    PowerLogicION7300 Series

    Power & Energy Meter

    User Guide

    January 2007

  • 8/12/2019 ION Meter-70002-0162-03

    2/152

  • 8/12/2019 ION Meter-70002-0162-03

    3/152

    Notices Danger

    Thissymbolindicatesthepresenceofdangerousvoltagewithinandoutsidetheproductenclosurethatmayconstituteariskofelectric

    shock,serious

    injury

    or

    death

    to

    persons

    if

    proper

    precautions

    are

    not

    followed.

    Caution

    Thissymbolalertstheusertothepresenceofhazardsthatmaycauseminorormoderateinjurytopersons,damagetopropertyordamagetothedeviceitself,ifproperprecautionsarenotfollowed.

    Note

    Thissymboldirectstheusersattentiontoimportantinstallation,operatingandmaintenanceinstructions.

    Installation ConsiderationsInstallationandmaintenanceoftheION7300seriesmetershouldonlybeperformedbyqualified,competentpersonnelthathaveappropriatetrainingandexperiencewithhighvoltageandcurrentdevices.ThemetermustbeinstalledinaccordancewithallLocalandNationalElectricalCodes.

    DANGER

    Failure to observe the following instructions may result in severe injury or death.

    DuringnormaloperationoftheION7300seriesmeter,hazardousvoltagesarepresentonitsterminalstrips,andthroughouttheconnectedpotentialtransformer(PT),currenttransformer(CT),digital(status)input,controlpowerandexternalI/Ocircuits.PTandCTsecondarycircuitsarecapableofgeneratinglethalvoltagesandcurrentswiththeirprimarycircuitenergized.Followstandardsafetyprecautionswhileperforminganyinstallationorservicework(i.e.removingPTfuses,shortingCTsecondaries,etc.).

    Theterminalstripsonthemeterbaseshouldnotbeuseraccessibleafterinstallation.

    Donotusedigitaloutputdevicesforprimaryprotectionfunctions.Theseincludeapplicationswherethedevicesperformenergylimitingfunctionsor

    provideprotectionofpeoplefrominjury.DonotusetheION7300seriesinsituationswherefailureofthedevicescancauseinjuryordeath,orcausesufficientenergytobereleasedthatcanstartafire.Themetercanbeusedforsecondaryprotectionfunctions.

    DonotHIPOT/Dielectrictestthedigital(status)inputs,digitaloutputs,orcommunicationsterminals.RefertothelabelontheION7300seriesmeterforthemaximumvoltagelevelthedevicecanwithstand.

  • 8/12/2019 ION Meter-70002-0162-03

    4/152

    CAUTION

    Observe the following instructions, or permanent damage to the meter may occur.

    TheION7300seriesmeteroffersarangeofhardwareoptionsthataffectinputratings.TheION7300seriesmetersserialnumberlabellistsallequipped

    options.Applyingcurrentlevelsincompatiblewiththecurrentinputswillpermanentlydamagethemeter.Thisdocumentprovidesinstallationinstructionsapplicabletoeachhardwareoption.

    TheION7300seriesmeterschassisgroundmustbeproperlyconnectedtotheswitchgearearthgroundforthenoiseandsurgeprotectioncircuitrytofunctioncorrectly.Failuretodosowillvoidthewarranty.

    Terminalscrewtorque:Barriertype(current,voltage,andrelayterminalscrews:1.35Nm(1.00ftlbs.)max.Capturedwiretype(digitalinputs/outputs,communications,powersupply:0.90Nm(0.66ftlbs.)max.

    FCC NoticeThisequipmenthasbeentestedandfoundtocomplywiththelimitsforaClassAdigitaldevice,pursuanttoPart15oftheFCCRules.Theselimitsaredesignedtoprovidereasonableprotectionagainstharmfulinterferencewhentheequipmentisoperatedinacommercialenvironment.Thisequipmentgenerates,uses,andcanradiateradiofrequencyenergyand,ifnotinstalledandusedinaccordancewiththeinstructionmanual,maycauseharmfulinterferencetoradiocommunications.Operationofthisequipmentinaresidentialareaislikelytocauseharmfulinterferenceinwhichcasetheuserwillberequiredtocorrecttheinterferenceathisownexpense.TheRingerEquivalenceNumber(REN)fortheION7300seriesoptionalinternalmodemis0.6.ConnectiontotheION7300seriesinternalmodemshouldbemadeviaanFCCPart68complianttelephonecord(notsupplied).TheION7300seriescannotbeusedonapubliccoinphoneserviceorpartyline

    services.

    Network Compatibility Notice for the Internal ModemTheinternalmodeminmetersequippedwiththisoptioniscompatiblewiththetelephonesystemsofmostcountriesintheworld,withtheexceptionofAustraliaandNewZealand.Useinsomecountriesmayrequiremodificationoftheinternalmodemsinitializationstrings.Ifproblemsusingthemodemonyourphonesystemoccur,pleasecontactSchneiderElectricTechnicalSupport.

    Standards Compliance

    MadebyPowerMeasurementLtd.

    CSA: Certified to CAN/CSA C22.2 No.1010-1

    Certified toUL 3111

  • 8/12/2019 ION Meter-70002-0162-03

    5/152

    PowerLogic,ION,IONEnterprise,MeterM@ilandModbusareeithertrademarksorregisteredtrademarksofSchneiderElectric. Allothertrademarksarepropertyoftheirrespectiveowners.

    Coveredbyoneormoreofthefollowingpatents:

    U.S.

    Patent

    No

    s

    7010438,

    7006934,

    6990395,

    6988182,

    6988025,

    6983211,

    6961641,

    6957158,6944555,6871150,6853978,6825776,6813571,6798191,6798190,6792364,6792337,6751562,6745138,6737855,6694270,6687627,6671654,6671635,6615147,6611922,6611773,6563697,6493644,6397155,6236949,6186842,6185508,6000034,5995911,5828576,5736847,5650936,D505087,D459259,D458863,D443541,D439535,D435471,D432934,D429655,D427533.

  • 8/12/2019 ION Meter-70002-0162-03

    6/152

  • 8/12/2019 ION Meter-70002-0162-03

    7/152

    Table of Contents

    Chapter 1 Introduction .................................................................. 9

    Chapter 2 Front Panel ................................................................. 21

    Chapter 3 Templates, Frameworks and Firmware ........................ 39

    Chapter 4 Basic Setup ................................................................. 45

    Chapter 5 Security ...................................................................... 49

    Chapter 6 Communications ......................................................... 55

    Chapter 7 Third-Party Protocols ................................................... 73

    Chapter 8 Time ........................................................................... 89

    Chapter 9 Demand ..................................................................... 93

    Chapter 10 Inputs / Outputs ......................................................... 97

    Chapter 11 Energy Pulsing .......................................................... 109

    Chapter 12 Logging .................................................................... 115

    Chapter 13 Power Quality (ION7350 only) .................................. 125Chapter 14 Meter Resets ............................................................. 129

    Chapter 15 Alerting (ION7350 only) ........................................... 133

    Chapter 16 Setpoints (ION7330 and ION7350) ........................... 139

    Chapter 17 Reporting ................................................................. 143

  • 8/12/2019 ION Meter-70002-0162-03

    8/152

  • 8/12/2019 ION Meter-70002-0162-03

    9/152

    2007 Schneider Electric. All rights reserved. Page 9

    1 Introduction

    ThismanualexplainshowtouseallPowerLogicION7300seriesmeters.Throughoutthemanual,thetermmetergenerallyreferstoallmetermodels:ION7300,ION7330andION7350.Alldifferencesbetweenthemodels,suchasafeaturespecifictoonemodel,areindicatedwiththeappropriatemodelnumber.

    Beforeusingthisguide,yourmetershouldbeinstalled,mostbasicsetupshouldhavebeenperformed,andcommunications/basicoperationshouldhavebeenverified.

    Iftheunitisnotyetinstalledandoperational,refertotheInstallationGuideshippedwiththemeter.

    ThischapterprovidesanoverviewofION7300seriesmeters,andsummarizesmanyoftheirkeyfeatures.

    In This Chapter

    ION7300 Series Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    The ION Meter in an Enterprise Energy Management System . . . . . . . . . . . 12

    Meter Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14MeasuredParameters ................................................. 14

    DataDisplayandAnalysisTools ....................................... 16

    SupportedProtocols .................................................. 17

    CommunicationsOptions.............................................. 17

    DigitalandAnalogI/OOptions......................................... 17

    IONEnterpriseSoftwareSupport ....................................... 18

    IONSetupSoftwareSupport ........................................... 20

    Getting More Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

  • 8/12/2019 ION Meter-70002-0162-03

    10/152

  • 8/12/2019 ION Meter-70002-0162-03

    11/152

    ION7300 Series User Guide Chapter 1 - Introduction

    2007 Schneider Electric. All rights reserved. Page 11

    IONEnterpriseisapowerfulwebreadysoftwaresuitethatcanprocess,analyze,store,andshareinformationfromacrossyourentireorganization.Itscompatibilityandflexibilitymeansyoucanintroduceindividualcomponents,atapaceyoudecide,whilemaintainingyouroriginalinvestments.Youcanaccessinformationandalarmsfromanyworkstation,pager,PDA,orcellphonelocallyoraroundtheworld,intheformatyourequire.Youcanalsoperformcoordinated

    load

    and

    equipment

    control

    functions,

    either

    manually

    or

    automatically.

    ION

    softwarecollectsdataautomaticallyfromIONmetersandthirdpartydevices,soyoucanmanageasinglesiteoraglobalnetworkofdevices.IONsoftwareandhardwareproductsreducecostofinstallationandownershipbyleverageexistingcorporatenetworksandpopularnetworkingtechnologies,includingserial,wireless,modem,EthernetandInternetlinks.

    AwideselectionofIONintelligentmeteringandcontroldevicesareavailable,withchoicestomeetthespecificneedsofvariouskeypointswithinanenterprise.Devicesofferarangeofhighaccuracymetering,powerqualityandreliabilityanalysis,dataandeventlogging,alarming,controlandcommunications.

    TheION7300seriesmeterscanbeusedeffectivelyinnumeroussupplysideand

    demandside

    operations.

    Some

    common

    meter

    applications

    are:

    RevenueMetering

    SubstationAutomation

    ReplacementofAnalogTransducers

    Commercial/IndustrialMetering

    DemandMonitoring

    GensetApplications

    UniversalMetering(ION7330andION7350)

    UtilitySubMetering(ION7330andION7350)

    Thesearejustafewofthemanypossibilities.ContactSchneiderElectricTechnicalSupportifyouwouldlikeassistancewithyourapplication.

  • 8/12/2019 ION Meter-70002-0162-03

    12/152

    Chapter 1 - Introduction ION7300 Series User Guide

    Page 12 2007 Schneider Electric. All rights reserved.

    The ION Meter in an Enterprise Energy Management SystemApplicationsthatincludethemetertypicallyrequireadditionalequipment.Displayandanalysissoftwaretoolsarealmostalwaysusedtomanage,interpretanddistributethedatameasuredorloggedbyameter.Thereareusuallyavarietyoftoolsused,andoftenthesetoolsareconnectedusingdifferentcommunications

    standardsand

    protocols.

    In

    many

    cases,

    ameter

    must

    also

    provide

    control

    capabilitiesanddeviceleveldatasharing.

    Themetercanadapttomanysituations.Advancedcommunicationsallowdatatobesharedsimultaneouslyacrossmultiplenetworks,builtinI/Oprovidesmonitoringandcontrolcapabilities,andavarietyofdisplayandanalysistoolscan

    beusedtomonitoryourpowersystem.

    Power System ConnectionsPhase voltage and phase current

    from Wye, Delta or single-phasepower systems.

