Joseph Mashao Managing Director SMA Solar Technology...
Transcript of Joseph Mashao Managing Director SMA Solar Technology...
SMA Solar Technology AG
Joseph Mashao
Managing Director
SMA Solar Technology South Africa (Pty) Ltd
Decentral Energy Concepts with Sunny Island
Solar and Off-Grid Renewables Africa Nairobi: 04 – 05 March 2014
1
SMA Solar Technology AG
Agenda
1. Introduction SMA Off-Grid Solutions
2. Functions
3. Components
4. Installation
5. Battery Technology
6. Communication in Island Systems
7. Dimensioning
2
SMA Solar Technology AG
Introduction SMA Off-Grid concepts
3
SMA Solar Technology AG
Off-Grid solution
4
SMA Solar Technology AG
DC Coupling
> Connection of PV array and load via a DC power bus
PV array Load
DC power bus
Charge controller
Example 2: Solar home system (with battery)
DC power bus
Battery
Example 1: DC water pump (without battery)
DC power bus
PV array Load
5
SMA Solar Technology AG
AC Coupling
> Connection of sources and loads via an AC bus
PV array
PV inverter
Load Source
AC power bus
6
Example 1: PV inverter feeds an AC power bus (typical for utility connected systems)
SMA Solar Technology AG
AC Coupling
> Connection of PV array and load via an AC power bus
Example 2: SMA off-grid systems (micro grid/mini grid)
Load
PV array
PV inverter Battery inverter
Battery
AC power bus
7
SMA Solar Technology AG
Advantages of AC Coupling:
> Independent energy supply (self-sufficient)
> Free choice of power sources and loads (flexible)
> Simple to expand even after many years (expandable)
> Large distance between components possible (decentralized)
Load
PV array
PV inverter Battery inverter
Battery
AC power bus
8
SMA Solar Technology AG 9
Sunny Island – Standard Installation
SMA Solar Technology AG 10
Sunny Island – Extendable
SMA Solar Technology AG 11
Sunny Island – Modular Design
SMA Solar Technology AG 12
Sunny Island – Multiple Energy Sources
SMA Solar Technology AG 13
Sunny Island – Power in Network Quality
SMA Solar Technology AG
Technical data
Technical data SI 8.0H SI 6.0H
AC
AC power 30 min 8000 W 6000 W
Rated power 6000 W 4600 W
DC
Rated input voltage 48 V 48 V
Rated DC charging current 115 A 90 A
Fea
ture
s /
fun
ctio
n
1~ paral. | 3~ | Multicluster || ||
Mixed systems |Easy to Use | |
SOC | SOH | |
Display SRC-20 SRC-20
Ge
ne
ral
da
ta Operation temperature range
-25 °C ... +60 °C
-25 °C ... +60 °C
Protection class IP54 IP54
14
SMA Solar Technology AG
Sunny Island – Basic Tasks
> Grid forming
> Supply and control of frequency
> Supply and control of voltage
> Supply of power
> Supply of active power
> Supply of reactive power
> Transfer and conversion of energy
> Conversion from AC into DC form for battery charge
> Conversion from DC into AC form for supply of energy
[f] [U]
[P] [Q]
~ =
15
SMA Solar Technology AG
Product Portfolio
Nominal AC-Output at 25 ºC
16
MC-Box-6 MC-Box-12 (U) MC-Box-36
30Min.AC-Output at 25 ºC
6 12 36
48 96 kW 288
36 72 kW 216
55 110 kW 328
1Min. AC-Output at 25 ºC
SI 6.0H SI 8.0H
6,0
4,6
6,8 (5 Min)
8,0
6,0
9,1 (5 Min)
6,0 4,5
7,0 5,3
8,4 (1 Min) 8,4 (1 Min)
SI 4548-US SI 6048-US
SMA Solar Technology AG 17
Sunny Remote Control
> The SI system is configured with Sunny Remote Control
> Connection to Sunny Island 6.0 H via an RJ45 data cable
(max. length 20 m)
> Four-line display showing operating data
> SD card slot
> Loading and saving parameters
> Saving the event history and fault history
> e.g. 4 years in one-minute intervals
> Firmware updates
SMA Flexible Storage System
SMA Solar Technology AG
Battery Inverter Sunny Island, the Manager of the Off-Grid System
18
SMA Solar Technology AG
Application Examples
> Sunny Island forms and controls the stand-alone grid (battery, generator and load management)
> PV array and PV inverter supply the stand-alone grid (AC-coupled) with electricity
> Battery stores electricity
> Self-sufficiency period depends on battery capacity
Straight Off-Grid System
PV array
PV inverter
Battery
Load
Battery inverter
19
SMA Solar Technology AG
Application Examples
> Sunny Island forms and controls the stand-alone grid (battery, generator and load management)
> PV array and PV inverter supply the stand-alone grid (AC-coupled) with electricity
> Battery stores electricity
> When the battery is empty, the combustion generator supplies the loads and charges the battery (grid-
forming) 20
Off-Grid System and Combustion Generator
PV array
PV inverter
Battery
Load
Battery inverter
Combustion generator
SMA Solar Technology AG
Application Examples
> Sunny Island forms and controls the stand-alone grid (battery, generator and load management)
> PV array and PV inverter supply the stand-alone grid (AC-coupled) with electricity
> Battery stores electricity
> When the battery is empty, the public grid supplies the loads and charges the battery.
