KGN-HYD-13-2018 - ADDENDUM 1: Page 1 of 42 Kenya Electricity Generating Company Limited KGN-HYD-13-2018 TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS ADDENDUM NO. 1 Kenya Electricity Generating Company Limited, Stima Plaza Phase III, Kolobot Road, Parklands, P.O. Box 47936, Nairobi, Kenya. www.kengen.co.ke April 2018

Transcript of Kenya Electricity Generating Company Limited No 1 KGN-HY… · method statement on how the works...

KGN-HYD-13-2018 - ADDENDUM 1: Page 1 of 42

Kenya Electricity Generating Company Limited

KGN-HYD-13-2018

TENDER FOR SUPPLY, INSTALLATION, TESTING AND

COMMISSIONING OF INDUSTRIAL UNINTERRUPTIBLE POWER

SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE &

TURKWEL POWER STATIONS

ADDENDUM NO. 1

Kenya Electricity Generating Company Limited,

Stima Plaza Phase III, Kolobot Road, Parklands,

P.O. Box 47936,

Nairobi, Kenya.

www.kengen.co.ke

April 2018

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 2 of 42

AMENDED CLAUSES

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 3 of 42

AMENDED CLAUSES

APPENDIX TO INSTRUCTIONS TO TENDERERS

TDS clauses 1 (1.1-page 12), clause 3. (3.2- page 13) and clause 5 (5.1 page14-

17) have been amended as per table below

TDS

Ref.

No

ITT

Clause

No

Amendments of, and Supplements to, Clauses in the Instruction to Tenderers

A. INTRODUCTION

1.1 Date and Time for submission is:

Date: 10th May 2018

Time: 2.00 p.m. (14:00 hrs)

C. PREPARATION OF TENDERS

3.2 Bidder shall submit their offer with all the following documents below

arranged as per the order given below

1) The Form of Tender;

2) Price Schedules (the three schedules)

3) Copy of certificate of incorporation /Registration.

4) Copy of AGPO certificate for youth

5) Copy of NCA registration and practicing certificate (NCA 8 and

above)

6) Copy of ERC registration certificate (class C and above)

7) Tender securing declaration form

8) Mandatory confidential business questionnaire

9) Manufacturer’s authorization forms for each of the following

(i) Industrial UPS system

(ii) Industrial VRLA long life batteries

10) Duly completed and signed Mandatory site visit certificate

11) Copy of Valid Tax Compliance Certificate

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 4 of 42

TDS

Ref.

No

ITT

Clause

No

Amendments of, and Supplements to, Clauses in the Instruction to Tenderers

12) Signed CV of personnel proposed for installation work

13) Signed Warranty and after sales support from manufacturer or

manufacturer representative/ local agent

14) Signed clarifications and addendums

15) Copy of Type test reports & certificates certified by

EU/USA/Canadian National Standards and Testing Authority (NSTA)

or by a third party (not manufacturer or manufacturer subsidiary)

Reputable Testing Authority accredited by EU/USA/Canadian

National Standards and Testing Authority (NSTA) for:

(i) Battery performance type test in accordance to IEC 60896 –

21/22

(ii) UPS performance type tests in accordance to IEC/EN

62040-3

16) Bidders technical offer composed of the following

(i) Duly filled schedule of requirements (two schedules)

(ii) Proposed UPS single line diagram

(iii) Proposed UPS and battery cabinets layout diagram

(iv) Method statement

(v) Programme of works

(vi) UPS manufacturer technical manuals, datasheets, catalogues

and drawings

(vii) Batteries manufacturer technical manuals, datasheets,

catalogues and drawings

5 5.1 Evaluation Criteria

A) Preliminary/Mandatory Evaluation

1) The following documents shall be examined. Each document below

MUST be submitted, duly filled, signed & stamped, authentic and valid

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 5 of 42

TDS

Ref.

No

ITT

Clause

No

Amendments of, and Supplements to, Clauses in the Instruction to Tenderers

for tender submission to be responsive.

a) Duly completed Bill of Quantities, Signed, and Stamped with

date on every page.

b) Duly completed Tender Forms, Signed and stamped with date.

c) Copy of certificate of incorporation /Registration.

d) Copy of AGPO certificate for youth

e) Copy of NCA registration and practicing certificate (NCA 8 and

above)

f) Copy of ERC registration certificate (class C and above)

g) Duly filled and signed mandatory confidential business

questionnaires provided

h) Valid manufacturer authorisation duly filled and signed by

manufacturer for each of the following

(i) Industrial UPS system

(ii) Industrial VRLA long life batteries

i) Duly completed and signed Mandatory site visit certificate

j) Copy of Valid Tax Compliance Certificate

k) Duly filled and signed Tender Securing Declaration form

l) Signed Warranty and after sales support from manufacturer or

manufacturer representative/ local agent

m) Duly filled schedule of requirements (two schedules)

n) Type test reports & certificates certified by EU/USA/Canadian

National Standards and Testing Authority (NSTA) or by a third

party (not manufacturer or manufacturer subsidiary)

Reputable Testing Authority accredited by EU/USA/Canadian

National Standards and Testing Authority (NSTA) for:

(i) Battery performance type test in accordance to IEC 60896 –

21/22

(ii) UPS performance in accordance to IEC/EN 62040-3

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 6 of 42

TDS

Ref.

