Interpact Catalogue_ 2008
Transcript of Interpact Catalogue_ 2008
Catalogue2008
Low Voltage
InterpactSwitch-disconnectors INS/INV40 to 2500 A
�
Interpact INS/INV Contents
Presentation 2
Functions and characteristics A-1
Installation recommendations
B-1
Dimensions and connection
C-1
Additional characteristics D-1
Catalogue numbers E-1
�
Presentation Who else offers such from 40 to 2500 A?
Interpact INS
05��
64a-
�7
05��
68a-
��
0566
48a-
�5 �
��
��Switch-disconnectors
with positive contact indication
Interpact INV
0566
50a-
�5
��
��
���Switch-disconnectors
with visible break
Interpact INS
059�
03a-
�7
059�
0�a-
��
0566
5�a-
�5 �
��Emergency-off
switch-disconnectors with positive contact indication
Interpact INV
0566
54a-
�5 �
��Emergency-off
switch-disconnectors with visible break
The complete range 40 A 63 A 80 A 100 A 125 A 160 A 200 A 250 A
Modular profile INS40 INS63 INS80 INS100 INS125 INS160
INS250-100 INS250-160 INS250-200 INS250
Mounting on backplate INV100 INV160 INV200 INV250
3
���
���� �
0594
87a-
�8
PB
�000
�6a-
37
PB
�000
�0a-
38
�
0594
9�a-
�8
PB
�000
�7a-
37
PB
�000
��a-
38
��
��
��
��
0594
89a-
�8
PB
�000
�8a-
37
�
0594
93a-
�8
PB
�000
�9a-
37
320 A 400 A 500 A 630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A
INS320 INS400 INS500 INS630 INS800 INS1000 INS1250 INS1600 INS2000 INS2500INS630b
INV320 INV400 INV500 INV630 INV800 INV1000 INV1250 INV1600 INV2000 INV2500INV630b
... in a wide range
4
Presentation Who else covers
6��7
8a-�
7
E9�
069a
-3�_
�50d
pi
E45
�06
3�
��
�
Local isolation enclosures
Current ratings: up to 63 A for commercial and 630 A for industrial applications
Merlin Gerin switch-disconnectors
NG125NA, Interpact INS40 to 160 and I modular switches
Interpact INS/INVCompact NSATelemecanique switch-
disconnectorsVario 12 to 175 A.
b
v
v
vvv
b
Control panelsCurrent ratings:
up to 63/80 AMerlin Gerin
switch-disconnectors:Interpact INSTelemecanique
switch-disconnectorsVario.
b
b
vb
v
Sub-distribution boards
Current ratings: up to 160 A
Merlin Gerin switch-disconnectors:
Interpact INS/INVNG125.
b
b
vv
DB
�068
�� Local isolationIndustrial or commercial
Final distribution
Sub-distribution
Power distribution
5
so many applications?
���
��
� ��
0566
99a-
49
E9�
07�
�04
Industrial switchboards and automatic control panels
Current ratings: up to 400 AMerlin Gerin switch-disconnectors:Interpact INS/INVCompact NSA.
bbvv
���
Main power distribution boards for commercial and industrial applications
Current ratings:400 to 1000 A for commercial applications400 to 1600 A for industrial applicationsMerlin Gerin switch-disconnectors:Interpact INS/INVCompact NSA Masterpact NA/HA/HA10/HF.
bvvbvvv
6
Presentation Who else offers such
INS/INV switch-disconnectors:
0566
48a-
�5
INS INS40 INS63 INS80 INS100 INS125
INV
Ith at 60 °C 40 63 80 �00 ��5 � � � � � � � �� � � � �
Ui CA 50/60 Hz/CC (V) 690 690 690 750 750 � � � � � �
Uimp (kV) 8 8 8 8 8 �� �� �� �� �� �� ��
INS/INV switch-disconnectors:
0566
50a-
�5
INS INS40 INS63 INS80 INS100 INS125
Ue AC22A 380/415 V 40 63 80 �00 ��5 � � � � � � � �� � � � �
Ue AC22A 660/690 V - - - �00 ��5 � � � � � � � �� �� � � �
DB
�068
��
Ue AC23A 380/415 V 40 63 7� �00 ��5 � � � � � � � �� ��
Ue AC23A 500/525 V 3� 40 40 �00 ��5 � � � � � � � �� ��
Ue AC23A 660/690 V - - - 63 80 � � � � � � � �� ��
(1) 1600 A at 45 °C and 1450 A at 60 °C.(2) Ue AC22A / AC22B.(3) Ue AC22B.
Source changeover systems:
Standards and certifications:The Interpact INS/INV range complies with international standards, as officially certified by an independent organisation.IEC 60 947-1, IEC 60 947-3EN 60 947-1, EN 60 947-3
E95
578
DB
�073
89
Conformity with UL and CSA standardsSpecial versions of Interpact switch-disconnectors are available that comply with UL and CSA standards for moulded case switches.UL489 and CSA C22.2 No. 5-02
7
high performances and safety?
... for high industrial performance
�
INS160 INS250-100
INS250-160
INS250-200
INS250 INS320 INS400 INS500 INS630 INS630b INS800 INS1000 INS1250 INS1600 INS2000 INS2500
INV100 INV160 INV200 INV250 INV320 INV400 INV500 INV630 INV630b INV800 INV1000 INV1250 INV1600 INV2000 INV2500
� �� �60 �00 �60 �00 �50 3�0 400 500 630 630 800 �000 ��50 �600 (�) �000 �500
750 750 750 750 750 750 750 750 750 750 �000 �000 �000 �000 �000 �000
8 8 8 8 8 8 8 8 8 �� �� �� �� �� �� ��
... for maximum operational voltage
�
INS160 INS250-100
INS250-160
INS250-200
INS250 INS320 INS400 INS500 INS630 INS630b INS800 INS1000 INS1250 INS1600 INS2000 INS2500
� �� �60 �00 �60 �00 �50 3�0 400 500 630 630 800 �000 ��50 �450/ �600 (2) �000 (3) �500 (3)
� �� �60 �00 �60 �00 �50 3�0 400 500 630 630 800 �000 ��50 ��50/ �600 (2) �000 (3) �500 (3)
���
� � �� �60 �00 �60 �00 �50 3�0 400 500 630 630 800 �000 ��50 ��50 - -
� � �� �60 �00 �60 �00 �50 3�0 400 500 630 630 800 �000 ��50 ��50 - -
�00 �00 �60 �00 �50 3�0 400 500 630 630 800 �000 ��50 ��50 - -
Identical performance up to 500/690 V
... from 100 to 630 A, with identical performance
The entire range has been fully certified IEC 60947-1, IEC 60947-3 and EN 60947-1, EN 60947-3. Certification was carried out within the framework of the LOVAG agreement by independent certification organisations
Marine certification is underway
b
b
�
Certain ratings are UL listed (UL 489 listed for the switch part) for markets requiring such certification.b
8
Presentation Designed to work
INS for positive contact indication and INV for visible break
0594
87R
a-33
A mechanical system ensures that the position of the handle always reflects the position of the main contacts. With positive contact indication, Schneider Electric guarantees optimum safety for all users of the Interpact range.
0594
9�R
a-33
The physical separation of the main contacts is directly visible through a transparent cover.With this visible break function in addition to positive contact indication, the Interpact INV range offers double safety.
Rotary, front and lateral handles... a very wide choice.
0566
50a-
�5
E9�
076a
-34
0566
60a-
�7
0566
56a-
4�
0594
87a-
�8
0594
95a-
33
Specially design handles for easy operation
PB
�000
�6a-
47
The interruption of current flowing in high-power circuits is associated with high mechanical forces within small volumes.To facilitate the operation of the Interpact range of switch-disconnectors, Schneider Electric has paid particular attention to the design of the handles.As a result, the Interpact range offers both high performance and easy operation.
9
the way you work
One-piece spreader
0563
84a-
56
INS and INV devices may be equipped with a spreader corresponding to the pitch of the terminals of the next highest frame size, just like Compact NS devices.This one-piece spreader offers improved accessibility and ensures a uniform electrical installation. It may be fitted with all the connection and isolation accessories of the Compact NS device with the next highest frame size.
0559
94a-
�76
�0
Presentation Manual source-changeover systems:
b Easy installation
b Built-in safety
b Automatic interlocking
b Simple operating mechanism
��
solutions for continuous performance
The complete source-changeover assembly makes it possible to transfer between a normal source (N) and a replacement source (R) using a single operating handle
��
Presentation A complete offeringD
B��
7444
13
for all your needs
Power distribution incomers and coupling devices
PB
1007
44a-
47
PB
1000
16a-
47
PB
1012
06-3
0
Masterpact NW25HA. Interpact INS2000. Compact NS1600NA.
Final distribution outgoers and local isolation and control devices
PB
1031
99-1
7
PB
1010
50a-
17
E92
089b
-21
E92
090b
-16
E92
091b
-19
E92
092a
Compact NSX250NA.
Compact NS250NA. Interpact INV250. NG125. Interpact INS80. Vario. Multi 9.
Sub-distribution incomers
PB
1032
71-1
6
PB
1010
44a-
16
E92
085b
-43
E92
086b
-22
E92
087b
-16
Compact NSX400NA.
Compact NS400NA. Interpact INS630 complete source-changeover assembly.
Interpact INV400. NG125.
This international site allows you to access all the Schneider Electric products in just � clicksvia comprehensive range data-sheets, with direct links to:
complete library: technical documents, catalogs, FAQs, brochures…
selection guides from the e-catalog.
product discovery sites andtheir Flash animations.You will also fi nd illustrated overviews, news to which you can subscribe, the list of country contacts…
p
p
p
These technical guides help you comply with installation standards and rules i.e.: the electrical installation guide, the protection guide, the switchboard implementation guide,the technical bookletsand the co-ordination tables all form genuine reference tools for the design of high performance electrical installations.For example, the LV protectionco-ordination guide - discrimination and cascading - optimises choiceof protection and connection devices while also increasing markedly continuity of supplyin the installations.
schneider-electric.com The technical guide
TOOLS
A-�
Interpact INS/INV Functions and characteristics
Presentation 2
General characteristics A-2
Switch-disconnector selection A-6Interpact INS40 to �60 A-6Interpact INS�50-�00 to 630 A-�0Interpact INS630b to �500 A-�4Interpact INV�00 to 630 A-�8Interpact INV630b to �500 A-�3
Complete source-changeover assembly selection A-26Interpact INS�50-�00 to 630 A-�6
Switch-disconnector selection A-30Interpact INS40 to 80 A-30Interpact INS�00 to �60 A-3�Interpact INS�50-�00 to 630 A-3�Interpact INV�00 to 630 A-3�Interpact INS3�0 to 630 A-33Interpact INV3�0 to 630 A-33Interpact INS630b to �600 A-34Interpact INV630b to �600 A-34Interpact INS�000 to �500 A-35Interpact INV�000 to �500 A-35
Electrical and mechanical accessories A-36
Manual source-changeover systems A-40
Connection accessories A-42
Installation A-52Installation recommendations B-1Dimensions and connection C-1Additional characteristics D-1Catalogue numbers E-1
A-�
Functions and characteristics General characteristicsD
B�0
544�
Ith : conventional thermal current.Ui : rated insulation voltage.Uimp : rated impulse-withstand voltage.Ue : rated operational voltage.Ie : rated operational current.
suitable for isolation.
Conformity with standardsInterpact switch-disconnectors and auxiliaries comply with the following standards and international recommendations:
IEC 60947-�: general rulesIEC 60947-3: switches, disconnectors, switch-disconnectors, etc.IEC 60947-5.� and following: control-circuit devices and switching elements;
automatic-control components.In that these standards and recommendations are applied in most countries, Interpact switch-disconnectors and auxiliaries comply with European (EN 60947-�, EN 60947-3, EN 60947-5-�) and the corresponding national standards:
France NFGermany VDEUnited Kingdom BSAustralia ASItaly CEI.
Interpact switch-disconnectors are suitable for the control of machine-tools in that they comply with French standard NF C 79-�30 and with the recommendations issued by the CNOMO organisation.
Installation in class II switchboardsAll Interpact INS and INV switch-disconnectors are class II front-face devices. They may be installed through the door of class II switchboards (as per standard IEC 60664) without downgrading switchboard insulation. Installation requires no special operations even when the switch-disconnector is equipped with rotary handles.
Environmental withstand capacity (tropicalisation)Interpact INS/INV switch-disconnectors meet the environmental requirements of the following standards:
IEC 60068-�-� - dry cold (-55 °C)IEC 60068-�-� - dry heat (+85 °C)IEC 60068-�-30 - damp heat (95 % relative humidity at +55 °C)IEC 68-�-5� (level �) - salt mist.
Degree of pollutionThe Interpact range is certified for operation in pollution-degree 3 environments as defined by IEC standard 60947 for industrial environments.
Ambient temperatureOperating-temperature range
Interpact INS and INV switch-disconnectors may be used between -�5 °C and +70 °C
Switch-disconnectors should be put into service under the normal, ambient operating temperatures indicated above. Exceptionally, they may be put into service when the ambient temperature is between -35 °C and -�5 °C.Storage-temperature rangeInterpact INS and INV switch-disconnectors may be stored in their original packing between -50 °C and +85 °C.