Off-Grid System and Public Grid
Battery inverter
Load Public grid
PV inverter
PV array
Battery
21
SMA Solar Technology AG
> In normal operation, the public grid supplies the loads and charges the battery
> If the grid fails, the Sunny Island forms a stand-alone grid after a maximum of 30 ms, and supplies the
loads
> Hold-up time depends on battery capacity
Straight Backup System
22
Power distribution grid
Battery inverter
Battery
Load
Application Examples
SMA Solar Technology AG
Functions
23
SMA Solar Technology AG
Basic principle of battery supply
SMA Solar Technology AG
Off-Grid system with solar power
PPV < PLoad
SMA Solar Technology AG
Off-Grid system with solar power
PPV > PLoad
SMA Solar Technology AG
Off-Grid system with solar and generator power
PPV < PLoad
SMA Solar Technology AG
Off-Grid system with solar and generator power
PPV < PLoad
SMA Solar Technology AG
Adjustable battery SOC limits
29
SOC
100%
70%
50%
40%
SOC1 – State-of-Charge Limit for generator start
User set to 70% (example)
Generator start requested
SMA Solar Technology AG
Adjustable battery SOC Limits
30
SOC
100%
70%
50%
40%
Generator Failure !
SOC2 – State-of-Charge Limit for load shedding
User set to 50% (example)
System SOC warning
Load shedding
SMA Solar Technology AG
Components
31
SMA Solar Technology AG
Components & Functions
AC 2 AC1
Public Grid Battery PV array Wind turbine systems
Hydro-electric systems
Consumption
Gas/Diesel Generator
Bi-directional Battery Inverter
PV Inverter Windy Boy Hydro Boy Load
32
SMA Solar Technology AG
PV Inverters in Off-Grid Systems
> SMA PV inverters can be used in off-grid
systems *
> All Sunny Boys with transformer
> All Sunny Boys without transformer
> All Sunny Mini Centrals
> All Sunny Tripower 10000-17000 TL-10
> All Sunny Tripower 5000-9000 TL-20
* Observe special requirements in off-grid operation: set to off-grid mode
33
SMA Solar Technology AG
BatFuse
> As an external DC fuse, the BatFuse secures the battery connection cables and enables DC
disconnection (without load)
34
Load shedding contactor
BatFuse-B.03
Battery
Sunny Island Charger
Sunny Island
Line Protection of SIC 40 e.g. 63 A circuit breaker
SMA Solar Technology AG
BatFuse
> All-pole fusing near by the battery
> NH (low voltage high power) fuse
> Inclusive fuse link + spare fuse
> ‚Always‘ necessary
> BatFuse-B.01
> For one Sunny Island (AC, one phase)
> BatFuse-B.03
> For three Sunny Island (Commercial installation)
35
SMA Solar Technology AG
> Several options for controlling internal and external
processes
> two relays integrated in the Sunny Island (potential-
free contacts)
> Relay function as contact
> Configuration: In menu #241
> 241.01 Rly1Op
> 241.02 Rly2Op
> Functions/contactor/fault controlling
> Functions: load shedding and generator request at
master
Multi-Function Relay
NC
NO
C
36
SMA Solar Technology AG
Relay Functions: (Expert)
Function / Settings:
Meaning: Function Description:
Off Relay remains permanently switched off (deactivated)
On Relay remains permanently switched on (e.g. relay function test during commissioning)
AutoGn Automatic generator request
Generator is automatically connected due to set criteria (see section 14.1.5 "Automatic Generator Operation" (page 112)) zugeschaltet
AutoLodExt Automatic load shedding depending on an external source
Automatic connection/disconnection of loads. Connecting only if the device is connected to an external source (e.g. generator) or if the absorption phase is active
AutoLodSoc1 Auto LoadShedding Soc1 Automatic connection/disconnection of loads. Connecting only if SOC limit 1 has exceeded the set value again
AutoLodSoc2 Auto LoadShedding Soc2 Automatic load disconnection. Connecting only if SOC limit 2 has exceeded the set value again
Tm1 Timer 1 (time-controlled switching of relay 1) Programmable time (timer) (once, daily, weekly) with duty cycle
Tm2 Timer 2 (time-controlled switching of relay 2) Programmable time (timer) (once, daily, weekly) with duty cycle
ExtPwrDer The off-grid inverter controls additional loads in order to put excess energy to practical use
37
SMA Solar Technology AG
> Internal relay switches on (e.g.) an external power contactor (load shedding contactor)
> Safety function prior to deep discharge of battery
Load Management: Load Shedding
AC power contactor
DC power contactor
Low energy generation
Fully discharged battery
High energy demand
High energy demand
38
SMA Solar Technology AG
Load Management: Load Shedding
> Example: The load-shedding function should not be active at night (from 6.00pm to 6.00am) if
possible, as the battery may be discharged by up to SOC= 30% before the load-shedding contactor
is connected
39
SMA Solar Technology AG
Load Shedding Contactors
> For different power ranges
> 45A and 100A
> 48 V DC
> 3-Pole Contactor
> All loads should be connected with a
contactor (danger of battery discharging
in spite of load shedding)
> However, selective load shedding of
only one load group is possible
40
SMA Solar Technology AG
> Through the off-grid frequency, the Sunny Island can limit the output power of the PV and wind
inverters so as to prevent battery overload
Generator Management: Power Adjustment via Frequency
f= 50 Hz
Low energy demand
Fully charged battery High
energy generation
f= (50+∆f) Hz
41
SMA Solar Technology AG
Frequency Shift Power Control
> No additional communication necessary
> A rising grid frequency lowers the energy output of the Sunny Boys
PAC [%]
