Kentucky Army National Guard Steps to Sustainability Kentucky Army National Guard’s Energy Initiatives Jayson McDonald, EIT

Transcript of Kentucky Army National Guard’s Energy Initiativesenergy.ky.gov/renewable/Documents/KYARNG CRERES...

Page 1: Kentucky Army National Guard’s Energy Initiativesenergy.ky.gov/renewable/Documents/KYARNG CRERES Presentation.pdf · Kentucky Army National Guard Steps to Sustainability Kentucky

Kentucky Army National Guard

Steps to Sustainability

Kentucky Army National Guard’s Energy Initiatives

Jayson McDonald, EIT

Page 2: Kentucky Army National Guard’s Energy Initiativesenergy.ky.gov/renewable/Documents/KYARNG CRERES Presentation.pdf · Kentucky Army National Guard Steps to Sustainability Kentucky

Kentucky Army National Guard

KYARNG Energy Management Team

• COL Steve King, Construction & Facility Management Officer

• Joe Sanderson, DMA Director of Facilities

• CPT Kenny Staley, Facilities Manager

• Will Phillips PE, EMIT, Energy Manager II

• Jayson McDonald EIT, Energy Manager I

Page 3: Kentucky Army National Guard’s Energy Initiativesenergy.ky.gov/renewable/Documents/KYARNG CRERES Presentation.pdf · Kentucky Army National Guard Steps to Sustainability Kentucky

Kentucky Army National Guard

From Ashland to Paducah…

• 2,326,406 sqft. of building space

• 12,642 acres of training land

• 57 Armories & Readiness Centers

• 11 Field Maintenance Shops

• 4 Regional Maintenance Shops

• 3 Training Sites – Wendell H. Ford Regional Training Center

– Harold L. Disney Training Site (Artemus)

– Eastern Kentucky Training Site (Hidden Valley)

Page 4: Kentucky Army National Guard’s Energy Initiativesenergy.ky.gov/renewable/Documents/KYARNG CRERES Presentation.pdf · Kentucky Army National Guard Steps to Sustainability Kentucky

Kentucky Army National Guard

Renewable Energy Goals

• 10 USC §2911 (e) Energy Performance Goals & Master Plan for the Department of Defense

– Goal of producing 25% of facility energy with renewable energy sources by 2025.

• Executive Order 13423

– Reduce energy intensity by 3% annually, leading to 30% by the end of 2015.

– 57.62% decrease in Energy Use Index (EUI) from 2003 to 2014.

Page 5: Kentucky Army National Guard’s Energy Initiativesenergy.ky.gov/renewable/Documents/KYARNG CRERES Presentation.pdf · Kentucky Army National Guard Steps to Sustainability Kentucky

Kentucky Army National Guard

Renewable Energy Goals

• Executive Order 13514

– Reduce potable water intensity by 2% annually, leading to 26% by the end of 2020.

• The Net Zero Initiative

Page 6: Kentucky Army National Guard’s Energy Initiativesenergy.ky.gov/renewable/Documents/KYARNG CRERES Presentation.pdf · Kentucky Army National Guard Steps to Sustainability Kentucky

Kentucky Army National Guard

Building Controls Strategy

• KYARNG facilities are integrated into a web-based building automation systems

– Reporting, trending, scheduling, control

• Occupancy schedules and other building parameters are tuned to accurately match facility operation and maximize the benefit of energy consumed

• Advanced Metering Technology

Page 7: Kentucky Army National Guard’s Energy Initiativesenergy.ky.gov/renewable/Documents/KYARNG CRERES Presentation.pdf · Kentucky Army National Guard Steps to Sustainability Kentucky

Kentucky Army National Guard

Integrating Sustainable Design

• Incorporating energy saving techniques during design such as: – Insulation & Durable Materials, Building Envelope

– Building Orientation, Daylight Harvesting

– Efficient HVAC & Ground Source Heat Pumps

– Efficient lighting & Controls

– Cool Roof Systems

• ANSI/ASHRAE/IESNA Standard 90.1 (2004)

• 200 KAR 6:070

• LEED Silver

Page 8: Kentucky Army National Guard’s Energy Initiativesenergy.ky.gov/renewable/Documents/KYARNG CRERES Presentation.pdf · Kentucky Army National Guard Steps to Sustainability Kentucky

Kentucky Army National Guard

Harnessing The Earth:

Geothermal • Facilities with GSHPs:

– Richmond Armed Forces Reserve Readiness Center

– Richmond Armory Expansion

– Richmond Field Maintenance Shop

– Morehead Readiness Center

– Burlington Readiness Center

– Harlan Armory

– NEW Army Aviation Support Facility

• 108 wells at 400ft deep

• $0.21/SF/Year in savings

Page 9: Kentucky Army National Guard’s Energy Initiativesenergy.ky.gov/renewable/Documents/KYARNG CRERES Presentation.pdf · Kentucky Army National Guard Steps to Sustainability Kentucky

Kentucky Army National Guard

Powered by the SUN

• In 2014, the KYARNG total solar production was 824,899 kWh.

• Projected 1.5 MW of PV installed by the end of 2015.

• Estimated 15% of KYARNG total electric from PV by the end of 2015.

