PowerLogicION7300 Series
Power & Energy Meter
User Guide
January 2007
-
8/12/2019 ION Meter-70002-0162-03
2/152
-
8/12/2019 ION Meter-70002-0162-03
3/152
Notices Danger
Thissymbolindicatesthepresenceofdangerousvoltagewithinandoutsidetheproductenclosurethatmayconstituteariskofelectric
shock,serious
injury
or
death
to
persons
if
proper
precautions
are
not
followed.
Caution
Thissymbolalertstheusertothepresenceofhazardsthatmaycauseminorormoderateinjurytopersons,damagetopropertyordamagetothedeviceitself,ifproperprecautionsarenotfollowed.
Note
Thissymboldirectstheusersattentiontoimportantinstallation,operatingandmaintenanceinstructions.
Installation ConsiderationsInstallationandmaintenanceoftheION7300seriesmetershouldonlybeperformedbyqualified,competentpersonnelthathaveappropriatetrainingandexperiencewithhighvoltageandcurrentdevices.ThemetermustbeinstalledinaccordancewithallLocalandNationalElectricalCodes.
DANGER
Failure to observe the following instructions may result in severe injury or death.
DuringnormaloperationoftheION7300seriesmeter,hazardousvoltagesarepresentonitsterminalstrips,andthroughouttheconnectedpotentialtransformer(PT),currenttransformer(CT),digital(status)input,controlpowerandexternalI/Ocircuits.PTandCTsecondarycircuitsarecapableofgeneratinglethalvoltagesandcurrentswiththeirprimarycircuitenergized.Followstandardsafetyprecautionswhileperforminganyinstallationorservicework(i.e.removingPTfuses,shortingCTsecondaries,etc.).
Theterminalstripsonthemeterbaseshouldnotbeuseraccessibleafterinstallation.
Donotusedigitaloutputdevicesforprimaryprotectionfunctions.Theseincludeapplicationswherethedevicesperformenergylimitingfunctionsor
provideprotectionofpeoplefrominjury.DonotusetheION7300seriesinsituationswherefailureofthedevicescancauseinjuryordeath,orcausesufficientenergytobereleasedthatcanstartafire.Themetercanbeusedforsecondaryprotectionfunctions.
DonotHIPOT/Dielectrictestthedigital(status)inputs,digitaloutputs,orcommunicationsterminals.RefertothelabelontheION7300seriesmeterforthemaximumvoltagelevelthedevicecanwithstand.
-
8/12/2019 ION Meter-70002-0162-03
4/152
CAUTION
Observe the following instructions, or permanent damage to the meter may occur.
TheION7300seriesmeteroffersarangeofhardwareoptionsthataffectinputratings.TheION7300seriesmetersserialnumberlabellistsallequipped
options.Applyingcurrentlevelsincompatiblewiththecurrentinputswillpermanentlydamagethemeter.Thisdocumentprovidesinstallationinstructionsapplicabletoeachhardwareoption.
TheION7300seriesmeterschassisgroundmustbeproperlyconnectedtotheswitchgearearthgroundforthenoiseandsurgeprotectioncircuitrytofunctioncorrectly.Failuretodosowillvoidthewarranty.
Terminalscrewtorque:Barriertype(current,voltage,andrelayterminalscrews:1.35Nm(1.00ftlbs.)max.Capturedwiretype(digitalinputs/outputs,communications,powersupply:0.90Nm(0.66ftlbs.)max.
FCC NoticeThisequipmenthasbeentestedandfoundtocomplywiththelimitsforaClassAdigitaldevice,pursuanttoPart15oftheFCCRules.Theselimitsaredesignedtoprovidereasonableprotectionagainstharmfulinterferencewhentheequipmentisoperatedinacommercialenvironment.Thisequipmentgenerates,uses,andcanradiateradiofrequencyenergyand,ifnotinstalledandusedinaccordancewiththeinstructionmanual,maycauseharmfulinterferencetoradiocommunications.Operationofthisequipmentinaresidentialareaislikelytocauseharmfulinterferenceinwhichcasetheuserwillberequiredtocorrecttheinterferenceathisownexpense.TheRingerEquivalenceNumber(REN)fortheION7300seriesoptionalinternalmodemis0.6.ConnectiontotheION7300seriesinternalmodemshouldbemadeviaanFCCPart68complianttelephonecord(notsupplied).TheION7300seriescannotbeusedonapubliccoinphoneserviceorpartyline
services.
Network Compatibility Notice for the Internal ModemTheinternalmodeminmetersequippedwiththisoptioniscompatiblewiththetelephonesystemsofmostcountriesintheworld,withtheexceptionofAustraliaandNewZealand.Useinsomecountriesmayrequiremodificationoftheinternalmodemsinitializationstrings.Ifproblemsusingthemodemonyourphonesystemoccur,pleasecontactSchneiderElectricTechnicalSupport.
Standards Compliance
MadebyPowerMeasurementLtd.
CSA: Certified to CAN/CSA C22.2 No.1010-1
Certified toUL 3111
-
8/12/2019 ION Meter-70002-0162-03
5/152
PowerLogic,ION,IONEnterprise,MeterM@ilandModbusareeithertrademarksorregisteredtrademarksofSchneiderElectric. Allothertrademarksarepropertyoftheirrespectiveowners.
Coveredbyoneormoreofthefollowingpatents:
U.S.
Patent
No
s
7010438,
7006934,
6990395,
6988182,
6988025,
6983211,
6961641,
6957158,6944555,6871150,6853978,6825776,6813571,6798191,6798190,6792364,6792337,6751562,6745138,6737855,6694270,6687627,6671654,6671635,6615147,6611922,6611773,6563697,6493644,6397155,6236949,6186842,6185508,6000034,5995911,5828576,5736847,5650936,D505087,D459259,D458863,D443541,D439535,D435471,D432934,D429655,D427533.
-
8/12/2019 ION Meter-70002-0162-03
6/152
-
8/12/2019 ION Meter-70002-0162-03
7/152
Table of Contents
Chapter 1 Introduction .................................................................. 9
Chapter 2 Front Panel ................................................................. 21
Chapter 3 Templates, Frameworks and Firmware ........................ 39
Chapter 4 Basic Setup ................................................................. 45
Chapter 5 Security ...................................................................... 49
Chapter 6 Communications ......................................................... 55
Chapter 7 Third-Party Protocols ................................................... 73
Chapter 8 Time ........................................................................... 89
Chapter 9 Demand ..................................................................... 93
Chapter 10 Inputs / Outputs ......................................................... 97
Chapter 11 Energy Pulsing .......................................................... 109
Chapter 12 Logging .................................................................... 115
Chapter 13 Power Quality (ION7350 only) .................................. 125Chapter 14 Meter Resets ............................................................. 129
Chapter 15 Alerting (ION7350 only) ........................................... 133
Chapter 16 Setpoints (ION7330 and ION7350) ........................... 139
Chapter 17 Reporting ................................................................. 143
-
8/12/2019 ION Meter-70002-0162-03
8/152
-
8/12/2019 ION Meter-70002-0162-03
9/152
2007 Schneider Electric. All rights reserved. Page 9
1 Introduction
ThismanualexplainshowtouseallPowerLogicION7300seriesmeters.Throughoutthemanual,thetermmetergenerallyreferstoallmetermodels:ION7300,ION7330andION7350.Alldifferencesbetweenthemodels,suchasafeaturespecifictoonemodel,areindicatedwiththeappropriatemodelnumber.
Beforeusingthisguide,yourmetershouldbeinstalled,mostbasicsetupshouldhavebeenperformed,andcommunications/basicoperationshouldhavebeenverified.
Iftheunitisnotyetinstalledandoperational,refertotheInstallationGuideshippedwiththemeter.
ThischapterprovidesanoverviewofION7300seriesmeters,andsummarizesmanyoftheirkeyfeatures.
In This Chapter
ION7300 Series Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
The ION Meter in an Enterprise Energy Management System . . . . . . . . . . . 12
Meter Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14MeasuredParameters ................................................. 14
DataDisplayandAnalysisTools ....................................... 16
SupportedProtocols .................................................. 17
CommunicationsOptions.............................................. 17
DigitalandAnalogI/OOptions......................................... 17
IONEnterpriseSoftwareSupport ....................................... 18
IONSetupSoftwareSupport ........................................... 20
Getting More Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
-
8/12/2019 ION Meter-70002-0162-03
10/152
-
8/12/2019 ION Meter-70002-0162-03
11/152
ION7300 Series User Guide Chapter 1 - Introduction
2007 Schneider Electric. All rights reserved. Page 11
IONEnterpriseisapowerfulwebreadysoftwaresuitethatcanprocess,analyze,store,andshareinformationfromacrossyourentireorganization.Itscompatibilityandflexibilitymeansyoucanintroduceindividualcomponents,atapaceyoudecide,whilemaintainingyouroriginalinvestments.Youcanaccessinformationandalarmsfromanyworkstation,pager,PDA,orcellphonelocallyoraroundtheworld,intheformatyourequire.Youcanalsoperformcoordinated
load
and
equipment
control
functions,
either
manually
or
automatically.
ION
softwarecollectsdataautomaticallyfromIONmetersandthirdpartydevices,soyoucanmanageasinglesiteoraglobalnetworkofdevices.IONsoftwareandhardwareproductsreducecostofinstallationandownershipbyleverageexistingcorporatenetworksandpopularnetworkingtechnologies,includingserial,wireless,modem,EthernetandInternetlinks.
AwideselectionofIONintelligentmeteringandcontroldevicesareavailable,withchoicestomeetthespecificneedsofvariouskeypointswithinanenterprise.Devicesofferarangeofhighaccuracymetering,powerqualityandreliabilityanalysis,dataandeventlogging,alarming,controlandcommunications.
TheION7300seriesmeterscanbeusedeffectivelyinnumeroussupplysideand
demandside
operations.
Some
common
meter
applications
are:
RevenueMetering
SubstationAutomation
ReplacementofAnalogTransducers
Commercial/IndustrialMetering
DemandMonitoring
GensetApplications
UniversalMetering(ION7330andION7350)
UtilitySubMetering(ION7330andION7350)
Thesearejustafewofthemanypossibilities.ContactSchneiderElectricTechnicalSupportifyouwouldlikeassistancewithyourapplication.
-
8/12/2019 ION Meter-70002-0162-03
12/152
Chapter 1 - Introduction ION7300 Series User Guide
Page 12 2007 Schneider Electric. All rights reserved.
The ION Meter in an Enterprise Energy Management SystemApplicationsthatincludethemetertypicallyrequireadditionalequipment.Displayandanalysissoftwaretoolsarealmostalwaysusedtomanage,interpretanddistributethedatameasuredorloggedbyameter.Thereareusuallyavarietyoftoolsused,andoftenthesetoolsareconnectedusingdifferentcommunications
standardsand
protocols.
In
many
cases,
ameter
must
also
provide
control
capabilitiesanddeviceleveldatasharing.
Themetercanadapttomanysituations.Advancedcommunicationsallowdatatobesharedsimultaneouslyacrossmultiplenetworks,builtinI/Oprovidesmonitoringandcontrolcapabilities,andavarietyofdisplayandanalysistoolscan
beusedtomonitoryourpowersystem.
Power System ConnectionsPhase voltage and phase current
from Wye, Delta or single-phasepower systems.