FAC [Hz]+1 +2 +3-1-2-3 f0
50
100
FAC-Start Delta (1Hz)
FAC-Limit Delta (2Hz)
+4
FAC-Delta+ (4,5Hz)
-4
FAC-Delta- (4,5Hz)
42
SMA Solar Technology AG
> The Sunny Island supports the integration of external
energy sources
> The integration of the combustion generator or the
power distribution grid takes place via the AC-2
terminal
> Integration can be one-phase or three-phase
> Depending on the battery state of charge or the load
power, a combustion generator can be started and
stopped
> Important points for the Sunny Island:
> Grid-forming or parallel to the grid
> Manual start or remote start
> Remote start with one or two contacts
Generator Management
43
SMA Solar Technology AG
> In this case, the Sunny Island does not have the option of starting the generator
> By monitoring the generator input (AC-2), the Sunny Island can determine whether the voltage and
frequency of the generator are within the set limits, then synchronize and connect
Manual Generator Start
44
Generator that cannot be started remotely
Sunny Island
Island grid
Generator
SMA Solar Technology AG
> In this case, the Sunny Island has the option of starting the generator. It requests the generator using the
GnReq signal
> If the generator voltage and frequency are within the set limits, the device is synchronized and switched
on following the warm up time (#233/12)
Automatic Generator Start
45
Generator that can be started remotely
GnReq signal
Sunny Island
Island grid
SMA Solar Technology AG
Automatic Generator Start
> Example: If possible, the combustion generator should not run at night. From 6.00am to 6.00pm, the
generator is started with an SOC= 40%. From 6.00pm to 6.00am, the battery may be discharged to
30% before the generator starts
46
SMA Solar Technology AG
Sunny Island Charger SIC50
> The universally usable Sunny Island Charger from SMA
> Its broad DC input voltage range makes sensible system configuration possible for almost all PV
modules
> Thanks to the integrated MPP tracking system, the charger guarantees an energy yield between 15 to
30% higher than that of conventional charge controllers
47
SMA Solar Technology AG
DC Coupling with SIC
> For 12/24/48 V off-grid systems (630/1250/2100W)
> Parallel connection of up to four devices
> BMS for OPzS and OPzV
> Part of SMA communication bus
> Efficiency > 98%
50
55
60
65
70
75
80
85
90
95
100
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400
PPV in W
eta
in %
C-Muster@70V
C-Muster@85V
C-Muster@100V
Battery
Sunny Island
PV array
Sunny Island Charger
Sunny Boy
Generator Load
48
SMA Solar Technology AG
Technical Data SI Charger
49
SMA Solar Technology AG
Measuring Shunt
> Separate measuring shunt for battery current measurement on the DC side
> Use with DC generators or DC loads, the Sunny Island cannot measure internal power accurately and
the battery’s charge state is not precisely determined otherwise
> 200 and 600 A available
> The measuring shunt must be looped around the negative pole of the battery
> Use intrinsically safe and twisted cables
> Compatible with Sunny Island 6.0H, 8.0H
50
Sunny Island
DC -
Battery
DC -
BatCur + BatCur -
SMA Solar Technology AG
> The Multicluster Boxes allow easy installation of off-grid systems from 30 to 300 kW
> For this purpose, between two and twelve three-phase clusters consisting of three SI 5048 or 6.0H and
8.0H mixed can be connected in parallel
> The Multicluster Boxes were specially developed as AC distribution centers for connecting generators
and for supplying loads
Multicluster Box
51
SMA Solar Technology AG
Three Phase Sunny Island Systems
Nominal AC-Output at 25 ºC
52
MC-Box-6 MC-Box-12 MC-Box-36
30Min.AC-Output at 25 ºC
6 12 36
48 96 kW 288
36 72 kW 216
55 110 kW 328
1Min. AC-Output at 25 ºC
SI 6.0H SI 8.0H
6,0
4,6
6,8 (5 Min)
8,0
6,0
9,1 (5 Min)
SMA Solar Technology AG
Multicluster Box
53
SMA Solar Technology AG
Technical Data MC-Box
54
SMA Solar Technology AG
Technical Data MC-Box
55
SMA Solar Technology AG
> Communication lines allow communication (synchronization) between the Sunny Island and the Multicluster Box
Interior View of the Multicluster Box 6
56
SMA Solar Technology AG
Multiclusterbox
57
SMA Solar Technology AG
1 Phase parallel Sunny Island System
58
Slave 1 Slave 2
Loads
Battery
Battery fuse
Solar modules
Sunny WebBox
optional
Synchronous Generator
optional
Equipotential bar with foundation earth
Load shedding contactor
RC
D
Sunny Island
Sunny Island
Charger 50
M aster
Sunny Boy,
Sunny M ini Central
Solar modules
Comments:
Live wire
Neutral wire
Earth wire (PE)
Negative DC wire
Positive DC wire
Communication wire
Further options:
Instead of using a generator the public grid (TN type only) can be
connected to the system
The Sunny Island can control different operations automatically depending
on SOC, power, time, ...
e.g. Automatic generator start, load shedding
optional
optional
optional
Sunny Remote
Control
SMA Solar Technology AG
3-Phase Sunny Island System
59
Loads
Battery
Battery fuse
Sunny Boy,
Sunny M ini Central,
Sunny Tripower
Solar modules
Sunny WebBox
optional
Synchronous generator
Equipotential bar with
foundation earth
Load shedding contactor
RC
D
Sunny Island
M aster Slave 1 Slave 2
Sunny Island
Charger 50
Solar modules
optional
Comments:
Live wire
N eutral wire
Earth wire (PE)
N egative DC wire
Positive DC wire
Communication wire
Further options:
Instead of using a generator the public grid (TN type only) can be
connected to the system.
