Inverter ad onda sinusoidale pura con caricabatterie integratoPure sine wave Inverter with battery charger included
Manuale d’uso ed installazioneUser and installation manual
KSTA1000S-12 KSTA1000S-24KSTA2000S-12 KSTA2000S-24KSTA3000S-12 KSTA3000S-24
KSTA6000S-48
2 MNL005001R4
Indice - Table of contents
Caratteristiche generali ed utilizzi - Functional features and uses 3
Figure unità - Unit Figures 4
Specifiche funzionamento inverter - Inverter mode specifications 5
Specifiche funzionamanto in rete - Line mode specifications 6
Specifiche modalità carica - Charge mode specifications 7
Utilizzo tastiera, allarmi e protezioni - Keyboard utility, alarms and protections 10
Collegamenti - Connections 11
Procedura primo avviamento 12
Display LCD - LCD Display 14
Tabella segnalazioni led e suono buzzer - Table of leds and buzzer reports 17
Funzionamento ventola, specifiche generali - Fan Operation, general specifications 18
Altre specifiche generali - Other general specifications 18
Esempi applicativi - Application examples 19
Contatto per segnalazione remoto - Contact for remote signal 20
Smaltimento/Garanzia - Disposal/Warranty 21
La ringraziamo per la scelta di questo prodotto.Prima di installare l’inverter leggete attentamente il presente manuale.Questo manuale fornisce istruzioni per la sicurezza, l’installazione ed il funzionamento dell’apparecchiatura.Permette inoltre la più completa conoscenza dell’apparecchiatura in modo da ottenere da essa il miglior ser-vizio. Conservate questo manuale.
Thank you for choosing this product.Carefully read this manual before installing this Inverter. This manual includesimportant safety instructions for the installation and operation of this device, and it suppliesthorough information about all its functions for a safe and efficient use.Please keep this manual for reference.
I dati e le informazioni indicate in questo manuale sono da ritenersi suscettibili di modifica in qualsiasi momento e
senza obbligo di preavviso da parte di K.E.R.T. Srl.
Data and information included in this manualcould be changed in every moment and
without duty of advanced warning by K.E.R.T. Srl.
3MNL005001R4
Idoneo all’alimentazione di qualsiasi tipo di carico o apparecchiatura, compresi carichi fortemente induttivi.L’elevata capacità di sovraccarico ne permette l’utilizzazione per l’alimentazione di carichi non lineari, quali frigoriferi, condizionatori, elettropompe, motori di ogni genere. Con caricabatterie automatico integrato, consente di selezionare il tipo di batteria da utilizzare. Questo ne permette l’utilizzo su sistemi / mezzi che necessitano il mantenimento della carica delle batterie costante, es. ambulanze, camper e imbarcazioni.
Evoluta comunicazione e praticità.Display LCD integrato con le seguenti indicazioni:tensione ingresso batterie, tensione uscita, potenza collegata W / VA, temperature di funzionamento, frequenze, autonomia batteria.Funzione “Energy saving ON”, per assicurare un importante risparmio di energia, semplicemente selezionando un efficiente circuito di stand-by.Ideale per l’utilizzo in impianti fotovoltaici ad isola.
Suitable to supply every kind of charge or equipment, including very inductive charges.Its very high capacity of overload to allows used it to supply non linear charges, as fridges, air conditioners, electropumps, every kind of motor.With the integrated battery charger, it allows to select what kind of battery has to be used. This feature allows to use the inverter on systems/means that need to keep the battery charge constant, for example ambulances, campers and boats
High level of communication and handiness.Integrated LCD display with following information: batteries input voltage, output voltage, connected power W/VA, working temperature, frequencies, battery back up time.“Energy saving ON” function, to allow a high energy saving, by regulating the start up of an efficient stand- by circuit.Suitable to be used in stand-alone photovoltaic systems.
Caratteristiche funzionali ed utilizzi Functional features and uses
Quote di fissaggio per modelli fino a 3kW-Mounting dimensions for models up to 3kW
Dimensioni in mm Dimension in mm
Posizionamento Inverter. ATTENZIONE! Posizionare / installare l’Inverter in un luogo ventilato. Non ostruire le griglie di areazione. ATTENTION! Place / install the inverter in a ventilated place. Don’t obstruct the ventilation grilles.
422,30
224,00205,40 358,60
307,80
128,40 128,40
ø = 7,0ø = 9,5
26,50
4 MNL005001R4
Lato collegamenti DCDC connection side
Viste - Figures
Lato collegamenti ACAC connection side
MorsettieraTerminal block
Presa schuko (uscita)Per carichi continui superiori a 1500W, si consiglia di utilizzare il collegamento a morsettiera.
Schuko socket (output)For continuos loads higher than 1500W, please use the terminal block connection.
Quote di fissaggio per modelli 6kW - Mounting dimensions for model 6kW
Dimensioni in mm - Dimension in mm
203,40
ø = 7,0ø = 9,5
26,50
477,0
238,5
50,8
597,0
222,4
5MNL005001R4
KSTA1000S
-12
KSTA1000S
-24
KSTA2000S
-12
KSTA2000S
-24
KSTA3000S
-12
KSTA3000S
-24
KSTA6000S
-48
Specifiche di funzionamento inverter - Inverter mode specificationsForma d’onda uscitaOutput voltage waveform sinusoidale - sine wave
Potenza nominale - Rated power W 1000 2000 2600 3000 6000Potenza a vuoto (con Energy saving ON) - Power no load (Energy saving ON)
W 5
Fattore potenza - Power factor 0 ÷ 1,0
Tensione nominale uscitaNominal output voltage Vac 230±10%
Frequenza nominale uscitaNominal output frequency Hz 50 ± 0,3
Regolazione tensione uscitaOutput voltage regulation ± 10% rms
Efficienza - Efficiency > 80%Protezione sovraccarico-cortocircuitoOver load - shortcircuit protection fusibile magnetotermico - circuit breaker
SovraccaricabilitàOverload capability
1. Da 110% a 125% per 30’ (min)2. Da 125% a 150% per 30’’ (sec)3. Sovraccarico > 150% per 5’’ (sec) 4. Sovraccarico > 170% 150ms
1. From 110% to 125% for 30’ (min)2. From 125% to 150% for 30’’ (sec)3. Overload > 150% for 5’’ (sec)4. Overload > 170% for 150ms
Avviamento motore elettricoElectric motor starting HP 1 1,5 2 2 3
Tensione ingresso nominale DC Nominal DC input voltage Vdc 12 24 12 24 12 24 48
Minima tensione DC ammessaMin DC input voltage Vdc 10 20 10 20 10 20 41
Pre-allarme batterie scaricaLow battery alarm
10,5 Vdc ± 0,3 - 12Vdc / 21,0 Vdc ± 0,3 - 24Vdc42,0 Vdc ± 0,6 - 48Vdc
Distacco per batteria (DC) scaricaLow DC input shut-down
10,0 Vdc ± 0,3 - 12Vdc / 20,0 Vdc ± 0,6 - 24Vdc40,0 Vdc ± 0,6 - 48Vdc
Tensione batteria (DC) elevata High DC input voltage
16,0 Vdc ± 0,3 - 12Vdc / 32,0 Vdc ± 0,6 - 24Vdc64,0 Vdc ± 0,6 - 48Vdc
Ripristino da tensione batteria elevataHigh DC input voltage recovery
15,5 Vdc ± 0,3 - 12Vdc / 31,0 Vdc ± 0,6 24Vdc62,0 Vdc ± 0,6 48Vdc
Risparmio energiaPower saving
Carico < 25W (con “Energy saving ON” abilitato)Load < 25W (with “Energy saving ON” enable)
ATTENZIONE: E’ obbligatorio collegare le batterie per avviare l’Inverter, in caso contrario il display rimarrà spento e l’apparecchio non si avvierà. NON è sufficiente collegare ingresso 230Vac.
WARNING: You must connect the battery to start the Inverter, otherwise the display will remain off, and the unit doesn’t work. DO NOT simply connect 230Vac input.
6 MNL005001R4
KSTA1000S-12
KSTA1000S-24
KSTA2000S-12
KSTA2000S-24
KSTA3000S-12
KSTA3000S-24
KSTA6000S-48
Specifiche di funzionamento in rete - Line mode specifications
Forma d’onda ingressoInput waveform sinusoidale - sine wave
Tensione ingressoInput voltage 230Vac
Disconnessione ingresso per bassa tensione Low voltage input disconnection 184Vac ± 4%
Riconnessione da ingresso bassa tensione Low voltage input re-connection 194Vac ± 4%
Disconnessione ingresso per alta tensioneHigh voltage input disconnection 265Vac ± 4%
Riconnessione da ingresso alta tensioneHigh voltage input re-connection 255Vac ± 4%
Massima tensione ingresso AC Max AC Input Voltage 270Vac
Frequenza ingresso nominaleNominal input frequency 50Hz
Disconnessione ingresso per bassa frequenza Low frequency input disconnection 48 ± 0,3 Hz for 50Hz
Riconnessione da ingresso bassa frequenza Low frequency input re-connection 47 ± 0,3 Hz for 50Hz
Disconnessione ingresso per alta frequenzaHigh frequency input disconnection 54 ± 0,3 Hz for 50Hz
Riconnessione da ingresso alta frequenzaHigh frequency input re-connection 55 ± 0,3 Hz for 50Hz
Forma d’onda uscitaOutput voltage waveform
stessa forma d’onda ingressosame as input waveform
Protezione da sovraccarico - cortocircuitoOverload - shortcircuit protection
fusibile magnetotermicocircuit breaker
Efficienza (da rete)Efficiency (line mode) > 95%
Tempo di risposta (da AC a DC)Transfer time (AC to DC) 10ms (tipica - typical)
Tempo di risposta (da DC a AC)Transfer time (DC to AC) 10ms (tipica - typical)
Bypass senza batteriaBypass without battery si / yes
Corrente massima sovraccarico bypassBypass overload max current 30A 40A
7MNL005001R4
KSTA1000S-12
KSTA1000S-24
KSTA2000S-12
KSTA2000S-24
KSTA3000S-12
KSTA3000S-24
KSTA6000S-
48
Specifiche funzionamento caricabatterie - Battery charge mode specifications
Tensione ingressoInput voltage Vac 230
Range tensione ingressoInput voltage range Vac 196 ÷ 255
Tensione uscita nominaleNominal output voltage
in base al tipo di batterie selezionateaccording to the selected battery type
Corrente di ricarica nominaleNominal charge current A 35* 20* 65* 35* 75* 45* 50*
Corrente di ricarica regolabileAdjustable charge current
si / yes si / yes si / yes si / yes si / yes si / yes si / yes
Tensione iniziale batteriaBattery initial voltage Vdc
0-15.7 / 31.4 / 62.8(può funzionare con tensione batteria 0V)
(it can work with 0Vdc battery voltage)Protezione cortocircuito caricabatterieShortcircuit charger protection
fusibile magnetotermicocircuit breaker
Protezione sovraccarica batterieOver charge battery protection
Bat. Vdc ≥ 15.7Vdc / 31.4Vdc / 62.8Vdcsegnale acustico 0.5s ogni secondo, guasto dopo 60s
beeps 0.5s every 1s, fault after 60sCorrente assorbita da batteria alla massima potenza in uscitaCurrent consumption from the battery with the maximum output power
A 128 65 250 125 325 188 185
Potenza massima assorbita da rete (a carico in uscita = 0W) con massima corrente o con i diversi step di ricarica Maximum power consumption from the mains (if output load = 0W) with maximum or different charging current steps
W25% = 140*50% = 280*75% = 420*
100% = 560*
25% = 154*50% = 308*75% = 462*
100% = 615*
25% = 260*50% = 520*75% = 780*
100% = 1040*
25% = 270*50% = 540*75% = 810*
100% = 1080*
25% = 308*50% = 615*75% = 923*
100% = 1230*
25% = 353*50% = 705*75% = 1058*
100% = 1410*
25% = 675*50% = 1350*75% = 2025*100% = 2700*
* corrente di ricarica regolabile mediante trimmer: 25%, 50%, 75%, 100% (vedi punto 12 a pag. 10)* charging current adjustable with trimmer: 25%, 50%, 75%, 100% (see point 12 at page 10)
Selezione batterie - Batterie selectionPosizione selettore
Switch setting
Tipo batteria
Battery type
Rapida - Boost Mantenimento - FloatingTensione - Voltage Tensione Voltage
12V 24V 48V 12V 24V 48V
0 - Caricabatterie OFF1 Gel USA 14.0 28.0 56.0 13.7 27.4 54.8
2 AGM 1 14.1 28.2 56.4 13.4 26.8 53.6
3 AGM 2 14.6 29.2 58.4 13.7 27.4 54.8
4 Piombo ermetico Sealed lead acid 14.4 28.8 57.6 13.6 27.2 54.4
5 Gel Euro 14.4 28.8 57.6 13.8 27.6 55.2
6 Acido liberoOpen lead acid 14.8 29.6 58.2 13.3 26.6 53.2
7 CalcioCalcium 15.1 30.2 60.4 13.6 27.2 54.4
8 De-solfatazioneDe-sulphation 15.5 31.0 62.0 -
8 MNL005001R4
Stadi di carica batterie - Stages of battery chargeLa ricarica delle batterie è gestita da un microprocessore interno, e viene suddivisa in 3 diversi stadiThe battery recharging is managed by an internal microprocessor, and it is divided into 3 stages• Lo stadio iniziale CC carica la batteria con corrente costante fino al raggiungimento di una tensione di 2,4V /
elemento (Il tempo impiegato per il raggiungimento di questa tensione viene memorizzato dal microprocessore = T1)The initial stage CC charges the battery with a constant current till a voltage of 2,4V / element is reached (the time taken to reach this voltage is read by the microprocessor as T1)
• Il secondo stadio CV carica la batteria ad una tensione costante 2,4V / elemento per un tempo calcolato dal microprocessore (T1 x 10). Il tempo appena considerato non può superare le 12h
The second stage CV charges the battery with a constant voltage of 2,4V / element for the time calculated by the microprocessor (T1 x 10). This time can’t exceed 12hours
• Nel terzo stadio di ricarica (di mantenimento) il caricabatterie eroga una tensione di 2,2V / elemento. Se il caricabatterie mantiene per 10 giorni questo tipo di ricarica, il microprocessore riavvierà un nuovo ciclo di ricaricaIn the third stage of recharging (floating), the battery charger supplies a voltage of 2,2V / element. If the battery
charger keeps this kind of recharging for 10 days, the microprocessor will start a new charging cycle
Attenzione: I dati sopra indicati sono calcolati con batterie al piombo ermetico senza manutenzione (seletto-re tipo batterie in posizione 4)Attention: Above data are calculated using sealed lead acid - maintenance free batteries (battery selection on 4)
Attenzione: E’ importante selezionare il tipo di batterie (vedi tabella B pagina 5)Attention: It is important to select the battery type (see table B at page 5)
Attenzione: E’ consigliato, al momento dell’installazione, per proteggere le batterie, il collegamento di un fusibile sul positivo (+) batteriaAttention: At installation step, to protect batteries, we recommend to connect a fuse on the battery positive (+) pole
KSTA1000S-12
KSTA1000S-24
KSTA2000S-12
KSTA2000S-24
KSTA3000S-12
KSTA3000S-24
KSTA6000S-48
Valore fusibile consigliatoRaccommended fuse rating A 100 50 200 100 300 150 150
In caso di non utilizzo dell’apparecchio, le batterie devono essere scollegate, per evitare un’ec-cessiva scarica ed un conseguente danneggiamento delle stesse.
When the device is not used, batteries have to be disconnected, to avoid an over discharging of the batteries and also their damage.
9MNL005001R4
Tem
po
Tim
e
Tem
po
x 1
0, c
on
un
min
imo
di 1
ora
ed
un
mas
sim
o d
i 12
ore
Tim
e x
10, w
ith
a m
inim
um
1 h
ou
r m
ax 1
2 h
ou
rs
INIZ
IOS
TAR
T T
IME
FIN
EFI
NIS
H T
IME
Per 24 Vdc, considerare x 2For 24Vdc, consider x 2
T E N S I O N E - V O L T A G E
CO
RR
EN
TE
DI
RIC
AR
ICA
(%
)
CH
AR
GIN
G
CU
RR
EN
T (
%)
step
1 =
Co
rren
te d
i ric
aric
a co
stan
te -
co
nst
ant
curr
ent
char
ge
step
2 =
Ass
orb
imen
to c
aric
a a
14,4
/ 14
,8V
dc
- co
nst
ant
volt
age
at 1
4,4
/ 14,
8 V
dc
step
3 =
Ten
sio
ne
cost
ante
a 1
3,5
Vd
c -
Co
nst
ant V
olt
age
at 1
3,5
Vd
cst
ep 4
= Te
nsi
on
e b
assa
, rip
arte
da
step
1 -
Lo
w v
olt
age
rese
t to
ste
p 1
PR
OFI
LO D
I RIC
AR
ICA
BA
TT
ER
IER
EC
HA
RG
ING
BA
TT
ER
Y R
AT
E
Stadi di carica batterie - Stages of battery charge
10 MNL005001R4
Tastiera - Keyboard
25%
50%75%
100%
InterruttoreSwitch
1Risparmio energetico automatico
Auto power saving
Apparecchio acceso con risparmio automatico.In assenza di carico l’inverter si spegne e si porta in stand-by .Alla riattivazione del carico in uscita (> 25W) l’inver-ter si riavvia automaticamente
Device ON with auto power saving mode.If load not connected, the inverter turns off and gets into standby.When the output load (> 25W) is on again, the inverter will automatically restart
2 Off - Unit offApparecchio completamente spentoTotally off device
ONON
Apparecchio acceso, uscita sempre presentePower on, always present output
Allarmi acustici e visivi - Audible and visual alarms
4 Led verde intermittente - batterie in carica costante (rapida) / Led ON - batterie in carica di manteni-mento / Green led flashing - battery constant charging (boost) / Led ON - battery floating charge
5 Led verde ON - rete Vac presenteGreen led ON - Vac mains present
6 Led verde ON - Modalità Inverter, rete assenteGreen Led ON - Inverter mode, Absent mains
7 Led rosso 7 ON - Errore, anomalia, controllare errore o comunicazioni date dal display LCD
(tab. pag. 15)Red led N. 7 ON - Error, fault, check code or communication on LCD display
(tab. page 15)
8 Selettore tipo batteria collegataBattery type selector
9Pulsante scorrimento display -
Con questo tasto è possibile cambiare tipo di comunicazione sul displayDisplay scroll button
With this button you can change the type of communication on display
10 Display LCDLCD display
11 Lista dei tipi di batterie installabili - selezionabiliList of types of installable - selectable batteries
12 Corrente di ricarica regolabile (25%, 50%, 75%, 100%) Adjustable recharge current (25%, 50%, 75%, 100%)
12
3
12
5
4
6
11
10
7
8
9
3
11MNL005001R4
1. Assicurarsi che l’interruttore sia in posizione OFF “0”;2. Collegare la/e batteria/e rispettando le polarità.
Se utilizzato con rete presente, per la corretta ricarica delle batterie, selezionare tipo di batterie collegate con commutatore (vedi 8 pag. 10). Inoltre selezionare corrente di ricarica con trimmer 12 considerando come corrente di ricarica corretta circa 1/10 della capacità delle batterie collegate.
Es. KSTA3000S-24 con 2 batterie in serie da 12Vac 200Ah cad. = 24Vdc 200Ah corrente di ricarica ideale 200/10 = 20A di ricarica. Trimmer N. 12 impostato su 50% poichè la corrente di ricarica nominale dell’Inverter è 45A (per configurare la corrente di ricarica vedi tabella con dati relativo alle correnti di ricarica a pag. 7).
Utilizzare kit cavi batterie in dotazione (l’eventuale modifica dei cavi può provocare la perdita di potenza, utilizzare cavi con sezione adeguata).
ATTENZIONE! Rispettare le polarità. Consigliato il posizionamento di un sezionatore/fusibile batterie (vedi tab. valori consigliati pag. 8).Se presente collegare le batterie con sezionatore/fusibile aperto.
ATTENZIONE! Non stringere eccessivamente le viti di fissaggio dei cavi sui morsetti di ingresso batterie dell’Inverter. 3. Collegare ingresso 230Vac (qualora sull’impianto sia utilizzata rete ingresso o altra fonte 230Vac) ai mor-
setti rispettando F - N ed il collegamento di terra. Questa operazione va fatta ad Inverter completamente spento con sezionatore/fusibile batterie aperto.
4. Collegare il carico all’uscita utilizzando morsettiera o presa schuko. Inserire sezionatore (consigliato) se si utilizza la morsettiera; Assicurarsi che la potenza del carico non sia superiore alla potenza nominale dell’Inverter.
Collegamenti
Connections
1. Make sure that the switch is set in OFF “0”;2. Connect the battery (ies) respecting the polarities
If used with mains present, for the correct recharge of the batteries, select the type of batteries connected to the selector (see 8 page 10). Moreover select the recharging current with trimmer 12 considering as correct recharging current about 1/10 of the capacity of the batteries connected. Ex. KSTA3000S-24 with 2 batteries in series of 12Vac 200Ah each = 24Vdc 200Ah ideal recharging power 200/10 = 20A of recharge. Trimmer N.12 set in 50% since the rated recharging current of the Inverter is 45A (to pro-gram the recharging current see the chart about recharging currents at page 7).
Use the kit of battery cables supplied (the possible modification of the cables can cause a loss of power, use cables with an appropriate section).
ATTENTION! Respect the polarities. The positioning of a battery fuse is suggested (see recommended values chart page 8).If there is a battery fuse, let it open and connect it to the batteries
ATTENTION! Do not tighten excessively the fastening cable screws on the input batteries terminals of the Inverter. 3. Connect the input 230Vac (if in the system is used an input network or another source 230Vac) to the
terminals respecting F – N and the ground connection. This procedure must be done with the Inverter completely turned off with the battery fuse open
4. Connect the load to the output using a terminal block or a schuko socket. Insert the battery fuse (sug-gested) if a terminal block is used; Make sure that the load power is not higher than the rated output of the Inverter.
12 MNL005001R4
Procedura primo avviamento - First starting procedure
Procedura primo avviamento a vuoto:1. Con il carico scollegato accendere l’inverter da batteria spostando l’interruttore su posizione 2. Verificare dati a display scorrendo le informazioni a Display con il tasto scorrimento (pagine 14, 15, 16). Con il Voltmetro verificare presenza tensione uscita 230Vac sulla morsettiera/presa schuko. 2. Qualora sia presente la rete alimentare l’Inverer. L’Inverter commuta in bypass e carica le batterie. Veri-
ficare il corretto funzionamente a Display (pag. 14, 15, 16).
Procedura primo avviamento con carico presente: ATTENZIONE! Le batterie devono essere almento al 50% della loro capacità di carica (vedi lettura display).
1. Scollegare la rete se presente dall’avviamento a vuoto precedente;2. Spegnere Inverter Interruttore posizione 0 / OFF;3. Collegare il carico;4. Accendere l’Inverter con interruttore in posizione 2 / ON con le sole batterie collegate (ingresso 12, 24,
48Vdc).L’Inverter deve alimentare il carico collegato (per visualizzare la potenza impegnata vedi display (barra, per-centuale). 5. Qualora sia presente la rete collegare la stessa (morsettiera). L’Inverter commuta in bypass e carica le
batterie. Verificare il corretto funzionamente a Display (pag. 14, 15, 16)Verificare il corretto funzionamento del carico.
ATTENZIONE! Se si collegano carichi con alti assorbimenti / spunti alti (pompe, elettrodomestici, ...) verifi-care che non provochino errori all’Inverter e lo stesso non sia sovraccaricato.
First starting procedure
First starting procedure without load:1. With the load disconnected switch on the battery Inverter moving the switch to position 2.Check the display data browsing the Display information using the browsing key (pages 14, 15, 16). Check the voltage presence input 230Vac on the terminal block/ schuko socket using the Voltmeter. 2. In case of power presence feed the Inverter. The Inverter commutes to bypass and charges the batte-
ries.Check the correct Display operation (pages 14, 15, 16).
First starting procedure with load connected: ATTENTION! Keep the voltage of the batteries at least above 50% of their charge capacity (see
display reading).1. If present since the first starting in neutral, disconnect the network;2. Turn off the Inverter with the switch set in 0/OFF;3. Connect the load;4. Turn on the Inverter with the switch set in 2/ON with the only connected batteries (input 12, 24, 48Vdc).The Inverter must supply the connected load (to visualize the occupied power see the display (bar, percen-tage).5. In case of power presence connect it (terminal block). The Inverter commutes to bypass and char-ges the batteries. Check the correct Display operation (pages 14, 15, 16).Verify the correct operation of the load.
ATTENTION! If you connect high electrical absorption loads (pumps, domestic appliances, …) check that they do not cause any error to the Inverter and that the latter is not overloaded.
13MNL005001R4
Procedura avviamento standard modalità Inverter
ATTENZIONE! Le seguenti procedure sono da ritenersi consigliate per il corretto funzionamento dell’In-verter.
Impianto ad isola (senza alimentazione 230Vac):Modalità ON
1. Interruttore in posizione “0” OFF;2. Chiudere il sezionatore ingresso batterie (consigliato);3. Accendere l’Inverter interruttore posizione “2” ON;4. Attivare il carico collegatoNota: è possibile avviare l’inverter anche con il carico collegato
Modalità Energy Saving ON1. Interruttore in posizione “0” OFF;2. Chiudere il sezionatore ingresso batterie (consigliato);3. Accendere l’Inverter interruttore posizione “1” Energy saving ON (risparmio energia);4. Attivare un carico > 25W ed attendere circa 30’’ per l’avvviamento dell’Inverter
Standard starting procedure Inverter mode
ATTENTION! The following procedures are recommended for the correct operation of the Inverter
Stand-alone grid (without power source 230Vac)Mode ON1. Switch set in “0” OFF;2. Close the input battery fuse (suggested);3. Turn on the Inverter, switch set in “2” ON;4. Activate the load connectedNote: it is possible to start the Inverter also with the load connected
Energy Saving Mode ON1. Switch set in “0” OFF;2. Close the input battery fuse (suggested);3. Turn on the Inverter, switch set in “1” Energy Saving ON;4. Activate a > 25W load and wait about 30’’ for the starting of the Inverter
14 MNL005001R4
Protezioni - Protections
Protezione sovratemperaturaOver temperature protection
temperatura interna ≥ 105 ° C, errore (arresto uscita) dopo 30 secondi internal temperature ≥ 105°C, fault (output shutdown) after 30 seconds
Protezione back-feedBack-feed protection si / yes
Ripristino erroriFault recovery
Riavvio apparecchioRestarting of the machine
Allarmi acustici e visivi - Audible and visual alarms
Tensione batteria bassa*Battery low voltage*
Led rosso intermittente, 0.5 s ogni 5 s, suono (beep) buzzer della durata di 0.5 s ogni 5 sFlashing red led, 0.5 s every 5 s, 0.5 s buzzer beep every 5 s
Tensione batteria altaBattery high voltage
Led verde acceso, suono (beep) buzzer della durata di 0.5 s ogni 1 s, errore dopo 60 s Green Led on, 0.5 s buzzer (beep) every 1 s, fault after 60 s
Sovraccarico modalità inverter Inverter mode over-load
1. Da 110% a 125% per 30’ - Primi 15’ minuti beep intermittente, altri 15’ beep continuo prima di andare in blocco: l’Inverter non darà più uscita (beep continuo rimane - Errore 2 a display). 2. Da 125% a 150% per 30’’. Beep intermittente per 30’’. Dopo 30’’ l’Inverter non darà uscita, il beep diventa continuo ed appare errore 2 a display.3. Sovraccarico > 150% per 5’’. Beep intermittente per 5’’, errore N. 2 e beep continuo.4. Sovraccarico > 170% per 150ms. Beep continuo, l’inverter non darà uscita e compare errore 2 a display.
1. From 110% to 125% for 30’ - Firts 15’ minutes intermittent beep, other 15’ beep conti-nuosly beep before fault: The inverter doesn’t give 230Vac output (The acoustic signal persists). 2. From 125% to 150% for 30’’. Intermittent Beep for 30’’. Fault, stop and continuosly beep after these 30’’.3. Overload > 150% for 5’’. Intermittent Beep for 5’’, then continuosly beep.4. Overload > 170% for 15ms. Inverter doesn’t give 230Vac output, continusly beep and fault N. 2 on display.
SovratemperaturaOver temperature
temperatura interna ≥ 105 ° C, led rosso acceso, suono (beep) di 0.5s ogni secondoInternal temperature ≥ 105°C, red led on, 0.5s beep every 1s
*Tensione batteria bassa: ricaricare le batterie, le stesse stanno per terminare l’autonomia, e l’Inverter entro pochi minuti non darà più uscita.
*Low battery voltage: recharge the batteries, they are going to end the back-up time within a few minutes, and the inverter will give no more output.
1) Modalità carica - charge modeIn questo modo di funzionamento, l’Inverter caricherà le batterie come indicatoIn this operation mode, the inverter will charge the battery as displayed
Display LCD - LCD display
15MNL005001R4
2) Modalità utilizzo con rete presente - operating mode with present mainsDurante il regolare funzionamento, il display riporterà le seguenti indicazioniDuring normal operating mode, the display will show as follows
Con l’Inverter collegato alla rete 230Vac, non sarà possibile visualizzare la percentuale di carico collegato. Figura F3
With the Inverter connected to 230Vac mains, you will not see the percentage of the connected load. Figure F3
F3
3) Modalità batteria, inverter, rete assente - battery, inverter mode, absent mains
Durante il funzionamento da batteria, il display riporterà le indicazioni in figura F1. Nel caso in cui la tensione batteria in ingresso sia inferiore al 25%, e dunque insufficente per alimentare il carico, l’inverter presenterà lo scenario (alternato ad intervalli regolari) in figura F2. In questo caso, caricare le batterie.
During the battery operating mode, the display will show indications as in picture F1. If input battery voltage is lower than 25%, therefore not enough to supply the load, the inverter will show the scenario (alternated with regular intervals) as in picture F2. In this case, charge the batteries.
E’ possibile visualizzare la percentuale di carico collegato - in uscita
It is possible to display the percentage of the output connected load
Tensione ingresso batterie, relativa per-centuale autonomia residua
Input battery voltage, percentage of back up time remaining
16 MNL005001R4
4) Modalità errore - fault modeIn caso di anomalia inverter, il display indicherà il codice di errore come riportato in figura F3In the inverter faulty operating mode, the display will show as follows (figure F3)
codice-code descrizione - description1 anomalia ventola - fan anomaly2 sovraccarico - overload
3 / 6 / 7 corto circuito uscita - output short circuit4 sovratemperatura - over temperature
8 / 9 sovratensione batteria - battery over voltage
F1 F2
In caso di allarme tensione batteria bassa, si alternano le visualizzazioni in figura F2
In case of low battery voltage alarm, the display will show intermittently the indica-tions as per the figure F2
Funzionamento da batteria figura F1
Back up / battery operating mode, figure F1
F3
17MNL005001R4
Modo funzionamento
Status
Situazione
Item
Indicazioni Led
Led indicatorsBuzzer
Charge Line Inverter Fault
Modalità rete presente
Line mode
Carica costante CCCC constant charge V V X X -
Carica costante CV CV constant charge
intermittenteblink V X X -
Carica flottante mantenimentoFloating charge
intermittenteblink V X V -
Standby X V X X -
Modalità inverter
Inverter mode
Inverter ON
(power saver OFF)X X V X -
Power saver ON X X intermittenteblink X -
Modalità allarme
Alarm mode
Tensione bassa batteria Battery low voltage X X V intermittente
blinkbeep 0.5 s ogni /
every 5 sec
Tensione batteria elevataBattery high voltage X X V X beep 0.5 s ogni /
every 1 sec
Sovraccarico mod. Inverter Overload on inverter mode X X V intermittente
blinkbeep 0.5 s ogni /
every 1 sec
Sovratemperatura mod. InverterOvertemp on inverter mode
X X V X beep 0.5 s ogni /every 1 sec
Sovratemperatura modalità rete presenteOvertemp on line mode
V V X X beep 0.5 s ogni /every 1 sec
Eccessiva carica batteriaBattery over charge V V X X beep 0.5 s ogni /
every 1 sec
Modalitàerrore/guasto
Fault mode
Guasto ventolaFan fault X X X V beep continuo
continuos beep
Tensione batteria elevataBattery high voltage X X X V beep continuo
continuos beep
Sovraccarico mod. inverterInverter mode overload X X X V beep continuo
continuos beep
SovratemperaturaOver temperature X X X V beep continuo
continuos beep
Eccessiva carica batteriaBattery over charge X X X V beep continuo
continuos beep
Protezione back feedBack feed protection X X X V beep continuo
continuos beep
Legenda: V = Led acceso; X = Led spento; intermittente = circa 0.5 secondi led acceso, 0.5 sec led spento
Remark: V = indicator Led ON; X = Indicator Led OFF; blink = indicator blinking about 0.5 sec ON and 0.5 sec OFF
4 5 6 7
18 MNL005001R4
Funzionamento ventola - Fan operation
La ventola a velocità variabile opera nelle modalità inverter e di ricarica. Ciò per garantire un’elevata affidabilità ed un ottimale funzionamento dei componenti ad una temperatura ambiente fino a 50 ° C
The variable speed fan works during inverter and recharging mode. In this way, a high reliability and an optimal operation of components at a room temperature up to 50°C is assured
Specifiche generali - General specifications
KSTA1000S
-12
KSTA1000S
-24
KSTA2000S
-12
KSTA2000S
-24
KSTA3000S
-12
KSTA3000S
-24
KSTA6000S
-48
Certificazione sicurezzaSafety certification EN 60950-1 - EN 61000-3-2 - EN 61000-3-3 - EN 62040-1
Classificazione EMCEMC classification
Direttiva 2004/108/CE - EN 55022 - EN 55024 - EN 62040-2ECE R10-05 Automotive Industry: Electromagnetic Compatibility
Temperatura di funzionamento Working temperature range -10°C ÷ +60 °C
Umidità di funzionamento Operation humidity 5% ÷ 95%
Rumore udibileAudible noise < 60 dB
RaffreddamentoCooling
convenzione forzata, ventola a velocità variabileforced air, variable speed fan
Dimensioni mm L x h x PDimensions mm L x h x D 224 x 181 x 449 224 x 181
x 624
Peso netto kgNet weight kg 17,5 17,5 22,5 22,5 25 25 44
Peso lordo kgGross weight kg 19,5 19,5 24,5 24,5 27 27 47,5
La ventola funzionerà alla velocità necessaria e per un tempo indefinito per garantire raffreddamento adeguato, ed evitare danni ai componenti interni
The fan will work at the needed speed and for an undefined time to assure the suitable cooling and to avoid damages to internal components
19MNL005001R4
Esempi applicativi - Application examples
Il carico è alimentato normalmente dalla rete elettrica, le batterie vengono ricaricate. In caso di mancanza rete entra in funzione l’InverterThe load is normally supplied by the mains, the batteries are recharged. In case of mains failure the inverter starts working
Funzione inverter, isolato da rete (impianto ad isola) Inverter mode, isolated from the mains (stand-alone equipment)
Modello Fuse Magnetotermico Differenziale - OUT
KSTA1000S-12 100A 6A (Curva C) Id=0,03A (Classe A)KSTA1000S-24 50A 6A (Curva C) Id=0,03A (Classe A)KSTA2000S-12 200A 10A (Curva C) Id=0,03A (Classe A)KSTA2000S-24 100A 10A (Curva C) Id=0,03A (Classe A)KSTA3000S-12 300A 16A (Curva C) Id=0,03A (Classe A)KSTA3000S-24 150A 16A (Curva C) Id=0,03A (Classe A)KSTA6000S-48 150A 32A (Curva C) Id=0,03A (Classe A)
Modello Fuse Magnetotermico Differenziale - IN
MagnetotermicoOUT
KSTA1000S-12 100A 10A (Curva C) Id=0,03A (Classe A) 10A Curva CKSTA1000S-24 50A 10A (Curva C) Id=0,03A (Classe A) 10A Curva CKSTA2000S-12 200A 16A (Curva C) Id=0,03A (Classe A) 16A Curva CKSTA2000S-24 100A 16A (Curva C) Id=0,03A (Classe A) 16A Curva CKSTA3000S-12 300A 25A (Curva C) Id=0,03A (Classe A) 25A Curva CKSTA3000S-24 150A 25A (Curva C) Id=0,03A (Classe A) 25A Curva CKSTA6000S-48 150A 40A (Curva C) Id=0,03A (Classe A) 40A Curva C
20 MNL005001R4
Contatto per comando remoto - Contact for remote control
Se si utilizza il comando remoto, l’interruttore sull’inverter va in posizione “0”, rif. 2 su tabella pagina 10.If you use the remote control, the switch on the inverter must be in “0” position, reference 2 of table on page 10
Utilizzare cavo standard con spina RJ11 fornito
Use supplied standard cable with RJ11
Esempio di utilizzo comando remoto per attivazione Inverter Example of use for the activation of the inverter
giallo/yellowblu/blue
vede/green
rosso/rednero/black
bianco/white
Utilizzare contatto pulitoON/OFF
Use dry contact ON/OFF
Cavi blu e giallo
Blue and yellow cables
Risparmio energetico automatico
Auto power saving
Apparecchio acceso con risparmio automatico.In assenza di carico l’inverter si spegne e si porta in stand-by .Alla riattivazione del carico in uscita (< 25W) l’inver-ter si riavvia automaticamente
Device ON with auto power saving mode.If load not connected, the inverter turns off and gets into standby.When the output load (< 25W) is on again, the inverter will automatically restart
Fili giallo e verde
Yellow and green cables
Risparmio energetico Off
Power saving off
Apparecchio acceso, uscita sempre presentePower on, always present output
giallo/yellow
vede/green
Inserire il connettore alla presa RJ
Insert the connector into the RJ port
Cavetti colore rosso, nero e bianco da non utilizzare
Don’t use red, black and white cables
21MNL005001R4
Gli accessori comunicano con l’Inverter me-diante cavo RJ11 indicato in figura.
KREM-S
Radiocomando per accensione - spegnimento remoto. Disponibile su modelli da 1000W a 3000W.
Radio remote control for switching on - switching off. Available on models from 1000W to 3000W.
The optionals communicate with the inverter by RJ11 cable as indicated in the figure.
Il sistema KREM-S viene utilizzato quando si ha l’esigienza di comandare a distanza l’accensione e lo spegnimento dell’inverter disponibile solo su modelli da 1000W fino a 3000W.
The system KREM - S is used when you need to remotely control the switching on and off of the inverter only available on models from 1000W to 3000W .
22 MNL005001R4
GARANZIAApparecchio garantito 24 mesi da qualsiasi difetto di materiali o di fabbricazione, esclu-se quelle parti il cui deterioramento è dovuto all’uso. Ogni garanzia decade in caso di cattivo uso dell’apparecchio o di manomissioni di ogni genere.Per ogni controllo o riparazione (in garanzia e non) l’apparecchio DEVE essere conse-gnato al rivenditore, o al centro assistenza, che provvederanno a fornire tale servizio. Solo nel caso non sia più possibile reperire il rivenditore od un centro assistenza, con-tattare K.E.R.T. srl.ATTENZIONE: La garanzia è valida solo se l’apparecchio è accompagnato da scontrino fi scale o da fattura. In caso contrario farà fede la data di costruzione.
WARRANTYThis appliance is guaranteed for 24 months from any kind of construction defect (those componets whose worsening is due to the use). Warranty is not valid in case of negli-gent, incorrect or improper use of the product, or any kind of tampering. For any control or repair (covered or not by warranty) the appliance MUST be delivered to the retailer. If you cannot find the dealer, please contact directly to K.E.R.T. srl. WARNING: this warranty is valid only if the device is accompanied by in-voice or fiscal receipt. If they are not available, we will refer to the con-struction date.
SMALTIMENTO Smaltire questi prodotti solo tramite centri di raccolta specializzati ed autorizzati. Non devono essere considerati come semplici rifiuti urbani.
DISPOSALDispose these products only through specialized and authorized collection centres. They must not be considered as normal urban waste.
K.E.R.T. S.r.l. Via Paolo Viganò 21 - 31031 Caerano di San Marco (TV) - Italytel. +39 0423 650707 - fax +39 0423 650385 - [email protected]
kert.itPer maggiori informazioni:
MNL005001 R4 04-2016