Experimental Evaluation Of Cascade Refrigeration Plant
![Page 2: K10854 Experimental evaluation of cascade refrigeration plant](https://reader035.fdocuments.us/reader035/viewer/2022062310/588136ac1a28ab00438b7b95/html5/thumbnails/2.jpg)
NIKHIL PANJWANIMECHANICAL ENGINEERING
KID- K10854
![Page 3: K10854 Experimental evaluation of cascade refrigeration plant](https://reader035.fdocuments.us/reader035/viewer/2022062310/588136ac1a28ab00438b7b95/html5/thumbnails/3.jpg)
Experimental Evaluation of A cascade refrigeration system prototype with CO2 and NH3 for freezing process applications
![Page 4: K10854 Experimental evaluation of cascade refrigeration plant](https://reader035.fdocuments.us/reader035/viewer/2022062310/588136ac1a28ab00438b7b95/html5/thumbnails/4.jpg)
AimTo obtain the optimum value of CO2
condensing temperature
![Page 5: K10854 Experimental evaluation of cascade refrigeration plant](https://reader035.fdocuments.us/reader035/viewer/2022062310/588136ac1a28ab00438b7b95/html5/thumbnails/5.jpg)
Advantages and Disadvantages Of Ammonia RefrigerantAdvantages: naturally available excellent thermodynamic and transport properties as
refrigerant Ozone friendly• Disadvantages: toxicity Flammability Applications at temperatures lower than 35 degree C, the
volumetric displacement requirements of the NH3compressor works out relatively higher.
Evaporating pressure ˂ ambient pressure, could lead to leakage into the system.
![Page 6: K10854 Experimental evaluation of cascade refrigeration plant](https://reader035.fdocuments.us/reader035/viewer/2022062310/588136ac1a28ab00438b7b95/html5/thumbnails/6.jpg)
Advantages and Disadvantages Of CO2Advantages: CO2 is environmentally friendly non-toxic non-explosive easily available can be used in refrigeration processes within a wide range of
temperatures. it is compatible with the oils commonly used in actual
refrigeration systems It offers low pressure ratios and low specific volume values which
when coupled with high pressure levels allows for reduction in size of refrigeration components
Disadvantage: high work pressures (7.2 MPa at 30 C)
![Page 7: K10854 Experimental evaluation of cascade refrigeration plant](https://reader035.fdocuments.us/reader035/viewer/2022062310/588136ac1a28ab00438b7b95/html5/thumbnails/7.jpg)
Characteristics of prototypeDesigned to supply a horizontal plate freezerRefrigeration capacity of the plate freezer is 9 kW, at 50deg C of
evaporating temperature.The operating controller- PLC (Programmable Logic Controller).The controlled variables are: the condensing pressures of NH3, the
evaporating pressure of NH3 and the evaporating pressure of CO2.The condensing pressure of NH3 is controlled by modifying the
velocity of the fans of the air condenser. To control the evaporating pressure ofCO2, a flow line which connects
the CO2 compressor discharge line to its suction line was installed, thus allowing the recirculation of a small portion of the mass flow of compressed CO2. The recirculation of the mass flow of CO2 is controlled using a valve installed in the flow line previously mentioned.
The evaporating pressure of NH3 is controlled by varying the capacity of the high temperature system.
![Page 8: K10854 Experimental evaluation of cascade refrigeration plant](https://reader035.fdocuments.us/reader035/viewer/2022062310/588136ac1a28ab00438b7b95/html5/thumbnails/8.jpg)
Observation
![Page 9: K10854 Experimental evaluation of cascade refrigeration plant](https://reader035.fdocuments.us/reader035/viewer/2022062310/588136ac1a28ab00438b7b95/html5/thumbnails/9.jpg)
Observations...For CO2 refrigerant:
For NH3 refrigerant:
Condensing temperature
increase
Pressure ratio
increase
Electric power
increase
COP decrease
Condensing temperature
increase
COP increase
Electric power
decrease
Pressure ratio
decrease
![Page 10: K10854 Experimental evaluation of cascade refrigeration plant](https://reader035.fdocuments.us/reader035/viewer/2022062310/588136ac1a28ab00438b7b95/html5/thumbnails/10.jpg)
Observations...The optimum CO2 condensing temperatures
experimentally measured were compared to the values of the optimum CO2 condensing temperatures given by several correlations published by different authors. The resulting maximum difference was 2.4%.