The Sunny Island can control different operations automatically depending
on SOC, power, time…
e.g. Automatic generator start, load shedding
optional
Sunny Remote
Control
SMA Solar Technology AG
Planned village power supply (>100 kW)
60
Sunny Island
Charger 50
Cluster 1 Cluster 2 Cluster y Cluster z
to
Cluster 3
(not for M C-Box 6)from
Cluster x
Battery fuse
Sunny Boy,
Sunny M ini Central,
Sunny Tripower
M ulticluster Box 6 , 12 or 36
Generator
contactorLoadshedding
Sunny
Webbox
External
Communication
External
Communication
Solar modules
PV Unterverteilung / PV–Subdistribution Box
PO
WER
SY
STE
M
RE
PO
RT
ME
MO
RY
SM
AC
OM
NE
TCO
M
US
BC
OM
Sunny
WebBox
BatteryBattery
Battery fuse Battery fuseBattery fuse
Battery Battery
Sunny Island
Loads
RC
DR
CD
optional
AC - Service Pa nel
Loads
Solar modules
Synchronous Generator (optional)
Equipotential bar with foundation earth
Comments:
Live wire
Neutral wire
Earth wire (PE)
Negative DC wire
Positive DC wire
Communication wire
Further options:
Instead of using a generator the public grid (TN type only) can be
connected to the system
The Sunny Island can control different operations automatically
depending on SOC, power, time, ...
e.g. Automatic generator start, load shedding
optional optional optional optional
Solar modules Solar modules Solar modules
Sunny Remote
Control
SMA Solar Technology AG
Battery Technology
61
SMA Solar Technology AG
Battery in an Off-Grid System
> The purpose of the battery is to ensure that the supply and demand of energy are always in balance
> All Sunny Island systems require a battery
> It is one of the most important components in an Off-Grid system
Sunny Island
Battery
62
SMA Solar Technology AG
Battery in an Off-Grid System
> Overcharging or deep discharging of the battery will shorten its service life
> SMA battery management can help prevent battery damage
> SMA battery management prolongs the service life of the battery
63
Battery damage: Condition: Countermeasures:
Corrosion Irreversible Avoid overcharging
Sulfation Irreversible Avoid deep discharging
Acid stratification Reversible Gas loading and "mechanical" circulation
Cell divergence Voltages (V)
Reversible Selective overcharging and evenly distributed thermal load
Siltation Irreversible Avoid deep discharging, Avoid overcharging
Desiccation Irreversible Avoid overcharging
SMA Solar Technology AG
Battery design life time
64
SMA Solar Technology AG
VRLA / OPzV
Valve Regulated Lead Acid: Closed lead-acid batteries with electrolyte fixed in gel or glass mat in all standard designs currently on the market (e.g., OPzV)
FLA / OPzS
Flooded Lead Acid: Closed lead-acid batteries with liquid electrolyte in all designs currently on the market (e.g., OPzS).
NiCd / FNC
Nickel Cadmium: Closed nickel cadmium batteries with pocket-type plate or fiber plate design
Battery Type
65
SMA Solar Technology AG
Discharge Time
0
200
400
600
800
1000
1200
1400
1600
5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100
Av
aila
ble
ca
pa
city
in A
h
Discharge time in h
Battery 10 OPzS 1250
66
SMA Solar Technology AG
Battery Capacity
> The nominal capacity is always relative to the discharge time that C n refers to
Type C100/1.85 V Ah
C50/1.85 V Ah
C24/1.83 V Ah
C10/1.80 V Ah
C5/1.77 V Ah
Max. weight kg
Length L mm
Width B mm
Height H mm
Fig.