    I / O- Energy Pulses

    - Breaker Closures- Digital Signals- Analog Transducers

    Protocols- ION

    - Modbus RTU- DNP V3.00- Profibus (ION7300)

    Communications- RS-485

    - Optical Infrared- 10 Base-T Ethernet- 33.6 kbps internal modem- Profibus port (ION7300)

    Data Analysis Tools- ION Enterprise Software- 3rd-Party tools

    On-Site Data Display- Front Panel Display- Remote Data Display (RMD)- Vista- WebReach

    Corporate Network

    Internet Connectivity- MeterM@il

    - WebMeter

  • 8/12/2019 ION Meter-70002-0162-03

    13/152

    ION7300 Series User Guide Chapter 1 - Introduction

    2007 Schneider Electric. All rights reserved. Page 13

    Power System ConnectionsPhase voltage and phase currentfrom Wye, Delta or single-phasepower systems.

    I / O- Energy Pulses- Breaker Closures- Digital Signals- Analog Transducers

    Protocols- ION- Modbus RTU- DNP V3.00- Profibus (ION7300)

    Communications- RS-485- Optical Infrared- 10 Base-T Ethernet- 33.6 kbps internal modem- Profibus port (ION7300)

    Data Analysis Tools- ION Enterprise Software- 3rd-Party tools

    On-Site Data Display- Remote Modular DisplayRemote Data Display- Vista- WebReach

    Corporate Network

    Internet Connectivity- MeterM@il- WebMeter

  • 8/12/2019 ION Meter-70002-0162-03

    14/152

    Chapter 1 - Introduction ION7300 Series User Guide

    Page 14 2007 Schneider Electric. All rights reserved.

    Meter FeaturesYourmeterincludesanimpressivearrayofstandardfeatures.Seebelowforanoverview.

    Measured ParametersION7300seriesmetersprovidefullybidirectional,4quadrant,revenueaccurateorrevenuecertifiedenergymetering.Thefollowingisaselectionofsomeparametersmeasuredbythesemeters.

    EnergyThemetersprovideallcommonactive,reactiveandapparentenergyparameters.

    kWh,imported,exported,net(importedandexported),andtotal(importedandexported)

    kVARhimported,exported,net(importedandexported),andtotal(importedandexported)

    kVAhtotal

    kVAh,imported,exported,net(ION7330andION7350metersonly)

    Volthoursandamphours

    Integrationofanyinstantaneousmeasurement

    Allenergyparametersrepresentthetotalforallthreephases.EnergyreadingsaretrueRMSandareupdatedapproximatelyonceeachsecond.Maximumrangeofenergyreadingsis999,999,999.Beyondthisvalue,readingsrollovertozero(0).

    DemandION7300seriesmeterssupportrollingblock,thermal,andpredicteddemand.Themeterscalculatedemandonanyinstantaneousmeasurementandrecordpeak(maximum)andminimumdemand.

    Defaultsetup:

    kWdemandandmin/max

    kVARdemandandmin/max

    kVAdemandandmin/max

    Ampsdemandandmin/max

    Voltsdemandandmin/max

    Demandonanyinstantaneousmeasurement

  • 8/12/2019 ION Meter-70002-0162-03

    15/152

    ION7300 Series User Guide Chapter 1 - Introduction

    2007 Schneider Electric. All rights reserved. Page 15

    Real-timeION7300seriesmetersofferacomprehensivearrayofinstantaneous(realtime)measurements.MeasurementsincludetrueRMS,perphaseandtotalfor:

    Voltageandcurrent

    kW,kVARandkVA

    Powerfactor

    Frequency

    Voltageandcurrentunbalance

    HarmonicsION7300seriesmetersfeatureharmonicdistortionmetering.

    TotalHarmonicDistortionandindividualharmonicstothe15th,(31stfortheION7350meter)onvoltageandcurrentinputs

    Kfactorforcurrentinputs

    Min/Max RecordingThemetersrecordeachnewminimumandnewmaximumvaluewithdateandtimestampforthefollowingparameters:

    Voltageandcurrentmin/max

    kW,kVAR,andkVAmin/max

    Powerfactor

    Frequency

    Voltage

    unbalance Plusanymeasuredvalue

    Residual Current Calculation (I4)ThePowerMetermoduleprovidesanoutputregisterlabeledI4whichholdstheresidualcurrentvalue,derivedfromthethreephasecurrentmeasurements.Assuch,I4representsthegroundfaultcurrent,orthecurrentflowintheneutralorgroundconductor.

    NOTE

    This quantity is only available when the meter's Volts Modeis set to 4-WIREWYE. If the Power Meter module

    is set to any other Volts Mode, the I4 output will read NOTAVAILABLE.

  • 8/12/2019 ION Meter-70002-0162-03

    16/152

    Chapter 1 - Introduction ION7300 Series User Guide

    Page 16 2007 Schneider Electric. All rights reserved.

    Data Display and Analysis ToolsDisplayandanalyzemeterdatawithawidevarietyoftools.

    The Front Panel

    Usethemetersfrontpanelinterfaceforlocalmonitoringandstandaloneapplications.ThebrightLCDdisplayletsyouviewrealtimevaluesandperformdeviceconfiguration.

    NOTE

    TRAN (transducer) model meters do not have a front panel.

    The Remote Modular DisplayTheRemoteModularDisplay(RMD)canbeaddedtoanexistingION7300seriesTRANmodeltofacilitatelocalmonitoringandstandaloneapplications.TheION7300seriesBasicModelprovidesanintegratedfrontpaneldisplay.

    BoththefrontpanelandRMD,whenusedincombinationwithIONsoftware,provideaninterfaceforfieldpersonnel.

    WebMeterEmbedded Web Server FeatureEthernetmetersincludeWebMeterfunctionality;anonboardwebserverthatprovidesquickandeasyaccesstorealtimeenergyandbasicpowerqualityinformationwithoutspecialsoftware.Thebuiltinwebpagesdisplayarangeofenergyandbasicpowerqualityinformationthroughthewebenableddevice,andevensupportbasicmeterconfigurationtasks.

    MeterM@il Internal E-Mail Client FeatureWithMeterM@il,youcanconfigurethemetertoautomaticallyemailhighpriorityalarmnotificationsorscheduledsystemstatusupdatemessagestoanyone,anywherewithinthefacilityoraroundtheworld.Specifythetypeofeventthattriggersanemailalert,suchaspowerqualitydisturbancesorloggeddataatanypredeterminedinterval,andhaveyourIONsoftwareadministratorprogramthemetertorespondwithaMeterM@ilmessagewhentheseeventsoccur.MeterM@ilmessagesarereceivedlikeanyemailmessageoveraworkstation,cellphone,pager,orPDA.

    XML CompatibilityYourmetercanexchangeinformationusingindustrystandardXMLformat.Thissimplemachinereadableformatsupportseasyintegrationwithcustomreporting,spreadsheet,database,andotherapplications.

  • 8/12/2019 ION Meter-70002-0162-03

    17/152

    ION7300 Series User Guide Chapter 1 - Introduction

    2007 Schneider Electric. All rights reserved. Page 17

    Supported ProtocolsYoucanintegratethemeterintovariousindustrystandardnetworks.Meterdatacanbemadeavailabletootherdevicesusingthefollowingprotocols:

    ION

    ModbusRTU

    DNP3.0(ION7330andION7350)

    MV90translationsystem(ION7330andION7350).

    Profibus(optionalforION7300)

    Youcanalsoconfigurethemetertoimportdatafromotherdevicesonthesenetworks.Withtheseadvancedcommunicationsfunctions,thepowerofthemetercanbeutilizedinmostexistingpowermonitoringsystems.AnydatadisplayandanalysissoftwarethatworkswithModbusRTUorDNP3.0devicesalsofunctionswiththemeter.

    Communications OptionsThestandardmeterhasoneinfraredportandoneortwoRS485communicationsports(theION7300hasone,theION7330andION7350havetwo).Theseportsarecapableofdataratesupto19,200bps.TheinfraredportonthefrontpaneliscompatiblewithanANSIC12.13TypeIImagneticopticalcommunicationscoupler.ItcanbeusedtocommunicaterealtimemeasurementsviaION,Modbus,orDNPprotocols.TheRS485andinfraredportscancommunicatesimultaneously.Orderingoptionscanincludea10BaseTEthernetport,a33.6kbpsinternalmodem,andaProfibusport,dependingonthemodeltypeofyourION7300seriesmeter.

    Digital and Analog I/O OptionsTheION7300seriesmeteroffersavarietyofanaloganddigitalI/Ocombinations.I/Oconnectionstothemeteraremadeviacapturedwireterminalsonthebackofthemeter.TheanalogI/OoptioncanbespecifiedforanyION7300seriesmeter,allowingyoutomonitorawiderangeofconditions,suchasflowrates,devicecycles(RPM),fuellevels,oilpressuresandtransformertemperatures.YoucanoutputenergypulsestoanRTUorperformequipmentcontroloperations.

    Digital Outputs

    AllION7300seriesmetershavefourprogrammabledigitaloutputports.Thesearesuitableforpulsingorcontrollingrelays.TheInfraredDataPortand/orarearpanelLEDcanalsobeusedforenergypulsing.

    Status InputsFouropticallyisolateddigitalinputsontheION7330andION7350meterscanmonitorstatus,counttransducerpulses,breakertripsandpulsesfromanyexternalvoltsfreedrycontact.

  • 8/12/2019 ION Meter-70002-0162-03

    18/152

    Chapter 1 - Introduction ION7300 Series User Guide

    Page 18 2007 Schneider Electric. All rights reserved.

    Analog Inputs/OutputsAnymeterintheION7300seriescanbeequippedwithanoptionalanalogI/Ocardfeaturing:

    4analoginputsaccepting01mAor020mA,(scalableto420mA)

    4analogoutputsaccepting01mAor020mA,(scalableto420mA)

    NOTE

    When equipped with analog I/O, TRAN base units cannot be ordered with a remote display (RMD).

    REB OptionAddingtheRelayExpansionBoard(REB)optioncanenhancethefunctionalityoftheonboarddigitaloutputs.TheREBoptionincludesafourpositionGrayhillmodulerackanda100240VACto5VDCpowersupply.Grayhillmodulesareorderedseparately.

    ION Enterprise Software SupportThecompleteIONEnterprisesoftwarepackageintegratesthemeterintoafullynetworkedinformationsystemwithothermetersandlocalandwideareacomputernetworks.IONEnterpriseisrecommendedforallpowermonitoringsystemswhereadvancedanalysisandcontrolcapabilitiesarerequired.

    IONEnterpriseprovidestoolsformanagingyourpowermonitoringnetwork,loggingdata,analyzingrealtimeandloggeddata,generatingpowersystemreports,andcreatingcustomfunctionalityatthemeterlevel.

    VistaVistapresentsagraphicalviewofyourpowersystem,allowingyoutoviewandanalyzerealtimedatafrompowermetersandhistoricaldatafromtheIONdatabase.Vistareportsonthestatusofyoursystemcomponents,informingyouofalarmconditionsandprovidingyouwithcontrolcapabilitiesforinitiatingintelligentdevicefunctionsoractuatingfieldmachinery.Vistaincludessophisticatedtoolsforanalyzingrealtimeandloggedpowerdataandsystemevents.

    Formoreinformation,refertotheVistasectionintheonlineIONEnterpriseHelp.

    WebReachTheWebReachcomponentofIONEnterpriseaddsthinclientsupportfunctionalitytotheIONEnterprisesoftware.WiththeWebReachfeatureyoucanusethewebbrowserfromanymachineonyournetworktoviewtheVistadiagramsofallthemetersonyournetwork,regardlessofwhethertheyarelocatedlocallyoracrossthecountry.YoucancreatecustomscreensinVistafordisplayinyourwebbrowser,includingrealtimenumericdata,backgroundgraphicsordiagrams,andbasicviewsofevent,dataandwaveformlogs.

