Introduction to Indoor Electrical[2]
description
Transcript of Introduction to Indoor Electrical[2]
Introduction to Indoor Electrical Equipment Inspection
©2010 Infrared Training Center, All rights reserved
1
1©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Indoor Electrical
2©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Infrared Training Center
Global Leader in IR Thermography Training. ISO-9001 Registered and NETA accredited in IR Thermography Training. Level I, II and III Condition Monitoring IR Certification, R&D Courses, and Application Courses.
3©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Your Presenter
• Jay Bowen• Electrician/ Engineer 32 years• Thermographer 15 years –
Level III• Master Electrician - Wisconsin• Certified Electrical Inspector -
Wisconsin• Designer of Electrical Systems
- Wisconsin• Associate Degree Electronics
Technology• Electrical Contractor -
Previous Business owner
• Green Bay, Wisconsin• Packer Fan (season ticket
holder),
Introduction to Indoor Electrical Equipment Inspection
©2010 Infrared Training Center, All rights reserved
2
4©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Electrical Safety Requirements
• NFPA 70E (National Fire Protection Association):”Electrical Safety Requirements for Employee Workplaces”
• Details OSHA 1910 Requirements
5©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
NFPA 70E
• Electrical Safety Training• Approach Limits• Flash Hazard Analysis per NFPA 70E-2000, Part
II 2-1.3.3 • Personal Protective Equipment (PPE)
• Face shields• Body protection from arc flash
6©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Existing Standards
• NETA 2007 - Acceptance Testing Specifications for Electrical Power Distribution Equipment and Systems
• NEMA MG-1 - Information Guide for General Purpose Industrial AC Small and Medium Squirrel-Cage Induction Motor Standards
• NFPA 70B - Recommended Practice for Electrical Equipment Maintenance
• NFPA 70 – National Electrical Code – Table 310 -13 Wire insulation temperatures
• NFPA 70E - Electrical Safety in the Workplace
Introduction to Indoor Electrical Equipment Inspection
©2010 Infrared Training Center, All rights reserved
3
7©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Existing Standards
• ASNT SNT-TC-1A- [(2001)],” Recommended Practice for Training and Certification Non-Destructive Testing”
• ASTM E1934.2050-1 Examining Electrical and Mechanical Equipment with Infrared Thermography
• ASTM E1933.4671-1 Measuring and Compensating for Emissivity Using Infrared Imaging Radiometers
• ASTM E1897.4369-1 Measuring and Compensating for Transmittance of an Attenuating Medium Using Infrared Imaging Radiometers
• ASTM E1862.3882-1 Measuring and Compensating for Reflected Temperature Using Infrared Imaging Radiometers
• ASTM E1213 - 97(2009) Standard Test Method for Minimum Resolvable Temperature Difference for Thermal Imaging Systems
• ASTM E1311 - 89(2004) Standard Test Method for Minimum Detectable Temperature Difference for Thermal Imaging Systems
• ASTM E1256 - 95(2007) Standard Test Methods for Radiation Thermometers (Single Waveband Type)
8©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Criteria
• One size does not fit all• Must have more than just temperature
measurements• Component• Load or amperage• Season• Time of day• System Importance
• Accuracy of temperature• Emissivity • Angle• Trefl• Distance• Resolution
• Direct and indirect tables
9©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
NETA
Temperature difference (ΔT) based on
comparisons between similar components
under similar loading.
Temperature difference (ΔT) based upon
comparisons between component and ambient
air temperatures. Recommended Action
2ºF - 5ºF 2ºF - 18ºF Possible deficiency; warrants investigation
5ºF - 27ºF 18ºF - 36ºF Indicates probable deficiency; repair as time permits
- - - - - - 36ºF - 72ºF Monitor until corrective measures can be accomplished
>27ºF >72ºF Major discrepancy; repair immediately
*** Metric Challenged ***
Introduction to Indoor Electrical Equipment Inspection
©2010 Infrared Training Center, All rights reserved
4
10©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Criteria
• Load is very important -- heating with low load is very serious
• Equipment designation -- key equipment should have tighter criteria
• Circuit consideration -- critical nodes should have tighter criteria
• Time of use or cycle – how is this used and when
• Heat transfer effects -- wind, ambient or environment, location these are not considered in most criteria
• Indirect Measurements – how critical are these?
11©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
An Example
Problem= 133
Reference=87
Or…
Delta = 46
Make this a monitor.
12©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
An Example
Problem= 126
Reference=85
Or…
Delta = 41
Make this a monitor.
Wrong!!!
This is serious!
Introduction to Indoor Electrical Equipment Inspection
©2010 Infrared Training Center, All rights reserved
5
13©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Preparing for an IR Survey
• Routes are set up and routinely done to satisfy the requirements driven by the Equipment Listing and Schedule
• Often, Level I thermographers are given responsibility to perform IR surveys on a route basis
• We also recommend doing “IR by walking around” as about 10% of your routine surveys
• Someone authorized to open cabinets, etc should accompany the thermographer
• A method to collect the data
14©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Routine Survey
• Systematically look at all “IR sensitive” components• These are the components determined by
the results of the Equipment List and Schedule study
• The survey will normally be categorized by • Equipment type• Location• Time to do the survey
• This all rolls up into an “IR Route”
15©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Other Tips and tricks
• Compare, compare, compare• Stand still when looking at your thermal
or visual image• Large warm targets may indicate a more
severe problem than smaller hotter targets—Area matters!