4 OPzV solar.power 250 250.0 225.0 225.6 207.0 188.5 20.0 105 208 420 A
5 OPzV solar.power 310 310.0 285.0 278.4 259.0 235.5 24.0 126 208 420 A
6 OPzV solar.power 370 370.0 340.0 336.0 310.0 283.0 28.0 147 208 420 A
5 OPzV solar.power 420 440.0 440.0 436.8 391.0 347.0 31.0 126 208 535 A
6 OPzV solar.power 520 560.0 530.0 525.6 469.0 416.0 37.0 147 208 535 A
7 OPzV solar.power 620 660.0 620.0 612.0 548.0 484.5 42.0 168 208 535 A
6 OPzV solar.power 750 810.0 745.0 739.2 682.0 595.0 50.0 147 208 710 A
8 OPzV solar.power 1000 1080.0 995.0 981.6 910.0 795.0 68.0 215 193 710 B
10 OPzV solar.power 1250 1350.0 1245.0 1228.8 1140.0 990.0 82.0 215 235 710 B
12 OPzV solar.power 1500 1570.0 1490.0 1476.0 1370.0 1190.0 97.0 215 277 710 B
12 OPzV solar.power 1700 1720.0 1675.0 1658.4 1520.0 1275.0 120.0 215 277 840 B
16 OPzV solar.power 2300 2320.0 2235.0 2210.4 2030.0 1695.0 165.0 215 400 815 C
20 OPzV solar.power 2900 2930.0 2795.0 2760.0 2540.0 2125.0 200.0 215 490 815 D
24 OPzV solar.power 3500 3540.0 3350.0 3312.0 3050.0 2545.0 240.0 215 580 815 D
C100,C50, C24, C10, nd C5 = capacity at 100, 50, 24, 10 and 5 hours of discharge time
67
SMA Solar Technology AG
Battery Capacity in Sunny Island System
> The battery capacity in a Sunny Island must be indicated as the nominal capacity for a ten hour
discharge rate C10 ("221.02 NomBatCpy" parameter)
> If this rated capacity is not specified in the battery manufacturer's data sheet, it can be estimated
based on the data for other discharging times as follows:
C10 C1/0.61
C10 C5/0.88
C10 C10
C10 C20/1.09
C10 C100/1.25
C10 C120/1.28
68
SMA Solar Technology AG
Battery Terms
69
SOC
State of Charge: The state of charge refers to the percentage amount of battery capacity that is currently available
DOD
Depth of Discharge: The depth of discharge is an alternative method for displaying the state of charge of a battery. DOD can be indicated as a percentage or in units of ampere-hour
SOH
State of Health: The state of health of a battery refers to the percentage amount of usable capacity relative to rated capacity C n
Total number of battery cycles
A battery cycle is the complete cycle of charging and discharging of a battery
SMA Solar Technology AG
Battery Terms
> Only when a cell is new its usable capacity will match the rated capacity specified by the battery
manufacturer
> (e.g., rated capacity 1000 Ah a C 10 and 20 ºC)
2 V 2 V
1000 Ah 1000 Ah
70
SMA Solar Technology AG
Cell condition: "Used"
Battery Terms: SOH
Cell condition: "New"
0%
100% Nominal capacity
0%
90% current, max.
Capacity
> As a battery ages, its usable capacity may temporarily or permanently drop by a significant margin
(new)
(used)
capacity Nominal
capacity max.Current SOH
71
SMA Solar Technology AG
0%
100%
SOC
0%
100%
SOC
Cell condition: "Used"
Cell condition: "New"
Battery Terms: SOH and SOC
> The Sunny Island can use a self-adapting procedure to determine the state of health.
> Required time: approx. 4 to 8 weeks
72
SMA Solar Technology AG
0%
100%
SOC
0%
100%
SOC
Cell condition: "Used"
Cell condition: "New"
Battery Terms: DOD and SOC
SOC
DOD
0%
100%
SOC
DOD
100%
0%
SOCDOD100% )x.capacity(currentma
73
SMA Solar Technology AG
0%
100%
SOC
0%
100%
SOC
Battery Terms: Maximum Depth of Discharge
SOC
DOD
0%
100%
SOC
DOD
0%
100%
SOC
DOD
0%
100%
0%
100%
SOC
DOD
0%
MinMax)x.capacity(currentma SOCDOD100%
74
Cell condition: "Used"
Cell condition: "New"
SMA Solar Technology AG
Service life in cycles
75
SMA Solar Technology AG
Battery Temperature
> The battery temperature is taken into consideration when the charging voltage is calculated
> The present capacity for the Sunny Island is automatically adjusted for the current temperature
Battery temperature sensor
76
SMA Solar Technology AG
Charging Voltage
77
Ambient temperature
Charging voltage in relation to ambient temperature (continous battery power supply)
Cha
rgin
g v
olta
ge
per
cel
l
SMA Solar Technology AG
State of Charge Determination
> The Sunny Island has a very precise internal state of charge
calculation ("120.01 BatSoc" display value) that is based on three
different methods of calculation:
> 1. Ampere hour balancing
> 2. Recalibration via battery voltage (at night)
> 3. Calculation of self-discharges and charge losses caused by
gassing
> Both the ampere hour balancing and recalibration via battery
voltage methods will automatically adapt themselves to the
connected battery over time (approx. 4 to 8 weeks)
> If other loads or generators are connected to the battery, then an
external battery current sensor (shunt) must be connected to
allow the proper functioning of the state of charge calculation
Ah Ah
78
SMA Solar Technology AG
Boost Charge(U0 Phase)
Full Charge(U0 Phase)
Equalization Charge(U0 Phase)
Float Charge(U Phase)
Silent Mode(Ruhephase)
Cha rging Process
Ch
arg
ing
Ph
ase
s
Manuell
3 2
2
54
76
4 4
explanations:1: If BatVtg = BatChrgVtg 2: after time CycTmEqu (#225.05)3: after time CycTmFul (#225.04)4: if AptTmRmg = 0 (#120.04)5: if SOC < 70 % (#120.01)6: only with Grid, after time SilentTmFlo (#224.02)7: only with Grid, after time SilentTmMax (#224.03)
I-Phase
1
Charging Process
79
SMA Solar Technology AG
Battery Preservation Mode
Level 1: "223.05 BatPro1Soc" parameter For example: SOC limit < 20%
4W
4W
0h 6h 12h 18h 24h
BatPro1TmStp BatPro1TmStp
Standby Operation Standby
> The battery preservation mode is designed to prevent, to the greatest degree possible, any deep
discharge of the battery when the energy supply is low, thus avoiding total system failure and battery
damage.
> The first level is used to switch the inverter to standby mode when there is no urgent need for power (e.g.,
at night). For example: only if SOC limit is < 20%
80
SMA Solar Technology AG
Battery Preservation Mode
Level 2: "223.03 BatPro2TmStr" parameter. For example: 8 a.m.