  • 8/12/2019 ION Meter-70002-0162-03

    19/152

    ION7300 Series User Guide Chapter 1 - Introduction

    2007 Schneider Electric. All rights reserved. Page 19

    ReporterReporterletsyoudefineandcreatecomprehensivedatabasereportsusingMicrosoftExcel.ConfiguredPowerQuality,LoadProfile,andEnergyandDemandreportsareincludedwithReporter.

    Formoreinformation,refertotheReportersectionintheonlineIONEnterpriseHelp.Management ConsoleManagementConsoleisusedtobuildyourIONEnterprisepowermonitoringnetworktoreflectthewaythephysicalcommunicationsnetworkiswired,soIONEnterprisesoftwarecancommunicatewithyourdevices.Thenetworkiscreatedusingsites,servers,modems,andintelligentdevicesthatcanbeadded,removed,configured,orduplicated.

    YoucanaccessthefollowingtoolsfromtheManagementConsolemenus:

    DiagnosticsVieweristheprimarysourceoftroubleshootinginformationinIONEnterprise.

    DeviceUpgraderletsyouupgradetheoperatingsoftwareinsideanIONmeter. RemoteModemSetupletsyousetupmodemsforremotesites. DatabaseManagerletsyoumanageyourIONEnterprisedatabaseswithboth

    manualtasksandscheduledtasks.

    UserManagerletsyouconfigureIONEnterprisesoftwareuseraccountsthatdefinedifferentoperationspermittedwithintheIONsoftware,suchasviewingmeterdata,performingcontrolactions,orconfiguringthemeters.

    LicenseManagerletsyouupgradethenumberofdevicesyoucanhavewithoutreinstallingthesoftware.

    Formoreinformation,refertotheManagementConsolesectionintheonlineIONEnterpriseHelp.DesignerDesignerletsyoucustomizetheoperationofhardwarenodes,suchasIONmeters,andsoftwarenodes,suchastheVirtualProcessor,theLogInserter,andtheQueryServer.DesignerusesaWYSIWYGgraphicaluserinterfacetopictoriallyrepresentanodesconfiguration(i.e.,howthedifferentIONmodulesarelinkedtogetherinaframework).InadditiontogivingyoutheabilitytochangethesettingsofanyIONmodule,Designeralsoletsyouchangeexistinglinksbetweenmodules,add

    newlinks,

    add

    new

    modules

    or

    delete

    modules.

    Designer

    helps

    you

    visualize

    the

    logicwhenyouareprogrammingcustomfunctionalityinanIONdevice.

    Formoreinformation,refertotheDesignersectionintheonlineIONEnterpriseHelp.

  • 8/12/2019 ION Meter-70002-0162-03

    20/152

  • 8/12/2019 ION Meter-70002-0162-03

    21/152

    2007 Schneider Electric. All rights reserved. Page 21

    2 Front Panel

    Themetersfrontpanelisusedforbothdisplayandconfigurationpurposes.Theliquidcrystaldisplay(LCD)screenandtheselection,navigation,andconfigurationbuttonsallowquickaccesstobasicmeterconfigurationprovidedbyspecialsetupscreens.ComprehensivemeterconfigurationisalsoaccessibleviatheAdvancedsetupmenus.

    Thischapterprovidesinformationaboutthemetersfrontpanel,includinginstructionsforusingthesetupmenusandfordisplayingmetervalues.

    In This Chapter

    Displaying Data with the Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22FrontPanelDisplayResolution ......................................... 23

    DisplayScreenTypes ................................................. 24

    DefaultFrontPanelDisplayScreens..................................... 24

    Configuring the Meter with the Front Panel . . . . . . . . . . . . . . . . . . . . . . . . 25TheFrontPanelsMainSetupMenu..................................... 26

    AdvancedMeterSetupMenu .......................................... 26

    DisplaySetupMenu .................................................. 27

    ScreenSetupMenu ................................................... 28

    NameplateInfo

    Menu

    .................................................29

    DiagnosticMenu ..................................................... 29

    Display Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32DisplayOptionsModuleSettings ....................................... 32

    DisplayModuleSettings............................................... 32

    Custom Front Panel Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34BeforeCustomizingtheFrontPanel ..................................... 34

    DisplayFrameworkOverview.......................................... 34

    ChangingDefaultDisplayFrameworks .................................. 35

    RemovingaDisplayScreen ............................................ 36

    ChangingDisplayedParametersinanExistingScreen ..................... 36

  • 8/12/2019 ION Meter-70002-0162-03

    22/152

    Chapter 2 - Front Panel ION7300 Series User Guide

    Page 22 2007 Schneider Electric. All rights reserved.

    Displaying Data with the Front PanelThefrontpanelprovidesadetailedgraphicsandtextdisplayforthemeter.Thefrontpanelisconfiguredatthefactorywitheightdisplaysshowingsomeofthemorecommonlyusedpowersystemvaluesmeasuredbythedevice(refertoDefaultFrontPanelDisplayScreens).

    NOTE

    A Remote Modular Display (RMD) can be added to an existing TRAN meter to provide a front panel

    display.

    Themetersdisplayshowsnumericdatascreens,eventlogs,phasordiagrams,bargraphs,andharmonicshistograms.

    Using the Front Panel Buttons to Display DataPresstheUpandDownarrowbuttonstoscrollthroughthedatadisplayscreens.Youdonotrequirepasswordauthorizationtoviewthesescreens.TheRound

    button,whenpressed,providesaccesstotheSetupmenu.Usethefrontpanelsthreebuttonstonavigatethismenu,andentersettingsintothemeter.

    Measurements aredisplayed here.

    Press the Round button toaccess the Setup menu ormake a selection.

    Use the arrow buttonsto scroll through datadisplay screens.

    Optical (Infrared)port

  • 8/12/2019 ION Meter-70002-0162-03

    23/152

    ION7300 Series User Guide Chapter 2 - Front Panel

    2007 Schneider Electric. All rights reserved. Page 23

    Front Panel Display ResolutionWhendisplayingnumericvalues,thefrontpaneldisplayscreencanshowuptoninedigitsofresolution.Thisninedigitresolutionisavailablewhenthedisplayscreenissettodisplayoneparameter.Anymultiparameterscreendisplaysuptofivedigitsofresolution.

    Ifyourequiremoredigitresolutionthanisavailable,useIONsoftwaretodisplaydata.Ifavalueistoolargetobedisplayedonyourdisplayscreen(i.e.greaterthan99,999onatwoparameterscreen),thefrontpanelusesanabbreviatedengineeringnotationwithstandardmetricprefixestoindicatethemagnitudeofthereading.Thefollowingtableprovidessomeexamples:

    Numericvaluesaredisplayedinbaseunits;voltagesaredisplayedinvolts,whilecurrentisdisplayedinamps.Thefollowingvalues,however,aredisplayedinkilounitsratherthanbaseunitssincekiloisthemostfrequentlyusedvaluerange:

    kW

    kVA

    kVAR

    Whenviewingtheseparameterswiththefrontpanel,rememberthatthevaluesare

    already

    multiplied

    by

    1000.

    For

    example,

    the

    reading

    below

    indicates120,000kilowatts,not120,000watts.

    INVLD and N/A Messages

    Ifthefrontpanelisunabletoreadanumericorstatusvaluefromthemeter,itwilldisplayeitherINVLDorN/Ainplaceofthevalue.INVLDindicatesthatthevaluereceivedcannotbedisplayedbecauseitistoolarge(above9G999).N/Aappearsiftheregisterisnotavailable

    Front Panel Display Value

    124K0 124,000

    124M0 124,000,000

    1G240 1, 240, 000, 000

    kW total 120K0

  • 8/12/2019 ION Meter-70002-0162-03

    24/152

    Chapter 2 - Front Panel ION7300 Series User Guide

    Page 24 2007 Schneider Electric. All rights reserved.

    Display Screen TypesThemetersfrontpaneldisplaysmeasurements,configurablesettings,andcurrentconfigurationdatainvariousforms.Thesedatadisplayscreensaredescribed

    below.

    Default Front Panel Display ScreensThemeterseightdefaultdatadisplaysareasfollows:

    NOTE

    Your default data display screens will differ if the meter is in Fixed mode, or if your meter has custom

    displays.

    Display 1 (kWh net)Net Energy

    Display 5 (Power)Total Power (true, reactive,and apparent), Power Factor.

    Display 2 (kWh swd / mx)Present Interval and MaximumSliding Window Demand

    Display 6 (Frequency)Frequency

    Display 3 (Volts)Per-phase and average

    line-to-line voltage

    Display 7 (V-THD)Per-phase Voltage

    Total Harmonic Distortion

    Display 4 (Amps)Per-phase andaverage current

    Display 8 (I-THD)Per-phase CurrentTotal Harmonic Distortion

  • 8/12/2019 ION Meter-70002-0162-03

    25/152

    ION7300 Series User Guide Chapter 2 - Front Panel

    2007 Schneider Electric. All rights reserved. Page 25

    Configuring the Meter with the Front PanelThefrontpanelallowsyoutosetupandconfigurethemeteratitsinstalledlocation.WhenyouchangeasettinginthefrontpanelsSetupmenu,youareactuallyalteringthesetupregistervalueofanIONmodule.

    NOTE

    ION module links cannot be added or deleted using the front panel.

    YoucanalsousethefrontpanelsSetupmenutoquicklyresetcommoncumulativevalueslikekilowatthours.

    Using the Front Panel Buttons for ConfigurationPresstheRoundbuttontwicetoaccesstheSetupmenus.Usethefrontpanelsthreebuttonstonavigatethesemenus,andentersettingsintothemeter.

    Navigating MenusEachmenuhasatitledisplayedatthetopofthedisplayscreenandmenuitemsdisplayedbelowthetitle.Usethearrowbuttonstoscrollthroughthemenuitems.Toselectanitemthatishighlighted,presstheRoundbutton.Toreturntothepreviousscreen,selectRETURN.ReturntothedatadisplayscreensbyrepeatedlyselectingRETURN.

    Editing RegistersToeditthevalueofaregister,navigatethroughtheregistersusingthearrowkeys

    until

    the

    register

    you

    want

    is

    highlighted,

    then

    press

    the

    Round

    button.

    The

    registerappearsinoneoftwoways:asanumber,orasanoptionselectedfromamenu.Onceyouhaveenteredthepassword(ifrequired),aYESorNOverificationscreenappearsshowingthenewvalueoftheregister.SelectYEStochangethevalueofthesetupregister;selectNOtoreturntothepreviousscreenwithoutchangingthevalue.

    Numeric Registers

    Usethearrowbuttonstochangethevalueofthedigitabovethe cursor.Changethepositionofthecursorbyholdingdownanarrowkeyforaboutonesecond.HoldingtheUparrowbuttonmovesthecursorleftoneposition,andholdingtheDownarrowbuttonmovesthecursorrightoneposition.Onceyouhavethevalueyouwant,presstheRoundbutton.

    Enumerated Registers

    Someregistersaredisplayedasamenuofoptions.Thecurrentvalueoftheregisterwillbedisplayedinthelistwithanasterix(*)oneithersideofit.Usethearrow

    buttonstohighlightthesettingyouwant,andpresstheRoundbutton.

  • 8/12/2019 ION Meter-70002-0162-03

    26/152

    Chapter 2 - Front Panel ION7300 Series User Guide

    Page 26 2007 Schneider Electric. All rights reserved.

    PasswordsAllconfigurationfunctionsinthefrontpanelarepasswordprotected.Thepasswordissetto0(zero)inthefactory.Thefrontpanelonlypromptsyouforthemeterpasswordbeforeyoumakeyourfirstconfigurationchange.SeetheSecuritychapterformoreinformationonpasswords.