Environmental protectionInterpact INS and INV switch-disconnectors take into account important concerns for environmental protection. Most components are recyclable. Insulating parts making up the Interpact INS and INV switch-disconnectors are marked as specified in applicable environmental standards.
bbb
bbbbb
bbbb
b
b
A-3
General characteristicsFunctions and characteristics
AltitudeInterpact INS and INV switch-disconnectors are designed to operate at their rated values at altitudes under �000 metres.Above �000 metres, the changes in the characteristics of the ambient air (electrical resistance, cooling capacity) result in a reduction of the characteristics below. Altitude (m) 2000 3000 4000 5000
Dielectric resistance voltage (V) 3500 3�50 �500 ��00Rated insulation voltage (V) 750 700 600 500Maximum utilisation voltage (V) 690 550 480 4�0Rated current (A) at 60 °C � x In 0 96 In 0.93 In 0.9 In
VibrationsInterpact INS and INV switch-disconnectors are guaranteed against electromagnetic or mechanical v brations.Tests are carried out in compliance with standard IEC 68-�-6 for the levels required by merchant-marine inspection organisations (Veritas, Lloyd’s, etc.):
� to �3.� Hz: amplitude ±� mm�3.� to �00 Hz: constant acceleration 0.7 g.
Excessive vibration may cause tripping, breaks in connections or damage to mechanical parts.
Electromagnetic compatibilityInterpact INS and INV switch-disconnectors are protected against:
overvoltages caused by devices that generate electromagnetic disturbancesovervoltages caused by atmospheric disturbances or by a distribution-system
outage (e.g. failure of a lighting system) and devices emitting radio waves (radios, walkie-talkies, radar, etc.).Interpact INS and INV switch-disconnectors comply with the following electromagnetic-compatibility standards:
IEC/EN 6�000-4-� - electrostatic immunity discharge testIEC/EN 61000-4-3 - electromagnetic-field immunity testIEC/EN 6�000-4-4 - electrical fast transient/burst immunity testIEC/EN 6�000-4-5 - surge immunity testIEC/EN 6�000-4-6 - immunity to conducted disturbances, induced by
radiofrequency fieldsCISPR �� - radio-frequency conducted and radiated emission tests required for
CE markingEN 6�000-6-� - immunity standard for industrial environmentsEN 5008�-�-� - emissions in commercial and industrial environments.
Degree of protectionInterpact INS and INV switch-disconnectors offer the following protection characteristics depending on the installation conditions:
IP: degree of protection (standard IEC 605�9)IK: protection against external mechanical impacts (standard EN 50�0�).
bb
bb
bbbbb
b
vv
bb
IP40 IK07 IP40 IK07 IP55 IK08
DB
�054
43
DB
�054
44
DB
�054
45
Bare switch-disconnector with terminal shields.
Switch-disconnector in cabinet or enclosure(direct handle).
Switch-disconnector in cabinet or enclosure(extended handle).
A-4
General characteristicsFunctions and characteristics05
9487
Ra-
50
Suitable for isolation with positive contact indication
DB
�054
38
All Interpact switch-disconnectors are suitable for isolation as defined in IEC standards 60947-� and 3:
The isolation position corresponds to the O (OFF) positionThe operating handle cannot indicate the OFF position unless the contacts are
actually openPadlocking in the OFF position is not possible unless the contacts are actually
open.
Installation of an extended handle does not alter the suitability for isolation. The isolation function is certified by tests guaranteeing:
The mechanical reliability of the position-indication systemThe absence of leakage currentsOvervoltage withstand capacity between upstream and downstream connections.
Suitable for isolation with visible breakThe physical separation of the main contacts is directly visible through a transparent cover.The Interpact INV range offers both positive contact indication and visible break.
bb
b
bbb
Suitable for isolation with positive contact indication.
0594
9�R
a-5�
Suitable for isolation with visible break.
0566
5�a-
47
Emergency-off switch disconnectorThis switch-disconnector can be used as an emergency-off device. For this application, it must be easily visible, accessible and identifiable (see standards and rules concerning the safety of machines VDE 0660, VDE 0��3, CNOMO, etc.).For easy identification, the emergency-off switch-disconnector uses special colours stipulated by the standards and different from those of the standard version:
Yellow for the front face of the deviceRed for the handle.
The electrical and mechanical performance characteristics of Interpact emergency-off switch-disconnector are the same as those of the standard version.The emergency-off switch-disconnectors are available in positive contact indication and visible-break versions.
bb
INS250 emergency-off switch-disconnector.
0566
54a-
47
INV250 emergency-off switch-disconnector.
A-5
A-6
Functions and characteristics Switch-disconnector selectionInterpact INS40 to 160
Interpact INS switch-disconnectorsNumber of polesElectrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3
Conventional thermal current (A) Ith at 60 °C � �� �Conventional thermal current in enclosure Ithe at 60 °C � �� �Rated insulation level (V) Ui AC 50/60 HzImpulse-withstand voltage (kV) UimpRated operational voltage (V) Ue AC 50/60 Hz
DC � � � � � �Rated operational voltage AC�0 and DC�0 (V) AC 50/60 HzRated operational current (A) Ie Electrical AC 50/60 Hz
��0-�40 V � � �� �� � �380-4�5 V � � � �� �� � �440-480 V (1) � � �� �� � �500 V � � � �� �� � �660-690 V � �� � �
Electrical DC��5 V (�P in series) � � �� �� � ��50 V (4P in series) � � �� �� � �
Rated operational power AC�3 (kW) Electrical AC 50/60 Hz��0-�40 V �� � �� ���30 V (NEMA) � � ��380-4�5 V �440 V ��480 V (NEMA) ��500-5�5 V � �� �� ��660-690 V
Rated duties Uninterrupted dutyIntermittent duty �� �� �� �� �� ��
Short-circuit making capacity (kA peak) Icm Min. (switch-disconnector alone) � � � � � �Max. (with upstream protection circuit breaker)
� � �
Short-time withstand current (A rms) Icw � s3 s � � � � � ��0 s �� �� ��30 s � � �
Suitability for isolationDurability (O-C cycles) Mechanical � � � � � �
Electrical AC 50/60 Hz��0-�40 V � � � � � � � � � � � �380-4�5 V � � � � � � � � � � � �440 V � � � � � � � � � � � �500 V � � � � � � � � � � � �690 V � � � � � �
Electrical DC�50 V � � � � � � � � � � � �
Positive contact indication Visible breakEmergency-off switch disconnectorDegree of pollutionUpstream protection
See the “Additional characteristics” page D-1..(1) Suitable for 480 V NEMA.
05��
64a-
38
Interpact INS80 switch-disconnector.
059�
03a-
38
Interpact INS40 emergency-off switch-disconnector.
05��
68a-
50
Interpact INS160 switch-disconnector.
059�
0�a-
50
Interpact INS160 emergency-off switch-disconnector.
A-7
Switch-disconnector selectionInterpact INS40 to 160
Functions and characteristics
INS40 INS63 INS80 INS100 INS125 INS160 3-4 3-4 3-4 3-4 3-4 3-4
40 63 80 �00 ��5 �60 40 63 80 �00 ��5 �60
690 690 690 750 750 750 8 8 8 8 8 8
500 500 500 690 690 690�50 �50 �50 �50 �50 �50
� � 690 690 690 750 750 750 AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A
�� � 40 40 63 63 80 80 �00 �00 ��5 ��5 �60 �60� 40 40 63 63 80 7� �00 �00 ��5 ��5 �60 �60
40 40 63 63 80 63 �00 �00 ��5 ��5 �60 �60 40 3� 63 40 80 40 �00 �00 ��5 ��5 �60 �60
- - - - - - �00 63 ��5 80 �60 �00 DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A
�� � 40 40 63 63 80 80 �00 �00 ��5 ��5 �60 �60� 40 40 63 63 80 80 �00 �00 ��5 ��5 �60 �60
� �� � �� �5 �� �� 37 45� 7,5 �5 �5 �� 37 45
� �0 30 37 45 55 75 �� 30 37 55 55 90 �� 30 30 55 75 90
� �8,5 �� �� 55 75 ��0 - - - 55 75 90
b b b b b b Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 %
�5 �5 �5 �0 �0 �0
75 75 75 �54 �54 �54
� 3000 3000 3000 5500 5500 5500 �730 �730 �730 3�75 3�75 3�75
� 670 670 670 ��30 ��30 ��30 550 550 550 �000 �000 �000
b b b b b b �0000 �0000 �0000 �5000 �5000 �5000
AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A�� � �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500
� �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 - - - - - - �500 �500 �500 �500 �500 �500
DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A� �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500
b b b b b b - - - - - -
b b b b b b 3 3 3 3 3 3
� � - - - - - -
A-8
Functions and characteristics Switch-disconnector selectionInterpact INS40 to 160
Interpact INS switch-disconnectorsInstallation
Fixed, front connectionFixed, rear connectionOn symmetrical railsOn a backplateConnection
By cables To bare cable connectorsBy cables with lugs Directly to terminals
To spreadersTo vertical-connection adapters via cable-lug adapters
Flat-facing bars Directly to terminals To spreaders
Edgewise bars To vertical-connection adaptersIndication and measurement auxiliaries
Auxiliary contactsVoltage-presence indicatorCurrent-transformer moduleAmmeter moduleControl, locking and interlocking
Control Direct front rotary handleExtended front rotary handleDirect lateral rotary handleExtended lateral rotary handle
Locking By keylockBy padlocks
Interlocking By keylockMechanical
Complete source-changeover assemblyOperating torque (Nm) (typical value for 3-4 poles with front handle) � � � � � � � � �Installation and connection accessories
Bare cable connectorsRear connectorsTerminal extensionsSpreadersOne-piece spreaderTerminal shroudsTerminal shieldsInterphase-barrierFront panel escutcheonsCoupling accessoriesTightening torque for electrical connections (Nm)Dimensions and weights
Overall dimensions H x W x D (mm) 3 poles � � � � � � � � � � � �4 poles � � � � � � � � � � � �
Approximate weight (kg) 3 poles4 poles
Enclosure dimensions for Ithe
DB
�054
�3
H x W x D (mm) � �� � �� � �� � � � � � �
A-9
Switch-disconnector selectionInterpact INS40 to 160
Functions and characteristics
INS40 INS63 INS80 INS100 INS125 INS160
b b b b b b - - - b b b
b b b - - - b b b b b b
b b b b b b - - - b b b
- - - - - - - - - - - -
b b b b b b - - - - - -
- - - - - -
b b b b b b - - - - - -
- - - - - - - - - - - -
b b b b b b
b b b b b b b b b b b b
b b b b b b - - - - - - b b b b b b - - - - - -
b b b b b b - - - - - - 0.7 < Nm < �.3 0.7 < Nm < �.3 0.7 < Nm < �.3 �.4 < Nm < � �.4 < Nm < � �.4 < Nm < �
b b b b b b - - - - - -
- - - - - -- - - - - -
- - - - - - b b b b b b b b b b b b
b b b b b b - - - - - -
- - - - - - 8 8 8 8 8 8
85 x 90 x 6�.5 85 x 90 x 6�.5 85 x 90 x 6�.5 �00 x �35 x 6�.5 �00 x �35 x 6�.5 �00 x �35 x 6�.5
85 x 90 x 6�.5 85 x 90 x 6�.5 85 x 90 x 6�.5 �00 x �35 x 6�.5 �00 x �35 x 6�.5 �00 x �35 x 6�.5 0.5 0.5 0.5 0.8 0.8 0.8
0.6 0.6 0.6 0.9 0.9 0.9
��
�90 x ��5 x 55 �90 x ��5 x 55 �90 x ��5 x 55 �60 x �60 x 55 �60 x �60 x 55 �60 x �60 x 55
A-�0
Functions and characteristics Switch-disconnector selectionInterpact INS250-100 to 630
Interpact INS switch-disconnectorsNumber of polesElectrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3
Conventional thermal current (A) Ith at 60 °C � � � � �Conventional thermal current in enclosure Ithe at 60 °C � � � � � Rated insulation level (V) Ui AC 50/60 HzImpulse-withstand voltage (kV) UimpRated operational voltage (V) Ue AC 50/60 Hz
DC � � � � � � � �Rated operational voltage AC�0 and DC�0 (V) AC 50/60 HzRated operational current (A) Ie Electrical AC 50/60 Hz
��0-�40 V � � � � � � � � � �380-4�5 V � � � � � � � � � �440-480 V (1) � � � � � � � � � �500-5�5 V � � � � � � � � � �660-690 V � � � � � � � � � �
Electrical DC��5 V (�P in series) � � � � � � � � � ��50 V (4P in series) � � � � � � � � � �
Rated operational power AC�3 (kW) Electrical AC 50/60 Hz��0-�40 V �� �� � � ��30 V (NEMA) �� �� � �380-4�5 V � � � � � �440 V �� � � �� �480 V (NEMA) �� � � �� �500-5�5 V �� � � � �� �660-690 V � �� �
Rated duties Uninterrupted dutyIntermittent duty �� �� �� �� �� �� �� ��
Short-circuit making capacity (kA peak) Icm Min. (switch-disconnector alone)Max. (with upstream protection circuit breaker)
Short-time withstand current (A rms) Icw � s � � � �3 s �� �� �� ���0 s �� �� �� ��30 s � � � �
Suitability for isolationDurability (O-C cycles) Mechanical � � � � � � � �
Electrical AC 50/60 Hz440 V � � � � � � � � � � � � � � � �500 V � � � � � � � � � � � � � � � �690 V � � � � � � � � � � � � � � � �
Electrical DC�50 V � � � � � � � � � � � � �
Positive contact indicationVisible breakEmergency-off switch disconnectorDegree of pollutionUpstream protection
See the “Additional characteristics” page D-1.(1) Suitable for 480 V NEMA.(2) 550 A (DC).
0566
48a-
4�
Interpact INS250 switch-disconnector.
0566
5�a-
4�
Interpact INS250 emergency-off switch-disconnector.
0594
87a-
54
Interpact INS400 switch-disconnector.
0594
88a-
54
Interpact INS400 emergency-off switch-disconnector.