I / O- Energy Pulses
- Breaker Closures- Digital Signals- Analog Transducers
Protocols- ION
- Modbus RTU- DNP V3.00- Profibus (ION7300)
Communications- RS-485
- Optical Infrared- 10 Base-T Ethernet- 33.6 kbps internal modem- Profibus port (ION7300)
Data Analysis Tools- ION Enterprise Software- 3rd-Party tools
On-Site Data Display- Front Panel Display- Remote Data Display (RMD)- Vista- WebReach
Corporate Network
Internet Connectivity- MeterM@il
- WebMeter
-
8/12/2019 ION Meter-70002-0162-03
13/152
ION7300 Series User Guide Chapter 1 - Introduction
2007 Schneider Electric. All rights reserved. Page 13
Power System ConnectionsPhase voltage and phase currentfrom Wye, Delta or single-phasepower systems.
I / O- Energy Pulses- Breaker Closures- Digital Signals- Analog Transducers
Protocols- ION- Modbus RTU- DNP V3.00- Profibus (ION7300)
Communications- RS-485- Optical Infrared- 10 Base-T Ethernet- 33.6 kbps internal modem- Profibus port (ION7300)
Data Analysis Tools- ION Enterprise Software- 3rd-Party tools
On-Site Data Display- Remote Modular DisplayRemote Data Display- Vista- WebReach
Corporate Network
Internet Connectivity- MeterM@il- WebMeter
-
8/12/2019 ION Meter-70002-0162-03
14/152
Chapter 1 - Introduction ION7300 Series User Guide
Page 14 2007 Schneider Electric. All rights reserved.
Meter FeaturesYourmeterincludesanimpressivearrayofstandardfeatures.Seebelowforanoverview.
Measured ParametersION7300seriesmetersprovidefullybidirectional,4quadrant,revenueaccurateorrevenuecertifiedenergymetering.Thefollowingisaselectionofsomeparametersmeasuredbythesemeters.
EnergyThemetersprovideallcommonactive,reactiveandapparentenergyparameters.
kWh,imported,exported,net(importedandexported),andtotal(importedandexported)
kVARhimported,exported,net(importedandexported),andtotal(importedandexported)
kVAhtotal
kVAh,imported,exported,net(ION7330andION7350metersonly)
Volthoursandamphours
Integrationofanyinstantaneousmeasurement
Allenergyparametersrepresentthetotalforallthreephases.EnergyreadingsaretrueRMSandareupdatedapproximatelyonceeachsecond.Maximumrangeofenergyreadingsis999,999,999.Beyondthisvalue,readingsrollovertozero(0).
DemandION7300seriesmeterssupportrollingblock,thermal,andpredicteddemand.Themeterscalculatedemandonanyinstantaneousmeasurementandrecordpeak(maximum)andminimumdemand.
Defaultsetup:
kWdemandandmin/max
kVARdemandandmin/max
kVAdemandandmin/max
Ampsdemandandmin/max
Voltsdemandandmin/max
Demandonanyinstantaneousmeasurement
-
8/12/2019 ION Meter-70002-0162-03
15/152
ION7300 Series User Guide Chapter 1 - Introduction
2007 Schneider Electric. All rights reserved. Page 15
Real-timeION7300seriesmetersofferacomprehensivearrayofinstantaneous(realtime)measurements.MeasurementsincludetrueRMS,perphaseandtotalfor:
Voltageandcurrent
kW,kVARandkVA
Powerfactor
Frequency
Voltageandcurrentunbalance
HarmonicsION7300seriesmetersfeatureharmonicdistortionmetering.
TotalHarmonicDistortionandindividualharmonicstothe15th,(31stfortheION7350meter)onvoltageandcurrentinputs
Kfactorforcurrentinputs
Min/Max RecordingThemetersrecordeachnewminimumandnewmaximumvaluewithdateandtimestampforthefollowingparameters:
Voltageandcurrentmin/max
kW,kVAR,andkVAmin/max
Powerfactor
Frequency
Voltage
unbalance Plusanymeasuredvalue
Residual Current Calculation (I4)ThePowerMetermoduleprovidesanoutputregisterlabeledI4whichholdstheresidualcurrentvalue,derivedfromthethreephasecurrentmeasurements.Assuch,I4representsthegroundfaultcurrent,orthecurrentflowintheneutralorgroundconductor.
NOTE
This quantity is only available when the meter's Volts Modeis set to 4-WIREWYE. If the Power Meter module
is set to any other Volts Mode, the I4 output will read NOTAVAILABLE.
-
8/12/2019 ION Meter-70002-0162-03
16/152
Chapter 1 - Introduction ION7300 Series User Guide
Page 16 2007 Schneider Electric. All rights reserved.
Data Display and Analysis ToolsDisplayandanalyzemeterdatawithawidevarietyoftools.
The Front Panel
Usethemetersfrontpanelinterfaceforlocalmonitoringandstandaloneapplications.ThebrightLCDdisplayletsyouviewrealtimevaluesandperformdeviceconfiguration.
NOTE
TRAN (transducer) model meters do not have a front panel.
The Remote Modular DisplayTheRemoteModularDisplay(RMD)canbeaddedtoanexistingION7300seriesTRANmodeltofacilitatelocalmonitoringandstandaloneapplications.TheION7300seriesBasicModelprovidesanintegratedfrontpaneldisplay.
BoththefrontpanelandRMD,whenusedincombinationwithIONsoftware,provideaninterfaceforfieldpersonnel.
WebMeterEmbedded Web Server FeatureEthernetmetersincludeWebMeterfunctionality;anonboardwebserverthatprovidesquickandeasyaccesstorealtimeenergyandbasicpowerqualityinformationwithoutspecialsoftware.Thebuiltinwebpagesdisplayarangeofenergyandbasicpowerqualityinformationthroughthewebenableddevice,andevensupportbasicmeterconfigurationtasks.
MeterM@il Internal E-Mail Client FeatureWithMeterM@il,youcanconfigurethemetertoautomaticallyemailhighpriorityalarmnotificationsorscheduledsystemstatusupdatemessagestoanyone,anywherewithinthefacilityoraroundtheworld.Specifythetypeofeventthattriggersanemailalert,suchaspowerqualitydisturbancesorloggeddataatanypredeterminedinterval,andhaveyourIONsoftwareadministratorprogramthemetertorespondwithaMeterM@ilmessagewhentheseeventsoccur.MeterM@ilmessagesarereceivedlikeanyemailmessageoveraworkstation,cellphone,pager,orPDA.
XML CompatibilityYourmetercanexchangeinformationusingindustrystandardXMLformat.Thissimplemachinereadableformatsupportseasyintegrationwithcustomreporting,spreadsheet,database,andotherapplications.
-
8/12/2019 ION Meter-70002-0162-03
17/152
ION7300 Series User Guide Chapter 1 - Introduction
2007 Schneider Electric. All rights reserved. Page 17
Supported ProtocolsYoucanintegratethemeterintovariousindustrystandardnetworks.Meterdatacanbemadeavailabletootherdevicesusingthefollowingprotocols:
ION
ModbusRTU
DNP3.0(ION7330andION7350)
MV90translationsystem(ION7330andION7350).
Profibus(optionalforION7300)
Youcanalsoconfigurethemetertoimportdatafromotherdevicesonthesenetworks.Withtheseadvancedcommunicationsfunctions,thepowerofthemetercanbeutilizedinmostexistingpowermonitoringsystems.AnydatadisplayandanalysissoftwarethatworkswithModbusRTUorDNP3.0devicesalsofunctionswiththemeter.
Communications OptionsThestandardmeterhasoneinfraredportandoneortwoRS485communicationsports(theION7300hasone,theION7330andION7350havetwo).Theseportsarecapableofdataratesupto19,200bps.TheinfraredportonthefrontpaneliscompatiblewithanANSIC12.13TypeIImagneticopticalcommunicationscoupler.ItcanbeusedtocommunicaterealtimemeasurementsviaION,Modbus,orDNPprotocols.TheRS485andinfraredportscancommunicatesimultaneously.Orderingoptionscanincludea10BaseTEthernetport,a33.6kbpsinternalmodem,andaProfibusport,dependingonthemodeltypeofyourION7300seriesmeter.
Digital and Analog I/O OptionsTheION7300seriesmeteroffersavarietyofanaloganddigitalI/Ocombinations.I/Oconnectionstothemeteraremadeviacapturedwireterminalsonthebackofthemeter.TheanalogI/OoptioncanbespecifiedforanyION7300seriesmeter,allowingyoutomonitorawiderangeofconditions,suchasflowrates,devicecycles(RPM),fuellevels,oilpressuresandtransformertemperatures.YoucanoutputenergypulsestoanRTUorperformequipmentcontroloperations.
Digital Outputs
AllION7300seriesmetershavefourprogrammabledigitaloutputports.Thesearesuitableforpulsingorcontrollingrelays.TheInfraredDataPortand/orarearpanelLEDcanalsobeusedforenergypulsing.
Status InputsFouropticallyisolateddigitalinputsontheION7330andION7350meterscanmonitorstatus,counttransducerpulses,breakertripsandpulsesfromanyexternalvoltsfreedrycontact.
-
8/12/2019 ION Meter-70002-0162-03
18/152
Chapter 1 - Introduction ION7300 Series User Guide
Page 18 2007 Schneider Electric. All rights reserved.
Analog Inputs/OutputsAnymeterintheION7300seriescanbeequippedwithanoptionalanalogI/Ocardfeaturing:
4analoginputsaccepting01mAor020mA,(scalableto420mA)
4analogoutputsaccepting01mAor020mA,(scalableto420mA)
NOTE
When equipped with analog I/O, TRAN base units cannot be ordered with a remote display (RMD).
REB OptionAddingtheRelayExpansionBoard(REB)optioncanenhancethefunctionalityoftheonboarddigitaloutputs.TheREBoptionincludesafourpositionGrayhillmodulerackanda100240VACto5VDCpowersupply.Grayhillmodulesareorderedseparately.
ION Enterprise Software SupportThecompleteIONEnterprisesoftwarepackageintegratesthemeterintoafullynetworkedinformationsystemwithothermetersandlocalandwideareacomputernetworks.IONEnterpriseisrecommendedforallpowermonitoringsystemswhereadvancedanalysisandcontrolcapabilitiesarerequired.
IONEnterpriseprovidestoolsformanagingyourpowermonitoringnetwork,loggingdata,analyzingrealtimeandloggeddata,generatingpowersystemreports,andcreatingcustomfunctionalityatthemeterlevel.
VistaVistapresentsagraphicalviewofyourpowersystem,allowingyoutoviewandanalyzerealtimedatafrompowermetersandhistoricaldatafromtheIONdatabase.Vistareportsonthestatusofyoursystemcomponents,informingyouofalarmconditionsandprovidingyouwithcontrolcapabilitiesforinitiatingintelligentdevicefunctionsoractuatingfieldmachinery.Vistaincludessophisticatedtoolsforanalyzingrealtimeandloggedpowerdataandsystemevents.
Formoreinformation,refertotheVistasectionintheonlineIONEnterpriseHelp.
WebReachTheWebReachcomponentofIONEnterpriseaddsthinclientsupportfunctionalitytotheIONEnterprisesoftware.WiththeWebReachfeatureyoucanusethewebbrowserfromanymachineonyournetworktoviewtheVistadiagramsofallthemetersonyournetwork,regardlessofwhethertheyarelocatedlocallyoracrossthecountry.YoucancreatecustomscreensinVistafordisplayinyourwebbrowser,includingrealtimenumericdata,backgroundgraphicsordiagrams,andbasicviewsofevent,dataandwaveformlogs.
-
8/12/2019 ION Meter-70002-0162-03
19/152
ION7300 Series User Guide Chapter 1 - Introduction
2007 Schneider Electric. All rights reserved. Page 19
ReporterReporterletsyoudefineandcreatecomprehensivedatabasereportsusingMicrosoftExcel.ConfiguredPowerQuality,LoadProfile,andEnergyandDemandreportsareincludedwithReporter.
Formoreinformation,refertotheReportersectionintheonlineIONEnterpriseHelp.Management ConsoleManagementConsoleisusedtobuildyourIONEnterprisepowermonitoringnetworktoreflectthewaythephysicalcommunicationsnetworkiswired,soIONEnterprisesoftwarecancommunicatewithyourdevices.Thenetworkiscreatedusingsites,servers,modems,andintelligentdevicesthatcanbeadded,removed,configured,orduplicated.
YoucanaccessthefollowingtoolsfromtheManagementConsolemenus:
DiagnosticsVieweristheprimarysourceoftroubleshootinginformationinIONEnterprise.
DeviceUpgraderletsyouupgradetheoperatingsoftwareinsideanIONmeter. RemoteModemSetupletsyousetupmodemsforremotesites. DatabaseManagerletsyoumanageyourIONEnterprisedatabaseswithboth
manualtasksandscheduledtasks.
UserManagerletsyouconfigureIONEnterprisesoftwareuseraccountsthatdefinedifferentoperationspermittedwithintheIONsoftware,suchasviewingmeterdata,performingcontrolactions,orconfiguringthemeters.
LicenseManagerletsyouupgradethenumberofdevicesyoucanhavewithoutreinstallingthesoftware.
Formoreinformation,refertotheManagementConsolesectionintheonlineIONEnterpriseHelp.DesignerDesignerletsyoucustomizetheoperationofhardwarenodes,suchasIONmeters,andsoftwarenodes,suchastheVirtualProcessor,theLogInserter,andtheQueryServer.DesignerusesaWYSIWYGgraphicaluserinterfacetopictoriallyrepresentanodesconfiguration(i.e.,howthedifferentIONmodulesarelinkedtogetherinaframework).InadditiontogivingyoutheabilitytochangethesettingsofanyIONmodule,Designeralsoletsyouchangeexistinglinksbetweenmodules,add
newlinks,
add
new
modules
or
delete
modules.
Designer
helps
you
visualize
the
logicwhenyouareprogrammingcustomfunctionalityinanIONdevice.
Formoreinformation,refertotheDesignersectionintheonlineIONEnterpriseHelp.
-
8/12/2019 ION Meter-70002-0162-03
20/152
-
8/12/2019 ION Meter-70002-0162-03
21/152
2007 Schneider Electric. All rights reserved. Page 21
2 Front Panel
Themetersfrontpanelisusedforbothdisplayandconfigurationpurposes.Theliquidcrystaldisplay(LCD)screenandtheselection,navigation,andconfigurationbuttonsallowquickaccesstobasicmeterconfigurationprovidedbyspecialsetupscreens.ComprehensivemeterconfigurationisalsoaccessibleviatheAdvancedsetupmenus.
Thischapterprovidesinformationaboutthemetersfrontpanel,includinginstructionsforusingthesetupmenusandfordisplayingmetervalues.
In This Chapter
Displaying Data with the Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22FrontPanelDisplayResolution ......................................... 23
DisplayScreenTypes ................................................. 24
DefaultFrontPanelDisplayScreens..................................... 24
Configuring the Meter with the Front Panel . . . . . . . . . . . . . . . . . . . . . . . . 25TheFrontPanelsMainSetupMenu..................................... 26
AdvancedMeterSetupMenu .......................................... 26
DisplaySetupMenu .................................................. 27
ScreenSetupMenu ................................................... 28
NameplateInfo
Menu
.................................................29
DiagnosticMenu ..................................................... 29
Display Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32DisplayOptionsModuleSettings ....................................... 32
DisplayModuleSettings............................................... 32
Custom Front Panel Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34BeforeCustomizingtheFrontPanel ..................................... 34
DisplayFrameworkOverview.......................................... 34
ChangingDefaultDisplayFrameworks .................................. 35
RemovingaDisplayScreen ............................................ 36
ChangingDisplayedParametersinanExistingScreen ..................... 36
-
8/12/2019 ION Meter-70002-0162-03
22/152
Chapter 2 - Front Panel ION7300 Series User Guide
Page 22 2007 Schneider Electric. All rights reserved.
Displaying Data with the Front PanelThefrontpanelprovidesadetailedgraphicsandtextdisplayforthemeter.Thefrontpanelisconfiguredatthefactorywitheightdisplaysshowingsomeofthemorecommonlyusedpowersystemvaluesmeasuredbythedevice(refertoDefaultFrontPanelDisplayScreens).
NOTE
A Remote Modular Display (RMD) can be added to an existing TRAN meter to provide a front panel
display.
Themetersdisplayshowsnumericdatascreens,eventlogs,phasordiagrams,bargraphs,andharmonicshistograms.
Using the Front Panel Buttons to Display DataPresstheUpandDownarrowbuttonstoscrollthroughthedatadisplayscreens.Youdonotrequirepasswordauthorizationtoviewthesescreens.TheRound
button,whenpressed,providesaccesstotheSetupmenu.Usethefrontpanelsthreebuttonstonavigatethismenu,andentersettingsintothemeter.
Measurements aredisplayed here.
Press the Round button toaccess the Setup menu ormake a selection.
Use the arrow buttonsto scroll through datadisplay screens.
Optical (Infrared)port
-
8/12/2019 ION Meter-70002-0162-03
23/152
ION7300 Series User Guide Chapter 2 - Front Panel
2007 Schneider Electric. All rights reserved. Page 23
Front Panel Display ResolutionWhendisplayingnumericvalues,thefrontpaneldisplayscreencanshowuptoninedigitsofresolution.Thisninedigitresolutionisavailablewhenthedisplayscreenissettodisplayoneparameter.Anymultiparameterscreendisplaysuptofivedigitsofresolution.
Ifyourequiremoredigitresolutionthanisavailable,useIONsoftwaretodisplaydata.Ifavalueistoolargetobedisplayedonyourdisplayscreen(i.e.greaterthan99,999onatwoparameterscreen),thefrontpanelusesanabbreviatedengineeringnotationwithstandardmetricprefixestoindicatethemagnitudeofthereading.Thefollowingtableprovidessomeexamples:
Numericvaluesaredisplayedinbaseunits;voltagesaredisplayedinvolts,whilecurrentisdisplayedinamps.Thefollowingvalues,however,aredisplayedinkilounitsratherthanbaseunitssincekiloisthemostfrequentlyusedvaluerange:
kW
kVA
kVAR
Whenviewingtheseparameterswiththefrontpanel,rememberthatthevaluesare
already
multiplied
by
1000.
For
example,
the
reading
below
indicates120,000kilowatts,not120,000watts.
INVLD and N/A Messages
Ifthefrontpanelisunabletoreadanumericorstatusvaluefromthemeter,itwilldisplayeitherINVLDorN/Ainplaceofthevalue.INVLDindicatesthatthevaluereceivedcannotbedisplayedbecauseitistoolarge(above9G999).N/Aappearsiftheregisterisnotavailable
Front Panel Display Value
124K0 124,000
124M0 124,000,000
1G240 1, 240, 000, 000
kW total 120K0
-
8/12/2019 ION Meter-70002-0162-03
24/152
Chapter 2 - Front Panel ION7300 Series User Guide
Page 24 2007 Schneider Electric. All rights reserved.
Display Screen TypesThemetersfrontpaneldisplaysmeasurements,configurablesettings,andcurrentconfigurationdatainvariousforms.Thesedatadisplayscreensaredescribed
below.
Default Front Panel Display ScreensThemeterseightdefaultdatadisplaysareasfollows:
NOTE
Your default data display screens will differ if the meter is in Fixed mode, or if your meter has custom
displays.
Display 1 (kWh net)Net Energy
Display 5 (Power)Total Power (true, reactive,and apparent), Power Factor.
Display 2 (kWh swd / mx)Present Interval and MaximumSliding Window Demand
Display 6 (Frequency)Frequency
Display 3 (Volts)Per-phase and average
line-to-line voltage
Display 7 (V-THD)Per-phase Voltage
Total Harmonic Distortion
Display 4 (Amps)Per-phase andaverage current
Display 8 (I-THD)Per-phase CurrentTotal Harmonic Distortion
-
8/12/2019 ION Meter-70002-0162-03
25/152
ION7300 Series User Guide Chapter 2 - Front Panel
2007 Schneider Electric. All rights reserved. Page 25
Configuring the Meter with the Front PanelThefrontpanelallowsyoutosetupandconfigurethemeteratitsinstalledlocation.WhenyouchangeasettinginthefrontpanelsSetupmenu,youareactuallyalteringthesetupregistervalueofanIONmodule.
NOTE
ION module links cannot be added or deleted using the front panel.
YoucanalsousethefrontpanelsSetupmenutoquicklyresetcommoncumulativevalueslikekilowatthours.
Using the Front Panel Buttons for ConfigurationPresstheRoundbuttontwicetoaccesstheSetupmenus.Usethefrontpanelsthreebuttonstonavigatethesemenus,andentersettingsintothemeter.
Navigating MenusEachmenuhasatitledisplayedatthetopofthedisplayscreenandmenuitemsdisplayedbelowthetitle.Usethearrowbuttonstoscrollthroughthemenuitems.Toselectanitemthatishighlighted,presstheRoundbutton.Toreturntothepreviousscreen,selectRETURN.ReturntothedatadisplayscreensbyrepeatedlyselectingRETURN.
Editing RegistersToeditthevalueofaregister,navigatethroughtheregistersusingthearrowkeys
until
the
register
you
want
is
highlighted,
then
press
the
Round
button.
The
registerappearsinoneoftwoways:asanumber,orasanoptionselectedfromamenu.Onceyouhaveenteredthepassword(ifrequired),aYESorNOverificationscreenappearsshowingthenewvalueoftheregister.SelectYEStochangethevalueofthesetupregister;selectNOtoreturntothepreviousscreenwithoutchangingthevalue.
Numeric Registers
Usethearrowbuttonstochangethevalueofthedigitabovethe cursor.Changethepositionofthecursorbyholdingdownanarrowkeyforaboutonesecond.HoldingtheUparrowbuttonmovesthecursorleftoneposition,andholdingtheDownarrowbuttonmovesthecursorrightoneposition.Onceyouhavethevalueyouwant,presstheRoundbutton.
Enumerated Registers
Someregistersaredisplayedasamenuofoptions.Thecurrentvalueoftheregisterwillbedisplayedinthelistwithanasterix(*)oneithersideofit.Usethearrow
buttonstohighlightthesettingyouwant,andpresstheRoundbutton.
-
8/12/2019 ION Meter-70002-0162-03
26/152
Chapter 2 - Front Panel ION7300 Series User Guide
Page 26 2007 Schneider Electric. All rights reserved.
PasswordsAllconfigurationfunctionsinthefrontpanelarepasswordprotected.Thepasswordissetto0(zero)inthefactory.Thefrontpanelonlypromptsyouforthemeterpasswordbeforeyoumakeyourfirstconfigurationchange.SeetheSecuritychapterformoreinformationonpasswords.
Confirming Configuration ChangesAconfirmationscreenappearswheneveryouattempttochangethemeterssettingsthroughthefrontpanel.Thisallowsyoutoabortanunwantedconfigurationchange.Thefrontpanelalsoinformsyouwhenanentryisoutofrange.
Writing Errors
Iftheconfirmationscreendoesnotappearforavalidentry,orthedisplayreportsawritingerror,repeattheconfigurationchange.Iftheproblempersists,contactTechnicalSupport.
The Front Panels Main Setup MenuToaccessthefrontpanelsmainSetupmenu,presstheRoundbutton.TheSetupmenuappearslistingthemetersfrontpanelsetupoptions:
Advanced Meter Setup MenuTheAdvancedMeterSetupmenuprovidesaccesstothesetupregistersofeveryIONmoduleinthemeter.Toaccessthismenuscreen,selectADVMETERSETUPfromthemainSetupmenu.
Setup Option Description
Clear Functions
Resets Min/Max, Sliding Window Demand, Energy, Thermal Demand, PeakDemand Registers, Harmonics Min/Max, Status Counters, Manual WaveformCapture, and Disturbance Counts.See the Resets chapter for more information.
Quick SetupChanges settings in the Communications, Power Meter, and Sag/Swell modules.See the Communications, Basic Setup and Power Quality chapters for moreinformation.
Adv MeterSetup
Provides access to all the modules in the meter.
Display Setup Customizes the appearance of the display screen.
Screen Setup Customizes the style and values appearing on the display screens.
Nameplate Info Displays information about the device.
SecurityAllows you to modify your password.See the Security chapter for more information.
Diagnostics Screens to aid in troubleshooting.
-
8/12/2019 ION Meter-70002-0162-03
27/152
ION7300 Series User Guide Chapter 2 - Front Panel
2007 Schneider Electric. All rights reserved. Page 27
Followthisproceduretoaccessasetupregister:
1. FromtheFeatureManagerscreen,selectthemodulestype.
2. Selectthemoduleyouwanttoconfigurefromthelistofavailablemodules.
3. Fromthelistofthemodulessetupregisters,selecttheoneyouwantto
configure.4. Editthevalueoftheregister(seeEditingRegistersonpage 25).
Youmaybepromptedtoenteryourpassword.SelectYEStothenextprompttochangethevalueoftheregister.SelectNOifyouwanttoleavethescreenwithoutmakinganychanges.
RefertotheIONReferenceforcompletedetailsoneachsetupregistersfunction.
Display Setup Menu
SelectDISPLAY
SETUP
from
the
main
Setup
menu
to
access
these
settings:
Auto ScrollAutoScrollactivateseachoftheenableddisplayscreensinsequence.Bydefault,theAutoScrollisdisabled.Usethearrowbuttonstospecifythenumberofsecondsthateachscreenisdisplayedbeforeitflipstothenextdisplayscreen,thenpresstheRoundbuttontosetthevalue.AnyscreensthathavebeendisabledwillnotappearwhenAutoScrollisenabled.Setthenumericvaluetozero(thedefaultvalue)todisableautoscrolling.
ContrastTochangethecontrastofthefrontpanelsdisplay,selectCONTRAST.Pressanarrowbuttononce,andthedisplayscreenscontrastslowlychanges.Pressanarrowbuttontostoptheprocess.PresstheRoundbuttonwhenyouaresatisfiedwiththecontrastlevel.
NOTE
Contrast can be adjusted from any screen by holding down the Round button for more than ten seconds.
Release the Round button when the contrast is at a suitable level.
Display Setup Option Default Description
Auto Scroll 0 s (Disabled) Time between automatic display screen advance.
Backlight Time 1800 secondsTime before display screen backlight automaticallyturns off.
Display Update 4 s Period between data display refreshes.
Display Mode Programmable Custom or Factory configured display screen option.
Contrast mid The display screens contrast level.
-
8/12/2019 ION Meter-70002-0162-03
28/152
Chapter 2 - Front Panel ION7300 Series User Guide
Page 28 2007 Schneider Electric. All rights reserved.
Backlight TimeoutThissettingchangestheamountoftimethefrontpanelsbacklightstaysonwhenthefrontpanelisidle.Thebacklighthasalimitedlifespan;toprolongit,youshouldonlyhavebacklightingonwhenyouareactivelyusingthefrontpanel.SelectBACKLIGHTTIMEOUT,thenusethefrontpanelsbuttonstochangetheamountoftimeinsecondsthatthebacklightstaysonafterabuttonispressed.
Display UpdateThedisplayupdatespecifieshowfrequentlydataonthedisplayscreenisrefreshed.Youmayfindthevaluesarebeingupdatedtoofrequently,orthatthedatashownonscreenlagstoofarbehindtheactualvalues.Thedefaultupdaterateisfourseconds;usethefrontpanelsbuttonstochangetheupdateratetosuityourneeds.
Display ModeTherearetwodisplaymodes:PROGRAMMABLEMODEandFIXEDMODE.Thedefaultisprogrammablemode,whichprovideseightdatadisplayscreenswhichcanbeconfiguredtomeetyourrequirements(seeCustomFrontPanelDisplays).FixedModedisplaysfourscreens,eachwithlargecharactersinthedisplay,easilyvisiblefromadistance.ThefourfixedmodescreensdisplayAverageVolts,AverageAmps,kWtotal,andPFtotal.Youcannotcustomizethefixedmodedisplays.
Screen Setup MenuTheSCREENSETUPmenuscreenallowsyoutochangethedatadisplayedontheeightdisplayscreens.FromtheSELECTSETUPmenu,selectSCREENSETUP.Thelistofdisplaytitlesappearthatcorrespondtoeachoftheeightdisplayscreens(see
DefaultFrontPanelDisplayScreens).Thescreennumberwithanasterix(*)besideitindicatestheactivedisplay(thescreendisplayedbeforeyouenteredSELECTSETUP).Selectthescreenyouwanttochange,andpresstheRoundbutton.Twosettingsappear,VALUESandSTYLE,thatallowyoutospecifywhichmeasurementstodisplay.
StyleTheSTYLEsettingdefinesthenumberofparametersoneachscreen.Thissettinghasfiveoptionsforeachdisplayscreen:ONEPARAMETER,TWOPARAMETER,THREEPARAMETER,FOURPARAMETER,andDISABLED.Selectthenumberofvaluesyouwanttodisplay(thefewervaluesyouselectfordisplay,thelargerthe
measurement
will
appear
on
the
display
screen).
Ifyouselectalargestyle(forexample,oneparameter)foradisplayscreenthatisalreadysettodisplaymorethanonevalue,thefrontpanelwarnsyouwithamessage,anddisplaysonlythefirstvaluethelinkstoallsubsequentvaluesareseveredandhavetobereprogrammed.
Style = One Parameter
Style = Four Parameter
-
8/12/2019 ION Meter-70002-0162-03
29/152
ION7300 Series User Guide Chapter 2 - Front Panel
2007 Schneider Electric. All rights reserved. Page 29
ValuesTheVALUESsettingspecifieswhichofthedevicesmeasurementsaredisplayedoneachdisplayscreen.Whenyouchangethevaluedisplayedonascreen,youarepresentedwithacompletelistofthemetersmeasurements.Usingthelistsofmodulesprovided,selectthevaluesyouwanttohavedisplayedonthatdisplayscreen.
ThenumberofVALUESyoucanselectisafunctionoftheSTYLEsetting.Youcannotselectmorevaluesthanthestyleissettodisplay.
Nameplate Info MenuSelectNAMEPLATEINFOtodisplayinformationaboutthevariousoptionsofthedevice,suchas:
Diagnostic MenuTheDIAGNOSTICmenuisaccessedfromtheSetupmenu;youcanviewperphasevoltageandcurrentharmonicsscreens,verifycommunications,verifythedigitalI/O,andcheckthemeterslocaltime.
Harmonics Diagnostics
SelectHARMONICSfromtheDiagnosticsmenutoviewperphasevoltageandcurrentharmonicstothe31stharmonic.Thefollowingisanexampleofaharmonicsdisplay:
PressandholdtheUpandDownbuttonstomovethecursortotheharmonicofinterest.Thepercentageofthefundamentalisalsodisplayed.
manufacturer
metertypeandclass
servicetype
voltageandcurrentinputratings
auxiliarypower
operatingfrequency
transformerratios
meterfirmwarerevision
digitaloutputinformation
approvals
serialnumber
accuracyrating
acceptableoperatingtemperature
batterylife
configureddemandsettings
threecustomtextlineswrittenintothemetersFactorymodule
-
8/12/2019 ION Meter-70002-0162-03
30/152
Chapter 2 - Front Panel ION7300 Series User Guide
Page 30 2007 Schneider Electric. All rights reserved.
Communications Diagnostics
TheCommunicationsdiagnosticscreendiffersdependingonyourmeterscommunicationsoptions.
TheRS485diagnosticscreenshowsthreeboxeslabelledCOM1,COM2(orETHifthemeterhastheoptionalEthernetcard)andCOM3.Thefollowingscreenis
anexample
of
Ethernet
(COM2)
communication:
COM1andCOM2refertothecommunicationsportsonthebackpanelofthemeter.AsthereareisnoCOM2portontheION7300meter,theCOM2boxneverappearsactive.TheCOM3boxverifiescommunicationthroughtheInfraredportonthefrontpanel(IR1).
TheEthernetdiagnosticscreendisplaystextsimilartowhatyouseeinthetablebelow eachlabelappearswithavaluenexttoit.Thetablebelowexplainsthemeaningofeachpossiblevalue.
TheEthernetConnectiondiagnosticscreendisplaystextsimilartowhatyouseeinthetablebelow eachlabelappearswithavaluenexttoit.Thetablebelowexplainsthemeaningofeachpossiblevalue.
Label Possible Values Description
ETH73 Version see description Displays the Ethernet meters firmware version (e.g. v270)
ETH73 in UPG YES, NO YES means the meter is currently being upgraded
ETH73 Setup N/A, RecdN/A means the Setup/options on the meter have not beentransmittedRecd means the Setup/options have been received
EtherGate YES, NOYES means EtherGate is supported (ION7330 andION7350)NO means EtherGate is not supported (ION7300)
Label Possible Values Description
# Power Ups see descriptionDisplays the number of times the Ethernet card has powercycled
ConnectionN/A, ION,Modbus
The type of Ethernet connection: N/A indicates no connection
ION indicates ION over Ethernet
Modbus indicates either Modbus RTU over Ethernet orModbus TCP
# WEB Reqs see description Displays the number of received WEB Page requests
# MeterM@il see descript ion Displays the number MeterM@ils sent
-
8/12/2019 ION Meter-70002-0162-03
31/152
ION7300 Series User Guide Chapter 2 - Front Panel
2007 Schneider Electric. All rights reserved. Page 31
I/O Diagnostics
TheI/Odiagnosticsmodeverifiestheoperationofthedigitalinputs/outputsyoumayhaveconnectedtothedeviceand,ifyouorderedtheanalogI/Ooption,allowsyoutomonitortheAnalogInputorAnalogOutputportsonyourmeter.Thefollowingdiagnosticscreensareavailable:
DigitalInsThisscreendisplaysthefourdigitalinputvaluesasseenatthelowlevel.
DigitalOutsThisscreendisplaysthefourdigitalinputvaluesasseenatthelowlevel.
AnalogInsThisscreendisplaysthefouranaloginputvaluesasseenateachAnalogInputmodulesoutputregister.
AnalogOutsThisscreendisplaysthefouranalogoutputvaluesasseenateachAnalogOutputmodulesoutputregister.
Troubleshooting Diagnostics
Therearethreetroubleshootingdiagnosticscreensavailable:
kiloWattsThisscreenshowsperphaseandtotalkilowatts.
VoltsThisscreensshowslinetoneutralandaveragevolts.
PowerFactorThisscreenshowssignedperphaseandtotalpowerfactor.
Date/Time Screen
FortheION7330andION7350meters,thisscreendisplaysthetimeanddatefromthedevicesinternalclock.
FortheION7300meter,thisscreendisplaysthedateandtimesentviaatimesync.TheION7300meterdoesnotincrementitsinternalclockwhilethemeterispowereddown.
-
8/12/2019 ION Meter-70002-0162-03
32/152
Chapter 2 - Front Panel ION7300 Series User Guide
Page 32 2007 Schneider Electric. All rights reserved.
Display SetupThemetersfrontpaneldisplayiscontrolledbytwotypesofIONmodules:theDisplayOptionsmoduleandtheDisplaymodule.UseDesignersoftwaretoconfigureyourdisplays.
Formoreinformationaboutthesemodules,seetheIONReference.
Display Options Module SettingsTheDisplayOptionsmoduleisacoremodulethatcannotbedeleted,copied,orlinked.SettingsintheDisplayOptionsmoduleareglobalandaffecttheentiresetoffrontpaneldisplayscreens.
Display Module SettingsADisplaymodulecontrolswhichvaluesaredisplayedonadisplayscreen,andhowthesevaluesarepresented.EachDisplaymodulecorrespondstoonemeterdisplayscreen.
TheDisplaymodulesSourceinputsarelinkedtothenumericparametersyouwanttodisplay.TheseparametersaresenttothefrontpanelwhentheDisplaymodulesShowinputispulsed.
Screen Type Register
TheScreenTypesetupregisterhasfiveoptions:ONEPARAMETER,TWOPARAMETER,THREEPARAMETER,FOURPARAMETER,andDISABLED.ThenumberofinputsfortheDisplaymoduleshouldmatchtheScreenTypesetupregister.IfyouselectaScreenTypewithmoreparametersthanarecurrentlylinkedtotheDisplaymodule,thedisplayscreenwillshowanyunavailableinputsasN/A.
Setup Register Function Default
Autoscroll Sets the time between automatic display scrolling (in seconds). Disabled
Backlight TimeoutSets how long the front panel display will stay bright after the last press of a frontpanel button (in seconds).
1800
Display Update Time Sets how frequently the screen data values will be updated (in seconds). 4
Display ModeSets whether the screens displayed on the front panel are programmable via Displaymodules or fixed.
Programmable
Setup Register Function Default
Screen TypeThis specifies the way the linked parameters are displayed on the front panelscreen.
Defaults vary among displayscreens.
-
8/12/2019 ION Meter-70002-0162-03
33/152
ION7300 Series User Guide Chapter 2 - Front Panel
2007 Schneider Electric. All rights reserved. Page 33
IfaScreenTypeisselectedwhichhasfewerparametersthanarelinkedtothemodule,theDisplaymodulewillonlydisplaythenumberofvaluesallowedbytheScreenType,andwillbreakanylinkstoparametersthatitcannotdisplay.
Forexample,ifyouhaveadisplayscreenwithfourparameters,andyouselectaScreenTypeofONEPARAMETER,thefirstparameterisdisplayedandtheother
three
links
to
the
Display
module
are
severed.
Changing the Parameters that are DisplayedThemetersdefaultdisplayconfigurationshowsacomprehensivesetofparameters.ChangingtheseparametersrequiresalteringthelinksbetweenvariousIONmodules.CompletedetailsonconfiguringthefrontpaneldisplaysareprovidedinthesectionCustomFrontPanelDisplays.
-
8/12/2019 ION Meter-70002-0162-03
34/152
Chapter 2 - Front Panel ION7300 Series User Guide
Page 34 2007 Schneider Electric. All rights reserved.
Custom Front Panel DisplaysCustomfrontpaneldisplayscanbecreatedtoshowanydatathemetermeasuresorcalculates.Eachdisplayscreencanbeconfiguredtodisplayanymeasurementsyourequire.Youcanalsoadjustthesizeofthecharactersineachscreensoyoucaneasilyreadthedevicesdisplayfromfartheraway.
Thereareonlyeightdisplayscreensavailableforconfiguration.Sincealleightofthefrontpanelsscreendisplaysareusedinthefactoryconfiguration,anexistingdisplaymustbechangedifyouwantacustomdisplay.RefertoDefaultFrontPanelDisplayScreensonpage 24fordetailsontheeightdefaultdisplayscreens.
Before Customizing the Front PanelInorderforthecustomizedscreenstobedisplayedinthefrontpanelsdisplay,themetersDisplayModemustbeproperlyset.EnsurethattheDisplayOptionsmodulesDisplayModesetupregisterissettoPROGRAMMABLE.Thisisthedefaultsetting.UsethemetersfrontpanelorIONsoftwaretosetthisregister.
Customizing Displays Using the Front PanelTheSCREENSETUPmenuscreenallowsyoutochangethedatadisplayedontheeightdisplayscreensusingthefrontpanel(seeScreenSetupMenuonpage 28).
Customizing Displays Using ION softwareThefrontpaneldisplaysoftheION7300seriesarecontrolledbytheDisplaymodulesandtheDisplayOptionsmodule.RefertotheIONReferencefordetaileddescriptionsofthesemodules.
LinkstoaDisplaymodulecanbemadeusingDesignerorthefrontpanel.EachDisplaymodulehasonesetupregister,ScreenType,whichsetsthenumberofparametersthatthedisplayscreenwillshow.
Display Framework OverviewThefollowingdiagramsillustratehowtheDisplayOptionsmoduleandDisplaymoduleworktogethertoprovideyourmetersfrontpanelwiththeappropriatedisplayscreens.
-
8/12/2019 ION Meter-70002-0162-03
35/152
ION7300 Series User Guide Chapter 2 - Front Panel
2007 Schneider Electric. All rights reserved. Page 35
Module Behavior
TheorderinwhichdatadisplaysdependsonthenumberingoftheDisplaymodules.Therefore,thedatalinkedtoDisplaymodule1isdisplayedonthefirstfrontpanelscreenandsoon.ScrollingbetweenthedisplayscreensisdonewiththeUp/Downarrowbuttonsonthefrontofthemeter.
Viewing all Display and Display Options modules at once
1. LaunchDesignerandopenyourmeter.
2. Doubleclick
the
Meter
Display
Setup
folder
in
the
main
meter
configuration
screen.ThelabelbelowthefolderreadsDisplayModules.
AllDisplaymodulesandashortcuttotheDisplayOptionsmoduleappear.
Changing Default Display FrameworksThreecommoncustomizationsarediscussedinthefollowingsections:
removingadisplayscreen
addinganewdisplayscreen
replacingtheparametersinanexistingdisplayscreen
Making a Framework BackupBeforeyoureconfigureordeleteaframework,youshouldmakeacopy.Thisensuresthatyoucanrestoretheframeworkwithouthavingtoreinitializethefactoryconfiguration.
There is anAutoScrollregister for the
ION7300series meter,though it isdisabled bydefault.
Display
Options
Module
Diagnostic
module
Power Meter
module
TotalLogMemory
FreeLogMemory
kW tot
kVAR tot
kVA tot
PF sign tot
kWh net
V unbalance
I unbalance
Display
Module 4
Display
Module 3
Display
Module 2
DisplayModule 1
Source 1
Source 2
Source 1
Source 2
Source 4
Source 1
Source 1
Source 2
Source 3
kW tot 187
kVAR tot 62
kVA tot 197
PF sign tot -94.9
kWh net
1475.35
Total Log Memory
300
Free Log Memory
300
V unbalance 0.96
I unbalance 0.97
-
8/12/2019 ION Meter-70002-0162-03
36/152
Chapter 2 - Front Panel ION7300 Series User Guide
Page 36 2007 Schneider Electric. All rights reserved.
Making a framework copy
1. Selectthedesiredframework.
2. ChooseCopytoFrameworkfromtheEditmenu.Givetheframeworkauniquename.Selectalocationinwhichtosavetheframework.
3. ClickOk.
Formoreinformationonreinitializingfactoryconfigurations,seeRestoringtheFactoryConfigurationinChapter3.
Removing a Display ScreenUsecautionwhendeletingmodules,asanydependantmodulesarealsoaffected.Designerinformsyouofdependantmodulesiftheyexistonthesamenode.
Removing a data display screen
1. LaunchDesigner.
2. SelecttheDisplaymoduleresponsibleforthescreen.
3. Pressdelete.ThisalsodeletesalllinkstothatparticularDisplaymodule.
Ifthedisplayscreenyouaredeletingispartoftheautomaticscrollingcycle,youshouldreconfigurethelinksfromtheScrollmodulesTriggeroutputstotheremainingDisplaymodulessothatthefollowingconsiderationsholdtrue:
ThefirstDisplaymoduleinthescrollingcycleislinkedtotheTrigger1outputoftheScrollmodule.
ThelastDisplaymoduleinthescrollingcycle(modulen)islinkedtotheTriggernoutputoftheScrollmodule.Forexample,ifyourscrollingcycleconsistsof5screens,
thenTrigger
5
should
be
linked
to
the
fifth
module
in
the
cycle. TheWraparoundsetupregisteroftheScrollmoduledesignatesthelasttrigger
output(Triggern).Expandingonthepreviousexample,sinceTrigger5isthelasttrigger,theScrollmodulesWraparoundsetupregisterwouldhaveavalueof5.
Changing Displayed Parameters in an Existing ScreenYoucanchangedisplayedparametersinexistingscreensusingDesignersoftware.
NOTE
You must set the Display Options modules Display Mode setup register to PROGRAMMABLE before
changing displayed parameters in an existing screen.
Tochangeparametersshowninadisplayscreen,linktheoutputregistercontainingthenumericdatayouwanttodisplaytotheSourceinputsoftheDisplaymodule.IfthereisnotafreeSourceinput,youwillhavetofirstdelete(i.e.,unlink)anexistinglinktoaSourceinput.
-
8/12/2019 ION Meter-70002-0162-03
37/152
ION7300 Series User Guide Chapter 2 - Front Panel
2007 Schneider Electric. All rights reserved. Page 37
Changing Displayed Parameters using the Meters FrontPanelYoucanalsochangethedisplayedparametersinanexistingscreenusingthemetersfrontpanel.
Before changing displayed parameters in an existing screenForcustomizedscreenstodisplayonthefrontpanel,youmustsettheDisplayOptionsmodulesDisplayModesetupregistertoPROGRAMMABLEbeforechangingdisplayedparametersinanexistingscreen.
Onthemetersfrontpanel,gotoDISPLAYSETUP>DISPLAYMODEandselectPROGRAMMABLE.
Changing displayed parameters in an existing screen
TheSCREENSETUPmenuscreenallowsyoutochangethedatadisplayedontheeightdisplayscreens.
1. Fromthe
SELECT
SETUP
menu,
select
SCREEN
SETUP.
The
list
of
display
titles
appearsthatcorrespondtoeachoftheeightdisplayscreens.Thescreennumberwithanasterix(*)besideitindicatestheactivedisplay(thescreendisplayedbeforeyouenteredSELECTSETUP).
2. Selectthescreenyouwanttochange,andpresstheRoundbutton.Twosettingsappear,VALUESandSTYLE,thatallowyoutospecifywhichmeasurementstodisplay.
3. SelectSTYLEifyouneedtochangethenumberofdisplayedparametersintheselectedscreen.
Thissettinghasfiveoptionsforeachdisplayscreen:ONEPARAMETER,TWOPARAMETER,THREEPARAMETER,FOURPARAMETER,andDISABLED.Selectthenumberofvaluesyouwanttodisplay(thefewerthevaluesyouselectfordisplay,thelargerthemeasurementwillappearonthedisplayscreen).
Ifyouselectalargestyle(forexample,onevalue)foradisplayscreenthatissettodisplaymorethanonevalue,thefrontpanelwillwarnyouwithamessage,andwilldisplayonlythefirstvaluethelinkstotheundisplayablevaluesareseveredandwillhavetobereprogrammed.
4. SelectVALUEStochangethedisplayedparameterintheselectedscreen.
Whenyouchangethevaluedisplayedonascreen,youarepresentedwithacompletelistofthemetersmeasurements.Usingthelistsofmodulesprovided,selectthevaluesyouwanttohavedisplayedonthatdisplayscreen.
ThenumberofVALUESyoucanselectisafunctionoftheSTYLEsetting.You
cannotselect
more
values
than
the
STYLE
is
set
to
display.
-
8/12/2019 ION Meter-70002-0162-03
38/152
Chapter 2 - Front Panel ION7300 Series User Guide
Page 38 2007 Schneider Electric. All rights reserved.
-
8/12/2019 ION Meter-70002-0162-03
39/152
2007 Schneider Electric. All rights reserved. Page 39
3 Templates, Frameworks and Firmware
Yourmetercomesinstalledwithapreconfigureddefaulttemplate.Thistemplatecontainsvariousframeworkswhichprovideallthepowermeasuringandanalyzingfunctionalityofthemeter.Templatesandframeworkscanbeusedimmediatelywithoutanyuserconfiguration(rightoutofthebox).Theycanalso
becustomized,reconfigured,andpastedfromonemetertoanother.
Formoreinformationontemplates,frameworksandIONmodules,seetheIONReference.
Yourmetersoperatingsystemisknownasfirmware.Whennewerfirmwareisavailableforyourmeter,simplyupgradetothelatestversionforalltheadded
featuresandfunctionality.
CAUTION
Early ION7300 series meters (Revision A) are not compatible with Revision B firmware, and vice versa.
See the Schneider Electric website for more information.
In This Chapter
Factory Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
FactoryModule
Settings
...........................................40
HowtoTAGYourMeter .............................................. 40
UsingIONSetup ................................................. 40
UsingDesigner ................................................... 41
Restoring the Factory Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42UsingDesigner ................................................... 42
UsingIONSetup ................................................. 43
Upgrading Your Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
-
8/12/2019 ION Meter-70002-0162-03
40/152
Chapter 3 - Templates, Frameworks and Firmware ION7300 Series User Guide
Page 40 2007 Schneider Electric. All rights reserved.
Factory InformationTheFactorymoduledisplaysfirmwareversion,serialnumberandotherdeviceinformationinreadonlysetupregisters(readonlyregisterscanbeviewedbutnotchanged).
Factory Module SettingsThedeviceinformationprovidedisasfollows::
TheFactorymodulealsocontainsnumerousreadonlysetupregistersthatholdthecalibrationconstantsusedatthefactory.
How to TAG Your MeterThreeconfigurablesetupregistersareprovidedforyoutoenteryourcompanynameandothertextinformationyouwantstoredinthemeter:
Owner Thisisatextregisterforstoringuserinformation(e.g.companyname);itcanbeupto255charactersinlength.
Tag1 Thisisatextregisterforstoringuserinformation(e.g.devicelocation);itcanbeupto15charactersinlength.
Tag2 Thisisatextregisterforstoringuserinformation(e.g.devicenumberoridentifier);itcanbeupto15charactersinlength.Ifthisfieldisnotleftblank,MV90requirestheirDeviceIDfieldtomatchthisfield.
Using ION Setup1. ConnecttoyourmeterinIONSetup,usingBasicMode.
2. NavigatetoSetupAssistant>BasicSetup
Setup Register Description
Device Type A device type ident ifier (7300 for the ION7300)
Compliance A statement of whether the device is ION compliant or not
Options Shows model number of meter
Revision The meters firmware version
Serial Num The meters serial number
ION Version The ION version supported by the device
Template The name of the factory default template (framework) installed on the device
Nom Freq The expected frequency of the power system being monitored
-
8/12/2019 ION Meter-70002-0162-03
41/152
ION7300 Series User Guide Chapter 3 - Templates, Frameworks and Firmware
2007 Schneider Electric. All rights reserved. Page 41
3. ClicktheNameplateInfotab.
4. Selectthe
register
you
want
to
configure
and
click
Edit.
Using DesignerOpenyourmeterinDesignerandnavigatetothemainConfigurationscreen.RightclickontheFactorymoduletoedit.
-
8/12/2019 ION Meter-70002-0162-03
42/152
-
8/12/2019 ION Meter-70002-0162-03
43/152
ION7300 Series User Guide Chapter 3 - Templates, Frameworks and Firmware
2007 Schneider Electric. All rights reserved. Page 43
10. ClickthePowerMetershortcutintheBasicConfigurationareatoselectit.Onceselected,clickResetintheDesignertoolbar,orselectResetfromtheEditmenu.ThisrevertsthePowerMetertothesettingsithadbeforeyoudeletedanymodules(retainingthebasicsetupyoupreviouslyhad).
11. ChooseSend&SavefromtheFilemenu.Thefactoryconfigurationisnowrestoredandanycustomfunctionalityyoucreatedbeforeisremoved.
NOTE
The time required to complete steps 3, 5, and 11 may vary depending on your connection and the meter
configuration.
Using ION Setup1. Downloadyourdeviceslatesttemplatefromhttp://www.powerlogic.com/
support/downloads/.Savethe.DCFfileinthe.../IONSetup/TEMPLATEfolderforeasyaccess.
2. ConnecttoyourmeterinIONSetup,usingBasicMode.
3. NavigatetoSetupAssistant>Template
4. ClicktheSendtoMetertabandclicktheSendbutton.
5. Selectthe.DCFfilefromtheTEMPLATEfolderandclickOK.
6. TheTemplatePasteOptionsscreenappears.Selectthecheckboxesforthesettingsyouwishtoretain(notoverwrite)andclickOK.
-
8/12/2019 ION Meter-70002-0162-03
44/152
Chapter 3 - Templates, Frameworks and Firmware ION7300 Series User Guide
Page 44 2007 Schneider Electric. All rights reserved.
IONSetuppastesthetemplateontoyourmeter.Adialogboxconfirmsthepastewassuccessful.
Upgrading Your MeterSeetheUpgradingIONDeviceFirmwaretechnicalnotefordetails.
-
8/12/2019 ION Meter-70002-0162-03
45/152
2007 Schneider Electric. All rights reserved. Page 45
4 Basic Setup
Thischapterexplainshowtoperformbasicmetersetup.
In This Chapter
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Configuring Basic Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46UsingtheFrontPanel ............................................. 46
UsingIONSetup ................................................. 47
UsingDesigner
...................................................47
PowerMeterModuleSettings .......................................... 48
-
8/12/2019 ION Meter-70002-0162-03
46/152
Chapter 4 - Basic Setup ION7300 Series User Guide
Page 46 2007 Schneider Electric. All rights reserved.
IntroductionBasicconfigurationofthemeterisprovidedbythePowerMetermodule.ThePowerMetermoduleisthemainconnectionbetweenthepowersystemmeasurementsandallotherIONmodulesinthedevice.Thismodulereportsthevaluesforallvoltage,currentandpowermeasurements.ThePowerMetermodulessetupregistersdescribedetailsofthepowersystembeingmonitored.ManyofthePowerMetermodulessetupregistersareconfiguredwhenthemeterisinitiallyputintoservice,althoughthedevicecannotoperateproperlyuntiltheVoltsModeandPTandCTratiosareset.Someregistersmayneedtobechangedtorefinethedevicesoperation.
SeetheIONReferenceformoredetailsonthePowerMetermodule.
Configuring Basic SetupUsethefrontpanelorIONsoftwaretoperformbasicmetersetup.
Using the Front PanelNavigatetoQuickSetup>PowerMetertoaccesstothefollowingpowersystemsettings:
Menu Setting Description Range (Values) Default
PowerMeter
Volts ModeThe power systems configuration WYE, DELTA, etc.
4W-WYEDELTASINGLEDEMO
3W-WYEDIRECT-DELTA
4W-WYE
PT1 (Primary)The Potential Transformersprimary winding voltage rating
1 to 999,999,999 347
PT2 (Secondary)The Potential Transformerssecondary winding voltage rating
1 to 999,999,999 347
CT1 (Primary)The Current Transformersprimary winding current rating
1 to 999,999,999 5
CT2 (Secondary)The Current Transformerssecondary winding current rating
1 to 999,999,999 5
V1 PolarityThe polarity of the PotentialTransformer on V1
Normal or Inverted Normal
V2 PolarityThe polarity of the PotentialTransformer on V2
Normal or Inverted Normal
V3 Polarity The polarity of the PotentialTransformer on V3
Normal or Inverted Normal
I1 PolarityThe polarity of the CurrentTransformer on I1
Normal or Inverted Normal
I2 PolarityThe polarity of the CurrentTransformer on I2
Normal or Inverted Normal
I3 PolarityThe polarity of the CurrentTransformer on I3
Normal or Inverted Normal
-
8/12/2019 ION Meter-70002-0162-03
47/152
ION7300 Series User Guide Chapter 4 - Basic Setup
2007 Schneider Electric. All rights reserved. Page 47
Using ION SetupTheBasicSetupAssistanthelpsyouconfigurethePowerMetermoduleandenergyrolloversettings.
1. OpenIONSetupandconnecttoyourmeter,usingBasicMode.
2. IntheSetupAssistant,navigatetoBasicSetupandclickonthePT/CTRatiostab.
3. ConfigureeachregisterasrequiredbyselectingtheparameterandclickingEdit.
4. ClicktheRollovertabtoconfigureEnergyRollover.Thisregisterdetermineshowmanyenergyvalues(forexample,kilowatts)accumulatebeforethenumberrollsovertozero.Thedefaultsettingistenmillion.
Using DesignerOpenyourmeterinDesignerandnavigatetotheBasicConfigurationFramework.RightclickonthePowerMetermoduletoedit.
-
8/12/2019 ION Meter-70002-0162-03
48/152
Chapter 4 - Basic Setup ION7300 Series User Guide
Page 48 2007 Schneider Electric. All rights reserved.
Power Meter Module SettingsThePowerMetermodulecontainsthefollowingsetupregisters:
Setup Register Function Default
Volts Mode The power systems configuration WYE, DELTA, Single, etc 4W-WYE
PT Prim The Potential Transformers primary winding rating for V1, V2 and V3 347
PT Sec The Potential Transformers secondary winding rating for V1, V2 and V3 347
CT Prim The Current Transformers primary winding rating for I1, I2 and I3 5
CT Sec The Current Transformers secondary winding rating for I1, I2 and I3 5
Vn Polarity The polarity of the Potential Transformer on Vn Normal
In Polarity The polarity of the Current Transformer on In Normal
Phase Order The expected rotation of the voltage phases (ABC or ACB) ABC
Phase Lbls The phase label format assigned to the outputs (ABC, RST, XYZ, RYB, RWB or 123) ABC
-
8/12/2019 ION Meter-70002-0162-03
49/152
2007 Schneider Electric. All rights reserved. Page 49
5 Security
ION7300seriesmetersofferFrontPanelmetersecurity,whichisenabledfromthefactory.ThischapterexplainsFrontPanelmetersecurityandhowtochangethemeterpassword.Italsodetailssomesecurityfeaturesavailableforrevenuemeters.
In This Chapter
Meter Security Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50FrontPanelSecurity................................................... 50
EnteringtheMeterPassword ....................................... 50
ChangingtheMeterPassword ...................................... 51
Device Security Access for ION Services . . . . . . . . . . . . . . . . . . . . . . . . . . . 52AllowingIONServicesaccesstosecurityenabledmeters............... 52
Additional Revenue Metering Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53HardwareLockSecurityOption .................................... 53
-
8/12/2019 ION Meter-70002-0162-03
50/152
Chapter 5 - Security ION7300 Series User Guide
Page 50 2007 Schneider Electric. All rights reserved.
Meter Security FeaturesYourmeterincludesthefollowingsecurityfeatures:
Front panel security
Anytimeyou
make
configuration
changes
to
your
meter
through
the
front
panel
youmustenterapassword.
Anti-tamper sealing
Yourrevenuemetercanbeprotectedbyantitampersealing.
Software security
IONsoftwaresecuritybringsaccesslevelsecuritytothemeter.WithIONsoftware,youcanconfiguremultipleuserswithdifferentpasswordsandspecifyaccessrights.IONsoftwaresecurityonlyappliestouserswhoareaccessingthemeterviaIONsoftware.
Formore
information
on
security,
refer
to
the
ION
System
Security
technical
note.
Front Panel SecurityFrontpanelmetersecurityletsyouconfigurethemeterthroughthefrontpanelusingameterpassword.
Entering the Meter PasswordFrontpanelmetersecurityisenabledbydefaultonallION7300seriesmeters;allconfigurationfunctionsinthefrontpanelarepasswordprotected.Thepassword
isfactory
set
to
0(zero).
Ifyoumakeconfigurationchangestothemeterviathefrontpanel,themeterpromptsyouforapasswordbeforeacceptinganyconfigurationchanges.Onceyouenterthecorrectmeterpasswordandconfirmthenewconfiguration,thechangeissetonthemeter.
Notethatthefrontpanelwillpromptyouforthemeterpasswordbeforeyoumakeyourfirstconfigurationchange.Youwillnotneedtoreenterthepasswordforeachsubsequentchange.
NOTE
The password enables users to change the configuration of the meter. It is recommended that you changeyour password from the default when you put the meter into service.
Ifyouenteranincorrectpassword,thefrontpanelwilldisplayaninvalidpasswordmessageandyoumusttryagain.
-
8/12/2019 ION Meter-70002-0162-03
51/152
ION7300 Series User Guide Chapter 5 - Security
2007 Schneider Electric. All rights reserved. Page 51
Changing the Meter Password1. SelectSECURITYfromthemainSetupmenu.
2. Youwillseethatthescreendisplays00000.Enterthecurrentpassword.Ifyouhavenotpreviouslychangedyourpassword,thedefaultis00000.
3. ChooseMODIFYPASSWORDtoalteryourpassword(theFACTORYUSEONLYoptionisforfactorypurposesandisnotaccessible).
4. Enteryournewnumericpassword.
TochangethevalueofthehighlighteddigitusetheUpandDownarrowbuttons.
Tochangethepositionofthecursoronespacetotheleft,holdtheUparrowbuttonforaboutonesecond.
Tochangethepositionofthecursoronespacetotheright,holdtheDownarrowbuttonforaboutonesecond.
SelectYEStoacceptyournewpasswordandreturntothemainSetupmenu.
New Password
00000
-
8/12/2019 ION Meter-70002-0162-03
52/152
Chapter 5 - Security ION7300 Series User Guide
Page 52 2007 Schneider Electric. All rights reserved.
Device Security Access for ION ServicesManyIONServicesneedconstantaccesstoyourmeter.TheseservicesincludetheLogInserter,QueryServer,theVirtualProcessorandSiteServerthatperformthefollowingtypeoffunctions:
NOTE
You may want to configure a separate user for accessing services. If you observe trouble with IONsoftware accessing the meter, it is likely that these services either do not have access rights or the original
user name and password have changed.
Allowing ION Services access to security enabled meters1. LaunchtheManagementConsoleandclickDevicesontheManagement
ConsolesSystemSetupPane.
2. Highlightyourmeter,rightclickandselectSecurity....
3. SelectStandardSecurityfromthedropdownmenu.Clickthecheckboxifyouwanttoallowthisusertosendtimesynchronizationsignalstothemeter.Click
OK.
4. EnterthevalidmeterpasswordforStandardSecurity,retypethepasswordtoconfirm,andclickOK.
Service Function
Log InserterQuery Server
Reads the ION meter Data Recorder or waveform modules and canautomatically rearm recorders that are configured as Stop-When-Full
Virtual ProcessorCan be configured to read from a meter or perform control actionusing Distributed Control.
Site Server Broadcasts time signals to the meter.
-
8/12/2019 ION Meter-70002-0162-03
53/152
ION7300 Series User Guide Chapter 5 - Security
2007 Schneider Electric. All rights reserved. Page 53
Additional Revenue Metering SecurityTomeetgovernmentregulationsandutilitysecurityrequirements,therevenuemeterincorporatesadditionalsecuritysystems:
ahardwarelockedsecuritysystemthatpreventsmodificationofrevenue
quantitiesafterthemeterissealed.
atraditionalantitampermechanicalsealonthemeterbaseunit.
Hardware Lock Security OptionION7300seriesmetersofferahardwarelockedsecurityfeature.Tomakeconfigurationchangesonahardwarelockedmeter,youmustfirstunlockthemeter.
SeetheION7300SeriesRevenueMeterproductoptiondocumentformoreinformation.
Hardware Lock and Protected ValuesTherevenuerelatedsettingsonmeterswiththeHardwareLockoptionarefactoryconfiguredandcannotbechangedwhilethemeterislocked.
Typicalvaluesthatareprotectedinclude:
kWh,kVARh,kVAhdelivered,received,delrec,del+rec.
kW,kVAR,kVAThermalandSlidingWindowdemandminandmaxvalues.
DigitalOutputscontrollingtheenergypulsingapplications.
AllPowersystemsettings,includingPTandCTratios.
Incertaincountriesrevenuecertificationisvoidifthehardwarelockisbroken.
Locked Module Listings
Foracompletelistoflockedmodulesspecifictoyourmeterandfirmware,contactTechnicalSupport.
Anti-Tamper Seals
ION7300seriesrevenuemetersincorporatesealingtabsthroughwhichtraditionallead/wiresealsareinserted.Thesesealseffectivelypreventunauthorizedpersonnelfromgainingaccesstometerinternals,andareprovidedwiththemeter.
-
8/12/2019 ION Meter-70002-0162-03
54/152
Chapter 5 - Security ION7300 Series User Guide
Page 54 2007 Schneider Electric. All rights reserved.
-
8/12/2019 ION Meter-70002-0162-03
55/152
2007 Schneider Electric. All rights reserved. Page 55
6 Communications
Thischapterincludesgeneralinstructionsforconnectingandconfiguringallthecommunicationportsonyourmeter.
Forspecificinstallationstepsandmeterspecifications,consultyourInstallationGuide.
In This Chapter
Communications Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Communications Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57RS485Connections(COM1andCOM2) ................................. 57
OpticalPortConnections(COM3)....................................... 59
EthernetConnections(optional) ........................................ 60
InternalModemConnections(optional) ................................. 61
ProfibusPort ......................................................... 61
Configuring Meter Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63SerialCommunicationsSetup .......................................... 64
ProfibusSetup(ION7300) .............................................. 65
EthernetCommunicationsSetup........................................ 66
ModemCommunicationsSetup ........................................ 68
Internet Connectivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70IONWebMeterFeature................................................ 70
IONMeterM@ilFeature(ION7330andION7350) ......................... 70
WebReach ........................................................... 71
TelnetandHyperTerminal ............................................. 71
CommunicationsLEDs ................................................ 72
-
8/12/2019 ION Meter-70002-0162-03
56/152
Chapter 6 - Communications ION7300 Series User Guide
Page 56 2007 Schneider Electric. All rights reserved.
Communications OverviewThefollowingillustrationshowsallthepossiblecommunicationsconnectionstothemeter.
ION7300seriesmetershavenumerouscommunicationpossibilitiesdependingonyourorderingpreferences.However,notallcommunicationsoptionsareavailabletoeachmodel.
Thetablebelowoutlinesthecommunication(COM)portsforeachION7300seriesmeter.TheProfibuscommunicationoptionisavailableonlyontheION7300meter.
COM1:
RS-485 serial connection or ModemGate
All ION7300 series meters provide COM1, an RS-485 serial communications port that supportsthese protocols: ION, Modbus RTU, or DNP(ION7330 / ION7350).ION7330 and ION7350 meters with aninternal modem can use the ModemGateprotocol on COM1, allowing the metersinternal modem to communicate with the
meter, the ION Enterprise server computer, andany devices that are wired to the metersCOM1 port.
COM2:
RS-485 serial connection or EtherGate
The ION7330 or ION7350 meter providesCOM2. If your meter has an Ethernet card,then COM2 functions as an Ethernetgateway (EtherGate) EtherGate transfersdata directly between an Ethernet networkand any devices that are wired to themeters COM2 port. If there is no Ethernetcard, then COM2 functions as a serial
communications RS-485 port, and supportsION, Modbus RTU, or DNP protocols.
The meters internal modemcommunicates to the servercomputer over the telephonenetwork.
Ethernet port
All ION7300 series meters support theoptional Ethernet card. An Ethernet connection
supports ION, Modbus RTU, or Modbus/TCPprotocols.
COM3:
Optical serial connection
All ION7300 series meters provide COM3, an optical(infrared) port. The optical port (located on the front ofthe meter) is used for serial communications, andsupports these protocols: ION, Modbus RTU, or DNP(ION7330 / ION7350). The port can also be used forenergy pulsing.
NOTE
The Profibus meter option for the ION7300
uses special communications connections.
Meter COM1 COM2COM3(Infrared)
Ethernet EtherGate Modem ModemGate
ION7300 Standard Not Available Standard Optional Not Available Not Available Not Available
ION7330 Standard Standard Standard Optional Optional Optional Optional
ION7350 Standard Standard Standard Optional Optional Optional Optional
-
8/12/2019 ION Meter-70002-0162-03
57/152
ION7300 Series User Guide Chapter 6 - Communications
2007 Schneider Electric. All rights reserved. Page 57
Communications ConnectionsThefollowingsectionprovidesreferenceforconnectingtothemetersvariouscommunicationports.Forthemostcurrentcommunicationspecifications,seeyourmetersInstallationGuide.
RS485andProfibuscommunications connectionstothemeteraremadetotherearofthemeter.Ethernetandmodemconnectionsaremadetothesides.Opticalconnectionsaremadetotheportonthefrontofthemeter.Seebelowfordetails.