    Confirming Configuration ChangesAconfirmationscreenappearswheneveryouattempttochangethemeterssettingsthroughthefrontpanel.Thisallowsyoutoabortanunwantedconfigurationchange.Thefrontpanelalsoinformsyouwhenanentryisoutofrange.

    Writing Errors

    Iftheconfirmationscreendoesnotappearforavalidentry,orthedisplayreportsawritingerror,repeattheconfigurationchange.Iftheproblempersists,contactTechnicalSupport.

    The Front Panels Main Setup MenuToaccessthefrontpanelsmainSetupmenu,presstheRoundbutton.TheSetupmenuappearslistingthemetersfrontpanelsetupoptions:

    Advanced Meter Setup MenuTheAdvancedMeterSetupmenuprovidesaccesstothesetupregistersofeveryIONmoduleinthemeter.Toaccessthismenuscreen,selectADVMETERSETUPfromthemainSetupmenu.

    Setup Option Description

    Clear Functions

    Resets Min/Max, Sliding Window Demand, Energy, Thermal Demand, PeakDemand Registers, Harmonics Min/Max, Status Counters, Manual WaveformCapture, and Disturbance Counts.See the Resets chapter for more information.

    Quick SetupChanges settings in the Communications, Power Meter, and Sag/Swell modules.See the Communications, Basic Setup and Power Quality chapters for moreinformation.

    Adv MeterSetup

    Provides access to all the modules in the meter.

    Display Setup Customizes the appearance of the display screen.

    Screen Setup Customizes the style and values appearing on the display screens.

    Nameplate Info Displays information about the device.

    SecurityAllows you to modify your password.See the Security chapter for more information.

    Diagnostics Screens to aid in troubleshooting.

  • 8/12/2019 ION Meter-70002-0162-03

    27/152

    ION7300 Series User Guide Chapter 2 - Front Panel

    2007 Schneider Electric. All rights reserved. Page 27

    Followthisproceduretoaccessasetupregister:

    1. FromtheFeatureManagerscreen,selectthemodulestype.

    2. Selectthemoduleyouwanttoconfigurefromthelistofavailablemodules.

    3. Fromthelistofthemodulessetupregisters,selecttheoneyouwantto

    configure.4. Editthevalueoftheregister(seeEditingRegistersonpage 25).

    Youmaybepromptedtoenteryourpassword.SelectYEStothenextprompttochangethevalueoftheregister.SelectNOifyouwanttoleavethescreenwithoutmakinganychanges.

    RefertotheIONReferenceforcompletedetailsoneachsetupregistersfunction.

    Display Setup Menu

    SelectDISPLAY

    SETUP

    from

    the

    main

    Setup

    menu

    to

    access

    these

    settings:

    Auto ScrollAutoScrollactivateseachoftheenableddisplayscreensinsequence.Bydefault,theAutoScrollisdisabled.Usethearrowbuttonstospecifythenumberofsecondsthateachscreenisdisplayedbeforeitflipstothenextdisplayscreen,thenpresstheRoundbuttontosetthevalue.AnyscreensthathavebeendisabledwillnotappearwhenAutoScrollisenabled.Setthenumericvaluetozero(thedefaultvalue)todisableautoscrolling.

    ContrastTochangethecontrastofthefrontpanelsdisplay,selectCONTRAST.Pressanarrowbuttononce,andthedisplayscreenscontrastslowlychanges.Pressanarrowbuttontostoptheprocess.PresstheRoundbuttonwhenyouaresatisfiedwiththecontrastlevel.

    NOTE

    Contrast can be adjusted from any screen by holding down the Round button for more than ten seconds.

    Release the Round button when the contrast is at a suitable level.

    Display Setup Option Default Description

    Auto Scroll 0 s (Disabled) Time between automatic display screen advance.

    Backlight Time 1800 secondsTime before display screen backlight automaticallyturns off.

    Display Update 4 s Period between data display refreshes.

    Display Mode Programmable Custom or Factory configured display screen option.

    Contrast mid The display screens contrast level.

  • 8/12/2019 ION Meter-70002-0162-03

    28/152

    Chapter 2 - Front Panel ION7300 Series User Guide

    Page 28 2007 Schneider Electric. All rights reserved.

    Backlight TimeoutThissettingchangestheamountoftimethefrontpanelsbacklightstaysonwhenthefrontpanelisidle.Thebacklighthasalimitedlifespan;toprolongit,youshouldonlyhavebacklightingonwhenyouareactivelyusingthefrontpanel.SelectBACKLIGHTTIMEOUT,thenusethefrontpanelsbuttonstochangetheamountoftimeinsecondsthatthebacklightstaysonafterabuttonispressed.

    Display UpdateThedisplayupdatespecifieshowfrequentlydataonthedisplayscreenisrefreshed.Youmayfindthevaluesarebeingupdatedtoofrequently,orthatthedatashownonscreenlagstoofarbehindtheactualvalues.Thedefaultupdaterateisfourseconds;usethefrontpanelsbuttonstochangetheupdateratetosuityourneeds.

    Display ModeTherearetwodisplaymodes:PROGRAMMABLEMODEandFIXEDMODE.Thedefaultisprogrammablemode,whichprovideseightdatadisplayscreenswhichcanbeconfiguredtomeetyourrequirements(seeCustomFrontPanelDisplays).FixedModedisplaysfourscreens,eachwithlargecharactersinthedisplay,easilyvisiblefromadistance.ThefourfixedmodescreensdisplayAverageVolts,AverageAmps,kWtotal,andPFtotal.Youcannotcustomizethefixedmodedisplays.

    Screen Setup MenuTheSCREENSETUPmenuscreenallowsyoutochangethedatadisplayedontheeightdisplayscreens.FromtheSELECTSETUPmenu,selectSCREENSETUP.Thelistofdisplaytitlesappearthatcorrespondtoeachoftheeightdisplayscreens(see

    DefaultFrontPanelDisplayScreens).Thescreennumberwithanasterix(*)besideitindicatestheactivedisplay(thescreendisplayedbeforeyouenteredSELECTSETUP).Selectthescreenyouwanttochange,andpresstheRoundbutton.Twosettingsappear,VALUESandSTYLE,thatallowyoutospecifywhichmeasurementstodisplay.

    StyleTheSTYLEsettingdefinesthenumberofparametersoneachscreen.Thissettinghasfiveoptionsforeachdisplayscreen:ONEPARAMETER,TWOPARAMETER,THREEPARAMETER,FOURPARAMETER,andDISABLED.Selectthenumberofvaluesyouwanttodisplay(thefewervaluesyouselectfordisplay,thelargerthe

    measurement

    will

    appear

    on

    the

    display

    screen).

    Ifyouselectalargestyle(forexample,oneparameter)foradisplayscreenthatisalreadysettodisplaymorethanonevalue,thefrontpanelwarnsyouwithamessage,anddisplaysonlythefirstvaluethelinkstoallsubsequentvaluesareseveredandhavetobereprogrammed.

    Style = One Parameter

    Style = Four Parameter

  • 8/12/2019 ION Meter-70002-0162-03

    29/152

    ION7300 Series User Guide Chapter 2 - Front Panel

    2007 Schneider Electric. All rights reserved. Page 29

    ValuesTheVALUESsettingspecifieswhichofthedevicesmeasurementsaredisplayedoneachdisplayscreen.Whenyouchangethevaluedisplayedonascreen,youarepresentedwithacompletelistofthemetersmeasurements.Usingthelistsofmodulesprovided,selectthevaluesyouwanttohavedisplayedonthatdisplayscreen.

    ThenumberofVALUESyoucanselectisafunctionoftheSTYLEsetting.Youcannotselectmorevaluesthanthestyleissettodisplay.

    Nameplate Info MenuSelectNAMEPLATEINFOtodisplayinformationaboutthevariousoptionsofthedevice,suchas:

    Diagnostic MenuTheDIAGNOSTICmenuisaccessedfromtheSetupmenu;youcanviewperphasevoltageandcurrentharmonicsscreens,verifycommunications,verifythedigitalI/O,andcheckthemeterslocaltime.

    Harmonics Diagnostics

    SelectHARMONICSfromtheDiagnosticsmenutoviewperphasevoltageandcurrentharmonicstothe31stharmonic.Thefollowingisanexampleofaharmonicsdisplay:

    PressandholdtheUpandDownbuttonstomovethecursortotheharmonicofinterest.Thepercentageofthefundamentalisalsodisplayed.

    manufacturer

    metertypeandclass

    servicetype

    voltageandcurrentinputratings

    auxiliarypower

    operatingfrequency

    transformerratios

    meterfirmwarerevision

    digitaloutputinformation

    approvals

    serialnumber

    accuracyrating

    acceptableoperatingtemperature

    batterylife

    configureddemandsettings

    threecustomtextlineswrittenintothemetersFactorymodule

  • 8/12/2019 ION Meter-70002-0162-03

    30/152

    Chapter 2 - Front Panel ION7300 Series User Guide

    Page 30 2007 Schneider Electric. All rights reserved.

    Communications Diagnostics

    TheCommunicationsdiagnosticscreendiffersdependingonyourmeterscommunicationsoptions.

    TheRS485diagnosticscreenshowsthreeboxeslabelledCOM1,COM2(orETHifthemeterhastheoptionalEthernetcard)andCOM3.Thefollowingscreenis

    anexample

    of

    Ethernet

    (COM2)

    communication:

    COM1andCOM2refertothecommunicationsportsonthebackpanelofthemeter.AsthereareisnoCOM2portontheION7300meter,theCOM2boxneverappearsactive.TheCOM3boxverifiescommunicationthroughtheInfraredportonthefrontpanel(IR1).

    TheEthernetdiagnosticscreendisplaystextsimilartowhatyouseeinthetablebelow eachlabelappearswithavaluenexttoit.Thetablebelowexplainsthemeaningofeachpossiblevalue.

    TheEthernetConnectiondiagnosticscreendisplaystextsimilartowhatyouseeinthetablebelow eachlabelappearswithavaluenexttoit.Thetablebelowexplainsthemeaningofeachpossiblevalue.

    Label Possible Values Description

    ETH73 Version see description Displays the Ethernet meters firmware version (e.g. v270)

    ETH73 in UPG YES, NO YES means the meter is currently being upgraded

    ETH73 Setup N/A, RecdN/A means the Setup/options on the meter have not beentransmittedRecd means the Setup/options have been received

    EtherGate YES, NOYES means EtherGate is supported (ION7330 andION7350)NO means EtherGate is not supported (ION7300)

    Label Possible Values Description

    # Power Ups see descriptionDisplays the number of times the Ethernet card has powercycled

    ConnectionN/A, ION,Modbus

    The type of Ethernet connection: N/A indicates no connection

    ION indicates ION over Ethernet

    Modbus indicates either Modbus RTU over Ethernet orModbus TCP

    # WEB Reqs see description Displays the number of received WEB Page requests

    # MeterM@il see descript ion Displays the number MeterM@ils sent

  • 8/12/2019 ION Meter-70002-0162-03

    31/152

    ION7300 Series User Guide Chapter 2 - Front Panel

    2007 Schneider Electric. All rights reserved. Page 31

    I/O Diagnostics

    TheI/Odiagnosticsmodeverifiestheoperationofthedigitalinputs/outputsyoumayhaveconnectedtothedeviceand,ifyouorderedtheanalogI/Ooption,allowsyoutomonitortheAnalogInputorAnalogOutputportsonyourmeter.Thefollowingdiagnosticscreensareavailable:

    DigitalInsThisscreendisplaysthefourdigitalinputvaluesasseenatthelowlevel.

    DigitalOutsThisscreendisplaysthefourdigitalinputvaluesasseenatthelowlevel.

    AnalogInsThisscreendisplaysthefouranaloginputvaluesasseenateachAnalogInputmodulesoutputregister.

    AnalogOutsThisscreendisplaysthefouranalogoutputvaluesasseenateachAnalogOutputmodulesoutputregister.