A-��
Switch-disconnector selectionInterpact INS250-100 to 630
Functions and characteristics
INS250-100 INS250-160 INS250-200 INS250 INS320 INS400 INS500 INS630 3-4 3-4 3-4 3-4 3-4 3-4 3-4 3-4
�00 �60 �00 �50 3�0 400 500 630 �00 �60 �00 �50 3�0 400 500 630 (2)
750 750 750 750 750 750 750 750 8 8 8 8 8 8 8 8
690 690 690 690 690 690 690 690�50 �50 �50 �50 �50 �50 �50 �50
� � 750 750 750 750 750 750 750 750 AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A
�� � �00 �00 �60 �60 �00 �00 �50 �50 3�0 3�0 400 400 500 500 630 630� �00 �00 �60 �60 �00 �00 �50 �50 3�0 3�0 400 400 500 500 630 630
�00 �00 �60 �60 �00 �00 �50 �50 3�0 3�0 400 400 500 500 630 630� �00 �00 �60 �60 �00 �00 �50 �50 3�0 3�0 400 400 500 500 630 630
�00 �00 �60 �60 �00 �00 �50 �50 3�0 3�0 400 400 500 500 630 630 DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC23B
�� � �00 �00 �60 �60 �00 �00 �50 �50 3�0 3�0 400 400 500 500 550 550 630� �00 �00 �60 �60 �00 �00 �50 �50 3�0 3�0 400 400 500 500 550 550 630
� �� � �� 45 55 75 90 ��0 �3� �00� �� 45 55 75 90 ��0 �50 �00
� 45 75 90 �3� �60 �00 �50 3�5 55 90 ��0 �50 �85 ��0 �50 400 55 90 ��0 �50 �85 ��0 �50 375
� 55 ��0 �3� �60 ��0 �50 355 400 55 90 �60 ��0 �50 400 500 560
b b b b b b b b Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 %
30 30 30 30 50 50 50 50
330 330 330 330 330 330 330 330
� 8500 8500 8500 8500 �0000 �0000 �0000 �0000 4900 4900 4900 4900 ��500 ��500 ��500 ��500
� ��00 ��00 ��00 ��00 4900 4900 4900 4900 �800 �800 �800 �800 4000 4000 4000 4000
b b b b b b b b �5000 �5000 �5000 �5000 �0000 �0000 �0000 �0000
AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500
DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC23A DC23B DC23A DC23B DC23A DC23B DC23A DC23B� �500 �500 �500 �500 �500 �500 �500 �500 �000 - �000 - �000 - �000 �00
b b b b b b b b - - - - - - - -
b b b b b b b b 3 3 3 3 3 3 3 3
� � - - - - - - - -
A-��
Interpact INS switch-disconnectorsInstallation
Fixed, front connectionFixed, rear connectionOn symmetrical railsOn a backplateConnection
By cables To bare cable connectorsBy cables with lugs Directly to terminals
To spreadersTo vertical-connection adapters via cable-lug adapters
Flat-facing bars Directly to terminalsTo spreaders
Edgewise bars To vertical-connection adaptersIndication and measurement auxiliariesAuxiliary contactsVoltage-presence indicatorCurrent-transformer moduleAmmeter moduleControl, locking and interlockingControl Direct front rotary handle
Extended front rotary handleDirect lateral rotary handleExtended lateral rotary handle
Locking By keylockBy padlocks
Interlocking By keylockMechanical
Complete source-changeover assemblyOperating torque (Nm) (typical value for 3-4 poles with front handle) � � � � � � � � � � � �Installation and connection accessories
Bare cable connectorsRear connectorsTerminal extensionsSpreadersOne-piece spreaderTerminal shroudsTerminal shieldsInterphase-barrierFront panel escutcheonsCoupling accessoriesTightening torque for electrical connections (Nm) � � � �Dimensions and weights
Overall dimensions H x W x D (mm) 3 poles � � � � � � � � � � � � � � � � � � � �4 poles � � � � � � � � � � � � � � � � � � � �
Approximate weight (kg) 3 poles � � � �4 poles � � � � � � � �
Enclosure dimensions for Ithe
DB
�054
�3
H x W x D (mm) � � � � � � � �
Functions and characteristics Switch-disconnector selectionInterpact INS250-100 to 630
A-�3
INS250-100 INS250-160 INS250-200 INS250 INS320 INS400 INS500 INS630
b b b b b b b b b b b b b b b b
- - - - - - - - b b b b b b b b
b b b b b b b b b b b b b b b b
b b b b b b b b - - - - - - - -
b b b b b b b b b b b b b b b b
- - - - b b b b
b b b b b b b b b b b b b b b b
b b b b b b b b b b b b b b b b
b b b b b b b b
b b b b b b b b b b b b - - - -
b b b b - - - - b b b b b b b b b b b b b b b b b b b b b b b b
b b b b b b b b b b b b b b b b 5 < Nm < 6.� 5 < Nm < 6.� 5 < Nm < 6.� 5 < Nm < 6.� �3 5 < Nm < �6.5 �3.5 < Nm < �6.5 �3.5 < Nm < �6.5 �3.5 < Nm < �6.5
b b b b b b b b b b b b b b b b
b b b b b b b bb b b b b b b b
b b b b - - - - - - - - - - - - b b b b b b b b
b b b b b b b b b b b b b b b b
b b b b b b b b �5 �5 �5 �5 50 50 50 50
�36 x �40 x 96 �36 x �40 x 96 �36 x �40 x 96 �36 x �40 x 96 �05 x �85 x �30 �05 x �85 x �30 �05 x �85 x �30 �05 x �85 x �30
�36 x �40 x 96 �36 x �40 x 96 �36 x �40 x 96 �36 x �40 x 96 �05 x �85 x �30 �05 x �85 x �30 �05 x �85 x �30 �05 x �85 x �30 � � � � 4.6 4.6 4.6 4.6
�.� � � �.� �.� 4.9 4.9 4.9 4.9
��
400 x 300 x �00 400 x 300 x �00 400 x 300 x �00 400 x 300 x �00 600 x 400 x �00 600 x 400 x �00 600 x 400 x �00 600 x 400 x �00
Switch-disconnector selectionInterpact INS250-100 to 630
Functions and characteristics
A-�4
Functions and characteristics Switch-disconnector selectionInterpact INS630b to 2500
Interpact INS switch-disconnectorsNumber of polesElectrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3
Conventional thermal current (A) Ith at 60 °C � �� � � �Conventional thermal current in enclosure Ithe at 60 °C � �� � � �Rated insulation level (V) Ui AC 50/60 Hz � � � � � � �Impulse-withstand voltage (kV) Uimp �� �� �� �� �� �� ��Rated operational voltage (V) Ue AC 50/60 Hz
DC � � � � � � �Rated operational voltage AC�0 and DC�0 (V) AC 50/60 HzRated operational current (A) Ie Electrical AC 50/60 Hz
��0-�40 V � � � �� �� �� � � �� � � � �� �
380-4�5 V � � � �� �� �� � � �� � � � �� �
440-480 V (1) � � � �� �� �� � � �� � � � ��� ��
500-5�5 V � � � �� �� �� � � �� � � � ��� ��
660-690 V � � � �� �� �� � � �� � � � ��� ��
Electrical DC��5 V (�P in series) � � � � � � � � � � � � �� � �� � �� � � � � � � � � � � � � � � ��50 V (4P in series) � � � �� �� �� � � � � � � �
Rated operational power AC�3 (kW) Electrical AC 50/60 Hz��0-�40 V � � �380-400 V � �4�5 V500-5�5 V �660-690 V � �
Rated duties Uninterrupted dutyIntermittent duty �� �� �� �� �� �� ��
Short-circuit making capacity (kA peak) Icm Min. (switch-disconnector alone) � �Max. (with upstream protection circuit breaker)
Short-time withstand current (kA rms) Icw 0.5 s0.8 s � � � � �� s3 s � � � � ��0 s � � � � � � �30 s �� ��
Suitability for isolationDurability (O-C cycles) Mechanical
Electrical AC 50/60 Hz
��0-�40 V � � � � � � � � �
380-4�5 V � � � � � � � � �
440-480 V (1) � � � � � � � � �
500-5�5 V � � � � � � � � �
660-690 V � � � � � � � � �
Electrical DC��5 V (�P) � � � � � � ��50 V (4P) � � � � � � �
Positive contact indicationVisible breakEmergency-off switch disconnectorDegree of pollutionUpstream protection
See the "Additional characteristics" page D-1.(1) Suitable for 480 V NEMA.(2) For vertical connection busbars only. For horizontal connection busbars, see derating charts in “Installation recommendations” see p. B-22.
PB
�000
�6a-
55
Interpact INS1600 switch-disconnector.
PB
�000
�8a-
55
Interpact INS1600 emergency-off switch-disconnector.
PB
�000
�0a-
65
Interpact INS2500 switch-disconnector.
A-�5
Switch-disconnector selectionInterpact INS630b to 2500
Functions and characteristics
INS630b INS800 INS1000 INS1250 INS1600 INS2000 INS2500 3-4 3-4 3-4 3-4 3-4 3-4 3-4
630 800 �000 ��50 �600 (2) �000 �500 630 800 �000 ��50 �600 (2) �000 �500
�000 �000 �000 �000 �000 �000 �000 �� �� �� �� �� �� ��
690 690 690 690 690 690 690�50 �50 �50 �50 �50 �50 �50
� � 800 800 800 800 800 800 800 AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21B AC22B AC23A AC21B AC22B AC23B AC21B AC22B AC23B
AC21A AC22A�� � 630 630 630 800 800 800 �000 �000 �000 ��50 ��50 ��50 �600 �600 ��50 �000 �000 - �500 �500 -
�450 �450� 630 630 630 800 800 800 �000 �000 �000 ��50 ��50 ��50 �600 �600 ��50 �000 �000 - �500 �500 -
�450 �450 630 630 630 800 800 800 �000 �000 �000 ��50 ��50 ��50 �600 �600 ��50 �000 �000 - �500 �500 -
��50 ��50� 630 630 630 800 800 800 �000 �000 �000 ��50 ��50 ��50 �600 �600 ��50 �000 �000 - �500 �500 -
��50 ��50 630 630 630 800 800 800 �000 �000 �000 ��50 ��50 ��50 �600 �600 ��50 �000 �000 - �500 �500 -
��50 ��50 DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21B DC22B DC23B DC21B DC22B DC23B
�� � 630/� 630/� 630/� 800/� 800/� 800/� �000/� �000/� �000/� ��50/� ��50/� ��50/� �600/� �600/� �600/� �000/� �000/� - �500/� �500/� -� 630/4 630/4 630/4 800/4 800/4 800/4 �000/4 �000/4 �000/4 ��50/4 ��50/4 ��50/4 �600/4 �600/4 �600/4 �000/4 �000/4 - �500/4 �500/4 -
� �� � �50 �50 3�5 400 400 - -
400 400 560 7�0 7�0 - -� 500 500 630 800 800 - -
� 560 560 7�0 900 900 - - 7�0 7�0 900 - - - -
b b b b b b b Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 %
75 75 75 75 75 �05 �05
330 330 330 330 330 330 330
50 50 50 50 50 50 50 4� 4� 4� 4� 4� 50 50
� 35 35 35 35 35 50 50 �0 �0 �0 �0 �0 30 30
� �0 �0 �0 �0 �0 �3 �3 8 8 8 8 8 �� ��
b b b b b b b 5000 3000 3000 3000 3000 3000 3000
AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21B AC22B AC23A AC21B AC22B AC23B AC21B AC22B AC23BAC21A AC22A
�� � �000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500
� �000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500
�000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500
� �000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500
�000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500
DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23B DC21B DC22B DC23B DC21B DC22B DC23B�� � �000 �000 �000 500 500 500 500 500 500 500 500 500 500 500 500 �00 �00 - �00 �00 -� �000 �000 �000 500 500 500 500 500 500 500 500 500 500 500 500 �00 �00 - �00 �00 -
b b b b b b b - - - - - - -
b b b b b - - 3 3 3 3 3 3 3
� � � - - - - - - -
A-�6
Interpact INS switch-disconnectorsInstallation
Fixed, front connectionFixed, rear connectionOn symmetrical railsOn a backplateConnection
By cables To bare cable connectorsBy cables with lugs Directly to terminals
To spreadersTo vertical-connection adapters via cable-lug adapters
Flat-facing bars Directly to terminalsTo spreaders
Edgewise bars To vertical-connection adaptersIndication and measurement auxiliaries
Auxiliary contactsVoltage-presence indicatorCurrent-transformer moduleAmmeter moduleControl, locking and interlocking
Control Direct front rotary handleExtended front rotary handleDirect lateral rotary handleExtended lateral rotary handle
Locking By keylockBy padlocks
Interlocking By keylockMechanical
Complete source-changeover assemblyOperating torque (Nm) (typical value for 3-4 poles with front handle)Installation and connection accessories
Bare cable connectorsRear connectorsTerminal extensionsSpreadersOne-piece spreaderTerminal shroudsTerminal shieldsInterphase-barrierFront panel escutcheonsCoupling accessoriesTightening torque for electrical connections (Nm)Dimensions and weights
Overall dimensions H x W x D (mm) 3 poles � � � � � �� ��4 poles � � � � � � � � � � � �� � ��
Approximate weight (kg) 3 poles � � � � �4 poles � � � � �
Enclosure dimensions for Ithe
DB
�054
�3
H x W x D (mm)
Functions and characteristics Switch-disconnector selectionInterpact INS630b to 2500
A-�7
INS630b INS800 INS1000 INS1250 INS1600 INS2000 INS2500
b b b b b b b b b b b b b b
- - - - - - - b b b b b b b
- - - - - - - - - - - - b b
- - - - - - - b b b b b - -
b b b b b b b b b b b b - -
b b b b b - -
b b b b b b b - - - - - - -
- - - - - - - - - - - - - -
b b b b b b b
b b b b b b b - - - - - - -
- - - - - - - b b b b b b b b b b b b b b b b b b b b b
- - - - - - - - - - - - - - 30 30 30 30 30 60 60
- - - - - - - - - - - - - -
b b b b b b bb b b b b b b
- - - - - - - - - - - - - - b b b b b b b
b b b b b b b b b b b b b b
- - - - - - -
50 50 50 50 50 50 50
300 x 340 x �46 5 300 x 340 x �46.5 300 x 340 x �46.5 300 x 340 x �46.5 300 x 340 x �46.5 440 x 347.5 x ��7.5 440 x 347.5 x ��7.5
300 x 4�0 x �46 5 300 x 4�0 x �46.5 300 x 4�0 x �46.5 300 x 4�0 x �46.5 300 x 4�0 x �46.5 440 x 46�.5 x ��7.5 440 x 46�.5 x ��7.5 �4 �4 �4 �4 �4 35 35
�8 �8 �8 �8 �8 45 45
��
- - - - - - -
Functions and characteristics Switch-disconnector selectionInterpact INS630b to 2500
A-�8
Functions and characteristics Switch-disconnector selectionInterpact INV100 to 630
Interpact INV switch-disconnectorsNumber of polesElectrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3
Conventional thermal current (A) Ith at 60 °C � � � � �Conventional thermal current in enclosure Ithe at 60 °C � � � � �
Rated insulation level (V) Ui AC 50/60 HzImpulse-withstand voltage (kV) UimpRated operational voltage (V) Ue AC 50/60 Hz
DC � � � � � � � �Rated operational voltage AC�0 and DC�0 (V) AC 50/60 HzRated operational current (A) Ie Electrical AC 50/60 Hz
��0-�40 V � � � � � � � � � � � � � � �380-4�5 V � � � � � � � � � � � � � � �440-480 V (1) � � � � � � � � � � � � � � �500-5�5 V � � � � � � � � � � � � � � �660-690 V � � � � � � � � � � � � � � �
Electrical DC
��5 V (�P in series) � � � � � � � � � � � � � � ��50 V (4P in series) � � � � � � � � � � � � � � �
Rated operational power AC�3 (kW) Electrical AC 50/60 Hz��0-�40 V �� �� � � ��30 V (NEMA) �� �� � �380-4�5 V � � � � � �440 V �� � � �� �480 V (NEMA) �� � � �� �500-5�5 V �� � � � � �� �660-690 V � � �
Rated duties Uninterrupted dutyIntermittent duty �� �� �� �� �� �� �� ��
Short-circuit making capacity (kA peak) Icm Min. (switch-disconnector alone)Max. (with upstream protection circuit breaker)
Short-time withstand current (A rms) Icw � s � � � �3 s �� �� �� ���0 s �� �� �� ��30 s � � � �
Suitability for isolationDurability (O-C cycles) Mechanical � � � � � � � �
Electrical AC 50/60 Hz
440 V � � � � � � � � � � � � � � � � � � � �500 V � � � � � � � � � � � � � � � � � � � � �690 V � � � � � � � � � � � � � � � � � � � � �
Electrical DC
�50 V � � � � � � � � � � � � � � � � � � � � �Positive contact indicationVisible breakEmergency-off switch disconnectorDegree of pollutionUpstream protection
See the “Additional characteristics” page D-1.(1) Suitable for 480 V NEMA.(2) 550 A (DC).
