RT-SVP04F-EN 2010 Trane All rights reserved
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Commonly Used Acronyms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Glossary of Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4UCM Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Human Interface Module (Local = 1U2, Remote = 9U13 IntelliPak II) (1U65 IntelliPak I)10Unit Operation Keys. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Password Protected Screens. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
System Operating Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
STATUS Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
System Programming SETUP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
SETUP Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53Ventilation Override Definitions (with VOM installed). . . . . . . . . . . . . . . . . . 66
Temperature Input Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
System Programming SETPOINTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
SETPOINT Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101CONFIGURATION Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
System Testing & Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
SERVICE MODE Menu (Local Human Interface only) . . . . . . . . . . . . . . . . . . . 108
DIAGNOSTICS Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Failure Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Communication Link Problems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Contents
-
8/14/2019 ipak trblshoot
3/150
RT-SVP04F-EN 3
Commonly Used Acronyms
For convenience, a number of acronyms and abbreviations are used throughout this
manual. These acronyms are alphabetically listed and defined below.
General Information
Table 1. Acronyms
Act = active HGBP = Hot Gas Bypass
AH = Air Handler HGP = Hot Gas Bypass
Annunc = Annunciator Hi = high
AS = AirSide HI = where all caps Human Interface
Aux = auxiliary HO = History Only (Diagnostic)
BAS = building automation systems HVAC = heating, ventilation and air conditioningBCI = BACnetCommunication Interface ICS = Integrated Comfort System
CCFM = hundreds of cubic-feet-per-minute IGV = inlet guide vanes
CCW = counterclockwise INFO = Information Only (Diagnostic)
cfm = cubic-feet-per-minute I/O = input/output
Cfg = Configured, configuration Indep = Independent
ckt = circuit IOM = installation/operation/ maintenance manual
Cmd = command IPC = interprocessor communications
Comp (s) = compressor, compressors IPCB = interprocessor communications bridge (module)
Cond = condenser, condensers IWC = inches water column
Config = configured, configuration LH = left-hand
Ctrl = control Lo = lowCV = constant volume LCI = LonTalkCommunication Interface
Cy = cycle LCI-I = LonTalk Communication Interface for IntelliPak
Module
CVDA = Constant Speed Fan (CV)/Discharge Air Temp ControlManif = manifolded
CVZT = Constant Speed Fan (CV)/Zone Temperature Control Max = maximum
CW = clockwise Min = minimum
DCV = Demand Control Ventilation Misc = miscellaneous
Dflt = default MCM = Multiple Compressor Module
Diag = diagnostic MDM = Modulating Dehumidification Module
Dmpr = damper Mod = modulating
DWU = Daytime Warm-up MPM = Multi-Purpose ModuleE/A = exhaust air MWU = morning warm-up
ECEM = exhaust control/enthalpy module NSB = night setback panel
Econ = economizer, economizing Num = number
Ent = entering O/A = outside air
Evap = evaporator Occ = occupied
F/A = fresh air OVRD = override
Funct = function PAR = Partial System Disable, Auto Reset (Diagnostic)
GBAS = generic building automation system (module) PMR = Partial System Disable, Manual Reset (Diagnostic)
Pos = position
-
8/14/2019 ipak trblshoot
4/150
-
8/14/2019 ipak trblshoot
5/150
RT-SVP04F-EN 5
General Information
Comparative Enthalpy. An economizer control strategy which compares return air
enthalpy with outdoor enthalpy. The air with the least heat content (enthalpy) is used
for cooling.
Compressor Protection Switch. A pressure switch installed on the suction line that
prevents compressor operation below the switchs SETPOINT. The purpose is to prevent
no-flow scroll compressor operation.
Comm3/4. Trane proprietary network communication protocol.
Comm5. Trane's implementation of LonTalk or BACnet (an open network
communication protocol).
Condenser Pressure. The saturated condenser pressure measured on each circuit's(2)
condenser section on Evaporative Condenser units. Condenser pressure is converted
to Saturated Condenser Temperature for display on the Human Interface. The data
from these sensors is used in head pressure control.
Control Band. The range of temperatures or pressures which would normally be
maintained by the various control functions.
Control Point. The value of a SETPOINT that an algorithm is using at any given time.
Deadband. As applied to SA temp control, this refers to a range of temperatures
equally spaced above and below the SA temp control point in which the control
algorithm is satisfied.
Dehumidification Override High Zone Temp. The temperature in the critical zone on
VAV units where Dehumidification is disabled to prevent over-heating the space due toexcess reheat.
Dehumidification Override Low Zone Temp. The temperature in the critical zone on
VAV units where Dehumidification is disabled to prevent sub-cooling the space due to
insufficient reheat.
Demand Control Ventilation (DCV). An ASHRAE compliant ventilation scheme that
varies the Outside Air Damper minimum position or Fresh Air Flow (TRAQs) between
minimum and maximum ventilation SETPOINTs based on CO2level.
Dry Bulb. An outdoor temperature above which economizing will be disabled (unless
comparative enthalpy is the economizer control type being used.)
Economizer Zone Temp SETPOINT Suppression. a parameter used for setting the Zone
Temp SETPOINT at a lower value than the mechanical cooling zone temp SETPOINT.
Emergency Stop. A binary input on the RTM which allows unit shutdown with manual
reset when connected to a field-supplied switch.
Energy Recovery Wheel. A device incorporating a specially coated rotating disc that
spins across both outdoor and exhaust air streams transferring to or removing energy
from the incoming outdoor air prior to mixing with return air to increase unit efficiency.
-
8/14/2019 ipak trblshoot
6/150
6 RT-SVP04F-EN
General Information
Evap Diff. Evap Diff is a calculated value indicating performance of a refrigeration
system. It is calculated by determining the difference between the Entering and Leaving
temperatures of the evaporator. If this value rises too high it may indicate a problem
with the system.
External Stop. A binary input on the RTM that allows unit shutdown, with automatic
reset, when connected to a field-supplied switch.
Hot Gas Bypass. A feature to reduce a refrigeration circuit's cooling capacity by
bypassing hot discharge line refrigerant directly to the evaporator coil of the system to
more effectively operate in low load conditions.
Humidification Control. During modes of continuous fan operation a relay is energized
when the Humidity measured in the controlled space drops below an adjustable
Humidification SETPOINT. The humidifier device is a user supplied device placed in the
supply air stream.
LonTalk. An open, device networking communications protocol for controls. This
protocol is defined in ANSI approved standard EIA/CEA-709.1-A-1999.
Low Ambient Compressor Lockout. A function which prevents compressor operation
at low outdoor ambient temperatures.
Night SetBack (NSB). Applies to the control of the rooftop unit during unoccupied
periods. Also refers to the NSB panel, a communicating wall sensor with night setback
capability.
Reference Enthalpy. An outdoor enthalpy value above which economizing will be
disabled.
Remote Human Interface. A human interface module designed to be mounted
remotely from the unit. There are some functional differences between a unit mounted
and a remote mounted human interface module.
Reset Amount Maximum. The maximum amount of reset allowed.
Reset End Temperature. The temperature at which the maximum reset amount will
occur.
Reset Start Temperature. The temperature at which reset will begin.
Return Fan Control. Return Fan Control is a feature which allows units to operate at a
higher external or duct system static pressure, or to reduce the load (horsepower
requirement) on the supply fan motor. The fan is placed in the return air path.
Return Fan Plenum Pressure. The area between the Exhaust and Return Dampers and
the outlet of the Return Fan defines the return plenum. The absolute static pressure
measured in this area is the Return Fan Plenum Pressure.
-
8/14/2019 ipak trblshoot
7/150
RT-SVP04F-EN 7
General Information
Return Plenum Pressure High Limit. This control feature, available on all return fan
options, shuts the supply fan and return fan off if the pressure in the return plenum
exceeds a non-adjustable SETPOINT of 3.5 iwc.
Space Pressure. The pressure in the building as measured by the Space Pressure
Transducer, referenced to outside (atmospheric) pressure.
Supply Air Pressure High Limit. A pressure limit to prevent unit casing and/or ductwork
over pressurization.
Statitrac. A trademark for control of space pressurization.
Supply Air Pressure. The pressure in inches water column (IWC) of the supply duct
plenum or outlet as measured by the Supply Air Pressure Transducer, referenced to
local outside (atmospheric) pressure.
Supply Air Tempering. Turning on heat when the supply air temperature drops below a
preset value usually due to cold outside air being brought in to provide building
ventilation.
Supply Air Temperature Control Point. The revised value of supply air temperature
SETPOINT after supply air temp reset has been applied.
Supply Air Temperature Reset. A function that shifts the SA Temp SETPOINT an
amount based on the value of another parametertypically Zone Temp or Outdoor Air
Temp. The purpose of this function is to lower unit capacity to better meet load
requirements.
Target. Dynamic control point the unit is controlling to at any given time.
UCM Control System
Trane Large Commercial Rooftop Units are controlled by a microelectronic control
system that consists of a network of modules and are referred to as Unit Control
Modules (UCM).