    Troubleshooting Diagnostics

    Therearethreetroubleshootingdiagnosticscreensavailable:

    kiloWattsThisscreenshowsperphaseandtotalkilowatts.

    VoltsThisscreensshowslinetoneutralandaveragevolts.

    PowerFactorThisscreenshowssignedperphaseandtotalpowerfactor.

    Date/Time Screen

    FortheION7330andION7350meters,thisscreendisplaysthetimeanddatefromthedevicesinternalclock.

    FortheION7300meter,thisscreendisplaysthedateandtimesentviaatimesync.TheION7300meterdoesnotincrementitsinternalclockwhilethemeterispowereddown.

  • 8/12/2019 ION Meter-70002-0162-03

    32/152

    Chapter 2 - Front Panel ION7300 Series User Guide

    Page 32 2007 Schneider Electric. All rights reserved.

    Display SetupThemetersfrontpaneldisplayiscontrolledbytwotypesofIONmodules:theDisplayOptionsmoduleandtheDisplaymodule.UseDesignersoftwaretoconfigureyourdisplays.

    Formoreinformationaboutthesemodules,seetheIONReference.

    Display Options Module SettingsTheDisplayOptionsmoduleisacoremodulethatcannotbedeleted,copied,orlinked.SettingsintheDisplayOptionsmoduleareglobalandaffecttheentiresetoffrontpaneldisplayscreens.

    Display Module SettingsADisplaymodulecontrolswhichvaluesaredisplayedonadisplayscreen,andhowthesevaluesarepresented.EachDisplaymodulecorrespondstoonemeterdisplayscreen.

    TheDisplaymodulesSourceinputsarelinkedtothenumericparametersyouwanttodisplay.TheseparametersaresenttothefrontpanelwhentheDisplaymodulesShowinputispulsed.

    Screen Type Register

    TheScreenTypesetupregisterhasfiveoptions:ONEPARAMETER,TWOPARAMETER,THREEPARAMETER,FOURPARAMETER,andDISABLED.ThenumberofinputsfortheDisplaymoduleshouldmatchtheScreenTypesetupregister.IfyouselectaScreenTypewithmoreparametersthanarecurrentlylinkedtotheDisplaymodule,thedisplayscreenwillshowanyunavailableinputsasN/A.

    Setup Register Function Default

    Autoscroll Sets the time between automatic display scrolling (in seconds). Disabled

    Backlight TimeoutSets how long the front panel display will stay bright after the last press of a frontpanel button (in seconds).

    1800

    Display Update Time Sets how frequently the screen data values will be updated (in seconds). 4

    Display ModeSets whether the screens displayed on the front panel are programmable via Displaymodules or fixed.

    Programmable

    Setup Register Function Default

    Screen TypeThis specifies the way the linked parameters are displayed on the front panelscreen.

    Defaults vary among displayscreens.

  • 8/12/2019 ION Meter-70002-0162-03

    33/152

    ION7300 Series User Guide Chapter 2 - Front Panel

    2007 Schneider Electric. All rights reserved. Page 33

    IfaScreenTypeisselectedwhichhasfewerparametersthanarelinkedtothemodule,theDisplaymodulewillonlydisplaythenumberofvaluesallowedbytheScreenType,andwillbreakanylinkstoparametersthatitcannotdisplay.

    Forexample,ifyouhaveadisplayscreenwithfourparameters,andyouselectaScreenTypeofONEPARAMETER,thefirstparameterisdisplayedandtheother

    three

    links

    to

    the

    Display

    module

    are

    severed.

    Changing the Parameters that are DisplayedThemetersdefaultdisplayconfigurationshowsacomprehensivesetofparameters.ChangingtheseparametersrequiresalteringthelinksbetweenvariousIONmodules.CompletedetailsonconfiguringthefrontpaneldisplaysareprovidedinthesectionCustomFrontPanelDisplays.

  • 8/12/2019 ION Meter-70002-0162-03

    34/152

    Chapter 2 - Front Panel ION7300 Series User Guide

    Page 34 2007 Schneider Electric. All rights reserved.

    Custom Front Panel DisplaysCustomfrontpaneldisplayscanbecreatedtoshowanydatathemetermeasuresorcalculates.Eachdisplayscreencanbeconfiguredtodisplayanymeasurementsyourequire.Youcanalsoadjustthesizeofthecharactersineachscreensoyoucaneasilyreadthedevicesdisplayfromfartheraway.

    Thereareonlyeightdisplayscreensavailableforconfiguration.Sincealleightofthefrontpanelsscreendisplaysareusedinthefactoryconfiguration,anexistingdisplaymustbechangedifyouwantacustomdisplay.RefertoDefaultFrontPanelDisplayScreensonpage 24fordetailsontheeightdefaultdisplayscreens.

    Before Customizing the Front PanelInorderforthecustomizedscreenstobedisplayedinthefrontpanelsdisplay,themetersDisplayModemustbeproperlyset.EnsurethattheDisplayOptionsmodulesDisplayModesetupregisterissettoPROGRAMMABLE.Thisisthedefaultsetting.UsethemetersfrontpanelorIONsoftwaretosetthisregister.

    Customizing Displays Using the Front PanelTheSCREENSETUPmenuscreenallowsyoutochangethedatadisplayedontheeightdisplayscreensusingthefrontpanel(seeScreenSetupMenuonpage 28).

    Customizing Displays Using ION softwareThefrontpaneldisplaysoftheION7300seriesarecontrolledbytheDisplaymodulesandtheDisplayOptionsmodule.RefertotheIONReferencefordetaileddescriptionsofthesemodules.

    LinkstoaDisplaymodulecanbemadeusingDesignerorthefrontpanel.EachDisplaymodulehasonesetupregister,ScreenType,whichsetsthenumberofparametersthatthedisplayscreenwillshow.

    Display Framework OverviewThefollowingdiagramsillustratehowtheDisplayOptionsmoduleandDisplaymoduleworktogethertoprovideyourmetersfrontpanelwiththeappropriatedisplayscreens.

  • 8/12/2019 ION Meter-70002-0162-03

    35/152

    ION7300 Series User Guide Chapter 2 - Front Panel

    2007 Schneider Electric. All rights reserved. Page 35

    Module Behavior

    TheorderinwhichdatadisplaysdependsonthenumberingoftheDisplaymodules.Therefore,thedatalinkedtoDisplaymodule1isdisplayedonthefirstfrontpanelscreenandsoon.ScrollingbetweenthedisplayscreensisdonewiththeUp/Downarrowbuttonsonthefrontofthemeter.

    Viewing all Display and Display Options modules at once

    1. LaunchDesignerandopenyourmeter.

    2. Doubleclick

    the

    Meter

    Display

    Setup

    folder

    in

    the

    main

    meter

    configuration

    screen.ThelabelbelowthefolderreadsDisplayModules.

    AllDisplaymodulesandashortcuttotheDisplayOptionsmoduleappear.

    Changing Default Display FrameworksThreecommoncustomizationsarediscussedinthefollowingsections:

    removingadisplayscreen

    addinganewdisplayscreen

    replacingtheparametersinanexistingdisplayscreen

    Making a Framework BackupBeforeyoureconfigureordeleteaframework,youshouldmakeacopy.Thisensuresthatyoucanrestoretheframeworkwithouthavingtoreinitializethefactoryconfiguration.

    There is anAutoScrollregister for the

    ION7300series meter,though it isdisabled bydefault.

    Display

    Options

    Module

    Diagnostic

    module

    Power Meter

    module

    TotalLogMemory

    FreeLogMemory

    kW tot

    kVAR tot

    kVA tot

    PF sign tot

    kWh net

    V unbalance

    I unbalance

    Display

    Module 4

    Display

    Module 3

    Display

    Module 2

    DisplayModule 1

    Source 1

    Source 2

    Source 1

    Source 2

    Source 4

    Source 1

    Source 1

    Source 2

    Source 3

    kW tot 187

    kVAR tot 62

    kVA tot 197

    PF sign tot -94.9

    kWh net

    1475.35

    Total Log Memory

    300

    Free Log Memory

    300

    V unbalance 0.96

    I unbalance 0.97

  • 8/12/2019 ION Meter-70002-0162-03

    36/152

    Chapter 2 - Front Panel ION7300 Series User Guide

    Page 36 2007 Schneider Electric. All rights reserved.

    Making a framework copy

    1. Selectthedesiredframework.

    2. ChooseCopytoFrameworkfromtheEditmenu.Givetheframeworkauniquename.Selectalocationinwhichtosavetheframework.

    3. ClickOk.

    Formoreinformationonreinitializingfactoryconfigurations,seeRestoringtheFactoryConfigurationinChapter3.

    Removing a Display ScreenUsecautionwhendeletingmodules,asanydependantmodulesarealsoaffected.Designerinformsyouofdependantmodulesiftheyexistonthesamenode.

    Removing a data display screen

    1. LaunchDesigner.

    2. SelecttheDisplaymoduleresponsibleforthescreen.

    3. Pressdelete.ThisalsodeletesalllinkstothatparticularDisplaymodule.

    Ifthedisplayscreenyouaredeletingispartoftheautomaticscrollingcycle,youshouldreconfigurethelinksfromtheScrollmodulesTriggeroutputstotheremainingDisplaymodulessothatthefollowingconsiderationsholdtrue:

    ThefirstDisplaymoduleinthescrollingcycleislinkedtotheTrigger1outputoftheScrollmodule.

    ThelastDisplaymoduleinthescrollingcycle(modulen)islinkedtotheTriggernoutputoftheScrollmodule.Forexample,ifyourscrollingcycleconsistsof5screens,

    thenTrigger

    5

    should

    be

    linked

    to

    the

    fifth

    module

    in

    the

    cycle. TheWraparoundsetupregisteroftheScrollmoduledesignatesthelasttrigger

    output(Triggern).Expandingonthepreviousexample,sinceTrigger5isthelasttrigger,theScrollmodulesWraparoundsetupregisterwouldhaveavalueof5.

    Changing Displayed Parameters in an Existing ScreenYoucanchangedisplayedparametersinexistingscreensusingDesignersoftware.

    NOTE

    You must set the Display Options modules Display Mode setup register to PROGRAMMABLE before

    changing displayed parameters in an existing screen.

    Tochangeparametersshowninadisplayscreen,linktheoutputregistercontainingthenumericdatayouwanttodisplaytotheSourceinputsoftheDisplaymodule.IfthereisnotafreeSourceinput,youwillhavetofirstdelete(i.e.,unlink)anexistinglinktoaSourceinput.

  • 8/12/2019 ION Meter-70002-0162-03

    37/152

    ION7300 Series User Guide Chapter 2 - Front Panel

    2007 Schneider Electric. All rights reserved. Page 37

    Changing Displayed Parameters using the Meters FrontPanelYoucanalsochangethedisplayedparametersinanexistingscreenusingthemetersfrontpanel.

    Before changing displayed parameters in an existing screenForcustomizedscreenstodisplayonthefrontpanel,youmustsettheDisplayOptionsmodulesDisplayModesetupregistertoPROGRAMMABLEbeforechangingdisplayedparametersinanexistingscreen.

    Onthemetersfrontpanel,gotoDISPLAYSETUP>DISPLAYMODEandselectPROGRAMMABLE.

    Changing displayed parameters in an existing screen

    TheSCREENSETUPmenuscreenallowsyoutochangethedatadisplayedontheeightdisplayscreens.

    1. Fromthe

    SELECT

    SETUP

    menu,

    select

    SCREEN

    SETUP.

    The

    list

    of

    display

    titles

    appearsthatcorrespondtoeachoftheeightdisplayscreens.Thescreennumberwithanasterix(*)besideitindicatestheactivedisplay(thescreendisplayedbeforeyouenteredSELECTSETUP).

