Laser- based smoke detectors
Lzr-1
7251
![Page 2: Laser- based smoke detectors Lzr-1 7251. Schneider Electric 2 - Division - Name – Date LZR-1 Detector Chamber Laser Diode Laser produces a brighter, more.](https://reader030.fdocuments.us/reader030/viewer/2022020111/56649ea05503460f94ba3175/html5/thumbnails/2.jpg)
Schneider Electric 2- Division - Name – Date
LZR-1 Detector Chamber
Laser Diode
• Laser produces a brighter, more concentrated beam of light
• More signal is achieved due to the more concentrated light
• Smaller particles can be detected due to the brighter light
![Page 3: Laser- based smoke detectors Lzr-1 7251. Schneider Electric 2 - Division - Name – Date LZR-1 Detector Chamber Laser Diode Laser produces a brighter, more.](https://reader030.fdocuments.us/reader030/viewer/2022020111/56649ea05503460f94ba3175/html5/thumbnails/3.jpg)
Schneider Electric 3- Division - Name – Date
Laser Detector Benefits
• Focussed beam
• improves settled dust performance
• improves airborne dust performance
Light Source(LED)
Smoke Sensor
(Photodiode)
Standard optical smoke detector princible
![Page 4: Laser- based smoke detectors Lzr-1 7251. Schneider Electric 2 - Division - Name – Date LZR-1 Detector Chamber Laser Diode Laser produces a brighter, more.](https://reader030.fdocuments.us/reader030/viewer/2022020111/56649ea05503460f94ba3175/html5/thumbnails/4.jpg)
Schneider Electric 4- Division - Name – Date
Applications suitable for LZR-1
• High value property, clean environments•Telecommunications switching rooms•Computer Rooms•Electrical equipment rooms•Museums, galleries etc..
• Avoid•cigarette smoke, dust, steam, exhaust fumes, textile fibres
![Page 5: Laser- based smoke detectors Lzr-1 7251. Schneider Electric 2 - Division - Name – Date LZR-1 Detector Chamber Laser Diode Laser produces a brighter, more.](https://reader030.fdocuments.us/reader030/viewer/2022020111/56649ea05503460f94ba3175/html5/thumbnails/5.jpg)
Schneider Electric 5- Division - Name – Date
• Low Airflow ( < 10 air changes per hour)•40m2 per detector (3.5m radius)
• High Airflow ( > 10 air changes per hour)•25m2 per detector (2.8m radius)
• Extra detectors may be placed•at inlets to air conditioning systems•areas of high air movement•inside cabinets•floor and ceiling voids
Detector spacing / coverage
![Page 6: Laser- based smoke detectors Lzr-1 7251. Schneider Electric 2 - Division - Name – Date LZR-1 Detector Chamber Laser Diode Laser produces a brighter, more.](https://reader030.fdocuments.us/reader030/viewer/2022020111/56649ea05503460f94ba3175/html5/thumbnails/6.jpg)
Schneider Electric 6- Division - Name – Date
Function of LZR-1 laser detector and a laser group in Esa1 system
PW4 analogue value of the new detector is between 100 … 500s.
The Basic Environment Level (B.E.L) in panel memory is updated every 5th minute.
Time constant is 21h when the value is rising (up to 65% of the new value) and 25min when it’s decreasing (65% of new value).
Fire- and pre-alarm levels can be set between B.E.L + 60 … 2000s.
Saturation value of panel’s memory is updated once during daytime between 10.00 … 16.00, and it can be between 2600 … 4000s.
Time constant for saturation is 16 days (65% of new value).
Fire level or pre-alarm level are in any case 100s under the saturation value, no matter what the configured value is.
Maintenance warning level is fixed to 1200s.