0566
50a-
4�
Interpact INV250 switch-disconnector.
0566
54a-
4�
Interpact INV250 emergency-off switch-disconnector.
0594
9�a-
54
Interpact INV400 Std.
0594
93a-
5�
Interpact INV400 emergency-off switch-disconnector.
A-�9
Switch-disconnector selectionInterpact INV100 to 630
Functions and characteristics
INV100 INV160 INV200 INV250 INV320 INV400 INV500 INV630 3-4 3-4 3-4 3-4 3-4 3-4 3-4 3-4
�00 �60 �00 �50 3�0 400 500 630 �00 �60 �00 �50 3�0 400 500 630 (2)
750 750 750 750 750 750 750 750 8 8 8 8 8 8 8 8
690 690 690 690 690 690 690 690�50 �50 �50 �50 �50 �50 �50 �50
� � 750 750 750 750 750 750 750 750 AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A/
AC23B�� � �00 �00 �00 �60 �60 �60 �00 �00 �00 �50 �50 �50 3�0 3�0 3�0 400 400 400 500 500 500 630 630 630/630
� �00 �00 �00 �60 �60 �60 �00 �00 �00 �50 �50 �50 3�0 3�0 3�0 400 400 400 500 500 500 630 630 630/630 �00 �00 �00 �60 �60 �60 �00 �00 �00 �50 �50 �50 3�0 3�0 3�0 400 400 400 500 500 500 630 630 630/630
� �00 �00 �00 �60 �60 �60 �00 �00 �00 �50 �50 �00 3�0 3�0 3�0 400 400 400 500 500 500 630 630 500/630 �00 �00 �00 �60 �60 �60 �00 �00 �00 �50 �50 �00 3�0 3�0 3�0 400 400 400 500 500 500 630 550 500/630
DC21A DC22A DC23B DC21A DC22A DC23B DC21A DC22A DC23B DC21A DC22A DC23B DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A/DC23B
�� � �00 �00 �00 �60 �60 �60 �00 �00 �00 �50 �50 �00 3�0 3�0 3�0 400 400 400 500 500 500 550 550 550/630� �00 �00 �00 �60 �60 �60 �00 �00 �00 �50 �50 �00 3�0 3�0 3�0 400 400 400 500 500 500 550 550 550/630
� �� � �� 45 55 75 90 ��0 �3� �00� �� 45 55 75 90 ��0 �50 �00
� 45 75 90 �3� �60 �00 �50 3�5 55 90 ��0 �50 �85 ��0 �50 400 55 50 ��0 �50 �85 ��0 �50 375
� 55 ��0 �3� �3� ��0 �50 355 400 55 90 �60 �60 �50 400 500 560
b b b b b b b b Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 %
30 30 30 30 50 50 50 50
330 330 330 330 330 330 330 330
� 8500 8500 8500 8500 �0000 �0000 �0000 �0000 4900 4900 4900 4900 ��500 ��500 ��500 ��500
� ��00 ��00 ��00 ��00 4900 4900 4900 4900 �800 �800 �800 �800 4000 4000 4000 4000
b b b b b b b b �5000 �5000 �5000 �5000 �0000 �0000 �0000 �0000
AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A/AC23B
�500 �500 �500 �500 �500 �500 �500 �500 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000 �500 �500 �500 �500 �500 �500 �500 �500 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000/�00 �500 �500 �500 �500 �500 �500 �500 �500 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000/�00
DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A/DC23B
� �500 �500 �500 �500 �500 �500 �500 �500 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000/�00 b b b b b b b b
b b b b b b b b b b b b b b b b
3 3 3 3 3 3 3 3
� � - - - - - - - -
A-�0
Interpact INV switch-disconnectorsInstallation
Fixed, front connectionFixed, rear connectionOn symmetrical railsOn a backplateConnection
By cables To bare cable connectorsBy cables with lugs Directly to terminals
To spreadersTo vertical-connection adapters via cable-lug adapters
Flat-facing bars Directly to terminalsTo spreaders
Edgewise bars To vertical-connection adaptersIndication and measurement auxiliaries
Auxiliary contactsVoltage-presence indicatorCurrent-transformer moduleAmmeter moduleControl, locking and interlocking
Control Direct front rotary handleExtended front rotary handleDirect lateral rotary handleExtended lateral rotary handle
Locking By keylockBy padlocks
Interlocking By keylockMechanical
Complete source-changeover assemblyOperating torque (Nm) (typical value for 3-4 poles with front handle) � � � � � � � � � � � �Installation and connection accessories
Bare cable connectorsRear connectorsTerminal extensionsSpreadersOne-piece spreaderTerminal shroudsTerminal shieldsInterphase-barrierFront panel escutcheonsCoupling accessoriesTightening torque for electrical connections (Nm) � � � �Dimensions and weights
Overall dimensions H x W x D (mm) 3 poles � � � � � � � � � � � � � � � � � � � �4 poles � � � � � � � � � � � � � � � � � � � �
Approximate weight (kg) 3 poles � � � �4 poles � � � � � � � �
Enclosure dimensions for Ithe
db�0
54�3
H x W x D (mm) � � � � � � � �
Functions and characteristics Switch-disconnector selectionInterpact INV100 to 630
A-��
INV100 INV160 INV200 INV250 INV320 INV400 INV500 INV630
b b b b b b b b b b b b b b b b
- - - - - - - - b b b b b b b b
b b b b b b b b b b b b b b b b
b b b b b b b b - - - - - - - -
b b b b b b b b b b b b b b b b
- - - - b b b b
b b b b b b b b b b b b b b b b
b b b b b b b b b b b b b b b b
b b b b b b b b
b b b b b b b b b b b b - - - -
b b b b - - - - b b b b b b b b b b b b b b b b b b b b b b b b
b b b b b b b b - - - - - - - - 5 < Nm < 6.� 5 < Nm < 6.� 5 < Nm < 6.� 5 < Nm < 6.� �3 5 < Nm < �6.5 �3.5 < Nm < �6.5 �3.5 < Nm < �6.5 �3.5 < Nm < �6.5
b b b b b b b b b b b b b b b b
b b b b b b b bb b b b b b b b
b b b b b b b b - - - - - - - - b b b b b b b b
b b b b b b b b b b b b b b b b
b b b b b b b b �5 �5 �5 �5 50 50 50 50
�36 x �40 x 96 �36 x �40 x 96 �36 x �40 x 96 �36 x �40 x 96 �05 x �85 x �30 �05 x �85 x �30 �05 x �85 x �30 �05 x �85 x �30
�36 x �40 x 96 �36 x �40 x 96 �36 x �40 x 96 �36 x �40 x 96 �05 x �85 x �30 �05 x �85 x �30 �05 x �85 x �30 �05 x �85 x �30 � � � � 4.6 4.6 4.6 4.6
�.� � � �.� �.� 4.9 4.9 4.9 4.9
��
400 x 300 x �00 400 x 300 x �00 400 x 300 x �00 400 x 300 x �00 600 x 400 x �00 600 x 400 x �00 600 x 400 x �00 600 x 400 x �00
Functions and characteristics Switch-disconnector selectionInterpact INV100 to 630
A-��
PB
�000
�7a-
55
Interpact INV1600 switch-disconnector.
PB
�000
�9a-
55
Interpact INV1600 emergency-off switch-disconnector.
PB
�000
��a-
65
Interpact INV2500 switch-disconnector.
Switch-disconnector selectionInterpact INV630b to 2500
Functions and characteristics
Interpact INV switch-disconnectorsNumber of polesElectrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3
Conventional thermal current (A) Ith at 60 °C � �� � � �Conventional thermal current in enclosure Ithe at 60 °C � �� � � �Rated insulation level (V) Ui AC 50/60 Hz � � � � � � �Impulse-withstand voltage (kV) Uimp �� �� �� �� �� �� ��Rated operational voltage (V) Ue AC 50/60 Hz
DC � � � � � � �Rated operational voltage AC�0 and DC�0 (V) AC 50/60 HzRated operational current (A) Ie Electrical AC 50/60 Hz
��0-�40 V � � � �� �� �� � � �� � � � �� �
380-4�5 V � � � �� �� �� � � �� � � � �� �
440-480 V (1) � � � �� �� �� � � �� � � � ��� ��
500-5�5 V � � � �� �� �� � � �� � � � ��� ��
660-690 V � � � �� �� �� � � �� � � � ��� ��
Electrical DC��5 V (�P in series) � � � � � � � � � � � � �� � �� � �� � � � � � � � � � � � � � � ��50 V (4P in series) � � � �� �� �� � � � � � � �
Rated operational power AC�3 (kW) Electrical AC 50/60 Hz��0-�40 V � � �380-400 V � �4�5 V500-5�5 V �660-690 V � �
Rated duties Uninterrupted dutyIntermittent duty �� �� �� �� �� �� ��
Short-circuit making capacity (kA peak) Icm Min. (switch-disconnector alone) � �Max. (with upstream protection circuit breaker)
Short-time withstand current (kA rms) Icw 0.5 s0.8 s � � � � �� s3 s � � � � ��0 s � � � � � � �30 s �� ��
Suitability for isolationDurability (O-C cycles) Mechanical
Electrical AC 50/60 Hz
��0-�40 V � � � � � � � � �
380-4�5 V � � � � � � � � �
440-480 V (1) � � � � � � � � �
500-5�5 V � � � � � � � � �
660-690 V � � � � � � � � �
Electrical DC��5 V (�P) � � � � � � ��50 V (4P) � � � � � � �
Positive contact indicationVisible breakEmergency-off switch disconnectorDegree of pollutionUpstream protection
See the "Additional characteristics" page D-1.(1) Suitable for 480 V NEMA.(2) For vertical connection busbars only. For horizontal connection busbars, see derating charts in “Installation recommendations” p. B-22.