The unit size, type (CV or VAV), heating functions, peripheral devices, options, exhaust
capabilities, etc. determine the number and type of modules that a particular rooftop
unit may employ.
The UCM receives analog and binary inputs, then processes this information and
supplies outputs in the form of modulating voltages, contact closures, etc. to controldamper actuators, fan motors, compressors, valves, electric heating coils and other
electrical devices in the unit to maintain set comfort levels.
The UCM provides some equipment protection functions both directly and indirectly,
such as duct pressure limits and compressor lockouts.
Listed below are the various modules that may be employed in a UCM control system.
-
8/14/2019 ipak trblshoot
8/150
8 RT-SVP04F-EN
General Information
Rooftop Module (1U1 IntelliPak II) (1U48 IntelliPak I)
(Standard on all units) The RTM is the central processor of the system. It continuously
receives information from the other unit modules, sensors, the remote control panel,
and customer supplied relays. It then interprets this information and responds to
cooling, heating, and ventilation requests by directing the other modules in the system
to energize the proper unit components. It also directly initiates supply and exhaust fan
operations, and economizer operation.
Compressor Module (SCM/MCM) (IU3 IntelliPak II) (1U49 IntelliPak I)
The Compressor module, (Single Circuit & Multiple Circuit), upon receiving a request
for mechanical cooling, energizes the appropriate compressors and condenser fans. It
monitors the compressor operation through feedback information it receives from
various protection devices.
Heat Module (1U6 IntelliPak II) (1U50 IntelliPak I)
(Standard on all heating units) The Heat module directs the units heater to stage up and
down to bring the temperature in the controlled space to within the applicable heating
SETPOINT.
Exhaust/Comparative Enthalpy Module (1U5 IntelliPak II) (1U52 IntelliPak I)
(Option - used with Statitrac and/or comparative enthalpy) The ECEM receives data
from the return air humidity sensor, the return air temperature sensor, and the return air
space pressure transducer to control the economizer, exhaust fan and the exhaust
dampers to maintain set space pressure.
Ventilation Control Module (7U14 IntelliPak II) (3U218 IntelliPak I)
(Option - used with TRAQ dampers, DCV, and Outdoor Air Preheat) The VCM receives
data from two velocity pressure sensors associated with front and back TRAQ
assemblies to measure fresh air flow entering the unit. These measurements are
converted to CFM and added to give total fresh air flow. This value can be used for
monitoring purposes, to maintain flow to a minimum fresh air flow SETPOINT, or to
maintain appropriate CO2levels in the controlled space using its space CO2sensor
input and the DCV feature. Without TRAQ assemblies installed the VCM can use DCV
and the CO2sensor input to control OA Damper minimum position to maintain CO2
levels in the space. A preheat control relay output is also provided on this module to
maintain tempered outdoor air during ventilation using the VCM Auxiliary Temperature
input. The preheat unit is user-supplied.
Multi Purpose Module (1U9 IntelliPak II) (1U105 IntelliPak I) (Optional - used
with Return Fan Control)
The MPM supports the function of return plenum pressure control by providing inputs
for measuring return plenum pressure, calibrating that reading, and providing an
output to control the return fan speed (if variable speed configured) in response to
control algorithm requests.
-
8/14/2019 ipak trblshoot
9/150
RT-SVP04F-EN 9
General Information
Modulating Dehumidification Module (1U15 IntelliPak II) (1U107 IntelliPak I)
(Optional - used with Dehumidification Control)
The MDM supports specific control inputs and outputs for Modulating Dehumidification
control including modulating Reheat and Cooling valve control as well as the Reheat
Pumpout Coil Relay output.
Generic Building Automation System Module (1U10 = GBAS 0-5V, 1U11 = GBAS
0-10V IntelliPak II) (1U51 = GBAS 0-5V/0-10V IntelliPak I) (Optional - used with
Non-Trane Building Control System)
The Generic Building Automation System (GBAS) module allows a non-Trane building
control system to communicate with the unit and accepts external SETPOINTs in form
of analog inputs (0 - 5 V or 0 - 10 V depending on the module selected) and a binary
Input for demand limit. Five (5) binary outputs are available on 0 - 5 V modules. One (1)
binary output and four (4) analog outputs are available on the 0 - 10 V modules. Refer tothe Field Installed Control Wiring section of the Unit Installation, Operation,
Maintenance Manual (IOM) for the control wiring to the GBAS module and the various
desired SETPOINTs with the corresponding DC voltage inputs.
Ventilation Override Module (VOM) (1U8 IntelliPak II) (1U53 IntelliPak I)
(Optional - used on units with special ventilation requirements)
The Ventilation Override module can control the units air handling functions to perform
customer specified functions such as space pressurization, exhaust, purge, unit off, etc.
Interprocessor Communications Board (IPCB) (1U12 IntelliPak II) (1U55
IntelliPak I) (Optional - used with Optional Remote Human Interface)
The Interprocessor Communication Board expands communications from the unit UCM
network to a Remote Human Interface Panel. DIP switch settings on the IPCB module for
this application should be; Switches 1 and 2 Off, Switch 3 On.
BACnet Communication Interface Module (BCI) (1U66 IntelliPak II) (1U104
IntelliPak I) (Optional - used on units with Trane ICS or 3rd party Building
Automation Systems)
The BACnet Communication Interface module expands communications from the unit
UCM network to a Trane Tracer Summit, or a 3rd party building automation system that
utilizes BACnet, and allows external SETPOINT and configuration adjustment andmonitoring of status and diagnostics.
Lontalk Communication Interface Module (LCI) (1U7 IntelliPak II) (1U65
IntelliPak I) (Optional - used on units with Trane ICS or 3rd party Building
Automation Systems)
The LonTalk Communication Interface module expands communications from the unit
UCM network to a Trane Tracer Summit, or a 3rd party building automation system that
utilizes LonTalk, and allows external SETPOINT and configuration adjustment and
monitoring of status and diagnostics.
-
8/14/2019 ipak trblshoot
10/150
10 RT-SVP04F-EN
General Information
Human Interface Module (Local = 1U2, Remote = 9U13 IntelliPak II) (1U65 IntelliPak I)
The Human Interface (HI) Module illustrated in Figure 1is the device which enables the
customer, building owner, or contractor, to communicate to the Rooftop unit the
necessary parameters for unit operation such as cooling and heating SETPOINTs,
demand limiting, ventilation override modes, etc.
The local (unit mounted) Human Interface and the Remote Human Interface Panel
functions are identical, except for Service mode which is not available on the Remote
Human Interface Panel.
The local HI Module is located in the units main control panel. A small door located in
the units control panel door allows access to the HI Modules keypad and display
window.
There is a 2 line by 40 character LCD screen which provides status information for the
various unit functions as well as menus used to set or modify the operating parameters.
There is a 16 key keypad adjacent to the LCD screen, which allows the operator to scroll
through the various menus and make adjustments to the SETPOINTs, etc.
The information displayed in the LCD window will be top-level status information
unless the operator initiates other displays.
At power-up, the Human Interface LCD will display one of four initial screens illustrated
in the General Status section.
1. Unit Status (Unit Off or Stopped) (The unit is configured and operational, but is not
running). This screen shows state, mode, and function information when the unit is
off or stopped.
2. Unit Status (Unit On) (The unit is configured and operational, and is running). Thisscreen shows state, mode, and function information when the unit is on.
3. VOM Active (a ventilation override command was received) This screen shows that
the unit is in a Ventilation Override Mode.
4. No Configuration (the unit needs to be configured). This screen shows that required
configuration data is missing.
The LCD screen has a backlight that makes the information easier to read. The light will
go out if no keys are pressed for 30 minutes. If it goes out, simply press the STATUS
key.
-
8/14/2019 ipak trblshoot
11/150
RT-SVP04F-EN 11
General Information
Menu Keys
The six keys illustrated in Figure 2in the MENU area (STATUS, SETPOINTS, SETUP,
CONFIGURATION, DIAGNOSTICS, and SERVICE MODE) are used to bring up the
various interactive menus where the user inputs and accesses unit operating data.
Pressing these keys will display the initial screen for the menu designated by the keys
name. The following information describes the keys and their functions when viewing
the various menus.
If no key is pressed for 30 minutes while the LCD is displaying a menu screen, it will
revert back to the unit operating status screen.
STATUS Key
Pressing the STATUS key causes the LCD to display the operating status screen; i.e.
On, Unit Stop, External Stop, Emergency Stop, Service Mode. Pressing the
NEXT key allows the operator to scroll through the screens which provide information
such as air and refrigerant temperatures, humidity levels, fan operation, compressor
operation, heater operation, economizer positioning, exhaust operation, as well as
heating, cooling, and compressor lockout SETPOINTs. Pressing the STATUS key while
viewing any of the data screens will cause the LCD to go back to the operating status
screen.
