Kotte MC EA

download Kotte MC EA

of 19

description

Energy Audit report

Transcript of Kotte MC EA

  • Super Market Welikada Kotte Municipal Council

    Energy Auditor: Ruwan Wijemanne (B.ScEng.Hons)

    Organized By:

    Sri Lanka Sustainable Energy Authority Conducted By:

    EnerFab Pvt Ltd 20, First Lane, Koswata Road, Nawala

  • Content

    Introduction

    History Bill Analyse

    Load Profile

    Energy Saving Opportunities

  • Building Introduction Location : Rajagiriya

    Description : 4 storied Building, Sheet roof,

    Court yard

    Usage : 70 Shops, Public Library

    Operation : 7.00 am 9.00 pm

  • Energy Background Grid Electricity and Solar Power are main energy

    sources to the building

    Bill Scope : Library, Common area (Corridor, Wash

    rooms, Outdoor lighting)

    Service Provider LECO

    Tariff GP2

    Monthly Energy Consumption 1,775 kWh

    Maximum Demand 11 kVA

    Monthly Bill 58,000.00 Rs.

  • History Bill Analyses Total electricity bill of common area for 14 months

    0

    2

    4

    6

    8

    10

    12

    14

    16

    18

    20

    0

    500

    1000

    1500

    2000

    2500

    Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb

    Dem

    an

    d (

    kV

    A)

    En

    erg

    y (

    kW

    h)

    Energy Demand

  • History Bill Analyses Time of Use Energy Consumption

    0

    200

    400

    600

    800

    1000

    1200

    Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb

    To

    U E

    nerg

    y C

    onsum

    ption (

    kW

    h)

    Day Peak Off peak

  • History Bill Analyses

    Day 41%

    Peak 31%

    Off peak 28% Day

    42%

    Peak 38%

    Off peak 20%

    Time of Use Energy & Cost Share

    Energy

    Share

    Cost

    Share

  • End User Profile

    Utility wise energy consumption

    Light 71%

    Lift 7%

    Pump 1%

    Fan 18%

    Other 3%

  • Load Profile Demand and Power Factor Variation

    0.500

    0.550

    0.600

    0.650

    0.700

    0.750

    0.800

    0.850

    0.900

    0.950

    1.000

    0.000

    2000.000

    4000.000

    6000.000

    8000.000

    10000.000

    12000.000

    12:1

    51

    4:1

    51

    6:1

    51

    8:1

    52

    0:1

    52

    2:1

    50

    :15

    2:1

    54

    :15

    6:1

    58

    :15

    10:1

    51

    2:1

    51

    4:1

    51

    6:1

    51

    8:1

    52

    0:1

    52

    2:1

    50

    :15

    2:1

    54

    :15

    6:1

    58

    :15

    10:1

    51

    2:1

    51

    4:1

    51

    6:1

    51

    8:1

    52

    0:1

    52

    2:1

    50

    :15

    2:1

    54

    :15

    6:1

    58

    :15

    10:1

    51

    2:1

    51

    4:1

    51

    6:1

    51

    8:1

    52

    0:1

    52

    2:1

    50

    :15

    2:1

    54

    :15

    6:1

    5

    Po

    we

    r F

    ac

    tor

    Dem

    an

    d (

    VA

    )

    Time

    Aperant Power: Triphasic (VA) Power Factor: Triphasic

  • Temperature Profile T & RH profile of the library under mechanical ventilation

    74

    75

    76

    77

    78

    79

    80

    81

    82

    83

    84

    28

    28.5

    29

    29.5

    30

    30.5

    31

    31.5

    0:0

    0

    1:0

    0

    2:0

    0

    3:0

    0

    4:0

    0

    5:0

    0

    6:0

    0

    7:0

    0

    8:0

    0

    9:0

    0

    10

    :00

    11:0

    0

    12:0

    0

    13:0

    0

    14:0

    0

    15:0

    0

    16:0

    0

    17:0

    0

    18:0

    0

    19:0

    0

    20:0

    0

    21:0

    0

    22:0

    0

    23:0

    0

    0:0

    0

    Re

    lati

    ve H

    um

    idit

    y (

    %)

    Tem

    pera

    ture

    (o

    C)

    Time (25-04-2015)

    TEMPERATURE RELATIVE-HUMIDITY

  • Recommendations Tariff Switching

    Switch building tariff to GP1 category from GP2

    Recommendation Switch tariff to GP1 category

    Energy Saving Potential 0 kWh

    Annual energy cost saving 146,000.00 Rs.

  • Recommendations Power Factor Correction

    Building maintain power factor at 0.9 at maximum demand

    and recommended to improve power factor

    Recommendation Install an automatic capacitor

    Monthly Demand Saving

    Potential

    1.1 kVA

    Likely Investment 14,400.00 Rs.

    Annual Energy Cost Saving 29,600.00 Rs.

    SPP 24 Months

  • Recommendations Outdoor lighting system

    Replace 12 Nos of Metal Halides with 20W LED fittings

    Recommendation Replace Metal halides with

    30W LED cobra fittings

    Monthly Energy Saving

    Potential

    367 kWh

    Likely Investment 156,000.00 Rs.

    Annual Energy Cost Saving 84,000.00 Rs.

    SPP 22 Months

  • Recommendations Indoor lighting system

    Replace old inefficient T8 tube light fittings with T5 lights

    Recommendation Replace T8 Tube lights with

    T5 tube lights

    Monthly Energy Saving

    Potential

    276 kWh

    Annual Energy Cost Saving 72,000.00 Rs.

  • Recommendations Solar Net Metering System

    Install solar net metering system to generate buildings own

    power.

    Recommendation Install 15 kWp rooftop solar

    net metering system

    Monthly Energy Saving

    Potential

    1,800 kWh

    Likely Investment 3,000,000.00 Rs.

    Annual Energy Cost Saving 553,500.00 Rs.

    SPP 5.4 years

  • Recommendations General

    Shift peak loads to off peak or day

    Attach identification name tags for each circuit breaker

    Replace damaged solar panels and lamps

  • Recommendations Summary Total energy saving potential except solar net metering

    Parameter Savings Present

    Consumption

    Saving

    Percentage

    Energy (kWh) 7,717 21,296 36%

    Cost (Rs.) 317,000 698,000 45%

  • Questions..?

  • Thank You..!