Introduction to Indoor Electrical Equipment Inspection
©2010 Infrared Training Center, All rights reserved
6
16©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Where to Start
• Begin at service entrance • Recommend IR windows for over 600 volts.• 600 volts and under, you can often remove covers with
proper PPE and safety considerations.• Look at bolted connections, terminations, bolted
pressure switches.
17©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
facility electrical
• Power distribution. • Panel boards, bus ducts, dry type transformers, tap/splice boxes.
• Disconnect switches• Fusible/non-fusible. Remove cover, if possible
• MCCs (Motor Control Centers)• Open the buckets, or use IR windows
18©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Normal Heating
Motors
Introduction to Indoor Electrical Equipment Inspection
©2010 Infrared Training Center, All rights reserved
7
19©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Localized Heating
Motors
20©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Motors
TABLE 1
Insulation System Class A B F HTemperature Rating in Degrees Centigrade / Fahrenheit
105°C/221°F 130°C/266°F 155°C/311°F 180°C/356°F
Temperature Rise Allowance by Resistance (Based on 40°C(104F) / Ambient Temperature)
All Motors with 1.15 Service Factor(Hot Spot Allowance)
70(158)*
90(194)*
115(239)* —
Totally Enclosed Fan Cooled Motors(Hot Spot Allowance)
60(140)(5)
80(176)(10)
105(221)(10)
125(257)(15)
Totally Enclosed Non-Ventilated Motors(Hot Spot Allowance)
65(149)(0)
85(185)(5)
110(230)(5)
135(275)(5)
Motors other than those listed above(Hot Spot Allowance)
60(149)(5)
80(176)(10)
105(221)(10)
125(257)(15)
* When operating at service factor loading the hot spot temperatures can actually exceed the insulation rating resulting in shortened motor life.
Insulation Code
21©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Motors
Comparison
Introduction to Indoor Electrical Equipment Inspection
©2010 Infrared Training Center, All rights reserved
8
22©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Controller
78.3°F
228.6°F
100
150
200
Ref Temp: 103.0°F
Max Temp: 241.7°F
Overload screw loose
23©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Panel Boards
Termination
24©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Panel Boards
Breaker Heating
Introduction to Indoor Electrical Equipment Inspection
©2010 Infrared Training Center, All rights reserved
9
26©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Panel Boards
Load correction software
27©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Panel Boards
Bus Compression Connection
28©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Clip Tension
Fuses / Switches
Introduction to Indoor Electrical Equipment Inspection
©2010 Infrared Training Center, All rights reserved
10
29©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Blade Mating
Fuses / Switches
30©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
20.6°F
650.9°F
200
400
600
Reference: 114°F
Anaylsis: >1076°F
Termination Failure
Breakers
31©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Connection Torque
Breakers
Introduction to Indoor Electrical Equipment Inspection
©2010 Infrared Training Center, All rights reserved
11
33©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Harmonics
Transformers
34©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Low Oil
Transformers
35©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Connection Torque
Bus ways / Buss duct
Introduction to Indoor Electrical Equipment Inspection
©2010 Infrared Training Center, All rights reserved
12
36©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
73.8°F
83.5°F
74
76
78
80
82
81.7°F
74.9°F
Bus ways / Buss duct
38©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
82.7°F
105.6°F
85
90
95
100
105
99.5°F
91.5°F
Improper Conductor Size
Conductors / Terminations
39©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Conductors / Terminations
Introduction to Indoor Electrical Equipment Inspection
©2010 Infrared Training Center, All rights reserved
13
40©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
161.4°F
391.6°F
200
250
300
350291.8°F
395.1°F
Improper Crimp
Conductors / Terminations
41©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
70.4°F
132.0°F
80
100
120
132.8°F
87.6°F
Improper Tightening
Conductors / Terminations
42©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Cell Breakdown
Capacitors / Batteries
Introduction to Indoor Electrical Equipment Inspection
©2010 Infrared Training Center, All rights reserved
14
43©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
77.0°F
136.0°F
80
100
120
Reference: 87.8°F
Anaylsis: 136.1°F
Capacitors / Batteries
44©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Common Item
45©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Tools
First Surface Mirrors
Anemometer
Phasing meter
MultimeterTach or RPM
Power Quality Ammeter
Motor Tester
Introduction to Indoor Electrical Equipment Inspection
©2010 Infrared Training Center, All rights reserved
15
46©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Reporting
47©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Reporting
• EPRI lists the following for an effective report• Time/date• Equipment identification• Location• Specific problem• Corrective action• Visible light image• Infrared image• Inspector’s name and signature• Component temperature • Acceptance criteria • Ambient temperature • Site Conditions• Equipment load (for electrical equipment),• IR camera and lens
48©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
InfraMation: The Newsletter
Sign up at www.infraredtraining.com/
Introduction to Indoor Electrical Equipment Inspection
©2010 Infrared Training Center, All rights reserved
16
49©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Message Board Threads for
“Thermography"
Forum
50©2009 FLIR Systems, Inc. All rights reserved. Intended solely for use by FLIR/ITC distributors, customers and prospects only.
Thank-you for your attendance
Question and Answer starts now
Post session - Email Questions [email protected]