Energy supply
Charging the battery
4W
4W
0h 6h 12h 18h 24h
BatPro2TmStp BatPro2TmStr
Standby Regular starts Standby
> The second level of the battery preservation mode ensures that the inverter regularly starts every two hours
during the time window when a supply of energy is expected and then attempts to charge the battery from
the AC side. For PV plants, the time window is daytime.
81
SMA Solar Technology AG
Automatic shutdown
Battery Preservation Mode
Level 3: "223.07 BatPro3Soc" parameter. For example: SOC limit < 10%
0 W
0h 6h 12h 18h 24h
> The third level ensures that the battery is protected from deep discharging and associated damage
> The inverter is completely shutdown for this purpose
> "Last protective function„
82
SMA Solar Technology AG 83
Different battery sizes - 24 x 2V cells
SMA Solar Technology AG 84
Different battery sizes - parallel connection
SMA Solar Technology AG 85
Different battery sizes - parallel connection
SMA Solar Technology AG 86
Battery Systems bad
SMA Solar Technology AG 87
Battery Systems good
SMA Solar Technology AG
Installation
88
SMA Solar Technology AG 89
Grounding and DC connection - Sunny Island
Sunny Island
Battery 48 V
Battery Fuse
+ -
> Grounding connection in use without
Multi Cluster box!
> Recommended cable size 16mm²
> Cable lug M8
SMA Solar Technology AG 90
DC connection - 1 phase system with 1 Sunny Island
Sunny Island
Battery 48 V
Battery Fuse
Bat +
Bat -
+ -
> Recommended cable size 70mm²
> Cable lug M8
> Same cable length
> Max torque clamps 5-6 NM
SMA Solar Technology AG
DC connection - 1 phase system 3 Sunny Island in parallel
Master Slave 2 Slave 1
Battery 48 V
Battery Fuse
Bat +
Bat -
+ -
> Recommended cable size 70mm²
Sunny Island
> Cable lug M8
> Same cable length
> Max torque clamps 5-6 NM
91
SMA Solar Technology AG
DC connection - 3 phase / Multi Cluster system
Master (L1) Slave 2 (L3) Slave 1 (L2)
Battery 48 V
+ - Bat +
Bat -
> Recommended cable size 70mm²
Sunny Island
> Maximum cable size 185mm²
BatFsue-B.03
> Cable lug M8
> Same cable length
> Max torque clamps 5-6 NM
Battery Fuse
92
SMA Solar Technology AG 93
AC 1/2 connection - 1 phase system with 1 Sunny Island
Equipotential-bar Generator
Loads Connection necessary
SMA Solar Technology AG 94
AC 1/2 connection - 1 phase system 3 Sunny Island in parallel
Equipotential-bar
Master Slave 2 Slave 1
Generator Loads
Connection necessary
SMA Solar Technology AG 95
AC 1/2 connection - 3 phase system
Equipotential-bar
Master (L1) Slave 2 (L3) Slave 1 (L2)
Generator Loads
Connection necessary
SMA Solar Technology AG 96
Multi Cluster Systems
MC-Box-6.3 MC-Box-12.3 Dimension 760*760*210 1000*1400*300 (W*H*D in mm) Weight (in kg) 60 kg 140 kg Diameter Bolt clamps 6mm 10mm Max torque bolt clamps 3-6 Nm 10-20 Nm Fuse for Gen / Loads 80A 160A Max cable dimension 35qmm 120qmm
SMA Solar Technology AG 97
AC connection Multi Cluster system - Main Cluster
MC-BOX-6
From main cluster
SMA Solar Technology AG 98
AC connection Multi Cluster system - Main Cluster
Master (L1) Slave 2 (L3) Slave 1 (L2)
Main Cluster
MC-BOX-12
SMA Solar Technology AG 99
AC connection Multi Cluster system - Extension Cluster
MC-BOX-6
From Extension cluster
SMA Solar Technology AG 100
AC connection Multi Cluster system - Extension Cluster
Extension Cluster 1
MC-BOX-12
SMA Solar Technology AG 101
AC connection Multi Cluster system - Generator
MC-BOX-12
From Generator
SMA Solar Technology AG 102
AC connection Multi Cluster system - Loads
MC-BOX-12
To Loads
Connection necessary
SMA Solar Technology AG 103
AC connection Multi Cluster system - Grounding
MC-BOX-12
To Equipotential-bar
MC-BOX-6
To Equipotential-bar
SMA Solar Technology AG 104
AC connection Multi Cluster system - Sunny Boy/Sunny Mini Central
Sunny Boy (L3)
Sunny Boy (L2)
Sunny Boy (L1)
From other Sunny Boys
Distribution
From other Sunny Boys
SMA Solar Technology AG 105
Master Slave 2 Slave 1
Resistor
Internal communication - 1 phase system with 3 devices
> Can bus communication
> Information transfer
> Synchronization
> Measured Values
> Software update
SMA Solar Technology AG 106
Internal communication - 3 phase system / Multi Cluster system
Master (L1) Slave 2 (L3) Slave 1 (L2)
Resistor > Can bus communication
> Information transfer
> Synchronization
> Measured Values
> Software update
SMA Solar Technology AG 107
Internal communication - Multi Cluster Box Overview
SMA Solar Technology AG 108
SMA Solar Technology AG 109
Internal communication - Multi Cluster box - Main Cluster
Master (L1) Slave 2 (L3) Slave 1 (L2)
Main Cluster
MC-BOX-12
Resistor
to Extension Cluster
Sync
VtgCur
SysCAN
L1 L3 L2
SMA Solar Technology AG 110
Internal communication - Multi Cluster box - Extension Cluster
Master (L1) Slave 2 (L3) Slave 1 (L2)
Extension Cluster
MC-BOX-12
Resistor
to Main Cluster
Sync
SysCAN
Either resistor or to Extension Cluster 2
SMA Solar Technology AG
Communication in Island Systems
111
SMA Solar Technology AG
> Sunny Island and Sunny Remote Control can file firmware,
parameters, and measurement data on an MMC/SD card
> Measurement data from the battery, inverter, sources, and
loads are stored cyclically
> Events and errors only stored when they occur
> Stored data can be processed using common table
calculation programs
> The installer must ground himself/herself before inserting or
removing the MMC/SD card at the Sunny Island enclosure
(ESD protection!)
MMC/SD Card
Sunny Island 5048
Sunny Remote Control
MMC/SD card
112
SMA Solar Technology AG
Data/information
Analyses/solutions
MMC/SD card
Sunny Remote Control
MMC/SD card
> Always use the MMC/SD card for storing data and events. This way, SMA can help you quickly
in the event of a fault. Send the data via the Internet or by post
> When the Sunny Island starts up or when the MMC/SD card is inserted, the Sunny Island
searches for special update files on the card. If it finds such files, it performs an update when it is
on standby
MMC/SD Card
113
SMA Solar Technology AG
Communication
www.SM A.deSM A Sola r Technology AGSonnenallee 1 34266 N iestetal Germany
Tel. +49 561 9522 0 Fax +49 561 9522 100
SI2
22
4_
18
12
09
NPE NPE N
N
PE
PV
Verbraucher / Loads
M aster Slave1 Slave2
Sunny
Boy
L1
L2
L3
Sunny
WebBox
Batterie Temperatursensor /Battery temperature sensor
Batterie / Battery
Erläuterung / Discription:
AC-N etz / AC Grid
DC-N etz / DC Grid
Kommunikationsleitungen / Communication
M essleitungen / M easurement wires
Steuerleitung / Control wire
* ) Lastschütz/ Loadshedding contactor
BATFUSE-B.03
PV PV
* )
DigIn
AC2
AC2
AC1
Com
SM A In
Relay1/ 2
Bat
TmpBatCur DC
Bat
VtgOut
DigIn Display
Relay1/ 2
ComSM A In
Com Sync In
DigIn
AC2
AC2
AC1
Com
SM A In
Com Sync Out
Bat
TmpBatCur DC
Bat
VtgOut
Relay1/ 2 Display
Relay1/ 2
ComSM A In
Com Sync In
DigIn
AC2
AC2
AC1
Com
SM A In
Com Sync Out
Bat
TmpBatCur DC
Bat
VtgOut
Relay1/ 2 Display
Relay1/ 2
ComSM A In
Com Sync In
SRC-1
Sunny
Boy
Sunny
Boy
Dieselgenerator
NPE
N PE N PE N PE
N
PE
PE
+ I
114
SMA Solar Technology AG
Dimensioning
115
SMA Solar Technology AG
1. Dimensioning Questionnaire
116
SMA Solar Technology AG
Project Data
> Use the specific yield instead of insolation for an estimation > E PV : Specific yield kWh/a/kWp (worst case!)
117
SMA Solar Technology AG
Demand of Energy
> E a : Average consumption kWh/a
118
SMA Solar Technology AG
Typical daily load curve
> P max : 30 min max. AC Consumption at 25ºC
119
SMA Solar Technology AG
Electric Data
Battery Gas generator PV Wind CHP
120
SMA Solar Technology AG
Which Bi-directional Inverter?
Nominal AC-Output at 25 ºC
121
MC-Box-6 MC-Box-12 MC-Box-36
30Min.AC-Output at 25 ºC
6 12 36
48 96 kW 288
36 72 kW 216
55 110 kW 328
1Min. AC-Output at 25 ºC
SI 6.0H SI 8.0H
6,0
4,6
6,8 (5 Min)
8,0
6,0
9,1 (5 Min)
SMA Solar Technology AG
N SI Number of Sunny Islands
P max Maximum AC power of usage for less than 30 minutes and at 25 ºC [kW]
P SI-30 Maximum AC power of the Sunny Island for 30 minutes and at 25ºC [kW]
2.1 Number of Sunny Islands
P SI-30
P max
30SIP
maxP
SIN
122
SMA Solar Technology AG
C 10 Battery capacity for 10-hour discharge E a Average power consumption [kWh/a]
η Batt Average battery efficiency P d Maximum deep discharge
U Batt
Battery voltage [12V, 24V, 48V] N d Autonomous time [d]
Ea
3. Which Battery Capacity (C10)?
C 10
[Ah]*
BattU
dP
Battη
d/365)N
aE (
10C
η Batt = 80 – 90%
123
SMA Solar Technology AG
Bridging time
N d (days)
Battery type Battery cost
Backup (good grid) 0.5 OPzV ~ 260 €/kWh
Backup (bad grid) 1.0 OPzV ~ 280 €/kWh
System with PV 4.0 OPzS ~ 200 €/kWh
System with PV + diesel 2.0 OPzS ~ 200 €/kWh
System with water turbine 0.5 OPzS ~ 200 €/kWh
Recommended Values N d
124
SMA Solar Technology AG
Recommended Values P d
125
SMA Solar Technology AG
Sunny Island Battery Capacity
The rated capacity is always related to the discharge time on which the nominal capacity Cn is based. The parameter "221.02 NomBatCpy" is to be entered as the nominal capacity for a ten hour discharge (C10)
Type C100/1.85 V Ah
C50/1.85 V Ah
C24/1.83 V Ah
C10/1.80 V Ah
C5/1.77 V Ah
Max. weight kg
Length L mm
Width B mm
Height H mm
Fig.
4 OPzV solar.power 250 250.0 225.0 225.6 207.0 188.5 20.0 105 208 420 A
5 OPzV solar.power 310 310.0 285.0 278.4 259.0 235.5 24.0 126 208 420 A
6 OPzV solar.power 370 370.0 340.0 336.0 310.0 283.0 28.0 147 208 420 A
5 OPzV solar.power 420 440.0 440.0 436.8 391.0 347.0 31.0 126 208 535 A
6 OPzV solar.power 520 560.0 530.0 525.6 469.0 416.0 37.0 147 208 535 A
7 OPzV solar.power 620 660.0 620.0 612.0 548.0 484.5 42.0 168 208 535 A
6 OPzV solar.power 750 810.0 745.0 739.2 682.0 595.0 50.0 147 208 710 A
8 OPzV solar.power 1000 1080.0 995.0 981.6 910.0 795.0 68.0 215 193 710 B
10 OPzV solar.power 1250 1350.0 1245.0 1228.8 1140.0 990.0 82.0 215 235 710 B
12 OPzV solar.power 1500 1570.0 1490.0 1476.0 1370.0 1190.0 97.0 215 277 710 B
12 OPzV solar.power 1700 1720.0 1675.0 1658.4 1520.0 1275.0 120.0 215 277 840 B
16 OPzV solar.power 2300 2320.0 2235.0 2210.4 2030.0 1695.0 165.0 215 400 815 C
20 OPzV solar.power 2900 2930.0 2795.0 2760.0 2540.0 2125.0 200.0 215 490 815 D
24 OPzV solar.power 3500 3540.0 3350.0 3312.0 3050.0 2545.0 240.0 215 580 815 D
C100,C50, C24, C10, and C5 = capacity for 100, 50, 24, 10 and 5 hour discharge
126
SMA Solar Technology AG
PPV PV array capacity in kWp E a Average power consumption [kWh/a]
SF Solar fraction η System System efficiency
EPV
Specific energy yield [kWh/a/kWp]
[kWp]η*E
SF*EP
SystemPV
aPV
4. Which PV Array Capacity PPV?
PPV
Ea
η System ≈ 70%
127
SMA Solar Technology AG
Specific yield EPV
Source: DGS
kWh/m²x anno
kWh/ kWp
2000 1700
1700 1450
1400 1200
1100 930
800 680
128
SMA Solar Technology AG
Specific energy yield (EPV) kWh/a/kWp
Solar fraction (SF)
Germany 800 – 900 50 – 70%
Southern Europe 1300 – 1450 60 – 90%
Africa 1450 – 1700 60 – 100%
Saudi Arabia 1800 – 2000 70 – 100%
Solar Irradiation in kWh/kWp/a
129
SMA Solar Technology AG
Solar radiation kWh/m2/d
http://eosweb.larc.nasa.gov/sse/RETScreen/
Month Air
temperature Relative humidity
Daily solar radiation - horizontal
Atmospheric pressure
Wind speed Earth
temperature Heating
degree-days Cooling
degree-days
°C % kWh/m2/d kPa m/s °C °C-d °C-d
January 22.1 59.3% 5.57 88.2 3.3 22.7 0 375
February 22.8 57.2% 5.79 88.2 3.5 23.6 0 361
March 22.0 70.3% 5.53 88.2 3.5 22.9 0 376
April 21.1 79.1% 5.20 88.2 3.4 21.7 0 337
May 21.0 74.9% 5.00 88.4 3.3 21.2 0 343
June 21.5 62.7% 4.89 88.5 3.5 21.9 0 342
July 21.9 55.1% 4.91 88.5 3.3 22.7 0 362
August 22.1 59.6% 4.99 88.5 3.3 23.1 0 369
September 21.4 70.9% 5.15 88.4 3.3 22.2 0 342
October 20.6 79.9% 4.80 88.3 3.3 21.3 0 333
November 20.5 79.1% 4.78 88.3 3.1 20.9 0 319
December 21.0 70.1% 5.18 88.3 3.0 21.2 0 345
Annual 21.5 68.2% 5.15 88.3 3.3 22.1 0 4204
Lowest radiation = worst case!
130
SMA Solar Technology AG
5. Which inverter?
5,0 kW 3,8 11,0
Sunny Boy Sunny Boy TL-20 Sunny Mini Central
1,2
Sunny Boy
131
SMA Solar Technology AG
5. 1 Sunny Design
> Worldwide choice of location
> Use of high-resolution meteorological data
> Database with all common PV modules
> System design made easy
132
SMA Solar Technology AG
P SI Continuous AC power of the Sunny Island [W]
P SB Continuous AC power of the Sunny Boy [W]
5. 2 Selection Criterion for PV Inverter
P SB P SI
SISB P2P
133
SMA Solar Technology AG
P SI Continous AC power of the Sunny Island [W]
P Gen Continuous AC power of the combustion generator [W]
6. Which Combustion Generator Capacity?
P Gen P SI
0.8 P SI < P Gen < 1.2 P SI
134
SMA Solar Technology AG
Let‘s be realisic and try the impossible!
135