Large Chilled Water System Design Seminar
Presented by:Larry Konopacz, Manager of Training & Education
Bell & Gossett Little Red Schoolhouse
This presentation is being brought to you by:
ASHRAE India Chapter and Xylem, Inc.
Saturday, September 21, 2013
![Page 2: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/2.jpg)
Large Chilled Water System Design Seminar
The Production Loop
![Page 3: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/3.jpg)
• Chillers• Cooling towers• Free-Cooling &
Waterside Economizer• Thermal Storage• Water Source Heat Pumps
Chilled Water Sources
![Page 4: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/4.jpg)
I Ton Ice =2000 LB;1LB Ice =144 Btu;
1 Ton ice =288,000 Btu
What’s a Ton?
![Page 5: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/5.jpg)
12,000 Btu/h = 500 x gpm x t°F = 1 ton
gpm/ton = 12,000/(500 x t°F)
= 24/t°F
Rule of 24
![Page 6: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/6.jpg)
What Types of Chillers are Available?
• Centrifugal• Rotary screw• Reciprocating• Absorption
Evaporator
Condenser
Compressor
![Page 7: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/7.jpg)
Refrigeration Cycle
Cooling Tower
Condenser
CondenserWater Pump
CompressorMotor
Expansion Device
ChilledWaterPump
High P
ressure Zone
Low P
ressure Zone
Load
Hot Water Liquid Flow
ReturnWater
Vapor FlowCool Water
SupplyWaterEvaporator
![Page 8: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/8.jpg)
Where is What Used?
• Large chilled water plants - centrifugal• Mid-range size - rotary screw• Smaller chilled water applications -
reciprocating• Inexpensive source of steam or other
energy source - absorption• Combinations of the above
![Page 9: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/9.jpg)
CHILLER Chiller 2
Chiller 1
SupplyReturn Common Pipe
Chiller Piping - Evaporator Side
![Page 10: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/10.jpg)
Supply
Return
CommonPipe
TripleDuty
Chiller 3
Chiller 2
Chiller 1TripleDuty
Typical Piping Method
![Page 11: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/11.jpg)
Supply
Return
CommonPipe
TripleDuty
Chiller 2
TripleDutyChiller 1
Adding Pump Redundancy
![Page 12: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/12.jpg)
Piped forStandbyPumps
Supply
Return
CommonPipe
TripleDuty
Chiller 3
Chiller 2
Chiller 1TripleDuty
Actuated Control Valve
Headered Primary Pumps
![Page 13: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/13.jpg)
Chiller Piping - Condenser Side
Condenser Condenser
Condenser
Pumps
Cooling Towers
Triple Duty
SRS SRS SRS
![Page 14: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/14.jpg)
TripleDuty
Standby Pump
Condenser
Condenser
Condenser
Multi-cell Cooling Tower
SRS
Multi-celled Cooling Tower
![Page 15: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/15.jpg)
Cooling Towers
Triple Duty
Condenser
Condenser
Condenser
EqualizationLine
SRS
Tower Equalization
![Page 16: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/16.jpg)
Cooling Tower Piping Practices
• Fill all sections of pipe to purge air.• Size piping at a minimum of 2 fps to
move free air bubbles to tower.• All piping installed below system purge
level.
![Page 17: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/17.jpg)
System Purge Level
SRS
Condenser Water Piping Above Grade
![Page 18: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/18.jpg)
Overhead Piping Concerns
• Piping manifolds can result in low velocities.• Low velocity will allow air to be released.• Air trapped in piping increases head required.• Piping installed above purge level compounds
problem.• Unpurged areas are potential sources of
problems when pumps are turned on.
![Page 19: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/19.jpg)
Elevated Suction Piping Concerns
• Condenser water pump difficult to purge.• At start-up a manual air vent may be required.• During operation air will again accumulate.• Automatic air vent may not work.• If above the basin fill level, the result is
cavitation.
![Page 20: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/20.jpg)
Improper Piping Above Basin Level
System Purge Level
Basin Fill Level
![Page 21: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/21.jpg)
System Purge Level
SRS
Multi-tower System, Properly Piped
![Page 22: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/22.jpg)
Tower Piping Observations• At part load reduced velocities in headers may
allow air to be released.• Idle pumps will accumulate air that should be
released prior to starting the pump.• Tower basins should be elevated to ensure
positive pressure under all flow conditions.• Pump casings should be fitted with automatic
air vents.
![Page 23: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/23.jpg)
Condenser Head Pressure Control
With centrifugal chillers a minimum supplywater temperature is needed to:
• Maintain optimum efficiency• Maintain a minimum pressure differential
between condenser and evaporator• Prevent pressure imbalance
![Page 24: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/24.jpg)
Hermetic Compressor Guidelines
• Condenser water temperature > 75 °F.• Establish 75 °F within 15 minutes.• N/O condenser water throttling valve.• Three-way bypass valve can be used.• Constant condenser water flow.• Water temperature control through fan
modulation, or other methods.
![Page 25: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/25.jpg)
Open Compressor Guidelines
• Condenser water temperature > 55 °F.• Three-way bypass valve can be used.• Constant condenser water flow.• Water temperature control through fan
modulation, or other methods.
![Page 26: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/26.jpg)
Water In Water out
Air in Air out
Cooling Towers
![Page 27: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/27.jpg)
Water out
Air in Air in
Water in
Air Out
Induced Draft, Counter-flow Tower
![Page 28: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/28.jpg)
Air Out
Air inAir in
Water out
Water in
Forced Draft, Cross-flow Tower
![Page 29: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/29.jpg)
Temperature Water Flow
Hot water °F
Cold water °F
Wet bulb °F
“L” lb/min of water
“L” lb/min of water
Load
Ran
ge(“R
” °F)
Ap
proa
ch(°
F)
Heat Load = L x R
Dynamic Relationship of Load, Approach, and Range
![Page 30: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/30.jpg)
Tower Size Relationships
Variables:• Heat Load (Varies Directly)• Range (Varies Inversely)• Approach (Varies Inversely)• Wet-bulb Temperature (Varies Inversely)
Varying any of these variables will affect the size of the tower.
![Page 31: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/31.jpg)
Types of Free-Cooling(Waterside Economizer)
Water out
Air in Air in
Water in
Air Out
Earth Contact Evaporative
![Page 32: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/32.jpg)
Earth Contact Characteristics
• Usually indirect.• Cooling medium and load separated by heat
exchanger.• Stable temperatures.• Water temperature limitations.• Water treatment and pumping costs.• Environmental concerns.
![Page 33: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/33.jpg)
Heat Exchangers
![Page 34: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/34.jpg)
How do they work?• Thin plates are stamped with
a unique chevron pattern and assembled in a frame
• Four holes punched in the plate corners form a continuous tunnel which acts as a distribution manifold for the inlet and outlet of each fluid
![Page 35: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/35.jpg)
How do they work?• Each plate has a gasket that
confines the fluid to the port or to the heat transfer area of the plate
• Units are built to order with a standard 150 psi ASME Code stamped design or to custom designs
![Page 36: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/36.jpg)
LOADCOND
EVAP
Triple Duty
Sediment RemovalSeparator
Triple Duty
TOWER
HEAT
EXCH
GPX
Earth Contact - Summer Cycle
![Page 37: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/37.jpg)
LOADCOND
EVAP
Triple Duty
Sediment RemovalSeparator
Triple Duty
TOWER
HEAT
EXCH
GPX
Earth Contact - Winter Cycle
![Page 38: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/38.jpg)
Evaporative Characteristics
• Heat rejection device (tower) exists.• As temperature declines, opportunity
arises.• Higher sensible vs. latent loads• Leaving water temperature approaches
42 F.• Freeze protection may be required.
![Page 39: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/39.jpg)
Freeze Protection
• Sump heaters.• Close temperature control.• Accurate water level control.• Prevention of moist air recirculation.• External piping freeze protection.
![Page 40: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/40.jpg)
Evaporative Cooling - Direct
LOADCOND
EVAP
Triple Duty
Triple DutySediment RemovalSeparator
TOWER
Single Tower, Summer Cycle
![Page 41: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/41.jpg)
LOADCOND
EVAP
Triple Duty Triple Duty
Sediment RemovalSeparator
TOWER
* Alternate location of SRS, depending onsystem conditions
NOT RECOMMENDED
Single Tower, Winter Cycle
Evaporative Cooling - Direct
![Page 42: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/42.jpg)
Evaporative Cooling - Indirect
LOADCOND
EVAP
Triple Duty
Sediment RemovalSeparator
Triple Duty
TOWER
HEAT
EXCH
GPX
Single Tower/GPX, Summer Cycle
![Page 43: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/43.jpg)
Evaporative Cooling - Indirect
LOADCOND
EVAP
Triple Duty
Sediment RemovalSeparator
Triple Duty
TOWER
HEAT
EXCH
GPX
Single Tower/GPX, Winter Cycle
![Page 44: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/44.jpg)
COND. WATER
CH. WATER
TEMP.DEG. F
EXCHANGERLENGTH
57=
42=
45=
52=
7°F TEMPERATURECROSS
3°F COOLINGAPPROACH
T1
t2
t1
T2
Temperature Cross and Approach
![Page 45: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/45.jpg)
Temperatures are in F Flow is in USGPM
Heat exchanger selection based on max pressure drop of 7 psi
10/3.92=2.55 Approach = 3F
10/4.93=2.03 Approach = 4F
10/5.94=1.69 Approach = 5F
COND. WATER CH. WATER LMTD AREA EXCH. COSTEWT LWT FLOW EWT LWT FLOW DEG F SQ.FT. MODEL INDEX
42 52 1000 57 45 834 3.92 1390 GPX807 1.00
42 52 1000 58 46 834 4.93 1135 GPX807 0.85
42 52 1000 59 47 834 5.94 975 GPX807 0.76
Heat Transfer Area vs Approach
![Page 46: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/46.jpg)
Production Source - Thermal Storage
• Application Criteria• Economics• Storage Media• Storage Technologies• System Configurations
![Page 47: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/47.jpg)
Application Criteria
• High maximum load.• Significant premium for peak demand.• Incentives.• Limited space available.• Limited electrical capacity.• Back-up or redundancy required.
