VENT THRU ROOF TRANSFER GRILLE CEILING DIFFUSER ABOVE FINISHED FLOOR SIDEWALL SUPPLY REGISTER CEILING SUPPLY REGISTER RETURN AIR FILTER GRILLE RETURN AIR REGISTER FAN COIL RETURN AIR ROOFTOP A/C UNIT CONDENSING UNIT EXHAUST REGISTER EXHAUST FAN AIR HANDLING UNIT SSR CSR F/C RTU AHU CU EF ER R/A RAR RAFG FD CD VTR TG DG EXH DIA OA MU AFF EXHAUST DIAMETER DOOR GRILLE OUTSIDE AIR FIRE DAMPER MAKE UP CEILING RADIATION DAMPER CRD HVAC COMPLIANCE NOTES: ABBREVIATIONS SYMBOL DESCRIPTION RECTANGULAR SUPPLY DUCT RECTANGULAR RETURN AIR DUCT FIRE DAMPER W/ ACCESS PANEL 90° ELL DOWN - FLEX 90° ELL DOWN - RIGID 90° ELL UP - FLEX 90° ELL UP - RIGID THREE WAY DUCT TRANSITION FOUR WAY DUCT TRANSITION BALANCING DAMPER 3-WAY REGISTER - CEILING 4-WAY REGISTER - CEILING 2-WAY REGISTER - CEILING 1-WAY REGISTER - CEILING LINEAR DIFFUSERS SIDE WALL REGISTER AIR HANDLER - HORIZONTAL AIR HANDLER - VERTICAL GAS FURNACE AIR HANDLER - ELECTRIC OR HEAT PUMP EXHAUST FAN - WALL MOUNT EXHAUST FAN - CEILING MOUNT WALL CAP CONDENSING UNIT OUTSIDE AIR INTAKE - CEILING O.A. FLEX DUCT SPIRAL DUCT THERMOSTAT RAFG FIRE/ SMOKE DAMPER DUCT FREE EXHAUST FAN - CEILING MOUNT DUCT SMOKE DETECTOR BASEBOARD HEATER COMBUSTION AIR LOUVERS IN WALL OR DOOR CASED AIR HANDLER - HORIZONTAL OUTSIDE AIR INTAKE - WALL O.A. MECHANICAL SYMBOL SCHEDULE ALL SYMBOLS DO NOT NECESSARILY APPEAR ON ALL DRAWINGS. SYMBOLS ARE NOT SCALED. CONTRACTOR SHALL PROVIDE WATERTIGHT AND WATER PROOF INSTALLATION OF ALL DRYER AND EXHAUST VENT CAPS. COORDINATE FLASHING AND WATERPROOFING WITH GENERAL CONTRACTOR. MECHANICAL CONTRACTOR SHALL: VERIFY THAT ALL WORK IS COMPLETED AND IS IN COMPLIANCE WITH THE DESIGN INTENT. ALL WORK SHALL BE IN COMPLIANCE WITH ALL LOCAL AND NATIONAL CODES AND OR ORDINANCES. FURNISH AND INSTALL ALL HVAC EQUIPMENT, DUCT WORK AND REFRIGERANT PIPING AS WELL AS ALL OTHER ITEMS NECESSARY TO COMPLETE THE PROJECT PER MANUFACTURER'S RECOMMENDATIONS. PROVIDE SLEEVES AND OTHER NECESSARY ITEMS TO WEATHER PROOF PENETRATIONS OF BUILDING BY REFRIGERANT LINES AND EXHAUST DUCTS. USE ONLY APPROVED TAPES AND HANGERS FOR DUCT. INSTALL R6 DUCT IN DROP CEILINGS OR FLOOR TRUSSES AND R8 DUCT IN ATTICS OR OTHER UNCONDITIONED SPACES OTHER THAN FLOOR TRUSS. PROVIDE EACH HVAC SYSTEM WITH A PROPERLY SIZED NEW FILTER. VERIFY TYPE OF FILTER REQUIRED BY 2009 IECC PRIOR TO INSTALLATION. PROVIDE FIRE DAMPERS AND CEILING RADIATION DAMPERS AT PENETRATIONS OF ANY RATED ASSEMBLY OR WHERE REQUIRED BY CODE OR LOCAL AUTHORITIES. COORDINATE PRIOR TO INSTALLATION OF ANY EQUIPMENT OR DUCTWORK WITH ALL OTHER TRADES AND GENERAL CONTRACTOR. VERIFY THAT ALL DRYER AN EXHAUST VENT HOODS ARE INSTALLED PER MANUFACTURES REQUIREMENTS AND ARE WEATHER TIGHT. REFRIGERANT LINES PENETRATING THROUGH ANY PORTION OF THE BUILDING SHALL BE INSTALLED TO PREVENT ANY ACCESS OF WATER, INSECTS OR INCLEMENT WEATHER THAT COULD BREACH THE BUILDING ENVELOPE. COORDINATE FLASHING AND WATER PROOFING WITH GENERAL CONTRACTOR. PVC SHALL NOT BE USED IN RETURN AIR PLENUMS UNLESS APPROVED BY LOCAL AUTHORITIES. CONTRACTOR SHALL LOCATE ALL EXHAUST HOODS A MIN. OF 36" FROM ANY OPERABLE WINDOW, DOOR OR OPENING INTO THE BUILDING. CONTRACTOR SHALL VERIFY MFG. REQUIREMENTS FOR REFRIGERANT LINES AND SHALL NOT EXCEED MFG. RECOMMENDED MAXIMUM LENGTHS BOTH HORIZONTAL AND VERTICAL. CONTRACTOR SHALL NOT REQUEST ADDITIONAL SERVICES FOR FAILURE TO EXAMINE AND BE KNOWLEDGEABLE OF ALL CONSTRUCTION DOCUMENT REQUIREMENTS, INCLUDING BUT NOT LIMITED TO THE ELECTRICAL, MECHANICAL, PLUMBING, CIVIL, LANDSCAPE, STRUCTURAL AND ARCHITECTURAL. NO COMBUSTIBLE MATERIALS SHALL BE LOCATED IN RETURN OR SUPPLY AIR PLENUMS. MECHANICAL CONTRACTOR SHALL INSTALL LOUVERS THROUGH WALL, PROVIDING A MINIMUM OF 100 SQ. INCHES OF MAKEUP AIR FOR ALL CLOTHES DRYER CLOSETS. CONDENSING UNITS SHALL BE SECURED PER SMACNA STANDARDS. CONTRACTOR SHALL VERIFY A MINIMUM OF 13.0 SEER ON ALL HVAC UNITS PRIOR TO INSTALLATION. CONTRACTOR SHALL VERIFY COMPATIBILITY OF AIR HANDLERS AND CONDENSING UNITS PRIOR TO PURCHASE AND OR INSTALLATION. CONTRACTOR SHALL USE THERMOSTATIC EXPANTION VALVES WHERE REQUIRED BY MANUFACTURER. SQUARE DUCT ALL CONDENSING UNITS SHALL BE INSTALLED ON 4" CONCRETE PAD. DISTANCES FROM STRUCTURES SHALL BE MAINTAINED TO MANUFACTURERS REQUIREMENTS. WATER HEATER VENT TERMINATION POINT SHALL BE 10' FROM EDGE OF ROOF. ALL REFRIGERANT CIRCUITS SERVICE PORTS LOCATED ON THE EXTERIOR OF THE BUILDING SHALL BE PROVIDED WITH LOCKING ACCESS PORT CAPS. DESIGN OF MECHANICAL SYSTEMS ARE BASED ON INFORMATION PROVIDED BY OTHERS WITH NO GUARANTEE AS TO ACCURACY. PRIMARY DRAIN LINES LOCATED IN ANY UNCONDITIONED SPACE, EXCEPT FOR CRAWL SPACES, SHALL BE INSULATED WITH FOAM PLASTIC RUBBER BASED INSULATION OR OTHER APPROVED MATERIAL WITH A MINIMUM THICKNESS OF 3/8 INCH. 15 JRF ASSOCIATES SCALE 3620 Winding Way Round Rock Texas 78664 512-970-9478 Ph ISSUE DATE SHEET NUMBER PROJECT NUMBER 1322013 05-27-2014 LANDMARK SAN ANTONIO C 2010 BY JRF ASSOCIATES ALL RIGHTS RESERVED. THE DESIGNS DEPICTED HEREIN ARE THE SOLE PROPERTY OF JRF ASSOCIATES AND MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION. ALL DESIGNS ARE BASED ON THE INFORMATION FROM OTHERS AND TO BE USED ON LANDMARK SAN ANTONIO APARTMENTS Firm registration number f-15222 Automation Engineering PERMIT SET M1 N/A 15 ADA COMMENTS 07-21-2014

Transcript of LANDMARK SAN ANTONIO€¦ · above finished floor sidewall supply register ceiling supply register...

Page 1: LANDMARK SAN ANTONIO€¦ · above finished floor sidewall supply register ceiling supply register return air filter grille return air register fan coil return air rooftop a/c unit

VENT THRU ROOF

TRANSFER GRILLE

CEILING DIFFUSER

ABOVE FINISHED FLOOR

SIDEWALL SUPPLY REGISTER

CEILING SUPPLY REGISTER

RETURN AIR FILTER GRILLE

RETURN AIR REGISTER

FAN COIL

RETURN AIR

ROOFTOP A/C UNIT

CONDENSING UNIT

EXHAUST REGISTER

EXHAUST FAN

AIR HANDLING UNIT

SSR

CSR

F/C

RTU

AHU

CU

EF

ER

R/A

RAR

RAFG

FD

CD

VTR

TG

DG

EXH

DIA

OA

MU

AFF

EXHAUST

DIAMETER

DOOR GRILLE

OUTSIDE AIR

FIRE DAMPER

MAKE UP

CEILING RADIATION DAMPERCRD

HVAC COMPLIANCE NOTES:

ABBREVIATIONS

SYMBOL DESCRIPTION

RECTANGULAR SUPPLY DUCT

RECTANGULAR RETURN AIR DUCT

FIRE DAMPER W/ ACCESS PANEL

90° ELL DOWN - FLEX

90° ELL DOWN - RIGID

90° ELL UP - FLEX

90° ELL UP - RIGID

THREE WAY DUCT TRANSITION

FOUR WAY DUCT TRANSITION

BALANCING DAMPER

3-WAY REGISTER - CEILING

4-WAY REGISTER - CEILING

2-WAY REGISTER - CEILING

1-WAY REGISTER - CEILING

LINEAR DIFFUSERS

SIDE WALL REGISTER

AIR HANDLER - HORIZONTAL

AIR HANDLER - VERTICAL

GAS FURNACE

AIR HANDLER - ELECTRIC OR HEAT PUMP

EXHAUST FAN - WALL MOUNT

EXHAUST FAN - CEILING MOUNT

WALL CAP

CONDENSING UNIT OUTSIDE AIR INTAKE - CEILINGO.A.

FLEX DUCT

SPIRAL DUCT

THERMOSTAT

RAFG

FIRE/ SMOKE DAMPER

DUCT FREE EXHAUST FAN - CEILING MOUNT

DUCT SMOKE DETECTOR

BASEBOARD HEATER

COMBUSTION AIR LOUVERS IN WALL OR DOOR

CASED AIR HANDLER - HORIZONTAL

OUTSIDE AIR INTAKE - WALLO.A.

MECHANICAL SYMBOL SCHEDULE

ALL SYMBOLS DO NOT NECESSARILY APPEAR ON ALL DRAWINGS.SYMBOLS ARE NOT SCALED.

CONTRACTOR SHALL PROVIDE WATERTIGHT AND WATER PROOFINSTALLATION OF ALL DRYER AND EXHAUST VENT CAPS.

COORDINATE FLASHING AND WATERPROOFING WITH GENERALCONTRACTOR.

MECHANICAL CONTRACTOR SHALL:

VERIFY THAT ALL WORK IS COMPLETED AND IS IN COMPLIANCEWITH THE DESIGN INTENT. ALL WORK SHALL BE IN COMPLIANCEWITH ALL LOCAL AND NATIONAL CODES AND OR ORDINANCES.

FURNISH AND INSTALL ALL HVAC EQUIPMENT, DUCT WORK ANDREFRIGERANT PIPING AS WELL AS ALL OTHER ITEMS NECESSARY

TO COMPLETE THE PROJECT PER MANUFACTURER'SRECOMMENDATIONS.

PROVIDE SLEEVES AND OTHER NECESSARY ITEMS TO WEATHERPROOF PENETRATIONS OF BUILDING BY REFRIGERANT LINES ANDEXHAUST DUCTS.

USE ONLY APPROVED TAPES AND HANGERS FOR DUCT.