Figure 1. Human Interface Module
-
8/14/2019 ipak trblshoot
12/150
12 RT-SVP04F-EN
General Information
SETPOINTS Key
Pressing the SETPOINTS key will cause the LCD screen to display the first of the
SETPOINT screens where the operator will designate default temperature and pressure
SETPOINTs. While scrolling through the SETPOINT screens, pressing this key again will
cause the LCD to display the first SETPOINT screen.
DIAGNOSTICS Key
Pressing the DIAGNOSTICS key at any time will allow the operator to view any unit
function failures. The LCD screen will display one of the diagnostic screens (depending
on which diagnostic, if any, is present). If no key is pressed for 30 minutes while the
screen is displaying diagnostic information, it will revert back to the operating status
display.
CONFIGURATION KeyPressing the CONFIGURATION key will cause the LCD screen to display the first of the
configuration screens where the operator will designate unit configuration data such as
unit type, capacity, system control, etc....
This information was programmed at the factory. Pressing the configuration key at any
level in the configuration menu will display the first configuration screen.
Note: This key should be used if the units configuration data is lost or new options are
added in the field, and to view current configuration.
SETUP Key
Pressing the SETUP key will cause the LCD screen to display screens where theoperator will designate various operating parameters such as temperature and
pressure ranges, limits, percentages, SETPOINT source selections, and sensor input
definitions for the control of the rooftop units various operating modes. Pressing the
SETUP key at any level in the SETUP menu will display the first SETUP screen.
SERVICE MODE Key
Pressing the SERVICE MODE key causes the LCD to display the first of the service test
mode screens showing various unit components which may be turned on or off for the
particular test being performed. Once the status of these components is designated, the
LCD will display screens that allow the operator to designate the TEST START time
delay for each test.
Data Manipulation Keys
The six data manipulation keys illustrated in Figure 2, (ENTER, CANCEL, + (Plus), -
(Minus), PREVIOUS, and NEXT are used to modify the data within the screens (change
values, move the cursor, confirm choices, etc....)
-
8/14/2019 ipak trblshoot
13/150
-
8/14/2019 ipak trblshoot
14/150
14 RT-SVP04F-EN
General Information
STOP Key
Pressing the STOP key will cause the unit to transition to the stop state. If the current
display is editable, pressing the STOP key will cancel the desired edit.
TEST START Key (SERVICE)
Pressing this key while viewing any screen in the SERVICE Mode menu will start the
service test. When viewing status, SETUP, SETPOINT, and diagnostics screens, it has no
function.
CUSTOM Key
The Custom menu is simply a status menu that contains screens that the user monitors
most frequently. The Custom menu can only contain five status screens. To create the
Custom menu, press the STATUS key, followed by the NEXT key (this brings up the
initial status screen). If you want to add this screen to the Custom menu, press the +
(Plus) key, if not, press the Next key again until a status screen appears that you would
like to add to the Custom menu. Pressing the + (Plus) key while viewing any of the
various status screens will add that screen to the Custom menu. Once the Custom
menu is programed it can be accessed by pressing the CUSTOM key. To remove a
status screen from the Custom menu, press the CUSTOM key, then press the NEXT key
until the status screen that you want to remove appears, then press the - (Minus) key.
-
8/14/2019 ipak trblshoot
15/150
RT-SVP04F-EN 15
General Information
General Status Display
Anytime the rooftop unit is powered up, or the STATUS, AUTO, or STOP keys are
pressed, the unit mounted Human Interface will display one of the following four
general status display screens. The operator will then be able to enter keystrokes which
will allow him to navigate through a set of menus and submenus in order to provide/
access various monitoring, SETUP, and configuration information. The Human Interface
will not display screens or parts of screens for which the unit is not configured.
Unit Off or Stopped
If at power up the unit is not running, the following display will appear on the Human
Interface LCD screen. When this screen is being displayed, the only functional keys arethe six menu keys (STATUS, SETPOINTS, DIAGNOSTICS, SETUP, CONFIGURATION,
and SERVICE MODE), the AUTO key, the CUSTOM key, and the STOP key.
Figure 2. Human Interface Keypad
-
8/14/2019 ipak trblshoot
16/150
-
8/14/2019 ipak trblshoot
17/150
RT-SVP04F-EN 17
General Information
Emergency Override Active (units with LCI or BCI module)
If the unit has entered an Emergency Override mode of operation, one of the following
displays will appear on the Human Interface LCD screen.
Ventilation Override Mode
PRESSURIZE
Ventilation Override Mode
DEPRESSURIZE
Ventilation Override Mode
PURGE
Ventilation Override Mode
SHUTDOWN
Ventilation Override Mode
FIRE
VVDA OA Flow ___ CCFM SupplyFan
___________
CVZT
VVDA
CVDA
Occupied
Unoccupied
Morning WU
Daytime WU
Standby
Shutdown
Occupied TOV
Initializing
(Blank)
Tempering
ONOFF
(Blank)
Diagnostics
______ ____________
Heat
Cool
OA Dmpr
Dehumid
Purge
Humidify
(Blank)
1-6
1-6
0-100%
OA Flow
(Blank)
Range
0-5980 CCFM
(Blank)
Freeze Avoidance
-
8/14/2019 ipak trblshoot
18/150
18 RT-SVP04F-EN
General Information
VOM Active
If at power up the unit is running and has entered a Ventilation Override mode of
operation, the following display will appear on the Human Interface LCD screen.
No Configuration
If at power up the unit has not been programmed with the necessary configuration data
for normal unit operation, the following display will appear on the Human Interface LCD
screen. When this screen is being displayed, the only functional key is the
CONFIGURATION key.
Note: This screen will only appear when the RTM has been field replaced. Refer to the
Configuration Menu.
Factory Presets
The UCM controlled unit has many operating functions which are preset at the factory,
but may be modified to meet the unique requirements of each job. The following list
identifies each of the units adjustable functions and the value assigned to it. If these
factory presets match the applications requirements, simply press the AUTO key at the
Human Interface module to begin unit operation (after completing the Pre-Start and
Start-Up procedures in the Installation, Operation, and Maintenance manual). If the
application requires different settings, turn to the listed page beside the function, press
the designated function menu key, then press and hold the NEXT or PREVIOUS keyuntil its screen appears on the LCD. Once the proper screen appears, simply follow the
programming instructions given below the applicable screen in this manual.
Note: Record any changes made to the factory-preset values in the corresponding
space provided.
VO Mode in Operation
(A,B,C,D,E)
Trouble Indicator
(Blank)
(Diagnostics)
Ventilation Override Mode ______
_____________
No Configuration Present
Press Configuration Key
-
8/14/2019 ipak trblshoot
19/150
RT-SVP04F-EN 19
General Information
Adjustable Function Factory Preset Changed To
To adjust
Press...
Control Parameters
Default system mode Auto SETUP
Demand limit definition for cooling None SETUP
Demand limit definition for heating None SETUP
Economizer control enable type Drybulb SETUP
Exhaust enable point 25% SETUP
Morning Warmup type Full SETUP
Supply air low limit 50 deg F SETUP
Unit Control Local SETUP
Coil Frost Cutout Temp 30 deg F SETUP
Evap Temperature Limit 35 deg F SETUP
OA Flow Calibration Gain (Front) 1.0 SETUP
OA Flow Calibration Offset (Front) 0 CFM SETUP
OA Flow Calibration Gain (Back) 1.0 SETUP
OA Flow Calibration Offset (Back) 0 CFM SETUP
OA Flow Calibration Data - Altitude: 0 feet SETUP
Unit Address (Comm3/Comm4 only) 1 SETUP
Default SETPOINTs
Economizer drybulb enable SETPOINT 75 deg F SETPOINTS
Low ambient compressor lockout (Std. units) 50 deg F SETPOINTS
Low ambient compressor lockout (Low ambient units) 0 deg F SETPOINTS
Occupied zone temp SETPOINT - cooling 74 deg F SETPOINTS
Occupied zone temp SETPOINT - heating 71 deg F SETPOINTS
Space pressure - deadband .04 iwc SETPOINTS
Space pressure - SETPOINT 0.08 iwc SETPOINTS
Occ Dehumidification 60% SETPOINTS
Occ Dehumid Hysteresis Offset 5% SETPOINTS
Unocc Dehumidification 60% SETPOINTS
Unocc Dehumid Hysteresis Offset 5% SETPOINTS
Supply Air Reheat Setpoint 70 F SETPOINTS
Supply Air Reheat Deadband 4 F SETPOINTS
Maximum Reheat Valve Limit 85% SETPOINTSDehumid Ovrd High Zone Temp Stpt 75 F SETPOINTS
Dehumid Ovrd Low Zone Temp Stpt 68F SETPOINTS
Cond Coil Purge Interval 90 min SETPOINTS
Unoccupied zone temp - cool 85 deg F SETPOINTS
Unoccupied zone temp - heat 60 deg F SETPOINTS
Unoccupied zone temp - morn warmup 72 deg F SETPOINTS
Min OA Flow - SETPOINT w\VCM Set per unit size SETPOINTS
Min OA Flow - deadband Set per unit size SETPOINTS
Preheat actuate temp 35 deg F SETPOINTS
-
8/14/2019 ipak trblshoot
20/150
20 RT-SVP04F-EN
General Information
Design Min CO2(DCV) 1000 PPM SETPOINTS
DCV Min CO2 8001/4002PPM SETPOINTS
DCV Min OA Flow Deadband 5 CCFM SETPOINTS
Design Min OA Flow (DCV) 220 CCFM SETPOINTS
DCV Min OA Flow 67 CCFM SETPOINTS
Design Min OA Damper Position(DCV) 15% SETPOINTS
DCV Min OA Damper Position 5% SETPOINTS
OA Damper Min Position (non-DCV) 15% SETPOINTS
Hydronic Heat Freeze Avoidance Open To: 0% SETPOINTS
Recovery Frost Avoidance Setpoint 27F SETPOINTS
Functions enable/disable
Compressor lead/lag Enable SETUP
Adjustable Function
Factory
Preset Changed To
To adjust
Press...