![Page 48: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/48.jpg)
Storage Media
• Chilled Water• Ice Harvesting• External/Internal Ice Melt
![Page 49: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/49.jpg)
T
Vent
Load
Pressure sustainingand check valve
StorageWarmCool
Variable volumedistributionpump
Constant volumeprimary pump
Chiller
Stratified Chilled Water System
![Page 50: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/50.jpg)
30 40 50 60 70
-5
-10
-15
Bottom -20
Top 0
Depth of tank, ft
Temperature, °F
Thermocline
Temperature Stratification
![Page 51: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/51.jpg)
Vent
Pressure sustainingand check valve
StorageWarm
Cool
Constant volumeprimary pump
Chiller
Distributionpump
Primary pump
Load
Transfer PumpDirectioncontrolvalves
Use of Pressure Sustaining Valves
![Page 52: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/52.jpg)
Load
T
Vent
Pressure sustainingand check valve
StorageWarm
Cool
Variable volumeprimarypump
Constant volumeprimary pump
Chiller
T
Heat Exchanger
Variable volumesecondarypump
Incorporating Heat Exchangers
![Page 53: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/53.jpg)
Section1
Section2
Section3
Section4
Ice harvesterchiller
Load
Chilled water pump
Ice waterrecirculationpump
Ice Harvesting System
![Page 54: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/54.jpg)
Charging ModeDischarging Mode
External Melt Ice Storage
![Page 55: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/55.jpg)
Ice
WaterIceCold glycol Warm glycol
Charging Mode Discharging Mode
Encapsulated Ice StorageCharge and Discharge Modes
![Page 56: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/56.jpg)
Tons
Time of Day
Cooling load (met by storage)
ChargingStorage
ChargingStorage
Chiller meets load directly
Chiller on
Chiller off
Full Storage Strategy
![Page 57: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/57.jpg)
Tons
Time of Day
Cooling load(met by storage)
ChargingStorage
ChargingStorage
Cooling load(met by chiller)
Chiller runs continuously
Partial Storage - Load Leveling
![Page 58: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/58.jpg)
Tons
Time of Day
(met by storage)ChargingStorage
ChargingStorage
(met by chiller)
Cooling load
Reduced on-peak demand
Partial Storage - Demand Limiting
![Page 59: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/59.jpg)
Production Source - Water Source Heatpumps
• Growing market segment• System temperature range 40 - 90 °F• Energy added below 40 °F (heat)• Heat removed above 90 °F (cooling
tower)
![Page 60: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/60.jpg)
Air Coil(Evaporator)
CoolAir Compressor
Reversing Valve
Capillary
Air Conditioner Cooling
Air Coil(Condenser)
WarmAir
Reversing Valve
Capillary
Air Conditioner Heating
Water Coil(Evaporator)
Water Coil(Condenser)
System Water Supply
Return
Compressor
RefrigerantLoop
Heat Pump Cycles - Water Source
![Page 61: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/61.jpg)
Design Considerations
• Use slow closing two-way valves for each zone
• Good system balance required• Use staged c/s or v/s pumps• Use with cooling towers and GPX• Use with closed circuit cooling towers
![Page 62: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/62.jpg)
Water SourceHeat Pump
Water SourceHeat Pump
Water SourceHeat Pump
Water SourceHeat Pump
Water SourceHeat Pump
Water SourceHeat Pump
Water SourceHeat Pump
Water SourceHeat Pump
Water SourceHeat Pump
BufferTank
( Optional )
Compression Tank
GasketedPlate HeatExchanger
CoolingTower
Heat Pump-Water Source Schematic
![Page 63: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/63.jpg)
Closed Circuit CoolerHeat Rejecter
Water SourceHeat Pump
Water SourceHeat Pump
Water SourceHeat Pump
Water SourceHeat Pump
Water SourceHeat Pump
Water SourceHeat Pump
Water SourceHeat Pump
Water SourceHeat Pump
Water SourceHeat Pump
BufferTank
( Optional )
Compression Tank
Heat Pump-Water Source Schematic
![Page 64: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/64.jpg)
Comments?Questions?
Observations?
![Page 65: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/65.jpg)
Large Chilled Water System Design Seminar
Variable Volume Distribution
![Page 66: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/66.jpg)
Variable flow through coil Constant flow through system
Three Way Valve
Variable flow through coil Variable flow through system
Two Way Valve
![Page 67: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/67.jpg)
Three-Way Valve Systems
• Low return temperatures• Balance problems• Increased flow at part load• Extra chillers to provide flow at low t• Chillers operate at high kW/ton
![Page 68: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/68.jpg)
CHILLER
CHILLER
Two-Way Valve System with Chiller BypassA
![Page 69: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/69.jpg)
We want:a. variable volume, to save pumping
costs at part load,b. constant flow through the chiller to
protect it.
A Solutiona. constant flow primary system for the chillersb. variable flow secondary system for the load
A Problem
![Page 70: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/70.jpg)
CHILLER
CHILLER
CHILLER
Return
Primary-SecondaryCommon Pipe
SupplyPrimary Loop
Production
Secondary LoopDistribution
Primary-Secondary Terms
![Page 71: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/71.jpg)
Fundamental Idea
SecondaryPump
Tee“A”Primary
Pump
Tee“B”
Low pressure drop in the “common pipe”
![Page 72: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/72.jpg)
Primary-Secondary Pumping
The idea is based on:
– Conservation of Mass
– Conservation of Energy
![Page 73: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/73.jpg)
50 GPM100 GPM
50 GPM
Law of the Tee: Diversion
![Page 74: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/74.jpg)
40 GPM60 GPM
100 GPM
Law of the Tee: Mixing
![Page 75: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/75.jpg)
No Secondary Flow
100 GPM @ 45°F
SecondaryPump
Off
A B100 GPM @ 45°F 100 GPM @ 45°F
PrimaryPump
![Page 76: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/76.jpg)
Primary = Secondary
100 GPM @ 45°F0 GPM
Pump On
A B
100 GPM @ 45°F 100 GPM @ 55°F
100 GPM @ 55°F
![Page 77: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/77.jpg)
Primary > Secondary
Pump On
A B
Mixing at Tee B
100 GPM @ 45°F
50 GPM @ 45°F
100 GPM @ 50°F
50 GPM @ 55°F
50 GPM @ 45°F
![Page 78: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/78.jpg)
Pump On
A B
Mixing at Tee A
100 GPM @ 45°F 100 GPM @ 55°F100 GPM @55F
200 GPM @ 50°F 200 GPM @ 55°F
Primary < Secondary
![Page 79: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/79.jpg)
Two-way Valve
Control Valve in Secondary
![Page 80: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/80.jpg)
Primary-Secondary Pumping
CHILLER
CHILLER
CHILLER
Return
Primary-SecondaryCommon
SupplyPrimary Loop
Production
Secondary LoopDistribution
![Page 81: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/81.jpg)
Common Pipe Design Criteria
• Use the flow of the largest chiller– Chiller staging at half of this flow is
common• Head loss in common <1 1/2 ft
– Distribution pipe size is often used where reductions would be inconvenient
• Three pipe diameters between tees– Excessive length increases total head loss
• Low velocities in system piping
![Page 82: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/82.jpg)
Return
Supply
PumpController
SecondaryConstant Speed
Pumps
Common
Chiller 3
Chiller 2
Chiller 1
Design of the Common Pipe
10 dia.
![Page 83: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/83.jpg)
Common Pipe Configurations
A B
C D
![Page 84: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/84.jpg)
Head
F1 F2 F3
H1H2
H3
Flow
Control ValvesClosing
Control ValvesOpening
Secondary System Curve
![Page 85: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/85.jpg)
From Loads
Common
To Loads
Production
Secondary Pumps1500 gpm each
Distribution
Chiller 2, off
Chiller 1, on
1500 gpmeach
45F
Typical System
![Page 86: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/86.jpg)
Common -- No Flow
SecondaryPumps
1500
1500
1500 15000
CHWS Temp45oF
CHWR Temp55oF
ECW Temp55oF
1500
Chiller 2, off
Chiller 1, on
Production = Distribution
![Page 87: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/87.jpg)
Common -- 500
SecondaryPumps
1500
2000
1500 20000
CHWS Temp47.5oF
CHWR Temp55oF
ECW Temp55oF
Mixing (1500 @ 45) + (500 @ 55)
Chiller 2, off
Chiller 1, on
2000
Distribution > Production
![Page 88: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/88.jpg)
>1500 GPM
ReturnCommon
Supply
>1500 GPM
0 GPM
>1500 GPM@ 47.5oF
>1500 GPM@ 55oF
Be Careful!
Chiller 2, off
Chiller 1, on
Check Valve in Common?
![Page 89: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/89.jpg)
StepFunction
LinearFunction
Return
Primary/SecondaryCommon
Supply
Production
Distribution
Chiller 3
Chiller 2
Chiller 1
What can we do?
![Page 90: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/90.jpg)
0-10 30-40 60-70 90-1000
5
10
15
20
25
30
0-10 30-40 60-70 90-100
% T
ime
% Load
Typical Load Profile
![Page 91: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/91.jpg)
Chiller 2, 60%
Chiller 1, 40%
% Load
% Time
100
80
60
40
20
100755025
Chiller 1
Chiller 2
1
1 2 2
Multiple Chillers
![Page 92: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/92.jpg)
What else can we do?Reset Supply Temperature
• Lower chiller set point when mixing occurs to maintain a constant temperature to the system.– Allows us to mix colder water and maintain supply
temperature to secondary. (coils)• Expect increases in cost of chiller operation at
lower set point: 1-3% per degree of reset.• Adds to control complexity.• Delays start of the next chiller.
![Page 93: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/93.jpg)
Common -- 900
SecondaryPumps
3000
2100
15002100
1500
CHWS Temp45oF
CHWR Temp55oF
ECW Temp52oF
Mixing (2100 @ 55) + (900 @ 45)
(Flow in GPM)
P/S Chiller Bridge - Front Loaded Common
Chiller1, on
Chiller 2, on
Production > Distribution
![Page 94: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/94.jpg)
“Loading” a Chiller
• A chiller is a heat transfer device. Like most equipment, it is most efficient at full load.
• To “load” a chiller means:– Supply it with its rated flow of water– Insure that water is warm enough to permit
removal of rated Btu without freezing the water
![Page 95: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/95.jpg)
Chiller Performance Curve1.1
20 30 40 50 60 70 80 90 10010
1.0
0.9
0.8
0.7
0.6
0.5
KW
per Ton
Percent Load
![Page 96: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/96.jpg)
0-10 30-40 60-70 90-1000
5
10
15
20
25
30
0-10 30-40 60-70 90-100
% T
ime
% Load
Typical Load Profile
![Page 97: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/97.jpg)
Chiller 2, 60%
Chiller 1, 40%% Load
% Time
100
80
60
40
20
100755025
Chiller 1
Chiller 2
1
1 2 2
60/40 Chiller Split to Help Minimize Low Part Load Operation
![Page 98: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/98.jpg)
% Load
% Time
100
80
60
40
20
100755025Chiller 1
orChiller 2
Chiller 3
Chiller 1and
Chiller 2
Chiller 1 or Chiller 2and
Chiller 3
Chiller 2, 40%
Chiller 1, 40%
Chiller 3, 60%
Three Unequally Sized Chillers
![Page 99: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/99.jpg)
% Load
Time
Approaching Flow = Load
![Page 100: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/100.jpg)
% Load
% Flow
100755025
100
75
50
25
Ch 1Ch 2 Ch 3 Ch 4
Ch 1 Ch 2 Ch 3
Ch 1 Ch 2
Ch 1
Applying a Variable Speed Chiller
![Page 101: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/101.jpg)
From loads
Common
To Loads
Chiller 3
Chiller 2
Chiller 1
Back Loaded Common
![Page 102: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/102.jpg)
Common0 Flow
SecondaryPumps
1500
CHWS Temp45oF
CHWR Temp55oF
Chiller 2, off
Chiller 1, on
1500
1500
15001500
Production = Distribution
![Page 103: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/103.jpg)
Common500 gpm
SecondaryPumps1500
2000
1500 20000
CHWS Temp47.5oF
CHWR Temp55oF
500
Mixing (1500 @ 45) + (500 @ 55)
500
Chiller 1, on
Chiller 2, off
Distribution > Production
![Page 104: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/104.jpg)
Common900
SecondaryPumps1500
2100
1500
2100
1500 GPM@ 49oF
CHWS Temp45oF
CHWR Temp55oF
Mixing (900 @ 45) + (600 @ 55)
900 600
900 GPM@ 45oF
600 GPM@ 55oF
1500 GPM@ 55oF
Chiller 2, on
Chiller 1, on
Production > Distribution
![Page 105: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/105.jpg)
Return
Supply
PumpController
SecondaryPumps
Primary-SecondaryCommon
Chiller 3
Chiller 2
Free Cooling
Maximize Free Cooling
![Page 106: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/106.jpg)
Return
Supply
PumpController
SecondaryPumps
Primary-SecondaryCommon
Chiller 3
Chiller 2
Chiller 1
Primary-Secondary System
![Page 107: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/107.jpg)
BHP
125
100
75
50
25
150
25 50 75 100
Design Coil Flow%
Primary Pumps = V/V
Secondary Pumps +
Constant Flow Primary Pumps, only
Pump Horsepower Comparison
![Page 108: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/108.jpg)
2012 ASHRAE Handbook - HVAC Systems and Equipment, p 44.11
![Page 109: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/109.jpg)
% Flow
90
80
70
60
50
40
30
20
10
0 10 1009080706050403020
100
110
120
130
140
150
BaseDesignHP %
% Full Load(Design) HP
Pump Over-headed by 150%Constant Flow, C/S Pump(3 Way Valve)
Constant Flow, C/S Pump(3 Way Valve)
C/S Pump(2 Way Valve)
Pump Head Matchedto System @Design Flow
Constant vs Variable Volume
![Page 110: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/110.jpg)
0
50
100
150
200
250
300
350
0 1000 2000 3000 4000 5000 6000 7000 8000 9000
Pipe Length, Feet
Yearly Operating C
ost x $1000
c/s @ 1.0
c/s @ 1.25
c/s @ 1.50
c/s @ 2.0
Impact of Piping Length and Overheading
![Page 111: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/111.jpg)
Always Size the Pump to the System!
But...• Uncertainties
– Coils– Control valves– Primary data
• Lead times
![Page 112: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/112.jpg)
Dealing With an Overheaded Pump
• Throttle at the discharge valve– Limits on the valve
• Flow balance & trim pump impeller– Required by ASHRAE/IES 90.1
![Page 113: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/113.jpg)
Additional Concerns
• Pump Protection at minimum flow
• Chiller Staging and De-staging instrumentation.
![Page 114: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/114.jpg)
Pump Protection
Minimum recommended flow from ESP Plus = 900 gpm
![Page 115: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/115.jpg)
Bypass Options1. Establish a minimum flow equal to or greater than
the minimum required to protect the pump.2. Install a bypass at the end of the mains with a
balance valve to set minimum flow.3. Install a bypass at ends of zones.4. In retrofits, leave a three way valve at the end of the
system.5. Use P or flow sensing to open pump bypass only
when needed.6. V/S pumps are not as big a problem because of
lower head at reduced flow.
![Page 116: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/116.jpg)
6
System Bypass Options
Return
Supply
PumpController
SecondaryConstant Speed
Pumps
PrimarySecondaryCommon
Chiller 3
Chiller 2
Chiller 1
2
5
3
![Page 117: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/117.jpg)
From Loads
Common
To LoadsProduction
Secondary/Pumps
Distribution
Chiller 2, off
Chiller 1, on
FP
FSTS-S
TS-RTP-R
TP-S
Chiller Staging Instrumentation
![Page 118: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/118.jpg)
Common Pipe Flow Indication
From LoadsCommon
To Loads
Production
Secondary/Pumps
Distribution
Chiller 2
Chiller 1 Flow
Switches
![Page 119: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/119.jpg)
Comments?Questions?
Observations?
![Page 120: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/120.jpg)
Large Chilled Water Design SeminarVariable Speed Pumping
![Page 121: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/121.jpg)
Why variable speed?
1. When should I use it?2. How does it work?3. What about variable primary flow?
![Page 122: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/122.jpg)
Typical operating load profile
2% 3%5%
15%
20%
30%
15%
5%3% 2%
![Page 123: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/123.jpg)
Bell & Gossett 70V1970s
![Page 124: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/124.jpg)
![Page 125: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/125.jpg)
Adjustable Frequency Drives
• Rectifier section– converts AC to DC– several varieties available
• Inverter section– forms a synthetic sine wave– several varieties available– maintains a controlled frequency/voltage ratio
• Requires an automatic control system• Adds to the initial cost of the system
![Page 126: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/126.jpg)
Affinity Laws
1. Capacity varies as the RPM change ratio:
FLOW 2 = FLOW 1 ( SPEED 2 / SPEED 1)
2. Head varies as the square of the RPM change ratio:
HEAD 2 = HEAD 1 (SPEED 2 / SPEED 1)2
3. Brake horsepower varies as the cube of the RPM change ratio:
BHP 2 = BHP 1 (SPEED 2 / SPEED 1)3
![Page 127: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/127.jpg)
Affinity Laws for Centrifugal Pumps
0
1020
3040
50
6070
8090
100
0 10 20 30 40 50 60 70 80 90 100
Flow/Speed, Percent
Perc
ent
FlowHeadHorsepower
![Page 128: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/128.jpg)
Theoretical Savings
% H
ead
% B
HP
% Design Flow
120
110
100
90
80
50
40
30
20
10
70
60
120
110
100
90
80
50
40
30
20
10
70
60
0 0
Pump Curves 100% Speed
90%
80%
70%
60%
50%
40%30%
Head
FlowBHP
10 20 30 40 50 60 70 80 90 1000
HP Draw
Design
Head
![Page 129: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/129.jpg)
P Sensor/Transmitter25 Ft. Head
Required Differential Pressure
![Page 130: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/130.jpg)
System Curve& V/S Control System
Flow
piping headloss curve
Distribution
Pum
p TDH
Overall system curve
Hea
d 80
60
40
20
110
0200 400 600 800 1000 1200 1400 16000
100
Set Point25 FT Differential Head Maintained Across Load
(Set Point)
![Page 131: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/131.jpg)
Effect of Constant* Set Point
piping headloss curve
Distribution
Pum
p TDH
Overall system curve
Head
80
60
40
20
110
0200 400 600 800 1000 1200 1400 16000
Flow
100
Control curve Set point,25 FT
As the valve closes, the pump slows down
*What’s Constant?
![Page 132: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/132.jpg)
AB
Q1Q2Flow, Q (gpm)
Head, H (feet)
PumpInitial Speed
Decrease in Heat Load Results in Troom < T set pointCauses Two Way Valves to Throttle Flow
Control Curve
Pipe, FittingFriction Loss
![Page 133: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/133.jpg)
AB
Q1Q2Flow, Q (gpm)
Head, H (feet)
Pump Curve
Control Curve
Decrease in Pump Speed Reduces Flow, Reduces Error
Speed 1
Speed 2
C
Q3
Pipe, FittingFriction Loss
![Page 134: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/134.jpg)
System Operation on Control Curve at Lower Speed
AB
Q1Flow, Q (gpm)
Head(ft) Pipe, Fitting
Friction Loss
Control CurveSpeed 1
Final Speed C
Q4
![Page 135: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/135.jpg)
Return
CHILLER
CHILLER
CHILLER
Supply
Variable Head Loss
Constant Head Loss
PumpController
Adjustable Freqy. Drives
Variable vs Constant Head Loss
![Page 136: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/136.jpg)
Percent D
esign BH
P
% Flow
90
80
70
60
50
40
30
20
10
0 10 1009080706050403020
100 C/S, Constant Flow System Pump Head Matched toSystem at Design Flow
C/S, Variable FlowV/S, 0% Variable Hd Loss, 100% Constant Hd
V/S, 25% Variable Hd Loss, 75% Constant Hd
V/S, 50% Variable Hd Loss, 50% Constant Hd
V/S, 75% Variable Hd Loss, 25% Constant Hd
V/S, 100% Variable Hd Loss, 0% Constant Hd
Base
Variable Head Loss Ratio
![Page 137: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/137.jpg)
Variable Head Ratio w/ Overheading
90
80
70
60
50
40
30
20
10
0 10 1009080706050403020
100
110
120
130
140
150
BaseDesignHP %
% Full Load(Design) HP
Pump O’Headed by 150%Constant Flow, C/S Pump(3 Way Valve)
Constant Flow, C/S Pump
(3 Way Valve)
C/S Pump(2 Way Valve)
Pump HD Matchedto System @Design Flow
* 25/75 Means:25 % Variable HD Loss75 % Constant HD Loss
![Page 138: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/138.jpg)
120
110
100
90
80
50
40
30
20
10
70
60
0100 200 300 400 500 600 700 800 900 10000
100 %
90 %
80 %
70 %
60 %
50%
40 %30 %
80 %85 %80 %70 %60 %50 %
85 %
% Speed Curves
Constant Efficiency Curve
% EfficiencyH
ead,
Fee
t
GPM
V/S Curves
![Page 139: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/139.jpg)
120
110
100
90
80
50
40
30
20
10
70
60
0100 200 300 400 500 600 700 800 900 10000
100 %
90 %
80 %
70 %
60 %
50%
40 %30 %
80 %85 %80 %70 %60 %50 %
85 %
% Speed Curves
Constant Efficiency Curve
% EfficiencyH
ead,
Fee
t
GPM
Efficiency Changes
![Page 140: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/140.jpg)
Minimum Drive Speed120
110
100
90
80
50
40
30
20
10
70
60
0100 200 300 400 500 600 700 800 900 10000
100 %
90 %
80 %
70 %
60 %
50%
40 %30 %
80 %85 %80 %70 %60 %50 %
85 %
% Speed Curves
Constant Efficiency Curve
% Efficiency
Hea
d, F
eet
GPM
![Page 141: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/141.jpg)
Return
CHILLER
CHILLER
CHILLER
Supply
Variable Head Loss
Constant Differential Head Loss
PumpController
Adjustable Freqy. Drives
Multiple Pump System Staging
![Page 142: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/142.jpg)
Control Curve
Pump 1
Pumps 1 & 2 Pumps 1, 2 & 3
1770 RPM
600 RPM 900 RPM1150 RPM
1450 RPM
Parallel V/S Operation
![Page 143: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/143.jpg)
Set Point (Input Signal)
Technologic™ Pump
Controller
Adjustable Frequency
Drive (Controlled Device)
SystemSensor/ Transmitter
3f , 60 Hz Power (Control Agent)
3f, Variable Frequency Variable Voltage
Feedback Signal
Controlled Variable
Set Point +/- error
Variable Speed Pumping Equipment
![Page 144: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/144.jpg)
The Controlled Variable Determines the Type of Sensor
Pressure
Differential Pressure
Differential Temperature
Flow
••••• •••••
Pump Controller
Temperature
4-20 ma
signal
![Page 145: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/145.jpg)
Set Point (Input Signal)
Technologic™ Pump
Controller
Adjustable Frequency
Drive (Controlled Device)
SystemSensor/ Transmitter
3f , 60 Hz Power (Control Agent)
3f, Variable Frequency Variable Voltage
Feedback Signal
Controlled Variable
Set Point +/- error
![Page 146: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/146.jpg)
Technologic™ Pump Controller
• Controls pumps and drives– Accept set point, analyze sensor input– PID function– Pump staging– Pump alternation
• Recognize and react to component failure• Provide message display• Central management system link• Safeguard system
![Page 147: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/147.jpg)
PID Control
• Eliminates offset from set point• Allows for timely speed change• Handles large, sudden disturbances• Prevents oscillation and over-damping
![Page 148: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/148.jpg)
Set Point (Input Signal)
Technologic™ Pump
Controller
Adjustable Frequency
Drive (Controlled Device)
SystemSensor/ Transmitter
3f , 60 Hz Power (Control Agent)
3f, Variable Frequency Variable Voltage
Feedback Signal
Controlled Variable
Set Point +/- error
![Page 149: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/149.jpg)
Adjustable Frequency Drive
Constant Voltage & Frequency
Power
Rectifier Section
Direct Current
Inverter Section
Variable Voltage & Frequency
Power
Pump Motor
Some important issues: Rectifier and Inverter Design Drive Efficiency RFI and EMI Noise Audible Noise Size and CostManual drive bypass
![Page 150: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/150.jpg)
0
20
40
60
80
100
120
0 20 40 60 80 100
Design Speed, %
Effic
ienc
y, %
Currently AvailableAFDsTypical Older AFDs
Other Types
Typical Efficiency RangeVariable Speed Drives
![Page 151: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/151.jpg)
Pump and Motor
![Page 152: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/152.jpg)
The Pump
• Minimum Flow• Minimum Speed• “Inverter Duty”
Motors• Motor Couplers
![Page 153: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/153.jpg)
Maintaining Minimum Flow120110
100
90
80
50
40
30
20
10
70
60
010 20 30 40 50 60 70 80 90 1000
% Flow
Hea
d100 % Speed
30% Speed
![Page 154: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/154.jpg)
EPDM couplers on variable-speed pumps
![Page 155: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/155.jpg)
Failed Hytrel Coupler from a Variable Speed Pump
![Page 156: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/156.jpg)
Variable Flow Through
The Evaporator
![Page 157: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/157.jpg)
Return
CHILLER
CHILLER
CHILLER
Supply
Variable Head Loss
Constant Differential Head Loss
PumpController
Adjustable Freqy. Drives
Primary-Secondary System
![Page 158: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/158.jpg)
Primary-Secondary
• Common Practice.
• Why?
– Protection.
• Nuisance shutdowns.
• Freezing.
• Costly downtime.
![Page 159: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/159.jpg)
Variable Primary Flow
AFD AFD AFD
CHILLER
CHILLER
CHILLER
Flow Meter, option
ModulatingValve
Two-position Control Valves
DP
Sensor
Controller
DP
Sen
sor D
P SensorD
P S
enso
r
![Page 160: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/160.jpg)
What’s different?• Primary pumps only • Flow meters or p sensors at each
chiller.• Two-position isolation valves at each
chiller• Minimum flow bypass with a modulating
control valve.• “Smarter” controller.
![Page 161: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/161.jpg)
Alternative #1
• Minimum Flow Bypass at Chillers–Minimum Chiller Flow
–Minimum Pump flow
• Ganged Pumps
![Page 162: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/162.jpg)
DPSENSOR
FLOW METER
DPSENSOR
DPSENSOR
DPSENSOR
DPSENSOR
AFD AFD AFD
SIGNALS TO TECH
SIGNAL TO TECH
SIGNAL TO TECH
SIGNAL TO TECH
NOTE:ALL SENSOR SIGNALS WIRED TO TECHNOLOGIC 5500
BYPASS: FOR SYSTEMS WITH EXTENDED LIGHT LOADS/WEEKEND SHUTDOWNS. SET BALANCE VALVE FOR LOW FLOW TO REDUCE THERMAL STRATIFICATION AND ALLOW QUICK START UP AFTER SHUT DOWN.
T
T
FFF
SIGNALS TO TECH
SIGNALS TO TECH
F
T
FLOWMETER/TRANSMITTER
TEMPERATURE SENSOR
ISOLATION VALVE
CHECK VALVE
CHILLER CHILLER CHILLER
SUPPLY
RETURN
TDV TDV TDV
![Page 163: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/163.jpg)
Monitoring Chiller Flow
P sensors - Technologic controller ensures the chiller is in proper working condition by monitoring each working chiller’s differential pressure. Flow through the chiller is calculated using the values defined in the user setup.
OR
Flow sensors - Technologic controller ensures the chiller is in proper working condition by monitoring each working chiller’s flow rate.
![Page 164: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/164.jpg)
Technologic 5500
• Initial programming is crucial.
• Must use accurate data from the chiller manufacturer.
• Start-up coordination should include the BMS too.
![Page 165: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/165.jpg)
Technologic 5500 Control Variables
1. Monitor zone differential pressure sensors, compare actual values to the required set points.
• Pump speed is modulated to maintain set point.
• Pump staging will occur as required to meet set point.
Control sequence is exactly as described earlier.
![Page 166: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/166.jpg)
Technologic 5500 Control Variables2. Determine if the minimum flow requirements are being met for all working chillers.
Prevents freeze-up or chiller low-flow trips
If chiller flow is too low, controller opens minimum flow bypass valve in programmed increments. Size the valve for system p.
“Requests” de-staging action from the chiller control system or BMS.
Allows for operator intervention, decision making.
Required by code in some areas.
Ganged pumps allow operation of two chillers with one pump.
![Page 167: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/167.jpg)
Technologic 5500 Control Variables3. Monitors chiller flow rate to prevent operation above the maximum flow for the chillers and the pumps.
Excess chiller flow generates a request to stage on an additional chiller. Minimum flow bypass valve is closed.
Operator or BMS intervention required.
Ganged pumps allow operation of one chiller, two pumps.
Optional system flow meter provides end-of-curve protection for the pumps
![Page 168: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/168.jpg)
Alternative #2
• Bypass at End of System
• Minimum chiller flow
• Minimum pump flow
• Ganged Pumps
![Page 169: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/169.jpg)
DPSENSOR
FLOW METER
DPSENSOR
DPSENSOR DP
SENSORDP
SENSOR
AFD AFD AFD
SIGNALS TO TECH
SIGNAL TO TECH
SIGNAL TO TECH
SIGNAL TO TECH
NOTE:ALL SENSOR SIGNALS WIRED TO TECHNOLOGIC 5500
T
T
FFF
SIGNALS TO TECH
SIGNALS TO TECH
F
T
FLOWMETER/TRANSMITTER
TEMPERATURE SENSOR
ISOLATION VALVE
CHECK VALVE
SUPPLY
RETURN
TDV TDV TDV
CHILLER CHILLERCHILLER
![Page 170: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/170.jpg)
Alternative #2
• Minimum flow bypass valve is controlled to protect both the pumps and the chillers.– Pump requires >25% BEP flow– Minimum flow of largest chiller
• Size the bypass valve using the zone p.
• Best for systems with extended light loads or weekend shut-down.
![Page 171: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/171.jpg)
Alternative #3
• Primary pumps piped directly to chillers.
• More common in retrofit systems.
• Easier for applying un-equally sized chillers in parallel.
![Page 172: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/172.jpg)
DPSENSOR
FLOW METER
DPSENSOR
DPSENSOR
DPSENSOR
DPSENSOR
AFD AFD AFD
SIGNALS TO TECH
SIGNAL TO TECH
SIGNAL TO TECH
SIGNAL TO TECH
NOTE:ALL SENSOR SIGNALS WIRED TO TECHNOLOGIC 5500
BYPASS: FOR SYSTEMS WITH EXTENDED LIGHT LOADS/WEEKEND SHUTDOWNS. SET BALANCE VALVE FOR LOW FLOW TO REDUCE THERMAL STRATIFICATION AND ALLOW QUICK START UP AFTER SHUT DOWN.
T
T
FFF
SIGNALS TO TECH
SIGNALS TO TECH
F
T
FLOWMETER/TRANSMITTER
TEMPERATURE SENSOR
CHECK VALVE
ISOLATION VALVE
TDV TDV TDV
CHILLER CHILLER CHILLER
SUPPLY
RETURN
![Page 173: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/173.jpg)
Pump Selection• Equal size pumps.
– Redundancy.– Parts.– Maintenance.
• Unequal size pumps.– Control issues.– Flow issues.– Premature failure, large pump at low flow.
![Page 174: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/174.jpg)
Chiller Selection
• Equal size chillers.– Redundancy.– Parts.– Maintenance.
• Unequal size chillers.– Control issues.– Flow issues– Additional equipment.
![Page 175: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/175.jpg)
Design Considerations
• Size bypass for minimum flow of largest chiller.– Minimum building load?
• Size bypass modulating valve– for system p, if it’s installed near the chillers– for zone p, if it’s out in the system.
• Program the controller with the chiller p set points for minimum and maximum chiller flow.– Verify with chiller manufacturer.
![Page 176: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/176.jpg)
Design Considerations
• Sequence chillers based on p or temperature sensors.
• Use accurate, calibrated flow meter or p sensors at each evaporator
• Allow for operator training.– Initial– On-going
![Page 177: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/177.jpg)
Consider this design if:• System flow can be reduced by 30%.
• System can tolerate modest changes in water
temperature.
• Operators are well trained.
• Demonstrates a greater cost savings.
• High proportion of operating hours at:
– Part load.
– Full load with low entering condenser water.
![Page 178: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/178.jpg)
Turn-down Ratio• Chiller manufacturers publish 3 - 11 fps
evaporator velocity range (typically).• You may have to increase your
“acceptable head loss” targets, use more pump head.
• Nominal base of 7 fps desirable.• Variation of 1 to 2 fps.• Work with the manufacturer.
![Page 179: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/179.jpg)
Rate of Change*Maximum rate of flow change, % design flow per minute
Source Vapor Compression Absorption
#1 4-12 **
#2 20-30 2-5
#3 ** 30
#4 2 **
#5 ** 1.67
*Table 2-2ARTI-21CR/611-20070-01, 2004, Bahnfleth & Peyer** Information not provided
![Page 180: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/180.jpg)
Do not use if:
• Supply temperature is critical.
• Three-way valves are used throughout.
• Existing controls are old, inaccurate.
• Operators are unlikely to operate the
system as designed.
![Page 181: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/181.jpg)
Supply Water Temperature
• Dependant on :– System volume.– Rate of flow change.
• Application specific.• Consider thermal storage
![Page 182: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/182.jpg)
Operator Ability
• Within operator’s ability?.– Commercial buildings may not have well
qualified operators.• Training is mandatory.
– Initial– Periodic, in view of operator turnover.
![Page 183: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/183.jpg)
Start-Up & Shut-down• In systems that start-up and shut-down, it
may be advisable to anticipate, and avoid, rapid changes in flow as control valves all tend to act together.
• Control system, BMS, manual procedures.
• Use slow opening/closing valves at the chiller, 60-90 seconds.(?)
![Page 184: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/184.jpg)
Controls Complexity
• Additional controls for the chillers • Additional controls the pumps. • Pumps operate on flow, temperature, and P.
• Chiller P.
![Page 185: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/185.jpg)
Sensor Calibration
• Multiple sensors control:– Flow.– Temperature.– Delta p
• Maintenance.• Calibration.
![Page 186: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/186.jpg)
Summary• Evaluate all the options.
• Read some articles:– Variable Primary Flow CHW: Potential Benefits and Application Issues
by Bahnfleth and Peyer. Pennsylvania State University, ARTI-
21CR/611-20070-01
– Chilled Water System for University Campus by Stephen W. Duda, PE,
ASHRAE Journal May, 2006
• Another tool for the toolbox.
![Page 187: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/187.jpg)
Comments?Questions?
Observations?
![Page 188: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/188.jpg)
Large Chilled Water System Design Seminar
Primary-Secondary-Tertiary Pumping Systems
![Page 189: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/189.jpg)
CHILLER
CHILLER
Zone A
Zone B
Zone C
Variable Speed Pump
Primary-Secondary-Tertiary
![Page 190: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/190.jpg)
CHILLER
CHILLER
Zone AZone B Zone C
DP Controller
WRONG !
Direct Pumped Zones
![Page 191: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/191.jpg)
WRONG !
Zone A Zone BZone C
Automatic Flow ControlValve
T
Hard set valve
CHILLER
CHILLER
Constant Demand Zones
![Page 192: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/192.jpg)
CHILLER
CHILLER
Zone A
Zone B
Zone C
Variable Speed Pump
Primary-Secondary-Tertiary
RIGHT !
![Page 193: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/193.jpg)
Three Different Buildings• “A” has coils selected for 44°F.• “B” has coils selected for 45°F.• “C” has coils selected for 46°F.
• Therefore, the supply water temperature must be at least 44°F for “A”.
• But what about “B” and “C”?
![Page 194: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/194.jpg)
CHILLER
CHILLER
Zone A
Zone B
Zone C
Optional Variable Speed Pump
Primary-Secondary-Tertiarycan be even more useful
?
![Page 195: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/195.jpg)
T3
T1
LoadMV
Load MV
Load MV
Common T2
T4
ChilledWaterReturn
PumpedChilledWaterSupply
TertiaryZonePump
T2 T3 T4
Temperature Sensor Locations
T1
½” Circuit Setter
![Page 196: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/196.jpg)
T3
T1
LoadMV
Load MV
Load MV
CommonT2
T4
ChilledWaterReturn
PumpedChilledWaterSupply
TertiaryZonePump
Tertiary Bridge
Tertiary Bridge
![Page 197: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/197.jpg)
T3
T1
LoadMV
Load MV
Load MV
Common T2
T4
ChilledWaterReturn
PumpedChilledWaterSupply
TertiaryZonePump
T2 T3 T4
Temperature Sensor Locations
T1
![Page 198: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/198.jpg)
1. Permits operating at highest allowable zone temperature
2. Maximizes coil flow rate, good film coefficients
3. Maximizes flow rate through each control valve
4. Ensures good humidity control
5. Minimizes the amount of coil reheat
ADVANTAGES
![Page 199: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/199.jpg)
1. Temperature of return water is unknown
2. Temperature of return water to chiller may be too high
3. Will not recognize increased supply water temperature
DISADVANTAGES
![Page 200: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/200.jpg)
T3
T1
LoadMV
Load MV
Load MV
Common T2
T4
ChilledWaterReturn
PumpedChilledWaterSupply
TertiaryZonePump
T1 T2 T3 T4
T2 Operation
![Page 201: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/201.jpg)
1. Maintains chilled water return temperature at setpoint
2. Will not overload the chiller
ADVANTAGES
![Page 202: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/202.jpg)
1. No control of zone supply water temperature
2. Could lose humidity control
3. Will not recognize increased supply water temperature
DISADVANTAGES
![Page 203: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/203.jpg)
T3
T1
LoadMV
Load MV
Load MV
Common T2
T4
ChilledWaterReturn
PumpedChilledWaterSupply
TertiaryZonePump
T1 T2 T3 T4
T3 Operation
![Page 204: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/204.jpg)
1. There are no perceived advantages at this location
ADVANTAGES
![Page 205: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/205.jpg)
1. Little, if any, valve modulation unless it is set to close on sensing supply temperature lower than permissible in the zone
DISADVANTAGES
![Page 206: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/206.jpg)
T3
T1
LoadMV
Load MV
Load MV
Common T2
T4
ChilledWaterReturn
PumpedChilledWaterSupply
TertiaryZonePump
T1 T2 T3 T4
T4 Operation
![Page 207: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/207.jpg)
1. Maximizes coil flow rate
2. Ensures good humidity control
ADVANTAGES
![Page 208: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/208.jpg)
1. Temperature of return water is unknown
2. Temperature of return water to chiller may be too high
3. Will not recognize increased supply water temperature
DISADVANTAGES
![Page 209: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/209.jpg)
No single sensor location satisfies all design criteria
SO........
![Page 210: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/210.jpg)
T3
T1
LoadMV
Load MV
Load MV
Common T2
ChilledWaterReturn
PumpedChilledWaterSupply
TertiaryZonePump
T2 T3T1
Applying Zone Valve Controller
![Page 211: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/211.jpg)
1. Temperature control to the zone (T1 sensing).2. If T1 is satisfied, return water temperature to the chiller
plant (T2 sensing).3. Monitor secondary chilled water supply temperature
(T3 sensing) for temperature increase due to secondaryreturn water recirculation or temperature decrease due tochiller leaving water temperature reset.
4. Reference point for automatic reset and T (T2 - T3) control (T3 sensing).
Control Algorithm
![Page 212: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/212.jpg)
So what…?
• Satisfy zone cooling requirement at the maximum possible supply temperature
• Minimize secondary flow rate
• Optimize return water temperature
![Page 213: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/213.jpg)
Chiller P
lant
Secondary Pumps
TertiaryPump
TertiaryPump
TertiaryPump
3-way Valve Application
![Page 214: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/214.jpg)
Problems
• Bypass returns cold water to chillers, reduces system t.
• Linear valve characteristics can cause increased flow at part load.
• Balancing required in bypass pipe and coil-to-coil.
• High cost per ton at the chiller.
![Page 215: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/215.jpg)
T1MV
CommonT2
T3
Load
Load MV
Load MV
T2T1 T3
FlowMeter
SmallBy-Pass
Secondary Supply
Secondary Return
3-way Valve System
![Page 216: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/216.jpg)
T2 T2T2 T2
FlowMeter
T3Common
T3CommonCommon
T3
Zone SupplyTemperature
Chiller SupplyTemperature
TerminalUnit Control
Valve
TerminalUnit Balance
Valve
]e
Zone BiasControl Valve
Rolairtrol
Zone(Tertiary)
Pump
ReturnWater
Temperature
Zone 3Zone 1 Zone 2 Zone 4
Common
3D Valves
Distribution(Secondary)
Pumps
T1T1 T1T1
T3
Chiller
Chiller
Chiller
GPX
Multi-zone Application
![Page 217: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/217.jpg)
• Individual building temperature control• Static pressure isolation• Return water temperature control• Btu/hr totalization• Outdoor temperature reset• Independent operation
District Cooling Application
![Page 218: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/218.jpg)
• Independent pressure control
• HVAC fluid isolation
District Cooling Application with GPX
![Page 219: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/219.jpg)
T2 T2T2 T2
FlowMeter
T3Common
T3CommonCommon
T3
Zone SupplyTemperature
Chiller SupplyTemperature
TerminalUnit Control
Valve
TerminalUnit Balance
Valve
ZoneBalanceValve
Zone BiasControl Valve
Rolairtrol
Zone(Tertiary)
Pump
ReturnWater
Temperature
Zone 3Zone 1 Zone 2 Zone 4
3D Valves
T1T1 T1T1
T3
Chiller
Chiller
Chiller
GPX
VPF Application
![Page 220: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/220.jpg)
Comments?Questions?
Observations?
![Page 221: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/221.jpg)
Large Chilled Water System Design Seminar
Primary-Secondary Zone Pumping Systems
![Page 222: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/222.jpg)
CHILLER
CHILLER
Return
Supply
Zone A Zone B Zone C
Primary-Secondary Zone Pumping
![Page 223: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/223.jpg)
![Page 224: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/224.jpg)
Shared Piping
CHILLER
CHILLER
Return
Supply
Zone A Zone B Zone C
Shared Pipe
![Page 225: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/225.jpg)
CHILLER
CHILLER
Return
Supply
Zone A Zone B Zone C
Shared Pipe
Shared Piping
![Page 226: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/226.jpg)
CHILLER
CHILLER
Return
Supply
Zone A Zone B Zone C
1500 gpm 1500 gpm (1500 gpm)
Current = 1500Future = 3000
Current = 0Future = 1500
Current = 3000Future = 4500
Future Zone C
Flow :
Present and Future Piping
![Page 227: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/227.jpg)
Return
Supply
Zone A Zone B Zone C
(1500 gpm) (1500 gpm)
A1 A2 A3
B1 B2 B3
Pressure drop:A to A1+B to B1Present = 20.8’*Future = 45.2’
A
B
1500 gpm @ 80’
Zone A
4500 gpm*
4500 gpm*
Zone A Requirements
![Page 228: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/228.jpg)
Table 9-1 Zone A calculations
Zone A (A to A1 + B to B1) Future Flow @ 4500 gpm Present Flow @ 3000 gpmPipe Size 14” 14”Pressure Drop - ft / 100 ft 2.26 1.04Equivalent Length(supply & return) 1000 ft x 2 = 2000 ft 1000 ft x 2 = 2000 ftPressure drop 45.2 ft 20.8 ftZone pressure drop 80 ft 80 ftTotal pressure drop 125.2 ft 100.8 ftPump Selection @ 1500 gpm 1510-6G @ 56.4 hp = 75 hp* 1510-6G @ 45.8 hp = 60 hp*
Note: 15 hp additional for future requirements* Nominal horsepower motor for NOL pump
Zone A Calculations
![Page 229: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/229.jpg)
![Page 230: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/230.jpg)
Return
Supply
Zone A Zone B Zone C
1500 gpm @ 80’ (1500 gpm)
A1 A2 A3
B1 B2 B3
Pressure drop: Zone BAtoA1+ BtoB1 + A1toA2 + B1toB2Present =20.8’ 9.0’*Future = 45.2’ 33.4’
A
B
1500 gpm @ 80’
4500 gpm* 3000 gpm*
4500 gpm* 3000 gpm*
Zone B Requirements
![Page 231: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/231.jpg)
Table 9-2 Zone B calculations
Zone B(A1to A2+B1 to B2) Future Flow @ 3000 gpm Present Flow @ 1500 gpmPipe Size 12” 12”Pressure Drop - ft / 100 ft 1.67 0.45Equivalent Length(supply & return) 1000 ft x 2 = 2000 ft 1000 ft x 2 = 2000 ftPressure drop 33.4 ft 9.0 ftPrevious pressure drop 45.2 ft 20.8 ftZone pressure drop 80 ft 80 ftTotal pressure drop 158.6 ft 109.8 ftPump Selection @ 1500 gpm 1510-6G @ 71.4 hp = 100 hp* 1510-6G @ 49.6 hp = 60 hp*
Note: 40 additional hp required for future requirements* Nominal horsepower motor for NOL pump
Zone B Calculations
![Page 232: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/232.jpg)
Return
Supply
Zone A Zone B Zone C
1500 gpm @ 80’
A1 A2 A3
B1 B2 B3
Pressure drop: Zone CAtoA1+ BtoB1 + A1toA2 + B1toB2 + A2toA3+ B2toB3Present = 45.2’ + 33.4’ + 21.4’Future = Present
A
B
1500 gpm @ 80’ 1500 gpm @ 80’
4500 gpm 3000 gpm 1500 gpm
4500 gpm 3000 gpm 1500 gpm
Zone C Requirements
![Page 233: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/233.jpg)
Zone C (A2 to A3 + B2 to B3) Future Flow @ 1500 gpm Present Flow @ 0 gpmPipe Size 10”Pressure Drop - ft / 100 ft 1.07Equivalent Length(supply & return) 1000 ft x 2 = 2000 ftPressure drop 21.4 ftPrevious pressure drop(A to A2, B to B2)
78.6 ft
Zone pressure drop 80 ftTotal pressure drop 180.0 ftPump Selection @ 1500 gpm 1510-6G @ 82.7 hp = 125 hp*; Note: 50 hp more
than Zone A
Zone C Calculations
![Page 234: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/234.jpg)
Zone Pumping SummaryPresent Requirement Future Requirement
Summary Duty Pump Standby Pump Duty Pump Standby PumpZone A 1 @ 75 hp 1 @ 75 hp 1 @ 75 hp 1 @ 75 hpZone B 1 @ 100 hp 1 @ 100 hp 1 @ 100 hp 1 @ 100 hpZone C 1 @ 125 hp 1 @ 125 hp
2 @ 175 hp 2 @ 175 hp 3 @ 300 hp 3 @ 300 hpTotal 4 @ 350 hp 6 @ 600 hp
* Nominal horsepower motor for NOL pump
![Page 235: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/235.jpg)
0 0
Zone Pump A
Zone Pump B
Zone Pump C
Friction LossSupply Header
Friction LossReturn Header
LoadFriction
Loss
Pressure Diagram - Zone Pumped System
![Page 236: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/236.jpg)
Return
Supply
PumpController
AFDs
Chiller 3
Chiller 2
Chiller 1
3000 GPM 1500 GPM
3000 GPM1500 GPM
1500 GPM 1500 GPM
A
A1 A2
BB1 B2
A3
(1500 GPM)
B3
Primary-Secondary Equivalent
![Page 237: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/237.jpg)
Primary-Secondary pressure drop calculation:
Pipe Segment Pressure DropPresent, feet
Pipe Segment Pressure DropFuture, feet
A to A1 + B to B1 20.8 A to A1 + B to B1 45.2A1 to A2 + B1 to B2 9.0 A1 to A2 + B1 to B2 33.4A2 to A3 + B2 to B3 DNA A2 to A3 + B2 to B3 21.4Zone B 80.0 Zone C 80.0Total 109.8 Total 180
P-S Calculations
![Page 238: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/238.jpg)
Distribution pump selection:
Present = 3000 gpm @ 109.8 feet, increase impeller to 13.5” for future head requirements:2 @ VSCS 8x10x17L @ 111.0 hp 125 NOL1 @ VSCS 8x10x17L @ 111.0 hp 125 NOL, standby
Total 3 Pumps 375 NOL, Total
Future = 4500 gpm @ 180 feet:3 @ VSCS 8x10x17L @ 114.4 hp 375 NOL1 @ VSCS 8x10x17L @ 114.4 hp 125 NOL
Total 4 Pumps 500 NOL
P-S Calculations
![Page 239: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/239.jpg)
Comparison
• Zone Pumping– Present
• 350 hp
– Future• 600 hp
• P/S Pumping– Present
• 375 hp
– Future• 500 hp
![Page 240: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/240.jpg)
Primary-Secondary Zone Pumping Cautions
• Excessive initial horsepower
• Initial equipment investment
• Future considerations
• Reduced Horsepower
![Page 241: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/241.jpg)
Comments?Questions?
Observations?
![Page 242: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/242.jpg)
Large Chilled Water System Design Seminar
Variable Speed Sensor Selection and Location
![Page 243: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/243.jpg)
Return
Supply
PumpController
AFDs
DifferentialPressureSensorC
hiller 3
Chiller 2
Chiller 1
Direct Return Piped System
![Page 244: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/244.jpg)
Return
Supply
PumpControllerAFDs
Chiller 3
Chiller 2
Chiller 1
WRONG!SinglePointPressure Sensor
Single Point Pressure Sensor
![Page 245: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/245.jpg)
Head, FT
90
80
50
40
30
20
10
70
60
0200 400 600 800 1000 1200 1400 16000
Flow, gpm
1750 RPM(Maximum rpm)
1480 RPM(Minimum rpm)
Constant PressureDesign PointShut-off head
Control Curve Using Single Point Pressure Sensor
![Page 246: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/246.jpg)
Single Point Pressure Sensor in a CHW System
• A rise in the average water temperature results in a net expansion of the water.
• This “net expansion” volume flows into the compression tank, raising the system pressure.
• The pump slows down.
![Page 247: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/247.jpg)
What if?
Return
CHILLER
CHILLER
CHILLER
Supply
PumpController
P Sensor hereZone A Zone B Zone C
AFDs
![Page 248: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/248.jpg)
Sensor Across Mains At Pump
• What’s the set point?– It’s the greatest branch and distribution
piping head loss calculated at design flow. In other words…design head.
• What will the flow be in each zone?– Determined by the zone path CV
![Page 249: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/249.jpg)
Head, FT
90
80
50
40
30
20
10
70
60
0200 400 600 800 1000 1200 1400 16000
Flow, gpm
Maximum rpm
Minimum rpm
Design Point
Differential Pressure Sensorat the Pump
![Page 250: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/250.jpg)
Variable Head Loss Ratio
Percent D
esign BH
P
% Flow
90
80
70
60
50
40
30
20
10
0 10 1009080706050403020
100 C/S, Constant Flow System Pump Head Matched toSystem at Design Flow
C/S, Variable FlowV/S, 0% Variable Hd Loss, 100% Constant Hd
V/S, 25% Variable Hd Loss, 75% Constant Hd
V/S, 50% Variable Hd Loss, 50% Constant Hd
V/S, 75% Variable Hd Loss, 25% Constant Hd
V/S, 100% Variable Hd Loss, 0% Constant Hd
Base
![Page 251: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/251.jpg)
25’ Head
Coil or Valve?
P
![Page 252: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/252.jpg)
Return
Supply
Variable Head Loss
Constant Head Loss
PumpController
AFDs
DifferentialPressureSensorC
hiller 3
Chiller 2
Chiller 1
Maximizing Variable Head Loss
![Page 253: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/253.jpg)
CHILLER
CHILLER
CHILLER Pump
Controller
DP Sensor
Zone 120 ft
Zone 220 ft
AFDs
A B C D
EF
Control Area
![Page 254: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/254.jpg)
P AB+EF20FT
P Zone 120FT
P BC+DE20FT
P Zone 220FT
TDH = P AB + EF + BC + DE + P ZONE 2 = 60 FT
Pressure Drops in Piping (Table 11-1)
![Page 255: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/255.jpg)
Control Area Calculation
What pump head is required at:zero flow?full flow?less than full flow?
Table 11-2 Control Area CalculationFlow
Zone 1Flow
Zone 2FrictionLoss
AB+EF
FrictionLoss
Zone 1
PZone 1
FrictionLoss
BC+DE
FrictionLoss
Zone 2
PZone 2
TDH
0 gpm 600 gpm 5 0 40 20 20 20 45300 gpm 300 gpm 5 5 25 5 20 20 30600 gpm 0 gpm 5 20 20 0 0 20 25
0 gpm 0 gpm 0 0 20 0 0 20 20600 gpm 600 gpm 20 20 40 20 20 20 60
![Page 256: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/256.jpg)
0
10
20
30
40
50
60
0 100 300 500 600 900 1100 1200Flow, gpm
Head, FT
Lower LimitUpper LimitSingle Point
Control Area
![Page 257: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/257.jpg)
So What...?• Staging pumps in a closed loop HVAC
system by flow alone may not work because of different head requirements for a given flow.
• “Wire to water” pump efficiency calculations at part load depend heavily on the assumptions made about the nature and shape of the control curve.
![Page 258: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/258.jpg)
Single Sensor, Including Balance Valve Pressure Drop
Zone 125 ft
Zone 220 ft
AB (50)
E (10)F
C
D
![Page 259: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/259.jpg)
What do you mean...?
• The head loss across the coil and the wide open valve in zone 1 is 25 feet at full flow.
• If that’s true, then we need to add an extra 15 feet of head loss in the balance valve to insure adequate flow out to Zone 2 when the Zone 1 valve is wide open.
![Page 260: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/260.jpg)
Set Point, Zone 1, 40 ft
Flow Zone 1 Flow Zone 2 Friction Loss
AB+EF
Friction Loss
BC+DE
Head Required
Zone 2Setpoint -
Friction Loss
0 gpm 600 gpm 5 20 20 0
300 gpm 300 gpm 5 5 5 30
600 gpm 0 gpm 5 0 0 40
Excess head means wasted energy
![Page 261: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/261.jpg)
CHILLER
CHILLER
CHILLER Pump
Controller
DP Sensor
Zone 1 Zone 2
AFDs
A B C D
EF
Sensor Location
![Page 262: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/262.jpg)
Single Sensor in Zone 2
FlowZone 1
FlowZone 2
Friction LossAB+EF
Friction LossZone 1
Friction LossBC+DE
P Zone1,Available
P Avail -Friction Loss
Zone 1 0 gpm 600 gpm 5 0 20 40 40300 gpm 300 gpm 5 6.25 5 25 13.75600 gpm 0 gpm 5 25 0 20 - 5
Zone 1 requires 600 gpm at 25 ftZone 2 requires 600 gpm at 20 ft
Inadequate head for Zone 1
![Page 263: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/263.jpg)
Sensor in Zone 1
Flow Zone 1 Flow Zone 2 Friction LossAB+EF
Friction LossBC+DE
Head RequiredZone 2
Setpoint -Friction Loss
0 gpm 600 gpm 5 20 20 5300 gpm 300 gpm 5 5 5 20600 gpm 0 gpm 5 0 0 25
Zone 1 requires 600 gpm at 25 ftZone 2 requires 600 gpm at 20 ft
Inadequate flow in Zone 2
![Page 264: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/264.jpg)
What can we do...?In this system:• Single sensor in Zone 2 at 20 ft fails to
provide adequate flow only when – load in Zone 2 < 50% and – load in Zone 1 > 75%
• Is this a predictable, recurring situation?– manual adjustment– programming
• Add a second sensor
![Page 265: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/265.jpg)
Return
CHILLER
CHILLER
CHILLER
Supply
PumpController
DP Sensors
Zone A Zone B Zone C
AFDs
Applying Multiple Sensors
![Page 266: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/266.jpg)
Use Multiple Sensors?• Load
– Similarity– Priority– Diversity
• One building or several• Redundancy• First cost vs operating cost
![Page 267: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/267.jpg)
The “Active Zone”• Zone set points do not have to be the
same.• Technologic™ pump controller scans all
zones often, comparing process variable to set point in each case.
• Pumps are controlled to satisfy the worst case.
• What happens to the rest of the zones?
![Page 268: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/268.jpg)
Effect of Sensor Location
Zone 1 Zone 2
AB
EF
C
D
OR
![Page 269: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/269.jpg)
Multiple sensors, set point across Zone 1, = 25 FT and setpoint across Zone 2 = 20 FT, (Table 11-6)FlowZone
1
FlowZone
2
Friction LossAB+EF
MinimumReq’d
P Zone 1,
PZone1
Available
Friction LossBC+DE
MinimumReq’d
P Zone2
PZone 2
Available 0 600 5 0 40 20 20 20300 300 5 6.25 25 5 5 20600 0 5 25 25 0 0 25
Multiple Sensors & Setpoints
Row 1. Sensor 2 is controlling, Zone 1 is over pumped.Row 3. Sensor 1 is controlling, Zone 2 is over pumped.Total pump head required:
row 1 45 ftrow 2 30 ftrow 3 30 ft
![Page 270: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/270.jpg)
CHILLER
Return
Supply
Reverse Return Piped System
![Page 271: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/271.jpg)
Reverse Return Systems• If all the circuits are the “same length”,
will the pump still change speed?• Suppose a coil with a high p
requirement and another with a lower p requirement are served by the same reverse return piping system. OK?
• If the coils are serving different sides of the building, could we have a problem?
![Page 272: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/272.jpg)
CHILLER
CHILLER
Return
Zone A Zone CZone B
Tertiary Piped System
![Page 273: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/273.jpg)
CHILLER
CHILLER
Return
Supply
Zone A Zone B Zone C
Zone Piped System
![Page 274: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/274.jpg)
Summary• Give priority to the needs of the branch.• The rule of sensor location is simple and easy
to apply: – If you have to use a single sensor, put it across
the critical branch.– What’s the “critical branch”?– It’s the same one that determined the pump head.
• As we’ve seen, the analysis is more important than the “rule”.
![Page 275: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/275.jpg)
Comments?Questions?
Observations?
![Page 276: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/276.jpg)
Large Chilled Water System Design Seminar
Achieving Hydronic System Balance
![Page 277: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/277.jpg)
Systems Approach
M
Load
Source
Air ManagementDistribution
Verification
Control
Philosophy
![Page 278: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/278.jpg)
Systems Approach
• All components work together as “team”– Components interact and work as well as we
understand them
• A collection of mismatched components will not perform as expected
• Owner, engineer, architect, contractor, and operators are part of the system too!
![Page 279: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/279.jpg)
Hydronic Balancing
• We worry about balance because:– Load calculations are approximate– Piping circuitry analysis is approximate– Control valve selection is approximate– Approximations will lead to underflow and
overflow situations• Results of overflow or underflow
– Design Dt cannot be achieved– Supply temperature controller hunts (?)– Sequence of operation can be upset.
![Page 280: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/280.jpg)
For example:
• Published by ASHRAE & Hydraulic Institute
• Darcy-WeisbachEquation.
Add 15%!
![Page 281: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/281.jpg)
• It’s test, adjust & balance• Test: The system, now built, is verified in
operation to perform to the expected level.– What do we measure?
• temperature, flow, pressure drop, energy consumption….
– What do we test with?– Can we test with what is installed?– Can we obtain accurate readings?
What Is Balancing?
![Page 282: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/282.jpg)
• What level of adjustment, and for what purpose?– Create comfort conditions– Minimize energy consumption– Prevent equipment damage
• How do we adjust?
Adjust: tested in operation, the system is found lacking and needs fine tuning.
Adjust
![Page 283: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/283.jpg)
Balance
• Balance is often interpreted to mean ±10% of design flow.
• This generalization may or may not yield satisfactory heat transfer required for comfort conditions
![Page 284: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/284.jpg)
Redefining Balance
• Evaluate System Operation– If the goal is occupant comfort, then heat
transfer becomes the key concern.– We control heat transfer as a sensible
temperature control process between controller, control valve and coil
– Analysis should account for interaction of all key components, and how they affect the rest of the system
![Page 285: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/285.jpg)
Balanced Hydronic Systems
• All terminals receive enough flow to produce satisfactory heat transfer (97.5% - 102.5%)
• At design conditions, all terminals receive satisfactory flow with the pump in a specified range of operation
• Under temperature control modulation to match load, circuit flow does not exceed design flow accuracy
![Page 286: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/286.jpg)
Chilled Water Coil Flow vs. Heat Transfer
0%
20%
40%
60%
80%
100%
120%
0% 20% 40% 60% 80% 100% 120% 140% 160% 180% 200%0
5
10
15
20
25
30
35
40
45Total
Sensible
Latent
• 30”H X 46”W •10 FPI / 4 Row •30 GPM / 10°∆T •85° DB/ 71° WB Ent •45° EWT •15 Circuits •3/8” Tube •4000 CFM •Nominal 10 Ton Rating
% H
eat E
mis
sion
% Flow
Wat
ersi
de ∆
T (°
F)
![Page 287: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/287.jpg)
Chilled Water Coil Flow vs. Emission
• 30”H X 46”W •10 FPI / 4 Row •30 GPM / 10°∆T •85° DB/ 71° WB Ent •45° EWT •15 Circuits •3/8” Tube •4000 CFM •Nominal 10 Ton Rating
80% 100%
10
20
30
40
50
60
70
80
90
10097%
![Page 288: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/288.jpg)
Flow Tolerance – 97% Design HT
260
4050607080
100120140160180200220240
0 2 4 6 8 10 12 14 16 18 20 22 24
±5% ±10% ±15% ±20%
Sup
ply
Wat
er T
empe
ratu
re °
F
Suggested Flow Tolerance (%)
-0 / +10%
Hea
ting
Coo
ling6°16°
![Page 289: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/289.jpg)
Balancing, The Obvious Answer
• Maximum branch flows need to be controlled• Balancing valves are one solution• Pressure independent flow control is another
method• “Systems” perspective needs to be
maintained; pipe, valves, calculations.
![Page 290: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/290.jpg)
Pressure Dependent Balancing Valve
![Page 291: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/291.jpg)
0
20
40
60
80
100
120
140
0 50 100 150 200 250
Flow (USGPM)
Hea
d (F
eet)
Pressure Dependent Balancing Valve
![Page 292: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/292.jpg)
Cartridge
Orifice is sized for the design flow
Pressure Independent Flow Limiting Valve
![Page 293: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/293.jpg)
Cartridge Operation
Flow Flow
P1 is lowCartridge Opens
P1 - P2 = Constant
P1 is highCartridge Closes
P1 - P2 = Constant
P1 P2 P1 P2
![Page 294: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/294.jpg)
Flow
in G
PM
Differential Pressure in PSI
FixedOrifice
Control Range
Design Flow AccuracyRange
Pressure Independent Flow Limiting Valve
![Page 295: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/295.jpg)
Externally adjustable flow limiting balance valves
½” – 2” sizes available
.18 to 45.46 GPM
Pressure Independent Flow Limiting Valve
![Page 296: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/296.jpg)
Externally adjustable flow limiting balance valve and a modulating control valve
½” – 2” sizes available
.13 to 37 GPM
Pressure Independent Control Valves
![Page 297: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/297.jpg)
It’s more than just “balancing valves”
• Piping system decisions:– Usually have a choice between two size pipes
– Varied methods of pipe head loss calculation
• Have to account for safety factors, aging
• Control valve selection: may not get the exact flow coefficient you need.
• Have to have a way to validate (test) and make adjustments (branch & system)
• It takes some judgment and experience.
![Page 298: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/298.jpg)
Design Criteria For Piping
ASHRAE recommends:• Velocity
– General 4 -10 fps– Mechanical rm. 6 -15 fps
• Maximum velocity– 1500 hr/yr 15 fps– 3000 hr/yr 13 fps– 6000 hr/yr 10 fps
• Pressure drop– 1.0 to 4.0 ft / 100 ft.
Consider:• Branch to riser pressure
drops should be 2:1 or greater
• Direct return circuits in variable speed / variable flow hydronic circuits require much more attention to detail and control sequence
![Page 299: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/299.jpg)
CHAPTER 6HEATING, VENTILATING, AND AIR CONDITIONING
SECTION 6.5Prescriptive Path
2½
3
4
5
6
8
10
12Maximum Velocity for Pipes
over 12 in. Size
120
180
350
410
740
1200
1800
2500
8.5 fps
180
270
530
620
1100
1800
2700
3800
13.0 fps
85
140
260
310
570
900
1300
1900
6.5 fps
130
210
400
470
860
1400
2000
2900
9.5 fps
68
110
210
250
440
700
1000
1500
5.0 fps
110
170
320
370
680
1100
1600
2300
7.5 fps
TABLE 6.5.4.5 Piping System Design Maximum Flow Rate in GPM
Operating Hours/Year
Nominal Pipe Size, in. Other Variable Flow/Variable Speed Other Variable Flow/
Variable Speed Other Variable Flow/Variable Speed
<2000 Hours/Year <2000 and <4400 Hours/Year >4400 Hours/Year
ASHRAE 90.1-2010
![Page 300: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/300.jpg)
Piping System Design Maximum Flow Rate –Friction Loss Rate Comparison
Friction Loss Rate
Velocity
Operating Hours/Year
Nominal Pipe Size, in. Other
(GPM)
Friction Loss Rate (Ft/100 Ft)
VariableSpeed(GPM)
FrictionLoss Rate
(Ft / 100 Ft)Other(GPM)
Friction Loss Rate
(Ft / 100 Ft)
VariableSpeed(GPM)
Friction Loss Rate
(Ft / 100 Ft)Other(GPM)
Friction Loss Rate
(Ft / 100 Ft)
VariableSpeed(GPM)
Friction Loss Rate
(Ft / 100 Ft)2 1/2 120 10.01 180 21.78 85 5.2 130 11.66 68 3.42 110 8.48
3 180 7.26 270 15.78 140 4.5 210 9.74 110 2.86 170 6.514 350 6.55 530 14.56 260 3.72 400 8.46 210 2.48 320 5.525 410 2.84 620 6.25 310 1.67 470 3.68 250 1.12 370 2.346 740 3.47 1100 7.44 570 2.11 860 4.63 440 1.3 680 2.968 1200 2.2 1800 4.79 900 1.27 1400 2.95 700 0.79 1100 1.8610 1800 1.52 2700 3.3 1300 0.82 2000 1.86 1000 0.5 1600 1.2112 2500 1.18 3800 2.63 1900 0.7 2900 1.57 1500 0.45 2300 1.01
>4400 Hours/Year<2000 Hours/Year<2000 and <4400
Hours/Year
Operating Hours/Year
Nominal Pipe Size, in. Other
(GPM)Velocity (ft/sec)
VariableSpeed(GPM)
Velocity (ft/sec)
Other(GPM)
Velocity (ft/sec)
VariableSpeed(GPM)
Velocity (ft/sec)
Other(GPM)
Velocity (ft/sec)
VariableSpeed(GPM)
Velocity (ft/sec)
2 1/2 120 8.04 180 12.06 85 5.69 130 8.71 68 4.56 110 7.373 180 7.81 270 11.72 140 6.08 210 9.12 110 4.78 170 7.384 350 8.82 530 13.36 260 6.55 400 10.08 210 5.29 320 8.075 410 6.57 620 9.94 310 4.97 470 7.53 250 4.01 370 5.936 740 8.22 1100 12.22 570 6.33 860 9.55 440 4.89 680 7.558 1200 7.7 1800 11.55 900 5.78 1400 8.98 700 4.49 1100 7.0610 1800 7.32 2700 10.98 1300 5.29 2000 8.13 1000 4.07 1600 6.5112 2500 7.17 3800 10.89 1900 5.45 2900 8.31 1500 4.3 2300 6.59
<2000 Hours/Year<2000 and <4400
Hours/Year >4400 Hours/Year
![Page 301: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/301.jpg)
SYSTEM SYZER– Flow/Pressure Drop
ASHRAE 90.1 max pipe size information
Estimated annual energy cost based
on pipe sizeNote that cost is based on a constant load – it is independent of the info in ASHRAE frame
![Page 302: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/302.jpg)
421
959080
% Design FlowIn End Circuit
Ratio, Branch ToDistribution
• And it falls off much more below 1:1
Branch to Riser Pressure Drop Ratio
![Page 303: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/303.jpg)
Branch:Riser Pressure Drop RatioH
ead
Distance From Pump0
100%Pump head constant
Improved β
![Page 304: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/304.jpg)
Branch:Riser Pressure Drop RatioH
ead
Distance From Pump0
100% β constantReduced pump head
![Page 305: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/305.jpg)
Issue: System Curve
• When we have many path’s, we have manysystem curves depending upon which valves are open.
• In VS/VF systems, the pump flow changes as the control valves modulate. The pump speed adjusts to those changes.
![Page 306: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/306.jpg)
Flow (USGPM)
Pipe Size
Friction Loss
(Feet)
Velocity (FPS)
Reynolds Number
Flow TypeFriction Factor
5000 12 4.48 14.34 1172764 Transition 0.01414 2.77 11.86 1066660 Transition 0.013916 1.41 9.08 933291 Transition 0.013818 0.78 7.17 829403 Transition 0.013820 0.45 5.77 743901 Transition 0.013824 0.18 3.99 618839 Transition 0.0138
5500 14 3.33 13.04 1173326 Transition 0.013816 1.7 9.99 1026626 Transition 0.013718 0.94 7.89 912343 Transition 0.013620 0.54 6.35 818292 Transition 0.013624 0.22 4.39 680723 Transition 0.0137
6000 14 3.94 14.23 1279992 Transition 0.013716 2.01 10.89 1119949 Transition 0.013618 1.11 8.61 995283 Transition 0.013520 0.64 6.92 892682 Transition 0.013524 0.26 4.79 742607 Transition 0.0136
A much larger system
![Page 307: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/307.jpg)
Balanced Flow
CoefficientCV
340
287
253
229
211
196
20
28
36
44
52
60
1000
1000
1000
1000
1000
1000
1
2
3
4
5
6
BranchAvailable
∆PBranchFlow
Total 6000@68’
CV
CV
CV
CV
CV
CV
1
2
3
4
5
6
A
B
C
D
E
F
G
b
c
d
e
f
g
a
4
4
4
4
4
4
4
4
4
4
4
4
10 10 0
Set Point = 20 Ft
8
16
24
32
40
Branch = 20’Risers = 48’Ratio = 0.4
![Page 308: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/308.jpg)
Flow (USGPM)
Hea
d (F
eet)
0.0
10.0
20.0
30.0
40.0
50.0
60.0
70.0
0.0 1000.0 2000.0 3000.0 4000.0 5000.0 6000
Inner Valves Close HeadOuter Valves CLoseSystem Curve
Head ControlMin 2
1
212
QQhh
![Page 309: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/309.jpg)
Flow (USGPM)
Hea
d (F
eet)
0.0
10.0
20.0
30.0
40.0
50.0
60.0
70.0
0.0 1000.0 2000.0 3000.0 4000.0 5000.0 6000.0
Out Valves Close HeadInner Valves CloseSystem Curve
CV
CV
CV
CV
CV
CV
1
2
3
4
5
6
A
B
C
D
E
F
G
b
c
d
e
f
g
a
.83
.83
.83
.83
.83
.83
.83
.83
.83
.83
.83
.83
10 10 0
6000 @ 30
Plot of Valve & Head Combinations 6000 GPM @ 30’ 2:1 Branch Riser Pressure Drop Ratio (BRPDR)
1.7
3.4
5.1
6.8
8.5
2:1 BRPDR
![Page 310: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/310.jpg)
2’
1234566000 GPM@88 Ft Hd
10’
10’
40’ 32’ 24’ 16’ 8’ 0’
10’10’10’10’10’
10’10’10’10’10’VFD
20’
4’ 4’ 4’ 4’ 4’F’ E’ D’ C’ B’ A’2’
4’ 4’ 4’ 4’ 4’F E D C B A4’
1
23
These Must Be Balanced!
Variable Primary Flow System
![Page 311: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/311.jpg)
Control Area for Variable Flow-Variable Speed Primary Distribution System
0.0
20.0
40.0
60.0
80.0
100.0
120.0
0 1000 2000 3000 4000 5000 6000 7000Flow (GPM)
Hea
d (F
eet)
System CurveInboardOutboard
Valve 6 Closed
Valve 6 & 5Closed
Valve 6,5,4ClosedValve 6,5,4,3
Closed
Valve 6,5,4,3,2 Closed
Valve 1 Closed
Valve 1,2 Closed
Valve 1,2,3 Closed
Valve 1,2,3,4 Closed
Valve 1,2,3,4,5 Closed
All Open
All Closed
![Page 312: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/312.jpg)
Thoughts On Selection
• Coil pressure drop dominates system controllability.
• Control valve selection with β = 0.5• Balancing valves: provide trim…
– Use as much PD as possible in control valves– Absorb the rest at the balancing valve.
• Use independent flow measurement– Triple Duty Valve– Pump– Circuit Setters
![Page 313: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/313.jpg)
Summary: Why Test & Balance?
• Load calculations can be inaccurate causing excess flow
• Pipe and fitting predicted losses will vary from actual performance– Aging factors / fouling will actually occur many years in
the future– Safety factors result in pump over-heading, improper
pump selection and over flow.• Control valve sizing is not exact.• Systems are not built as designed.
![Page 314: Large Chilled Water System Design Seminar - ASHRAE · PDF fileLarge Chilled Water System Design Seminar Presented by: Larry Konopacz, Manager of Training & Education Bell & Gossett](https://reader034.fdocuments.us/reader034/viewer/2022051201/5a6fd8017f8b9abb538b68cf/html5/thumbnails/314.jpg)
Additional Resources
• http://www.bellgossett.com– Resources & Tools
– XylemKnowsH2o
• http://mediasite.xyleminc.com• Our Representative in your area.
Questions?Thanks for Attending!