    2. Selectthescreenyouwanttochange,andpresstheRoundbutton.Twosettingsappear,VALUESandSTYLE,thatallowyoutospecifywhichmeasurementstodisplay.

    3. SelectSTYLEifyouneedtochangethenumberofdisplayedparametersintheselectedscreen.

    Thissettinghasfiveoptionsforeachdisplayscreen:ONEPARAMETER,TWOPARAMETER,THREEPARAMETER,FOURPARAMETER,andDISABLED.Selectthenumberofvaluesyouwanttodisplay(thefewerthevaluesyouselectfordisplay,thelargerthemeasurementwillappearonthedisplayscreen).

    Ifyouselectalargestyle(forexample,onevalue)foradisplayscreenthatissettodisplaymorethanonevalue,thefrontpanelwillwarnyouwithamessage,andwilldisplayonlythefirstvaluethelinkstotheundisplayablevaluesareseveredandwillhavetobereprogrammed.

    4. SelectVALUEStochangethedisplayedparameterintheselectedscreen.

    Whenyouchangethevaluedisplayedonascreen,youarepresentedwithacompletelistofthemetersmeasurements.Usingthelistsofmodulesprovided,selectthevaluesyouwanttohavedisplayedonthatdisplayscreen.

    ThenumberofVALUESyoucanselectisafunctionoftheSTYLEsetting.You

    cannotselect

    more

    values

    than

    the

    STYLE

    is

    set

    to

    display.

  • 8/12/2019 ION Meter-70002-0162-03

    38/152

    Chapter 2 - Front Panel ION7300 Series User Guide

    Page 38 2007 Schneider Electric. All rights reserved.

  • 8/12/2019 ION Meter-70002-0162-03

    39/152

    2007 Schneider Electric. All rights reserved. Page 39

    3 Templates, Frameworks and Firmware

    Yourmetercomesinstalledwithapreconfigureddefaulttemplate.Thistemplatecontainsvariousframeworkswhichprovideallthepowermeasuringandanalyzingfunctionalityofthemeter.Templatesandframeworkscanbeusedimmediatelywithoutanyuserconfiguration(rightoutofthebox).Theycanalso

    becustomized,reconfigured,andpastedfromonemetertoanother.

    Formoreinformationontemplates,frameworksandIONmodules,seetheIONReference.

    Yourmetersoperatingsystemisknownasfirmware.Whennewerfirmwareisavailableforyourmeter,simplyupgradetothelatestversionforalltheadded

    featuresandfunctionality.

    CAUTION

    Early ION7300 series meters (Revision A) are not compatible with Revision B firmware, and vice versa.

    See the Schneider Electric website for more information.

    In This Chapter

    Factory Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

    FactoryModule

    Settings

    ...........................................40

    HowtoTAGYourMeter .............................................. 40

    UsingIONSetup ................................................. 40

    UsingDesigner ................................................... 41

    Restoring the Factory Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42UsingDesigner ................................................... 42

    UsingIONSetup ................................................. 43

    Upgrading Your Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

  • 8/12/2019 ION Meter-70002-0162-03

    40/152

    Chapter 3 - Templates, Frameworks and Firmware ION7300 Series User Guide

    Page 40 2007 Schneider Electric. All rights reserved.

    Factory InformationTheFactorymoduledisplaysfirmwareversion,serialnumberandotherdeviceinformationinreadonlysetupregisters(readonlyregisterscanbeviewedbutnotchanged).

    Factory Module SettingsThedeviceinformationprovidedisasfollows::

    TheFactorymodulealsocontainsnumerousreadonlysetupregistersthatholdthecalibrationconstantsusedatthefactory.

    How to TAG Your MeterThreeconfigurablesetupregistersareprovidedforyoutoenteryourcompanynameandothertextinformationyouwantstoredinthemeter:

    Owner Thisisatextregisterforstoringuserinformation(e.g.companyname);itcanbeupto255charactersinlength.

    Tag1 Thisisatextregisterforstoringuserinformation(e.g.devicelocation);itcanbeupto15charactersinlength.

    Tag2 Thisisatextregisterforstoringuserinformation(e.g.devicenumberoridentifier);itcanbeupto15charactersinlength.Ifthisfieldisnotleftblank,MV90requirestheirDeviceIDfieldtomatchthisfield.

    Using ION Setup1. ConnecttoyourmeterinIONSetup,usingBasicMode.

    2. NavigatetoSetupAssistant>BasicSetup

    Setup Register Description

    Device Type A device type ident ifier (7300 for the ION7300)

    Compliance A statement of whether the device is ION compliant or not

    Options Shows model number of meter

    Revision The meters firmware version

    Serial Num The meters serial number

    ION Version The ION version supported by the device

    Template The name of the factory default template (framework) installed on the device

    Nom Freq The expected frequency of the power system being monitored

  • 8/12/2019 ION Meter-70002-0162-03

    41/152

    ION7300 Series User Guide Chapter 3 - Templates, Frameworks and Firmware

    2007 Schneider Electric. All rights reserved. Page 41

    3. ClicktheNameplateInfotab.

    4. Selectthe

    register

    you

    want

    to

    configure

    and

    click

    Edit.

    Using DesignerOpenyourmeterinDesignerandnavigatetothemainConfigurationscreen.RightclickontheFactorymoduletoedit.

  • 8/12/2019 ION Meter-70002-0162-03

    42/152

  • 8/12/2019 ION Meter-70002-0162-03

    43/152

    ION7300 Series User Guide Chapter 3 - Templates, Frameworks and Firmware

    2007 Schneider Electric. All rights reserved. Page 43

    10. ClickthePowerMetershortcutintheBasicConfigurationareatoselectit.Onceselected,clickResetintheDesignertoolbar,orselectResetfromtheEditmenu.ThisrevertsthePowerMetertothesettingsithadbeforeyoudeletedanymodules(retainingthebasicsetupyoupreviouslyhad).

    11. ChooseSend&SavefromtheFilemenu.Thefactoryconfigurationisnowrestoredandanycustomfunctionalityyoucreatedbeforeisremoved.

    NOTE

    The time required to complete steps 3, 5, and 11 may vary depending on your connection and the meter

    configuration.

    Using ION Setup1. Downloadyourdeviceslatesttemplatefromhttp://www.powerlogic.com/

    support/downloads/.Savethe.DCFfileinthe.../IONSetup/TEMPLATEfolderforeasyaccess.

    2. ConnecttoyourmeterinIONSetup,usingBasicMode.

    3. NavigatetoSetupAssistant>Template

    4. ClicktheSendtoMetertabandclicktheSendbutton.

    5. Selectthe.DCFfilefromtheTEMPLATEfolderandclickOK.

    6. TheTemplatePasteOptionsscreenappears.Selectthecheckboxesforthesettingsyouwishtoretain(notoverwrite)andclickOK.

  • 8/12/2019 ION Meter-70002-0162-03

    44/152

    Chapter 3 - Templates, Frameworks and Firmware ION7300 Series User Guide

    Page 44 2007 Schneider Electric. All rights reserved.

    IONSetuppastesthetemplateontoyourmeter.Adialogboxconfirmsthepastewassuccessful.

    Upgrading Your MeterSeetheUpgradingIONDeviceFirmwaretechnicalnotefordetails.

  • 8/12/2019 ION Meter-70002-0162-03

    45/152

    2007 Schneider Electric. All rights reserved. Page 45

    4 Basic Setup

    Thischapterexplainshowtoperformbasicmetersetup.

    In This Chapter

    Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

    Configuring Basic Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46UsingtheFrontPanel ............................................. 46

    UsingIONSetup ................................................. 47

    UsingDesigner

    ...................................................47

    PowerMeterModuleSettings .......................................... 48

  • 8/12/2019 ION Meter-70002-0162-03

    46/152

    Chapter 4 - Basic Setup ION7300 Series User Guide

    Page 46 2007 Schneider Electric. All rights reserved.

    IntroductionBasicconfigurationofthemeterisprovidedbythePowerMetermodule.ThePowerMetermoduleisthemainconnectionbetweenthepowersystemmeasurementsandallotherIONmodulesinthedevice.Thismodulereportsthevaluesforallvoltage,currentandpowermeasurements.ThePowerMetermodulessetupregistersdescribedetailsofthepowersystembeingmonitored.ManyofthePowerMetermodulessetupregistersareconfiguredwhenthemeterisinitiallyputintoservice,althoughthedevicecannotoperateproperlyuntiltheVoltsModeandPTandCTratiosareset.Someregistersmayneedtobechangedtorefinethedevicesoperation.

    SeetheIONReferenceformoredetailsonthePowerMetermodule.

    Configuring Basic SetupUsethefrontpanelorIONsoftwaretoperformbasicmetersetup.

    Using the Front PanelNavigatetoQuickSetup>PowerMetertoaccesstothefollowingpowersystemsettings:

    Menu Setting Description Range (Values) Default

    PowerMeter

    Volts ModeThe power systems configuration WYE, DELTA, etc.

    4W-WYEDELTASINGLEDEMO

    3W-WYEDIRECT-DELTA

    4W-WYE

    PT1 (Primary)The Potential Transformersprimary winding voltage rating

    1 to 999,999,999 347

    PT2 (Secondary)The Potential Transformerssecondary winding voltage rating

    1 to 999,999,999 347

    CT1 (Primary)The Current Transformersprimary winding current rating

    1 to 999,999,999 5

    CT2 (Secondary)The Current Transformerssecondary winding current rating

    1 to 999,999,999 5

    V1 PolarityThe polarity of the PotentialTransformer on V1

    Normal or Inverted Normal

    V2 PolarityThe polarity of the PotentialTransformer on V2

    Normal or Inverted Normal

    V3 Polarity The polarity of the PotentialTransformer on V3

    Normal or Inverted Normal

    I1 PolarityThe polarity of the CurrentTransformer on I1

    Normal or Inverted Normal

    I2 PolarityThe polarity of the CurrentTransformer on I2

    Normal or Inverted Normal

    I3 PolarityThe polarity of the CurrentTransformer on I3

    Normal or Inverted Normal

  • 8/12/2019 ION Meter-70002-0162-03

    47/152

    ION7300 Series User Guide Chapter 4 - Basic Setup

    2007 Schneider Electric. All rights reserved. Page 47

    Using ION SetupTheBasicSetupAssistanthelpsyouconfigurethePowerMetermoduleandenergyrolloversettings.

    1. OpenIONSetupandconnecttoyourmeter,usingBasicMode.

    2. IntheSetupAssistant,navigatetoBasicSetupandclickonthePT/CTRatiostab.

    3. ConfigureeachregisterasrequiredbyselectingtheparameterandclickingEdit.

    4. ClicktheRollovertabtoconfigureEnergyRollover.Thisregisterdetermineshowmanyenergyvalues(forexample,kilowatts)accumulatebeforethenumberrollsovertozero.Thedefaultsettingistenmillion.

    Using DesignerOpenyourmeterinDesignerandnavigatetotheBasicConfigurationFramework.RightclickonthePowerMetermoduletoedit.

  • 8/12/2019 ION Meter-70002-0162-03

    48/152

    Chapter 4 - Basic Setup ION7300 Series User Guide

    Page 48 2007 Schneider Electric. All rights reserved.

    Power Meter Module SettingsThePowerMetermodulecontainsthefollowingsetupregisters:

    Setup Register Function Default

    Volts Mode The power systems configuration WYE, DELTA, Single, etc 4W-WYE

    PT Prim The Potential Transformers primary winding rating for V1, V2 and V3 347

    PT Sec The Potential Transformers secondary winding rating for V1, V2 and V3 347

    CT Prim The Current Transformers primary winding rating for I1, I2 and I3 5

    CT Sec The Current Transformers secondary winding rating for I1, I2 and I3 5

    Vn Polarity The polarity of the Potential Transformer on Vn Normal

    In Polarity The polarity of the Current Transformer on In Normal

    Phase Order The expected rotation of the voltage phases (ABC or ACB) ABC

    Phase Lbls The phase label format assigned to the outputs (ABC, RST, XYZ, RYB, RWB or 123) ABC

  • 8/12/2019 ION Meter-70002-0162-03

    49/152

    2007 Schneider Electric. All rights reserved. Page 49

    5 Security

    ION7300seriesmetersofferFrontPanelmetersecurity,whichisenabledfromthefactory.ThischapterexplainsFrontPanelmetersecurityandhowtochangethemeterpassword.Italsodetailssomesecurityfeaturesavailableforrevenuemeters.