A-�3
Functions and characteristics Switch-disconnector selectionInterpact INV630b to 2500
INV630b INV800 INV1000 INV1250 INV1600 INV2000 INV2500 3-4 3-4 3-4 3-4 3-4 3-4 3-4
630 800 �000 ��50 �600 (2) �000 �500 630 800 �000 ��50 �600 (2) �000 �500
�000 �000 �000 �000 �000 �000 �000 �� �� �� �� �� �� ��
690 690 690 690 690 690 690�50 �50 �50 �50 �50 �50 �50
� � 800 800 800 800 800 800 800 AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21B AC22B AC23A AC21B AC22B AC23B AC21B AC22B AC23B
AC21A AC22A�� � 630 630 630 800 800 800 �000 �000 �000 ��50 ��50 ��50 �600 �600 ��50 �000 �000 - �500 �500 -
�450 �450� 630 630 630 800 800 800 �000 �000 �000 ��50 ��50 ��50 �600 �600 ��50 �000 �000 - �500 �500 -
�450 �450 630 630 630 800 800 800 �000 �000 �000 ��50 ��50 ��50 �600 �600 ��50 �000 �000 - �500 �500 -
��50 ��50� 630 630 630 800 800 800 �000 �000 �000 ��50 ��50 ��50 �600 �600 ��50 �000 �000 - �500 �500 -
��50 ��50 630 630 630 800 800 800 �000 �000 �000 ��50 ��50 ��50 �600 �600 ��50 �000 �000 - �500 �500 -
��50 ��50 DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21B DC22B DC23B DC21B DC22B DC23B
�� � 630/� 630/� 630/� 800/� 800/� 800/� �000/� �000/� �000/� ��50/� ��50/� ��50/� �600/� �600/� �600/� �000/� �000/� - �500/� �500/� -� 630/4 630/4 630/4 800/4 800/4 800/4 �000/4 �000/4 �000/4 ��50/4 ��50/4 ��50/4 �600/4 �600/4 �600/4 �000/4 �000/4 - �500/4 �500/4 -
� �� � �50 �50 3�5 400 400 - -
400 400 560 7�0 7�0 - -� 500 500 630 800 800 - -
� 560 560 7�0 900 900 - - 7�0 7�0 900 - - - -
b b b b b b b Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 %
75 75 75 75 75 �05 �05
330 330 330 330 330 330 330
50 50 50 50 50 50 50 4� 4� 4� 4� 4� 50 50
� 35 35 35 35 35 50 50 �0 �0 �0 �0 �0 30 30
� �0 �0 �0 �0 �0 �3 �3 8 8 8 8 8 �� ��
b b b b b b b 5000 3000 3000 3000 3000 3000 3000
AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21B AC22B AC23A AC21B AC22B AC23B AC21B AC22B AC23BAC21A AC22A
�� � �000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500
� �000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500
�000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500
� �000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500
�000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500
DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23B DC21B DC22B DC23B DC21B DC22B DC23B�� � �000 �000 �000 500 500 500 500 500 500 500 500 500 500 500 500 �00 �00 - �00 �00 -� �000 �000 �000 500 500 500 500 500 500 500 500 500 500 500 500 �00 �00 - �00 �00 -
b b b b b b b b b b b b b b
b b b b b - - 3 3 3 3 3 3 3
�� � � - - - - - - -
A-�4
Interpact INV switch-disconnectorsInstallation
Fixed, front connectionFixed, rear connectionOn symmetrical railsOn a backplateConnection
By cables To bare cable connectorsBy cables with lugs Directly to terminals
To spreadersTo vertical-connection adapters via cable-lug adapters
Flat-facing bars Directly to terminalsTo spreaders
Edgewise bars To vertical-connection adaptersIndication and measurement auxiliaries
Auxiliary contactsVoltage-presence indicatorCurrent-transformer moduleAmmeter moduleControl, locking and interlocking
Control Direct front rotary handleExtended front rotary handleDirect lateral rotary handleExtended lateral rotary handle
Locking By keylockBy padlocks
Interlocking By keylockMechanical
Complete source-changeover assemblyOperating torque (Nm) (typical value for 3-4 poles with front handle)Installation and connection accessories
Bare cable connectorsRear connectorsTerminal extensionsSpreadersOne-piece spreaderTerminal shroudsTerminal shieldsInterphase-barrierFront panel escutcheonsCoupling accessoriesTightening torque for electrical connections (Nm)Dimensions and weights
Overall dimensions H x W x D (mm) 3 poles � � � � � �� ��4 poles � � � � � � � � � � � �� � ��
Approximate weight (kg) 3 poles � � � � �4 poles � � � � �
Enclosure dimensions for Ithe
DB
�054
�3
H x W x D (mm)
Functions and characteristics Switch-disconnector selectionInterpact INV630b to 2500
A-�5
INV630b INV800 INV1000 INV1250 INV1600 INV2000 INV2500
b b b b b b b b b b b b b b
- - - - - - - b b b b b b b
- - - - - - - - - - - - b b
- - - - - - - b b b b b - -
b b b b b b b b b b b b - -
b b b b b - -
b b b b b b b - - - - - - -
- - - - - - - - - - - - - -
b b b b b b b
b b b b b b b - - - - - - -
- - - - - - - b b b b b b b b b b b b b b b b b b b b b
- - - - - - - - - - - - - - 30 30 30 30 30 60 60
- - - - - - - - - - - - - -
b b b b b b bb b b b b b b
- - - - - - - - - - - - - - b b b b b b b
b b b b b b b b b b b b b b
- - - - - - -
50 50 50 50 50 50 50
300 x 340 x �46 5 300 x 340 x �46.5 300 x 340 x �46.5 300 x 340 x �46.5 300 x 340 x �46.5 440 x 347.5 x ��7.5 440 x 347.5 x ��7.5
300 x 4�0 x �46 5 300 x 4�0 x �46.5 300 x 4�0 x �46.5 300 x 4�0 x �46.5 300 x 4�0 x �46.5 440 x 46�.5 x ��7.5 440 x 46�.5 x ��7.5 �4 �4 �4 �4 �4 35 35
�8 �8 �8 �8 �8 45 45
��
- - - - - - -
Functions and characteristics Switch-disconnector selectionInterpact INV630b to 2500
A-�6
0566
48a-
4�
Complete source-changeover assembly.
Complete source-changeover assembly selectionInterpact INS250-100 to 630
Functions and characteristics
Interpact INS switch-disconnectorsNumber of polesElectrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3
Conventional thermal current (A) Ith at 60 °C � � � � �Conventional thermal current in enclosure Ithe at 60 °C � � � � �Rated insulation level (V) Ui AC 50/60 HzImpulse-withstand voltage (kV) UimpRated operational voltage (V) Ue AC 50/60 Hz
DC � � � � � � � �Rated operational voltage AC�0 and DC�0 (V) AC 50/60 HzRated operational current (A) Ie Electrical AC 50/60 Hz
��0-�40 V � � � � � � � � � �380-4�5 V � � � � � � � � � �440-480 V (1) � � � � � � � � � �500-5�5 V � � � � � � � � � �660-690 V � � � � � � � � � �
Electrical DC��5 V (�P in series) � � � � � � � � � ��50 V (4P in series) � � � � � � � � � �
Rated duties Uninterrupted dutyIntermittent duty �� �� �� �� �� �� �� ��
Short-circuit making capacity (kA peak) Icm Min. (switch-disconnector alone)Max. (with upstream protection circuit breaker)
Short-time withstand current (A rms) Icw � s � � � �3 s �� �� �� ���0 s �� �� �� ��30 s � � � �
Suitability for isolationDurability (category A) (O - C-O cycles) Mechanical � � � � � � � �
Electrical AC 50/60 Hz440 V � � � � � � � � � � � � � � � �500 V � � � � � � � � � � � � � � � �690 V � � � � � � � � � � � � � � � �
Electrical DC�50 V � � � � � � � � � � � � �
Positive contact indicationVisible breakEmergency-off switch disconnectorDegree of pollutionUpstream protection
See the “Additional characteristics” page D-1.(1) Suitable for 480 V NEMA.
A-�7
Functions and characteristics Complete source-changeover assembly selectionInterpact INS250-100 to 630
INS250-100 INS250-160 INS250-200 INS250 INS320 INS400 INS500 INS630 3-4 3-4 3-4 3-4 3-4 3-4 3-4 3-4
�00 �60 �00 �50 3�0 400 500 630 �00 �60 �00 �50 3�0 400 500 630
750 750 750 750 750 750 750 750 8 8 8 8 8 8 8 8
690 690 690 690 690 690 690 690�50 �50 �50 �50 �50 �50 �50 �50
� � 750 750 750 750 750 750 750 750 AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A
�� � �00 �00 �60 �60 �00 �00 �50 �50 3�0 3�0 400 400 500 500 630 630� �00 �00 �60 �60 �00 �00 �50 �50 3�0 3�0 400 400 500 500 630 630
�00 �00 �60 �60 �00 �00 �50 �50 3�0 3�0 400 400 500 500 630 630� �00 �00 �60 �60 �00 �00 �50 �50 3�0 3�0 400 400 500 500 630 630
�00 �00 �60 �60 �00 �00 �50 �50 3�0 3�0 400 400 500 500 630 630 DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC23B
�� � �00 �00 �60 �60 �00 �00 �50 �50 3�0 3�0 400 400 500 500 550 550 630� �00 �00 �60 �60 �00 �00 �50 �50 3�0 3�0 400 400 500 500 550 550 630
b b b b b b b b Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 % Class ��0 - 60 %
30 30 30 30 50 50 50 50
330 330 330 330 330 330 330 330
� 8500 8500 8500 8500 �0000 �0000 �0000 �0000 4900 4900 4900 4900 ��500 ��500 ��500 ��500
� ��00 ��00 ��00 ��00 4900 4900 4900 4900 �800 �800 �800 �800 4000 4000 4000 4000
b b b b b b b b �5000 �5000 �5000 �5000 �0000 �0000 �0000 �0000
AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500
DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC23A DC23B DC23A DC23B DC23A DC23B DC23A DC23B� �500 �500 �500 �500 �500 �500 �500 �500 �000 - �000 - �000 - �000 �00
b b b b b b b b - - - - - - - -
- - - - - - - - 3 3 3 3 3 3 3 3
� - - - - - - - -
A-�8
Interpact INS switch-disconnectorsInstallation
Fixed, front connectionFixed, rear connectionOn symmetrical railsOn a backplateConnection
By cables To bare cable connectorsBy cables with lugs Directly to terminals
To spreadersTo vertical-connection adapters via cable-lug adapters
Flat-facing bars Directly to terminalsTo spreaders
Edgewise bars To vertical-connection adaptersIndication and measurement auxiliaries
Auxiliary contactsVoltage-presence indicatorCurrent-transformer moduleAmmeter moduleControl, locking and interlocking
Control Direct front rotary handleExtended front rotary handleDirect lateral rotary handleExtended lateral rotary handle
Interlocking By keylockMechanical
Complete source-changeover assemblyOperating torque (Nm) (typical value for 3-4 poles with front handle) � � � � � � � � � � � �Installation and connection accessories
Bare cable connectorsRear connectorsTerminal extensionsSpreadersOne-piece spreaderTerminal shroudsTerminal shieldsInterphase-barrierFront panel escutcheonsCoupling accessoriesTightening torque for electrical connections (Nm) � � � �Dimensions and weights
Overall dimensions H x W x D (mm) 3 poles � � � � � � � � � � � � � � � � � � � � � � � �4 poles � � � � � � � � � � � � � � � � � � � � � � � �
Approximate weight (kg) 3 poles � � � �4 poles � � � �
Functions and characteristics Complete source-changeover assembly selectionInterpact INS250-100 to 630
A-�9
INS250-100 INS250-160 INS250-200 INS250 INS320 INS400 INS500 INS630
b b b b b b b b b b b b b b b b
- - - - - - - - b b b b b b b b
b b b b b b b b b b b b b b b b
b b b b b b b b - - - - - - - -
b b b b b b b b b b b b b b b b
- - - - b b b b
b b b b b b b b b b b b b b b b
b b b b b b b b b b b b b b b b
b b b b b b b b
b b b b b b b b - - - - - - - -
- - - - - - - - b b b b b b b b
b b b b b b b b b b b b b b b b 5 < Nm < 6.� 5 < Nm < 6.� 5 < Nm < 6.� 5 < Nm < 6.� �3 5 < Nm < �6.5 �3.5 < Nm < �6.5 �3.5 < Nm < �6.5 �3.5 < Nm < �6 5
b b b b b b b b b b b b b b b b
b b b b b b b b- - - - - - - -
- - - - - - - - - - - - - - - - b b b b b b b b
b b b b b b b b - - - - - - - -
b b b b b b b b �5 �5 �5 �5 50 50 50 50
�36 x �95 x �3� �36 x �95 x �3� �36 x �95 x �3� �36 x �95 x �3� �05 x 395 x �55 �05 x 395 x �55 �05 x 395 x �55 �05 x 395 x �55
�36 x �95 x �3� �36 x �95 x �3� �36 x �95 x �3� �36 x �95 x �3� �05 x 395 x �55 �05 x 395 x �55 �05 x 395 x �55 �05 x 395 x �55 6.4 6.4 6.4 6.4 �3 5 �3.5 �3.5 �3.5
6.4 6.4 6.4 6.4 �3 5 �3.5 �3.5 �3.5
Functions and characteristics Complete source-changeover assembly selectionInterpact INS250-100 to 630
A-30
Switch-disconnector selectionInterpact INS40 to 80
Functions and characteristicsD
B��
7753
A-3�
Functions and characteristics Switch-disconnector selectionInterpact INS100 to 160
DB
��77
5�
A-3�
Functions and characteristics Switch-disconnector selectionInterpact INS250-100 to 630Interpact INV100 to 630
DB
��77
55
A-33
Functions and characteristics Switch-disconnector selectionInterpact INS320 to 630Interpact INV320 to 630
DB
��77
5�
A-34
Functions and characteristics Switch-disconnector selectionInterpact INS630b to 1600Interpact INV630b to 1600
DB
��77
54
A-35
Functions and characteristics Switch-disconnector selectionInterpact INS2000 to 2500Interpact INV2000 to 2500
DB
��77
56
A-36
Electrical and mechanical accessories
Functions and characteristics05
7355
b-40
Indications and measurementAmmeter moduleFor Interpact INS�50 to 630 and INV�00 to 630.FunctionMeasures and displays the current of each phase (phase selection by a three-position switch on the front) on a dial-type ammeter.Installation
Connects directly to the downstream terminals of the switch-disconnector (except on a INS�50 with a direct handle).
Ammeter clips into module in any of four 90° positions, i.e. can be installed of devices mounted both vertically and horizontally.
Degree of protection: IP40, IK04.Class II insulation between front and power circuits.
Electrical characteristicsAccuracy: class 4.5.
