATION BLANKET

TYPE 'X' GYP. BOARD

NEW WALL

EXISTING WALL

WALL LEGEND

N

KEY PLAN

CONSULTANT:

ISSUE:

OWNER:

PROJECT:

DRAWING INFORMATION:

DRAWN BY:

PROJECT NO:

SHEET TITLE:

APPROVED BY:

CHECKED BY:

SHEET OF

1 2 3 4 5 6

A

B

C

D

E

1 2 3 4 5 6

P 303.607.0977www.hcm2.com

1331 Nineteenth StreetDenver, CO. 80202

hord|coplan|macht

1/2

9/2

01

8 9

:05:0

7 P

M

C:\R

evit L

ocal F

iles\1

17

38.0

01

_LC

CC

SE

_C

CR

_C

entr

al_

twe

llner@

hcm

2.c

om

.rvt

A-111

FIRST FLOOR PLAN

LARAMIE COUNTYCOMMUNITYCOLLEGE

CROSSROADSBUILDINGRENOVATION

TW

TM

11738.001

MP

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

1.4.2018 CONTRACT DOCUMENTS

SHEET NOTES -CONSTRUCTION PLANS

NOTE # NOTE1 EXISTING UNDERCOUNTER REF TO BE RELOCATED

2 RELOCATED DEFIBRILLATOR, MOUNTED AT EXISTING HEIGHT

3 RELOCATED FIRE EXTINGUISHER AND CABINET, MOUNT ATEXISTING HEIGHT

4 FLOOR BOX, RE: ELEC DWGS

5 EXISTING DRINKING FOUNTAIN

6 FILL SLAB WITH SELF LEVELING CONCRETE AT EXISTINGCUTOUT. DIMS TO BE VERIFIED IN FIELD.

1/8" = 1'-0"A1FIRST FLOOR

1 1/29/18 Addendum 1

1

ADD-1

Page 22: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

J

J

JJ

J

J

A B C D

1

C1

A-300

C-2

9' - 0"

A1

A-300

C-1

11' - 0"

C-7

11' - 6"

C-1

10' - 6"

C-6

9' - 6"

C-1

10' - 6"

C-2

9' - 0"

C-6

8' - 0"

C-1

9' - 0"

C-2

10' - 6"

C-1

10' - 0"

C-2

10' - 6"

C-2

10' - 0"

C-2

9' - 0"

C-2

9' - 0"

C-2

9' - 0"

C-2

9' - 0"

4' -

0"

16

' -

0"

EQ

6' - 0 1/4" 20' - 0"

11

' -

3"

58

' -

8 3

/4"

8' -

10

"

12' - 1 1/2"

COLLABORATION

103

CONFROOM

109

STUDENTVETERANSLOUNGE

110A

COMMUNITYCAFE

108

STUDY /COMPUTER

110C

OFFICE

104L

OFFICE

104M

CORRIDOR

104K

SPECIALISTOFFICE

105B

OFFICE

104J

OFFICE

104H

OFFICE

104G

OFFICE

104F

OFFICE

104E

STORAGE

104D

RECEPTION/WAITING

104A

CONFERENCEROOM

104BCORRIDOR

104C

STORAGE

105C

COMPUTERSTATIONS

107 IT/HELPDESK

105A

SVAOFFICE

110B

2' - 2 1/4"

3

5

1

P-5

P-5

C-2

9' - 0"

C-2

9' - 0"6" TYP

C-1

9' - 0"

C-2

10' - 0"

93.0°

5' -

0"

ALIG

N

EQ

EQ16' - 0"EQ

1

1

1

1

1

1

1

1

1

11

1

1

1

1

1

2

3

2

2

3

3

ELEC.106

C-2

9' - 0"

VESTIBULE100

1

A1

A-522

D3

A-522

C1

A-522

C3

A-522

C1

A-522

C1

A-522

BULKHEAD ABOVE

D5

A-522

C2

A-522

D1

A-522

P-5

P-5

MEN'STOILET

113

WOMEN'STOILET

114

CORR.

111

JAN.

112

80.6

°

C-5

C-2

9' - 0"

C-2

9' - 0"

C-2

9' - 0"

C-2

9' - 0"C-2

9' - 0"

C-2

9' - 0"

C-2

9' - 0"

C-2

9' - 0"

C-2

9' - 0"C-2

9' - 0"

C-2

9' - 0"

C-2

9' - 0"

4

4

EQ EQ

ALIGN

4

ALIGN

C-2

9' - 0"

C-2

9' - 0"

C-2

9' - 0"

C-5

A4

A-522 2

80.6

°

20' - 0"

EQ

EQ

6

EQ EQ

5' - 6" 10' - 0" 10' - 0"

EQ 11' - 2" EQ

6' -

6 1

/4"

7' -

10

"

5' - 0

"3' - 4

"3' - 1

1"

5' - 7

"6' - 2

3/4

"7' - 2

"7' - 2

"7' - 2

"

EQ 9' - 6 3/4" EQ

13' - 8 3/4"

L2

L3

L1L1

1' - 1 1/4"

5' - 11"

2' - 6

3/4

"6' - 1

1/4

"6' - 1

1/4

"

1' -

5"

A4

A-610

1

ADD-1

1

ADD-1

527 SF

CORRIDOR

124

94 SF

ENTRY

121

94 SF

ENTRY

122

494 SF

CORRIDOR

123

RCP GENERAL NOTES

ALL CEILING ELEVATIONS DIMENSIONED FROM FINISH FLOOR BELOW.

CENTER ALL DEVICES, SPRINKLER HEADS, ETC. IN CEILING TILE.

FIRE SPRINKLER CONTRACTOR TO REFERENCE ALL DRAWINGS & SPECIFICATIONS FOR DETERMING REQUIRED COVERAGE & HEAD LAYOUT/ DESIGN.

PAINT ALL EXPOSED STRUCTURE, RE: FINISH LEGEND

ALL GYPSUM BOARD SOFFITS AT 9'-0" AFF U.O.N.

PAINT ALL SOFFITS P-5 U.O.N.

1.

2.

3.

4.

5.

6.

CEILING TYPE LEGEND

NEW GYP BD

NEW 2X4 ACT, NEW GRID

NOT USED

NOT USED

OPEN TO STRUCTURE

WOOD CEILING

PERFORATED METAL CEILING, PAINT STRUCTURE ABOVE P-7

C-1

C-2

C-3

C-4

C-5

C-6

C-7

1

ADD-1

N

KEY PLAN

CONSULTANT:

ISSUE:

OWNER:

PROJECT:

DRAWING INFORMATION:

DRAWN BY:

PROJECT NO:

SHEET TITLE:

APPROVED BY:

CHECKED BY:

SHEET OF

1 2 3 4 5 6

A

B

C

D

E

1 2 3 4 5 6

P 303.607.0977www.hcm2.com

1331 Nineteenth StreetDenver, CO. 80202

hord|coplan|macht

1/2

9/2

01

8 9

:05:0

9 P

M

C:\R

evit L

ocal F

iles\1

17

38.0

01

_LC

CC

SE

_C

CR

_C

entr

al_

twe

llner@

hcm

2.c

om

.rvt

A-121

FIRST FLOORREFLECTED CEILINGPLAN

LARAMIE COUNTYCOMMUNITYCOLLEGE

CROSSROADSBUILDINGRENOVATION

MP

TW

11738.001

MP

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

1.4.2018 CONTRACT DOCUMENTS

1/8" = 1'-0"A1FIRST FLOOR REFLECTED CEILING PLAN

SHEET NOTES - RCP

NOTE # NOTE1 NEW GRID, CEILING TILES & LIGHT FIXTURES AS SCHEUDLED

THROUGHOUT SCOPE OF WORK. RE: ELEC DRAWINGS FORADDITIONAL INFORMATION

2 DECORATIVE PENDANT LIGHT FIXTURE, RE: ELEC DRAWINGS

3 NEW GYP & LIGHTING

4 CONTROL JOINT, TYP

5 NEW METAL GRID TILES & LIGHT FIXTURES AS SCHEUDLEDTHROUGHOUT SCOPE OF WORK. RE: ELEC DRAWINGS FORADDITIONAL INFORMATION

6 AT C-5, PAINT ALL EXPOSED ELEMENTS (PIPING, DUCTWORK,STRUCTURE) ABOVE GRID P-7

1 1/29/18 Addendum 1

DECORATIVE LIGHT FIXTURE SCHEDULETYPE DESCRIPTION LAMP MANUFACTURER FINISH MOUNTING NOTE

L1 PENDANT ACCENT LIGHT, 277V ELECTRONIC LED DRIVER, 0-10V DIMMING,1309 LUMENS, 5-YR WARRANTEE

LED, 3000,26.9W, 80 CRI

BEGA VELVET BLACK W/ MATTECOPPER INTERIOR

CEILING, +8'-6" AFF GENTS

L2 PENDANT ACCENT LIGHT, ELECTRONIC LED DRIVER, 0-10V DIMMING, WITHSOCKET HOLDER FOR EDISON BASE, 1-YR WARRANTEE

LED, 2200K, 2W BRUCK LIGHTING BYLEDRA BRANDS

BRUSHED NICKEL CEILING, +7'-0" TO +8'-6" INVARYING INCREMENTS

MULTI LINE VOLTAGE PENDANT -5 POINT CANOPY, BRONZE

L3 WALL MOUNTED ACCENT LIGHT WITH INDUSTRIAL PIPING LED CUSTOM WALL MOUNTED REFER TO ALLOWANCE NO. 1FOR ADDITIONAL INFORMATION

Page 23: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

UP

UP

UP

A-411

A1

7

3942 SF

COLLABORATION

103

541 SF

CONFROOM

109

102 SF

SVAOFFICE

110B

501 SF

STUDENTVETERANSLOUNGE

110A

204 SF

STUDY /COMPUTER

110C

188 SF

MEN'STOILET

113

180 SF

WOMEN'STOILET

114

99 SF

CORR.

111

304 SF

COMMUNITYCAFE

108

100 SF

STORAGE

105C

70 SF

ELEC.

106

121 SF

SPECIALISTOFFICE

105B

123 SF

OFFICE

104J

128 SF

OFFICE

104H

116 SF

OFFICE

104G

118 SF

OFFICE104F

170 SF

CORRIDOR

104K

113 SF

OFFICE

104L

113 SF

OFFICE104M

183 SF

CONFERENCEROOM

104B

170 SF

RECEPTION/WAITING

104A

165 SF

VESTIBULE

100

60 SF

STORAGE

104D

216 SF

OFFICE

104E

155 SF

CORRIDOR

104C

375 SF

FOODPANTRY

102 545 SF

MECHANICAL

101

A-420

A4

A1

A3

A-420

C3

A-420 C1

685 SF

COMPUTERSTATIONS

107

103 SF

IT/HELPDESK

105A

A-420 B2

A-420

D1

A-420D2

A-420B1

A-420 B1

OP

P.

ADA

1 1

2

2

ALIGN

TR

-1

TR-2

TR

-3T

R-3

3

P-2

WC

-1

CGCG

CG

CG

P-4

P-4

P-4

P-4

P-4

TR-1

80.6

°

WC

-1

B4

A-420

E1

A-411

A3

TR-2

TR-2

2

5

P-2

P-3

CG

MTL-1 P-3

6

WC-1

P-4

P-4

P-4

DP-1

P-4

A-420

B6

RS-1

P-3

A-420

D3

CG

CG

A-420

8' -

9 1

/2"

6' - 2 1/2" 2

22

VD-1

4

A-420 D4

WD-1

WD-1

2

1

ADD-1

94 SF

ENTRY

121

527 SF

CORRIDOR

124494 SF

CORRIDOR

123

94 SF

ENTRY

122

1. THE FOLLOWING INTERIOR FINISHES ARE LOCATED THROUGHOUT THE SCOPE OF WORK, UNLESS NOTED OTHERWISE. REFER TO INTERIOR FINISH LEGEND FOR SPECIFICATION:

a. ALL INTERIOR WALLS TO BE PAINTED P-1b. CARPET THROUGHOUT TO BE CPT-1c. BASE THROUGHOUT TO BE RB-1d. ALL WINDOW SILLS TO BE SS-1e. ALL HM DOOR FRAMES TO BE PAINTED P-6

2. ALL FLOOR MATERIALS TO BE BUTT JOINTED AT TRANSITIONS ON CENTER OF DOOR WHERE APPLICABLE, UNO. PROVIDE EDGE PROTECTION AND TRANSITION PROFILES WHERE FLOOR MATERIAL CHANGES AND/OR STOPS. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

3. PAINT ALL (EXPOSED PIPES, AIR GRILLES, ETC.) TO MATCH ADJACENT WALL COLOR.

4. ALL WALL (MOUNTED CASEWORK, MILLWORK, HARDWARE, EQUIPMENT, ETC.) SHALL BE ANCHORED TO METAL STRAPPING OR ½” FRT PLYWOOD BACKING BETWEEN STUDS,U.N.O. COORDINATE ACCORDINGLY.

5. REFER TO A-400 SHEETS AND OTHER DRAWINGS IN ADDITION TO THE FINISH PLANS AND KEYNOTE LEGEND FOR THE FULL EXTENT OF INTERIOR FINISHES.

6. ALL FLOORING MATERIALS CONTINUE UNDER CASEWORK TO TOE KICK OR IF OPEN, TO WALL.

7. REPLACE ALL EXISTING VINYL CORNER GUARDS.

8. RUBBER BASE TO BE REMOVED AND REPLACE WITH RB-1 IN CROSSROADS, VESTIBULES (121, 122) AND CORRIDORS BETWEEN BUILDINGS (123, 124).