INSTALL R6 DUCT IN DROP CEILINGS OR FLOOR TRUSSES AND R8DUCT IN ATTICS OR OTHER UNCONDITIONED SPACES OTHER THANFLOOR TRUSS.

PROVIDE EACH HVAC SYSTEM WITH A PROPERLY SIZED NEWFILTER.

VERIFY TYPE OF FILTER REQUIRED BY 2009 IECC PRIOR TOINSTALLATION.

PROVIDE FIRE DAMPERS AND CEILING RADIATION DAMPERS AT

PENETRATIONS OF ANY RATED ASSEMBLY OR WHERE REQUIRED BYCODE OR LOCAL AUTHORITIES.

COORDINATE PRIOR TO INSTALLATION OF ANY EQUIPMENT OR

DUCTWORK WITH ALL OTHER TRADES AND GENERALCONTRACTOR.

VERIFY THAT ALL DRYER AN EXHAUST VENT HOODS ARE

INSTALLED PER MANUFACTURES REQUIREMENTS AND AREWEATHER TIGHT.

REFRIGERANT LINES PENETRATING THROUGH ANY PORTION OFTHE BUILDING SHALL BE INSTALLED TO PREVENT ANY ACCESS OF

WATER, INSECTS OR INCLEMENT WEATHER THAT COULD BREACHTHE BUILDING ENVELOPE. COORDINATE FLASHING AND WATERPROOFING WITH GENERAL CONTRACTOR.

PVC SHALL NOT BE USED IN RETURN AIR PLENUMS UNLESS

APPROVED BY LOCAL AUTHORITIES.

CONTRACTOR SHALL LOCATE ALL EXHAUST HOODS A MIN. OF 36"FROM ANY OPERABLE WINDOW, DOOR OR OPENING INTO THE

BUILDING.

CONTRACTOR SHALL VERIFY MFG. REQUIREMENTS FORREFRIGERANT LINES AND SHALL NOT EXCEED MFG.RECOMMENDED MAXIMUM LENGTHS BOTH HORIZONTAL AND

VERTICAL.

CONTRACTOR SHALL NOT REQUEST ADDITIONAL SERVICES FORFAILURE TO EXAMINE AND BE KNOWLEDGEABLE OF ALLCONSTRUCTION DOCUMENT REQUIREMENTS, INCLUDING BUT NOT

LIMITED TO THE ELECTRICAL, MECHANICAL, PLUMBING, CIVIL,LANDSCAPE, STRUCTURAL AND ARCHITECTURAL.

NO COMBUSTIBLE MATERIALS SHALL BE LOCATED IN RETURN ORSUPPLY AIR PLENUMS.

MECHANICAL CONTRACTOR SHALL INSTALL LOUVERS THROUGHWALL, PROVIDING A MINIMUM OF 100 SQ. INCHES OF MAKEUP AIRFOR ALL CLOTHES DRYER CLOSETS.

CONDENSING UNITS SHALL BE SECURED PER SMACNA STANDARDS.

CONTRACTOR SHALL VERIFY A MINIMUM OF 13.0 SEER ON ALL HVACUNITS PRIOR TO INSTALLATION.

CONTRACTOR SHALL VERIFY COMPATIBILITY OF AIR HANDLERSAND CONDENSING UNITS PRIOR TO PURCHASE AND OR

INSTALLATION.

CONTRACTOR SHALL USE THERMOSTATIC EXPANTION VALVESWHERE REQUIRED BY MANUFACTURER.

SQUARE DUCT

ALL CONDENSING UNITS SHALL BE INSTALLED ON 4" CONCRETEPAD. DISTANCES FROM STRUCTURES SHALL BE MAINTAINED TO

MANUFACTURERS REQUIREMENTS.

WATER HEATER VENT TERMINATION POINT SHALL BE 10' FROM

EDGE OF ROOF.

ALL REFRIGERANT CIRCUITS SERVICE PORTS LOCATED ON THE

EXTERIOR OF THE BUILDING SHALL BE PROVIDED WITH LOCKINGACCESS PORT CAPS.

DESIGN OF MECHANICAL SYSTEMS ARE BASED ON INFORMATIONPROVIDED BY OTHERS WITH NO GUARANTEE AS TO ACCURACY.

PRIMARY DRAIN LINES LOCATED IN ANY UNCONDITIONED SPACE,

EXCEPT FOR CRAWL SPACES, SHALL BE INSULATED WITH FOAMPLASTIC RUBBER BASED INSULATION OR OTHER APPROVEDMATERIAL WITH A MINIMUM THICKNESS OF 3/8 INCH.

15

JRFASSOCIATES

SCALE

3620 Winding Way

Round Rock Texas 78664

512-970-9478 Ph

ISSUE DATE

SHEET NUMBER

PROJECT NUMBER

1322013

05-27-2014

LANDMARK SAN ANTONIO

C 2010 BY JRF ASSOCIATESALL RIGHTS RESERVED.

THE DESIGNS DEPICTED HEREIN ARE THE SOLEPROPERTY OF JRF ASSOCIATES AND MAY NOT BEREPRODUCED IN ANY FORM WITHOUT WRITTENPERMISSION. ALL DESIGNS ARE BASED ON THEINFORMATION FROM OTHERS AND TO BE USEDON LANDMARK SAN ANTONIO APARTMENTS

Firm registration number

f-15222

Automation Engineering

PERMIT SET

M1

N/A

15 ADA COMMENTS 07-21-2014

Page 2: LANDMARK SAN ANTONIO€¦ · above finished floor sidewall supply register ceiling supply register return air filter grille return air register fan coil return air rooftop a/c unit

2

8

18

JRFASSOCIATES

SCALE

3620 Winding Way

Round Rock Texas 78664

512-970-9478 Ph

ISSUE DATE

SHEET NUMBER

PROJECT NUMBER

1322013

05-27-2014

LANDMARK SAN ANTONIO

C 2010 BY JRF ASSOCIATESALL RIGHTS RESERVED.

THE DESIGNS DEPICTED HEREIN ARE THE SOLEPROPERTY OF JRF ASSOCIATES AND MAY NOT BEREPRODUCED IN ANY FORM WITHOUT WRITTENPERMISSION. ALL DESIGNS ARE BASED ON THEINFORMATION FROM OTHERS AND TO BE USEDON LANDMARK SAN ANTONIO APARTMENTS

Firm registration number

f-15222

Automation Engineering

PERMIT SET

M2

N/A

2

01-22-14

DELETED GARAGE

FAN SCHEDULE

8 05-16-2014ID COMMENTS

18 OWNERS CHANGES 9-08-2014

Page 3: LANDMARK SAN ANTONIO€¦ · above finished floor sidewall supply register ceiling supply register return air filter grille return air register fan coil return air rooftop a/c unit

A

25" x 12"RAFG

B

D

GI

T

C

F

H

K

12" x 6" CSR180 CFM3-WAYW/CRD

8" Ø

9" Ø

3" Ø

12" x 6" SSR

160 CFM

7" Ø

8" x 6" CSR80 CFM3-WAY

6" Ø12" x 6" SSR180 CFM

6

HORIZONTAL FAN COIL UNIT MOUNTED IN

FURR DOWN AS HIGH AS POSSIBLE.

FAN COIL CEILING ACCESS PANEL. PANEL

SHALL BE GASKETED AND AIR TIGHT.

SHEETROCK UP TO FURR DOWN ONLY

EXHAUST FAN IN WALL, EXTEND DUCT UP TOJOIST SPACE. TOP FLOOR SHALL HAVE THE

OPTION TO ROUTE DUCT DOWN TO JOISTSPACE BELOW.

WALL CAPS, EACH EXHAUST WALL CAP SHALLMAINTAIN A MINIMUM DISTANCE OF 36" FROM

ANY OPERABLE OPENING TO THE BUILDINGAND SHALL BE SEALED WEATHER TIGHT.

WATER HEATER BY PLUMBING CONTRACTOR.

DRYER VENT UP IN WALL.

DRYER VENT IN TRUSS/JOIST SPACE. EACHDRYER VENT SHALL BE 26 GAUGE RIDGED

SMOOTH METAL WITH ALL JOINTS CONNECTEDIN THE DIRECTION OF AIR FLOW.

MAKEUP AIR LOUVER, REFER TOARCHITECTURAL UNIT PLANS FOR

CALCULATIONS AND SIZING.

FIRE DAMPER WITH ACCESS PANEL. ALL FIRE

DAMPERS SHALL BE INSTALLED INACCORDANCE TO ALL SMACNA AND LOCALREQUIREMENTS.

B

A

C

D

E

F

G

H

I

J

MECHANICAL NOTES BY SYMBOL:

EXHAUST VENT IN TRUSS/JOIST SPACE.K

FURR DOWN LEGEND

MECHANICAL CONTRACTOR SHALL VERIFYTHAT ALL DRYER AND EXHAUST VENT HOODS

ARE INSTALLED PER MANUFACTURESREQUIREMENTS AND ARE WEATHER TIGHT.

REFRIGERANT LINE PENETRATION THROUGH ANYPORTION OF THE BUILDING SHALL BE INSTALLEDTO PREVENT ANY ACCESS OF WATER, INSECTS OR

INCLEMENT WEATHER REACHING THE INSIDE OFTHE BUILDING ENVELOPE.

RETURN AIR FURR DOWN, MECHANICAL

CONTRACTOR SHALL VERIFY ALL RETURN AIRFURRING IS AIR TIGHT AND SEPARATE FROMANY NON RETURN FURRING. CONTRACTOR

SHALL ALSO ENSURE THAT RETURN AIR PATH

FROM RETURN AIR GRILL TO AIR HANDLER ISCLEAR OF OBSTRUCTIONS THAT WOULD CAUSE

RESTRICTION TO RETURN AIR.

NON RETURN AIR FURR DOWN - SEPERATEFROM FURRING USED FOR RETURN AIR.

A B

C

H

K

3" Ø

12" x 6" SSR160 CFM

7" Ø

8" x 6" CSR

80 CFM3-WAY

6" Ø

A B

D

C

H

K

3" Ø

12" x 6" SSR

160 CFM

7" Ø

8" x 6" CSR80 CFM

3-WAY

6" Ø

D

I

25" x 12"

RAFG

G

T

A B F

K

8" x 6"

CSR 70CFM3-WAY

6" Ø

12" x 6" SSR180 CFM

8" Ø

12" x 6" CSR180 CFM3-WAY

W/CRD

12" x 6" CSR170 CFM

3-WAYW/CRD

8" Ø

8" Ø

9" Ø

D

I

G

25" x 12"RAFG

T

A BC

F

H

K

8"Ø

12" x 6" SSR170 CFM

8"Ø

8" x 6" CSR

80 CFM3-WAY - 5"Ø 4"Ø

6"Ø

12" x 6" SSR150 CFM

7"Ø

12" x 6" CSR 170 CFM3-WAY

A B

H

K

8"Ø

4"Ø

6"Ø

12" x 6" SSR150 CFM

7"Ø

D

I

G

25" x 12"

RAFG

T

A BC

F

H

K

8"Ø

12" x 6" SSR170 CFM

8"Ø

8" x 6" CSR 80 CFM

3-WAY - 5"Ø4"Ø

6"Ø

12" x 6" SSR

150 CFM

7"Ø

12" x 6" CSR

170 CFM3-WAY

T

I

D

A

B

CF

25" x 12"RAFG

G

H

K

12" x 6" CSR 190 CFM

3-WAYW/CRD

8"Ø

12" x 6" CSR

150 CFM3-WAYW/CRD

7"Ø

9"Ø

3"Ø

4"Ø

12" x 6" SSR

150 CFM

7"Ø

10" x 6" CSR

110 CFM3-WAY

JRFASSOCIATES

SCALE

3620 Winding Way

Round Rock Texas 78664

512-970-9478 Ph

ISSUE DATE

SHEET NUMBER

PROJECT NUMBER

1322013

05-27-2014

LANDMARK SAN ANTONIO

C 2010 BY JRF ASSOCIATESALL RIGHTS RESERVED.