Current-transformer moduleFor Interpact INS�50 to 630 and INV�00 to 630.FunctionThe module enables direct connection of a measurement device such as an ammeter or a Digipact power meter (not supplied).Installation
Connects directly to the downstream terminals of the switch-disconnector.Degree of protection: IP40, IK07.Class II insulation between front and power circuits.Connection via six built-in terminals for cables with a cross-sectional area
of �.5 mm².Electrical characteristics
Current transformer with 5 A secondary winding.Class 3 for the following values of consumed output power.
Accuracy:�00 A rating - �.6 VA�50 A rating - 3 VA�50 A rating - 5 VA400/630 A rating - 8 VA.
Current-transformer module with voltage measurement outputsFor direct connection of a digital power monitoring unit: Power Meter PM700, PM800, etc. (not supplied).Installation
Mounts directly on the downstream terminals of the circuit breaker.Degree of protection: IP40, IK04.Class II insulation of front with respect to the power circuits.Built-in connectors for cables from �.5 to �.5 mm².
Electrical characteristicsRated operational voltage Ue: 530 V.Frequencies of measured values: 50... 60 Hz.Three CTs with 5 A secondary windings for the rated primary current INclass 0.5 to � for rated power consumption values at the output:��5 A, �50 A and �50 A ratings: class � for �.� VA400/600 A rating: class 0.5 for � VAuse a cable of �.5 mm² section up to �.5 m long.Four voltage measurement outputs including protection with automatic resetvoltage measurement output impedance 3500 W ±�5 %, maximum current � mA.
Voltage presence indicatorThe indicator detects and indicates that circuit breaker terminals are supplied with power.Installation
In the long or short terminal shields, via the knockouts.Upstream or downstream of the circuit breaker.Degree of protection, IP40, IK04.
Electrical characteristicsOperates on all networks with voltages ranging from ��0 et 550 V AC.
b
b
bb
bbbb
bb
vvvv
bbbb
bbbv--vbv
bbb
Interpact INV250 with ammeter module.
A-37
Functions and characteristics Electrical and mechanical accessories
0443
14b-
18
DB
1197
06
Auxiliary contacts for Interpact INS and INV
Interpact INS40 to 160.
DB
1197
07
Interpact INS250and INV100 to 250.
DB
1197
08
Interpact INS/INV320 to 630.
DB
1197
09
Interpact INS/INV800 to 1600.
DB
1197
10
Interpact INS/INV2000 to 2500.
Auxiliary contactsInterpact INS and INVOne or four common-point changeover contacts can be used to remote switch-disconnector status information for indications, electrical interlocking, relays, etc.FunctionsEach contact may be used for the following functions:
OF (ON/OFF): indicates the position of the switch-disconnector polesCAM (early-make or early-break function): indicates the position of the handle.
Used in particular for:CAO early-break switch (auxiliary contacts open before the main contacts), used,
for example, to automatically open a circuit breaker or a contactor before opening the Interpact INS
CAF early-make switch (auxiliary contacts close before the main contacts)switching of very small loads. A “low-level” version of the auxiliary contacts exists
for switching very small loads (for example, to control a PLC or electronic circuits).StandardsThe auxiliary contacts comply with international standard IEC 60947-5.1.InstallationThey simply snap in under the auxiliaries cover (supplied as standard) of the switch-disconnector.Insulation Sealable auxiliary shield to protect against direct contact with power circuits.Electrical characteristics of auxiliary contacts for Interpact INS and INV
Standard Low levelRated thermal current (A) 6 5Minimum load 10 mA at 24 V 1 mA at 4 V
AC DC AC DCUtilisation category (IEC 60947-5-1) AC12 AC15 DC12 DC14 AC12 AC15 DC12 DC14Operational current (A) 24 V 6 6 6 1 5 3 5 1
48 V 6 6 2.5 0.2 5 3 2.5 0.2110 V 6 5 0.6 0.05 5 2.5 0.6 0.05200/240 V 6 4 - - 5 2 - -250 V - - 0.3 0.03 5 - 0.3 0.03380/440 V 6 2 - - 5 1.5 - -480 V 6 1.5 - - 5 1 - -660/690 V 6 0.1 - - - - - -
Interpact INS40 to 2500, INV100 to 2500Possible combinations
Interpact OF block CAM block (CAO/CAF)INS40 to 160 - - 2INS250 - - 2INS400 to 630 3 and 1INS630b to 1600 3 and 1INS2000 to 2500 3 and 1
bb
v
vb
A-38
Functions and characteristics Electrical and mechanical accessories
05��
7�b-
40
Interpact INS160 with lateral direct rotary handle.
0566
56b-
68
Interpact INS250 with lateral extended rotary handle.
0594
95b-
64
Interpact INS630 with front extended rotary handle.
0566
5�b-
40
Interpact INS250 emergency-off version with front direct rotary handle.
Rotary handleInterpact INS and INVThere are two types of rotary handle:
direct rotary handleextended rotary handle.
There are two models:standard with a black handlewith a red handle and yellow front for machine-tool control, in accordance with
VDE standard.
INS40-160 INS250 INS/INV INS/INV INS/INVINV100-250 320-630 630b-1600 2000-2500
Standard rotary handleFront direct Standard Standard Standard Standard StandardLateral direct Standard With
conversionNo No No
Front extended Optional Optional Optional Optional OptionalLateral extended Optional (1) Optional No No NoRed and yellow rotary handle for emergency-off switch-disconnectors
Front direct Standard Standard Standard Standard No (2)
Lateral direct Standard With conversion
No No No
Front extended Optional Optional Optional Optional No (2)
Lateral extended Optional (1) (3) Optional (3) No No No(1) Two models for universal enclosures and for Prisma G enclosures.(2) Emergency-off versions not available for INS/INV2000-2500.(3) The basic switch-disconnector must be the emergency-off (red and yellow) version.
Direct rotary handleDegree of protection IP40.IK07.The switch-disconnector may be locked in the OFF
position by one to three padlocks, hasp diameter 5 to 8 mm (not supplied).Models
Standard switch-disconnector: with black handle.Emergency-off version with red handle and yellow
front for machine-tool control.Extended rotary handleMakes it possible to operate the switch-disconnector, installed inside a switchboard, from the front or side of the switchboard. The extended rotary handle may be installed on the front or the side of the switch-disconnector. Degree of protection IP55.IK08.Operation
Suitability for isolation is maintained.Door opening is prevented when the switch-
disconnector is in ON position (for front handle only).The switch-disconnector may be locked in the OFF
position by one to three padlocks, hasp diameter 5 to 8 mm (not supplied). Locking prevents opening of the switchboard door (for front handle only).Models
Standard switch-disconnector: with black handle.Emergency-off: with red handle and yellow front for
machine-tool control.InstallationThe extended rotary handle is made up of:
An assembly that replaces the direct rotary handle on the Interpact switch-disconnector (secured by screws).
An assembly (handle and front plate) to be mounted on the door or the side of the switchboard. This assembly is always secured in the same position, whether the switch-disconnector is installed vertically or horizontally.
An adjustable extension shaft (see p. C-6 to p. C-9).
bb
bb
bb
b
bb
b
b
b
DB
�068
33Direct rotary handleon INS40 to 160.
DB
�068
34
Direct rotary handle on INS250 and INV100 to 250.
DB
�055
09
Direct rotary handleon INS/INV320 to 630.
DB
�055
�0
Direct rotary handleon INS/INV800 to 1600.
bb
bb
A-39
Functions and characteristics Electrical and mechanical accessories
0566
49b-
56
Padlocked Interpact INS250 switch-disconnector.
Disabling device closingPadlocking
INS40 to �500 A.INV�00 to �500 A.Complete source-changeover assembly from �00 to 630 A.
Switch-disconnectors may be locked in the OFF positionThe handle is designed for locking by up to three padlocks (not supplied). Locking in the OFF position guarantees isolation as defined by the IEC 60947-3 standard. The handle may also be lead-sealed in the OFF position.
bbb
DB
�055
��
DB
�055
�3
KeylockingINS�50-�00 to �500 A.INV�00 to �500 A.Complete source-changeover assembly from �00 to 630 A.
INS�50 to 630, INV�00 to 630 or INV�000 to �500 switch-disconnectors may be locked in the OFF position using a keylock (optional) that may be installed in the hole prepared for that purpose on the front of the devices. The key may not be removed when the switch-disconnector is in the ON position.Keylocks can also be fitted on switch-disconnectors equipped with extended rotary handles.
bbb
DB
�055
�4
DB
�055
�5
INS/INV switch disconnectors
INS40 to 80 INS80 to 160 INS250-100 to 250INV100 to 250
INS320 to 630INV320 to 630
INS630b to 1600INV630b to 1600
INV2000 to 2500INS2000 to 2500
OFF ON OFF ON OFF ON OFF ON OFF ON OFF ONLocking by padlocks b v b v b v b v b v b vLocking by keylock - - - - b v b v b v b vDoor locking (1) - b - b - b - b - b - bDoor lock defeat (1) - b (2) - b (2) - b (2) - b (2) - b (2) - b (2)
Door lockingdevice padlocked (1)
b - b - b - b - b - b -
Lead-sealable handle b v b v b v b v b v b v
Complete source changeover assembly INS250-100 to 250 INS320 to 630Normal ON OFF Replacement ON Normal ON OFF Replacement ON
Locking by padlocks v b v v b vLocking by keylock - b - - b -Door locking (1) b - b b - bDoor lock defeat (1) b (2) - b (2) b (2) - b (2)
Door lockingdevice padlocked (1) - b - - b -Lead-sealable handle v b v v b v
b Standard.v By simple modification of the standard rotary handle.(1) Using a special tool.(2) With extended rotary control.
A-40
Functions and characteristics Manual source-changeover systems
A source-changeover system is made up of two switch-disconnectors or circuit breakers that are mechanically interlocked. The mechanism prevents the simultaneous connection (even transient) of both sources. Switching from one source to the other can be achieved by:b a keylock-type interlocking systemb a mechanical interlocking systemb a complete source-changeover assembly.
DB
�055
�6D
B�0
77��
DB
�055
�7
Possible positions Normal � 0 0Replacement 0 � 0
Source-changeover
INS40…160 INS250INV100…250
INS320…630INV320…630
INS630b…2500
By keylock - b b bMechanical b b b -Complete assembly - b b -
Interlocking of two devices using keylocks and a captive keyInterlocking is based on two identical keylocks with a single key and a keylock adapter (different for each device). This solution enables interlocking between two devices that are physically distant or that have very different characteristics.
Interlocking of two devices with rotary handlesThe direct or extended rotary handles are padlocked with the devices in the OFF position. The mechanism prevents simultaneous closing of the devices, but allows them to be opened.Possible combinations of "Normal" and "Replacement" source INS40 to 160 switch-disconnectors"Normal N" "Replacement" R
Interpact INS (1) INS40 INS63 INS80 INS100 INS125 INS160INS40Ratings 40 A b b b b b b
INS63Ratings 63 A b b b b b b
INS80Ratings 80 A b b b b b b
INS100Ratings �00 A b b b b b b
INS125Ratings ��5 A b b b b b b
INS160Ratings �60 A b b b b b b
(1) With extended rotary handles only.
Possible combinations of "Normal" and "Replacement" source INS/INV100 to 250 switch-disconnectors "Normal N" "Replacement" R
Interpact INS /INV (2) INS250-100 INV100
INS250-160 INV160
INS250-200INV200
INS250-250INV250
INS250-100/INV100Ratings �00 A b b b b
INS250-160/INV160Ratings �60 A b b b b
INS250-200/INV200Ratings �00 A b b b b
INS250-250/INV250Ratings �50 A b b b b
INS320/INV320Ratings 3�0 A v v
INS400/INV400Ratings 400 A
INS500/INV500Ratings 500 A
INS630/INV630Ratings 630 A v v
v 250 A and 630 A ratings can be mixed by using INS320/630 rotary handle interlocking system.(2) Possible with INV, but visible-break function is significantly impaired.
A-4�
Functions and characteristics Manual source-changeover systems
DB
�055
�7D
B�0
55�8
Interlocking of two devices with rotary handlesPossible combinations of "Normal" and "Replacement" source INS/INV320 to 630 switch-disconnectors
"Normal N" "Replacement" RInterpact INS /INV (1) INS320
INV320INS400INV400
INS500INV500
INS630INV630
INS250-100/INV100Ratings �00 A v v v
INS250-160/INV160Ratings �60 A
INS250-200/INV200Ratings �00 A
INS250-250/INV250Ratings �50 A v v
INS320/INV320Ratings 3�0 A b b b b
INS400/INV400Ratings 400 A b b b b
INS500/INV500Ratings 500 A b b b b
INS630/INV630Ratings 630 A b b b b
v 250 A and 630 A ratings can be mixed by using INS320/630 rotary handle interlocking system.(1) Possible with INV, but visible-break function is significantly impaired.
Complete source-changeover assembly for two switch-disconnectorsThese assemblies provide an easy way to implement source changeover functions with:
a single 3-position rotary handle that controls the two switch-disconnectors (Normal source ON, OFF, Replacement source ON)
a smaller size, taking up less room in the switchboard.A complete source changeover assembly can be ordered with a single catalogue number.
Possible combinations of "Normal" and "Replacement" source switch-disconnectors"Normal N" "Replacement" R
INS250-100
INS250-160
INS250-200
INS250-250
INS320 INS400 INS500 INS630
INS250-100Ratings �00 A b
INS250-160Ratings �60 A b
INS250-200Ratings �00 A b
INS250-250Ratings �50 A b
INS320Ratings 3�0 A b
INS400Ratings 400 A b
INS500Ratings 500 A b
INS630Ratings 630 A b
b
b
A-4�
Connection accessoriesFunctions and characteristics
With Interpact INS/INV switch-disconnectors, it is easy to create a large number of series pole arrangements using prefabricated connections mounted on site during equipment installation.