![Page 7: Laser- based smoke detectors Lzr-1 7251. Schneider Electric 2 - Division - Name – Date LZR-1 Detector Chamber Laser Diode Laser produces a brighter, more.](https://reader030.fdocuments.us/reader030/viewer/2022020111/56649ea05503460f94ba3175/html5/thumbnails/7.jpg)
Schneider Electric 7- Division - Name – Date
Configuration levels vs. analogue values
Level 1 = 60s over B.E.LLevel 2 = 280s --------“-------Level 3 = 490s --------“--------Level 4 = 710s --------“-------Level 5 = 920s --------“--------Level 6 = 1140s --------“------- (default value for pre alarm)Level 7 = 1350s --------“------- (default value for fire alarm)Level 8 = 1570s --------“-------Level 9 = 1780s --------“-------Level 10 = 2000s --------“-------
![Page 8: Laser- based smoke detectors Lzr-1 7251. Schneider Electric 2 - Division - Name – Date LZR-1 Detector Chamber Laser Diode Laser produces a brighter, more.](https://reader030.fdocuments.us/reader030/viewer/2022020111/56649ea05503460f94ba3175/html5/thumbnails/8.jpg)
Schneider Electric 8- Division - Name – Date
Signal processing
-Panel is filtering interferences from the signal of detectors, and will proportionate the signal between 0 and 1, so that B.E.L is 0 and alarm value is 1.
Example 1 Fire alarm set to level L1
360s Fire alarm level = B.E.L + 60s (level 1)
330s Measuring value 330s proportion value is 0.5
300s B.E.L 300s
![Page 9: Laser- based smoke detectors Lzr-1 7251. Schneider Electric 2 - Division - Name – Date LZR-1 Detector Chamber Laser Diode Laser produces a brighter, more.](https://reader030.fdocuments.us/reader030/viewer/2022020111/56649ea05503460f94ba3175/html5/thumbnails/9.jpg)
Schneider Electric 9- Division - Name – Date
Example 2 Fire alarm set to level L7
1350s Fire alarm level = B.E.L + 1350s (level 7)
330s Measuring value 330s Proportion value is 0.022
300s B.E.L 300s
Signal processing
![Page 10: Laser- based smoke detectors Lzr-1 7251. Schneider Electric 2 - Division - Name – Date LZR-1 Detector Chamber Laser Diode Laser produces a brighter, more.](https://reader030.fdocuments.us/reader030/viewer/2022020111/56649ea05503460f94ba3175/html5/thumbnails/10.jpg)
Schneider Electric 10- Division - Name – Date
Function of a laser group
•Laser detectors in the same fire zone will automatically form a laser group
•There is no need for configuration.
•Proportion values of all detectors in same laser group are squared and added together. •If the sum value is 1 or more, it will activate the alarm, which is shown from the address where the proportion value is highest.
•If the value of a single detector is 1 or more, it will activate the alarm.
•The function is the same with Fire-alarm and Pre-alarm
![Page 11: Laser- based smoke detectors Lzr-1 7251. Schneider Electric 2 - Division - Name – Date LZR-1 Detector Chamber Laser Diode Laser produces a brighter, more.](https://reader030.fdocuments.us/reader030/viewer/2022020111/56649ea05503460f94ba3175/html5/thumbnails/11.jpg)
Schneider Electric 11- Division - Name – Date
Grouping Algorithm
• Signal from detectors in close proximity is summed using a ‘mean square’ algorithm - 2= A 2 + B 2 + C 2
• Grouping of detectors gives a higher effective sensitivity with less risk of false alarms
• For best performance always use more than one detector in any area
![Page 12: Laser- based smoke detectors Lzr-1 7251. Schneider Electric 2 - Division - Name – Date LZR-1 Detector Chamber Laser Diode Laser produces a brighter, more.](https://reader030.fdocuments.us/reader030/viewer/2022020111/56649ea05503460f94ba3175/html5/thumbnails/12.jpg)
Schneider Electric 12- Division - Name – Date
Function of a laser group
Example 1: Three laser detectors in the same fire zone
Fire zone X Laser group
01.001 01.002 01.003
0.25 + 0.64 + 0.04 = 0.93 <1 No Alarm
Proportion value 0.5 0.8 0.2
Square rooting 0.5² 0.8² 0.2²
![Page 13: Laser- based smoke detectors Lzr-1 7251. Schneider Electric 2 - Division - Name – Date LZR-1 Detector Chamber Laser Diode Laser produces a brighter, more.](https://reader030.fdocuments.us/reader030/viewer/2022020111/56649ea05503460f94ba3175/html5/thumbnails/13.jpg)
Schneider Electric 13- Division - Name – Date
Function of a laser group
Example 2: Four laser detectors in the same fire zone
Fire zone X Laser group
01.007 01.012 01.053 01.094 Proportion value 0.5 0.8 0.2 0.3 Square rooting 0.5² 0.8² 0.2² 0.3²
0.25 + 0.64 + 0.04 + 0.09 = 1.02 >1 ALARM
-- Fire alarm is shown from this address.
![Page 14: Laser- based smoke detectors Lzr-1 7251. Schneider Electric 2 - Division - Name – Date LZR-1 Detector Chamber Laser Diode Laser produces a brighter, more.](https://reader030.fdocuments.us/reader030/viewer/2022020111/56649ea05503460f94ba3175/html5/thumbnails/14.jpg)
Schneider Electric 14- Division - Name – Date
Selection of Sensitivity
• High Sensitivity Pre-Alarm•Alarm sensitivity from 0.01% / ft to 1.0%/ft•Set Pre-alarm sensitivity just high enough to meet ‘hot-wire’ test•Monitor system for three months
• Use lower sensitivity alarm (> 1.63%/m)
![Page 15: Laser- based smoke detectors Lzr-1 7251. Schneider Electric 2 - Division - Name – Date LZR-1 Detector Chamber Laser Diode Laser produces a brighter, more.](https://reader030.fdocuments.us/reader030/viewer/2022020111/56649ea05503460f94ba3175/html5/thumbnails/15.jpg)
Schneider Electric 15- Division - Name – Date
Analyzing of LZR-1 signals
ZONE 0001 ADDR. 01.001 ENABLED
LASER SENSOR A2 S28 C204 M186 P 0 F 0
Analogue values of LZR-1 detector can be seen on access level three
There are six PW4 values at one window for one detector
A = Basic Enviroment Level (BEL), from which two least significant digits are removed.In this case A2 can be between 200s … 299s. S = Saturation value, from which the two least significant digits are removed.
In this case S28 can be between 2800s … 2899s.
C = Last value from detector without filtering.
M = Value after filtering (lowest of the last tree readings).
P = % of Pre alarm level.
F = % of Fire alarm level.
![Page 16: Laser- based smoke detectors Lzr-1 7251. Schneider Electric 2 - Division - Name – Date LZR-1 Detector Chamber Laser Diode Laser produces a brighter, more.](https://reader030.fdocuments.us/reader030/viewer/2022020111/56649ea05503460f94ba3175/html5/thumbnails/16.jpg)
Schneider Electric 16- Division - Name – Date
POWER ELECTRONIC CABINETS
DETAILS
ASPIRATING TUBE
AND DETECTORS
VESDA / AIR-SENSE
CENTRAL UNIT
Test: Aspirating system vs. ESA1+LZR-1
![Page 17: Laser- based smoke detectors Lzr-1 7251. Schneider Electric 2 - Division - Name – Date LZR-1 Detector Chamber Laser Diode Laser produces a brighter, more.](https://reader030.fdocuments.us/reader030/viewer/2022020111/56649ea05503460f94ba3175/html5/thumbnails/17.jpg)
Schneider Electric 17- Division - Name – Date
F IR E ZO N E 1 F IR E ZO N E 2
PO
WE
R E
LE
CT
RO
NIC
DE
VIC
ES
PO
WE
R E
LE
CT
RO
NIC
DE
VIC
ES
PO
WE
R E
LE
CT
RO
NIC
DE
VIC
ES
PO
WE
R E
LE
CT
RO
NIC
DE
VIC
ES
s mo k e s o u r c e
= L ZR - 1 d e t e c t o r
= v e s d a a s p ir a t io n t u b e
Smoke test 1 Fire Zone 1
00:00 START
00:55 ESA1 FIRE
01:20 ESA1 2nd FIRE
01:25 ESA1 3rd FIRE
01:40 VESDA FIRE
01:45 ESA1 4th FIRE
Smoke test 2 Fire Zone 1
00:00 START
00:45 VESDA WARNING
00:55 ESA1 FIRE
01:10 VESDA FIRE
01:15 ESA1 2nd FIRE
01:20 ESA 3rd FIRE
01:25 ESA 4th FIRE
Smoke test 1 Fire Zone 2
00:00 START
00:50 VESDA WARNING
01:05 ESA1 FIRE
01:15 VESDA FIRE
01:15 ESA1 2nd FIRE
01:20 ESA1 3rd FIRE
01:25 ESA1 4th FIRE