THE DESIGNS DEPICTED HEREIN ARE THE SOLEPROPERTY OF JRF ASSOCIATES AND MAY NOT BEREPRODUCED IN ANY FORM WITHOUT WRITTENPERMISSION. ALL DESIGNS ARE BASED ON THEINFORMATION FROM OTHERS AND TO BE USEDON LANDMARK SAN ANTONIO APARTMENTS

Firm registration number

f-15222

Automation Engineering

PERMIT SET

M3

1/4" = 1' - 0"

1/4" = 1'-0"

UNIT TYPE A1

1/4" = 1'-0"

UNIT TYPE A1-A

1/4" = 1'-0"

UNIT TYPE A1-B

1/4" = 1'-0"

UNIT TYPE A2

1/4" = 1'-0"

UNIT TYPE A3

1/4" = 1'-0"

UNIT TYPE A3-A

1/4" = 1'-0"

UNIT TYPE A3-B

1/4" = 1'-0"

UNIT TYPE A3-HC

5 REVISEDBACKGROUND,

OWNERS CHANGES

5 OWNERS CHANGES 4-21-2014

6 CITY COMMENTS 05-02-2014

Page 4: LANDMARK SAN ANTONIO€¦ · above finished floor sidewall supply register ceiling supply register return air filter grille return air register fan coil return air rooftop a/c unit

25" x 12"RAFG

D

G

I

T

A

B

C

CF

H

K

14" x 6" CSR 220 CFM

3-WAYW/CRD

9"Ø

10" x 6" SSR110 CFM

6"Ø

8" x 4" CSR70 CFM

3-WAY 4"Ø

14" x 6" SSR200 CFM

8"Ø

3"Ø

HORIZONTAL FAN COIL UNIT MOUNTED INFURR DOWN AS HIGH AS POSSIBLE.

FAN COIL CEILING ACCESS PANEL. PANELSHALL BE GASKETED AND AIR TIGHT.

SHEETROCK UP TO FURR DOWN ONLY

EXHAUST FAN IN WALL, EXTEND DUCT UP TOJOIST SPACE. TOP FLOOR SHALL HAVE THEOPTION TO ROUTE DUCT DOWN TO JOIST

SPACE BELOW.

WALL CAPS, EACH EXHAUST WALL CAP SHALLMAINTAIN A MINIMUM DISTANCE OF 36" FROMANY OPERABLE OPENING TO THE BUILDINGAND SHALL BE SEALED WEATHER TIGHT.

WATER HEATER BY PLUMBING CONTRACTOR.

DRYER VENT UP IN WALL.

DRYER VENT IN TRUSS/JOIST SPACE. EACH

DRYER VENT SHALL BE 26 GAUGE RIDGEDSMOOTH METAL WITH ALL JOINTS CONNECTEDIN THE DIRECTION OF AIR FLOW.

MAKEUP AIR LOUVER, REFER TOARCHITECTURAL UNIT PLANS FORCALCULATIONS AND SIZING.

FIRE DAMPER WITH ACCESS PANEL. ALL FIREDAMPERS SHALL BE INSTALLED INACCORDANCE TO ALL SMACNA AND LOCAL

REQUIREMENTS.

B

A

C

D

E

F

G

H

I

J

MECHANICAL NOTES BY SYMBOL:

EXHAUST VENT IN TRUSS/JOIST SPACE.K

FURR DOWN LEGEND

MECHANICAL CONTRACTOR SHALL VERIFYTHAT ALL DRYER AND EXHAUST VENT HOODS

ARE INSTALLED PER MANUFACTURESREQUIREMENTS AND ARE WEATHER TIGHT.

REFRIGERANT LINE PENETRATION THROUGH ANY

PORTION OF THE BUILDING SHALL BE INSTALLEDTO PREVENT ANY ACCESS OF WATER, INSECTS ORINCLEMENT WEATHER REACHING THE INSIDE OF

THE BUILDING ENVELOPE.

RETURN AIR FURR DOWN, MECHANICALCONTRACTOR SHALL VERIFY ALL RETURN AIRFURRING IS AIR TIGHT AND SEPARATE FROM

ANY NON RETURN FURRING. CONTRACTORSHALL ALSO ENSURE THAT RETURN AIR PATHFROM RETURN AIR GRILL TO AIR HANDLER IS

CLEAR OF OBSTRUCTIONS THAT WOULD CAUSERESTRICTION TO RETURN AIR.

NON RETURN AIR FURR DOWN - SEPERATEFROM FURRING USED FOR RETURN AIR.

H

K

14" x 6" CSR 220 CFM

3-WAYW/CRD

36" x 12"

RAFGT

A

B

C

F

I

K

3"Ø

4"Ø

14" x 6" SSR

220 CFM8"Ø

10" x 6" SSR120 CFM

6"Ø8" x 6" CSR

100 CFM3-WAY

6"Ø

7"Ø

14" x 6" SSR160 CFM

4

K

3"Ø

4"Ø

K

14" x 6" SSR220 CFM

8"Ø

7"Ø

14" x 6" SSR160 CFM

JRFASSOCIATES

SCALE

3620 Winding Way

Round Rock Texas 78664

512-970-9478 Ph

ISSUE DATE

SHEET NUMBER

PROJECT NUMBER

1322013

05-27-2014

LANDMARK SAN ANTONIO

C 2010 BY JRF ASSOCIATESALL RIGHTS RESERVED.

THE DESIGNS DEPICTED HEREIN ARE THE SOLEPROPERTY OF JRF ASSOCIATES AND MAY NOT BEREPRODUCED IN ANY FORM WITHOUT WRITTENPERMISSION. ALL DESIGNS ARE BASED ON THEINFORMATION FROM OTHERS AND TO BE USEDON LANDMARK SAN ANTONIO APARTMENTS

Firm registration number

f-15222

Automation Engineering

PERMIT SET

M4

1/4" = 1' - 0"

1/4" = 1'-0"

UNIT TYPE A41/4" = 1'-0"

UNIT TYPE A4-A

1/4" = 1'-0"

UNIT TYPE A5, A5-A, A5-B, A5-C

1/4" = 1'-0"

UNIT TYPE A5-D

1/4" = 1'-0"

UNIT TYPE A5-E

4 OWNERS CHANGES 3-27-2014

4 REVISEDBACKGROUND, A5,

A5A, A5B

5 REVISEDBACKGROUND,

OWNERS CHANGES

5 OWNERS CHANGES 4-21-2014

Page 5: LANDMARK SAN ANTONIO€¦ · above finished floor sidewall supply register ceiling supply register return air filter grille return air register fan coil return air rooftop a/c unit

E

D

G

I

36" x 12"

RAFG

T

A

B

C

F

H

K

12" x 6" CSR

200 CFM3-WAYW/CRD

8"Ø

8" x 8" CSR 150 CFM

4-WAYW/CRD

7"Ø

9"Ø

10" x 6" SSR

150 CFM

8" x 6" CSR 70 CFM

3-WAY

6"Ø

8" x 4" SSR

30 CFM

4"Ø

4"Ø

3"Ø3"Ø

4

HORIZONTAL FAN COIL UNIT MOUNTED INFURR DOWN AS HIGH AS POSSIBLE.

FAN COIL CEILING ACCESS PANEL. PANELSHALL BE GASKETED AND AIR TIGHT.

SHEETROCK UP TO FURR DOWN ONLY

EXHAUST FAN IN WALL, EXTEND DUCT UP TOJOIST SPACE. TOP FLOOR SHALL HAVE THE

OPTION TO ROUTE DUCT DOWN TO JOISTSPACE BELOW.

WALL CAPS, EACH EXHAUST WALL CAP SHALLMAINTAIN A MINIMUM DISTANCE OF 36" FROMANY OPERABLE OPENING TO THE BUILDING

AND SHALL BE SEALED WEATHER TIGHT.

WATER HEATER BY PLUMBING CONTRACTOR.

DRYER VENT UP IN WALL.

DRYER VENT IN TRUSS/JOIST SPACE. EACHDRYER VENT SHALL BE 26 GAUGE RIDGEDSMOOTH METAL WITH ALL JOINTS CONNECTED

IN THE DIRECTION OF AIR FLOW.

MAKEUP AIR LOUVER, REFER TOARCHITECTURAL UNIT PLANS FORCALCULATIONS AND SIZING.

FIRE DAMPER WITH ACCESS PANEL. ALL FIRE

DAMPERS SHALL BE INSTALLED INACCORDANCE TO ALL SMACNA AND LOCALREQUIREMENTS.

B

A

C

D

E

F

G

H

I

J

MECHANICAL NOTES BY SYMBOL:

EXHAUST VENT IN TRUSS/JOIST SPACE.K

FURR DOWN LEGEND

MECHANICAL CONTRACTOR SHALL VERIFYTHAT ALL DRYER AND EXHAUST VENT HOODS

ARE INSTALLED PER MANUFACTURESREQUIREMENTS AND ARE WEATHER TIGHT.

REFRIGERANT LINE PENETRATION THROUGH ANYPORTION OF THE BUILDING SHALL BE INSTALLEDTO PREVENT ANY ACCESS OF WATER, INSECTS OR

INCLEMENT WEATHER REACHING THE INSIDE OFTHE BUILDING ENVELOPE.

RETURN AIR FURR DOWN, MECHANICAL

CONTRACTOR SHALL VERIFY ALL RETURN AIRFURRING IS AIR TIGHT AND SEPARATE FROMANY NON RETURN FURRING. CONTRACTOR

SHALL ALSO ENSURE THAT RETURN AIR PATH

FROM RETURN AIR GRILL TO AIR HANDLER ISCLEAR OF OBSTRUCTIONS THAT WOULD CAUSE

RESTRICTION TO RETURN AIR.

NON RETURN AIR FURR DOWN - SEPERATE

FROM FURRING USED FOR RETURN AIR.

E

D

H

K

10"

8" x 6" CSR 70 CFM

3-WAY

4"Ø

3"Ø3"Ø

12" x 6" CSR200 CFM

3-WAYW/CRD

G

36" x 12RAFG

T

A

B

C

F

9"Ø

10" x 6" SSR

150 CFM

CSR

FMY

6"Ø

8" x 4" SSR30 CFM

4"Ø

4

36" x 12"

RAFGI

DT

A

B

C

F

K

10" x 6" CSR 160 CFM3-WAYW/CRD

7"Ø

10" x 6" CSR 100 CFM

3-WAYW/CRD

6"Ø10" x 6" SSR130 CFM

7"Ø

8" x 4" CSR 70 CFM

3-WAY

5"Ø

8" x 4" CSR 50 CFM3-WAY

W/CRD

5"Ø

6"Ø

12" x 6" SSR90 CFM

6"Ø

3"Ø

4"Ø

36" x 12"RAFG

T

F

3"Ø

4"Ø 12" x 6" SSR160 CFM

7"Ø

12" x 6" SSR

150 CFM

7"Ø

12" x 6" SSR

160 CFM

7"Ø

10" x 6" CSR 90 CFM3-WAY

6"Ø

8" x 4" CSR

40 CFM3-WAY

5"Ø

7"Ø

3"Ø

4"Ø

10" x 6" CSR 90 CFM3-WAY

6"Ø

5"Ø

7"Ø

JRFASSOCIATES

SCALE

3620 Winding Way

Round Rock Texas 78664

512-970-9478 Ph

ISSUE DATE

SHEET NUMBER

PROJECT NUMBER

1322013

05-27-2014

LANDMARK SAN ANTONIO

C 2010 BY JRF ASSOCIATESALL RIGHTS RESERVED.

THE DESIGNS DEPICTED HEREIN ARE THE SOLEPROPERTY OF JRF ASSOCIATES AND MAY NOT BEREPRODUCED IN ANY FORM WITHOUT WRITTENPERMISSION. ALL DESIGNS ARE BASED ON THEINFORMATION FROM OTHERS AND TO BE USEDON LANDMARK SAN ANTONIO APARTMENTS

Firm registration number

f-15222

Automation Engineering

PERMIT SET

M5

1/4" = 1' - 0"

1/4" = 1'-0"

UNIT TYPE A6

1/4" = 1'-0"

UNIT TYPE A6-A

1/4" = 1'-0"

UNIT TYPE A6-B

1/4" = 1'-0"

UNIT TYPE A6-C

1/4" = 1'-0"

UNIT TYPE A7

1/4" = 1'-0"

UNIT TYPE A8

1/4" = 1'-0"

UNIT TYPE A8-A

4 OWNERS CHANGES 3-27-2014

4 REVISEDBACKGROUND, A6,

A6A, A6B, A6C

5 REVISEDBACKGROUND,

OWNERS CHANGES

5 OWNERS CHANGES 4-21-2014

Page 6: LANDMARK SAN ANTONIO€¦ · above finished floor sidewall supply register ceiling supply register return air filter grille return air register fan coil return air rooftop a/c unit

36" x 12"

RAFG

T

A

B

D

F

H

I

K

12" x 6" CSR 190 CFM3-WAYW/CRD

12" x 6" CSR 220 CFM3-WAYW/CRD

8"Ø

8"Ø

10"Ø

10" x 6" CSR 110 CFM

3-WAYW/CRD

7"Ø

12" x 6" CSR 200 CFM3-WAY

W/CRD

8"Ø

9"Ø

8" x 6" CSR 80 CFM3-WAY

5"Ø

13

HORIZONTAL FAN COIL UNIT MOUNTED INFURR DOWN AS HIGH AS POSSIBLE.