Morning warmup Enable SETUP
Supply air tempering Enable SETUP
Unoccupied economizer Enable SETUP
Unoccupied mechanical cooling Enable SETUP
Unoccupied heating Enable SETUP
Occupied Dehumidification Enable SETUP
Unoccupied Dehumidification Enable SETUP
Demand Control Ventilation Disable SETUP
Occupied Humidification Disable SETUP
Unoccupied Humidification Disable SETUP
GBAS Input/Output Definitions...
GBAS analog input definitions Not Assigned SETUP
GBAS output definitions SETUP
Information format
Text displays English SETUP
Unit displays English SETUP
RTM alarm output definitions Any Active Diagnostic SETUP
Sensor source selection for...
Monitor RTM Zone Temp SETUP
Morning warmup RTM Zone Temp SETUP
Occupied zone control RTM Zone Temp SETUP
Unoccupied zone control RTM Zone Temp SETUP
Space Humidity Control RTM Space Humidity SETUP
Dehumid OVRD Zone Temp RTM Zone Temp SETUP
SETPOINT source selection for...
Morning warmup Default SETUP
Occupied zone cooling Default SETUP
-
8/14/2019 ipak trblshoot
21/150
RT-SVP04F-EN 21
General Information
Occupied zone heating Default SETUP
Space Pressure Default SETUP
Unoccupied zone cooling Default SETUP
Unoccupied zone heating Default SETUP
Economizer Dry Bulb Enable Default SETUP
Occupied Dehumidification Default SETUP
Unoccupied Dehumidification Default SETUP
Supply Air Reheat Default SETUP
OA Damper Actuator (if equipped)
Actuator SETUP DIRECT SETUP
Max stroke time 30 sec SETUP
Max voltage 10 VDC SETUP
Min voltage 2 VDC SETUP
Exhaust Damper Actuator (if equipped)
Actuator SETUP... (Direct/reverse action) DIRECT SETUP
Max stroke time 30 sec SETUP
Max voltage 10 VDC SETUP
Min voltage 2 VDC SETUP
Adjustable Function
Factory
Preset Changed To
To adjust
Press...
Hydronic Heat Actuator (if equipped)
Actuator SETUP... (Direct/reverse action) Direct Acting SETUP
(Max stroke time) 60 seconds SETUP
(Max voltage) 10 VDC SETUP
(Min voltage) 2 VDC SETUP
Lo Ambient Damper Actuator Ckt#1 and Ckt #2
(if equipped)
Actuator SETUP... (Direct/reverse action) Direct Acting SETUP
(Max stroke time) 60 seconds SETUP
(Max voltage) 10 VDC SETUP
(Min voltage) 2 VDC SETUP
Cond Fan VFD Ckt #1
Actuator SETUP Direct Acting SETUP
Max Stroke Time 60 sec SETUP
Max Voltage 10 VDC SETUP
Min Voltage 0 VDC SETUP
Cond Fan VFD Ckt #2
Actuator SETUP Direct Acting SETUP
Max Stroke Time 60 sec SETUP
Max Voltage 10 VDC SETUP
Min Voltage 0 VDC SETUP
-
8/14/2019 ipak trblshoot
22/150
22 RT-SVP04F-EN
General Information
Supply Fan IGV/VFD (if equipped)
Actuator SETUP Direct Acting SETUP
Max Stroke Time 30 sec SETUP
Max Voltage 10 VDC SETUP
Min Voltage 2 VDC SETUP
Exhaust Damper/VFD (if equipped)
Actuator SETUP Direct Acting SETUP
Max Stroke Time 60 sec SETUP
Max Voltage 10 VDC SETUP
Min Voltage 0 VDC SETUP
Return Fan VFD (if equipped)
Actuator SETUP Direct Acting SETUP
Max Stroke Time 60 sec SETUP
Max Voltage 10 VDC SETUP
Min Voltage 2 VDC SETUP
Exhaust bypass damper
Actuator SETUP Direct Acting SETUP
Max Stroke Time 60 sec SETUP
Max Voltage 10 VDC SETUP
Min Voltage 2 VDC SETUP
Outdoor air bypass damper
Actuator SETUP Direct Acting SETUP
Max Stroke Time 60 sec SETUP
Max Voltage 10 VDC SETUP
Min Voltage 2 VDC SETUP
Modulating Gas Heat Actuator (if equipped)
Actuator SETUP... (Direct/reverse action) Direct2/Reverse1
Acting
SETUP
Max stroke time 90 seconds SETUP
Max voltage 10 VDC SETUP
Min voltage 2 VDC2/5 VDC1 SETUP
Head Pressure Control
Temporary low limit suppression 10 deg F SETUP
Upper limit 120 deg F SETUP
Low limit 80 deg F SETUP
Efficiency check point 105 deg F SETUP
Low ambient control point 90 deg F SETUP
Sump Drain Relay Control (on power loss)2 Drain SETUP
Sump Purge Interval Time2 3 hours SETUP
-
8/14/2019 ipak trblshoot
23/150
RT-SVP04F-EN 23
General Information
Password Protected Screens
Some of the operating displays on the Human Interface LCD screens and require a
password to change. The following screens display the various programming sections
that require a password in order to view or to modify the preset operating parameters.
The password for each screen is a different series of + (Plus) or - (Minus) key strokes in
a predefined sequence. Shown below are the password protected screens, and the
passwords for accessing them.
The following screens display the various programming sections that require a specific
PASSWORD to be entered by a qualified operator in order to modify the operating
parameters. The following screen will appear if the PASSWORD is not entered within
approximately 15 seconds.
Sump Purge Duration Time2 60 sec. SETUP
Sump Water Heater Setpoint2 38 F SETUP
Temperature Input Offset for...
Heat morning warmup 0 deg F SETUP
Return air 0 deg F SETUP
RTM zone temperature 0 deg F SETUP
RTM aux temperature 0 deg F SETUP
Outdoor air 0 deg F SETUP
Ventilation override definition See Definitions SETUP
Note 1. Reference note 1 applies to IntelliPak I units only.Note 2. Reference note 2 applies to IntelliPak II units only.
Password Entry Time Limit Exceeded
1. Press the NEXT key until the following screen is displayed.
Configuration is Password Protected
Please Enter Password: __________
2. Press the + or - keys in this sequence ( + - - - ) to access this restricted screen.
3. Press the ENTER key to confirm the password and enter the menu.
4. Press the NEXT key until the following screen is displayed.
Ventilation Override Mode _______
Enter Password to Lock Definition:
1. Press the + or - keys in this sequence ( + - - + ) to lock each VO Mode.
2. Press the ENTER key to confirm the password and Lock the definitions.
3. Press the NEXT key until the following screen is displayed.
-
8/14/2019 ipak trblshoot
24/150
24 RT-SVP04F-EN
General Information
Diagnostic Reset is Password Protected
Please Enter Password: ____________
1. Press the + or - keys in this sequence ( - + + ) to access this restricted screen.
2. Press the ENTER key to confirm the password and Lock the definitions.
3. Press the NEXT key until the following screen is displayed.
Diagnostic Log is Password Protected
Please Enter Password: __________
1. Press the + or - keys in this sequence ( - + + -) to access this restricted screen.
2. Press the ENTER key to confirm the password and Lock the definitions.
3. Press the NEXT key until the following screen is displayed.
-
8/14/2019 ipak trblshoot
25/150
RT-SVP04F-EN 25
STATUS MenuThe STATUS menu is used to view various operating conditions such as temperatures
and humidity levels. Its used to view unit component status such as fan, compressor,
heater, and economizer operation, as well as SETPOINT status.
The screens shown in this section are for example only. Pressing the + (Plus) key while
viewing any of the status display screens will add that screen to the Custom menu.
When a status screen is displayed for 30 minutes without a key being pressed, the LCD
screen will revert to the general operating status display. If this happens, press the
STATUS key again to return to the status menu. The following are examples of status
screens that may be viewed by pressing the STATUS key.