No

ITT

Clause

No

Amendments of, and Supplements to, Clauses in the Instruction to Tenderers

o) Proposed UPS single line diagram

p) Proposed UPS and battery cabinet layout diagrams

2) Bid offer shall also be examined to ensure:

a) The Tender has been signed by the person lawfully authorized

to do so;

b) Completeness of Tender – submission of the required number

of copies,

c) sequential organization of the bid document

d) Pagination/serialization of all pages of the bid document

Note:

Only tenders which meet the preliminary requirements shall be subjected to

technical evaluation and shall not subsequently be made responsive by the

tenderer correcting the nonconformity

(B) Technical Evaluation

I

t

e

m

Description Requirement Bidder

complianc

e (yes/no)

1 Compliance

to

Specification

All UPS equipment and Battery

banks offered shall comply fully

with the tender specifications.

All entries in the schedule of

requirements TENDERER’S OFFER

column have been filled

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 7 of 42

TDS

Ref.

No

ITT

Clause

No

Amendments of, and Supplements to, Clauses in the Instruction to Tenderers

Any empty cell/entry shall lead to

rejection of the bid.

All items in the schedules of

requirements have been supported

by manufacturer technical

datasheets, catalogues, manuals,

drawings or test reports

Bidder meets or exceeds all the

employer requirements in the

schedules of requirements

All items in the price schedule have

been quoted for

The offered UPS shall be Industrial

designed for industrial environment

of: temperature 5°C - 40°C

continuous, humidity ≥90%,

altitude ≥1000m without derating

and vibration 0.2g. standards

3 Evidence of

after sales

support and

warranty

services

Attach manufacturers’ statement of

commitment to extend warranty for

the equipment to be supplied.

4 Method

statement

and

programme

of works

Bidder shall submit comprehensive

method statement on how the works

will be implemented and a complete

program of works. The method

statement shall cover: -

• Preliminary works

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 8 of 42

TDS

Ref.

No

ITT

Clause

No

Amendments of, and Supplements to, Clauses in the Instruction to Tenderers

• UPS and Battery banks

installation works.

• Test and Commissioning

procedures.

• Safety arrangement

• Waste management

Submitted programme of works is

complete, covers all items of the

requirements and fits the offered

delivery time

The method statements are

comprehensive and pragmatic

Delivery time does not exceed nine

months

5 Qualified

full time

Technical

Staff.

1. project Manager with

Degree /Higher National Diploma

and minimum 5 years’ experience

in similar works

2. Site supervisor with Diploma

Certificate and at least 5 years’

experience in similar works.

CVs should be signed by authorized

representative of the bidder. The

CVs should include mobile

telephone and email contacts of the

staff. KenGen will verify

information given.

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 9 of 42

TDS

Ref.

No

ITT

Clause

No

Amendments of, and Supplements to, Clauses in the Instruction to Tenderers

7 Manufacture

r

Authorisatio

n

Valid, authentic and signed

manufacturer authorisation has

been provided for the following

1. Complete Industrial UPS

system

2. VRLA industrial type long life

batteries

8 Warranty 1-year warranty from date of

commissioning.

9 Preliminary

drawings

submitted

The UPS SLD clearly shows the

offered UPS components and meets

requirements

The offered cabinets shall fit the

available space

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 10 of 42

SPECIFICATIONS AND BILLS OF QUANTITIES

GENERAL REQUIREMENTS

2. SCOPE OF WORK.

Scope of work clause (g) (page 38) have been annulled and replaced with the

clause below

f) ……..

g) Decommissioning and buy back of all battery banks that shall be

replaced during the installation works for Gitaru, Kindaruma,

Kiambere, Masinga, Kamburu and Turkwel. The tenderer shall

quote buy back price along with the offer for the old battery banks

as per the existing system with the following specifications:

Station Number

of

batteries

Battery rating

AH

Battery Type

Masinga 72 57.2

Kamburu 108 90

Gitaru 72 74 YUASA, UK SWL1850

Turkwel 72 74 YUASA, UK SWL1850

Kiambere 72 74 YUASA, UK SWL1850

Kindaruma 72 75 HIGH POWER SERIES

Total 468 - -

• Some of Masinga batteries are in Kindaruma

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 11 of 42

TECHNICAL SPECIFICATIONS OF UPS SYSTEMS

5.12. Battery specification

The first six paragraphs of clause 5.12 in the tender (page 49-50) have been annulled and replaced

with the clauses below

5.12.0. Battery system general requirements

h) The battery voltage and capacity shall be such as to fulfil the

inverter input power requirements when the inverter is delivering

its rated output (VA), for an autonomy time of 4hours.

i) The battery system shall consist of two battery banks each with its

own battery cabinet. Each battery bank shall consist of valve

regulated, lead acid batteries (VLRA), with each battery rated at

12V. Batteries shall be connected in series to form a batteries string

one or more parallel battery strings shall be connected to form a

battery bank of a high DC voltage suitable for the UPS rating.