DB
�044
68
One type of connection per framesize, two catalogue numbers for all series connections.
b Indifferent connection of polarities, from left to right or right to left.b Indifferent connection of upstream and downstream cables to top or bottom terminals.b Series connection of poles is possible by upstream/downstream connections. Creation of the connections is the responsibility of the panel builder or the installer.
Series connection of poles for direct current applications
Examples of series connectionThree-pole devices
DB
���5
94
DB
���5
95
Four-pole devices
DB
���5
96
DB
���5
97
Great flexibility for connections
DB
���5
98
DB
���5
99
Indifferent connection of polarities. Upstream/downstream connections to top or bottom connectors.
DB
���6
00
Series connection of poles is possible by upstream/downstream connections (user made).
A-43
Functions and characteristics Connection accessories
The exceptional performance levels of Interpact INS/INV switch-disconnectors mean the poles can be parallel connected. This technique virtually doubles, triples or quadruples the current rating depending on the type of circuit breaker and thus reduces the cost of solutions.
DB
�044
85
Parallel pole connection accessories are identical to those for series connections. The are equipped with heat sinks.Customer connections are made directlyto the connection plates after removing the heat sinks.
DB
�044
86
Specific connections are required for parallel connection of three poles.
Parallel connection of poles for direct current applications
Examples of parallel connectionThree-pole devices
DB
���6
0�
Four-pole devices (2 x 2 poles in parallel)
DB
���6
0�
It is possible to mix series and parallel connections
DB
���6
05
Note: creation of the additional connection (1) is the responsibility of the panel builder or the installer.
Great flexibility for connectionsIndifferent connection of polarities, from left to right or right to left.Indifferent connection of upstream and downstream cables to top or bottom
terminals.
bb
A-44
Functions and characteristics Connection accessories
Solutions depending on the distribution system and the voltage Type of distribution system
Type Earthed IsolatedSource One polarity (negative here) connected to earth
(or exposed conductive parts)Mid-point connected to earth
Isolated polarities
Protected polarities � (disconnection of �P) � (disconnection of �P) � �Diagrams, connection method
DB
�086
�4
DB
�086
�5
DB
�086
�6
DB
�086
�7
Series connection of polesSelection of switch-disconnectors and pole connectionInterpact INS/INV
24 V y Un y 125 V
DB
�086
�9
DB
�085
89
DB
�085
90
DB
�085
9�
Two-pole (1). Three-pole. Two-pole (1). Four-pole.
125 V < Un y 250 V
DB
���6
06
DB
�085
9�
DB
�085
9�
Not applicable
Four-pole. Four-pole. Four-pole.
(1) A 3P switch-disconnectors can be used if a 2P version does not exist. In this case, the central pole is not connected.
Parallel connection of polesSelection of switch-disconnectors and pole connectionInterpact INS/INV
Un y 63 V
DB
�086
��
DB
�086
�3
DB
�086
�3
DB
�086
�3
Two, three-pole, 2, 3P in parallel, four-pole, 4P in parallel.
Four-pole, 2 x 2P in parallel. Four-pole, 2 x 2P in parallel. Four-pole, 2 x 2P in parallel.
63 V < Un y 125 V
DB
�086
�5
Not applicable
DB
�086
�3
Not applicable
Four-pole, 2 x 2P in parallel, connected in series.
Four-pole, 2 x 2P in parallel.
A-45
Functions and characteristics Connection accessories05
6384
a-56
One-piece spreader.
One-piece spreaderConnection of large cables may require an increase in the distance between the switch-disconnector terminals. The one-piece spreader is an accessory that can also be fitted on Compact NSX/NS circuit breakers. It offers the following features:
increases the pitch of the switch-disconnector terminals to correspond to that of the upstream device
compatible with all the connection and insulation accessories available for the upstream device (connectors, terminal extensions, etc.)
enhances insulation between phases in comparison with standard spreaders.
INS250 INS320 to 630INV100 to 250 INV320 to 630
Pitch withoutspreaders (mm)
35 45
Pitch with standard spreaders (mm)
45 52.5 or 70
Pitch with one-piece spreader (mm)
45 -
MountingWhen equipped with a one-piece spreader, INS and INV switch-disconnectors may be installed either at the back of a switchboard or on the front panel with a front alignment base.
Devices with different frame sizes can thus be aligned in the switchboard.
The same mounting plate can be used for all devices (including Compact NSX/NS circuit breakers).
b
b
b
b
b
DB
1054
96
DB
1054
97
Mounting at the backof a switchboard.
Mounting on the front panel with a front alignment base.
DB
1054
95
Connection and insulation accessories are identical to those for Compact NSX/NS.
A-46
Functions and characteristics Connection accessoriesP
D39
094�
R
Multi-stage distribution block 125 A Electrical characteristics:
rated operating current: Ie (40 °C) = ��5 Arated insulation voltage: Ui = 500 Vrated short-time withstand current: Icw = 3.5 kA rms/�speak withstand current: Ipk = �0 kÂrated impulse withstand voltage: Uimp = 8 kV.
Mounting:clipped onto Multifix or symmetrical railscrewed on plain or slotted plate.
Supplied with:transparent, insulating covermounting hardware.
bbbbb
bb
bb
04��
53a-
3�
DB
�073
5�
PD
3906
00R
Distribution block 125 to 160 A
DB
�068
�7
Distribloc 125 A.
DB
�073
4�
Cable connection.
GeneralDownstream circuits are connected from the front, to spring terminals.Contact pressure automatically adapts to the size of the conductor. It does not depend on the operator.Contacts are insensitive to vibrations and thermal variations.Only one cable (flex ble or rigid, without a metal ferrule) can be inserted in a spring terminal.Degree of protection: IPxxB.Advantages:
a reliable electrical connection, no maintenance required (tightness guaranteed over time)
very fast connectioneasy phase balancingrewiring is very easy if the switchboard is expanded or modified.
b
bbb
A-47
Functions and characteristics Connection accessoriesP
D39
065�
PD
3906
57
Distribution block 125 to 160 AMade up of:
a fully insulated, one-piece distribution block complying with the degree of protection IPxxB (protection against direct contacts)
a modular cover.The design of the front (45 mm nose) blends perfectly into a row comprising modular devices.Electrical characteristics
Rated insulation level: Ui = 750 V.Rated operational current Ie (40°C):��5 A for the ��5 A Distribloc�60 A for the �60 A Distribloc with its prefabricated connection for INS�60 or
NSA�60.Short-circuit withstand current: the reinforced breaking capacity due to cascading
in circuit-breaker combinations is maintained. The worst-case situations have been tested.
Complies with the low-voltage device standard IEC 60947.7.� and/or IEC 60439.�impulse withstand voltage Uimp = 8 kV.
SupplyTunnel terminal on ��5 A Distr bloc ��5 for 6 to 35v flexible cables (10 to 35v rigid
cables).The 160 A Distribloc is supplied with a prefabricated flexible connection. It is
designed for an INS�00/�60 or NSA�60 switch-disconnector, installed on the left or right.Distribution (��5 and �60 A Distribloc)
Spring terminals: � outgoers from � to �0v, flexible or rigid3 outgoers from � to 6v, flex ble or rigid7 outgoers from � to 4v, flex ble or rigid.Tunnel terminals:� outgoer from 4 to �6v, flexible (4 to 25v rigid).
SupplyAn identification labelAdhesive labels for phase identificationA prefabricated flex ble connection for the INS160 or NSA160
(�60 A Distribloc only).
b
b
bbvv
b
bb
b
b
bvvvbv
bbb
DB
�073
43P
D39
0658
AccessoriesSet of four flexible connections, 35v, L = ��0 mm.
To supply a ��5 A Distr bloc from an NG��5 or an INS��5.b
A-48
Functions and characteristics Connection accessoriesP
D39
0549
250 A Polybloc distribution blockGeneralDownstream circuits are connected from the front, without screws, to spring terminals. Contact pressure automatically adapts to the size of the conductor (minimum size = 1 mm2). Contacts are insensitive to vibrations and thermal variations. Only one cable (flex ble or rigid, without a metal ferrule) can be inserted in a spring terminal.Degree of protection: IPxxB.Advantages of spring terminals
A reliable electrical connection, no maintenance required.The fast connections make phase balancing very easy.Rewiring is very easy if the switchboard is expanded or modified.
ApplicationsThe Polybloc distribution block is designed for installation directly downstream of Compact circuit breakers and Interpact switch-disconnectors devices up to 250 A.It can be rapidly mounted in the horizontal position. Electrical connections are made directly to the device terminals.It has the same width as the devices and does not take up any additional space in the switchboard.The connection terminals are slanted to facilitate cable entry and not exceed the bending radius of the flexible and rigid cables.Electrical characteristicsThe electrical characteristics are perfectly compat ble with the connected devices. Neither the temperature derating curves nor the performance levels of the circuit breakers and switch-disconnectors are altered.
Rated insulation level Ui = 750 V.Short-circuit withstand current: the reinforced breaking capacity due to cascading
in circuit-breaker combinations is maintained. The worst-case situations have been tested.
Impulse withstand voltage Uimp = 8 kV.SupplyDirectly to the terminals of the Compact NSX/NS and Interpact INS devices up to 250 A.DistributionVia cables, up to six 10 mm² cables and three 16 mm² cables per phase.InstallationDirectly on the mounting plates of horizontally mounted Compact NSX/NS100/250 and Interpact INS250 devices in the enclosures.It can also be mounted downstream of vertically mounted Compact NSX/NS100/250 and Interpact INS250 devices in the enclosures. In this case, the Polybloc is mounted on a depth-adjustable modular rail (03002 System G) or (03402 System P).
bbb
bb
b
DB
1073
42D
B10
7345
Vertically mounted Polybloc on a depth-adjustable modular rail (03402) in a cubicle (System G).
DB
1073
47
AccessoriesSpecial connection blocks can be added to Polybloc 250 A distribution blocks for
connection of two 35 mm² cables per phase via screw terminals.b
A-49
Functions and characteristics Connection accessoriesD
B�0
7348
160 A Polybloc distribution blockThe �60 A Polybloc is made up of individual elements that can be used alone or with others to make two-pole, three-pole or four-pole distribution blocks.Mounting is very fast. It clips onto a modular rail and is supplied by cables via a tunnel terminal.The connection spring terminals are slanted to facilitate cable entry and bending of the flexible and rigid cables.It is supplied with a cover that also guides the cables.Electrical characteristics
Rated insulation level Ui = 750 V.Short-circuit withstand current: the reinforced breaking capacity due to cascading
in circuit-breaker combinations is maintained. The worst-case situations were tested. The electrical characteristics are perfectly compatible with the connected devices. Neither the temperature derating curves nor the performance levels of the circuit breakers and switch-disconnectors are altered.
Impulse withstand voltage Uimp = 8 kV.SupplyDirect to a tunnel terminal, for cables up to 70 mm².DistributionVia cables, up to six �6 mm² cables.InstallationThe blocks clip onto a modular rail.
bb
b
Three 160 A Polybloc distribution blocks in the vertical position on a modular rail, supplied by an INS160.
DB
�073
49
160 A Polybloc distribution block in a front plate cut-out.
A-50
Functions and characteristics Connection accessories05
6063
Rb-
57
Insulation of live partsTerminal shields for INS and INV switch-disconnectorsLead-sealable insulation accessories used to protect against direct contact with power circuits.
Degree of protection: IP40, IK07.Supplied with lead-sealing accessories.
Interphase-barrier for INS/INVSafety accessories providing maximum insulation
between the phases of the power connection.Easy installation by snapping into the case.May be combined with all other connection
accessories, except the terminal shields and terminal shrouds.
Terminal shrouds for INS40 to INS160These insulation accessories are used for protection against direct contact with live connection screws. It is also poss ble to attach an insulating plate (not supplied) to the shrouds to avoid any contact with the power conductors.
Spare viewport for Interpact INV switch-disconnectorsViewports are darkened by the electrical arc. A new viewport may be installed to maintain the vis ble-break function.
bb
b
bb
If 500 V y U y 690 V, interphase-barrier or long terminal shields are mandatory.
DB
�054
98
Terminal shieldsfor Interpact INS and INV.
DB
�054
99
Interphase-barrierfor Interpact INS and INV.
DB
�055
00
Terminal shroudsfor Interpact INS40 to 160 (with insulating plate to avoid contact with the conductors).
DB
�055
0�
Spare viewportfor Interpact INV.
A-51
Functions and characteristics Connection accessoriesD
B10
5511
Coupling accessory for complete source-changeover assemblyThis accessory simplifies connection of bars or cables with lugs when coupling two Compact NSX/NS100 to 630 circuit breakers or two Interpact INS/INV100 to 630switch-disconnectors of the same size.Pitch between outgoing terminals:
Interpact INS250 and INV100 to 250: 35 mmInterpact INS/INV320 to 630: 52.5 mmCompact NSX/NS100 to 250: 35 mmCompact NSX/NS400 to 630: 52.5 mm.
Connection and insulation accessoriesThe coupling accessory may be fitted with the same connection and insulation accessories as the coupled circuit breakers or switch-disconnectors.
Possible combinations Downstream couplingPoss ble Pitch of outgoing
terminals (mm)Manual source-changeover
INS250 (100 to 250 A) with rotary handle b 35NSX/NS100/250 with rotary handle b 35NSX/NS100/250 on mounting plate with toggle b 35INS400/630 (320 to 630 A) with rotary handle b 52 5NSX/NS400/630 with rotary handle b 52 5NSX/NS400/630 on mounting plate with rotary handle b 52 5Complete source-changeover assembly
INS250 (100 to 250 A) complete assembly b 35INS400/630 (320 to 630 A) complete assembly b 52 5Remote-operated source-changeover
NSX/NS100/250 b 35NSX/NS400/630 b 52 5
bbbb
A-52
InstallationFunctions and characteristics05
2760
b-39
Local isolation enclosure.
PD
3904
47b
Power distribution incomer in a Prisma cubicle.