![Page 11: K10854 Experimental evaluation of cascade refrigeration plant](https://reader035.fdocuments.us/reader035/viewer/2022062310/588136ac1a28ab00438b7b95/html5/thumbnails/11.jpg)
Experimental Evaluation Of Cascade Refrigeration Plant using R134a and CO2 couple
![Page 12: K10854 Experimental evaluation of cascade refrigeration plant](https://reader035.fdocuments.us/reader035/viewer/2022062310/588136ac1a28ab00438b7b95/html5/thumbnails/12.jpg)
AimEnergy performance analysis of the plant.Focusing on: compressors’ performance, temperature difference in the cascade heat
exchanger,Cooling capacity,COP, andCompressors’ discharge temperatures
![Page 13: K10854 Experimental evaluation of cascade refrigeration plant](https://reader035.fdocuments.us/reader035/viewer/2022062310/588136ac1a28ab00438b7b95/html5/thumbnails/13.jpg)
Cascade Refrigeration Prototype
CO2 compressor
R134a compressor
![Page 14: K10854 Experimental evaluation of cascade refrigeration plant](https://reader035.fdocuments.us/reader035/viewer/2022062310/588136ac1a28ab00438b7b95/html5/thumbnails/14.jpg)
Characteristics Of ExperimentLT evaporating temperatures -40 to -30 ºC HT condensing temperatures from 30 to 50
ºCOperation of the cascade was registered at
five LT condensing temperatures regulating the HT compressor speed.
Degree of superheat in the valves of the R134a cascade condensers and of the CO2 evaporator at 10 ºC.
![Page 15: K10854 Experimental evaluation of cascade refrigeration plant](https://reader035.fdocuments.us/reader035/viewer/2022062310/588136ac1a28ab00438b7b95/html5/thumbnails/15.jpg)
Observations And Conclusions..Energy Balance Of The Cascade Plant-COP of cascade plant-1.42COP of LT cycle- 3.10COP of HT cycle- 2.84
• Compressor’s Performance:Compressor’s speed varied under fixed compression
ratiosR134a Compressor Speed increased
efficiency improvedCO2 compressor Below nominal speed or at high
compression ratio efficiency degraded
![Page 16: K10854 Experimental evaluation of cascade refrigeration plant](https://reader035.fdocuments.us/reader035/viewer/2022062310/588136ac1a28ab00438b7b95/html5/thumbnails/16.jpg)
Energy Performance Of The Cascade Refrigeration Plant
![Page 17: K10854 Experimental evaluation of cascade refrigeration plant](https://reader035.fdocuments.us/reader035/viewer/2022062310/588136ac1a28ab00438b7b95/html5/thumbnails/17.jpg)
Cooling CapacityCooling capacity is negatively linear
dependent with the condensing temperature of the LT cycle.
Changes in cooling capacity is significant when subjected to modification of low evaporating temperature.
![Page 18: K10854 Experimental evaluation of cascade refrigeration plant](https://reader035.fdocuments.us/reader035/viewer/2022062310/588136ac1a28ab00438b7b95/html5/thumbnails/18.jpg)
Discharge Temperature of CO2 Compressorhigher than the environment temperature,
which brings the possibility of using a gas-cooler to reject heat, which improves COP of the plant.
![Page 19: K10854 Experimental evaluation of cascade refrigeration plant](https://reader035.fdocuments.us/reader035/viewer/2022062310/588136ac1a28ab00438b7b95/html5/thumbnails/19.jpg)
EXPERIMENTAL EVALUATION OF A CASCADE REFRIGERATION SYSTEM FOR LOW TEMPERATURE APPLICATIONS USING THE PAIR R22/R404A
![Page 20: K10854 Experimental evaluation of cascade refrigeration plant](https://reader035.fdocuments.us/reader035/viewer/2022062310/588136ac1a28ab00438b7b95/html5/thumbnails/20.jpg)
AimTo obtain the condensing temperature of the
LT that provides an optimal value for the coefficient of performance (COP) of the cycle.
![Page 21: K10854 Experimental evaluation of cascade refrigeration plant](https://reader035.fdocuments.us/reader035/viewer/2022062310/588136ac1a28ab00438b7b95/html5/thumbnails/21.jpg)
Schematic Diagram of the Experimental Plant
![Page 22: K10854 Experimental evaluation of cascade refrigeration plant](https://reader035.fdocuments.us/reader035/viewer/2022062310/588136ac1a28ab00438b7b95/html5/thumbnails/22.jpg)
COP Of Cascade Refrigeration
![Page 23: K10854 Experimental evaluation of cascade refrigeration plant](https://reader035.fdocuments.us/reader035/viewer/2022062310/588136ac1a28ab00438b7b95/html5/thumbnails/23.jpg)
Experimental Results For The HT, LT and Global COPs
•The increase in intermediate temperature causes intersection of the two curves, as provided by the simulation process.
• The COPG had a maximum value at the intersection of the COPcurves of each circuit.
![Page 24: K10854 Experimental evaluation of cascade refrigeration plant](https://reader035.fdocuments.us/reader035/viewer/2022062310/588136ac1a28ab00438b7b95/html5/thumbnails/24.jpg)