j) Each battery bank shall offer an autonomy of two hours at rated

UPS output giving a total of 4 hours for both battery banks. The

nominal ampere-hour (Ah) capacity of the battery system supplied

with the UPSs shall be for 4hr autonomy at full load The Nominal

Ampere-hour capacity of the battery shall be calculated in line

with a battery manufacturer’s approved battery sizing tool and

shall include all necessary allowances as specified in the datasheet,

required to compensate ageing effects that result in the progressive

loss of capacity

k) Each battery bank shall have a fused isolator for connecting the

battery bank to the UPS.

l) A cable shall be provided for connecting each battery bank to the

UPS. Cable shall be armoured and rated for 120% of maximum

battery bank current.

m) Estimated battery bank cable length is 25m for Masinga and 50m

for Kamburu

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 12 of 42

TECHNICAL SPECIFICATIONS FOR BATTERIES

.

The technical specifications for batteries in the tender (page 60-61) have been

annulled and replaced with clauses below

1.1 General requirements

1.1.1 The contractor shall supply batteries to Kiambere, Gitaru, Kindaruma and

Turkwel. These batteries shall be installed to operate the UPS’es already

installed in these stations.

1.1.2 The contractor shall also buy all the existing UPS batteries in Kiambere,

Gitaru, Kindaruma, Kamburu, Masinga and Turkwel.

1.1.3 The existing batteries are housed in two cabinets for each station other

than Kamburu which has four cabinets.

1.1.4 The contractor shall collect (buy back) all the existing batteries in all the

six stations if awarded the tender.

1.1.5 The existing battery cabinets shall be re used to house the new batteries

to be supplied in Kiambere, Gitaru, Kindaruma and Turkwel.

1.1.6 For Kaburu and Masinga the battery cabinets shall be removed and new

battery cabinets for the new UPS’es installed. The removed battery cabinet

shall be property of the employer and are not available for buy back.

1.2 Existing Batteries

1.2.1 General battery condition

1.2.1.1 The existing UPS systems at Gitaru, Kindaruma, Kiambere and

Turkwel are each rated at 15kVA. The UPSs are configured to

operate with VRLA maintenance free batteries.

1.2.1.2 The cells are housed in existing cubicles with tray dimensions of

L×W×H = 285 x 165 x 300mm

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 13 of 42

1.2.1.3 Condition of the Batteries in Masinga and Kamburu was shown to

bidders during site visit

1.2.1.4 Battery quantities

Station Number of

batteries

Battery rating

AH

Battery age

Years

Masinga 72 57.2 11

Kamburu 108 90 11

Gitaru 72 74 11

Turkwel 72 74 11

Kiambere 72 74 11

Kindaruma 72 75 11

• Some of Masinga batteries are in Kindaruma

1.2.2 Gitaru batteries rating and condition are as follows

1.2.2.1 Battery AH rating is 74AH

1.2.2.2 Battery manufacturer and model: YUASA UK, SWL1850

1.2.2.3 Battery age: ~11 years 1.2.2.4 Battery condition

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 14 of 42

1.2.2.5 Battery Cabinet

1.2.3 Kiambere batteries rating and condition are as follows

1.2.3.1 Battery AH rating is 74AH

1.2.3.2 Battery manufacturer and model: YUASA UK, SWL1850 1.2.3.3 Battery age: ~11 years

1.2.3.4 Battery condition

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 15 of 42

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 16 of 42

1.2.3.5 Battery Cabinet

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 17 of 42

1.2.4 Kindaruma batteries rating and condition are as follows

1.2.4.1 Battery AH rating is 75AH

1.2.4.2 Battery manufacturer and model: High power series 1.2.4.3 Battery age: ~11 years

1.2.4.4 Battery condition

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 18 of 42

1.2.4.5 Masinga batteries currently in Kindaruma

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 19 of 42

1.2.4.6 Battery cabinet

(a) Kindaruma battery cabinets are similar to what was shown in

Masinga

1.2.5 Turkwel batteries rating and condition are as follows

1.2.5.1 Battery AH rating is 74AH

1.2.5.2 Battery manufacturer and model: YUASA UK, SWL1850 1.2.5.3 Battery age: ~11 years

1.2.5.4 Battery condition

1.2.5.5 Battery cabinet

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 20 of 42

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 21 of 42

1.3 New Batteries Requirements

1.3.1 Specifications for batteries that follow are applicable to batteries to be supplied to Kiambere, Gitaru, Kindaruma and Turkwel that are to operate with already existing UPS’ es in these stations.