    In This Chapter

    Meter Security Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50FrontPanelSecurity................................................... 50

    EnteringtheMeterPassword ....................................... 50

    ChangingtheMeterPassword ...................................... 51

    Device Security Access for ION Services . . . . . . . . . . . . . . . . . . . . . . . . . . . 52AllowingIONServicesaccesstosecurityenabledmeters............... 52

    Additional Revenue Metering Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53HardwareLockSecurityOption .................................... 53

  • 8/12/2019 ION Meter-70002-0162-03

    50/152

    Chapter 5 - Security ION7300 Series User Guide

    Page 50 2007 Schneider Electric. All rights reserved.

    Meter Security FeaturesYourmeterincludesthefollowingsecurityfeatures:

    Front panel security

    Anytimeyou

    make

    configuration

    changes

    to

    your

    meter

    through

    the

    front

    panel

    youmustenterapassword.

    Anti-tamper sealing

    Yourrevenuemetercanbeprotectedbyantitampersealing.

    Software security

    IONsoftwaresecuritybringsaccesslevelsecuritytothemeter.WithIONsoftware,youcanconfiguremultipleuserswithdifferentpasswordsandspecifyaccessrights.IONsoftwaresecurityonlyappliestouserswhoareaccessingthemeterviaIONsoftware.

    Formore

    information

    on

    security,

    refer

    to

    the

    ION

    System

    Security

    technical

    note.

    Front Panel SecurityFrontpanelmetersecurityletsyouconfigurethemeterthroughthefrontpanelusingameterpassword.

    Entering the Meter PasswordFrontpanelmetersecurityisenabledbydefaultonallION7300seriesmeters;allconfigurationfunctionsinthefrontpanelarepasswordprotected.Thepassword

    isfactory

    set

    to

    0(zero).

    Ifyoumakeconfigurationchangestothemeterviathefrontpanel,themeterpromptsyouforapasswordbeforeacceptinganyconfigurationchanges.Onceyouenterthecorrectmeterpasswordandconfirmthenewconfiguration,thechangeissetonthemeter.

    Notethatthefrontpanelwillpromptyouforthemeterpasswordbeforeyoumakeyourfirstconfigurationchange.Youwillnotneedtoreenterthepasswordforeachsubsequentchange.

    NOTE

    The password enables users to change the configuration of the meter. It is recommended that you changeyour password from the default when you put the meter into service.

    Ifyouenteranincorrectpassword,thefrontpanelwilldisplayaninvalidpasswordmessageandyoumusttryagain.

  • 8/12/2019 ION Meter-70002-0162-03

    51/152

    ION7300 Series User Guide Chapter 5 - Security

    2007 Schneider Electric. All rights reserved. Page 51

    Changing the Meter Password1. SelectSECURITYfromthemainSetupmenu.

    2. Youwillseethatthescreendisplays00000.Enterthecurrentpassword.Ifyouhavenotpreviouslychangedyourpassword,thedefaultis00000.

    3. ChooseMODIFYPASSWORDtoalteryourpassword(theFACTORYUSEONLYoptionisforfactorypurposesandisnotaccessible).

    4. Enteryournewnumericpassword.

    TochangethevalueofthehighlighteddigitusetheUpandDownarrowbuttons.

    Tochangethepositionofthecursoronespacetotheleft,holdtheUparrowbuttonforaboutonesecond.

    Tochangethepositionofthecursoronespacetotheright,holdtheDownarrowbuttonforaboutonesecond.

    SelectYEStoacceptyournewpasswordandreturntothemainSetupmenu.

    New Password

    00000

  • 8/12/2019 ION Meter-70002-0162-03

    52/152

    Chapter 5 - Security ION7300 Series User Guide

    Page 52 2007 Schneider Electric. All rights reserved.

    Device Security Access for ION ServicesManyIONServicesneedconstantaccesstoyourmeter.TheseservicesincludetheLogInserter,QueryServer,theVirtualProcessorandSiteServerthatperformthefollowingtypeoffunctions:

    NOTE

    You may want to configure a separate user for accessing services. If you observe trouble with IONsoftware accessing the meter, it is likely that these services either do not have access rights or the original

    user name and password have changed.

    Allowing ION Services access to security enabled meters1. LaunchtheManagementConsoleandclickDevicesontheManagement

    ConsolesSystemSetupPane.

    2. Highlightyourmeter,rightclickandselectSecurity....

    3. SelectStandardSecurityfromthedropdownmenu.Clickthecheckboxifyouwanttoallowthisusertosendtimesynchronizationsignalstothemeter.Click

    OK.

    4. EnterthevalidmeterpasswordforStandardSecurity,retypethepasswordtoconfirm,andclickOK.

    Service Function

    Log InserterQuery Server

    Reads the ION meter Data Recorder or waveform modules and canautomatically rearm recorders that are configured as Stop-When-Full

    Virtual ProcessorCan be configured to read from a meter or perform control actionusing Distributed Control.

    Site Server Broadcasts time signals to the meter.

  • 8/12/2019 ION Meter-70002-0162-03

    53/152

    ION7300 Series User Guide Chapter 5 - Security

    2007 Schneider Electric. All rights reserved. Page 53

    Additional Revenue Metering SecurityTomeetgovernmentregulationsandutilitysecurityrequirements,therevenuemeterincorporatesadditionalsecuritysystems:

    ahardwarelockedsecuritysystemthatpreventsmodificationofrevenue

    quantitiesafterthemeterissealed.

    atraditionalantitampermechanicalsealonthemeterbaseunit.

    Hardware Lock Security OptionION7300seriesmetersofferahardwarelockedsecurityfeature.Tomakeconfigurationchangesonahardwarelockedmeter,youmustfirstunlockthemeter.

    SeetheION7300SeriesRevenueMeterproductoptiondocumentformoreinformation.

    Hardware Lock and Protected ValuesTherevenuerelatedsettingsonmeterswiththeHardwareLockoptionarefactoryconfiguredandcannotbechangedwhilethemeterislocked.

    Typicalvaluesthatareprotectedinclude:

    kWh,kVARh,kVAhdelivered,received,delrec,del+rec.

    kW,kVAR,kVAThermalandSlidingWindowdemandminandmaxvalues.

    DigitalOutputscontrollingtheenergypulsingapplications.

    AllPowersystemsettings,includingPTandCTratios.

    Incertaincountriesrevenuecertificationisvoidifthehardwarelockisbroken.

    Locked Module Listings

    Foracompletelistoflockedmodulesspecifictoyourmeterandfirmware,contactTechnicalSupport.

    Anti-Tamper Seals

    ION7300seriesrevenuemetersincorporatesealingtabsthroughwhichtraditionallead/wiresealsareinserted.Thesesealseffectivelypreventunauthorizedpersonnelfromgainingaccesstometerinternals,andareprovidedwiththemeter.

  • 8/12/2019 ION Meter-70002-0162-03

    54/152

    Chapter 5 - Security ION7300 Series User Guide

    Page 54 2007 Schneider Electric. All rights reserved.

  • 8/12/2019 ION Meter-70002-0162-03

    55/152

    2007 Schneider Electric. All rights reserved. Page 55

    6 Communications

    Thischapterincludesgeneralinstructionsforconnectingandconfiguringallthecommunicationportsonyourmeter.

    Forspecificinstallationstepsandmeterspecifications,consultyourInstallationGuide.

    In This Chapter

    Communications Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

    Communications Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57RS485Connections(COM1andCOM2) ................................. 57

    OpticalPortConnections(COM3)....................................... 59

    EthernetConnections(optional) ........................................ 60

    InternalModemConnections(optional) ................................. 61

    ProfibusPort ......................................................... 61

    Configuring Meter Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63SerialCommunicationsSetup .......................................... 64

    ProfibusSetup(ION7300) .............................................. 65

    EthernetCommunicationsSetup........................................ 66

    ModemCommunicationsSetup ........................................ 68

    Internet Connectivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70IONWebMeterFeature................................................ 70

    IONMeterM@ilFeature(ION7330andION7350) ......................... 70

    WebReach ........................................................... 71

    TelnetandHyperTerminal ............................................. 71

    CommunicationsLEDs ................................................ 72

  • 8/12/2019 ION Meter-70002-0162-03

    56/152

    Chapter 6 - Communications ION7300 Series User Guide

    Page 56 2007 Schneider Electric. All rights reserved.

    Communications OverviewThefollowingillustrationshowsallthepossiblecommunicationsconnectionstothemeter.

    ION7300seriesmetershavenumerouscommunicationpossibilitiesdependingonyourorderingpreferences.However,notallcommunicationsoptionsareavailabletoeachmodel.

    Thetablebelowoutlinesthecommunication(COM)portsforeachION7300seriesmeter.TheProfibuscommunicationoptionisavailableonlyontheION7300meter.

    COM1:

    RS-485 serial connection or ModemGate

    All ION7300 series meters provide COM1, an RS-485 serial communications port that supportsthese protocols: ION, Modbus RTU, or DNP(ION7330 / ION7350).ION7330 and ION7350 meters with aninternal modem can use the ModemGateprotocol on COM1, allowing the metersinternal modem to communicate with the

    meter, the ION Enterprise server computer, andany devices that are wired to the metersCOM1 port.

    COM2:

    RS-485 serial connection or EtherGate

    The ION7330 or ION7350 meter providesCOM2. If your meter has an Ethernet card,then COM2 functions as an Ethernetgateway (EtherGate) EtherGate transfersdata directly between an Ethernet networkand any devices that are wired to themeters COM2 port. If there is no Ethernetcard, then COM2 functions as a serial

    communications RS-485 port, and supportsION, Modbus RTU, or DNP protocols.

    The meters internal modemcommunicates to the servercomputer over the telephonenetwork.

    Ethernet port

    All ION7300 series meters support theoptional Ethernet card. An Ethernet connection

    supports ION, Modbus RTU, or Modbus/TCPprotocols.

    COM3:

    Optical serial connection

    All ION7300 series meters provide COM3, an optical(infrared) port. The optical port (located on the front ofthe meter) is used for serial communications, andsupports these protocols: ION, Modbus RTU, or DNP(ION7330 / ION7350). The port can also be used forenergy pulsing.

    NOTE

    The Profibus meter option for the ION7300

    uses special communications connections.

    Meter COM1 COM2COM3(Infrared)

    Ethernet EtherGate Modem ModemGate

    ION7300 Standard Not Available Standard Optional Not Available Not Available Not Available

    ION7330 Standard Standard Standard Optional Optional Optional Optional

    ION7350 Standard Standard Standard Optional Optional Optional Optional

  • 8/12/2019 ION Meter-70002-0162-03

    57/152

    ION7300 Series User Guide Chapter 6 - Communications

    2007 Schneider Electric. All rights reserved. Page 57

    Communications ConnectionsThefollowingsectionprovidesreferenceforconnectingtothemetersvariouscommunicationports.Forthemostcurrentcommunicationspecifications,seeyourmetersInstallationGuide.

    RS485andProfibuscommunications connectionstothemeteraremadetotherearofthemeter.Ethernetandmodemconnectionsaremadetothesides.Opticalconnectionsaremadetotheportonthefrontofthemeter.Seebelowfordetails.

    NOTE

    The Profibus meter option on the ION7300 meter does not use a COM port.

