  • UNITECH MACHINES LIMITED

    COMPLIANCE REPORT M/s NTPC Comments through letter ref: CC:9575151:1018 , Dated: 12/10/2012

    DOC. No. 9575-151-PVI-G-069 on Rev-00, I/O LIST

    S.No. M/s NTPC comments UML Resolution

    1. Separate signals shall be provided for Battery-Chager-1 and Battery-Charger-2

    Noted & Revised

    2. For all diesel engine operated pumps, ON feedback, OFF feedback, lube oil pressure low, engine over speed and cooling water temp. high shall also be included in I/O list.

    Noted & incorporated

    3 For all battery and battery chargers, analog signals like charger voltage, charger current, battery voltage etc shall be provided and alarm signals like battery fuse blown, battery charger I/P out of range, battery charger surge protection failure etc shall also be provided.

    Noted & incorporated

    4 Separate signals shall be provided for battery charger-1 and battery charger-2.

    Noted & Revised

    5 Analog signals for LT incomer like current and voltage shall also be included in the list.

    Noted & incorporated

    6 Signals from flow switch shall also be considered in I/O list.

    Noted & incorporated

  • S. No. Location Interfacing Signal Source Signal Form DI AI DO AO

    A

    1 - Booster Pump -1 MCC feeder on feedback MCC DI NO 1

    2 - Booster Pump -1 MCC feeder off feedback MCC DI NC 1

    3 - Booster Pump-1 MCC feeder Disturbance MCC DI NO 1

    4 - Booster Pump-1 emergency stop command from field UML EPBS DI NC 1

    5 - Booster Pump-1 Start command from PLC PLC DO NO 1

    6 - Booster Pump-1 Stop command from PLC PLC DO NC 1

    7 Booster Pump-1 Overload Trip Operated NTPC MCC MCC DI NO YES 1

    8 PT-102 Booster Pump-1 Running PT AI 4 to 20 mA YES 1

    9 PT-101 Booster Pump-1 motor start/ fail to start * PT AI 4 to 20 mA YES 1 1

    10 - Booster Pump -1 selected in the manual mode PLC - - YES

    11 Booster Pump DE MCC feeder On feedback NTPC MCC MCC DI NO 1

    12 Booster Pump DE MCC feeder Off feedback NTPC MCC MCC DI NC 1

    13 Booster pump lube oil pressure low from DECP EP DI NO 1

    14 Booster Pump engine overspeed from DECP EP DI NO 1

    15 Booster pump cooling water temp. high from DECP EP DI NO 1

    16 - Booster Pump-1 DE fuel oil tank level low from DECP EP DI NO YES 1

    17 - Booster Pump-1 engine start failure from DECP EP DI NO 1

    18 - Booster Pump-1 control supply healthy from DECP DECP-01 DI NO 1

    19 - Booster Pump-1 main control relay feedback from DECP

    DECP-01 DI NO 1

    20 - Booster Pump-1 local/remote selection from DECP DECP-01 DI NO 1

    21 - Booster Pump-1 Stop command from DECP DECP-01 DI NC 1

    22 - Booster Pump-1 Start command from PLC PLC DO NO 1

    23 - Booster Pump-1 Stop command from PLC PLC DO NC 1

    24 Booster Pump-1 Running annunciation in DECP PLC DO NO YES 1

    25 Booster Pump fail to start annunciation in DECP PLC DO NO

    26 PT-103 Booster Pump diesel engine start/ fail to start* PT AI 4 to 20 mA 1 1

    27 PT-104 Booster Pump Running PT AI 4 to 20 mA 1

    28 Booster Pump selected in the manual mode PLC - - YES

    29 FS-101 Booster Pump BP-M-01 start

    30 FS-101 Booster Pump BP-M-01 / BP-DE-01 fails to start

    31 - Float Cum Boost Charger-1 Fail/Trip UML BC-1 DI NO 1

    32 - Float Cum Boost Charger-1 DC over voltage UML BC-1 DI NO 1

    33 - Float Cum Boost Charger-2 Fail/Trip UML BC-2 DI NO 1

    34 - Float Cum Boost Charger-2 DC over voltage UML BC-2 DI NO 1

    35 - Battery under voltage UML BC-1 DI NO 1

    36 - Battery earth fault UML BC-1 DI NO 1

    37 - Battery Isolated UML BC-1 DI NO 1

    38 - Charger - trouble UML BC-1 DI NO 1

    39 - Battery on load UML BC-1 DI NO 1

    40 Battery fuse blown UML BC-1 DI NO 1

    41 Battery charger I/P out of range UML BC-1 DI NO 1

    42 Battery charger surge protection failure UML BC-1 DI NO 1

    43 Battery charger voltage UML BC-1 AI 4-20mA 1

    FS

    NTPC MCC

    BP-M-01

    Project : 2 X 660 MW, MOUDA, STPP STAGE II

    Vendor : Unitech Machines Limited

    Booster Pump House

    Package : FIRE DETECTION & PROTECTION SYSTEMNTPC Doc. No. : 9575-151-PVI-G-069

    I/O List of PLC System

    RemarkSignal/ Contact TypeDrive No. DescriptionAnnunciatio

    n IN OWSTag No.