Note: Many of the screens displayed in this section are applicable only for the options
that are installed in the unit and may not be visible on your unit.
Press the STATUS key to begin viewing the status screens.
Note: The range for all temperature inputs is 40 to 200 F. ERR will appear if the
temperature is out of range.
System Operating Status
VAV OA FLOW
OCCUPIED
*350.0 CCFM OADMPR 0%
SUPPLY FAN ONDIAGNOSTICS
Notes: *VCM only - if the unit does not havea VCM this section of the screen isblank.
1. Press the NEXT key until the following screen is displayed.
GENERAL SYSTEM STATUS SUBMENU SCREENS
General System Status Submenu
Press ENTER to View Data in this Submenu
Used With: All Units
1. Pressing the NEXT key will bypass this section.
Active Unit Control Source:
Active Cluster Member Role:
XXXXXXXXXXXX
XXXXXXXXXX
Used With: All Units
Possible Values:Source = Local,
BAS/Network
Role = Standalone, Slave, Master
1. Pressing the NEXT key will scroll forward through the screens.2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custommenu for the creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed. (if applicable)
-
8/14/2019 ipak trblshoot
26/150
26 RT-SVP04F-EN
System Operating Status
RTM Supply Fan Relay:
RTM Supply Airflow Proving:
OFF
FLOW
Used With: All Units
Possible Values:Fan = ON, OFF
Airflow = FLOW, NO FLOW
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custommenu for the creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed. (if applicable)
Supply Fan IGV/VFD Cmd Opening To 30%
Active Supply Air Pressure 2.0 IWC
Used With:All units with IGV/VFD.Active SAP only shown if SAP ispresent.
Possible Values: Opening to/
Closing to: 0-100%; Active SupplyAir Pressure= 0.0 -7.9 IWC
1. Press the NEXT key until the following screen is displayed.
OR
Active Supply Air Pressure 2.0 IWC
Used With: Rooftop units and AirHandlers when IGV/VFD is notinstalled and valid SAP sensor ispresent.
1. Press the NEXT key until the following screen is displayed. Possible Values: 0.0 IWC - 7.9IWC
Exhaust Fan OFF Used With:All units when PowerExhaust without Statitrac is installed
without Return FanPossible Values:Fan= ON/OFF,
1. Press the NEXT key until the following screen is displayed.
OR
Exhaust Fan ON
Exhaust Damper/VFD
Space Pressure
Opening to
0.00 IWC
32 %
Used With:All units when PowerExhaust with Statitrac is installedwithout Return Fan
Possible Values:Fan= ON, OFF,Damper/VFD = 0 to 100%
1. Press the NEXT key until the following screen is displayed. (ifapplicable)
Note: "Exhaust Fan" and "Exhaust Damper/VFD" is shown only if
"Power Exhaust Config" is not = NONE
"Exhaust Fan" is not shown if Return Fan is installed
"Space Pressure" is shown only if Power Exhaust or ReturnFan with Statitrac is installed
-
8/14/2019 ipak trblshoot
27/150
RT-SVP04F-EN 27
System Operating Status
Electric Heat: ENABLED
Stage: 6 K11: ON K12: ON K1: ON
Used With:All units with ElectricHeat installed.
Possible Values: Electric Heat:
ENABLED, DISABLED By Setup,LIMITED By Demand Limit
Stage: 0,1,2,3,4,5,6K*: ON, OFF
1. Press the NEXT key until the following screen is displayed.
(If applicable)
Note: Enabled indicates OK to
heat; disabled indicates
NOT OK to heat, such as
during cooling.
OR
Gas Heat: ENABLED
Stage: 2 K11: ON K12: ON K1: ON
Used With:All units with StagedGas Heat Installed.
Possible Values: ENABLED,DISABLED By Setup, LIMITED By
Demand LimitStage: 0,1,2K*: ON, OFF
1. Press the NEXT key until the following screen is displayed. (Ifapplicable)
OR
Hydronic Heat ENABLED
Valve Position: Opening To: 100%
Used With: All units with hydronic
heat is installed
1. Press the NEXT key until the following screen is displayed. Low tempair may be OK or tripped (If applicable)
Possible Values:ENABLED,DISABLED By Setup, LIMITED ByDemand Limit, LIMITED By Low AirTemp; Valve Position: Opening to/Closing to 0-100%
OR
Mod Gas Heat ENABLEDValve Position: Opening To: 100%
Used With: All units withmodulating gas heat is installed
1. Press the NEXT key until the following screen is displayed. (Ifapplicable)
Possible Values:ENABLED,DISABLED By Setup, LIMITED By
Demand Limit; Valve Position:Opening to/Closing to 0-100%
Chilled Water:
Valve Position:
Opening To ENABLED
100%
Used With:Air Handler Units withChilled Water Installed
Possible Values:Chilled Water:ENABLED, DISABLED By SETUP,LIMITED By Demand Limit, LIMITED
By Low Air Temp; Valve Position -Field One: Opening To, Closing To -Field Two: 0-100%
-
8/14/2019 ipak trblshoot
28/150
28 RT-SVP04F-EN
System Operating Status
Dehumidification Status:
by Comfort Control Override is Active
DISABLED Used With:All IntelliPak withDehumidification option installed.
1. Pressing the NEXT key will scroll forward through the screens. Top Line Possible Values:
ENABLED, DISABLEDBottom line Possible Values: See
below
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the NEXT key until the following screen is displayed.
(if applicable)
by Call for Cooling Demand Limit If 1st line is "DISABLED"
by Compressor Lockout Sources If 1st line is "DISABLED"
by Occ Dehumid Function Disable If 1st line is "DISABLED"
by Dehumid Override Zone Temp High If 1st line is "DISABLED"
by OA Temperature Out Of Range If 1st line is "DISABLED"
by Unocc Dehumid Function Disable If 1st line is "DISABLED"by Comfort Control Override is Active If 1st line is "DISABLED"
by Required Sensor Failure Condition If 1st line is "DISABLED"
by Insufficient Airflow Condition If 1st line is "DISABLED"
by Sat Reheat Cond Temp Sensor Fail If 1st line is "DISABLED"
By Reheat Head Pressure High Limit If 1st line is "DISABLED"
(Blank) If 1st line is "ENABLED"
Condenser Coil Purge is Active If 1st line is "ENABLED"
HumidificationStatus:
Humidification isActive
ENABLED Used With:Used With: All unitswith Humidification option installed.
Key Stroke Operation (1)
1. by Occ Humidification Function Disable
2. by Unocc Humidification Function Disable
3. Humidification is Inactive
4. Humidification is Active
Possible Values: ENABLED,DISABLEDby Occ Humidification FunctionDisable (If 1st line is "DISABLED"),by Unocc Humidification FunctionDisable (If 1st line is "DISABLED"),Humidification is Inactive (If 1st lineis "ENABLED" and output is de-energized, Humidification is Active(If 1st line is "ENABLED" and outputis energized)
1. Press the NEXT key until the following screen is displayed. (Ifapplicable)
End of Submenu (NEXT) to Enter STATUS
1. Press the NEXT key to leave the submenu and show followingscreen.
2. Press PREVIOUS to page back through the submenu.
-
8/14/2019 ipak trblshoot
29/150
RT-SVP04F-EN 29
System Operating Status
Compressor Status Submenu
Press ENTER to View Data in This Submenu
Used With: All Rooftop Units andAir Handlers with DX Coolinginstalled.
1. Pressing the NEXT key will bypass this section.
Compressor Relay KXX XXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX (MORE)
Used With:IntelliPak I RooftopUnits and Air Handlers with DXCooling installed.
Possible Values:K10, K11
Second Field: ON, OFF, LOCKED
Bottom Field: Enabled or any itemfrom Lockout Sources List.
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view thepreviously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that screento the custom menu. Refer to the custom menu for the creation and
maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed. (if
applicable)
Ckt 1 Compr Relay K11: ON
Enabled............................................ (MORE)
Used With:All IntelliPak II Rooftopunits or Air Handlers with DXCooling.
Possible Values:K11: ON, OFF,LOCKED; Second Field: Enabled or
any item from Lockout Sources List
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that screen
to the custom menu. Refer to the custom menu for the creation andmaintenance of customized menus.
4. Press the NEXT key until the following screen is displayed. (ifapplicable)
Compressor Relay KXX XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX (MORE)
Used With:IntelliPak I RooftopUnits and Air Handlers with DX
Cooling installed.
Possible Values:K11, K12
Second Field: ON, OFF, LOCKED
Bottom Field: Enabled or any itemfrom Lockout Sources List.
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view thepreviously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that screento the custom menu. Refer to the custom menu for the creation andmaintenance of customized menus.
4. Press the NEXT key until the following screen is displayed. (ifapplicable)
Ckt 1 Compr Relay K12: LOCKED
Disabled By Evap Temp Sensor Fail (MORE)
Used With:All IntelliPak II Rooftop
units or Air Handlers with DXCooling.