    RS-485 Connections (COM1 and COM2)COM1andCOM2areusedforRS485communications.

    NOTE

    On ION7330 and ION7350 meters with the Ethernet card, COM2 is hardwired for EtherGate only, and

    cannot be used for serial communication.

    Rear View of Meter

    Modem Ethernet

    RJ11 RJ45

    FCC part 68 complianttelephone cord Category 3 or 5 UTP

    Captured-wireconnectors

    22 AWG shielded,twisted pair

    RS-485

  • 8/12/2019 ION Meter-70002-0162-03

    58/152

    Chapter 6 - Communications ION7300 Series User Guide

    Page 58 2007 Schneider Electric. All rights reserved.

    IfyouhavetheModemGateoptiononyourmeter,COM1willautomaticallybesettoModemGate,notRS485.

    NOTE

    The internal modem option is hardwired to COM1. If you are using ModemGate, then any meter with an

    internal modem that will reside on the serial loop must connect to the serial loop using COM2. If COM1

    is used, then the two modems (gated meter internal modem and serially looped meter internal modem)

    conflict during communication.

    RS485connectionsaremadeviathecapturedwireconnectorsontherearofthemeter.Upto32devicescanbeconnectedonasingleRS485bus.UseagoodqualityshieldedtwistedpaircableforeachRS485bus.TheoveralllengthoftheRS485cableconnectingalldevicescannotexceed4000ft.(1219m).ConfiguretheRS485businstraightlineorlooptopologies.

    Straight-Line Topology

    Loop Topology

    General Bus Wiring Considerations

    Wirealldevicesconnectedonthebus,includingthemeter,converter(s)andotherinstrumentation,asfollows:

    Connecttheshieldofeachsegmentofthecabletogroundatoneendonly. Isolatecablesasmuchaspossiblefromsourcesofelectricalnoise.

    Useanintermediateterminalstriptoconnecteachdevicetothebus.Thisallowsforeasyremovalofadeviceforservicingifnecessary.

    RS-232 toRS-485converter

    TerminationResistor

    RS-232 toRS-485converter

    TerminationBlock

  • 8/12/2019 ION Meter-70002-0162-03

    59/152

    ION7300 Series User Guide Chapter 6 - Communications

    2007 Schneider Electric. All rights reserved. Page 59

    InstallaWattterminationresistor(RT)betweenthe(+)and()terminalsofthedeviceateachendpointofastraightlinebus.TheresistorshouldmatchthenominalimpedanceoftheRS485cable(typically120ohmsconsultthemanufacturersdocumentationforthecablesimpedancevalue).

    RS-485 Connection Methods to AvoidAnydeviceconnectionthatcausesabranchinthemainRS485busshouldbeavoided.Thisincludesstarandtee(T)methods.Thesewiringmethodscausesignalreflectionsthatmaycauseinterference.AtanyconnectionpointontheRS485bus,nomorethantwocablesshouldbeconnected.Thisincludesconnectionpointsoninstruments,converters,andterminalstrips.Followingthisguidelineensuresthat

    bothstarandteeconnectionsareavoided.

    Optical Port Connections (COM3)ThefrontopticalportisdesignedtoacceptANSIType2magneticcouplers.Theopticalmagneticcouplerispurchasedseparately;contactSchneiderElectricforalistofrecommendedoptocouplers.

    TheopticalportcancommunicaterealtimemeasurementstoalaptoporsimilardeviceviaION,ModbusRTU,orDNP3.0(ION7330andION7350).Theportcanalsobeusedforinfraredenergypulsing.SeetheOpticalMagneticCouplerstechnicalnoteformoreinformation.

    Avoid 3-way Star

    connection point

    Avoid 3-way T

    connection point

    Magnetic coupler

    attached to front

    optical port

  • 8/12/2019 ION Meter-70002-0162-03

    60/152

    Chapter 6 - Communications ION7300 Series User Guide

    Page 60 2007 Schneider Electric. All rights reserved.

    Toenablecommunicationsfromtheopticalport,configuretheComm3Communicationsmodule.TheProtocol,theBaudRateandUnitIDsetupregistersmustproperlymatchyoursystem.WhencreatinganIONsite,ensurethatRtsCtsisdisabled(settoNo)intheCOM3serialsite.

    RefertotheManagementConsolesectionintheonlineIONEnterpriseHelpformore

    details

    about

    adding

    serial

    sites.

    Ethernet Connections (optional)ThissectiononlyappliesifyourION7300seriesmeterhastheEthernetoption.

    10BaseTEthernetconnectionsaremadeviatheRJ45modularportontheleftsideoftheunit.UsehighqualityCategory3or5UTP(CAT5unshieldedtwistedpairrecommended)cablewithamaleRJ45modularconnectorforconnectiontothe10BaseTport.

    ThemetersupportsasingleEthernetconnectionatatime.WebMeterisaccessibleatthesametime,asareconnectionstoEtherGateandMeterM@il,aslongasthese

    featuresare

    available

    on

    your

    meter.

    TheoptionalEthernetport:

    iscapableofdataratesupto10Mbps

    supportsION,ModbusRTUandModbus/TCPprotocols

    iscontrolledbytheETH1Communicationsmodule

    TheEtherGatefeatureprovidescommunicationsbothtoanEthernetconnecteddeviceandthroughthatdevicetoaconnectedserialnetwork(SeethesectionTheEtherGateProtocol(ION7330andION7350)).OnlyoneEtherGateconnectionisallowedpermeterportatanygiventime.

    Ethernet

  • 8/12/2019 ION Meter-70002-0162-03

    61/152

    ION7300 Series User Guide Chapter 6 - Communications

    2007 Schneider Electric. All rights reserved. Page 61

    Internal Modem Connections (optional)

    Themetersoptionalinternalmodemcanbereadilyusedinmostcountries,andcomplieswithFCC,IndustryCanadaandTBR21regulationsrefertotheNoticesatthestartofthisdocumentformoredetails.

    ConnectiontotheinternalmodemismadeviatheRJ11jack,ortwocapturedwireconnectors,locatedontherightsideofthemeter.Connectthemetertothe

    telephonenetworkwithanFCCPart68complianttelephonecord(thathastwomaleRJ11plugs).

    Ifyouhavethecapturedwireconnectoroption,connectthemetertothetelephonesystemwiththe(barewiretoRJ11)cableprovided.IfyouhavetheCTR21compliantinternalmodemoption,youmayalsorequireanadaptortointerfacewithyourregionaltelephonejack.

    Toenablecommunicationsthroughthemetersinternalmodem,youmustconfiguretheComm1Communicationsmodule.TheBaudRate,UnitID,andProtocolsetupregistersmustproperlymatchyoursystem,andtheinitializationstringfortheinternalmodemmustbesetupusingtheModemInitregister.SeethesectionModemCommunicationsSetupfordetails.

    Profibus PortThisoptionisofferedexclusivelyontheION7300meter.

    Telephone Network

    Pin 3: Ring

    Pin 4: Tip

    RJ11

    LEDs (DE and PWR)Profibus femaleconnector.

    PRO I US

  • 8/12/2019 ION Meter-70002-0162-03

    62/152

    Chapter 6 - Communications ION7300 Series User Guide

    Page 62 2007 Schneider Electric. All rights reserved.

    NOTE

    The Profibus Master file (.GSD file) is included on a floppy disk with the meter. This file must be installed

    on your Profibus Masters before the meter can communicate with the Profibus network.

    TheoptionalProfibusportonthemeteriscapableofoperatingbaudratesupto12

    Mbps.ProfibusConnectionstothemeteraremadeviatheninepinconnectorontherearoftheunit.PlugyourProfibusconnectorfromthenetworkintothisconnector.

  • 8/12/2019 ION Meter-70002-0162-03

    63/152

    ION7300 Series User Guide Chapter 6 - Communications

    2007 Schneider Electric. All rights reserved. Page 63

    Configuring Meter CommunicationsCommunicationsettingsaretypicallyconfiguredwhentheIONmeterisinitiallyputintoservice.AsingleCommunicationsmodulecontrolseachcommunicationsportonthemeter.Themodulessetupregistersdefinetheparametersusedforeachport;theseparametersvaryaccordingtothetypeofcommunicationschannelselected(i.e.RS485,Modem,Optical,Ethernet).

    TheCommunicationmodulescontrolthefollowingchannels:

    1 For ION7330 / ION7350 meters with an optional modem, COM1 is hardwired for ModemGate.2 COM2is not available for the ION7300 meter.3 For ION7330 / ION7350 meters with an optional Ethernet card, COM2 is hardwired for EtherGate.4 Available for the ION7300 meter only.

    UsethemetersfrontpanelorIONSetuptoinitiallyconfigurethemeterscommunications.Oncecommunicationisestablished,Designermayalsobeusedtomakechanges.

    NOTEAltering certain settings of a communications channel that is in use may cause a loss of communications

    with the meter.

    RefertotheCommunicationsmoduledescriptionintheIONReferenceforcompletedetailsaboutallthesetupregistersintheCommunications module.

    Communications ProtocolsBydefault,allcommunicationportsareconfiguredtousetheIONprotocol.UsingotherprotocolsrequiresconfigurationoftheProtocolsetupregisterforthe

    Communicationsmodule

    that

    controls

    the

    port

    you

    want

    to

    use.

    Not

    all

    protocols

    areavailableonallports.

    Available Protocols

    ION

    ModbusRTU

    DNP3.0

    EtherGate

    Module Name Settings

    Comm 1 COM1 RS-485 port and internal modem 1

    Comm 2 2 COM2 RS-485 port or EtherGate 3port

    Infrared Comm COM3 Optical port

    Ethernet Comm 10Base-T Ethernet port

    Profibus Comm 4 Profibus Communications port

  • 8/12/2019 ION Meter-70002-0162-03

    64/152

    Chapter 6 - Communications ION7300 Series User Guide

    Page 64 2007 Schneider Electric. All rights reserved.

    ModemGate

    InfraredI/O

    Profibus

    Factory(reservedforusebyTechnicalSupport)

    Serial Communications SetupSerialcommunicationsareavailableonCOM1,COM2andCOM3(Infrared).Toenablecommunicationsthroughthemetersserialports,configuretheapplicableCommunicationsmodule.TheProtocol,TranDelay,BaudRateandUnitIDsetupregistersmustproperlymatchyoursystemandcanbesetthroughthemetersfrontpanelorIONsoftware.

    Using the Front PanelThecurrentconfigurationofthemeterscommunicationportsarefoundinthe

    variousCOMSetupmenuitems.EthernetsettingsarelocatedunderNetworkSetup.

    1 ModemGate is available on ION7330 and ION7350 meters with an internal modem.2 The factory set Unit ID for COM1 is based on the serial number of the meter, using the last four

    numbers before the dash. For example, if the serial number is PA-0009B263-01, the Unit ID is set in

    the factory to 9263. After a factory reset, the unit ID number will default to 100.3 EtherGate is available on ION7330 and ION7350 meters with Ethernet.

    Using ION Setup1. OpenIONSetupandconnecttoyourmeter,usingBasicMode.

    2. IntheSetupAssistant,navigatetotheCommSettingsfolder.

    Menu Setting Description Range (Values) Default

    Comm

    1CM1 PROTOCOL The communications protocol

    ION, Modbus RTU, DNP 3.00, Factory,

    ModemGate1ION

    CM1 BAUD RATE The data rate, in bits per second 1200, 2400, 4800, 9600, 19200 9600

    CM1 UNIT IDEvery meter on an RS-485 network must have aunique Unit ID number

    1 to 9999From serial

    number2

    Com

    m

    2CM2 PROTOCOL The communications protocol

    ION, Modbus RTU, DNP 3.00, Factory,

    Ethergate3ION

    CM2 BAUD RATE The data rate, in bits per second 1200,