    Date:- 12.10.2012UML DOC. NO.-P308-I-038Client : M/s. NTPC

    Booster Pump HouseBP-DE-01

    Booster Pump House

    REV-01

    DI NO

    UML

    1

    Page 2 of 5

  • S. No. Location Interfacing Signal Source Signal Form DI AI DO AO

    Project : 2 X 660 MW, MOUDA, STPP STAGE II

    Vendor : Unitech Machines LimitedPackage : FIRE DETECTION & PROTECTION SYSTEMNTPC Doc. No. : 9575-151-PVI-G-069

    I/O List of PLC System

    RemarkSignal/ Contact TypeDrive No. DescriptionAnnunciatio

    n IN OWSTag No.

    Date:- 12.10.2012UML DOC. NO.-P308-I-038Client : M/s. NTPC

    REV-01

    44 Battery charger current UML BC-1 AI 4-20mA 1

    45 Battery voltage UML BC-1 AI 4-20mA 1

    46 Battery under voltage UML BC-2 DI NO 1

    47 Battery earth fault UML BC-2 DI NO 1

    48 Battery Isolated UML BC-2 DI NO 1

    49 Charger - trouble UML BC-2 DI NO 1

    50 Battery On load UML BC-2 DI NO 1

    51 Battery fuse blown UML BC-2 DI NO 1

    52 Battery charger I/P out of range UML BC-2 DI NO 1

    53 Battery charger surge protection failure UML BC-2 DI NO 1

    54 Battery charger voltage BC-2 AI 4-20 mA 1

    55 Battery charger current BC-2 AI 4-20 mA 1

    56 Battery voltage BC-2 AI 4-20 mA 1

    37 11 6

    B

    1 - Foam Pump - 1 MCC feeder on feedback MCC DI NO 1

    2 - Foam Pump - 1 MCC feeder off feedback MCC DI NC 1

    3 - Foam Pump-1 MCC feeder Disturbance MCC DI NO 1

    4 - Foam Pump-1 emergency stop command from field EPBS DI NC 1

    5 - Foam Pump-1 Start command from PLC PLC DO NO 1

    6 - Foam Pump-1 Stop command from PLC PLC DO NC 1

    7 Foam Pump-1 Overload Trip Operated MCC DI NC YES 1

    8 PT-F-01 Foam Pump-1 Running signal/ Fail to start* PT AI 4 to 20 mA YES 1 1

    9 - Foam Pump - 1 selected in the manual mode PLC - - YES

    10 Foam pump DE MCC ON feedback NTPC MCC MCC DI NO 1

    11 Foam pump DE MCC OFF feedback NTPC MCC MCC DI NC 1

    12 Booster pump lube oil pressure low from DECP EP DI NO 1

    13 Booster pump engine overspeed from DECP EP DI NO 1

    14 Booster pump cooling water temperature high from DECP EP DI NO 1

    15 - Foam Pump-1 DE fuel oil tank level low from DECP EP DI NO YES 1

    16 - Foam Pump-1 engine start failure from DECP EP DI NO 1

    17 - Foam Pump-1 control supply healthy from DECP DECP-01 DI NO 1

    18 - Foam Pump-1 main control relay feedback from DECP DECP-01 DI NO 1

    19 - Foam Pump-1 local/remote selection from DECP DECP-01 DI NO 1

    20 Foam Pump Stop command from DECP DECP-01 DI NO

    21 Pump running annunciation in DECP PLC DO NO 1

    22 Pump fail to start annunciation in DECP PLC DO NO 1

    23 - Foam Pump-1 Start command from PLC PLC DO NO 1

    24 - Foam Pump-1 Stop command from PLC PLC DO NC 1

    25 Foam Pump selected in manual mode PLC YES

    Total

    FP-M-01

    Foam Pump House

    UML

    NTPC MCC

    UML

    Foam Pump House

    Page 3 of 5

  • S. No. Location Interfacing Signal Source Signal Form DI AI DO AO

    Project : 2 X 660 MW, MOUDA, STPP STAGE II

    Vendor : Unitech Machines LimitedPackage : FIRE DETECTION & PROTECTION SYSTEMNTPC Doc. No. : 9575-151-PVI-G-069

    I/O List of PLC System

    RemarkSignal/ Contact TypeDrive No. DescriptionAnnunciatio

    n IN OWSTag No.