Possible Values:K12: ON, OFF,LOCKED; Second Field: Enabled or
any item from Lockout Sources List
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view thepreviously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that screento the custom menu. Refer to the custom menu for the creation andmaintenance of customized menus.
4. Press the NEXT key until the following screen is displayed. (ifapplicable)
-
8/14/2019 ipak trblshoot
30/150
30 RT-SVP04F-EN
System Operating Status
Compressor Relay K3 XXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX (MORE)
Used With:All IntelliPak I RooftopUnits and Air Handlers with DXCooling installed.
Possible Values:Second Field: ON,OFF, LOCKED
Bottom Field: Enabled or any itemfrom Lockout Sources List.
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view thepreviously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that screento the custom menu. Refer to the custom menu for the creation andmaintenance of customized menus.
4. Press the NEXT key until the following screen is displayed. (ifapplicable)
Ckt 2 Compr Relay K3: OFF
Enabled............................................. (MORE)
Used With:All IntelliPak II Rooftopunits or Air Handlers with DXCooling.
Possible Values:K3: ON, OFF,
LOCKED; Second Field: Enabled orany item from Lockout Sources List
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that screento the custom menu. Refer to the custom menu for the creation andmaintenance of customized menus.
4. Press the NEXT key until the following screen is displayed. (ifapplicable)
Compressor Relay K4 XXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX (MORE)
Used With:All IntelliPak I RooftopUnits and Air Handlers with DXCooling installed.
Possible Values:Second Field: ON,OFF, LOCKED
Bottom Field: Enabled or any itemfrom Lockout Sources List.
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that screento the custom menu. Refer to the custom menu for the creation andmaintenance of customized menus.
4. Press the NEXT key until the following screen is displayed. (ifapplicable)
Ckt 2 Compr Relay K4: LOCKED
Disabled By Evap Temp Sensor Fail (MORE)
Used With:All IntelliPak II Rooftopunits or Air Handlers with DXCooling.
Possible Values:K4: ON, OFF,LOCKED; Second Field: Enabled or
any item from Lockout Sources List
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that screen
to the custom menu. Refer to the custom menu for the creation andmaintenance of customized menus.
4. Press the NEXT key until the following screen is displayed. (ifapplicable)
-
8/14/2019 ipak trblshoot
31/150
RT-SVP04F-EN 31
System Operating Status
Disable or Lockout Sources
Disabled By Compressor Protection (Compressor proving input did not close)
Disabled By Contactor Failure (Compressor proving input stuck closed)
Disabled By Low Pressure Cutout (Low pressure cutout input to MCM)Disabled By Bad Cond Temp Sensor (Temp Sensor is out of -40 F to 200 F range)
Disabled By Demand Limit (From GBAS or BAS/Network)
Disabled By Frost Protection (Leaving evap temp sensor colder than coil frost
temp setpoint (25 F to 35 F)
Disabled By BAS/Network Lockout
Disabled By Minimum Off Time (3 minutes)
Disabled By Low Ambient Lockout (setpoint range -20 F to 80 F)
Disabled By Ventilation Override (VOM input A-E or BAS/Network)
Disabled By LPC Delay (3 minutes)
Disabled By Water Flow Status
Disabled By Cond Coil Purge Request
Disabled By Sump Temp Sensor Fail
Disabled By Low Refrig Charge (Evap temp limit setpoint (24-45 F) has beenexceeded for 10 minutes
Disabled By Evap Temp Sensor Fail
Disabled By Sump Min Level Sensor Fail
Disabled By Sump Pump Failure
Disabled By Sump Min Level Control
* These entries apply to the following 4 screens.
Note: If a compressor output is
disabled or locked, these
lockout sources will be
found in the bottom field forIntelliPak I, or in the second
field for IntelliPak II.
Circuit 1 Evap Diff: 5.0
Enter Evap: 48.5 Leave Evap: 53.5
Used With: All Rooftop Units and
Air Handlers when DX cooling isinstalled.Possible Values:Evap Diff. = 0.0
to 200.0 F, Enter Evap= -40.0 to200.0 F, Leave Evap: -40 to 200.0F
1. Press the NEXT key until the following screen is displayed. (if
applicable)
Note: "Evap Diff" and associated value not displayed on inactive
circuit or for first ten minutes of circuit operation or if HGBP is
installed.
Note: "Enter Evap" and associated value not displayed if HGBP is
installed
1. Press the NEXT key until the following screen is displayed.
Circuit 1
Saturated Condensing Temp: 100.0
Used With:All Rooftops or Air
Handlers with DX Cooling.Possible Values:SaturatedCondensing Temp= -40.0 to 200.0F
1. Press the NEXT key until the following screen is displayed.
-
8/14/2019 ipak trblshoot
32/150
-
8/14/2019 ipak trblshoot
33/150
RT-SVP04F-EN 33
System Operating Status
Condenser Sump Pump Relay Command: ON Used With:All IntelliPak II unitswith water-cooled condensers
installed.Possible Values:Sump PumpRelay: ON, OFF; Sump Proving:FLOW, NO FLOW
Condenser Sump Pump Proving: FLOW
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the NEXT key until the following screen is displayed.
(if applicable)
Condenser Water Valve Relay Ckt1: OFF Used With:All IntelliPak II unitswith water-cooled condensersinstalled.
Possible Values:Water ValveRelay: ON, OFF; Water Valve:CLOSED, OPEN
Condenser Water Valve Ckt1: OPEN
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the NEXT key until the following screen is displayed.
(if applicable)
Condenser Water Valve Relay Ckt2: ON Used With:All IntelliPak II unitswith water-cooled condensersinstalled.
Possible Values:Water Valve
Relay: ON, OFF; Water Valve:CLOSED, OPEN
Condenser Water Valve Ckt2: CLOSED
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the NEXT key until the following screen is displayed.
(if applicable)
Condenser Sump Fill Relay: OFF Used With:All IntelliPak II units
with water-cooled condensersinstalled.
Possible Values:Sump Fill Relay:ON, OFF; Sump Fill Valve: CLOSED,
OPEN
Condenser Sump Fill Valve: OPEN
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the NEXT key until the following screen is displayed.
(if applicable)
Condenser Sump Drain Relay: ON Used With:All IntelliPak II unitswith water-cooled condensersinstalled.
Possible Values:Sump Drain
Relay: ON, OFF; Sump Drain Valve:CLOSED, OPEN
Condenser Sump Drain Valve: CLOSED
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the NEXT key until the following screen is displayed.
(if applicable)
Note: Valve position with Relay ON is configurable based on if need
to hold water in the sump or drain it on power loss. See
Installation and Operations Manual.
-
8/14/2019 ipak trblshoot
34/150
34 RT-SVP04F-EN
System Operating Status
Cond Sump Water Level Max Input: OPEN Used With:All IntelliPak II unitswith water-cooled condensersinstalled.
Possible Values:Max Input:CLOSED, OPEN; Min Input: CLOSED,
OPEN
Cond Sump Water Level Min Input: CLOSED
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the NEXT key until the following screen is displayed.
(if applicable)
External Sump Drain Request: INACTIVE Used With:All IntelliPak II unitswith water-cooled condensersinstalled.
Possible Values:ACTIVE,INACTIVE
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the NEXT key until the following screen is displayed.
(if applicable)
Reheat Coil Pumpout Relay: OFF Used With:All IntelliPak units withDehumidification installed.
Possible Values:Coil PumpoutRelay: ON, OFF; Coil Pumpout Valve:CLOSED, OPEN
Reheat Coil Pumpout Valve: CLOSED
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the NEXT key until the following screen is displayed.
(if applicable)
Dehumid Reheat Valve Position: 0% Used With:All IntelliPak units with
Dehumidification installed.
Possible Values:Reheat Valve: 0-Max Reheat Valve Position Setpoint;
Cooling Valve: 10-100%
Dehumid Cooling Valve Position: 100%
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the NEXT key until the following screen is displayed.
(if applicable)
Active Outside Air Temperature 70.0F Used With:All Rooftops or AirHandlers with DX Cooling.
Possible Values: Active Outside AirTemp= -40 to 200.0F; Low Ambient
Comp Lockout Temp= -20 to 80F(Default: 50 F Standard, 0 F Low-ambient with Hot Gas Bypass, 10 FLow-ambient without Hot GasBypass)
Low Ambient Comp Lockout Temp: 50F
1. Press the NEXT key until the following screen is displayed.
-
8/14/2019 ipak trblshoot
35/150
RT-SVP04F-EN 35
System Operating Status
End of Submenu (NEXT) to Enter STATUS
1. Press the NEXT key to leave the submenu and show following
screen.2. Press PREVIOUS to page back through the submenu.
ECONOMIZER STATUS SUBMENU SCREENS
Economizer Status Submenu
Press ENTER to View Data in This Submenu
Used With: All Units when aneconomizer is installed
1. Pressing the NEXT key will bypass the next section.
Air Economizing: ENABLED
Outside Air Damper Pos: 10%
Used With:All units when anEconomizer is installed.