FAN COIL CEILING ACCESS PANEL. PANELSHALL BE GASKETED AND AIR TIGHT.

SHEETROCK UP TO FURR DOWN ONLY

EXHAUST FAN IN WALL, EXTEND DUCT UP TOJOIST SPACE. TOP FLOOR SHALL HAVE THE

OPTION TO ROUTE DUCT DOWN TO JOISTSPACE BELOW.

WALL CAPS, EACH EXHAUST WALL CAP SHALLMAINTAIN A MINIMUM DISTANCE OF 36" FROMANY OPERABLE OPENING TO THE BUILDING

AND SHALL BE SEALED WEATHER TIGHT.

WATER HEATER BY PLUMBING CONTRACTOR.

DRYER VENT UP IN WALL.

DRYER VENT IN TRUSS/JOIST SPACE. EACHDRYER VENT SHALL BE 26 GAUGE RIDGEDSMOOTH METAL WITH ALL JOINTS CONNECTED

IN THE DIRECTION OF AIR FLOW.

MAKEUP AIR LOUVER, REFER TOARCHITECTURAL UNIT PLANS FORCALCULATIONS AND SIZING.

FIRE DAMPER WITH ACCESS PANEL. ALL FIREDAMPERS SHALL BE INSTALLED IN

ACCORDANCE TO ALL SMACNA AND LOCALREQUIREMENTS.

B

A

C

D

E

F

G

H

I

J

MECHANICAL NOTES BY SYMBOL:

EXHAUST VENT IN TRUSS/JOIST SPACE.K

FURR DOWN LEGEND

MECHANICAL CONTRACTOR SHALL VERIFYTHAT ALL DRYER AND EXHAUST VENT HOODS

ARE INSTALLED PER MANUFACTURESREQUIREMENTS AND ARE WEATHER TIGHT.

REFRIGERANT LINE PENETRATION THROUGH ANYPORTION OF THE BUILDING SHALL BE INSTALLEDTO PREVENT ANY ACCESS OF WATER, INSECTS OR

INCLEMENT WEATHER REACHING THE INSIDE OFTHE BUILDING ENVELOPE.

RETURN AIR FURR DOWN, MECHANICAL

CONTRACTOR SHALL VERIFY ALL RETURN AIRFURRING IS AIR TIGHT AND SEPARATE FROMANY NON RETURN FURRING. CONTRACTOR

SHALL ALSO ENSURE THAT RETURN AIR PATH

FROM RETURN AIR GRILL TO AIR HANDLER ISCLEAR OF OBSTRUCTIONS THAT WOULD CAUSE

RESTRICTION TO RETURN AIR.

NON RETURN AIR FURR DOWN - SEPERATE

FROM FURRING USED FOR RETURN AIR.

H

12" x 6" CSR 190 CFM

3-WAYW/CRD

12" x 6" CSR

220 CFM3-WAYW/CRD

8"Ø

8"Ø

10" x 6" CSR 110 CFM

T

G

D

I

24" x 18"RAFG

A

B

C

F

H

K

12" x 6" CSR 160 CFM3-WAY

W/CRD

12" x 6" CSR 170 CFM3-WAY

W/CRD

7"Ø

8"Ø

9"Ø

12" x 6" CSR 180 CFM

3-WAYW/CRD

8"Ø

10" x 6" CSR

90 CFM3-WAY

6"Ø

10" x 6" SSR

140 CFM

7"Ø8" x 6" SSR60 CFM

5"Ø

3"Ø

4"Ø

JRFASSOCIATES

SCALE

3620 Winding Way

Round Rock Texas 78664

512-970-9478 Ph

ISSUE DATE

SHEET NUMBER

PROJECT NUMBER

1322013

05-27-2014

LANDMARK SAN ANTONIO

C 2010 BY JRF ASSOCIATESALL RIGHTS RESERVED.

THE DESIGNS DEPICTED HEREIN ARE THE SOLEPROPERTY OF JRF ASSOCIATES AND MAY NOT BEREPRODUCED IN ANY FORM WITHOUT WRITTENPERMISSION. ALL DESIGNS ARE BASED ON THEINFORMATION FROM OTHERS AND TO BE USEDON LANDMARK SAN ANTONIO APARTMENTS

Firm registration number

f-15222

Automation Engineering

PERMIT SET

M6

1/4" = 1' - 0"

1/4" = 1'-0"

UNIT TYPE A9

1/4" = 1'-0"

UNIT TYPE A9-A

1/4" = 1'-0"

UNIT TYPE A105 REVISED

BACKGROUND,OWNERS CHANGES

5 OWNERS CHANGES 4-21-2014

13 OWNER CHANGES06-30-2014

Page 7: LANDMARK SAN ANTONIO€¦ · above finished floor sidewall supply register ceiling supply register return air filter grille return air register fan coil return air rooftop a/c unit

GD

D

E

EE

A B

C

F

H

I

J

K

K

J

12" x 6" SSR210 CFM

8"Ø

10" x 6" SSR

140 CFM 7"Ø

10" x 6" SSR140 CFM

7"Ø

8" x 6" CSR 80 CFM3-WAY

6"Ø

8" x 4" CSR 40 CFM3-WAY

5"Ø

10" x 6" SSR

130 CFM

7"Ø

8" x 6" CSR 60 CFM3-WAY

5"Ø

3"Ø

3"Ø

4"Ø

9"Ø

4

30" x 12"RAFG

T

12" x 12" RAFG

HORIZONTAL FAN COIL UNIT MOUNTED INFURR DOWN AS HIGH AS POSSIBLE.

FAN COIL CEILING ACCESS PANEL. PANELSHALL BE GASKETED AND AIR TIGHT.

SHEETROCK UP TO FURR DOWN ONLY

EXHAUST FAN IN WALL, EXTEND DUCT UP TOJOIST SPACE. TOP FLOOR SHALL HAVE THEOPTION TO ROUTE DUCT DOWN TO JOISTSPACE BELOW.

WALL CAPS, EACH EXHAUST WALL CAP SHALLMAINTAIN A MINIMUM DISTANCE OF 36" FROMANY OPERABLE OPENING TO THE BUILDINGAND SHALL BE SEALED WEATHER TIGHT.

WATER HEATER BY PLUMBING CONTRACTOR.

DRYER VENT UP IN WALL.

DRYER VENT IN TRUSS/JOIST SPACE. EACHDRYER VENT SHALL BE 26 GAUGE RIDGEDSMOOTH METAL WITH ALL JOINTS CONNECTEDIN THE DIRECTION OF AIR FLOW.

MAKEUP AIR LOUVER, REFER TOARCHITECTURAL UNIT PLANS FORCALCULATIONS AND SIZING.

FIRE DAMPER WITH ACCESS PANEL. ALL FIREDAMPERS SHALL BE INSTALLED IN

ACCORDANCE TO ALL SMACNA AND LOCALREQUIREMENTS.

B

A

C

D

E

F

G

H

I

J

MECHANICAL NOTES BY SYMBOL:

EXHAUST VENT IN TRUSS/JOIST SPACE.K

FURR DOWN LEGEND

MECHANICAL CONTRACTOR SHALL VERIFYTHAT ALL DRYER AND EXHAUST VENT HOODS

ARE INSTALLED PER MANUFACTURESREQUIREMENTS AND ARE WEATHER TIGHT.

REFRIGERANT LINE PENETRATION THROUGH ANYPORTION OF THE BUILDING SHALL BE INSTALLEDTO PREVENT ANY ACCESS OF WATER, INSECTS OR

INCLEMENT WEATHER REACHING THE INSIDE OFTHE BUILDING ENVELOPE.

RETURN AIR FURR DOWN, MECHANICALCONTRACTOR SHALL VERIFY ALL RETURN AIR

FURRING IS AIR TIGHT AND SEPARATE FROMANY NON RETURN FURRING. CONTRACTOR

SHALL ALSO ENSURE THAT RETURN AIR PATH

FROM RETURN AIR GRILL TO AIR HANDLER ISCLEAR OF OBSTRUCTIONS THAT WOULD CAUSE

RESTRICTION TO RETURN AIR.

NON RETURN AIR FURR DOWN - SEPERATE

FROM FURRING USED FOR RETURN AIR.

D

E

J

K

7"Ø

10" x 6" SSR130 CFM

7"Ø

R

5"Ø

3"Ø

4

30" x 12"RAFG

GD

D

E

EE

T

A B

C

F

H

I

J

J

K

K

12" x 6" SSR210 CFM

8"Ø

10" x 6" SSR140 CFM 7"Ø

10" x 6" SSR140 CFM

7"Ø

8" x 6" CSR 80 CFM3-WAY

6"Ø

8" x 4" CSR 40 CFM3-WAY

5"Ø

10" x 6" SSR130 CFM

7"Ø

8" x 6" CSR 60 CFM3-WAY

5"Ø

3"Ø

3"Ø

4"Ø

9"Ø

4

12" x 12"

RAFG

G36" x 12"RAFG

D

D

E

E

AB

C

F

H

I

JJ

K

K

T

14" x 6" CSR240 CFM3-WAYW/CRD

9"Ø

10" x 6" CSR

130 CFM3-WAYW/CRD

7"Ø

10" x 6" SSR140 CFM7"Ø

8" x 6" CSR 60 CFM3-WAY

5"Ø

3"Ø

3"Ø

4"Ø

8" x 4" CSR

40 CFM3-WAY

5"Ø

10" x 6" CSR

130 CFM3-WAYW/CRD

7"Ø

8" x 6" CSR60 CFM3-WAYW/CRD

5"Ø

7"Ø

10"Ø

7"Ø

10"Ø

4

JRFASSOCIATES

SCALE

3620 Winding Way

Round Rock Texas 78664

512-970-9478 Ph

ISSUE DATE

SHEET NUMBER

PROJECT NUMBER

1322013

05-27-2014

LANDMARK SAN ANTONIO

C 2010 BY JRF ASSOCIATESALL RIGHTS RESERVED.

THE DESIGNS DEPICTED HEREIN ARE THE SOLEPROPERTY OF JRF ASSOCIATES AND MAY NOT BEREPRODUCED IN ANY FORM WITHOUT WRITTENPERMISSION. ALL DESIGNS ARE BASED ON THEINFORMATION FROM OTHERS AND TO BE USEDON LANDMARK SAN ANTONIO APARTMENTS

Firm registration number

f-15222

Automation Engineering

PERMIT SET

M7

1/4" = 1' - 0"

1/4" = 1'-0"

UNIT TYPE B1

1/4" = 1'-0"

UNIT TYPE B1-A

1/4" = 1'-0"

UNIT TYPE B1-HC

1/4" = 1'-0"

UNIT TYPE B2

4 OWNERS CHANGES 3-27-2014

4 REVISEDBACKGROUND, B1,

B1A, B1HC, B2

5 REVISEDBACKGROUND,

OWNERS CHANGES

5 OWNERS CHANGES 4-21-2014

Page 8: LANDMARK SAN ANTONIO€¦ · above finished floor sidewall supply register ceiling supply register return air filter grille return air register fan coil return air rooftop a/c unit

25" x 20"RAFG

E

H

K

K

T

A

B

C

D

D

F

I

J

12" x 6" CSR

190 CFM3-WAYW/CRD

8" x 6" SSR70 CFM

5"Ø

8"Ø

8" x 6" CSR 80 CFM

3-WAYW/CRD

8"Ø

10"Ø14" x 6" SSR210 CFM

10" x 6" CSR 100 CFM

3-WAY

6"Ø

8"Ø

10" x 6" SSR

100 CFM6"Ø

3"Ø

3"Ø

4"Ø

12" x 6" SSR170 CFM

10" x 6" CSR

80 CFM3-WAY

6"Ø

8"Ø

9"Ø

4

4

HORIZONTAL FAN COIL UNIT MOUNTED INFURR DOWN AS HIGH AS POSSIBLE.

FAN COIL CEILING ACCESS PANEL. PANELSHALL BE GASKETED AND AIR TIGHT.

SHEETROCK UP TO FURR DOWN ONLY

EXHAUST FAN IN WALL, EXTEND DUCT UP TOJOIST SPACE. TOP FLOOR SHALL HAVE THEOPTION TO ROUTE DUCT DOWN TO JOIST

SPACE BELOW.

WALL CAPS, EACH EXHAUST WALL CAP SHALLMAINTAIN A MINIMUM DISTANCE OF 36" FROMANY OPERABLE OPENING TO THE BUILDINGAND SHALL BE SEALED WEATHER TIGHT.

WATER HEATER BY PLUMBING CONTRACTOR.

DRYER VENT UP IN WALL.

DRYER VENT IN TRUSS/JOIST SPACE. EACHDRYER VENT SHALL BE 26 GAUGE RIDGEDSMOOTH METAL WITH ALL JOINTS CONNECTEDIN THE DIRECTION OF AIR FLOW.

MAKEUP AIR LOUVER, REFER TOARCHITECTURAL UNIT PLANS FORCALCULATIONS AND SIZING.

FIRE DAMPER WITH ACCESS PANEL. ALL FIREDAMPERS SHALL BE INSTALLED IN

ACCORDANCE TO ALL SMACNA AND LOCALREQUIREMENTS.

B

A

C

D

E

F

G

H

I

J

MECHANICAL NOTES BY SYMBOL:

EXHAUST VENT IN TRUSS/JOIST SPACE.K

FURR DOWN LEGEND

MECHANICAL CONTRACTOR SHALL VERIFY

THAT ALL DRYER AND EXHAUST VENT HOODSARE INSTALLED PER MANUFACTURES

REQUIREMENTS AND ARE WEATHER TIGHT.

REFRIGERANT LINE PENETRATION THROUGH ANYPORTION OF THE BUILDING SHALL BE INSTALLEDTO PREVENT ANY ACCESS OF WATER, INSECTS OR

INCLEMENT WEATHER REACHING THE INSIDE OFTHE BUILDING ENVELOPE.

RETURN AIR FURR DOWN, MECHANICALCONTRACTOR SHALL VERIFY ALL RETURN AIR

FURRING IS AIR TIGHT AND SEPARATE FROMANY NON RETURN FURRING. CONTRACTOR

SHALL ALSO ENSURE THAT RETURN AIR PATHFROM RETURN AIR GRILL TO AIR HANDLER IS

CLEAR OF OBSTRUCTIONS THAT WOULD CAUSERESTRICTION TO RETURN AIR.

NON RETURN AIR FURR DOWN - SEPERATE

FROM FURRING USED FOR RETURN AIR.

12" x 6" CSR

190 CFM3-WAYW/CRD

8"Ø

8" x 6" CSR 80 CFM

G36" x 12"RAFG

E

EE

AB

C

D

D

F

H

I

J

K

K

T

12" x 8"RAFG

12" x 6" CSR

170 CFM3-WAYW/CRD

9"Ø

10" x 6" CSR

130 CFM3-WAYW/CRD

7"Ø

12" x 6" CSR 180 CFM3-WAY

W/CRD8"Ø

10"Ø

8" x 6" CSR 90 CFM3-WAY

W/CRD

8" x 4" CSR 50 CFM

3-WAYW/CRD

5"Ø

6"Ø

12" x 6" SSR170 CFM

8"Ø

10" x 6" CSR 110 CFM

3-WAY 6"Ø

9"Ø

10" x 6" CSR

100 CFM3-WAYW/CRD

6"Ø

7"Ø

3"Ø

4"Ø

3"Ø

7"Ø

4

E

AB

C

D

J

K

12" x 6" SSR170 CFM

8"Ø

10" x 6" CSR 110 CFM3-WAY 6"Ø

9"Ø

3"Ø

EE

D

H

K

12" x 6" CSR

180 CFM3-WAYW/CRD

8"Ø

8" x 6" CSR 90 CFM

3-WAYW/CRD

8" x 4" CSR

50 CFM3-WAYW/CRD

5"Ø

6"Ø

10"

3"Ø

4"Ø

JRFASSOCIATES

SCALE

3620 Winding Way

Round Rock Texas 78664

512-970-9478 Ph

ISSUE DATE

SHEET NUMBER

PROJECT NUMBER

1322013

05-27-2014

LANDMARK SAN ANTONIO

C 2010 BY JRF ASSOCIATESALL RIGHTS RESERVED.

THE DESIGNS DEPICTED HEREIN ARE THE SOLEPROPERTY OF JRF ASSOCIATES AND MAY NOT BEREPRODUCED IN ANY FORM WITHOUT WRITTENPERMISSION. ALL DESIGNS ARE BASED ON THEINFORMATION FROM OTHERS AND TO BE USEDON LANDMARK SAN ANTONIO APARTMENTS

Firm registration number

f-15222

Automation Engineering

PERMIT SET

M8

1/4" = 1' - 0"

1/4" = 1'-0"

UNIT TYPE B3

1/4" = 1'-0"

UNIT TYPE B3-A

1/4" = 1'-0"

UNIT TYPE B4

1/4" = 1'-0"

UNIT TYPE B4-A

4 OWNERS CHANGES 3-27-2014

4 REVISED

BACKGROUND, B3,B3,A B4, B4A

ADDED NEW UNIT B4B

1/4" = 1'-0"

UNIT TYPE B4-B

5 REVISEDBACKGROUND,

OWNERS CHANGES

5 OWNERS CHANGES 4-21-2014

Page 9: LANDMARK SAN ANTONIO€¦ · above finished floor sidewall supply register ceiling supply register return air filter grille return air register fan coil return air rooftop a/c unit

G

36" x 12"

RAFG

E

B

A

D

D

F

H

I

J

K

K

10" x 6" CSR

160 CFM3-WAYW/CRD

7"Ø

8" x 8" CSR 170 CFM

4-WAYW/CRD

8"Ø

14" x 6" CSR 200 CFM3-WAYW/CRD

8"Ø

10"Ø

4"Ø

3"Ø

3"Ø

8" x 6" CSR 70 CFM3-WAY

5"Ø8" x 6" CSR 60 CFM3-WAY 5"Ø

8" x 6" CSR

60 CFM3-WAY

5"Ø

14" x 6" CSR210 CFM3-WAY

W/CRD

8" x 6" CSR70 CFM3-WAYW/CRD

5"Ø

8"Ø

6"Ø

12" x 12" RAFG

6

6

13

HORIZONTAL FAN COIL UNIT MOUNTED INFURR DOWN AS HIGH AS POSSIBLE.

FAN COIL CEILING ACCESS PANEL. PANELSHALL BE GASKETED AND AIR TIGHT.

SHEETROCK UP TO FURR DOWN ONLY

EXHAUST FAN IN WALL, EXTEND DUCT UP TOJOIST SPACE. TOP FLOOR SHALL HAVE THEOPTION TO ROUTE DUCT DOWN TO JOISTSPACE BELOW.

WALL CAPS, EACH EXHAUST WALL CAP SHALL

MAINTAIN A MINIMUM DISTANCE OF 36" FROMANY OPERABLE OPENING TO THE BUILDINGAND SHALL BE SEALED WEATHER TIGHT.

WATER HEATER BY PLUMBING CONTRACTOR.

DRYER VENT UP IN WALL.

DRYER VENT IN TRUSS/JOIST SPACE. EACH

DRYER VENT SHALL BE 26 GAUGE RIDGEDSMOOTH METAL WITH ALL JOINTS CONNECTEDIN THE DIRECTION OF AIR FLOW.

MAKEUP AIR LOUVER, REFER TO

ARCHITECTURAL UNIT PLANS FORCALCULATIONS AND SIZING.

FIRE DAMPER WITH ACCESS PANEL. ALL FIREDAMPERS SHALL BE INSTALLED INACCORDANCE TO ALL SMACNA AND LOCAL

REQUIREMENTS.

B

A

C

D

E

F

G

H

I

J

MECHANICAL NOTES BY SYMBOL:

EXHAUST VENT IN TRUSS/JOIST SPACE.K

E

H

10" x 6" CSR 160 CFM3-WAY

W/CRD

7"Ø

8" x 8" CSR 170 CFM4-WAY

W/CRD

14" x 6" CSR

200 CFM3-WAYW/CRD

8"Ø

FURR DOWN LEGEND

MECHANICAL CONTRACTOR SHALL VERIFYTHAT ALL DRYER AND EXHAUST VENT HOODS

ARE INSTALLED PER MANUFACTURESREQUIREMENTS AND ARE WEATHER TIGHT.

REFRIGERANT LINE PENETRATION THROUGH ANYPORTION OF THE BUILDING SHALL BE INSTALLEDTO PREVENT ANY ACCESS OF WATER, INSECTS ORINCLEMENT WEATHER REACHING THE INSIDE OF

THE BUILDING ENVELOPE.

RETURN AIR FURR DOWN, MECHANICALCONTRACTOR SHALL VERIFY ALL RETURN AIRFURRING IS AIR TIGHT AND SEPARATE FROMANY NON RETURN FURRING. CONTRACTOR

SHALL ALSO ENSURE THAT RETURN AIR PATHFROM RETURN AIR GRILL TO AIR HANDLER ISCLEAR OF OBSTRUCTIONS THAT WOULD CAUSE

RESTRICTION TO RETURN AIR.

NON RETURN AIR FURR DOWN - SEPERATEFROM FURRING USED FOR RETURN AIR.

JRFASSOCIATES

SCALE

3620 Winding Way

Round Rock Texas 78664

512-970-9478 Ph

ISSUE DATE

SHEET NUMBER

PROJECT NUMBER

1322013

05-27-2014

LANDMARK SAN ANTONIO

C 2010 BY JRF ASSOCIATESALL RIGHTS RESERVED.

THE DESIGNS DEPICTED HEREIN ARE THE SOLEPROPERTY OF JRF ASSOCIATES AND MAY NOT BEREPRODUCED IN ANY FORM WITHOUT WRITTENPERMISSION. ALL DESIGNS ARE BASED ON THEINFORMATION FROM OTHERS AND TO BE USEDON LANDMARK SAN ANTONIO APARTMENTS

Firm registration number

f-15222

Automation Engineering

PERMIT SET

M9

1/4" = 1' - 0"

1/4" = 1'-0"

UNIT TYPE B5

1/4" = 1'-0"

UNIT TYPE B5-A

4 OWNERS CHANGES 3-27-2014

4 REVISEDBACKGROUNDS

6 CITY COMMENTS 05-02-2014

13 OWNER CHANGES06-30-2014

Page 10: LANDMARK SAN ANTONIO€¦ · above finished floor sidewall supply register ceiling supply register return air filter grille return air register fan coil return air rooftop a/c unit

E

T

A

D

D

E

H

I

J

J

J

J

K

FG

30" x 12"RAFG

B

C

J

K

12" x 12"

RAFG

12" x 6" CSR 180 CFM

3-WAYW/CRD

8"Ø

8" x 6" CSR 80 CFM

3-WAYW/CRD

5"Ø

12" x 6" SSR180 CFM 8"Ø

12" x 6" CSR 180 CFM3-WAY

W/CRD 8"Ø

9"Ø

10" x 6" CSR 90 CFM

3-WAY

5"Ø

8" x 4" CSR

60 CFM3-WAY

5"Ø

10" x 6" CSR 160 CFM

3-WAYW/CRD

7"Ø

10"Ø

12" x 6" SSR

70 CFM

5"Ø

3"Ø

3"Ø

4"Ø

4

HORIZONTAL FAN COIL UNIT MOUNTED INFURR DOWN AS HIGH AS POSSIBLE.

FAN COIL CEILING ACCESS PANEL. PANELSHALL BE GASKETED AND AIR TIGHT.

SHEETROCK UP TO FURR DOWN ONLY

EXHAUST FAN IN WALL, EXTEND DUCT UP TOJOIST SPACE. TOP FLOOR SHALL HAVE THE

OPTION TO ROUTE DUCT DOWN TO JOISTSPACE BELOW.

WALL CAPS, EACH EXHAUST WALL CAP SHALLMAINTAIN A MINIMUM DISTANCE OF 36" FROMANY OPERABLE OPENING TO THE BUILDING

AND SHALL BE SEALED WEATHER TIGHT.

WATER HEATER BY PLUMBING CONTRACTOR.

DRYER VENT UP IN WALL.

DRYER VENT IN TRUSS/JOIST SPACE. EACHDRYER VENT SHALL BE 26 GAUGE RIDGEDSMOOTH METAL WITH ALL JOINTS CONNECTED

IN THE DIRECTION OF AIR FLOW.

MAKEUP AIR LOUVER, REFER TOARCHITECTURAL UNIT PLANS FORCALCULATIONS AND SIZING.

FIRE DAMPER WITH ACCESS PANEL. ALL FIREDAMPERS SHALL BE INSTALLED IN

ACCORDANCE TO ALL SMACNA AND LOCALREQUIREMENTS.

B

A

C

D

E

F

G

H

I

J

MECHANICAL NOTES BY SYMBOL:

EXHAUST VENT IN TRUSS/JOIST SPACE.K

FURR DOWN LEGEND

MECHANICAL CONTRACTOR SHALL VERIFY

THAT ALL DRYER AND EXHAUST VENT HOODSARE INSTALLED PER MANUFACTURES

REQUIREMENTS AND ARE WEATHER TIGHT.

REFRIGERANT LINE PENETRATION THROUGH ANYPORTION OF THE BUILDING SHALL BE INSTALLEDTO PREVENT ANY ACCESS OF WATER, INSECTS OR

INCLEMENT WEATHER REACHING THE INSIDE OFTHE BUILDING ENVELOPE.

RETURN AIR FURR DOWN, MECHANICALCONTRACTOR SHALL VERIFY ALL RETURN AIR

FURRING IS AIR TIGHT AND SEPARATE FROMANY NON RETURN FURRING. CONTRACTOR

SHALL ALSO ENSURE THAT RETURN AIR PATH

FROM RETURN AIR GRILL TO AIR HANDLER ISCLEAR OF OBSTRUCTIONS THAT WOULD CAUSE

RESTRICTION TO RETURN AIR.

NON RETURN AIR FURR DOWN - SEPERATE

FROM FURRING USED FOR RETURN AIR.

E

A

H

J

J

J

KB

12" x 6" CSR 180 CFM3-WAY

W/CRD 8"Ø

9"Ø

10" x 6" CSR 90 CFM3-WAY

5"Ø

8" x 4" CSR 60 CFM

3-WAY

5"Ø

3"Ø

4"Ø

4

E

A

H

J

J

J

K

B

12" x 6" CSR 180 CFM

3-WAYW/CRD

9"Ø

10" x 903-W

5"Ø

8" x 4" CSR 60 CFM3-WAY

5"Ø

4"Ø

4

G

25" x 12"RAFG

J

D

D

A B

C

C

E

E

F

H

I

K

K

T

T

8" x 8" CSR 110 CFM4-WAYW/CRD

10" x 6" SSR150 CFM

14" x 6" SSR200 CFM

10" x 6" CSR 90 CFM3-WAY

8" x 4" CSR 50 CFM3-WAY

5"Ø

6"Ø

8"Ø

5"Ø

7"Ø

3"Ø

3"Ø

4"Ø

14" x 6" SSR200 CFM

8"Ø

12" x 6" SSR

180 CFM

8"Ø

8" x 6" CSR 70 CFM3-WAY

5"Ø

10" x 6" SSR

150 CFM

7"Ø18" x 12"RAFG

12" x 12"

RAFG

12" x 12"

RAFG

12" x 12"

RAFG

G

25" x 12"RAFG

J

D

D

A B

C

C

E

E

18" x 12"RAFG

F

H

I

K

K

T

T

8" x 8" CSR 110 CFM4-WAY

W/CRD

10" x 6" SSR150 CFM

14" x 6" SSR200 CFM

10" x 6" CSR 90 CFM3-WAY

8" x 4" CSR 50 CFM

3-WAY

5"Ø

6"Ø

8"Ø

5"Ø

7"Ø

3"Ø

3"Ø

4"Ø

14" x 6" SSR200 CFM

8"Ø

12" x 6" SSR180 CFM

8"Ø

8" x 6" CSR 70 CFM3-WAY

5"Ø

10" x 6" SSR

150 CFM

7"Ø

12" x 12" RAFG

12" x 12" RAFG

12" x 12" RAFG

JRFASSOCIATES

SCALE

3620 Winding Way

Round Rock Texas 78664

512-970-9478 Ph

ISSUE DATE

SHEET NUMBER

PROJECT NUMBER

1322013

05-27-2014

LANDMARK SAN ANTONIO

C 2010 BY JRF ASSOCIATESALL RIGHTS RESERVED.

THE DESIGNS DEPICTED HEREIN ARE THE SOLEPROPERTY OF JRF ASSOCIATES AND MAY NOT BEREPRODUCED IN ANY FORM WITHOUT WRITTENPERMISSION. ALL DESIGNS ARE BASED ON THEINFORMATION FROM OTHERS AND TO BE USEDON LANDMARK SAN ANTONIO APARTMENTS

Firm registration number

f-15222

Automation Engineering

PERMIT SET

M10

1/4" = 1' - 0"

1/4" = 1'-0"

UNIT TYPE B6

1/4" = 1'-0"

UNIT TYPE B6-A

1/4" = 1'-0"

UNIT TYPE B6-B

1/4" = 1'-0"

UNIT TYPE C1

1/4" = 1'-0"

UNIT TYPE C1-HC

4 OWNERS CHANGES 3-27-2014

4 REVISEDBACKGROUND, B6,

B6A, B6B

5 REVISEDBACKGROUND,

OWNERS CHANGES

5 OWNERS CHANGES 4-21-2014

Page 11: LANDMARK SAN ANTONIO€¦ · above finished floor sidewall supply register ceiling supply register return air filter grille return air register fan coil return air rooftop a/c unit

7

6

5

4

3

2

1CLUBHOUSE AIR HANDLER #1 MOUNTED ON RETURN AIR PLATFORM 32" AFG.

1-8"X10" O.A. INTAKE DUCT WITH DAMPER AT RETURN PLENUM, EXTENDTHROUGH WALL TO GRILLE. EXTEND 3/4" CONDENSATE DRAIN TOHUBDRAIN. INSTALL ELECTRONIC HIGH CONDENSATE LEVEL SHUTOFFSWITCH ON SECONDARY CONDENSATE LINE AT COIL.

DUCT SMOKE DETECTOR (TYP)(SEE DETAIL)

CEILING EXHAUST FAN WITH DISCHARGEDUCT THRU WALL TO WEATHER TIGHT WALL CAP.

BALANCING DAMPER

MECHANICAL NOTES BY SYMBOL

36" x 14"RAR

12" x 10"

12" x 10"

12" x 10"DOWN TO

BELOWPLATFORM

18" x 10"

12" x 12" CSR

320 CFM4-WAY

3 - 4' SIDEWALLADJUSTABLE LINEAR

DIFFUSER

2 - 1" SLOTS50CFM PER FT.

10" Ø

8" Ø

8" Ø

8" Ø

8" Ø

OUTSIDEAIR INTAKE

1 - 4' SIDEWALLADJUSTABLE LINEAR

DIFFUSER2 - 1" SLOTS

50CFM PER FT.

8" x 6" SSR80 CFM

1-WAY

6" Ø

12" x 6" CSR190 CFM3-WAY

12" x 12"RAR

12" x 12"RAR

8"ØJUMPERDUCT

8"ØJUMPER

DUCT

12" x 12"RAR

12" x 12"RAR

10" x 6" CSR

140 CFM3-WAY

10" x 6" CSR120 CFM

3-WAY

7" Ø

7" Ø

8" Ø

10" x 10" CSR190 CFM

4-WAY

10" x 10" CSR190 CFM

4-WAY 8" Ø

8" Ø

8" Ø

8" Ø

12" x 6" CSR170 CFM

3-WAY

9" Ø

14" x 10"

AHU # 2

T

T

12" x 18" RETURN AIRDUCT UP FROM RETURN

AIR GRILLE BELOW

12" x 18" RETURN AIRDUCT UP FROM RETURN

AIR GRILLE BELOW

DOWN FLOW AHU # 5

30" x 20"RAR ATCEILING

12" x 18" RETURN AIRDUCT UP TO HVAC

CLOSET ABOVE

1 - 4' SIDEWALLADJUSTABLE LINEAR

DIFFUSER2 - 1" SLOTS

50CFM PER FT.

1 - 4' SIDEWALLADJUSTABLE LINEAR

DIFFUSER2 - 1" SLOTS

50CFM PER FT.

1 - 5' CEILING MOUNTADJUSTABLE LINEAR

DIFFUSER

2 - 1" SLOTS50CFM PER FT.

1 - 5' CEILING MOUNTADJUSTABLE LINEAR

DIFFUSER2 - 1" SLOTS

50CFM PER FT.

1 - 5' CEILINGMOUNTADJUSTABLE

LINEAR DIFFUSER2 - 1" SLOTS50CFM PER FT.

12" x 18" SUPPLY DUCTDOWN FROM HVAC

CLOSET ABOVE

20" x 12"

14" x 12"

9" Ø

9" Ø

8" Ø

9" Ø

8" Ø

T

36" x 24" RAR ABOVE

BASEBOARD INTO RETURNAIR PLENUM UNDER

PLATFORM

12" x 6" SSR230 CFM3-WAY

12" x 6" SSR230 CFM

3-WAY

12" x 6" SSR230 CFM

3-WAY

12" x 6" SSR230 CFM3-WAY

12" x 6" SSR230 CFM3-WAY

T

12" x 6" CSR200 CFM3-WAY

12" x 6" CSR210 CFM

3-WAY8" Ø

8" Ø

20" x 12"

24" x 12"

12" x 6" CSR225 CFM3-WAY

8" Ø

8" Ø

8" Ø

8" Ø

8" Ø

8" Ø

8" Ø

12" Ø

24" x 12" RAR

24" x 12"

10" x 10" CSR185 CFM4-WAY

10" x 10" CSR

185 CFM4-WAY

10" x 10" CSR185 CFM

4-WAY

10" x 10" CSR

185 CFM4-WAY8" Ø

8" Ø

8" Ø

8" Ø

12" x 6" CSR170 CFM3-WAY

8" Ø

8" Ø

12" x 6" CSR170 CFM3-WAY

12" x 12" CSR

470 CFM4-WAY

12" x 12"RAR

10"Ø JUMPERDUCT

12" x 12"RAR

12" x 12"RAR

14" x 8" CSR300 CFM

3-WAY

10" x 6" CSR150 CFM3-WAY

7"Ø 10"Ø

12"Ø

18" x 12"

24" x 24" RAR

24" x 12"

AHU # 4

AHU # 1

THEATER

AEROBICS

COMPUTERROOM

RECEPTION

LEASING

WOMENS

MENS

GREAT ROOM

FITNESS

ASSISTANTMANAGER

GAMEROOM

MANAGER

CLUBHOUSE AIR HANDLER #2 MOUNTED ON RETURN AIR PLATFORM 32" AFG.1-8"Ø O.A. INTAKE DUCT WITH DAMPER AT RETURN PLENUM, EXTEND TOCLOSEST EXTERIOR LOCATION. EXTEND 3/4" CONDENSATE DRAIN TOHUBDRAIN. INSTALL ELECTRONIC HIGH CONDENSATE LEVEL SHUTOFF

SWITCH ON SECONDARY CONDENSATE LINE AT COIL.

OUTSIDEAIR INTAKE

AHU # 3

CLUBHOUSE AIR HANDLER #3 MOUNTED ON RETURN AIR PLATFORM 32" AFG.1-8"Ø O.A. INTAKE DUCT WITH DAMPER AT RETURN PLENUM, EXTEND TOCLOSEST EXTERIOR LOCATION. EXTEND 3/4" CONDENSATE DRAIN TO LAVTAILPIECE. INSTALL ELECTRONIC HIGH CONDENSATE LEVEL SHUTOFF

SWITCH ON SECONDARY CONDENSATE LINE AT COIL.

6

5

6

5

6

6

6

5

EF1

EF2

3" Ø

3" Ø

6" Ø

7

7

8CLUBHOUSE DOWN FLOW AIR HANDLER #5.1-8"Ø O.A. INTAKE DUCT WITH DAMPER AT RETURN PLENUM, EXTENDTO CLOSEST EXTERIOR LOCATION. EXTEND 3/4" CONDENSATE DRAINTO LAV TAILPIECE. INSTALL ELECTRONIC HIGH CONDENSATE LEVEL

SHUTOFF SWITCH ON SECONDARY CONDENSATE LINE AT COIL.

CLUBHOUSE AIR HANDLER #4 MOUNTED ON RETURN AIR PLATFORM 32" AFG.

1-8"Ø O.A. INTAKE DUCT WITH DAMPER AT RETURN PLENUM, EXTEND TOCLOSEST EXTERIOR LOCATION. EXTEND 3/4" CONDENSATE DRAIN TOHUBDRAIN. INSTALL ELECTRONIC HIGH CONDENSATE LEVEL SHUTOFFSWITCH ON SECONDARY CONDENSATE LINE AT COIL.8 3

4

12

4

DOWNDRAFT EXHAUST

SYSTEM. EXTEND 6"EXHAUST DUCT BELOWSITTING BOOTH ANDTERMINATE AT WALLCAP WITH BACKDRAFT

DAMPER

7

JRFASSOCIATES

SCALE

3620 Winding Way

Round Rock Texas 78664

512-970-9478 Ph

ISSUE DATE

SHEET NUMBER

PROJECT NUMBER

1322013

05-27-2014

LANDMARK SAN ANTONIO

C 2010 BY JRF ASSOCIATESALL RIGHTS RESERVED.