1.3.2 The cells shall be housed in existing cubicles with tray dimensions of

L×W×H = 285 x 165 x 300mm

1.3.3 The battery shall be valve regulated, lead acid batteries (VLRA).

1.3.4 The new batteries shall be sized (physical dimensions) to fit the existing

battery cabinets

1.3.5 Batteries shall meet the requirements below

BATTERY CELL UNIT SPECIFICATION

Battery capacity: C10 @ 20°C Ah 74

Nominal voltage V 12

Optimum battery temperature °C 20

Design life @ 20°C years >10

Operating temperature

Charge °C -15 to 50

Discharge °C -20 to 60

CELL casing material ABS

Terminal type Lead post with brass

insert C

Approx. Internal Resistance mΩ 6

Maximum Short Duration Discharge Current

(1min)

A 600

Percentage charge retention at 20°C

1month % 97

3 months % 91

6 months % 85

Battery type VRLA

Number of cells

Kiambere Pcs 75

Gitaru Pcs 75

Kindaruma Pcs 75

Turkwel Pcs 75

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 22 of 42

TOTAL Pcs 300

Charging

Recharge voltage V 13.6

Floating voltage V 12

Recharge current A 10

1.3.6 The batteries shall be industrial type from reputable manufacturers

meeting the following Standards

Subject Standard Reference Standard Title

Environment

& Safety IEC/EN 60068-2-32

Basic Environmental Testing procedures – Part

2

IEC 60695-11-10 Fire Hazard Testing – Part 11-10

Performance IEC 60896 - 22 Stationary Lead Acid Batteries – Part 22: Valve

Regulated types - Requirements

Testing IEC 60896 - 21

Stationary Lead Acid Batteries – Part 22: Valve

Regulated types – Methods of tests

IEC 61056-1 Shock Test (Drop Test) and Vibration Test

1.3.7 Type test reports & certificates certified by EU/USA/Canadian National

Standards and Testing Authority (NSTA) or by a third party (not

manufacturer or manufacturer subsidiary) Reputable Testing Authority

accredited by EU/USA/Canadian National Standards and Testing

Authority (NSTA) shall be provided for battery performance type test in

accordance to IEC 60896 – 21/22

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 23 of 42

SCHEDULE OF REQUIREMENTS

The Schedule of requirements in the tender (page 62-68) have been annulled

and replaced with schedules and clauses below

1.1 CONDITIONS FOR FILLING THE SCHEDULES

1.1.1 All entries in the TENDERER’S OFFER column MUST be filled, any empty

cell/entry shall lead to rejection of the bid.

1.1.2 All bidders’ responses MUST be supported by manufacturer technical

datasheets, manuals or catalogues for them to be considered by the

employer. Responses not supported by manufacturer data

sheets/catalogue/manual shall be invalid

1.2 TECHNICAL SCHEDULE 1

20 KVA INDUSTRIAL UPS SYSTEMS (3) FOR KAMBURU (2) AND MASINGA (1)

INDUSTRIAL UPS SYSTEM UNIT EMPLOYER REQUIREMENT TENDERER’S OFFER

GENERAL – – –

Quantity required Unit Three (3)

System Power rating kVA Twenty (20)

Type - Industrial UPS for industrial

environment (temperature,

humidity, vibration)

UPS power connections - 3 Phase In/ Single Phase Out

Number of converter modules Unit Two (2)

Topology Online double conversion

Power Converter Configuration Redundant - 2N

Industrial UPS type Modular

Power Converter layout withdrawable (draw out)

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 24 of 42

INDUSTRIAL UPS SYSTEM UNIT EMPLOYER REQUIREMENT TENDERER’S OFFER

Number of battery banks per UPS

unit

Unit Two (2)

Number of UPS panels per UPS unit no One (1)

Number battery bank cabinets per

UPS unit

no Two (2)

INPUT SPECIFICATIONS – – –

Input power factor 0.99

Input Voltage V 3X415+N

Total Harmonic Distortion (THDI) % ≤4%

Connections L1, L2, L3, N

OUTPUT SPECIFICATIONS – – –

Rated output voltage V 1 × 240 V+N

Output range % ±10

FREQUENCY Hz 50

Output voltage distortion % <4

Overload Capacity % 150% 1min, 125% 10min

Output short capability A 2.7 x Inom

Power factor 0.95

Crest factor 3:1

STATIC BYPASS SPECIFICATIONS – – –

Rated voltage V 1 × 240 V+N

FREQUENCY Hz 50

Rated capacity as % UPS rating % 100

Overload Capacity % 110 continuous

Static bypass transfer time ms <6

MANUAL BYPASS SWITCH (MBS): – – –

Connections L, N

Voltage rating V 1 × 240 V+N

Frequency Hz 50

Rated current A 200

MBS AUX contact At least 1CO

ENVIRONMENT AND PHYSICAL

FEATURES

– – –

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 25 of 42

INDUSTRIAL UPS SYSTEM UNIT EMPLOYER REQUIREMENT TENDERER’S OFFER

Storage temperature °C -25 to 70

Operating temperature °C 5 to 45

Humidity % 5 to 95, without

condensation

Altitude m 1000m without derating

Degree of protection IP42

Colour RAL 7035

Cable entry Bottom

Operating and maintenance access Front access

Ventilation (N+1 Redundant

ventilation fans)