Possible Values:Economizing:
ENABLED/DISABLED Outside Air:Opening To/Closing To 0 - 100%
1. Press the NEXT key until the following screen is displayed.
Note: Enabled = OK to economize
Disabled = Not OK to
economize
Active Outside Air Enthalpy
ECEM Return Air Enthalpy
29.5 BTU/LB
34.0 BTU/LB
Used With:All Units when anEconomizer is installed. "RA Enth" isdisplayed if Comparative Enthalpy orEnergy Recovery is installed.
1. Press the NEXT key until the following screen is displayed. Possible Values: 10 to 35 BTU/LB
Active Outside Air Temperature
ECEM Return Air Temperature
86.0 F
78.0 F
Used With:All Units when anEconomizer is installed. "RA Temp"is displayed if Comparative Enthalpyor Energy Recovery is installed.
1. Press the NEXT key until the following screen is displayed. (ifapplicable)
Active Outside Air Humidity
ECEM Return Air Humidity
30 %
62 %
Used With:All Units when anEconomizer is installed. "RA
Humidity" is displayed ifComparative Enthalpy or EnergyRecovery is installed.
1. Press the NEXT key until the following screen is displayed. Possible Values: 10 to 90 %
End of Submenu (NEXT) to Enter STATUS
1. Press the NEXT key to leave the submenu and show followingscreen.
2. Press PREVIOUS to page back through the submenu.
-
8/14/2019 ipak trblshoot
36/150
-
8/14/2019 ipak trblshoot
37/150
RT-SVP04F-EN 37
System Operating Status
End of Submenu (NEXT) to Enter STATUS
1. Press the NEXT key to leave the submenu and show following
screen.
2. Press PREVIOUS to page back through the submenu.
RETURN FAN STATUS SUBMENU SCREENS
Note: Return Fan and Energy Recovery are mutually exclusive
features. Only one of the following two status submenus will
be displayed.
Return Fan Status Submenu Used With:All units with ReturnFan installed.
Press ENTER to View Data in This Submenu1. Pressing the NEXT key will bypass this section.
Return Fan Relay: ON Used With:All units with ReturnFan installed.
Possible Values: ON, OFFReturn Airflow Proving: ON
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that
screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.(if applicable)
Return Fan VFD Command: 45% Used With:All units with ReturnFan installed.
Possible Values: 0 to 100%; -0.7to 3.5 IWC
Return Plenum Pressure: 0.8 IWC
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that
screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.
(if applicable)
Note: Top line shown only if Return Fan VFD is installed.
-
8/14/2019 ipak trblshoot
38/150
38 RT-SVP04F-EN
System Operating Status
Return Plenum Pressure Target: 0.8 IWC Used With:All units with ReturnFan installed.
Possible Values: 0.1 to 2.5 IWC;
Return Fan VFD= Opening to/Closingto 0 to 100%
Return Fan VFD Pos: Opening to 45%
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that
screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.
(if applicable)
Max Return Plenum Pressure Stp: 1.2 IWC Used With:All units with ReturnFan installed.
Possible Values: Max Return= 0.1
to 2.5 IWC (Default 1.2 IWC);Deadband = 0.1 to 1.0 IWC (Default0.2 IWC)
Note: High limit is 3.5 IWC and is not
adjustable.
High Limit: 3.5 IWC Deadband: 0.2 IWC
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that
screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.
(if applicable)
End of Submenu (NEXT) to Enter STATUS
1. Press the NEXT key to leave the submenu and show following
screen.2. Press PREVIOUS to page back through the submenu.
Energy Recovery Status Submenu Used With:All IntelliPak II units
with Energy Recovery installed.Press ENTER to View Data in This Submenu
1. Pressing the NEXT key will bypass this section.
Energy Wheel Relay: ON Used With:All IntelliPak II unitswith Energy Recovery installed.
Possible Values:ON, OFFEnergy Wheel Proving: ON
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that
screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.
(if applicable)
-
8/14/2019 ipak trblshoot
39/150
RT-SVP04F-EN 39
System Operating Status
Outside Air Bypass Damper Pos: 0% Used With:All IntelliPak II unitswith Energy Recovery installed.
Possible Values:0-100%Exhaust Air Bypass Damper Pos: 15%
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the NEXT key until the following screen is displayed.
(if applicable)
Energy Wheel Frost Avoidance: INACTIVE Used With:All IntelliPak II unitswith Energy Recovery installed.
Possible Values:Frost Avoidance:
ACTIVE, INACTIVE;
Recovery Exhaust Temp: -40.0 to
200.0 F
Leaving Recovery Exhaust Temp: 45.0F
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the NEXT key until the following screen is displayed.
(if applicable)
Energy Wheel Preheat Relay: OFF Used With:All IntelliPak II unitswith Energy Recovery Preheatinstalled.
Possible Values:ON, OFF1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the NEXT key until the following screen is displayed.
(if applicable)
CONTROLLING SETPOINT STATUS SUBMENU SCREENS
Controlling SETPOINT Status Submenu
Press ENTER to View Data in This Submenu
Used With: All Units
1. Pressing the NEXT key will bypass this section.
Active Supply Air Cooling STP From
HI (KEYPAD) SETPOINT MENU Is 55 F
Used With: All Units
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.
(if applicable)
Possible Values: HI (Keypad)SETPOINT Menu, Zone SensorSETPOINT Input, NSB PanelSETPOINT Input, GBAS 0-5 VDC
Module, BAS/Network, GBAS 0-10VDC Module
-
8/14/2019 ipak trblshoot
40/150
40 RT-SVP04F-EN
System Operating Status
Active Supply Air Heating STP From
HI (KEYPAD) SETPOINT MENU Is 100 F
Used With: All Units whenHydronic Heat, Electric Heat, orModulating Gas Heat is installed.
Possible Values: HI (Keypad)SETPOINT Menu, Zone Sensor
SETPOINT Input, GBAS 0-5 VDCModule, BAS/Network, GBAS 0-10VDC Module
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that
screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.
(if applicable)
Active Daytime Warmup SETPOINTs
Initiate: 67 F Terminate: 71 F
Used With:All Units when Gas,Electric, Hydronic or External Heat is
installed.
Possible Values: HI (Keypad)
SETPOINT Menu; Initiate= 50-87F;Terminate= 53-90 F (This SETPOINTsource is HI (keypad) or BAS/
Network
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that
screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.
(if applicable)
Active Occupied Zone Heating STP From
HI (KEYPAD) SETPOINT MENU Is 71 F
Used With: All Units when Gas,
Electric, Hydronic or External Heat isinstalled and Daytime Warmupenabled.
Possible Values: HI (Keypad)SETPOINT Menu Zone Sensor Setpnt
Input, NSB Panel SETPOINT Input,GBAS 0-5 VDC Module, BAS/Network, GBAS 0-10 VDC Module;Range 50 - 88F
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that
screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.
(if applicable)
Active Unoccupied Zone Cooling STP From
HI (KEYPAD) SETPOINT MENU Is 85 F
Used With: All Units
Possible Values: HI (KEYPAD)enabled.
Possible Values: HI (Keypad)
SETPOINT Menu Zone Sensor SetpntInput, NSB Panel SETPOINT Input,GBAS 0-5 VDC Module, BAS/
Network, GBAS 0-10 VDC Module;Range: 52 - 90 F
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that
screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.
(if applicable)
-
8/14/2019 ipak trblshoot
41/150
RT-SVP04F-EN 41
System Operating Status
Active Unoccupied Zone Heating STP From
HI (KEYPAD) SETPOINT MENU Is 60 F
Used With: All Units when Gas,Electric, Hydronic or External Heat isinstalled
Possible Values:HI (Keypad)SETPOINT Menu, NSB Panel
SETPOINT Input, GBAS 0-5 VDCModule, BAS/Network, GBAS 0-10VDC Module; Range 50 - 88F
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that
screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.
(if applicable)
Active Morning Warmup SETPOINT From
HI (KEYPAD) SETPOINT MENU Is 72 F
Used With: All Units when Gas,Electric, Hydronic or External Heat is
installed
Possible Values:HI (Keypad)
SETPOINT Menu Zone Sensor SetpntInput, NSB Panel SETPOINT Input,GBAS 0-5 VDC Module, BAS/
Network, GBAS 0-10 VDC Module;Range: 52 - 90 F
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that
screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.
(if applicable)
Active Occ Dehumidification Setpt From
HI (KEYPAD) SETPOINT MENU is 60%
Used With:All IntelliPak units with
Dehumidification installed.
Possible Values:HI (KEYPAD)
SETPOINT MENU, BAS/NETWORK,
GBAS 0-5VDC Module, BAS/Network, GBAS 0-10 vdc Module;
Range= 40 to 65%
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view thepreviously displayed screen.