THE DESIGNS DEPICTED HEREIN ARE THE SOLEPROPERTY OF JRF ASSOCIATES AND MAY NOT BEREPRODUCED IN ANY FORM WITHOUT WRITTENPERMISSION. ALL DESIGNS ARE BASED ON THEINFORMATION FROM OTHERS AND TO BE USEDON LANDMARK SAN ANTONIO APARTMENTS

Firm registration number

f-15222

Automation Engineering

PERMIT SET

M11

3/16" = 1' - 0"

CLUBHOUSE - FIRST FLOOR - HVAC

3/16" = 1'-0"

CLUBHOUSE - SECOND FLOOR - HVAC

3/16" = 1'-0"

4 OWNERS CHANGES 3-27-2014

4REVISED BACKGROUNDS

7 05-16-2014FIRE COMMENTS

Page 12: LANDMARK SAN ANTONIO€¦ · above finished floor sidewall supply register ceiling supply register return air filter grille return air register fan coil return air rooftop a/c unit

SANYO WALL

MOUNTED A/C

SANYO CONDENSING UNITBROAN THROUGH WALL

EXHAUST FAN MODEL. #512M

BROAN THROUGH WALLEXHAUST FAN MODEL. #L300MG

JRFASSOCIATES

SCALE

3620 Winding Way

Round Rock Texas 78664

512-970-9478 Ph

ISSUE DATE

SHEET NUMBER

PROJECT NUMBER

1322013

05-27-2014

LA

ND

MA

RK

SA

N A

NT

ON

IO

C 2010 BY JRF ASSOCIATESALL RIGHTS RESERVED.

THE DESIGNS DEPICTED HEREIN ARE THE SOLEPROPERTY OF JRF ASSOCIATES AND MAY NOT BEREPRODUCED IN ANY FORM WITHOUT WRITTEN

PERMISSION. ALL DESIGNS ARE BASED ON THEINFORMATION FROM OTHERS AND TO BE USED

ON LANDMARK SAN ANTONIO APARTMENTS

Firm registration number

f-15222

Automation Engineering

PERMIT SET

M12

1/4" = 1' - 0"

MAINTENANCE BUILDING

1/4" = 1'-0"

Page 13: LANDMARK SAN ANTONIO€¦ · above finished floor sidewall supply register ceiling supply register return air filter grille return air register fan coil return air rooftop a/c unit

JRFASSOCIATES

SCALE

3620 Winding Way

Round Rock Texas 78664

512-970-9478 Ph

ISSUE DATE

SHEET NUMBER

PROJECT NUMBER

1322013

05-27-2014

LANDMARK SAN ANTONIO

C 2010 BY JRF ASSOCIATESALL RIGHTS RESERVED.

THE DESIGNS DEPICTED HEREIN ARE THE SOLEPROPERTY OF JRF ASSOCIATES AND MAY NOT BEREPRODUCED IN ANY FORM WITHOUT WRITTENPERMISSION. ALL DESIGNS ARE BASED ON THEINFORMATION FROM OTHERS AND TO BE USEDON LANDMARK SAN ANTONIO APARTMENTS

Firm registration number

f-15222

Automation Engineering

PERMIT SET

N/A

M13

Page 14: LANDMARK SAN ANTONIO€¦ · above finished floor sidewall supply register ceiling supply register return air filter grille return air register fan coil return air rooftop a/c unit

System No. F-C-7001

(Formerly System No. 169)

F Rating - 1 Hr

T Rating - 1/2 Hr

1. Floor-Ceiling Assembly - The 1 hr fire-rated wood joist floor-ceiling assembly shall

be constructed of the materials and in the manner specified in the individual L500 Series

Floor-Ceiling Designs in the UL Fire Resistance Directory, as summarized below:

A. Flooring System - Lumber or plywood subfloor with finish floor of lumber, plywood

or Floor Topping Mixture* as specified in the individual Floor-Ceiling Design. Max diam

of opening is 11 in.

B. Wood Joists - Nom 2 by 10 in. lumber joists spaced 16 in. OC with nom 1 by 3 in.

lumber bridging and with ends firestopped.

C. Gypsum Board* - Nom 4 ft wide by 5/8 in. thick as specified in the individual

Floor-Ceiling Design. Max diam of opening is 11 in.

1.1 Chase Wall (Optional, not shown) - The through penetrants (Item No. 2) shall be

routed through a 1 hr fire-rated single, double or staggered wood stud/gypsum

wallboard chase wall constructed of the materials and in the manner specified in the

individual U300 Series Wall and Partition Designs in the UL Fire Resistance Directory and

shall include the following construction features:

A. Studs - Nom 2 by 6 in. or double nom 2 by 4 in. lumber studs.

B. Sole Plate - Nom 2 by 6 in. or parallel 2 by 4 in. lumber plates, tightly butted.

C. Top Plate - The double top plate shall consist of two nom 2 by 6 in. or two sets of

parallel 2 by 4 in. lumber plates, tightly butted. Max diam of opening is 5 in.

D. Gypsum Board* - Thickness, type, number of layers and fasteners shall be as

specified in individual Wall and Partition Design.

2. Steel Vent Duct - Nom 4 in. diam (or smaller) No. 30 gauge (or heavier) galv steel

vent duct or nom 10 in. diam (or smaller) No. 28 gauge (or Heavier) galv steel vent

duct. Diam of openings to be max 1 in. larger than outside diam of duct. Duct to be

installed approx midway between wood joists and installed either concentrically or

eccentrically in opening. The annular space between the duct and the periphery of

opening shall be min 0 in. (point contact) to max 1 in. Duct to be rigidly supported on

both sides of floor-ceiling assembly.

3. Fill,Void or Cavity Materials* - Caulk or Sealant - Min 3/4 in. thickness of fill

material applied within the annulus, flush with top surface of floor or sole plate. Min 5/8

in. thickness of fill material applied within the annulus, flush with bottom surface of

ceiling or top plate. An additional min 1/4 in. crown of fill material applied to perimeter

of duct at its egress from the top of flooring and underside of ceiling or from top of sole

plate and underside of top plate.

3M COMPANY - CP 25WB+ caulk or FB-3000 WT sealant

*Bearing the UL Classification Marking

JRFASSOCIATES

SCALE

3620 Winding Way

Round Rock Texas 78664

512-970-9478 Ph

ISSUE DATE

SHEET NUMBER

PROJECT NUMBER

1322013

05-27-2014

LANDMARK SAN ANTONIO

C 2010 BY JRF ASSOCIATESALL RIGHTS RESERVED.

THE DESIGNS DEPICTED HEREIN ARE THE SOLEPROPERTY OF JRF ASSOCIATES AND MAY NOT BEREPRODUCED IN ANY FORM WITHOUT WRITTENPERMISSION. ALL DESIGNS ARE BASED ON THEINFORMATION FROM OTHERS AND TO BE USEDON LANDMARK SAN ANTONIO APARTMENTS

Firm registration number

f-15222

Automation Engineering

PERMIT SET

N/A

M14

Page 15: LANDMARK SAN ANTONIO€¦ · above finished floor sidewall supply register ceiling supply register return air filter grille return air register fan coil return air rooftop a/c unit

DRYERBOX MODEL 350

DETAILS FOR 4" STRUCTURAL WALL

SCALE

MATERIAL

INSTALLATION

PRODUCT

DRYERBOX

REFER TO NOTES

SEE DETAIL

DATE

DRYERBOX DETAIL

DRYER VENTING: MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR

RUNNING ALL DUCTWORK FOR THE DRYER EXHAUST SYSTEM. ALL

CONCEALED DRYER DUCTING MUST BE RIGID METAL (GALVANIZED OR

ALUMINUM) MINIMUM OF 4" IN DIAMETER, SMOOTH 30 GA. CLEAN,

UNOBSTRUCTED, FRICTIONLESS DUCTS (NO FLEXIBLE DUCT ALLOWED IN

CONCEALED AREAS). SEAL ALL JOINTS WITH FOIL BACKED PRESSURE

SENSITIVE DUCT TAPE MEETING THE REQUIREMENTS OF UL 181. DUCT

JOINTS SHALL BE INSTALLED SO THAT THE MALE END OF THE DUCT

POINTS IN THE DIRECTION OF THE AIRFLOW. DO NOT USE RIVETS OR

SCREWS IN THE JOINTS OR ANYWHERE ELSE IN THE DUCT AS THESE WILL

ENCOURAGE LINT COLLECTION.

DRYERBOX® RECEPTACLE (WWW.DRYERBOX.COM) SHALL BE METAL AND

BE INSTALLED AS LOW AS POSSIBLE AS TO PERMIT THE PROPER AND SAFE

COLLECTION OF THE DRYER TRANSITION HOSE. DRYERBOX SHOULD BE

RESTING ON THE BOTTOM PLATE AND BE LOCATED AT OR NEAR THE

CENTERLINE OF THE PROPOSED DRYER APPLIANCE. RIGID DUCT SHOULD

PENETRATE DRYERBOX PORT 2 INCHES TO PROVIDE FOR FUTURE

CONNECTION AND STORAGE OF TRANSITION HOSE. BASEBOARD SHALL BE

"BUTTED" UP TO THE FIXED EXTENSION RIM AND SLIGHTLY BACK-CUT.

DRYERBOX SHOULD BE CAULKED AND THEN PAINTED WITH THE TRIM

PAINT. FOR USAGE IN A ONE-HOUR WALL ASSEMBLY, UL REQUIRES THAT

BATT INSULATION BE STUFFED AROUND THE DRYERBOX AND IN THE

ENTIRE WALL CAVITY CELL.

DRYERBOX INSTALLATION

RIDGID PIPE NOT TO EXCEED

2" THROUGH DRYER BOX

FLEX TRANSITION

HOSE

MOUNT DRYERBOX AS LOW AS

POSSIBLE UNLESS YOU HAVE A

PEDASTAL OR STACKABLE DRYER

FIRRING STRIP ON

2X4

JRFASSOCIATES

SCALE

3620 Winding Way

Round Rock Texas 78664

512-970-9478 Ph

ISSUE DATE

SHEET NUMBER

PROJECT NUMBER

1322013

05-27-2014

LANDMARK SAN ANTONIO

C 2010 BY JRF ASSOCIATESALL RIGHTS RESERVED.

THE DESIGNS DEPICTED HEREIN ARE THE SOLEPROPERTY OF JRF ASSOCIATES AND MAY NOT BEREPRODUCED IN ANY FORM WITHOUT WRITTENPERMISSION. ALL DESIGNS ARE BASED ON THEINFORMATION FROM OTHERS AND TO BE USEDON LANDMARK SAN ANTONIO APARTMENTS

Firm registration number

f-15222

Automation Engineering

PERMIT SET

N/A

M15

Page 16: LANDMARK SAN ANTONIO€¦ · above finished floor sidewall supply register ceiling supply register return air filter grille return air register fan coil return air rooftop a/c unit

MATCH LINE

MATCH LINE

MATCH LINE

MAT

AREA "A"SECTION 1

AREA "B"

AREA "A"SECTION 1

AREA "A"SECTION 1

MATCH

LINE

AREA"A"

SECTION

"1"

AREA"A"

SECTION

"2"

AREA"B"

MATCH

LINE

MATCH

LINE

JRFASSOCIATES

SCALE

3620 Winding Way

Round Rock Texas 78664

512-970-9478 Ph

ISSUE DATE

SHEET NUMBER

PROJECT NUMBER

1322013

05-27-2014

LANDM

ARK SAN A

NTONIO

C 2010 BY JRF ASSOCIATESALL RIGHTS RESERVED.

THE DESIGNS DEPICTED HEREIN ARE THE SOLEPROPERTY OF JRF ASSOCIATES AND MAY NOT BEREPRODUCED IN ANY FORM WITHOUT WRITTENPERMISSION. ALL DESIGNS ARE BASED ON THEINFORMATION FROM OTHERS AND TO BE USEDON LANDMARK SAN ANTONIO APARTMENTS

Firm registration number

f-15222

Automation Engineering

PERMIT SET

M16

1/8" = 1' - 0"

BUILDING 1 - AREA "A" - SECTION "1" - CONDENSING UNITS

1/8" = 1'-0"

4 OWNERS CHANGES 3-27-2014

4 REVISEDBACKGROUND

13 OWNER CHANGES06-30-2014

ADJUSTEDCONDENSING UNITLOCATIONS - REFERTO ARCHITECTURAL

PLANS FORDIMENSIONS

13

Page 17: LANDMARK SAN ANTONIO€¦ · above finished floor sidewall supply register ceiling supply register return air filter grille return air register fan coil return air rooftop a/c unit

MATCH

LINE

AREA"A"

SECTION"1"

AREA"A"

SECTION"2"

AREA"B"

MATCH

LINE

MATCH

LINE

MATCH LINE

MATCH LINE

AREA "B"

AREA "A"SECTION 2

AREA "A"SECTION 1

AREA "A"

SECTION 2

AREA "A"SECTION 1

JRFASSOCIATES

SCALE

3620 Winding Way

Round Rock Texas 78664

512-970-9478 Ph

ISSUE DATE

SHEET NUMBER

PROJECT NUMBER

1322013

05-27-2014

LANDM

ARK SAN A

NTONIO

C 2010 BY JRF ASSOCIATESALL RIGHTS RESERVED.

THE DESIGNS DEPICTED HEREIN ARE THE SOLEPROPERTY OF JRF ASSOCIATES AND MAY NOT BEREPRODUCED IN ANY FORM WITHOUT WRITTENPERMISSION. ALL DESIGNS ARE BASED ON THEINFORMATION FROM OTHERS AND TO BE USEDON LANDMARK SAN ANTONIO APARTMENTS

Firm registration number

f-15222

Automation Engineering

PERMIT SET

M17

1/8" = 1' - 0"

BUILDING 1 - AREA "A" - SECTION "2" - CONDENSING UNITS

1/8" = 1'-0"

4 OWNERS CHANGES 3-27-2014

4 REVISEDBACKGROUND

13 OWNER CHANGES06-30-2014

ADJUSTEDCONDENSING UNITLOCATIONS - REFERTO ARCHITECTURAL

PLANS FORDIMENSIONS

13

Page 18: LANDMARK SAN ANTONIO€¦ · above finished floor sidewall supply register ceiling supply register return air filter grille return air register fan coil return air rooftop a/c unit

MATCH

LINE

AREA"A"

SECTION"1"

AREA"A"

SECTION"2"

AREA"B"

MATCH

LINE

MATCH

LINE

MATCH LINE

MATCH LINE

AREA "B"

AREA "B"

AREA "B"

JRFASSOCIATES

SCALE

3620 Winding Way

Round Rock Texas 78664

512-970-9478 Ph

ISSUE DATE

SHEET NUMBER

PROJECT NUMBER

1322013

05-27-2014

LANDM

ARK SAN A

NTONIO

C 2010 BY JRF ASSOCIATESALL RIGHTS RESERVED.

THE DESIGNS DEPICTED HEREIN ARE THE SOLEPROPERTY OF JRF ASSOCIATES AND MAY NOT BEREPRODUCED IN ANY FORM WITHOUT WRITTENPERMISSION. ALL DESIGNS ARE BASED ON THEINFORMATION FROM OTHERS AND TO BE USEDON LANDMARK SAN ANTONIO APARTMENTS

Firm registration number

f-15222

Automation Engineering

PERMIT SET

M18

1/8" = 1' - 0"

BUILDING 1 - AREA "B" - CONDENSING UNITS

1/8" = 1'-0"

4 OWNERS CHANGES 3-27-2014

4 REVISEDBACKGROUND

13 OWNER CHANGES06-30-2014

ADJUSTEDCONDENSING UNITLOCATIONS - REFERTO ARCHITECTURAL

PLANS FORDIMENSIONS

13

Page 19: LANDMARK SAN ANTONIO€¦ · above finished floor sidewall supply register ceiling supply register return air filter grille return air register fan coil return air rooftop a/c unit

JRFASSOCIATES

SCALE

3620 Winding Way

Round Rock Texas 78664

512-970-9478 Ph

ISSUE DATE

SHEET NUMBER

PROJECT NUMBER

1322013

05-27-2014

LANDMARK SAN ANTONIO

C 2010 BY JRF ASSOCIATESALL RIGHTS RESERVED.

THE DESIGNS DEPICTED HEREIN ARE THE SOLEPROPERTY OF JRF ASSOCIATES AND MAY NOT BEREPRODUCED IN ANY FORM WITHOUT WRITTENPERMISSION. ALL DESIGNS ARE BASED ON THEINFORMATION FROM OTHERS AND TO BE USEDON LANDMARK SAN ANTONIO APARTMENTS

Firm registration number

f-15222

Automation Engineering

PERMIT SET

M19

1/8" = 1' - 0"

BUILDING 2 - CONDENSING UNITS

1/8" = 1'-0"

4 OWNERS CHANGES 3-27-2014

4 REVISEDBACKGROUND

13 OWNER CHANGES06-30-2014

ADJUSTEDCONDENSING UNITLOCATIONS - REFERTO ARCHITECTURAL

PLANS FORDIMENSIONS

13

Page 20: LANDMARK SAN ANTONIO€¦ · above finished floor sidewall supply register ceiling supply register return air filter grille return air register fan coil return air rooftop a/c unit

JRFASSOCIATES

SCALE

3620 Winding Way

Round Rock Texas 78664

512-970-9478 Ph

ISSUE DATE

SHEET NUMBER

PROJECT NUMBER

1322013

05-27-2014

LANDMARK SAN ANTONIO

C 2010 BY JRF ASSOCIATESALL RIGHTS RESERVED.

THE DESIGNS DEPICTED HEREIN ARE THE SOLEPROPERTY OF JRF ASSOCIATES AND MAY NOT BEREPRODUCED IN ANY FORM WITHOUT WRITTENPERMISSION. ALL DESIGNS ARE BASED ON THEINFORMATION FROM OTHERS AND TO BE USEDON LANDMARK SAN ANTONIO APARTMENTS

Firm registration number

f-15222

Automation Engineering

PERMIT SET

M20

1/8" = 1' - 0"

BUILDING 3 - CONDENSING UNITS

1/8" = 1'-0"

4 OWNERS CHANGES 3-27-2014

4 REVISEDBACKGROUND

13 OWNER CHANGES06-30-2014

ADJUSTEDCONDENSING UNITLOCATIONS - REFERTO ARCHITECTURAL

PLANS FORDIMENSIONS

13

Page 21: LANDMARK SAN ANTONIO€¦ · above finished floor sidewall supply register ceiling supply register return air filter grille return air register fan coil return air rooftop a/c unit

JRFASSOCIATES

SCALE

3620 Winding Way

Round Rock Texas 78664

512-970-9478 Ph

ISSUE DATE

SHEET NUMBER

PROJECT NUMBER

1322013

05-27-2014

LANDMARK SAN ANTONIO

C 2010 BY JRF ASSOCIATESALL RIGHTS RESERVED.

THE DESIGNS DEPICTED HEREIN ARE THE SOLEPROPERTY OF JRF ASSOCIATES AND MAY NOT BEREPRODUCED IN ANY FORM WITHOUT WRITTENPERMISSION. ALL DESIGNS ARE BASED ON THEINFORMATION FROM OTHERS AND TO BE USEDON LANDMARK SAN ANTONIO APARTMENTS

Firm registration number

f-15222

Automation Engineering

PERMIT SET

M21

1/8" = 1' - 0"

BUILDING 4 - AREA " A " - CONDENSING UNITS

1/8" = 1'-0"

4 OWNERS CHANGES 3-27-2014

4 REVISEDBACKGROUND

13 OWNER CHANGES06-30-2014

ADJUSTEDCONDENSING UNITLOCATIONS - REFERTO ARCHITECTURAL

PLANS FORDIMENSIONS

13

Page 22: LANDMARK SAN ANTONIO€¦ · above finished floor sidewall supply register ceiling supply register return air filter grille return air register fan coil return air rooftop a/c unit

JRFASSOCIATES

SCALE

3620 Winding Way

Round Rock Texas 78664

512-970-9478 Ph

ISSUE DATE

SHEET NUMBER

PROJECT NUMBER

1322013

05-27-2014

LANDMARK SAN ANTONIO

C 2010 BY JRF ASSOCIATESALL RIGHTS RESERVED.

THE DESIGNS DEPICTED HEREIN ARE THE SOLEPROPERTY OF JRF ASSOCIATES AND MAY NOT BEREPRODUCED IN ANY FORM WITHOUT WRITTENPERMISSION. ALL DESIGNS ARE BASED ON THEINFORMATION FROM OTHERS AND TO BE USEDON LANDMARK SAN ANTONIO APARTMENTS

Firm registration number

f-15222

Automation Engineering

PERMIT SET

M22

1/8" = 1' - 0"

BUILDING 4 - AREA " B " - CONDENSING UNITS

1/8" = 1'-0"

4 OWNERS CHANGES 3-27-2014

4 REVISEDBACKGROUND

13 OWNER CHANGES06-30-2014

ADJUSTEDCONDENSING UNITLOCATIONS - REFERTO ARCHITECTURAL

PLANS FORDIMENSIONS

13

Page 23: LANDMARK SAN ANTONIO€¦ · above finished floor sidewall supply register ceiling supply register return air filter grille return air register fan coil return air rooftop a/c unit

JRFASSOCIATES

SCALE

3620 Winding Way

Round Rock Texas 78664

512-970-9478 Ph

ISSUE DATE

SHEET NUMBER

PROJECT NUMBER

1322013

05-27-2014

LANDMARK SAN ANTONIO

C 2010 BY JRF ASSOCIATESALL RIGHTS RESERVED.

THE DESIGNS DEPICTED HEREIN ARE THE SOLEPROPERTY OF JRF ASSOCIATES AND MAY NOT BEREPRODUCED IN ANY FORM WITHOUT WRITTENPERMISSION. ALL DESIGNS ARE BASED ON THEINFORMATION FROM OTHERS AND TO BE USEDON LANDMARK SAN ANTONIO APARTMENTS

Firm registration number

f-15222

Automation Engineering

PERMIT SET

M23

1/8" = 1' - 0"

BUILDING 5 - AREA " A " - CONDENSING UNITS

1/8" = 1'-0"

4 OWNERS CHANGES 3-27-2014

4 REVISEDBACKGROUND

13 OWNER CHANGES06-30-2014

ADJUSTEDCONDENSING UNITLOCATIONS - REFERTO ARCHITECTURAL

PLANS FORDIMENSIONS

13

18 OWNERS CHANGES 9-08-2014ADJUSTED

CONDENSING UNITLOCATIONS DUE TOADDITION OF UNITS

AND TERRACEREVISION

18

Page 24: LANDMARK SAN ANTONIO€¦ · above finished floor sidewall supply register ceiling supply register return air filter grille return air register fan coil return air rooftop a/c unit

JRFASSOCIATES

SCALE

3620 Winding Way

Round Rock Texas 78664

512-970-9478 Ph

ISSUE DATE

SHEET NUMBER

PROJECT NUMBER

1322013

05-27-2014

LANDMARK SAN ANTONIO

C 2010 BY JRF ASSOCIATESALL RIGHTS RESERVED.

THE DESIGNS DEPICTED HEREIN ARE THE SOLEPROPERTY OF JRF ASSOCIATES AND MAY NOT BEREPRODUCED IN ANY FORM WITHOUT WRITTENPERMISSION. ALL DESIGNS ARE BASED ON THEINFORMATION FROM OTHERS AND TO BE USEDON LANDMARK SAN ANTONIO APARTMENTS

Firm registration number

f-15222

Automation Engineering

PERMIT SET

M24

1/8" = 1' - 0"

BUILDING 5 - AREA " B " - CONDENSING UNITS

1/8" = 1'-0"

4 OWNERS CHANGES 3-27-2014

4 REVISEDBACKGROUND

13 OWNER CHANGES06-30-2014

ADJUSTEDCONDENSING UNITLOCATIONS - REFERTO ARCHITECTURAL

PLANS FORDIMENSIONS

13

Page 25: LANDMARK SAN ANTONIO€¦ · above finished floor sidewall supply register ceiling supply register return air filter grille return air register fan coil return air rooftop a/c unit

3

JRFASSOCIATES

SCALE

3620 Winding Way

Round Rock Texas 78664

512-970-9478 Ph

ISSUE DATE

SHEET NUMBER

PROJECT NUMBER

1322013

05-27-2014

LANDMARK SAN ANTONIO

C 2010 BY JRF ASSOCIATESALL RIGHTS RESERVED.

THE DESIGNS DEPICTED HEREIN ARE THE SOLEPROPERTY OF JRF ASSOCIATES AND MAY NOT BEREPRODUCED IN ANY FORM WITHOUT WRITTENPERMISSION. ALL DESIGNS ARE BASED ON THEINFORMATION FROM OTHERS AND TO BE USEDON LANDMARK SAN ANTONIO APARTMENTS

Firm registration number

f-15222

Automation Engineering

PERMIT SET

M25

1/8" = 1' - 0"

BUILDING 5 - FOURTH FLOOR TERRACE / RR

1/8" = 1'-0"

3 02-21-2014OWNERS CHANGES

18 OWNERS CHANGES 9-08-2014

18

UPDATEDTERRACE

BACKGROUND