Large Air Receiver
description
Transcript of Large Air Receiver
Large Air Receiver
Medium Air Receiver
80 PSI Supply Air
Manifold
Muffler
Exhaust Valve (demand)
Transmitter
I2P4-20 ma
Foxboro743cbDigital
Controller4-20 ma
Pressure Station
LevelColumn
Pump
I2PConverter
S
0%
100%
1+ 1+ 1+1- 1- 1-
3+ 3+3-3- 2-
2+
2AI-I2V
2AP+A5
2AO-V2I
A/M Station
Level Station
Drain
NIA02 Loop Calibration, Control & NIA02 Loop Calibration, Control & TroubleshootingTroubleshooting
20092009
Given the necessary tools, equipment and references the I&C technician will calibrate and troubleshoot
instrumentation loops. Mastery will be demonstrated by successful completion of all in class exercises,
Laboratory Practical Evaluations and scoring 80% or better on an end of course exam.
Course Terminal Objective:
Topics:
• Isolating & Restoring Instruments• Foxboro coding refresher• Loop Calibration (calibration principles)• Loop Control (loop tuning)• Loop Troubleshooting• Industry Events
– 40 hour class– 7 labs- CBT exam
3 valve manifold section
• How many ways are there to valve out a transmitter?
• How many ways to put one back into service?
• How many are acceptable?
• What are we trying to prevent?
• What if the transmitter in question has a dry reference leg? How does this change valving it in or out?
Six ways.
Six ways.
What do we NOT want to happen when isolating & restoring an instrument
• Full system pressure on one side of a transmitter and atmospheric on the other side
• System flow through the 3-valve manifold• Loss of wet reference legs• Water in dry reference legs• Leaving instruments out of configuration• Disturbing other instruments on shared
sensing lines
Possible ways to valve out a transmitter
First Second Third ResultsShut high Open equalizer Shut low This is the recommended
correct method
Shut high Shut low Open equalizer disadvantage:temporarily locks pressure
into both sides of manifold and transmitter
Open equalizer Shut high Shut low Flow through manifold !!!
Open equalizer Shut low Shut high Flow through manifold !!!
Shut low Open equalizer Shut high Not so bad
shut low Shut high Open equalizer disadvantage:temporarily locks pressure
into both sides of manifold and transmitter
Equalizing Valve
Process High Pressure tap
Process Low Pressure tap
Instrument Low Pressure tap
Instrument High Pressure tap
HighSideIsolation
LowSideIsolation
High Pressure test tap
Low Pressure test tap
Typical Dragon Three-Valve Manifold
Low SideIsolation
High SideIsolation
Instrument Root Valves
Equalizer
Process
Flow
HP LP Flow through 3-valve manifold
Possible Sequences for returning a transmitter to service
First Second Third ResultsOpen Low Shut Equalizer Open High This is the recommended
correct method
Open Low Open High Shut Equalizer Flow through manifold !!!
Open High Shut Equalizer Open Low Not so bad.
Open High Open Low Shut equalizer Flow through manifold !!!
Shut equalizer Open High Open Low Hammers Transmitter with full system
pressure on only one side
Shut Equalizer Open Low Open High Hammers Transmitter with full system
pressure on only one side
Instrument Root Valves
High SideIsolation
Low SideIsolation
Equalizer
Process
Flow
HP LP
Out of service, root valves shut
Instrument Root Valves
High SideIsolation
Low SideIsolation
Equalizer
Process
Flow
HP LP
Open Root valves
Low SideIsolation
High SideIsolation
Instrument Root Valves
Equalizer
Process
Flow
HP LPCheck equalizer open, then open low side isolation
Low SideIsolation
High SideIsolation
Instrument Root Valves
Equalizer
Process
Flow
HP LP
Shut equalizer
Low SideIsolation
High SideIsolation
Instrument Root Valves
Equalizer
Process
Flow
HP LP
Shut equalizer valve
Low SideIsolation
High SideIsolation
Instrument Root Valves
Equalizer
Process
Flow
HP LPOpen High Side Isolation
Low SideIsolation
High SideIsolation
Instrument Root Valves
Equalizer
Process
Flow
HP LPTransmitter in service
On to SPEC 200 Coding