3. Press the NEXT key until the following screen is displayed.
(if applicable)
Active Unocc Dehumidification Setpt From
HI (KEYPAD) SETPOINT MENU is 60%
Used With:All IntelliPak units withDehumidification installed.
Possible Values:HI (KEYPAD)SETPOINT MENU, BAS/NETWORK,
GBAS 0-5VDC Module, BAS/Network, GBAS 0-10 vdc Module;
Range= 40 to 65%
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the NEXT key until the following screen is displayed.
(if applicable)
Active Supply Air Reheat Setpoint From
HI (KEYPAD) SETPOINT MENU is 70.0F
Used With:All IntelliPak units withDehumidification installed.
Possible Values:HI (KEYPAD)SETPOINT MENU, BAS/NETWORK,
GBAS 0-5VDC Module, BAS/
Network, GBAS 0-10 vdc Module;
Range= 60 to 80 F
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the NEXT key until the following screen is displayed.
(if applicable)
-
8/14/2019 ipak trblshoot
42/150
42 RT-SVP04F-EN
System Operating Status
Active Occ Humidification Setpt From Used With:All units with OccupiedHumidification option enabled.
Possible Values: HI (KEYPAD)
SETPOINT MENU, GBAS 0-5VDCModule, BAS/Network, GBAS 0-10
vdc Module; Range= 20 to 50%
HI (Keypad) Setpoint Menu is _________ 40%
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that
screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.
(if applicable)
Active Unocc Humidification Setpt From Used With:All units withUnoccupied Humidification optionenabled.
Possible Values: HI (KEYPAD)SETPOINT MENU, GBAS 0-5VDCModule, BAS/Network, GBAS 0-10vdc Module; Range= 20 to 50%
HI (Keypad) Setpoint Menu is_____________ 20%
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that
screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.
(if applicable)
Active Econ DB Enable SETPOINT From
HI (Keypad) Setpoint Menu is__________ 75 F
Used With: All Units when an
Economizer is installed
Possible Values: HI (KEYPAD)
SETPOINT MENU, GBAS 0-5VDC
Module, GBAS 0-10VDC Module;SETPOINT range: 40 F to 90 F
1. Press the NEXT key until the following screen is displayed. (if applicable)
Active OA Damper Min Position STP From Used With:All units with 0-25%Motorized Damper or 0-100% AirEconomizer and i) OA CFMCompensation function is DISABLEDor ii) OA Damper Min PositionSETPOINT source selection is otherthan HI (KEYPAD) SETPOINT
Possible Values: HI (KEYPAD)SETPOINT MENU, RTM Min PositionPot, GBAS 0-5VDC Module, GBAS 0-
10VDC Module, BAS/Network;Range from 0 to 100%
HI (Keypad) Setpoint Menu is_________ 25%
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that
screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.(if applicable)
-
8/14/2019 ipak trblshoot
43/150
RT-SVP04F-EN 43
System Operating Status
Active Min OA Flow SETPOINT From
HI (KEYPAD) SETPOINT MENU 34.2 CFM
Used With: All Units when FreshAir Measurement VCM is installed
Possible Values: HI (Keypad)
SETPOINT Menu, GBAS 0 - 5 VDCModule, BAS Network GBAS 0-10
VDC Module SETPOINT range: 0 toMax Unit Airflow
Refer to the table in the SETPOINTsection, "Default Min OA FlowSETPOINT Screen" for max airflow
SETPOINTs.
1. Press the NEXT key until the following screen is displayed. (if applicable)
Active Design Min OA Flow SETPOINTFrom HI (KEYPAD) SETPOINT MENU 34.2 CFM
Used With: All Units when FreshAir Measurement VCM is installed
Possible Values: HI (Keypad)SETPOINT Menu, GBAS 0 - 5 VDC
Module, BAS Network GBAS 0-10VDC Module SETPOINT range: 0 toMax Unit Airflow
Refer to the table in the SETPOINTsection, "Default Min OA FlowSETPOINT Screen" for max airflow
SETPOINTs.
1. Press the NEXT key until the following screen is displayed. (if applicable)
Active Min OA Flow Stp DCV Disabled Used With: All Units when FreshAir Measurement VCM is installed
Possible Values: HI (Keypad)SETPOINT Menu, GBAS 0 - 5 VDCModule, BAS Network GBAS 0-10
VDC Module SETPOINT range: 0 toMax Unit Airflow
Refer to the table in the SETPOINTsection, "Default Min OA FlowSETPOINT Screen" for max airflowSETPOINTs.
1. Press the NEXT key until the following screen is displayed. (if applicable)
Active Supply Air Pressure STP From
HI (KEYPAD) SETPOINT MENU is 2.0 IWC
Used With: Rooftop units and AirHandlers when IGV/VFD is installed.
Possible Values:HI (Keypad)SETPOINT Menu, GBAS 0-5 VDCModule, GBAS 0-10 VDC Module,BAS/Network SETPOINT Range:
0.7=5.1 IWC
1. Press the NEXT key until the following screen is displayed.
Active Supply Air Pressure SETPOINTS
High Limit: 4.0 IWC Deadband: 0.5 IWC
Used With: Rooftop units and AirHandlers with IGV/VFD installed orwith SAP present.
Possible Values: High Limit: 1.2 -4.7 IWC Deadband: 0.1 - 2.0 IWC
1. Press the NEXT key until the following screen is displayed.
-
8/14/2019 ipak trblshoot
44/150
44 RT-SVP04F-EN
System Operating Status
Active Space Pressure SETPOINT From
HI (KEYPAD) SETPOINT MENU is 0.08 IWC
Used With: All Units when PowerExhaust with Statitrac is installed orReturn Fan with Statitrac installed
Possible Values: HI (Keypad)SETPOINT Menu, GBAS 0-5 VDC
Module, BAS/Network, GBAS 0-10VDC Module; SETPOINT range: -0.2to 0.30 IWC
1. Press the NEXT key until the following screen is displayed. (if applicable)
Active Space Pressure Deadband 0.10 IWC
Used With: All Units when Power
Exhaust with Statitrac is installed orReturn Fan with Statitrac Installed
Possible Values: HI (KEYPAD)SETPOINT MENU, SETPOINT range:0.02 to 0.20 IWC
1. Press the NEXT key until the following screen is displayed.
End of Submenu (NEXT) to Enter SETUP Status
1. Press the NEXT key to leave the submenu and show followingscreen.
2. Press PREVIOUS to page back through the submenu.
CONTROLLING SENSOR STATUS SUBMENU SCREENS
Controlling Sensor Status Submenu
Press ENTER to View Data in This Submenu
Used With: All Units
1. Pressing the NEXT key will bypass this section.
Active Supply Air Temp Sensor Input From
SUPPLY AIR is 50.0 F
Used With: All Units
Possible Values: RTM Supply AirTemp Input, BAS/Network1. Press the NEXT key until the following screen is displayed.
Active Daytime WU Temp Sensor Input From
RTM ZONE TEMP INPUT is 82.0 F
Used With: All units when Gas,Electric, Hydronic or External Heat isinstalled and DWU is enabled
Possible Values: RTM Zone TempInput, NSB Panel Temp Sensor
Input, RTM Aux Temp Input, HeatModule Aux Temp Input, ECEMReturn Air Temp Input, BAS/NetworkSensor range: -40 F to 200 F
1. Press the NEXT key until the following screen is displayed.(ifapplicable)
Active Unocc Zone Temp Sensor Input From
RTM ZONE TEMP INPUT is 75.0 F
Used With: All Units
Possible Values: RTM Zone TempInput, NSB Panel Temp SensorInput, RTM Aux Temp Input, HeatModule Aux Temp Input, ECEMReturn Air Temp Input, BAS/Network, Sensor range: -40 F to200 F
1. Press the NEXT key until the following screen is displayed. (ifapplicable)
-
8/14/2019 ipak trblshoot
45/150
RT-SVP04F-EN 45
System Operating Status
Active Morning WU Temp Sensor Input From
RTM ZONE TEMP INPUT is 82.0 F
Used With: All Units when Gas,Electric, Hydronic or External Heat isinstalled and Morning Warmup is
enabled1. Press the NEXT key until the following screen is displayed.
(if applicable)
Possible Values: RTM Zone TempInput, NSB Panel Temp SensorInput, RTM Aux Temp Input, HeatModule Aux Temp Input, ECEMReturn Air Temp Input, BAS/Network, Sensor range: -40 F to
200 F
Active Space Humidity Sensor Input From Used With:All units withHumidification option enabled.
Possible Values: RTM Space,Humidity Input, BAS/Network, ECEM
RA Humidity Input; Range 10-90%
RTM space Humidity Input is 55%
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that
screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.
(if applicable)
Active Space CO2Sensor Input From Used With:All units with VCM
installed.
Possible Values: VCM SPACE CO2INPUT, BAS/Network; Range 50-
2000 ppm
VCM Space CO2Input is 600 ppm
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing th