JORDAN SCHNITZER MUSEUM OF ARTpages.uoregon.edu/hof/W11HOF/16HumidityControl_Poster.pdfcould be set...

1
ZONE 1 ZONE 3 ZONE 2 location of thermostat and return duct air supply 4 3 5 6 1 2 JORDAN SCHNITZER MUSEUM OF ART 1.01 .59 .44 .38 .30 .42 .57 D1 D2 D3 D4 D5 D6 D7 2.17 2.02 2.05 2.06 2.02 2.15 2.27 D1 D2 D3 D4 D5 D6 D7 4.25 4.18 4.16 4.21 4.29 4.38 4.53 D1 D2 D3 D4 D5 D6 D7 4.52 4.23 4.21 4.19 4.19 4.27 4.30 D1 D2 D3 D4 D5 D6 D7 D1 D2 D3 D4 D5 D6 D7 8.04 8.10 8.27 8.25 8.32 8.48 9.15 Hobo 1 - RH Hobo 4 - Baseline Hobo 2 - RH Hobo 4 - Baseline Hobo 3 - RH Hobo 4 - Baseline Hobo 5 - RH Hobo 4 - Baseline Hobo 6 - RH Hobo 4 - Baseline D1 D2 D3 D4 D5 D6 D7 D1 D2 D3 D4 D5 D6 D7 D1 D2 D3 D4 D5 D6 D7 D1 D2 D3 D4 D5 D6 D7 D1 D2 D3 D4 D5 D6 D7 D1 D2 D3 D4 D5 D6 D7 Hobo 1 RH Hobo 2 RH Hobo 3 RH Hobo 4 RH Hobo 5 RH Hobo 6 RH 3 4 5 0 1 2 8 9 6 7 Daily maximum percentage RH fluctuation 0 10 20 30 40 50 60 70 80 90 Day 1 Day 1 Day 1 Day 1 Day 1 Day 1 Day 1 Average Daily Outdoor RH Hobo 5 Hobo 6 THE PROBLEM: THE PLACE: HYPOTHESIS: CONCLUSION: DATA COLLECTION: The users of the textile and small decorations vault in the original part of the Jordan Schnitzer Museum of Art (JSMA) noticed daily variations in the humidity and temperature of the vault. Humidity and temperature fluctuation can cause significant damage to art work. There is a 10% variation in humidity levels around the room. The averages of humidity readings taken over a one week period at various locations around the room will range from 5% lower than the humidity level at the thermostat to 5% higher than the humidity level at the thermostat. The data we recorded throughout the week indicated that fluctuations within any given 24 hour period and throughout the space as a whole are less than ideal for storing art. The data also indicates that one of the factors influencing conditions within the vault is the un-insulated, exterior masonry wall on the west edge of the space. This suggests that a possible solution to difficulties maintaining consistent and appropriate RH and temperature levels within the vault could be mitigated with changes to the exterior wall such as the addition of insulation and a vapor barrier. The fact that all of the humidity data we collected was lower than the baseline RH levels measured at HOBO 4 indicates that the placement of the thermostat directly beneath the return duct is not ideal. Placing the thermostat farther away from any ducts would reflect more accurate measurements and therefore greater control of the environment. Because humidity levels throughout the space were up to 8% higher than those measured at baseline and recommended humidity levels for the storage of art, the RH could be set 8 -10% lower than the actual desired RH level. We collected data using Hobo data collectors strategically placed around the collections vault. “every building that we have to control humidity in is a headache” - Don Neet, ECS Technician The Art vault in the basement of the Jordan Schnitzer Art Museum TEMPERATURE & HUMIDITY DATA RESULTS INTERIOR/EXTERIOR RH COMPARISON PER ZONE ZONE 1 ZONE 2 ZONE 3 HOBO 1 COMPARED TO BASELINE RESULTS HOBO 2 COMPARED TO BASELINE RESULTS HOBO 3 COMPARED TO BASELINE RESULTS HOBO 5 COMPARED TO BASELINE RESULTS HOBO 6 COMPARED TO BASELINE RESULTS DAILY MAXIMUM RH FLUCTUATION AVERAGE DAILY RH DIFFERENCE FROM BASELINE

Transcript of JORDAN SCHNITZER MUSEUM OF ARTpages.uoregon.edu/hof/W11HOF/16HumidityControl_Poster.pdfcould be set...

Page 1: JORDAN SCHNITZER MUSEUM OF ARTpages.uoregon.edu/hof/W11HOF/16HumidityControl_Poster.pdfcould be set 8 -10% lower than the actual desired RH level. We collected data using Hobo data

ZONE 1

ZONE 3

ZONE 2location of thermostat and return duct

air supply

43

5

6

12

JORDAN SCHNITZER MUSEUM OF ART

1.01 .59.44 .38

.30 .42

.57

D1 D2 D3 D4 D5 D6 D7

2.17 2.022.05

2.06

2.02 2.15

2.27

D1 D2 D3 D4 D5 D6 D7

4.254.18

4.164.21

4.29 4.38

4.53

D1 D2 D3 D4 D5 D6 D7

4.52 4.234.21

4.19

4.19 4.27

4.30

D1 D2 D3 D4 D5 D6 D7 D1 D2 D3 D4 D5 D6 D7

8.048.10 8.27

8.25

8.32 8.48

9.15

Hobo 1 - RHHobo 4 - Baseline

Hobo 2 - RHHobo 4 - Baseline

Hobo 3 - RHHobo 4 - Baseline

Hobo 5 - RHHobo 4 - Baseline

Hobo 6 - RHHobo 4 - Baseline

D1 D2 D3 D4 D5 D6 D7 D1 D2 D3 D4 D5 D6 D7 D1 D2 D3 D4 D5 D6 D7 D1 D2 D3 D4 D5 D6 D7 D1 D2 D3 D4 D5 D6 D7 D1 D2 D3 D4 D5 D6 D7

Hobo 1 RH

Hobo 2 RH

Hobo 3 RH

Hobo 4 RH

Hobo 5 RH

Hobo 6 RH

Daily Maximum RH Fluctuation

3

4

5

0

1

2

8

9

6

7

Dai

ly m

axim

um p

erce

ntag

e R

H fl

uctu

atio

n

0

10

20

30

40

50

60

70

80

90

Day 1 Day 1 Day 1 Day 1 Day 1 Day 1 Day 1

Average Daily Outdoor RH

Hobo 5

Hobo 6

THE

PROB

LEM

:TH

E PL

ACE:

HYPO

THES

IS:

CONC

LUSI

ON:

DATA

COL

LECT

ION:The users of the textile and

small decorations vault in the original part of the Jordan Schnitzer Museum of Art (JSMA) noticed dailyvariations in the humidity and temperature of the vault. Humidity and temperature fluctuation can cause significant damage to art work.

There is a 10% variation in humidity levels around the room. The averages of humidity readings taken over a one week period at various locations around the room will range from 5% lower than the humidity level at the thermostat to 5% higher than the humidity level at the thermostat.

The data we recorded throughout the week indicated that fluctuations within any given 24 hour period and throughout the space as a whole are less than ideal for storing art. The data also indicates that one of the factors influencing conditions within the vault is the un-insulated, exterior masonry wall on the west edge of the space. This suggests that a possible solution to difficulties maintaining consistent and appropriate RH and temperature levels within the vault could be mitigated with changes to the exterior wall such as the addition of insulation and a vapor barrier.

The fact that all of the humidity data we collected was lower than the baseline RH levels measured at HOBO 4 indicates that the placement of the thermostat directly beneath the return duct is not ideal. Placing the thermostat farther away from any ducts would reflect more accurate measurements and therefore greater control of the environment.

Because humidity levels throughout the space were up to 8% higher than those measured at baseline and recommended humidity levels for the storage of art, the RH could be set 8 -10% lower than the actual desired RH level.

We collected data using Hobo data collectors strategically placed around the collections vault.

“every building that we have to control humidity in is a headache” - Don Neet, ECS Technician

The Art vault in the basement of the Jordan Schnitzer Art Museum

TEMPERATURE & HUMIDITY DATA RESULTS

INTERIOR/EXTERIOR RH COMPARISON PER ZONE

ZONE 1

ZONE 2

ZONE 3

HOBO 1 COMPARED TO BASELINE RESULTS

HOBO 2 COMPARED TO BASELINE RESULTS

HOBO 3 COMPARED TO BASELINE RESULTS

HOBO 5 COMPARED TO BASELINE RESULTS

HOBO 6 COMPARED TO BASELINE RESULTS

DAILY MAXIMUM RH FLUCTUATION

AVERAGE DAILY RH DIFFERENCE FROM BASELINE