NOTE
The Profibus meter option on the ION7300 meter does not use a COM port.
RS-485 Connections (COM1 and COM2)COM1andCOM2areusedforRS485communications.
NOTE
On ION7330 and ION7350 meters with the Ethernet card, COM2 is hardwired for EtherGate only, and
cannot be used for serial communication.
Rear View of Meter
Modem Ethernet
RJ11 RJ45
FCC part 68 complianttelephone cord Category 3 or 5 UTP
Captured-wireconnectors
22 AWG shielded,twisted pair
RS-485
-
8/12/2019 ION Meter-70002-0162-03
58/152
Chapter 6 - Communications ION7300 Series User Guide
Page 58 2007 Schneider Electric. All rights reserved.
IfyouhavetheModemGateoptiononyourmeter,COM1willautomaticallybesettoModemGate,notRS485.
NOTE
The internal modem option is hardwired to COM1. If you are using ModemGate, then any meter with an
internal modem that will reside on the serial loop must connect to the serial loop using COM2. If COM1
is used, then the two modems (gated meter internal modem and serially looped meter internal modem)
conflict during communication.
RS485connectionsaremadeviathecapturedwireconnectorsontherearofthemeter.Upto32devicescanbeconnectedonasingleRS485bus.UseagoodqualityshieldedtwistedpaircableforeachRS485bus.TheoveralllengthoftheRS485cableconnectingalldevicescannotexceed4000ft.(1219m).ConfiguretheRS485businstraightlineorlooptopologies.
Straight-Line Topology
Loop Topology
General Bus Wiring Considerations
Wirealldevicesconnectedonthebus,includingthemeter,converter(s)andotherinstrumentation,asfollows:
Connecttheshieldofeachsegmentofthecabletogroundatoneendonly. Isolatecablesasmuchaspossiblefromsourcesofelectricalnoise.
Useanintermediateterminalstriptoconnecteachdevicetothebus.Thisallowsforeasyremovalofadeviceforservicingifnecessary.
RS-232 toRS-485converter
TerminationResistor
RS-232 toRS-485converter
TerminationBlock
-
8/12/2019 ION Meter-70002-0162-03
59/152
ION7300 Series User Guide Chapter 6 - Communications
2007 Schneider Electric. All rights reserved. Page 59
InstallaWattterminationresistor(RT)betweenthe(+)and()terminalsofthedeviceateachendpointofastraightlinebus.TheresistorshouldmatchthenominalimpedanceoftheRS485cable(typically120ohmsconsultthemanufacturersdocumentationforthecablesimpedancevalue).
RS-485 Connection Methods to AvoidAnydeviceconnectionthatcausesabranchinthemainRS485busshouldbeavoided.Thisincludesstarandtee(T)methods.Thesewiringmethodscausesignalreflectionsthatmaycauseinterference.AtanyconnectionpointontheRS485bus,nomorethantwocablesshouldbeconnected.Thisincludesconnectionpointsoninstruments,converters,andterminalstrips.Followingthisguidelineensuresthat
bothstarandteeconnectionsareavoided.
Optical Port Connections (COM3)ThefrontopticalportisdesignedtoacceptANSIType2magneticcouplers.Theopticalmagneticcouplerispurchasedseparately;contactSchneiderElectricforalistofrecommendedoptocouplers.
TheopticalportcancommunicaterealtimemeasurementstoalaptoporsimilardeviceviaION,ModbusRTU,orDNP3.0(ION7330andION7350).Theportcanalsobeusedforinfraredenergypulsing.SeetheOpticalMagneticCouplerstechnicalnoteformoreinformation.
Avoid 3-way Star
connection point
Avoid 3-way T
connection point
Magnetic coupler
attached to front
optical port
-
8/12/2019 ION Meter-70002-0162-03
60/152
Chapter 6 - Communications ION7300 Series User Guide
Page 60 2007 Schneider Electric. All rights reserved.
Toenablecommunicationsfromtheopticalport,configuretheComm3Communicationsmodule.TheProtocol,theBaudRateandUnitIDsetupregistersmustproperlymatchyoursystem.WhencreatinganIONsite,ensurethatRtsCtsisdisabled(settoNo)intheCOM3serialsite.
RefertotheManagementConsolesectionintheonlineIONEnterpriseHelpformore
details
about
adding
serial
sites.
Ethernet Connections (optional)ThissectiononlyappliesifyourION7300seriesmeterhastheEthernetoption.
10BaseTEthernetconnectionsaremadeviatheRJ45modularportontheleftsideoftheunit.UsehighqualityCategory3or5UTP(CAT5unshieldedtwistedpairrecommended)cablewithamaleRJ45modularconnectorforconnectiontothe10BaseTport.
ThemetersupportsasingleEthernetconnectionatatime.WebMeterisaccessibleatthesametime,asareconnectionstoEtherGateandMeterM@il,aslongasthese
featuresare
available
on
your
meter.
TheoptionalEthernetport:
iscapableofdataratesupto10Mbps
supportsION,ModbusRTUandModbus/TCPprotocols
iscontrolledbytheETH1Communicationsmodule
TheEtherGatefeatureprovidescommunicationsbothtoanEthernetconnecteddeviceandthroughthatdevicetoaconnectedserialnetwork(SeethesectionTheEtherGateProtocol(ION7330andION7350)).OnlyoneEtherGateconnectionisallowedpermeterportatanygiventime.
Ethernet
-
8/12/2019 ION Meter-70002-0162-03
61/152
ION7300 Series User Guide Chapter 6 - Communications
2007 Schneider Electric. All rights reserved. Page 61
Internal Modem Connections (optional)
Themetersoptionalinternalmodemcanbereadilyusedinmostcountries,andcomplieswithFCC,IndustryCanadaandTBR21regulationsrefertotheNoticesatthestartofthisdocumentformoredetails.
ConnectiontotheinternalmodemismadeviatheRJ11jack,ortwocapturedwireconnectors,locatedontherightsideofthemeter.Connectthemetertothe
telephonenetworkwithanFCCPart68complianttelephonecord(thathastwomaleRJ11plugs).
Ifyouhavethecapturedwireconnectoroption,connectthemetertothetelephonesystemwiththe(barewiretoRJ11)cableprovided.IfyouhavetheCTR21compliantinternalmodemoption,youmayalsorequireanadaptortointerfacewithyourregionaltelephonejack.
Toenablecommunicationsthroughthemetersinternalmodem,youmustconfiguretheComm1Communicationsmodule.TheBaudRate,UnitID,andProtocolsetupregistersmustproperlymatchyoursystem,andtheinitializationstringfortheinternalmodemmustbesetupusingtheModemInitregister.SeethesectionModemCommunicationsSetupfordetails.
Profibus PortThisoptionisofferedexclusivelyontheION7300meter.
Telephone Network
Pin 3: Ring
Pin 4: Tip
RJ11
LEDs (DE and PWR)Profibus femaleconnector.
PRO I US
-
8/12/2019 ION Meter-70002-0162-03
62/152
Chapter 6 - Communications ION7300 Series User Guide
Page 62 2007 Schneider Electric. All rights reserved.
NOTE
The Profibus Master file (.GSD file) is included on a floppy disk with the meter. This file must be installed
on your Profibus Masters before the meter can communicate with the Profibus network.
TheoptionalProfibusportonthemeteriscapableofoperatingbaudratesupto12
Mbps.ProfibusConnectionstothemeteraremadeviatheninepinconnectorontherearoftheunit.PlugyourProfibusconnectorfromthenetworkintothisconnector.
-
8/12/2019 ION Meter-70002-0162-03
63/152
ION7300 Series User Guide Chapter 6 - Communications
2007 Schneider Electric. All rights reserved. Page 63
Configuring Meter CommunicationsCommunicationsettingsaretypicallyconfiguredwhentheIONmeterisinitiallyputintoservice.AsingleCommunicationsmodulecontrolseachcommunicationsportonthemeter.Themodulessetupregistersdefinetheparametersusedforeachport;theseparametersvaryaccordingtothetypeofcommunicationschannelselected(i.e.RS485,Modem,Optical,Ethernet).
TheCommunicationmodulescontrolthefollowingchannels:
1 For ION7330 / ION7350 meters with an optional modem, COM1 is hardwired for ModemGate.2 COM2is not available for the ION7300 meter.3 For ION7330 / ION7350 meters with an optional Ethernet card, COM2 is hardwired for EtherGate.4 Available for the ION7300 meter only.
UsethemetersfrontpanelorIONSetuptoinitiallyconfigurethemeterscommunications.Oncecommunicationisestablished,Designermayalsobeusedtomakechanges.
NOTEAltering certain settings of a communications channel that is in use may cause a loss of communications
with the meter.
RefertotheCommunicationsmoduledescriptionintheIONReferenceforcompletedetailsaboutallthesetupregistersintheCommunications module.
Communications ProtocolsBydefault,allcommunicationportsareconfiguredtousetheIONprotocol.UsingotherprotocolsrequiresconfigurationoftheProtocolsetupregisterforthe
Communicationsmodule
that
controls
the
port
you
want
to
use.
Not
all
protocols
areavailableonallports.
Available Protocols
ION
ModbusRTU
DNP3.0
EtherGate
Module Name Settings
Comm 1 COM1 RS-485 port and internal modem 1
Comm 2 2 COM2 RS-485 port or EtherGate 3port
Infrared Comm COM3 Optical port
Ethernet Comm 10Base-T Ethernet port
Profibus Comm 4 Profibus Communications port
-
8/12/2019 ION Meter-70002-0162-03
64/152
Chapter 6 - Communications ION7300 Series User Guide
Page 64 2007 Schneider Electric. All rights reserved.
ModemGate
InfraredI/O
Profibus
Factory(reservedforusebyTechnicalSupport)
Serial Communications SetupSerialcommunicationsareavailableonCOM1,COM2andCOM3(Infrared).Toenablecommunicationsthroughthemetersserialports,configuretheapplicableCommunicationsmodule.TheProtocol,TranDelay,BaudRateandUnitIDsetupregistersmustproperlymatchyoursystemandcanbesetthroughthemetersfrontpanelorIONsoftware.
Using the Front PanelThecurrentconfigurationofthemeterscommunicationportsarefoundinthe
variousCOMSetupmenuitems.EthernetsettingsarelocatedunderNetworkSetup.
1 ModemGate is available on ION7330 and ION7350 meters with an internal modem.2 The factory set Unit ID for COM1 is based on the serial number of the meter, using the last four
numbers before the dash. For example, if the serial number is PA-0009B263-01, the Unit ID is set in
the factory to 9263. After a factory reset, the unit ID number will default to 100.3 EtherGate is available on ION7330 and ION7350 meters with Ethernet.
Using ION Setup1. OpenIONSetupandconnecttoyourmeter,usingBasicMode.
2. IntheSetupAssistant,navigatetotheCommSettingsfolder.
Menu Setting Description Range (Values) Default
Comm
1CM1 PROTOCOL The communications protocol
ION, Modbus RTU, DNP 3.00, Factory,
ModemGate1ION
CM1 BAUD RATE The data rate, in bits per second 1200, 2400, 4800, 9600, 19200 9600
CM1 UNIT IDEvery meter on an RS-485 network must have aunique Unit ID number
1 to 9999From serial
number2
Com
m
2CM2 PROTOCOL The communications protocol
ION, Modbus RTU, DNP 3.00, Factory,
Ethergate3ION
CM2 BAUD RATE The data rate, in bits per second 1200,