Forced ventilation with

monitored fans

UPS maximum Panel dimensions – – –

Height mm 2200

Width mm 1200

Length mm 800

Maximum Weight Kg Max 650

Lifting Eyes Required

STANDARDS – – –

Safety IEC / EN 62040-1

Electromagnetic

Compatibility

IEC / EN 62040-2

Performance IEC / EN 62040-3

Environmental aspects IEC/EN 62040-4

Manufacturing ISO 9001:2015, ISO

14001:2015, OHSAS

18001

GALVANIC ISOLATION

TRANSFORMER

– – –

At Rectifier input Required

At Inverter output Required

Integrated back feed protection Required

INDUSTRIAL HMI INTERFACE – – –

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 26 of 42

INDUSTRIAL UPS SYSTEM UNIT EMPLOYER REQUIREMENT TENDERER’S OFFER

with graphical display, control

push keys, UPS operating status

indication and programmable

alarm section

Required

CONTROLLER INTERFACE TO

EMPLOYER SCADA

– – –

Modbus TCP/IP with Ethernet

port

Required

Modbus RS-485 with terminal

connection

Required

Detailed Configuration manual Required

USER CONFIGURABLE (RELAY)

INPUTS/ OUTPUTS

– – –

a) Input signals, Minimum No. Three (3)

b) Output signals,

Minimum

No. Nine (9)

ALARM LED INDICATIONS – – –

a) Mains input failure Required

b) Battery Low Required

c) Battery discharged Required

d) Battery disconnected Required

e) MBS Closed Required

f) Over temperature Required

g) UPS module Fan failure Required

h) Spare Required

PROTECTION FUNCTIONS – – –

1. Manual bypass switch

closed

Required

2. Over temperature Required

3. Fan failure Required

4. Main input failure Required

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 27 of 42

INDUSTRIAL UPS SYSTEM UNIT EMPLOYER REQUIREMENT TENDERER’S OFFER

5. Bypass operation Required

6. Battery operation Required

7. Battery low Required

8. Battery disconnected Required

9. Input breaker opened Required

10. Bypass breaker opened Required

11. MBS closed Required

12. Overload Required

13. Common alarm Required

14. Manual bypass switch

closed

Required

BATTERY CHARGER – – –

Battery charger rating To be sized for a full battery

recharge from 20% -100%

SoC in six hours with a

standing load of 50%

(10KVA) connected to the

UPS

Battery charger voltage rating V Bidder to state

Battery charger current rating A Bidder to state

BATTERIES – – –

Safety standard compliance IEC/EN 60068-2-32

IEC 60695-11-10

Performance standard compliance IEC 60896 - 22

Testing standard IEC 60896 - 21

IEC 61056-1

Battery type Industrial VRLA Battery

Battery Nominal Voltage V 12V

Ampere-Hour Rating @ 20°C Bidder to state

Battery temperature sensor Required

Temperature compensation - Required

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 28 of 42

INDUSTRIAL UPS SYSTEM UNIT EMPLOYER REQUIREMENT TENDERER’S OFFER

Guaranteed battery operating life

at 20°C temperature

years >Ten (10)

Battery Autonomy @100% load Hours Four(4)

OTHER FEATURES – – –

Panel earthing Required

Cold start Required

Schematic drawings interfaced to

employer drawings

Required

Detailed assembly, installation and

service manuals

Required

Assembly, installation layout

drawings

Required

Battery capability test at site Required

1.3 TECHNICAL SCHEDULE 2

BATTERIES for Gitaru, Kindaruma, Kiambere and Turkwel

All the batteries supplied for the all the four stations shall be of the same exact rating of 74Ah

FEATURES UNIT EMPLOYER

REQUIREMENT

TENDERER’S

OFFER

Battery type - Same as existing or

equivalent. Bidder

to state the offered

type, model and

country of

manufacture

Battery capacity: C10 @ 20°C Ah 74

Nominal voltage V 12

Optimum battery temperature °C 20

Operating temperature – – –

Charge °C -15 to 50

discharge °C -20 to 60

CELL casing material ABS

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 29 of 42

FEATURES UNIT EMPLOYER

REQUIREMENT

TENDERER’S

OFFER

Terminal type Lead post with

brass insert C

Approx. Internal Resistance mΩ 6

Maximum Short Duration Discharge Current

(1min)

A 600

Percentage charge retention at 20°C – – –

1month % 97

3 months % 91

6 months % 85

Battery type Industrial VRLA

Number of battery cells required Pcs 300

Charging – – –

Rating Ah 74

Recharge voltage V 13.6

Floating voltage V 12

Recharge current A 10

Battery capability test at site Required

Guaranteed battery operating life at 20°C

temperature

years >Ten (10)

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 30 of 42

1.4 BATTERY TESTING EQUIPMENT 1.4.1 The tenderer shall supply a battery analyzer: type Fluke BT521 together

with all accessories necessary for its operation.

1.4.2 The tenderer shall supply Spectro CA-12 Battery Rapid Tester together

with all accessories for testing 12V, 10-500Ah batteries

1.5 METHOD STATEMENT AND PROGRAMME OF WORKS Bidder shall submit comprehensive method statement on how the works will be

implemented and a complete program of works.

1.5.1 The method statement shall cover:

1.5.1.1 Preliminary works

1.5.1.2 UPS and Battery banks installation works.

1.5.1.3 Test and Commissioning procedures.

1.5.1.4 Safety arrangement

1.5.1.5 Waste management

1.5.2 Programme of works shall be provided in a Gantt chart format covering

all the works in a chronological order

1.6 MANUFACTURER AUTHORISATION Valid, authentic and signed manufacturer authorisation to be provided as per the

form provided for the following

1.6.1 Complete Industrial UPS system

1.6.2 VRLA industrial type long life batteries

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 31 of 42

PRICE SCHEDULES

The price schedules in the tender (page 69-71) have been annulled and

replaced with schedules and clauses below

1.1 General requirements 1.1.1 The tenderer shall complete all schedules. Schedules shall be read in

conjunction with the specification.

1.1.2 The total prices in the Main Summary of price schedules shall be deemed

to include for the whole of the contract works in accordance with the

specification.

1.1.3 Any prices omitted from any section or part of prices schedule shall be

deemed to have been included in another section of part.

1.1.4 All prices shall be shown inclusive of duty and of all taxes current at the

time of tendering.

1.1.5 The FINAL/ DISCOUNTED OFFER price of the offer shall be calculated as

follows:

𝐃𝐈𝐒𝐂𝐎𝐔𝐍𝐓𝐄𝐃 𝐎𝐅𝐅𝐄𝐑

= 𝐩𝐫𝐢𝐜𝐞 𝐒𝐮𝐩𝐩𝐥𝐲 𝐎𝐟 𝐔𝐏𝐒’𝐬 & 𝐒𝐜𝐚𝐝𝐚 𝐁𝐚𝐭𝐭𝐞𝐫𝐢𝐞𝐬 𝐓𝐨𝐭𝐚𝐥

− 𝐓𝐨𝐭𝐚𝐥 𝐩𝐫𝐢𝐜𝐞 𝐎𝐟𝐟𝐞𝐫 𝐟𝐨𝐫 𝐛𝐮𝐲 𝐛𝐚𝐜𝐤 𝐨𝐟 𝐁𝐚𝐭𝐭𝐞𝐫𝐢𝐞𝐬

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 32 of 42

1.2 UPS and batteries Price Schedule

NO

.

Item Description

UO

M

Qu

an

tity

Basi

c U

nit

Pri

ce

excl

usi

ve

all

tax

es a

nd

oth

er l

evie

s

Tax

es a

nd

oth

er l

evie

s

(sp

ecif

y)

Un

it P

rice

in

cl.

of

all

tax

es &

lev

ies

Tota

l Pri

ce i

ncl

usi

ve

of

all

lev

ies/

Tax

es

SUPPLY OF UPS’S and BATTERY BANKS – – – – – –

1. 20kVA UPS system complete with battery bank lot 3

2 Delivery to site, Installation, testing and commissioning

works of two (2) 20kVA UPS systems complete with

battery banks at Kamburu Power Station.

Decommissioning of existing UPS at Kamburu

lot 1

3 Delivery to site, Installation, testing and commissioning

works of 20kVA UPS system complete with battery bank

at Masinga Power Station.

Decommissioning of existing UPS at Masinga.

lot 1

GITARU POWER STATION BATTERIES – – – – – –

4 Supply of Gitaru SCADA UPS Batteries pcs 75

5 Delivery to site, Installation, testing and commissioning

of new SCADA UPS batteries, and decommissioning of

old of SCADA UPS Batteries at Gitaru Power Station

lot 1

KINDARUMA POWER STATION BATTERIES – – – – – –

6. Supply of Kindaruma SCADA UPS Batteries pcs 75

7 Delivery to site, Installation, testing and commissioning

of new SCADA UPS batteries, and decommissioning of

old of SCADA UPS Batteries at Kindaruma Power Station

lot 1

KIAMBERE POWER STATION BATTERIES – – – – – –

10 Supply of Kiambere SCADA UPS Batteries pcs 75

11 Delivery to site, Installation, testing and commissioning

of new SCADA UPS batteries, and decommissioning of

old of SCADA UPS Batteries at Kiambere Power Station

lot 1

TURKWEL POWER STATION

12 Supply of Turkwel SCADA UPS Batteries pcs 75

13 Delivery to site, Installation, testing and commissioning

of new SCADA UPS batteries, and decommissioning of

old of SCADA UPS Batteries at Turkwel Power Station

lot 1

TEST EQUIPMENT – – – – – –

15 Battery Analyser; Fluke BT521 plus accessories set 1

16 Spectro CA-12 Battery Rapid Tester plus accessories set 1

OTHER SERVICES

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 33 of 42

NO

.

Item Description

UO

M

Qu

an

tity

Basi

c U

nit

Pri

ce

excl

usi

ve

all

tax

es a

nd

oth

er l

evie

s

Tax

es a

nd

oth

er l

evie

s

(sp

ecif

y)

Un

it P

rice

in

cl.

of

all

tax

es &

lev

ies

Tota

l Pri

ce i

ncl

usi

ve

of

all

lev

ies/

Tax

es

17 Design/Engineering work lot 1

18 Factory acceptance tests lot 1

19 Technical documentation

SUPPLY OF UPS’S & SCADA BATTERIES TOTAL (Ksh.)

Total VAT

Total Other duties

TOTAL INCLUSIVE OF TAXES

1.3 Batteries buy back Price offer

Item Description UOM Quantity Basic Unit Price TOTAL PRICE

BUYBACK OF BATTERIES

1. Buy back of old battery banks Gitaru power station pcs 72

2. Buy back of old battery banks Kindaruma power station pcs 72

3. Buy back of old battery banks Kiambere power station pcs 72

4. Buy back of old battery banks Masinga power station pcs 72

5. Buy back of old battery banks Kamburu power station pcs 108

6. Buy back of old battery banks Turkwel power station pcs 72

Total no. of batteries pcs 468

Total price Offer for buy back of Batteries (Ksh.)

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: AMENDED CLAUSES April 2018 Page 34 of 42

1.4 Total offer Price

Amount (Ksh.)

SUPPLY OF UPS’S & SCADA BATTERIES TOTAL

Less Total price Offer for buy back of Batteries ( )

FINAL / DISCOUNTED OFFER PRICE

Delivery Period……………………………………………………………………………………….

Name: …………………………………… Signature: …………………………

Position in the Firm: ............…………………… Date: …………………………

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: ADDITIONAL CLAUSES April 2018 Page 35 of 42

ADDITIONAL CLAUSES

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: ADDITIONAL CLAUSES April 2018 Page 36 of 42

ADDITIONAL CLAUSES

TECHNICAL SPECIFICATIONS OF UPS SYSTEMS

5.2 Standards

Add the following after the table (page 43) The Batteries shall comply with the applicable sections of the current revision of the following standards: Subject Standard Reference Standard Title

Environment &

Safety IEC/EN 60068-2-32 Basic Environmental Testing procedures – Part 2

IEC 60695-11-10 Fire Hazard Testing – Part 11-10

Performance IEC 60896 - 22 Stationary Lead Acid Batteries – Part 22: Valve

Regulated types - Requirements

Testing IEC 60896 - 21

Stationary Lead Acid Batteries – Part 22: Valve

Regulated types – Methods of tests

IEC 61056-1 Shock Test (Drop Test) and Vibration Test

The bidders shall attach the test certificate to proof compliance to the above standards.

8. Testing & Commissioning

8.1 Type test

Add the following requirements for type test reports

8.1.1 Type test reports & certificates

8.1.1.1 Type test reports & certificates shall be certified by EU/USA/Canadian

National Standards and Testing Authority (NSTA) or by a third party (not

manufacturer or manufacturer subsidiary) Reputable Testing Authority

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: ADDITIONAL CLAUSES April 2018 Page 37 of 42

accredited by EU/USA/Canadian National Standards and Testing

Authority (NSTA).

8.1.1.2 Type Test Reports shall meet the following requirements:

(a) Type Test Reports shall be carried out by a laboratory independent

from the manufacturer.

(b) Where a body other than NSTA stated above is used to certify the

type-test reports, a copy of the certificate of accreditation shall be

attached.

(c) Results of type test shall have been conducted at least 6 months and

not more than ten years prior to the date of tender submission. The

bidder shall submit contact details (Title, email, and fax) of

certifying laboratory.

(d) Testing materials and equipment in Type Test Reports shall have

the same code/ country / manufacturer and technical parameters

as offered materials and equipment. Type tests of non-conforming

materials/equipment shall not be accepted.

(e) Type Test Reports shall include all items tested and results

confirming that they meet the requirements of applied standards

as stipulated in Tender Documents.

(f) Type Test reports shall have Report Numbers for authentication.

(g) Current contact information of the testing and certification

authority shall be provided.

8.1.1.3 Type tests reports and certificates for type tests carried out as per stated

standard less than TEN years from the date of bid opening for the

following equipment specified in the tender MUST be included in the bid:

(a) UPS performance in accordance to IEC/EN 62040-3

(b) UPS environmental aspects for industrial environments in accordance to

IEC/EN 62040-4

(c) Battery performance in accordance to IEC 60896 – 21/22

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: ADDITIONAL CLAUSES April 2018 Page 38 of 42

“add clause 8.4 (page 58)

8.4 Factory Inspection and Testing

8.4.1 Test Procedures

8.4.1.1 The Contractor shall prepare test procedures and result sheets for all

tests. The Contractor shall prepare and execute a testing program which

will establish that specified requirements have been met and that the

items furnished and installed will perform as specified and required.

8.4.1.2 The Contractor shall submit to the Employer program that shall establish

the sequence of the tests, the equipment preparation and operation

procedures to be followed and the DETAILED PROCEDURE for

conducting each test.

8.4.1.3 The test procedures and results sheets shall be approved by the employer

at least two months before the factory tests.

8.4.1.4 All the routine tests stated in the equipment design IEC standard and all

the tests stated in the tender document MUST be incorporated in the test

procedures

8.4.2 Attendance of Employer’s Personnel at Factory Tests

8.4.2.1 The Contractor shall arrange for two Client’s engineers or staff members

to witness tests of major items of equipment at the Contractor

manufacturing plant/s.

8.4.2.2 The Contractor shall submit factory acceptance tests schedule for

approval. After approval by the employer, the Contractor shall invite the

Client’s engineers for factory acceptance tests. A period of at least one

month shall be provided from date of invitation to the date of departure

to the contractor’s country of manufacture to allow enough time for

travelling preparations.

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: ADDITIONAL CLAUSES April 2018 Page 39 of 42

8.4.2.3 Contractor shall be responsible for all travel within country of

manufacture and all other associated costs of stay by client engineers

except accommodation and out of pocket expenses which will be catered

by the employer. Necessary expenses such as inland travel charges in the

Contractor’s manufacturing country shall be included in the Tender.

8.4.2.4 The employer will be responsible for the round-trip airfares between

Kenya and the Contractor’s factory country, accommodation and out of

pocket expenses for employer staff.

8.4.2.5 Contractor shall facilitate visa application for the employer engineers by

providing necessary support documents required by the contractors’

manufacturers’ country

8.4.3 Testing

8.4.3.1 Prior to commencement of the tests, the equipment shall be inspected to

ensure:

a) Correct standards of workmanship and quality

b) Correct identification labels, cabling, tagging, housing and

mounting etc.

c) Adequate accessibility

d) Compliance with the Specification and reviewed drawings

(including compliance with fire safety and materials

requirements)

e) Verification of model numbers, quantities of items etc.

8.4.3.2 All factory tests requirements detailed in the approved factory acceptance

test plan/program shall be carried out.

8.4.3.3 Valid calibration certificates from a third party accredited laboratory for

test equipment to be used during FAT shall be presented to the employer

engineers prior to the beginning of the FAT. Only test equipment with

valid calibration certificates from a third-party laboratory credited by

NTSA (KEBS or equivalent) shall be used.

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: ADDITIONAL CLAUSES April 2018 Page 40 of 42

8.4.3.4 Conduct of the Tests

a) The Contractor shall conduct the tests in accordance with the

approved test procedures and shall enter the results in the

approved result sheets.

b) For each test, the Employer will determine whether the test has

passed or failed. In general, the test will be considered to have

failed if either:

• The result of the test is not in accordance with the expected

result described in the test procedure, or

• The result of the test is in accordance with the expected result

described in the test procedure, but some other unexpected or

unexplained event occurred which the Employer considers to

be a fault

c) Full use shall be made during the tests of operator manuals and

other documentation provided by the Contractor to determine the

accuracy of the tests.

8.4.3.5 Failures

a) The Contractor shall correct all faults found during testing and

shall arrange for the test to be repeated. The test shall only be

repeated when the fault has been remedied and the equipment

demonstrated to function correctly.

b) Where remedial measures involve significant modifications that

might, in the Employer’s opinion, affect the validity of earlier tests

then the Contractor shall repeat the earlier tests and obtain

satisfactory results before repeating the test in which the fault was

first identified.

c) The Employer shall have the right to order the repeat or

abandonment of any test in the event that results demonstrate that

the equipment is significantly non-compliant with the Contract

requirements, without in any way prejudicing his rights under the

contract.

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: ADDITIONAL CLAUSES April 2018 Page 41 of 42

d) The Employer shall have the right to suspend any test in the event

that errors or failures have become unacceptable. The Employer

shall also have the right to suspend any test in the event of a fault

being detected by the Contractor but not reported to the Employer

within 24 hours. In this event, the suspension shall remain in effect

until reporting has been brought up to date to the satisfaction of

the Employer

8.4.3.6 Repeat Tests

a) The Contractor shall correct and re-test every fault detected during

the tests.

b) Time spent by the Employer witnessing re-tests or waiting at the

Contractor's premises or the test site while corrections are made

prior to re-test, shall be charged to the Contractor at the standard

hourly rate for the personnel concerned.

c) All other costs incurred by the Employer as a result of such re-tests,

including accommodation, subsistence and travel charges, will be

charged to the Contractor at cost. If the Employer is required to

return to the Contractor's premises or the test site to witness such

re-tests then time spent by the personnel concerned in travelling

to the site of and witnessing such re-tests, and all charges incurred

by them in so doing, shall be charged to the Contractor.

8.4.3.7 After the tests, detailed test report and employer inspection report shall

be signed by the employer engineers and contractor. These documents

shall then become part of the contract.

8.4.3.8 FAT meeting minutes duly signed by the contractor and the employer

representative shall form part of official project documentation and shall

be required by the employer to approve payment processing by the bank.

As part of the terms of letter of credit.

8.4.3.9 Employer will give consent for shipping ONLY after ALL the issues

discussed in the minutes and noted in the employer inspection report

have been rectified and evidence given to the employer.

TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF INDUSTRIAL

UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR KAMBURU & MASINGA AND SCADA UPS

BATTERY BANKS FOR GITARU, KINDARUMA, KIAMBERE & TURKWEL POWER STATIONS.

KGN-HYD-13-2018 - ADDENDUM 1

KGN-HYD-13-2018 - ADDENDUM 1: ADDITIONAL CLAUSES April 2018 Page 42 of 42

ACKNOWLEDGEMENT OF ADDENDUM NO.1 We, the undersigned hereby certify that the addendum is an integral part of the document and the alterations set out in the clarification has been incorporated in the tender proposal. Signed and Date ………………………………………………………. Tenderer ……………………………………………………………….