0

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

1.8

2010 2011 2012 2013 2014 2015

Cumulative Solar Installed (MW)

Cumlative PV Installed (MW)

Page 10: Kentucky Army National Guard’s Energy Initiativesenergy.ky.gov/renewable/Documents/KYARNG CRERES Presentation.pdf · Kentucky Army National Guard Steps to Sustainability Kentucky

Kentucky Army National Guard

Page 11: Kentucky Army National Guard’s Energy Initiativesenergy.ky.gov/renewable/Documents/KYARNG CRERES Presentation.pdf · Kentucky Army National Guard Steps to Sustainability Kentucky

Kentucky Army National Guard

Page 12: Kentucky Army National Guard’s Energy Initiativesenergy.ky.gov/renewable/Documents/KYARNG CRERES Presentation.pdf · Kentucky Army National Guard Steps to Sustainability Kentucky

Kentucky Army National Guard

Long Lasting Luminaries

• Upgrades of outdated luminaries serves as a simple method of reducing energy consumption and maintenance costs.

• LED luminaries

• Photo/motion sensors

• Daylight Harvesting

Page 13: Kentucky Army National Guard’s Energy Initiativesenergy.ky.gov/renewable/Documents/KYARNG CRERES Presentation.pdf · Kentucky Army National Guard Steps to Sustainability Kentucky

Kentucky Army National Guard

Total Lamps by Fixture Type

0

2000

4000

6000

8000

10000

Total Lamps by Fixture Type

2064

9728

4347

1215 229 41 33

511 378

T-5 T-8 T-12 CFL LED INC Halogen Metal Halides Other

Page 14: Kentucky Army National Guard’s Energy Initiativesenergy.ky.gov/renewable/Documents/KYARNG CRERES Presentation.pdf · Kentucky Army National Guard Steps to Sustainability Kentucky

Kentucky Army National Guard

KW Usage by Fixture

0

50

100

150

200

250

300

350

Total KW Usage by Fixture Type

58

307

165

39 24 3 9

189

16

T-5 T-8 T-12 CFL LED INC Halogen Metal Halides Other

Metal Halides account for 23% for

total usage

Page 15: Kentucky Army National Guard’s Energy Initiativesenergy.ky.gov/renewable/Documents/KYARNG CRERES Presentation.pdf · Kentucky Army National Guard Steps to Sustainability Kentucky

Kentucky Army National Guard

Case Study: MATES, FT Knox

• The KYARNG has seen its largest reductions when pairing lighting upgrades, both interior and exterior, with the installation of solar photovoltaic systems

Page 16: Kentucky Army National Guard’s Energy Initiativesenergy.ky.gov/renewable/Documents/KYARNG CRERES Presentation.pdf · Kentucky Army National Guard Steps to Sustainability Kentucky

Kentucky Army National Guard

Case Study: MATES, FT Knox • Phase 1: Upgrading Exterior Lights & PV Install

– LEDs reduced demand by 79.6KW

– 50 KW Solar

• Phase 2: Interior Lights & Controls

– LEDs reduced demand by 17.9KW

– 30 Daylight Harvesting sensors

– Over 100 Occupancy sensors

• Phase 3: Recoverable Energy

– De-stratification Fans

– Used Oil Furnaces

Page 17: Kentucky Army National Guard’s Energy Initiativesenergy.ky.gov/renewable/Documents/KYARNG CRERES Presentation.pdf · Kentucky Army National Guard Steps to Sustainability Kentucky

Kentucky Army National Guard

Case Study: MATES, FT Knox

1,392,853

1,015,223

848,859

0

200,000

400,000

600,000

800,000

1,000,000

1,200,000

1,400,000

1,600,000

Apr 2011 - MAR 2012 Apr 2012 - MAR 2013 Apr 2013 - MAR 2014

An

nu

al E

lect

rici

ty (

kWh

)

Calendar Year

FT. KNOX MATES FACILITY ELECTRIC USAGE

Solar/Exterior Lighting Project Completed

Interior Lighting Project Completed

Total annual electric consumption reduced by 40%

Page 18: Kentucky Army National Guard’s Energy Initiativesenergy.ky.gov/renewable/Documents/KYARNG CRERES Presentation.pdf · Kentucky Army National Guard Steps to Sustainability Kentucky

Kentucky Army National Guard

Signs of Progress

0

50,000

100,000

150,000

200,000

250,000

300,000

350,000

0

20

40

60

80

100

120

2003 2008 2009 2010 2011 2012 2013 2014

MM

Btu

MM

Btu

pe

r K

SF (

EUI)

Federal Fiscal Year

Kentucky Army National Guard Energy Usage Report

Total Energy (MMBtu)

EUI (MMBtu/KSF)

57.62% Decrease in EUI

Page 19: Kentucky Army National Guard’s Energy Initiativesenergy.ky.gov/renewable/Documents/KYARNG CRERES Presentation.pdf · Kentucky Army National Guard Steps to Sustainability Kentucky

Kentucky Army National Guard

Challenges Ahead

• Rising Energy Costs

– $0.047 per KWh in 2003

– $0.091 per KWh in 2014

• In 2003, KYARNG Energy Bill = $2,479,416

• In 2014, KYARNG Energy Bill = $2,431,393

• Without Energy Savings Initiatives = $5,430,307

Page 20: Kentucky Army National Guard’s Energy Initiativesenergy.ky.gov/renewable/Documents/KYARNG CRERES Presentation.pdf · Kentucky Army National Guard Steps to Sustainability Kentucky

Kentucky Army National Guard

Challenges Ahead

• Energy Awareness

– Behavioral Modification

– Changes in Attitude

• Multiple Distribution Co-ops

– 33 Different Electric Providers

– Multiple Gas & Water Providers

– Multiple tariffs, regulations, & fees

– Multiple rebates & incentives

Page 21: Kentucky Army National Guard’s Energy Initiativesenergy.ky.gov/renewable/Documents/KYARNG CRERES Presentation.pdf · Kentucky Army National Guard Steps to Sustainability Kentucky

Kentucky Army National Guard

QUESTIONS?