FINISH PLAN GENERAL NOTES

1

ADD-1

CARPET - LVT

CARPET - CONCRETE

CARPET - PORCELAIN TILE

FLOOR TRANSITION LEGEND

TR-1

TR-2

TR-3

XXX

#

WALL FINISH SYMBOL

SHEET NOTE SYMBOL

FINISH SYMBOL LEGEND

CORNER GUARD

CEILING FINISH SYMBOLXXTR-?

TRANSITION TAG

CG

PATTERN DIRECTION

CPT 1

CPT 3

SC-1

FLOOR FINISH LEGEND

CPT 2

LVT

N

KEY PLAN

CONSULTANT:

ISSUE:

OWNER:

PROJECT:

DRAWING INFORMATION:

DRAWN BY:

PROJECT NO:

SHEET TITLE:

APPROVED BY:

CHECKED BY:

SHEET OF

1 2 3 4 5 6

A

B

C

D

E

1 2 3 4 5 6

P 303.607.0977www.hcm2.com

1331 Nineteenth StreetDenver, CO. 80202

hord|coplan|macht

1/2

9/2

01

8 9

:05:1

5 P

M

C:\R

evit L

ocal F

iles\1

17

38.0

01

_LC

CC

SE

_C

CR

_C

entr

al_

twe

llner@

hcm

2.c

om

.rvt

A-141

FIRST FLOOR FINISHPLAN

LARAMIE COUNTYCOMMUNITYCOLLEGE

CROSSROADSBUILDINGRENOVATION

TW

TM

11738.001

MP

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

1.4.2018 CONTRACT DOCUMENTS

1/8" = 1'-0"A1FIRST FLOOR FINISH PLAN

ROOM FINISH SCHEDULEROOM

NUMBER ROOM NAME

FINISH MILLWORK

MISCFLOOR BASE WALL HORIZONTAL VERTICAL100 VESTIBULE CPT-3 RB-1 P-1

103 COLLABORATION CPT-1, CPT-2 RB-1 P-1, MTL-1,WC-1

FIREPLACE: CT-1,WD-1

104A RECEPTION/WAITING CPT-1 RB-1 P-1, P-3

104B CONFERENCE ROOM CPT-1 RB-1 P-1, P-2, WD-1

104C CORRIDOR CPT-1 RB-1 P-1

104D STORAGE SC-1 RB-1 P-1

104E OFFICE CPT-1 RB-1 P-1, P-4

104F OFFICE CPT-1 RB-1 P-1, P-4

104G OFFICE CPT-1 RB-1 P-1, P-4

104H OFFICE CPT-1 RB-1 P-1, P-4

104J OFFICE CPT-1 RB-1 P-1, P-4

104K CORRIDOR CPT-1 RB-1 P-1

104L OFFICE CPT-1 RB-1 P-1, P-4

104M OFFICE CPT-1 RB-1 P-1, P-4

105A IT/HELP DESK CPT-1 RB-1 P-1, P-3 SS-1 PL-1

105B SPECIALIST OFFICE CPT-1 RB-1 P-1, P-4 RS-1

105C STORAGE SC-1 RB-1 P-1

107 COMPUTER STATIONS CPT-1 RB-1 P-1

108 COMMUNITY CAFE LVT-1 RB-1 WD-1, P-3 SS-1 PL-1

109 CONF ROOM CPT-1 RB-1 P-1, P-2, WC-1 SS-1 PL-1

110A STUDENT VETERANSLOUNGE

CPT-1 RB-1 P-1, P-3, WC-1 SS-1 PL-1

110B SVA OFFICE CPT-1 RB-1 P-1, P-4

110C STUDY / COMPUTER CPT-1 RB-1 P-1

121 ENTRY CPT-1 RB-1

122 ENTRY CPT-1 RB-1

123 CORRIDOR CPT-3 RB-1

124 CORRIDOR CPT-3 RB-1

FINISH LEGENDCSI SECTION NUMBER CSI SECTION NAME TYPE CODE MANUFACTURER PRODUCT SIZE COLOR CONTACT REMARKS

DIVISION 6

06 2023 INTERIOR FINISH CARPENTRY DECORATIVE METAL PANELS DP-1 FORMS & SURFACES FUSED METAL - DALLAS 48X120SHEET

GRAPHITEDIAMOND

CHAD [email protected]

.0625" THICK

06 2023 INTERIOR FINISH CARPENTRY RECLAIMED WYOMING LICENSEPLATES

MTL-1 LOCAL ARTIST ORMILLWORKER

PLATE SIZES OF EQUALDIMENSIONS WITH A VARIETYOF STYLES AND COLORS

- - SCREW ATTACHMENT ATPAINTED PLYWOOD BACKERWITH 1/2" SPACING

06 2023 INTERIOR FINISH CARPENTRY WOOD BOARD PANELING WD-1 PIONEER MILLWORKS MIXED HARDWOODS 3/4X4 SETTLERS' PLANT

06 4116 PLASTIC LAMINATE FACEDARCHITECTURAL CABINETS

PLASTIC LAMINATE (VERTICAL) PL-1 WILSONART HIGH LINE - 7970K-18 BRYNN [email protected]

DIVISION 9

09 3013 CERAMIC TILING CERAMIC TILE CT-1 CROSSVILLE CRUX BY STILE 12X24 EARTH JESSICA [email protected]

09 5113 ACOUSTICAL PANEL CEILINGS ACOUSTICAL CEILING ACP-1 ARMSTRONG 895 FISSURED 24X48 KELLY [email protected]

09 5133 ACOUSTICAL METAL PAN CEILINGS METAL CEILING MTL-2 ARMSTRONG 6188 METALWORKS OPENCELL

24X24 PANEL RAL 7032 PEBBLEGREY

3" CELL SIZE. INSTALLS AS ALOCK-IN SYSTEM OFUNFRAMED OPEN CELLPANELS THAT CONNECT TOMOUNTING AND CROSSRAILS FOR ASELF-SUSPENDING SYSTEM -NO OTHER SUSPENSIONSYSTEM REQUIRED.

09 6513 RESILIENT BASE ANDACCESSORIES

RESILIENT BASE RB-1 JOHNSONITE RUBBER BASE 4" COVE,ROLLEDGOODS

63 BURNT UMBER

09 6519 RESILIENT TILE FLOORING LUXURY VINYL TILE LVT-1 ARMSTRONG NATURAL CREATIONS,MYSTIX SPETTRO

6X36 NA 931 CASPIANSAND

KRISTIN [email protected]

BRICK ASHLARINSTALLATION

09 6813 TILE CARPETING CARPET (FIELD) CPT-1 SHAW RENEW TILE - THE PARK5T141

9X36 NEST 38760 CAITLYN [email protected]

HERRINGBONEINSTALLATION

09 6813 CARPET (ACCENT) CPT-2 SHAW RENEW TILE - THE PARK5T141

9X36 DWELL 38535 HERRINGBONEINSTALLATION

09 6813 CARPET (WALK-OFF) CPT-3 TANDUS ASSERTIVE STRIA 04839 24X24 STEELWORK 26202 PAM [email protected]

09 7200 WALL COVERING VINYL WITH CUSTOM PRINTEDGRAPHIC

WC-1 MAHARAM TEXTURED 54" TBD CUSTOM GRAPHICPROVIDED BY ARCHITECT ASA PRINT-READY ELECTRONICFILE.

09 9123 INTERIOR PAINTING PAINT (FIELD) P-1 SHERWIN WILLIAMS EGGSHELL - SW 7005 PUREWHITE

PETER [email protected]

09 9123 PAINT (ACCENT) P-2 SHERWIN WILLIAMS EGGSHELL - SW 6244 NAVAL -

09 9123 PAINT (ACCENT) P-3 SHERWIN WILLIAMS EGGSHELL - SW 6520 GRANITEPEAK

-

09 9123 PAINT (ACCENT) P-4 SHERWIN WILLIAMS EGGSHELL - SW 7533 KHAKISHADE

09 9123 PAINT (CEILING) P-5 SHERWIN WILLIAMS FLAT - SW 7005 PUREWHITE

-

09 9123 PAINT (DOOR FRAME) P-6 SHERWIN WILLIAMS SEMI-GLOSS - SW 6990 CAVIAR -

09 9123 PAINT (STRUCTURE) P-7 SHERWIN WILLIAMS FLAT - SW 6990 CAVIAR

09 9123 CHALKBOARD PAINT P-8 TBD TBD - TBD

09 9123 INTERIOR PAINTING SEALED CONCRETE SC-1 - MATTE

DIVISION 10

10 1100 VISUAL DISPLAY UNITS PORCELAIN MARKERBOARD VD-1 CLARIDGE TBD TBD

DIVISION 12

12 2413 ROLLER WINDOW SHADES ROLLER SHADES RS-1 MECCOSHADE TBD TBD TBD

12 3661.16 SOLID SURFACING SOLID SURFACE COUNTERTOP SS-1 DU PONT CORIAN 1/2" THICK CLAM SHELL -

SHEET NOTES - FINISH PLANSNOTE # NOTE

1 VENDING MACHINE, OFOI

2 LCD MONITOR

3 (2) UNDERCOUNTER MICROWAVE, OFCI

4 (1) UNDERCOUNTER REF, OFCI

5 SLIDING BARN DOOR

1 1/29/18 Addendum 1

ACCESSORY SCHEDULE-VISUAL DISPLAY UNITSCSI DIV

# CSI DIV NAME Type Mark DESCRIPTION DIMENSIONS REMARKS10 1100 VISUAL DISPLAY UNITS VD-1 CLARIDGE PORCELAIN MARKERBOARD 4'-0" X 6'-0"

1

ADD-1

1

ADD-1

1

ADD-1

CPT-1CPT-1

CPT-3CPT-3

Page 24: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

T75

UP

UP

UP

100 SF

STORAGE

105C

70 SF

ELEC.

106

121 SF

SPECIALISTOFFICE

105B

123 SF

OFFICE104J

128 SF

OFFICE

104H

116 SF

OFFICE

104G

118 SF

OFFICE

104F

216 SF

OFFICE

104E

60 SF

STORAGE

104D183 SF

CONFERENCEROOM

104B

165 SF

VESTIBULE

100

545 SF

MECHANICAL

101

375 SF

FOODPANTRY

102

22 SF

FIRESERVICE

102A

204 SF

STUDY /COMPUTER

110C

501 SF

STUDENTVETERANSLOUNGE

110A

20 SF

JAN.

112

3942 SF

COLLABORATION

103

180 SF

WOMEN'STOILET

114

188 SF

MEN'STOILET

113

99 SF

CORR.

111

STUDENT ORGANIZATIONS

304 SF

COMMUNITYCAFE

108

3942 SF

COLLABORATION

103

541 SF

CONFROOM

109

102 SF

SVAOFFICE

110B

SKYLIGHT ABOVE, TYP

113 SF

OFFICE

104M

170 SF

CORRIDOR

104K

155 SF

CORRIDOR

104C

113 SF

OFFICE

104L

103 SF

IT/HELPDESK

105A

685 SF

COMPUTERSTATIONS

107

170 SF

RECEPTION/WAITING

104A

E

E

E

E

E

E

EE

E

E

E

E

1

1

1

3

2

E

E

E

E

E

DO NOT SCALE DRAWINGS. CONTACT ARCHITECT FOR DIMENSIONS.

FURNITURE AS SHOWN BEST REPRESENTS HOW EACH SPACE IS INTENDED TO BE USED. FINAL SELECTIONS (AS PART OF FF&E), SIZES & LOCATIONS MAY DIFFER FROM DRAWINGS. WHEN COORDINATING ELECTRICAL & SIMILAR ITEMS BASED ON FURNITURE LAYOUT, CONFIRM WITH ARCHITECT & OWNER PRIOR TO PROCEEDING.

DO NOT INSTALL FIRE STROBES & ALARMS AT (AREAS) WHERE ARTWORK OR WALL HUNG FF&E ITEMS ARE INDICATED. COORDINATE HEIGHTS WITH ARCHITECT.

ALL FURNITURE SPECIFICATIONS TO BE COORDINATED WITH FURNITURE DEALER AND ARCHITECT.

ALL FURNITURE PROCUREMENT TO BE COORDINATED WITH FURNITURE DEALER AND ARCHITECT.

REFER TO ARCHITECTURAL & ELECTRICAL DRAWINGS FOR ALL DECORATIVE LIGHTING, WALL MOUNTED T.V.’s, CONFERENCT TABLES, ETC. REQUIRING HARDWIRING.

FURNITURE NOTED WITH AN “E” REPRESENTS PRODUCTS THAT ARE EXISTING.

FURNITURE GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

N

KEY PLAN

CONSULTANT:

ISSUE:

OWNER:

PROJECT:

DRAWING INFORMATION:

DRAWN BY:

PROJECT NO:

SHEET TITLE:

APPROVED BY:

CHECKED BY:

SHEET OF

1 2 3 4 5 6

A

B

C

D

E

1 2 3 4 5 6

P 303.607.0977www.hcm2.com

1331 Nineteenth StreetDenver, CO. 80202

hord|coplan|macht

1/2

9/2

01

8 9

:05:2

1 P

M

C:\R

evit L

ocal F

iles\1

17

38.0

01

_LC

CC

SE

_C

CR

_C

entr

al_

twe

llner@

hcm

2.c

om

.rvt

A-150

FIRST FLOORFURNITURE PLAN

LARAMIE COUNTYCOMMUNITYCOLLEGE

CROSSROADSBUILDINGRENOVATION

TW

TM

11738.001

MP

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

1.4.2018 CONTRACT DOCUMENTS

1/8" = 1'-0"A1FIRST FLOOR FURNITURE PLAN

SHEET NOTES - FURNITURE PLANSNOTE # NOTE

1 PRINTER, OFOI

2 ALL FURNITURE IS SHOWN FOR REFERENCE ONLY AND IS NOT PART OFTHIS PROJECT SCOPE.

3 BUILT IN SHELVING TO REMAIN

1 1/29/18 Addendum 1

1

ADD-1

Page 25: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

FIRST FLOOR98' - 0"

1

C1

A-300

DEMO EXISTING ANGLED WOOD SOFFIT, REPLACE WITH GYP. BOARD BULKHEAD AND SOFFIT OVER EXISTING METAL STUDS

DEMO EXISTING WOOD SOFFIT, REPLACE WITH GYP. BOARD BULKHEAD

D1

A-522

A6

A-521

A4

A-522

C2

A-521

ADJ BLDG FLOOR100' - 0"

ROOF117' - 0"

T.O. PRECAST WALL114' - 0"

FIRST FLOOR98' - 0"

A B C D

A1

A-300

A-522

D1

DEMO EXISTING ANGLED WOOD SOFFIT, REPLACE WITH GYP. BOARD BULKHEAD AND SOFFIT OVER EXISTING METAL STUDS

A3

A-521

E3

A-522

C2

A-521

FIRST FLOOR98' - 0"

A

204 SF

STUDY /COMPUTER

110C

188 SF

MEN'STOILET

113

EXTERIOR PRECAST EXTERIOR WALL

DEMO EXISTING DOOR FRAME AND DOOR

DEMO EXISTING STEEL BEAM LINTEL

DEMO EXISTING CMU WALLS IN THEIR ENTIRETY

EXISTING PRECAST ROOF DOUBLE TEE

DEMO EXISTING CAST-IN-PLACE CONCRETE CEILING IN ITS ENTIRETY

A-522

E1

8' - 0"

B.O. C.I.P CEILING

E3

A-522 A-522

E1

SIM. OPP. HAND

A-610

A4

1

ADD-1

N

KEY PLAN

CONSULTANT:

ISSUE:

OWNER:

PROJECT:

DRAWING INFORMATION:

DRAWN BY:

PROJECT NO:

SHEET TITLE:

APPROVED BY:

CHECKED BY:

SHEET OF

1 2 3 4 5 6

A

B

C

D

E

1 2 3 4 5 6

P 303.607.0977www.hcm2.com

1331 Nineteenth StreetDenver, CO. 80202

hord|coplan|macht

1/2

9/2

01

8 9

:05:2

2 P

M

C:\R

evit L

ocal F

iles\1

17

38.0

01

_LC

CC

SE

_C

CR

_C

entr

al_

twe

llner@

hcm

2.c

om

.rvt

A-300

BUILDING SECTIONS

LARAMIE COUNTYCOMMUNITYCOLLEGE

CROSSROADSBUILDINGRENOVATION

TW

CM

11738.001

MP

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

1.4.2018 CONTRACT DOCUMENTS

1/4" = 1'-0"A1BUILDING SECTION - NORTH TO SOUTH

1/4" = 1'-0"C1BUILDING SECTION - EAST TO WEST

3/8" = 1'-0"D1WALL SECTION AT EXISTING VAULT

1 1/29/18 Addendum 1

Page 26: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

109

A1

A-522

064116.A01PLASTIC-LAMINATE-FACEDARCHITECTURALCABINET

123661.16.A00SOLID SURFACINGCOUNTERTOPS

FILL1/2" 3' - 9" 3' - 9"

BULKHEAD ABOVE

A4

A-520

096513.A01RESILIENT BASE

062023.A28INTERIOR WOOD BOARDPANELING

2' -

10

"

EQ EQ

5' -

0"

P-2

D2

A-520

096513.A01RESILIENT BASE

062023.A28INTERIOR WOOD BOARDPANELING

WALL MOUNTED LCD MONITOR, RE: AV/IT

WD-1

D3

A-522

BULKHEAD ABOVE

WALL BEYOND

3' - 0"3' - 0"

OPEN

2' - 3"

2' -

10

"D2

A-520

123661.16.A00SOLID SURFACINGCOUNTERTOPS

064116.A01PLASTIC-LAMINATE-FACEDARCHITECTURALCABINET

096513.A01RESILIENT BASE

110B

D3

A-522

P-3

WD-1

096513.A01RESILIENT BASE

062023.A28INTERIOR WOOD BOARDPANELING

FILL1/2"

3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0"

2' -

10

"

WD-1

A2

A-520

A5

A-520

BRADLEY LENOX 5-TIER LOCKERS, CFCI, RE: SPECS

062023.A28INTERIOR WOOD BOARDPANELING

096513.A01RESILIENT BASE

4"

OPEN OPEN A-420

C5

E1

A-521

A1

A-520

PROVIDE LOCKS ON SINK BASE CABINET

1

ADD-1

OPEN TO BEYOND

PRINTERS, OFOI

VENDING MACHINE

096513.A01RESILIENT BASE

104K

105A

ALIGN

062023.A00INTERIOR FINISHCARPENTRY

DP-1

E4

A-521

SLIDING DOORS

5' - 0" 3' - 1"

A1

A-521

A4

A-521

D1

A-521

105D 105D

2' -

6"

123661.16.A00SOLID SURFACINGCOUNTERTOPS

SOLID SURFACE ALL SIDESA-610

A1

DECORATIVE SCONCE LIGHTING, L3 TYPE, RE: RCP & ELEC

EQ EQ

096513.A01RESILIENT BASE

D2

A-520

5' -

0"

WALL MOUNTED LCD MONITOR, RE: AV/IT

EQ EQ

5' -

0"

WALL MOUNTED LCD MONITOR RECESSED INTO WALL, RE: AV/IT

D2

A-520

OPEN TO BEYOND

A6

A-521

MTL-1

8' -

0"

4' - 0"

103 103

A-420

E5

2"

TV

HT

.2

"

2" TV WIDTH 2"

CT-1, RE: FINISH SCHEDULE

A3

A-521

FINISHED CEILING, RE: RCP

C2

A-521

START FIRST FULL PLANK HERE

SEE FLOOR PLAN

093013.A01CERAMIC TILING, LARGEFORMAT

062023.A28INTERIOR WOOD BOARDPANELING

096513.A01RESILIENT BASE

3' -

0"

1' -

4"

FINISHED CEILING, RE: RCP

C2

A-521

START FIRST FULL PLANK HERE

096513.A01RESILIENT BASE

WOOD WALL BEYOND

105A

096513.A01RESILIENT BASE

OPEN TO BEYOND

(2) BF MOBILE PEDESTALS ON CASTERS, SAME LOCK&KEY ON BOTH

2' -

6"

9' - 0"

D1

A-521

SLIDING DOOR BEYOND

3/4" END SUPPORT W/ PLAM BOTH SIDES

1

A-420

D5

3' - 1

0 3

/4"

13' - 4

1/2

"

A-420

F2

A-420

E3

A-420

F3

A-420

E2

WD-1

P-3

3' - 6"8' - 9 1/2"

A-520

D1

OPEN BEYOND

2' -

8"

123661.16.A00SOLID SURFACINGCOUNTERTOPS

2' - 6"5' - 6"2' - 6"

145.0° 155.0°

50.0

°

096513.A01RESILIENT BASE

064116.A01PLASTIC-LAMINATE-FACEDARCHITECTURALCABINET

MITER CORNERS, TYP

B1

A-520

D1

A-520

OPEN BEYOND

2' -

8"

123661.16.A00SOLID SURFACINGCOUNTERTOPS

WATERFALL SOLID SURFACE DOWN TO FINISHEDFLOOR

D1

A-520

OPEN BEYOND

2' -

8"

123661.16.A00SOLID SURFACINGCOUNTERTOPS5' - 6"2' - 6"3' - 0"

53.0

° 25.0

°

145.0°

096513.A01RESILIENT BASE

064116.A01PLASTIC-LAMINATE-FACEDARCHITECTURALCABINET

MITER CORNERS, TYP

B1

A-520

D1

A-520

2' -

8"

123661.16.A00SOLID SURFACINGCOUNTERTOPS

WATERFALL SOLID SURFACE DOWN TO FINISHEDFLOOR

OPEN BEYOND

D1

A-520

4"

2"

8"

2"

10"

2"

4"

2"

1' -

0"

2"

4"

2"

8"

2"

1' -

0"

2"

8"

2"

8"

2"

1' -

0"

P-3BEYOND, TYP

062023.A28INTERIOR WOOD BOARDPANELING

096513.A01RESILIENT BASE

MIT

ER

ED

GE

S, T

YP

E1

A-521

20' - 11 1/2"

ALIGN FIRST FULL PLANK WITH T.O.

BLACKSPLASH

OPEN FOR CASEWORK

15' - 0 1/2"

3' -

2"

EQ EQ

5' -

0"

096513.A01RESILIENT BASE

WALL MOUNTED LCD MONITOR, RE: AV/IT

P-2

TERIMNATE PAINT AT INSIDE CORNER

D1

A-521

TY

P4

"

ALIGN STRIKE PLATE WITH OUTSIDE EDGE OF DOOR

105A

SLIDING DOOR BEYOND

3/4" END SUPPORT W/ PLAM BOTH SIDES

A3

A-521

C2

A-521

096513.A01RESILIENT BASE

062023.A28INTERIOR WOOD BOARDPANELING

093013.A01CERAMIC TILING, LARGEFORMAT

START FIRST FULL PLANK HERE

WALL MOUNTED LCD MONITOR, RE: AV/IT

3' -

6"

EQEQ

C2

A-521

096513.A01RESILIENT BASE

062023.A28INTERIOR WOOD BOARDPANELING

START FIRST FULL PLANK HERE

EQ

12 EQ PLATES

12' - 11" EQ

EQ

13

EQ

PLA

TE

S

7' -

6"

EQ

TY

P

1"

096513.A01RESILIENT BASE

062023.A00INTERIOR FINISHCARPENTRY

INSTALLATION: BRICK ASHLAR

CONSULTANT:

ISSUE:

OWNER:

PROJECT:

DRAWING INFORMATION:

DRAWN BY:

PROJECT NO:

SHEET TITLE:

APPROVED BY:

CHECKED BY:

SHEET OF

1 2 3 4 5 6

A

B

C

D

E

1 2 3 4 5 6

P 303.607.0977www.hcm2.com

1331 Nineteenth StreetDenver, CO. 80202

hord|coplan|macht

1/2

9/2

01

8 9

:05:3

3 P

M

C:\R

evit L

ocal F

iles\1

17

38.0

01

_LC

CC

SE

_C

CR

_C

entr

al_

twe

llner@

hcm

2.c

om

.rvt

A-420

INTERIORELEVATIONS

LARAMIE COUNTYCOMMUNITYCOLLEGE

CROSSROADSBUILDINGRENOVATION

TW

TM

11738.001

MP

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

1.4.2018 CONTRACT DOCUMENTS

1/4" = 1'-0"A3 CONFERENCE RM - EAST

1/4" = 1'-0"A1 CONFERENCE 109 - NORTH

1/4" = 1'-0"C3

STUDENT VETERANS LOUNGE 110A -SOUTH

1/4" = 1'-0"A4 CONFERENCE 109 - SOUTH

1/4" = 1'-0"D5 COMMUNITY CAFE - EAST

1/4" = 1'-0"C1 COMPUTER STATIONS 107 - EAST

1/4" = 1'-0"B1 COLLABORATION 103 - WEST

1/4" = 1'-0"B2 COLLABORATION 103 - EAST

1/4" = 1'-0"D1 FIREPLACE - 1

1/4" = 1'-0"D2 FIREPLACE - 2

1/4" = 1'-0"B4 IT/HELP DESK 105A - WEST

1/4" = 1'-0"E1

ENLARGED PLAN - COMMUNITY CAFEISLAND

1/4" = 1'-0"E3 ISLAND - 2

1/4" = 1'-0"F2 ISLAND - 3

1/4" = 1'-0"F3 ISLAND - 4

1/4" = 1'-0"E2 ISLAND - 1

1/2" = 1'-0"C5

ENLARGED ELEVATION - WOOD WALL @CAFE

1/4" = 1'-0"B6 CONFERENCE 104B - SOUTH

1 1/29/18 Addendum 1

1/4" = 1'-0"B5 IT/HELP DESK 105A CLOSED

1/4" = 1'-0"D3 FIREPLACE - 3

1/4" = 1'-0"D4 FIREPLACE - 4

1/2" = 1'-0"E5

ENLARGED ELEVATION - LICENSEPLATE WALL

Page 27: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

2' -

6 3

/4"

DESIGN INTENT: FLOATING WOOD PLANE FRAMES ENTRY INTO CONFERENCE ROOM

092900.B055/8" INTERIOR GYPSUM

BOARD - TYPE X

061053.A24FIRE-RETARDANT-TREATED

PLYWOOD

WOOD FASCIA

CASCADING WOOD WALL BEYOND

095113.A00ACOUSTICAL PANELCEILING

092900.B165/8" INTERIOR GYPSUMBOARD, MOISTURE-ANDMOLD-RESISTANT - TYPEX

ALIGN EDGE OF WOOD CEILING WITH WALL BEYOND

DEMONTABLE PARTITION

1' - 6"

2 1/4"

6 1

/2"

6 1

/2"

10' - 2 3/4"

MITER ALL CORNERS. EASE EDGES.

062023.A28INTERIOR WOOD BOARDPANELING

A-520

D6

SIM

RE

: R

CP

4"

MIN

5/8" GYP BD

SCHEDULED WALL, RE: WALL TYPES

3/4" Z-REVEAL

054000.A00COLD-FORMED METALFRAMING

062023.A00INTERIOR FINISHCARPENTRY

SUSPENDED GYP BD, RE: RCP

RE

: R

CP

062023.A00INTERIOR FINISHCARPENTRY

RE

: R

CP

054000.A00COLD-FORMED METALFRAMING

095113.A00ACOUSTICAL PANELCEILING

062023.A00INTERIOR FINISHCARPENTRY

MIN4"

062023.A00INTERIOR FINISHCARPENTRY

092900.B055/8" INTERIOR GYPSUMBOARD - TYPE X

095113.A00ACOUSTICAL PANELCEILING

095423.B01END CAP

EXISTING SKYLIGHT BEYOND

1 1/2" 3 1/4"

6"

4 3

/4"

MIN4"

1' -

0"

095131.01.A00ACOUSTICAL METALCEILINGS

COVE LIGHT, RE: ELEC

ALIG

N

MIN4"

EXISTING 3 5/8" METAL STUD AND GYP. BOARD WALL TO REMAIN

EXTEND NEW 3 5/8 STUD AND SECURELY FASTEN TO EXISTING STUD

092900.B055/8" INTERIOR GYPSUMBOARD - TYPE X

9 1/2"

EXISTING 3 5/8" METAL STUD TO REMAIN, CUT LENGTH TO REVISED CEILING HEIGHT

DEMOUNTABLE WALL AS SCHEDULED

SUSPENDED ACOUSTICAL CEILING SYSTEM, RE: RCP FOR TYPE

SCHEUDLED WALL, RE: WALL TYPES

MIN6"

AL

IGN

4"

MIN

RE

: R

CP

4"

SUSPENDED ACOUSTICAL CEILING SYSTEM, RE: RCP FOR TYPE

SCHEUDLED WALL, RE: WALL TYPES

SUSPENDED GYP. BD. CEILING SYSTEM, RE: RCP FOR TYPE

COVE LIGHT, RE: ELEC

2" AXIOM TRIM

RE

: R

CP GYP BD

DEMO EXISTING CAST-IN-PLACE CONCRETE CEILING

NEW CEILING AS SCHEDULED

DEMO EXISTING CMU WALLS

EXISTING PRECAST EXTERIOR WALL TO REMAIN

1-3F

6"

3 5/8" METAL STUD FRAMING TO UNDERSIDE ROOF DECK

DEMO EXISTING CAST-IN-PLACE CONCRETE CEILING

DEMO EXISTING CMU WALLS

DEMO EXISTING WALL FURRING

DEMO EXISTING CEILING GRID AND PANELS

CONSULTANT:

ISSUE:

OWNER:

PROJECT:

DRAWING INFORMATION:

DRAWN BY:

PROJECT NO:

SHEET TITLE:

APPROVED BY:

CHECKED BY:

SHEET OF

1 2 3 4 5 6

A

B

C

D

E

1 2 3 4 5 6

P 303.607.0977www.hcm2.com

1331 Nineteenth StreetDenver, CO. 80202

hord|coplan|macht

1/2

9/2

01

8 9

:05:3

6 P

M

C:\R

evit L

ocal F

iles\1

17

38.0

01

_LC

CC

SE

_C

CR

_C

entr

al_

twe

llner@

hcm

2.c

om

.rvt

A-522

CEILING DETAILS

LARAMIE COUNTYCOMMUNITYCOLLEGE

CROSSROADSBUILDINGRENOVATION

TW

CM

11738.001

MP

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

1.4.2018 CONTRACT DOCUMENTS

1 1/2" = 1'-0"A1

CEILING DETAIL - CONFERENCE RMWOOD ENTRY

1 1/2" = 1'-0"C1 CEILING DETAIL - TYP GYP TO ACT

1 1/2" = 1'-0"C3 CEILING DETAIL - WD TO GYP REVEAL

1 1/2" = 1'-0"C2 CEILING DETAIL - TYP WD TO ACT

1 1/2" = 1'-0"D1

CEILING DETAIL - MTL TO ACTTRANSITION @ SKYLIGHT

1 1/2" = 1'-0"D5 CEILING DETAIL - ACP @ TRANSOM

1 1/2" = 1'-0"D3

CEILING DETAIL - COVE LIGHT @CONFERENCE ROOM

1 1/2" = 1'-0"A4 CEILING DETAIL - TYP BULKHEAD

1 1/29/18 Addendum 1

1 1/2" = 1'-0"E1 DEMO CEILING DETAIL

1 1/2" = 1'-0"E3 DEMO CEILING DETAIL

1

ADD-1

Page 28: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

DOOR TYPES

7" 8"

8"

2' -

0"

SE

E S

CH

ED

ULE

SE

E S

CH

ED

ULE

A

PER SCHED.

PER SCHED.

B C D

SE

E S

CH

ED

ULE

SE

E S

CH

ED

ULE

PER SCHED.

PER SCHED.

4 1/2"4 1/2"

4 1

/2"

4 1

/2"

4 1

/2"

4 1/2" 4 1/2"

9"

STILE AND RAIL DOOR - MATCH FLUSH DOOR IN SPECIES, GRADE AND FINISH

STILE AND RAIL DOOR - MATCH FLUSH DOOR IN SPECIES, GRADE AND FINISH

MARKERBOARD MATERIAL SHOWN IN GRAY

SE

E S

CH

ED

ULE

PER SCHED.

E

GLASS

A

3' -

0" 2

"

PE

R S

CH

ED

.2

"

2" PER SCHED. 2"

FINISH FLOOR

EQ. PER SCHEDULE EQ.

8' -

0"

12' - 4"

TT

9 3/4" PER SCHEDULE EQ. EQ.

9' -

0"

TT

13' - 4 1/2"

FINISH FLOOR

3' -

4"

PE

R S

CH

ED

.

PER SCHED.

2" TYP.

A4

A-610

11' - 7 1/2"

EQ.PER SCHED.EQ.

9' -

0"

1' -

0"

8' -

0"

T T

BOTTOM DOOR SLIDING TRACK

DOOR AS SCHEDULED

WALL AS SCHEDULED

SOLID SURFACE COUTNER AND FRONT

SLIDING DOOR BOTTOM TRACK

DOOR AS SCHEDULED

WALL BEYOND

A2

A-610

081113.A02HOLLOW METAL FRAME

EXISTING STUD WALL, CUT NEW OPENING INTO WALL

079200.A01BACKER ROD ANDSEALANT

GLAZING OR DOOR AS OCCURS

081113.A02HOLLOW METAL FRAME

079200.A01BACKER ROD ANDSEALANT092900.B055/8" INTERIOR GYPSUMBOARD - TYPE X

081113.C05FRAME ANCHOR

METAL STUD FRAMING

GLAZING OR DOOR AS OCCURS

081113.A02HOLLOW METAL FRAME

079200.A01BACKER ROD ANDSEALANT

092900.B055/8" INTERIOR GYPSUMBOARD - TYPE X

081113.C05FRAME ANCHOR

METAL STUD FRAMING BOX HEADER

GLAZING OR DOOR AS OCCURS

092900.B055/8" INTERIOR GYPSUMBOARD - TYPE X

084113.A02ALUMINUM STOREFRONT

EXISTING PRECAST CONCRETE DOUBLE TEE

079200.A01BACKER ROD ANDSEALANT

061053.A24FIRE-RETARDANT-TREATEDPLYWOOD

EXISTING RIGID INSULATION

1 1/2"

079200.A01BACKER ROD ANDSEALANT

092216.B053 5/8" METAL STUD @ 16"O.C.

076200.B01MANUFACTURED SHEETMETAL FLASHING

072500.B01SELF-ADHERINGFLEXIBLE FLASHING

079200.A01BACKER ROD ANDSEALANT

079200.A01BACKER ROD ANDSEALANT

092900.B055/8" INTERIOR GYPSUMBOARD - TYPE X

084113.A02ALUMINUM STOREFRONT

061053.A24FIRE-RETARDANT-TREATEDPLYWOOD

061053.A24FIRE-RETARDANT-TREATEDPLYWOOD

092900.B055/8" INTERIOR GYPSUMBOARD - TYPE X

PREFINISHED METAL HEAD FLASHING SET IN

MASTIC

PREFINISHED METAL SILL FLASHING W/

CONT. CLEAT

EXISTING PRECAST CONCRETE DOUBLE TEE

EXISTING PRECAST CONCRETE DOUBLE TEE

EXISTING RIGID INSULATION

079200.A01BACKER ROD AND

SEALANT

FLEXIBLE FLASHING MEMBRANE

092216.B053 5/8" METAL STUD @ 16"O.C.

076200.B01MANUFACTURED SHEETMETAL FLASHING

072500.B01SELF-ADHERINGFLEXIBLE FLASHING

ADDITIONAL STUD TO SUPPORT PLYWOOD

PARTITION AS SCHEDULED

SHIM AND SEALANT

EXISTING METAL STUD

WALL

2"

SCHED.

SEE 2" 2"

SCHED.

SEE 2" 1' - 6" 2"

2"

SE

E S

CH

ED

ULE

2"

SE

E S

CH

ED

ULE

1 2

HM FRAME TYPES

T

CONSULTANT:

ISSUE:

OWNER:

PROJECT:

DRAWING INFORMATION:

DRAWN BY:

PROJECT NO:

SHEET TITLE:

APPROVED BY:

CHECKED BY:

SHEET OF

1 2 3 4 5 6

A

B

C

D

E

1 2 3 4 5 6

P 303.607.0977www.hcm2.com

1331 Nineteenth StreetDenver, CO. 80202

hord|coplan|macht

1/2

9/2

01

8 9

:05:3

7 P

M

C:\R

evit L

ocal F

iles\1

17

38.0

01

_LC

CC

SE

_C

CR

_C

entr

al_

twe

llner@

hcm

2.c

om

.rvt

A-610

DOOR, WINDOW &STOREFRONTSCHEDULE & TYPES

LARAMIE COUNTYCOMMUNITYCOLLEGE

CROSSROADSBUILDINGRENOVATION

Checker

Author

11738.001

Approver

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

1.4.2018 CONTRACT DOCUMENTS

DOOR SCHEDULE

DOOR # ROOM

DOOR HARDWARESET

FRAME DETAILS

WIDTH HEIGHT TYPE MATERIAL TYPE MATERIAL HEAD JAMB SILL103 SLIDING BARN DOOR 4' - 0" 8' - 0" C WD 100B A6/A-521 A6/A-521

104A RECEPTION/WAITING 3' - 0" 7' - 0" B WD 101 B HM B1/A-610 B1/A-610

104B CONFERENCE ROOM 3' - 0" 7' - 0" B WD 103 A HM B2/A-610 B2/A-610

104D STORAGE 2' - 8" 7' - 0" A WD 503 A HM B2/A-610 B2/A-610

104E OFFICE 2' - 8" 7' - 0" B WD 103 A HM B2/A-610 B2/A-610

104F OFFICE 3' - 0" 7' - 0" B WD 103 A HM B2/A-610 B2/A-610

104G OFFICE 3' - 0" 7' - 0" B WD 103 A HM B2/A-610 B2/A-610

104H OFFICE 3' - 0" 7' - 0" B WD 103 A HM B2/A-610 B2/A-610

104J OFFICE 3' - 0" 7' - 0" B WD 103 A HM B2/A-610 B2/A-610

104K CORRIDOR 3' - 0" 7' - 0" A WD 101 A HM B2/A-610 B2/A-610

104L OFFICE 3' - 0" 7' - 0" B WD 103 A HM B2/A-610 B2/A-610

104M OFFICE 3' - 0" 7' - 0" B WD 103 A HM B2/A-610 B2/A-610

105A IT/HELP DESK 3' - 0" 7' - 0" A WD 101 A HM B2/A-610 B2/A-610

105B SPECIALIST OFFICE 3' - 0" 7' - 0" B WD 103 A HM B2/A-610 B2/A-610

105C STORAGE 3' - 0" 7' - 0" A WD 503 A HM B2/A-610 B2/A-610

105D SLIDING BARN DOOR - IT/HELPDESK

2' - 10" 4' - 8" D WD 100B A1/A-521 D1/A-521 A1/A-521

109 CONF ROOM 6' - 0" 7' - 9 1/4" E GLASS 100 F.3 Aluminum - -

110A STUDENT VETERANS LOUNGE 6' - 0" 7' - 11" E GLASS 100A F.2 Aluminum - -

110B SVA OFFICE 3' - 0" 7' - 0" B WD 103 B HM B2/A-610 B2/A-610

110C STUDY/COMPUTER 3' - 0" 7' - 11" E GLASS 503A F.1 Aluminum - -

STOREFRONT SCHEDULE

TYPEMARK

R.O. FRAME DETAILS GLAZING

COMMENTSLENGTHHEIG

HT MATERIAL FINISH HEAD JAMB SILL THICKNESS TYPEF.1 11' - 10" 9'-0" Aluminum CLEAR D5/A-522 C2/A-610 - 3/8" TEMP DEMOUNTABLE PARTITION

F.2 13' - 7 1/4" 9'-2" Aluminum CLEAR D5/A-522 SIM - - 3/8" TEMP DEMOUNTABLE PARTITION

F.3 12' - 5" 8'-0" Aluminum CLEAR D6/A-520 D6/A-520 D6/A-520 3/8" TEMP DEMOUNTABLE PARTITION

F.4 3' - 0" 4'-8" Aluminum CLEAR A4/A-610 A3/A-610 A4/A-610 1" INSULATED ALTERNATE NO. 4

WINDOW SCHEDULETypeMark

R.O.

Finish

Glazing HEADDETAIL

JAMBDETAIL

SILLDETAIL CommentsWidth Height Thickness Type

A 4' - 0" 4' - 2" HM-PAINT 1/4" CLEAR B1/A-610 B1/A-610 B1/A-610

1/4" = 1'-0"

CONFERENCE ROOM STOREFRONT - F.3 1/4" = 1'-0"

SVA LOUNGE STOREFRONT - F.2 1/4" = 1'-0"

EXTERIOR FRAME - F.4 1/4" = 1'-0"

SVA STUDY STOREFRONT - F.1

1 1/29/18 Addendum 1

3" = 1'-0"A2 SLIDING DOOR DETAIL

1 1/2" = 1'-0"A1 SLIDING DOOR DETAIL

3" = 1'-0"B1 HM WINDOW DETAIL IN EXISTING WALL

3" = 1'-0"B2 TYP. HM JAMB DETAIL

3" = 1'-0"B3 TYP. HM HEAD DETAIL

1 1/2" = 1'-0"A3 STOREFRONT JAMB DETAIL

1 1/2" = 1'-0"A4 STOREFRONT HEAD & SILL DETAIL

1 1/2" = 1'-0"C2 JAMB DETAIL

1

ADD-1

Page 29: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

PLUMBING FIXTURE SCHEDULE

SYMBOL FIXTURE TRIMELECTRICAL ACCESSORY

REQUIREMENTS LEED CONNECTIONS REMARKS

FIXTURE NAME FIXTURE DESCRIPTION MANUFACTURER MODEL TYPE SIZE MANUFACTURER MODEL SUPPLY I.R. / BATTERY / HP GPF WASTE VENT CW HW

S-1 1 COMPT. SINKSINGLE BOWL UNDERMOUNT 18 GAUGE STAINLESS STEEL SINK

ADA COMPLIANT MANUAL OPERATED GOOSENECK FAUCET WITHVANDEL-RESISTANT 2.2 GPM LAMINAR FLOW OUTLET AND 4" WIDESPREAD WRISTBLADES

ELKAY ELUH211510 UNDERMOUNT STAINLESS STEEL 23.5" X 18.25" X 10" ZURN Z831B4-XL-ICT-4F RE: SPEC MANUAL 2.2 GPM 2" 1 1/2" 1/2" 1/2"PROVIDE WATTS LF1170 WATER TEMPERING VALVE WITH FAUCET. REFER TO ARCHITECTURAL DRAWINGS FORLOCATION AND MOUNTING HEIGHT.

REMARKS:

1. REFER TO GENERAL SPECIFICATIONS FOR SINKS AND MISCELLANEOUS FIXTURE REQUIREMENTS.

2. THIS SCHEDULE INCLUDES ITEMS THAT MAY NOT BE INCLUDED IN THE DRAWING DOCUMENTS.

1/29/2018 14:50

PLUMBING SPECIALTY SCHEDULE

PLAN CODE FIXTURE TYPE LOCATION MANUFACTURER MODEL REMARKS

WCO-1 WALL CLEANOUT INTERIOR FINISHED AREAS J.R.SMITH 4452C

AAV-1 AIR ADMITTANCE VALVE CAFÉ SINK STUDOR MINI-VENT INSTALL AIR ADMITTANCE VALVE A MINIMUM OF 18" ABOVE FINISHED FLOOR.

1/29/2018 14:50

ELECTRIC WATER HEATERELECTRIC HEAT STORAGE SIZE (INCHES)

DESIG. MFR. MODEL SERVICE LOCATION EFFICIENCY NUMBER KW PER KW CAPACITY OPER REMARKS

RATING OF ELEMENT TOTAL (GAL) DIA H WT

ELEMENTS (LBS)

EWH-1 RHEEM PROE6-1-RH-POU CAFÉ SINKCABINET UNDER

SINK 90% 1 2 2 6 16 16 36 1

REMARKS:

1. REFER TO ELECTRICAL DRAWINGS FOR POWER REQUIREMENTS FOR ELECTRIC WATER HEATERS.

1/29/2018 14:50 P:\Wyoming\LCCC\2017-245 Crossroads Building Renovations\Cad\Mech\Mschedules\[M-2017-245.xlsx]S458-1 Water Heater

PLUMBING LEGEND

SYMBOL DESCRIPTION ABBR. DESCRIPTION

ACID RESISTANT WASTE PIPING (ABOVE FLOOR IN BLDG)

DOMESTIC COLD WATER PIPING

DOMESTIC HOT WATER PIPING

DOMESTIC HOT WATER CIRC. PIPING

SOFTENED DOMESTIC COLD WATER PIPING

SOFTENED DOMESSTIC HOT WATER PIPING

DOMESTIC HOT WATER PIPING @ TEMPERATURE SHOWN

SURFACE CLEANOUT

FLOOR CLEANOUT

LINE CLEANOUT

FIXTURE OR DRAIN P-TRAP

AREA DRAIN

FLOOR SINK (SQUARE GRATE)

ROOF DRAIN OR OVERFLOW DRAIN

GAS PRESSURE REDUCING VALVE

ATMOSPHERIC VACUUM BREAKER

ACID RESISTANT VENT PIPING

WASTE PIPING (ABOVE FLOOR IN BUILDING)

WASTE PIPING (BELOW FLOOR IN BUILDING)

WALL CLEANOUT

CLEANOUT TEE

ABBR. SYMBOL

VENT PIPING

FLOOR DRAIN (ROUND GRATE)

HW

HWC

C-SW

140° HW

V

H-SW

AV

W

W

AW

AW

CW

FS

RD / OD

VB

AV

W

W

AW

AW

GD

IW

S

ST

SSD

SD

SD

OD

OD

A

G G

ACID RESISTANT WASTE PIPING (BELOW FLOOR IN BLDG)

IW

S

ST

SSD

SD

GD

SD

OD

OD

A COMPRESSED AIR

GREASE DRAIN (WASTE LINE TO GREASE INTERCEPTOR)

INDIRECT WASTE PIPING

SANITARY SEWER PIPING (OUTSIDE BUILDING)

STORM SEWER PIPING (BELOW GRADE OUTSIDE BUILDING)

SUB-SURFACE DRAIN PIPING

OVERFLOW DRAIN PIPING (ABOVE FLOOR IN BUILDING)

STORM DRAIN PIPING (ABOVE FLOOR IN BUILDING)

STORM DRAIN PIPING (BELOW FLOOR IN BUILDING)

OVERFLOW DRAIN PIPING (BELOW FLOOR IN BUILDING)

FCO

WCO

COT

AD

LCO

FD

SCO

BFP

SA

GC

FC

WH

HB

YH

MH

CI

MANHOLE

DOUBLE CHECK BACKFLOW PREVENTER

SHOCK ARRESTOR W / ISOLATION VALVE

GAS SHUT-OFF VALVE

STOP AND DRAIN VALVE

HOSE BIBB

HWC BALANCING VALVE

CAST IRON

WALL HYDRANT

YARD HYDRANT

INVERT ELEVATION

CATCH BASIN

POLYVINYL CHLORIDE

VITRIFIED CLAY PIPE

VENT THRU ROOF

VCP

CB

VTR

IE

PVC

SW

SW

140°

FIRE PROTECTION LEGEND

SYMBOL DESCRIPTION ABBR. DESCRIPTIONFIRE SERVICE PIPING

FIRE SPRINKLER PIPING

WET STANDPIPE

O.S.&Y. VALVE W/ TAMPER SWITCH

FLOW SWITCH

POST INDICATOR VALVE

NEW SPRINKLER HEAD

EXISTING SPRINKLER HEAD

DRY SPRINKLER HEAD (SHAFT)

FIRE HOSE CABINET

FIRE VALVE CABINET

FIRE DEPARTMENT CONNECTION

RELOCATED SPRINKLER HEAD

SIDEWALL SPRINKLER HEAD

ABBR.

F

SYMBOL

FIRE HYDRANT

AUTOMATIC FIRE SPRINKLER

FS

WSP

PIV

FH

FS

FDC

F

FS

N20

FHC

FVC

A/S

D24

GENERAL LEGEND

SYMBOL DESCRIPTION ABBR. DESCRIPTION

NEW

VIEW NUMBER

SHEET VIEW IS DRAWN ON

EQUIPMENT UNIT IDENTIFICATION

CAP END OF PIPE

PITCH DOWN IN DIRECTION OF ARROW

UNION OR FLANGE

PLUG VALVE

GATE VALVE

VERTICAL PIPE VALVE

DIFFUSER IDENTIFICATIONDIFFUSER NECK DIAMETERDIFFUSER CFM

EXISTING

ABBR. SYMBOL

EQUIPMENT UNIT NUMBER

(E)

(N)

(R)

DIA

NIC

AFF

GC

MC

EC

RELOCATED

POINT OF CONNECTION, NEW TO EXISTING

DIAMETER

ABOVE FINISHED FLOOR

ELECTRICAL CONTRACTOR

NOT IN CONTRACT

GENERAL CONTRACTOR

GLV

BFV

BV

CV

P/T

STRAINER W/ BLOWDOWN

GLOBE VALVE

BUTTERFLY VALVE

BALL VALVE

CHECK VALVE

SOLENOID VALVE

PRESSURE / TEMPERATURE TAP

BUTTERFLY SOLENOID VALVE

FLEXIBLE PIPE CONNECTOR

HOSE END DRAIN VALVE

STRAINER

CEILING ACCESS PANEL

PRESSURE GAUGE

PUMP

THERMOMETER

SIGHT GLASS

C.A.P.

MECHANICAL CONTRACTOR

#UNIT

M-X

X

GV

XX

P/T

DETAIL SHEETS

PLAN SHEETS

XX

NATURAL GAS PIPING

(Not all symbols listed below are used on these drawings)

(Not all symbols listed below are used on these drawings)

(Not all symbols listed below are used on these drawings)

NECKCFM

X

CONSULTANT:

ISSUE:

OWNER:

PROJECT:

DRAWING INFORMATION:

DRAWN BY:

PROJECT NO:

SHEET TITLE:

APPROVED BY:

CHECKED BY:

SHEET OF

1 2 3 4 5 6

A

B

C

D

E

1 2 3 4 5 6

P 303.607.0977www.hcm2.com

1331 Nineteenth StreetDenver, CO. 80202

hord|coplan|macht

1/2

9/2

01

8 5

:26:3

8 P

M

P-001

PLUMBING & FIREPROTECTIONLEGENDS, NOTES &SCHEDULES

LARAMIE COUNTYCOMMUNITYCOLLEGE

CROSSROADSBUILDINGRENOVATION

MEM

ELC

11738.001

MEM

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

P:\W

yom

ing

\LC

CC

\2017

-245

Cro

ssro

ad

s B

uild

ing

Re

novatio

ns\C

ad

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

01.04.2018 CONTRACT DOCUMENTS

FIRE PROTECTION PLAN NOTES:1. FURNISH ALL LABOR, MATERIALS, EQUIPMENT AND SERVICES NECESSARY

FOR THE INSTALLATION OF A COMPLETE AND PROPERLY FUNCTIONING FIRE PROTECTION SYSTEM.

2. THE FIRE PROTECTION WORK INVOLVES ENGINEERING AND DESIGN BY THE CONTRACTOR TO DETERMINE THE EXTENT OF NEW WORK AND THE MODIFICATION AND EXTENSION OF EXISTING SYSTEMS TO PROVIDE FULL COVERAGE TO THE PROJECT AREA SHOWN ON THESE AND THE ARCHITECTURAL PLANS.

3. THE INFORMATION PRESENTED ON THESE DRAWINGS IS DIAGRAMMATIC. IT DOES NOT NECESSARILY REPRESENT ALL ELBOWS, OFFSETS, HANGERS, ETC., REQUIRED FOR A COMPLETE WORKING SYSTEM.

4. ALL FIRE PROTECTION SYSTEMS INSTALLED SHALL BE IN ACCORDANCE WITH NFPA-13, 14, 20, ETC. AND LOCAL BUILDING CODES AND ORDINANCES.

5. FIRE PROTECTION CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL NEW FIRE PROTECTION EQUIPMENT AND PIPING WITH ALL OTHER TRADES PRIOR TO SUBMITTAL OF SHOP DRAWINGS AND SYSTEM INSTALLATION, SO AS NOT TO INTERFERE WITH THE ROUTING OF NEW DUCTWORK, PLUMBING PIPING, ETC.

6. PROVIDE ALL FITTINGS, RISER NIPPLES, ARM-OVERS, HANGERS, ETC. TO MAINTAIN CONFORMANCE WITH APPLICABLE STANDARDS AND TO POSITION THE SPRINKLERS IN THE PROPER LOCATIONS.

7. SEAL ALL PIPE PENETRATIONS THROUGH FIRE RATED WALLS AND CEILINGS WITH FIRE STOPPING MATERIALS AS REQUIRED.

8. FOR REMODEL AREAS NEW SPRINKLERS SHALL MATCH EXISTING SPRINKLERS.

9. PROVIDE WORKING DRAWINGS AND HYDRAULICALLY CALCULATE THIS FIRE SPRINKLER SYSTEM PER NFPA-13 WHERE REQUIRED BY THE LOCAL AUTHORITY HAVING JURISDICTION.

10. PROVIDE FIELD COORDINATION OF PIPING AND SPRINKLER INSTALLATIONS WITH DUCTWORK, LIGHTS, SMOKE DETECTORS, DIFFUSERS, ETC.

1 01.29.18 ADD 1

PLUMBING NOTES:1. CONTRACTOR SHALL NOT SHUT-OFF/PUT OUT OF SERVICE ANY

SYSTEMS/SERVICES WITHOUT FIRST COORDINATING WITH OWNER.

2. CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTING CONDITIONS PRIOR TO COMMENCEMENT OF ANY WORK AND SHALL NOTIFY THE ARCHITECT/ENGINEER OF ANY DISCREPANCIES FOR RESOLUTIONS.

3. THIS CONTRACTOR SHALL COORDINATE LOCATIONS OF PIPING WITH OTHER TRADES AND ADVISE ARCHITECT/ENGINEER OF ANY POSSIBLE CONFLICTS. VERIFY EXACT LOCATIONS, ELEVATIONS AND DIMENSIONS OF STRUCTURAL MEMBERS AND OPENINGS.

4. SEE PLUMBING FIXTURE SCHEDULE FOR PIPE SIZING TO INDIVIDUAL PLUMBING FIXTURES.

5. REFER TO ARCHITECTURAL DRAWINGS FOR FIXTURE ELEVATIONS AND LOCATIONS.

6. INVERT ELEVATIONS SHOWN ARE BASED ON A GROUND FLOOR FINISH ELEVATION OF 100'-0".

7. SEE ARCHITECTURAL CONSTRUCTION DOCUMENTS FOR DIMENSIONED LOCATION OF PLUMBING FIXTURES AND WALLS.

8. PROVIDE CLEANOUTS IN ACCESSIBLE LOCATIONS PER THE PROJECT SPECIFICATIONS AND LOCAL PLUMBING CODES.

1ADD-1

Page 30: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

UP UP

A B C D

1(E) 4" VTR

3/4" HW1 1/2" CW

1/2

" H

W

1 1

/2"

CW

3/4

" C

W

3/4" CW

3" WSLOPE

S-1AAV-1

2"

W

4" W 4" W

(E) CO

(E) CO

EWH-1

STORAGE105C

ELEC.106

SPECIALISTOFFICE

105B

OFFICE104J

OFFICE104H

OFFICE104G

OFFICE104F

OFFICE104E

STORAGE104D

CONFERENCEROOM104B

VESTIBULE100

MECHANICAL101FOOD

PANTRY102

FIRESERVICE

102A

STUDY /COMPUTER

110C

STUDENTVETERANSLOUNGE

110A

JAN.112

COLLABORATION103

WOMEN'STOILET

114

MEN'STOILET

113

CORR.111

CONFROOM

109

OFFICE104L

RECEPTION/WAITING104A

STUDYSPACE104C

CORRIDOR104K

OFFICE104M

SVAOFFICE

110B

COMMUNITYCAFE108

COMPUTERSTATIONS

107

IT/HELPDESK105A

P2

P3

P4

P1

P5

1ADD-1

N

KEY PLAN

CONSULTANT:

ISSUE:

OWNER:

PROJECT:

DRAWING INFORMATION:

DRAWN BY:

PROJECT NO:

SHEET TITLE:

APPROVED BY:

CHECKED BY:

SHEET OF

1 2 3 4 5 6

A

B

C

D

E

1 2 3 4 5 6

P 303.607.0977www.hcm2.com

1331 Nineteenth StreetDenver, CO. 80202

hord|coplan|macht

1/2

9/2

01

8 5

:26:3

9 P

M

P-111

FIRST FLOORPLUMBING PLAN

LARAMIE COUNTYCOMMUNITYCOLLEGE

CROSSROADSBUILDINGRENOVATION

MEM

ELC

11738.001

MEM

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

P:\W

yom

ing

\LC

CC

\2017

-245

Cro

ssro

ad

s B

uild

ing

Re

novatio

ns\C

ad

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

01.04.2018 CONTRACT DOCUMENTS

1 01.29.18 ADD 1

SCALE: 1/8" = 1'-0"

FIRST FLOOR PLUMBING PLAN

KEYNOTESP1 CONNECT TO EXISTING 1 1/2"CW MAIN IN THIS APPROXIMATE

LOCATION.

P2 PROVIDE 1/2"CW TO EWH-1 LOCATED IN CABINET UNDER SINK.INSTALL PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.

P3 PROVIDE 1/2"HW FROM EWH-1 AND 1/2"CW TO SINK, PROVIDE 2"WFROM SINK W/ WCO AND STUDOR AIR ADMITTANCE VALVE. INSTALLSTUDOR VALVE PER MANUFACTURER'S INSTRUCTIONS. UPSIZEWASTE PIPE TO 3" BEFORE DROPPING BELOW FLOOR.

P4 CONTRACTOR TO COORDINATE SAW CUTTING AND PATCHING OFFLOOR AS NEEDED TO INSTALL SANITARY PIPING. SLOPEUNDERGROUND PIPING AT 1/8"/12".

P5 CONNECT TO EXISTING 4" SANITARY IN THIS APPROXIMATELOCATION. CONTRACTOR TO VERIFY LOCATION OF SANITARY MAINAND ENSURE INVERT CAN BE HIT.

Page 31: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

UP UP

J

J

J

J

M

T75

J

J

J

J

A B C D

1

STORAGE

105C

ELEC.

106

SPECIALIST

OFFICE

105B

OFFICE

104J

OFFICE

104H

OFFICE

104G

OFFICE

104F

OFFICE

104E

STORAGE

104D

CONFERENCE

ROOM

104B

VESTIBULE

100

MECHANICAL

101FOOD

PANTRY

102

FIRE

SERVICE

102A

STUDY /

COMPUTER

110C

STUDENT

VETERANS

LOUNGE

110A

JAN.

112

COLLABORATION

103

WOMEN'S

TOILET

114

MEN'S

TOILET

113

CORR.

111

CONF

ROOM

109

WP

WP

WP

+65" +65"LA-43LA-43

USBUSBLA-43 LA-43

E1

E2

LA-49

LA-66

AC

LA-12LA-12LA-40

LA-49

LA-40

PM

PM

AC

USB

LA-34

LA-34

LA-3

LA-13

LA-15

E3

E3

LA-8

E4

LA-56

LA-54

LA-10

LA-3

LA-11

LA-4

LA-4

LA-7USB

LA-2

LA-2

LA-6

LA-5

LA-47LA-5

E1

E2

USB

LA-9

LA-9

+65"

LA-48

USBLA-9

LA-9

LA-2

LA-45 LA-45 LA-45 LA-45 LA-45

TO

HWP

3

LA-50,52

LB

LA

PA

3

1

LA-2

LA-2

LA-5

+65"

USB USB

RECEPTION/WAITING

104A

STUDY

SPACE

104C

OFFICE

104M

OFFICE

104L

CORRIDOR

104K

COMMUNITY

CAFE

108

SVA

OFFICE

110B

LA-16

LA-67

LA-57

LA-55LA-59

E13

E13

E14 E14E3

E8

E7

E6

E6

E9

E9 E9

ACUSB

E9

E9

E9

E9

E9E9

2LA-53

+65"LA-63

EWH

1

LA-69

LA-9

E2

E2

LA-22

LA-33

COMPUTER

STATIONS

107

IT/HELP

DESK

105A

+65"LA-67

LA-10

USB

E9

E4

LA-44

AC

LA-16

LA-58

J

E10

E11E11E11 E11E11E11

E11E11E11E11E11E11

LA-22

LA-33E5

LA-51LA-51

E5

LA-35LA-35E5

LA-35LA-35

LA-60LA-60

LA-60

LA-60

LA-2

ACAC

AC

AC

AC

ACAC

AC

E11

E1

E2

LA-40

LA-40

LA-40

LA-40

LA-40

LA-40

LA-49

LA-49LA-49

LA-49

LA-49

L5-30R

L5-30R

JE10

E11

E11 E11

E1

E2

E11

E11

E11

LA-66

LA-66

LA-63

LA-20LA-65

LA-20

LA-20

LA-20

LA-65LA-65

LA-65

LA-65

LA-20

E2

E2

LA-18

E2

E2

E12

TO

EF

2

LA-64

T

T

E15

E15

LA-72 LA-72

LA-72LA-72

SU1

ADD-1

1ADD-1

N

KEY PLAN

CONSULTANT:

ISSUE:

OWNER:

PROJECT:

DRAWING INFORMATION:

DRAWN BY:

PROJECT NO:

SHEET TITLE:

APPROVED BY:

CHECKED BY:

SHEET OF

1 2 3 4 5 6

A

B

C

D

E

1 2 3 4 5 6

P 303.607.0977www.hcm2.com

1331 Nineteenth StreetDenver, CO. 80202

hord|coplan|macht

1/2

9/2

01

8 4

:22:3

2 P

M

E-121

FIRST FLOOR POWERPLAN

LARAMIE COUNTYCOMMUNITYCOLLEGE

CROSSROADSBUILDINGRENOVATION

CMI

BJK

11738.001

CMI

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

P:\W

yom

ing

\LC

CC

\2017

-245

Cro

ssro

ad

s B

uild

ing

Re

novatio

ns\C

ad

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

01.04.2018 CONTRACT DOCUMENTS

KEYNOTESE1 RE-USE EXISTING RECEPTACLE BOX LOCATION TO TRANSITION TO

NEW SURFACE RACEWAY.

E2 LOW PROFILE SURFACE RACEWAY TO BE MOUNTED OVER FLOORCOVERING. SECURE PER MANUFACTURERS REQUIREMENTS.PROVIDE CONCEALED TRANSITIONS AT WALL. LEGRAND OFRSERIES OR EQUAL.

E3 DEDICATED RECEPTACLE FOR PRINTER. COORDINATE ROUGH INWITH CASEWORK AND EQUIPMENT CONNECTION POINT.

E4 DEDICATED RECEPTACLE FOR FUTURE USE.

E5 TIMBER POLE WITH WIRING CHANNEL. REFER TO ARCHITECTURALPLANS FOR FURTHER DETAILS.

E6 HORIZONTAL PLUGMOLD INSTALLED ALONG CASEWORK. PROVIDEDUPLEX RECEPTACLE AT EACH COMPUTER STATION. RACEWAYSHALL HAVE SEPARATE CHANNEL FOR DATA CABLING.

E7 RECONNECT EXISTING CIRCUITS TO NEW PANELBOARD. REFER TOPANEL SCHEDULE FOR ADDITIONAL INFORMATION.

E8 PROVIDE NEW K-RATED TRANSFORMER. INSTALL ON DOUBLEDEFLECTION NEOPRENE ISOLATORS.

E9 PROVIDE DEVICE WITH INTEGRAL USB CHARGER. LEGRAND #TM8OR EQUAL.

E10 PROVIDE FLOOR BOX FOR A/V CONNECTIONS. REFER TOTECHNOLOGY PLANS FOR DETAILS.

E11 DOUBLE SIDED FLOOR BOX TO HAVE PLATES FOR DUPLEXRECEPTACLE ON FRONT AND SINGLE DATA JACK ON BACK.

E12 PRICE EQUIPMENT AND CONNECTIONS WITH ADD ALTERNATE #1.

E13 DEDICATED RECEPTACLE FOR MICROWAVE. COORDINATE ROUGHIN WITH CASEWORK AND EQUIPMENT CONNECTION POINT.

E14 DEDICATED RECEPTACLE FOR VENDING MACHINE. COORDINATEROUGH IN WITH CASEWORK AND EQUIPMENT CONNECTION POINT.

E15 LINE VOLTAGE THERMOSTAT PROVIDED WITH EF-2. CONNECT INPARALLEL WITH OTHER STAT NOTED TO ENERGIZE FAN WHENROOM TEMPERATURE EXCEEDS SET POINT. REFER TO MECHANICALPLANS FOR FURTHER DETAILS.

SCALE: 1/8" = 1'-0"

FIRST FLOOR POWER PLAN

1 01.29.18 ADD 1

Page 32: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

T R A N S F O R M E R S C H E D U L E

KEY PRI FLA SEC FLA PRIMARY SECONDARY GEC DIMENSIONS WEIGHT BTUH NOTE

480 V 208 V CB CONDUCTORS "C CB CONDUCTORS "C CNDTRS "C HIGH WIDE DEEP OTPT

TK4-75 90.2 208.2 100 A 3 P 3 # 3 , 1 # 8 G 1-1/4 225 A 3 P 4 # 4/0 , 1 # 4 G 2 1 # 2 3/4 39.38 26.13 24.00 865 9696

NOTES: 1.) OVERCURRENT PROTECTION IS SIZED PER NEC 450.3.

2.) ALL CONDUCTORS ARE COPPER. SEE PLANS FOR INCREASED CONDUCTOR SIZES DUE TO VOLTAGE DROP, ETC.

3.) SECONDARY BONDING AND GROUNDING CONDUCTORS ARE SIZED PER NEC 250.66 AND 250.102.

4.) DIMENSIONS, WEIGHTS & BTUH OUTPUT SHOWN ARE FOR REFERENCE ONLY. ACTUAL DIMENSIONS MAY VARY FROM MANUFACTURER TO MANUFACTURER.

5.) FOR K-RATED TRANSFORMERS, PROVIDE PARALLEL NEUTRAL CONDUCTORS LUGS AT TRANSFORMERS, LOW VOLTAGE PANELBOARD, DISCONNECTS AND/OR LOAD.

6.) CONDUIT 40% FILL RATIO IS BASED ON EMT.

CONSULTANT:

ISSUE:

OWNER:

PROJECT:

DRAWING INFORMATION:

DRAWN BY:

PROJECT NO:

SHEET TITLE:

APPROVED BY:

CHECKED BY:

SHEET OF

1 2 3 4 5 6

A

B

C

D

E

1 2 3 4 5 6

P 303.607.0977www.hcm2.com

1331 Nineteenth StreetDenver, CO. 80202

hord|coplan|macht

1/2

9/2

01

8 4

:20:3

4 P

M

E-301

ELECTRICALSCHEDULES

LARAMIE COUNTYCOMMUNITYCOLLEGE

CROSSROADSBUILDINGRENOVATION

CMI

BJK

11738.001

CMI

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

P:\W

yom

ing

\LC

CC

\2017

-245

Cro

ssro

ad

s B

uild

ing

Re

novatio

ns\C

ad

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

01.04.2018 CONTRACT DOCUMENTS

Type Description LampApparent

LoadBallastVoltage

Manufacturer Catalog Series Finish Mounting Recess Note

C1

LINEAR COVE LIGHT; 4' ALUMINUM HOUSING;2,200 LUMEN PACKAGE AT 110 LPW EFFICACY;50,000 HR LIFE AT L70 DEPRECIATION;ELECTRONIC DRIVER; 0-10V DIMMING (TO 10%OUTPUT); UNIVERSAL INPUT; DAMP LOCATIONLISTED; 5-YR WARRANTEE.

LED, 4000K, 85CRI 20 VA 277 V SELFCREST SERIESFP14 SERIES

SILVERSURFACEMOUNT IN

COVE-

D1

RECESSED DOWNLIGHT; 6" APERATURE STEELHOUSING; SELF-FLANGED TRIM RING; 1,000LUMEN PACKAGE AT 97 LPW EFFICACY; 50,000HR LIFE AT L70 DEPRECIATION; LOWIRREDESCENT, SPECULAR REFLECTOR W/MEDIUM BEAM DISTRIBUTION; ELECTRONICDRIVER; 0-10V DIMMING (TO 10% OUTPUT);UNIVERSAL INPUT; 26" C-CHANNEL BARHANGERS; 5-YR WARRANTEE.

LED, 4000K, 80CRI 11 VA 277 VPORTFOLIO

CREEPRESCOLITE

LD6B SERIESS-DL6 SERIESLF6SL SERIES

WHITE TRIMRING

RECESSEDIN GYP/ACT

CEILING0'-6"

D2

RECESSED DOWNLIGHT; 4" APERATURE STEELHOUSING; SELF-FLANGED TRIM RING; 1,000LUMEN PACKAGE AT 97 LPW EFFICACY; 50,000HR LIFE AT L70 DEPRECIATION; LOWIRREDESCENT, SPECULAR REFLECTOR W/MEDIUM BEAM DISTRIBUTION; ELECTRONICDRIVER; 0-10V DIMMING (TO 10% OUTPUT);UNIVERSAL INPUT; 26" C-CHANNEL BARHANGERS; 5-YR WARRANTEE.

LED, 4000K, 80CRI 11 VA 277 VPORTFOLIO

CREEPRESCOLITE

LD4B SERIESS-DL4 SERIESLF4SL SERIES

WHITE TRIMRING

RECESSEDIN GYP/ACT

CEILING0'-4"

D3

SURFACE DOWNLIGHT; ALUMINUM HOUSINGWITH POLYCARBONATE LENS; 800 LUMENPACKAGE AT 66 LPW EFFICACY; 50,000 HR LIFEAT L70 DEPRECIATION; ELECTRONIC DRIVER;0-10v DIMMING (TO 10% OUTPUT); DAMPLOCATION LISTED; WET LOCATION LISTED; 5-YRWARRANTEE.

LED, 4000K, 80CRI 12 VA 277 V HALO SLD 600 SERIESWHITE TRIM

RINGSURFACE

MOUNT-

ED

EXIT DISCHARGE LIGHT; WEATHERPROOF,REMOTE LAMP HEAD; GASKETED FOR OUTDOORUSE; THERMOPLASTIC MOUNTING PLATE; WETLOCATION RATED; POWERED BY 'X3'; 1-YRWARRANTEE.

LED INCLUDED 5 VA 7 V CHLORIDE CA-51400 SERIES WHITEWALL

MOUNT+8'-0" A.F.F.

-

P2

LINEAR PENDANT; EXTRUDED ALUMINUMHOUSING; 4,000 (2,000 DIRECT, 2,000 INDIRECT)LUMEN PACKAGE AT 129 LPW EFFICACY; 60,000HR LIFE AT L80 DEPRECIATION; ELECTRONICDRIVER, 0-10V DIMMING (TO 1% OUTPUT);UNIVERSAL INPUT; 5-YR WARRANTEE.

LED, 4000K, 80CRI 31 VA 277 VLUMENWERX

AXISVIA 4 SERIES

BEAM 4 SERIESWHITE

SOLIDPENDANT

MOUNTFROM

STRUCTURE+8'-6" A.F.F.

- 1

S1

INDUSTRIAL STRIP; 4' STEEL HOUSING; 3,371LUMEN PACKAGE AT 153 LPW EFFICACY; 170,000HR LIFE AT L70 DEPRECIATION; ELECTRONICDRIVER, UNIVERSAL INPUT; 0-10V DIMMING (TO10% OUTPUT); DAMP LOCATION LISTED; 5-YRWARRANTEE.

LED, 4000K, 85CRI 22 VA 277 V METALUX SNLED SERIES WHITESURFACE,PENDANT,OR CHAIN

-

T1

RECESSED TROFFER; 2'X2' STEEL HOUSING;CURVED FROSTED ACRYLIC DIFFUSER; 3,900LUMEN PACKAGE AT 118 LPW EFFICACY; 50,000HR LIFE AT L70 DEPRECIATION; ELECTRONICDRIVER, UNIVERSAL INPUT; 0-10V DIMMING (TO10% OUTPUT); DAMP LOCATION LISTED; 5-YRWARRANTEE.

LED, 4000K, 85CRI 33 VA 277 V H.E. WILLIAMS LT SERIES WHITERECESSEDIN GYP/ACT

CEILING0'-4" 2

T2

RECESSED TROFFER; 2'X2' STEEL HOUSING;CURVED FROSTED ACRYLIC DIFFUSER; 2,700LUMEN PACKAGE AT 129 LPW EFFICACY; 50,000HR LIFE AT L70 DEPRECIATION; ELECTRONICDRIVER, UNIVERSAL INPUT; 0-10V DIMMING (TO10% OUTPUT); DAMP LOCATION LISTED; 5-YRWARRANTEE.

LED, 4000K, 85CRI 21 VA 277 V H.E. WILLIAMS LT SERIES WHITERECESSEDIN GYP/ACT

CEILING0'-4" 2

X1

EXIT SIGN; SINGLE FACE; SIX INCH LETTERS ONTHERMOPLASTIC FACE; HIGH INTENSITY LEDLIGHT SOURCE; SOLID STATE CHARGINGCIRCUIT; SEALED NICKEL CADMIUM BATTERIES;ORIENT CHEVRONS TO COINCIDE WITHARCHITECT'S EGRESS PLAN; 1-YR WARRANTEE.

LED INCLUDED 5 VA 277 VSURE-LITESEMERGI-LITE

DUAL-LITE

LPX SERIESPREMIER SERIES

EVE SERIES

WHITE WITHRED

LETTERS

CEILING ORWALL, +8'-0"A.F.F.,U.O.N.

-

X2

EXIT SIGN; DOUBLE FACE; SIX INCH LETTERS ONTHERMOPLASTIC FACE; HIGH INTENSITY LEDLIGHT SOURCE; SOLID STATE CHARGINGCIRCUIT; SEALED NICKEL CADMIUM BATTERIES;ORIENT CHEVRONS TO COINCIDE WITHARCHITECT'S EGRESS PLAN; 1-YR WARRANTEE.

LED INCLUDED 5 VA 277 VSURE-LITESEMERGI-LITE

DUAL-LITE

LPX SERIESPREMIER SERIES

EVE SERIES

WHITE WITHRED

LETTERS

CEILING ORWALL, +8'-0"A.F.F.,U.O.N.

-

X3

EXIT SIGN; SINGLE FACE; SIX INCH LETTERS ONTHERMOPLASTIC FACE; HIGH INTENSITY LEDLIGHT SOURCE; SOLID STATE CHARGINGCIRCUIT; SEALED, NICKEL CADMIUM BATTERIES;ORIENT CHEVRONS TO COINCIDE WITHARCHITECT'S EGRESS PLAN; BATTERY CAPACITYFOR 90-MINUTE OPERATION OF REMOTE HEAD;1-YR WARRANTEE.

LED INCLUDED 5 VA 277 V SURE-LITES LPXH SERIESWHITE WITH

REDLETTERS

CEILING ORWALL, +8'-0"A.F.F.,U.O.N.

-

GENERAL NOTES:A. Catalog number refers to first name listed under manufacturer per luminaire type. Remaining manufacturers listed are considered to be equivalent products for this project and shall meet all criteria listed including that called for by

the specific luminaire catalog number. Catalog numbers do not necessarily represent complete catalog numbers. All items listed in the description shall be provided.B. Refer to lighting specifications for additional requirements.C. Provide unit pricing for all luminaires by type and submit with bid form.

L U M I N A I R E S C H E D U L E

Key # Item HP FLA LoadEq Load

(VA) Voltage

Feeders Protection

NotesWire Ground ConduitBreake

r Disconnect Fuse

EF 2 EXHAUST FAN 0.25 0 A 0 VA 696 VA 120V 1ph 2#12 #12G 3/4” 20 A S

EWH 1 ELECTRIC WATER HEATER 0 0 A 2000 VA 2000 VA 120V 1ph 2#10 #10G 3/4" 25A S 20A

HWP 3 PUMP 0.5 0 A 0 VA 1123 VA 208V 1ph 2#12 #12G 3/4” 20 A S

M E C H A N I C A L E Q U I P M E N T S C H E D U L E

GENERAL NOTES: A. Prior to work, verify electrical requirements (voltage, amperage, recommended OCPD, conductors, and disconnect) for each piece of equipment.B. Prior to work, verify exact location for each piece of equipment.C. Coordinate and provide all field connections as required.D. Coordinate 120V power connections to dampers and other control circuits. Group equipment control circuits such that failure of one control circuit does not affect operation of other

equipment. For example, do not connect a damper associated with one air handling unit to the same branch circuit as dampers associated with a different air handling unit.E. Feeders, breakers, disconnects, and fusing applies to field-installed and/or factory-installed equipment.

SPECIFIC NOTES:1. Provide equipment with integral disconnect switch and fusing as indicated.

Key Item HP FLA Load Eq Load (VA) Voltage

Feeders Protection

NotesWire Ground Conduit BreakerDisconnec

t Fuse

1 TELE TERM BOARD (TTB) 0 12 A 0 VA 1440 VA 120V 1ph 2#10 #10G 3/4" 30 A 2

2 RACK 0 0 A 2880 VA 2880 VA 120V 1ph 2#10 #10G 3/4" 30 A 2

3 FIREPLACE 0 13 A 0 VA 1608 VA 120V 1ph 2#12 #12G 3/4” 20 A 3

O W N E R E Q U I P M E N T S C H E D U L E

GENERAL NOTES:A. Prior to work, verify electrical requirements (voltage, amperage, recommended OCPD, conductors, and disconnect) for each piece of equipment.B. Prior to work, verify exact location for each piece of equipment with Architect and/or owner.

SPECIFIC NOTES:1. Verify exact mounting height with architect and provide appropriate suspension length.2. No equals will be considered. Contractor shall provide unit pricing for the quantity as shown on these plans.

SPECIFIC NOTES:1. Connect equipment to emergency power.2. Provide twist lock receptacle. Refer to plans for configuration.3. Equipment furnished with integral disconnect switch.

GENERAL NOTES:A. Not all space names are listed for each lighting control type. Refer to plans for all spaces to be controlled.B. Spaces may contain multiple zones of control. Refer to plans for quantity of zones, switches, etc.C. Provide the quantity of sensors as required for full coverage of the space. Devices shown on plan are for design intent only and do not necessarily reflect the exact quantity required for full coverage.D. Where a single switch/dimmer is denoted with multiple switch legs, design intent is a single-gang device with multiple-mode control.E. All spaces with sensors shall be provided with manual 'off' means. All spaces with time schedule controls shall have means for manual 'on/off'.

L I G H T I N G C O N T R O L M A T R I X

SPECIFIC NOTES:1. Utilize 'flick warning' prior to timed lighting shutoff.

KEY:On / Off:Dimming:Sensor:Daylight:Emergency:Interface:

M = Manual (switch), A = Automatic (sensor), T = Time schedule, P = Photocell, #% = Control to #% light level0-10V, ELV, DMX, DALI, 2L = Dual-level step-dim, 3L = Tri-level step-dimC = Ceiling-mounted, W = Wall corner-mounted, S = Sensor integral to wall switch, PIR = PIR sensor, DT = Dual Technology sensorINT = Interior dimming photocell, EXT = Central exterior photocell input, LUM = Photocell integral to luminaire(s)ALCR = Provicde automatic load control relays for luminaires on emergency circuit, provide test switch if not integral to relayN = Tie zone to central control network, BAS = Send sensor status to BAS, AV = Enable scene control through AV system (re: Sec. 26 09 23)

Type Space On Off Dimming Sensor Timing Daylight Emergency Interface Notes

LC2 Office - Private A A 0-10V S PIR 10 min

LC3 Utility M M

LC4 Meeting - Conference Room A A 0-10V C DT 20 min

LC5 Circulation - Corridor T T 30 min 1

LC6 Workspace A A 0-10V C DT 30 min

LC7 Utility - Small Storage M A S PIR 5 min

1 01.29.18 ADD 1

SCALE: NONE

ENERGY CODE COMPLIANCE

1ADD-1

1ADD-1

Page 33: LCCC Crossroads Renovation HCM Job No.11738.001 … · LCCC Crossroads Renovation HCM Job No.11738.001 ADDENDUM 01 009113.01 - 2 H. Tech Lighting – 700 series shall be acceptable

L O A D R E V I S I O N S U M M A R Y

DESCRIPTION CONNECTED LOAD NEC DEMAND DEMAND KVA

DEMOLISHED LIGHTS 11.2 125% (14.0)

DEMOLISHED RECEPTACLES 13.9 100% (13.9)

NEW LIGHTING 4.7 125% 5.9

NEW RECEPTACLES 30.1 100% 30.1

NEW MECHANICAL LOAD 21.1 100% 21.1

LARGEST MOTOR 1.1 25% 0.3

TOTAL CALCULATED KVA 29.5

SERVICE VOLTAGE 480 V

SERVICE CAPACITY 600 A

REVISED LOAD ON DISTRIBUTION 35 A

CONSULTANT:

ISSUE:

OWNER:

PROJECT:

DRAWING INFORMATION:

DRAWN BY:

PROJECT NO:

SHEET TITLE:

APPROVED BY:

CHECKED BY:

SHEET OF

1 2 3 4 5 6

A

B

C

D

E

1 2 3 4 5 6

P 303.607.0977www.hcm2.com

1331 Nineteenth StreetDenver, CO. 80202

hord|coplan|macht

1/2

9/2

01

8 4

:23:1

1 P

M

E-302

ELECTRICAL PANELSCHEDULES

LARAMIE COUNTYCOMMUNITYCOLLEGE

CROSSROADSBUILDINGRENOVATION

CMI

BJK

11738.001

CMI

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

P:\W

yom

ing

\LC

CC

\2017

-245

Cro

ssro

ad

s B

uild

ing

Re

novatio

ns\C

ad

1400 EAST COLLEGE DRIVECHEYENNE, WY 82007

01.04.2018 CONTRACT DOCUMENTS

NEW PANELBOARD

General Notes:

O Other 0 VA 0.00% 0 VA

E Existing 0 VA 0.00% 0 VA Total Demand Current: 166 A

K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 59629 VA

G General 7300 VA 100.00% 7300 VA

C Continuous 0 VA 0.00% 0 VA Total Connected Current: 221 A

M Motor 14219 VA 104.22% 14819 VA Total Connected Load: 79504 VA

R Receptacle 53295 VA 59.38% 31648 VA

L Lighting 4690 VA 125.00% 5863 VA

Load Type Connected Load Demand Factor Demand Load Panel Totals

Phase Balance: 7 % A-B 1 % B-C 7 % C-A

Total Amps: 212 A 226 A 228 A

Total Load: 25472 VA 26945 VA 27088 VA

71 SPARE -- 20 A 1 0 VA 720 VA 1 20 A R REC-STUDY 110C 72

69 EQ- EWH-1 M 25 A 1 2000 VA 0 VA 1 20 A -- SPARE 70

67 REC-109 TV,110A TV R 20 A 1 1000 VA 0 VA 1 20 A -- SPARE 68

65 REC- CONF 104B R 20 A 1 900 VA 1080 VA 1 20 A R REC-CONF. 109 FLOOR 66

63 REC-103 TV, 104B TV R 20 A 1 1000 VA 696 VA 1 20 A M EQ-EF-2 64

61 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 62

59 REC-VEND 117 R 20 A 1 1380 VA 900 VA 1 20 A R REC-STUDY 110C 60

57 REC-COPIER 104K R 20 A 1 540 VA 780 VA 1 20 A R REC-CONF. 109... 58

55 REC-VEND 117 R 20 A 1 1380 VA 1440 VA 1 20 A R REC-MICROWAVE 117 56 2

53 REC-105D CLG R 35 A 1 2880 VA 1440 VA 1 20 A R REC-MICROWAVE 117 54 2

51 REC-PWR POLE 103B R 20 A 1 720 VA 562 VA 52

49 REC-CONFERENCE 109 R 20 A 1 1260 VA 562 VA2 20 A M EQ-PUMP 1

50

47 REC-105D SOUTH R 35 A 1 1440 VA 1608 VA 1 20 A R R-FIREPLACE 48

45 REC-103A NORTH R 20 A 1 900 VA 0 VA 1 20 A -- SPARE 46

43 REC-103C SOUTH R 20 A 1 720 VA 180 VA 1 20 A R REC-FUTURE USE 44 2

41 2160 VA 360 VA 1 20 A R REC-W WALL PHONE... 42

39 2360 VA 1440 VA 1 20 A R REC-CONFERENCE 109 40

37

PANEL LB R; M; L 60 A 3

3130 VA 2400 VA 38

35 REC-PWR POLE 103B R 20 A 1 1440 VA 2400 VA2 30 A G

EQ - HOT WATERHEATER

36

33 R-COLLAB COMPUTER R 20 A 1 1080 VA 336 VA 1 20 A R REC-PLG MOLD 110A 34

31 ATM G 20 A 1 1000 VA 1400 VA 1 20 A R REC-105,6,7 32

29 ATM G 20 A 1 1000 VA 1260 VA 1 20 A R REC-103,4,5 30

27 ELECT. HAND DRYER M 30 A 1 2400 VA 2400 VA 1 30 A M ELECT. HAND DRYER 28

25 ELECT. HAND DRYER M 30 A 1 2400 VA 2400 VA 1 30 A M ELECT. HAND DRYER 26

23 REC-RM 126 W/S WAL R 20 A 1 720 VA 720 VA 1 20 A R REC-124-125 24

21 REC-ADMISSIONS R 20 A 1 1260 VA 1080 VA 1 20 A R R-COLLAB COMPUTER 22

19 REC-N. BOOKSTORE R 20 A 1 720 VA 1080 VA 1 20 A R REC- CONF 104B 20

17 REC-N. BOOKSTORE R 20 A 1 720 VA 900 VA 1 20 A R REC-110A 18

15 REC-COPIER 105C R 20 A 1 1200 VA 1250 VA 1 20 A R REC- 110B,C 16

13 REC-COPIER 105C R 20 A 1 1200 VA 540 VA 1 20 A R REC-112 14

11 REC-104H R 20 A 1 540 VA 360 VA 1 20 A R REC-103C WEST 12

9 REC-103A R 20 A 1 1080 VA 1440 VA 1 20 A R REC-104L,104M 10

7 REC-104E R 20 A 1 720 VA 180 VA 1 20 A R REC-FUTURE USE 8 2

5 REC-105C,D R 20 A 1 1080 VA 1080 VA 1 20 A R REC-105A 6

3 REC-104J,105B R 20 A 1 1440 VA 1080 VA 1 20 A R REC-104F, 104G 4

1 TELEPHONE G 20 A 1 500 VA 1260 VA 1 20 A R REC- 104A,C,K 2

Note Circ... Load Type Trip Po... A B C Po... Trip Type Load Circ... Note

1. NEW LOAD ON EXISTING CIRCUIT BREAKER.2. PROVIDE GFCI CIRCUIT BREAKER.3. REPLACE EXISTING CIRCUIT BREAKER WITH NEW CIRCUIT BREAKER.

Circuit Notes:

Enclosure: Type 1 MCB Rating: 225 A

Mounting: Surface Wire: 4 Bus Rating: 225 A

Supply From: T75 Phase: 3 Mains Type: MCB

Location: ELEC. 106 Voltage: 120/208 Wye A.I.C. Rating: 10,000

Panel LA

EXISTING PANELBOARD

General Notes:

O Other 0 VA 0.00% 0 VA

E Existing 0 VA 0.00% 0 VA Total Demand Current: 25 A

K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 8973 VA

G General 0 VA 0.00% 0 VA

C Continuous 0 VA 0.00% 0 VA Total Connected Current: 21 A

M Motor 800 VA 118.75% 950 VA Total Connected Load: 7650 VA

R Receptacle 2160 VA 100.00% 2160 VA

L Lighting 4690 VA 125.00% 5863 VA

Load Type Connected Load Demand Factor Demand Load Panel Totals

Phase Balance: 32 % A-B 11 % B-C 46 % C-A

Total Amps: 26 A 20 A 18 A

Total Load: 3130 VA 2360 VA 2160 VA

29 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 30

27 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 28

25 REC-PWR POLE STUD.... R 20 A 1 360 VA 360 VA 1 20 A R REC-PWR POLE STUD.S 26

23 SPARE -- 20 A 1 0 VA 360 VA 1 20 A R REC-PWR POLE STUD.S 24

21 SPARE -- 20 A 1 0 VA 360 VA 1 20 A R REC-E. RECEP. AREA 22

19 0 VA 360 VA 1 20 A R REC-N. RECEP. AREA 20

17SPARE -- 20 A 2

0 VA 1000 VA 1 20 A L LTS-RECEP. AREA 18

15 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 16

13 REC-PWR POLE STUD.S R 20 A 1 360 VA 0 VA 1 20 A -- SPARE 14

11 SPARE -- 20 A 1 0 VA 600 VA 1 20 A M EQ-EXHAUST FAN 12

9 LTS-E. OF BOOKSTORE L 20 A 1 1000 VA 500 VA 1 20 A L LTS-FAN ROOM 10

7 LTS-OVER COUNTER L 20 A 1 500 VA 500 VA 1 20 A L LTS-CENTER AREA 8

5 SPARE -- 20 A 1 0 VA 200 VA 1 20 A M FAN COIL 6

3 SPARE -- 20 A 1 0 VA 500 VA 1 20 A L LTS-OVR SEAT AREA 4

1 SPARE -- 20 A 1 0 VA 690 VA 1 20 A L LTS-LOBBY 2

Note Circ... Load Type Trip Po... A B C Po... Trip Type Load Circ... Note

Circuit Notes:

Enclosure: Type 1

Mounting: Surface Wire: 4 Bus Rating: 100 A

Supply From: LA Phase: 3 Mains Type: MLO

Location: ELEC. 106 Voltage: 120/208 Wye A.I.C. Rating: 10,000

Panel LB

EXISTING PANELBOARD

General Notes:

O Other 0 VA 0.00% 0 VA

E Existing 0 VA 0.00% 0 VA Total Demand Current: 124 A

K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 102964 VA

G General 7300 VA 100.00% 7300 VA

C Continuous 0 VA 0.00% 0 VA Total Connected Current: 138 A

M Motor 31670 VA 113.78% 36033 VA Total Connected Load: 114652 VA

R Receptacle 53295 VA 59.38% 31648 VA

L Lighting 22387 VA 125.00% 27984 VA

Load Type Connected Load Demand Factor Demand Load Panel Totals

Phase Balance: 7 % A-B 1 % B-C 5 % C-A

Total Amps: 144 A 134 A 136 A

Total Load: 39755 VA 37216 VA 37682 VA

-- 41 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 42 --

-- 39 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 40 --

-- 37 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 38 --

-- 35 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 36 --

-- 33 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 34 --

-- 31 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 32 --

-- 29 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 30 --

-- 27 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 28 --

25 0 VA 0 VA 26

23 0 VA 0 VA 24

21

SPARE -- 15 A 3

0 VA 0 VA

3 40 A -- SPARE

22

19 5817 VA 0 VA 20

17 5817 VA 0 VA 18

15

EQ- HVAC UNIT M 50 A 3

5817 VA 0 VA

3 15 A -- SPARE

16

13 SPARE -- 20 A 1 0 VA 27088... 14

11 LTS - BKSTORE RM 126 L 20 A 1 3600 VA 26945... 12

9 LTS - BKSTORE RM 126 L 20 A 1 3200 VA 25472...

3 100 A R; G; M; LPANEL LA VIA 75kVAXFMR

10

2

7 LTS - BATH/STORE RM L 20 A 1 2800 VA 2800 VA 1 20 A L LTS-EXT LTG - TIME... 8

5 SPARE -- 20 A 1 0 VA 1320 VA 1 20 A L LTS-CENTER 6 1

3 LTS -122-103 L 20 A 1 1300 VA 1427 VA 1 20 A L LTS-EAST 4 1

1 SPARE -- 20 A 1 0 VA 1250 VA 1 20 A L LTS-WEST & 103C... 2 1

Note Circ... Load Type Trip Po... A B C Po... Trip Type Load Circ... Note

1. NEW LOAD ON EXISTING CIRCUIT BREAKER.2. REPLACE EXISTING CIRCUIT BREAKER WITH NEW CIRCUIT BREAKER.

Circuit Notes:

Enclosure: Type 1

Mounting: Surface Wire: 4 Bus Rating: 225 A

Supply From: Phase: 3 Mains Type: MLO

Location: ELEC. 106 Voltage: 480/277 Wye A.I.C. Rating: 14,000

Panel PA

1 01.29.18 ADD 1

1ADD-1 1

ADD-1

1ADD-1

1ADD-1