    Date:- 12.10.2012UML DOC. NO.-P308-I-038Client : M/s. NTPC

    REV-01

    26 PT-F-02 Foam Pump-1 Running signal/ Fail to start* PT AI 4 to 20 mA YES 1 1

    27 PT-F-03 Foam system for LDO tank PT AI 4 to 20 mA 1

    28 PT-F-04 Foam system for HFO tank-1 PT AI 4 to 20 mA 1

    29 PT-F-05 Foam system for HFO tank-2 PT AI 4 to 20 mA 1

    30 PT-F-06 Foam system for Hydrant PT AI 4 to 20 mA 1

    31 LT-F-01 Level low of Foam tank-1 LT AI 4 to 20 mA 1

    32 LT-F-02 Level low of Foam tank-2 LT AI 4 to 20 mA 1

    33 LSG Level of diesel Tank LSG DI NO 1

    34 - Float Cum Boost Charger-1 Fail/Trip UML BC-1 DI NO 1

    35 - Float Cum Boost Charger-1 DC over voltage UML BC-1 DI NO 1

    36 - Float Cum Boost Charger-2 Fail/Trip UML BC-2 DI NO 1

    37 - Float Cum Boost Charger-2 DC over voltage UML BC-2 DI NO 1

    38 - Battery under voltage UML BC-1 DI NO 1

    39 - Battery earth fault UML BC-1 DI NO 1

    40 - Battery Isolated UML BC-1 DI NO 1

    41 - Charger - trouble UML BC-1 DI NO 1

    42 - Battery on load UML BC-1 DI NO 1

    43 Battery fuse blown UML BC-1 DI NO 1

    44 Battery charger I/P out of range UML BC-1 DI NO 1

    45 Battery charger surge protection failure UML BC-1 DI NO 1

    46 Battery charger voltage BC-1 AI 4-20 mA 1

    47 Battery charger current BC-1 AI 4-20 mA 1

    48 Battery voltage BC-1 AI 4-20 mA 1

    49 Battery under voltage BC-2 DI NO 1

    50 - Battery earth fault UML BC-2 DI NO 1

    51 - Battery Isolated UML BC-2 DI NO 1

    52 - Charger - trouble UML BC-2 DI NO 1

    53 - Battery on load UML BC-2 DI NO 1

    54 Battery fuse blown BC-2 NO 1

    55 Battery charger I/P out of range BC-2 NO 1

    56 Battery charger surge protection failure BC-2 NO 1

    57 Battery charger voltage BC-2 AI 4-20 mA 1

    58 Battery charger current BC-2 AI 4-20 mA 1

    59 Battery voltage BC-2 AI 4-20 mA 1

    36 14 8

    C

    1 - Switchgear disturbance DI NO 1

    2 - Breaker OPEN status DI NO 1

    3 - Breaker CLOSE status DI NC 1

    4 - Breaker ready for remote operation DI NO 1

    5 - Overload/Trip relay operated DI NO 1

    6 - Breaker OPEN command DO NO 1

    7 Breaker CLOSE command DO NC 1

    Incomer-1

    LT Switchgear Signals

    Total

    Foam Pump HouseFP-DE-01

    Incomer-1 Booster pump house NTPC MCC

    Page 4 of 5

  • S. No. Location Interfacing Signal Source Signal Form DI AI DO AO

    Project : 2 X 660 MW, MOUDA, STPP STAGE II

    Vendor : Unitech Machines LimitedPackage : FIRE DETECTION & PROTECTION SYSTEMNTPC Doc. No. : 9575-151-PVI-G-069

    I/O List of PLC System

    RemarkSignal/ Contact TypeDrive No. DescriptionAnnunciatio

    n IN OWSTag No.

    Date:- 12.10.2012UML DOC. NO.-P308-I-038Client : M/s. NTPC

    REV-01

    8 Current measurement AI 4-20mA 1

    9 Voltage measurement AI 4-20mA 1

    10 - Switchgear disturbance DI NO 1

    11 - Breaker OPEN status DI NO 1

    12 - Breaker CLOSE status DI NC 1

    13 - Breaker ready for remote operation DI NO 1

    14 - Overload/Trip relay operated DI NO 1

    15 - Breaker OPEN command DO NO 1

    16 Breaker CLOSE command DO NC 1

    17 Current measurement AI 4-20mA 1

    18 Voltage measurement AI 4-20mA 1

    19 - Switchgear disturbance DI NO 1

    20 - Breaker OPEN status DI NO 1

    21 - Breaker CLOSE status DI NC 1

    22 - Breaker ready for remote operation DI NO 1

    23 - Overload/Trip relay operated DI NO 1

    24 - Overload trip operated DI NO 1

    25 - Breaker OPEN command DO NO 1

    26 - Breaker CLOSE command DO NC 1

    16 4 6

    89 29 20

    9 3 2

    NOTE: Annunciation marked with " * " above shall be annunciated in Main Fire Alarm panel.

    Total I/O

    Spare Channel ( 10%) for DI,DO & AI

    Total

    Bus coupler

    Incomer-2Incomer-2 Booster Pump House NTPC MCC

    Bus coupler Booster Pump House NTPC MCC