0566
99b-
59
Power distribution incomer in a Prisma Plus System G IP55 cubicle.
Interpact INS and INV switch-disconnectors offer a number of rational installation solutions to optimise available space inside enclosures. They may be installed in individual enclosures or as incomers in power distribution or control panels.
Interpact INS40 to 160 switch-disconnectors have a standard 45 mm high front and may be clipped onto a Multifix or symmetrical rail. They may be installed in all Multi 9 modular enclosures, including Pragma, Prisma, etc.
Interpact INS250 to 630 and INV100 to 630 switch-disconnectors may be installed on mounting plates or rails. Installation as incomers in Prisma power distribution cubicles is very flexible:
the mounting plates are the same as those used for Compact NSX/NS circuit breakers and are identical for direct and extended handles
installation in 300 mm ducts is possible for ratings up to 630 A.
b
b
v
v
Individual enclosuresEach individual enclosure includes:a door with a cut-outa mounting plateaccessories required for extended front or lateral
rotary handleremovable plates (without holes) for cable entry.
The Interpact INS switch-disconnector must be order separately.
bvvv
v
DB
1054
46
Heavy-duty individual enclosure (sheet metal or plastic).
Pragma modular enclosuresThe enclosures in the Pragma range are:made of self-extinguishing insulating materialsupplied with all accessories (terminal blocks,
blanking plates, etc.)rated class 2.
bvv
v
DB
1054
47
Interpact INS40on a symmetrical rail.
Prisma metal cubicles and enclosuresThe metal cubicles and enclosures in the Prisma
range are highly adaptable to the type of installation:basic cubicle or enclosuremultifix railmodular front platesdistribution accessoriesducts for running cables or installing terminalsplain or transparent doors.
b
vvvvvv
DB
1054
48
Installation in a 300 mm duct.
A-53
Functions and characteristics Installation
Front-panel escutcheonsEscutcheons for switch-disconnectors and ammeter modulesMounted on switchboard panel from the front using four screws.
DB
�055
�9
DB
�055
�0
Escutcheon for switch-disconnectors. Escutcheon for ammeter modules.
Identification labelsInterpact INS40 to �60 switch-disconnectors may receive Telemecanique prefabricated labels, catalogue number AB�- (eight characters). Interpact INS�50 to 630 and INV�00 to 630 switch-disconnectors are supplied as standard with a clip-on label for handwritten indications.These devices also come with a nameplate into which a label can be inserted.
DB
�055
��
6��7
8b-3
5
Individual enclosuresInterpact INS and INV switch-disconnectors equipped with a front handle may be installed in individual enclosures.All fixed, front connections are poss ble, except right-angle and edgewise terminal extensions. Spreaders may be installed in the enclosures intended for Interpact INS�50 to 630 and INV�00 to 630 switch-disconnectors.Heavy-duty metal individual enclosure for Interpact INS (IP55, IK08)
metal enclosuredoor with keylock and cut-out for switch-disconnector rotary handleextended rotary front handledevice mounting plateremovable plate (without holes) for cable entry through bottom.
Heavy-duty insulating individual enclosure for Interpact INS and INV (IP55, IK08)
thermoplastic enclosuretransparent cover, screwed, lead sealable, with cut-out for switch-disconnector
rotary handleextended rotary front handledevice mounting plateremovable plates (without holes) for cable entry through bottom and/or top.
DimensionsMetal enclosures H x W x D
Interpact INS40 to �60 350 x 350 x �60Interpact INS�50Interpact INV�00 to �50
450 x 350 x �60
Interpact INS3�0 to 630Interpact INV3�0 to 630
650 x 350 x �60
Insulating enclosures H x W x DInterpact INS40 to �60 �80 x �70 x �85Interpact INS�50Interpact INV�00 to �50
360 x �70 x �35
Interpact INS3�0 to 630Interpact INV3�0 to 630
7�0 x 360 x �35
bbbbb
bb
bbb
schneider-electric.com CAD software and tools
This international site allows you to access all the Schneider Electric products in just � clicksvia comprehensive range data-sheets, with direct links to:
complete library: technical documents, catalogs, FAQs, brochures…
selection guides from the e-catalog.
product discovery sites andtheir Flash animations.You will also fi nd illustrated overviews, news to which you can subscribe, the list of country contacts…
p
p
p
The CAD software and tools enhance productivity and safety. They help you create your installations by simplifying product choice through easy browsing in the Schneider Electric offers.Last but not least, they optimise use of our products while also complying with standards and proper procedures.
TOOLS
B-�
Interpact INS/INV Installation recommendations
Presentation 2Functions and characteristics A-1
Operating principle B-2
Possible installation positions and mounting techniques B-4
Implementation B-5
Interpact INS40 to 80 B-6
Interpact INS100 to 160 B-7
Interpact INS250-100 to 250 Interpact INV100 to 250 Complete source-changeover assembly INS250-100 to 250 B-8
Interpact INS320 to 630 Interpact INV320 to 630 Complete source-changeover assembly INS320 to 630 B-12
Interpact INS630b to 1600 Interpact INV630b to 1600 B-16
Interpact INS2000 to 2500 Interpact INV2000 to 2500 B-20
Use at high temperatures B-22Dimensions and connection C-1Additional characteristics D-1Catalogue numbers E-1
B-�
Operating principleInstallation recommendations
INS40 to 250 - INV100 to 250
DB
��95
4�
INS320 to 630 - INV320 to 630
DB
�056
07
B-3
Installation recommendations Operating principle
INS630b to 2500 - INV630b to 2500
DB
�056
08
B-4
Possible installation positions and mounting techniques
Installation recommendations
Possible installation positions
DB
�056
09
DB
�056
�0
DB
�056
��
DB
�056
��
DB
�056
�3
Possible mountingINS40 to 160
DB
�056
�4
DB
�056
�5
DB
�056
�6
Symmetrical rail. Plain mounting plate. Slotted mounting plate.
INS250-100 to 630 - INV100 to 630
DB
�056
�7
DB
�056
09
DB
�056
�8
Rails. Plain mounting plate. Slotted mounting plate.
INS/INV630b to 2500
DB
�056
�9
DB
�056
�0
Rails. Plain mounting plate.
B-5
Installation recommendations ImplementationD
B�0
56��
Reverse supplyInterpact switch-disconnectors may be supplied indifferently via the top or bottom terminals, without any reduction in performance.
Neutral pole positionOn Merlin Gerin switch-disconnectors, the neutral pole is traditionally located on the left-hand side. On the INS and INV ranges, the four poles are identical and the neutral pole can therefore be located on the right-hand side simply by adding an appropriate label.
DB
�068
35
Conductor materials and electrodynamic forcesInterpact switch-disconnectors may be connected using either bare copper, tinned copper or tinned aluminium conductors (flexible or rigid bars, cables).In the event of a short-circuit, thermal and electrodynamic forces are exerted on the conductors. The conductors must therefore be adequately sized and suitably supported.Note that the terminals of electrical devices (switch-disconnectors, contactors, circuit breakers, etc.) should not be considered to contribute to the support of the conductors.
Cables ties and flexible barsThe table below indicates the maximum distances between cable ties depending on the prospective short-circuit current.Care must be taken not to exceed a distance of 400 mm between ties mechanically secured to the switchboard frame.
Type of tie "Panduit" type Width: 4.5 mm Max. load: 22 kg Colour: white
"Sarel" type Width: 9 mm Max. load: 90 kg Colour: black
Max. distance between ies (mm)
�00 �00 50 350 �00 �00 70 50 (double ties)
Short-circuit current (kA rms)
�0 �5 �0 �0 �7 35 45 �00
Note: for cables u 50 mm², 9 mm wide ties must be used.
B-6
Interpact INS40 to 80Installation recommendationsD
B�0
5450
DB
�054
5�
Front connection of bare copper and aluminium cablesInterpact INS40 to INS80 switch-disconnectors are equipped as standard with connectors for bare copper or aluminium cables (�.5 to 50 mm² rigid cables, 1.5 to 35 mm² flexible cables)Distribution connectorThis connector screws directly into the switch-disconnector terminals for connection of three cables of the following types:
1 to 10 mm² flexible cables (1)
�.5 to �6 mm² rigid cables.
Pole pitch�8 mm
Standard device
With distribution connector
Bars e (mm) y �5 -L (mm) �3 �3
Lugs L (mm) y �0 y �0S (mm²) �.5 to 50 rigid �.5 to �6 rigidCu / Al 1.5 to 35 flexible 1 to 10 flexible (1)
Torque (Nm) 5 �(1) Connection of 1.5 to 4 mm² flexible cables requires crimped or auto-crimping ferrules.
bb
DB
�068
38
Distribution connector.
DB
�067
6�
If 500 V y U y 690 V, long terminal shields are mandatory.
Insulation of live partsWith long terminal shields.With terminal shrouds.
bb
DB
�054
5�
DB
�068
4�
Terminal shields. Terminal shrouds.
B-7
Installation recommendations Interpact INS100 to 160D
B�0
5453
DB
�054
54
Front connection of insulated bars and cables with crimped lugsInterpact INS�00 to INS�60 switch-disconnectors are equipped as standard with terminals comprising nuts with M6 screws for direct connection of insulated bars or cables with lugs.LugsThe special lugs for copper cables may be used for cables with cross-sectional areas up to 95 mm². Secure the lugs by hexagonal crimping or punching. Lugs are supplied with interphase-barrier and are compatible with the terminal shields.
Pole pitch30 mmDimensions
Bars d (mm) y �0e (mm) �…6.4L (mm) y ��
Lugs L (mm) �5Ø (mm) u 6.�
Torque (Nm) 8
DB
�068
39
Lug.D
B�0
7386
DB
�054
56
DB
�054
57
Front connection of bare copper and aluminium cables1-cable connectors snap directly onto the device terminals (1 to 10 mm² flexible
cables (1))Distribution connectors for 4 flex ble cables (1.5 to 25 mm² rigid cables or 1.5 to
16 mm² flexible cables (1)) are screwed directly to the device terminals. These connectors are supplied with interphase-barrier (mandatory installation) which may be replaced by long terminal shields
Distribloc distribution block supplied via tunnel terminals. Provides �� screwless spring type and � screw type outgoing terminals.
1-cable connector
Distribution connector
Lugs L (mm) �5 �5S (mm²)Cu / Al
� 5 to 35 rigid 50 to 95 rigid � 5 to �5 rigid1 5 to 35 flexible (1) 50 to 95 flexible 1 5 to 16 flexible (1)
Torque (Nm) �0 �� 3Distribloc
Torque (Nm) Supply: 5 NmDistribution: 3 Nm
(1) Connection of 1.5 to 4 mm² flexible cables requires crimped or auto-crimping ferrules.
b
b
b
DB
�054
59
DB
�054
59
DB
�056
30
1-cable connector. Distribution connector.
DB
���6
03
2
4
4
9
75
48108
127
100
DB
�073
40
Distribloc 125 and 160 A. Multi-stage distribution block.
If 500 V y U y 690 V, interphase-barrier or long terminal shields are mandatory.
Insulation of live partsWith long terminal shields.With terminal shrouds.Interphase-barrier:distribution blocks, lugs, right-angle/straight/edgewise terminal extensions and
spreaders are supplied with interphase-barrierinterphase-barrier may be positioned horizontally or verticallythey may be replaced by long terminal shields.
bbbv
vv
DB
�054
5�
DB
�068
4�
DB
�068
43
Terminal shields. Terminal shrouds. Interphase-barrier.
B-8
Interpact INS250-100 to 250 Interpact INV100 to 250 Complete source-changeover assembly INS250-100 to 250
Installation recommendationsD
B�0
5456
DB
�056
�9D
B�0
56�9
DB
�054
74
DB
�054
77
1-cable connector. Distribution connector.
Front connection of bare copper and aluminium cablesBare-cable connectors for Interpact INS/INV switch-disconnectors may be used for both copper and aluminium cables.1-cable connectorsThe connectors snap directly on to the device terminals or clip onto right-angle and straight terminal extensions as well as spreaders. These connectors are supplied with interphase-barrier.Material: steel I y �60 A and tinned aluminium I y �50 A.6-cable distribution connectorsThese connectors are screwed directly to device terminals. These connectors are supplied with interphase-barrier (mandatory installation) which may be replaced by long terminal shields. Each connector can receive six cables with cross-sectional areas ranging from �.5 to 35 mm² each.Material: tinned aluminium.Polybloc distribution blocks, for 6 or 9 rigid or flexible cablesThe Polybloc connects directly to the device terminals and is used to connect up to six or nine flexible or rigid cables with cross-sectional areas not exceeding 10 mm², to each pole. Connection is made to spring terminals without screws.
1-cable connector Steel Aluminiumy 160 A y 250 A
L (mm) �0 �0S (mm²) Cu / Al �.5…95 (1) �5…50 70…95 ��0…�85Torque (Nm) �� �0 �6 �6Distribution connector, 6 cables Cu or Al
L (mm) �5 or 30S (mm²) Cu / Al �.5…6 (1) 8…35Torque (Nm) 4 6Polybloc distribution block, 6 or 9 cables
L (mm) ��S (mm²) Cu / Al �.5…�0
(1) Connection of 1.5 to 4 mm² flexible cables requires crimped or auto-crimping ferrules.
Dimensions�-cable connector
DB
�056
33
DB
�073
46
DB
�056
3�
Polybloc 250 A distribution block.
Distr bution connector, 6 cables
DB
�073
5�
DB
�056
34
Polybloc 160 A.
B-9
Installation recommendations Interpact INS250-100 to 250 Interpact INV100 to 250 Complete source-changeover assembly INS250-100 to 250
DB
�056
�7
Front connection of insulated bars and cables with crimped lugsInterpact INS�50-�00 to INS�50 and INV�00 to �50 switch-disconnectors are equipped as standard with terminals receiving snap-in nuts and M8 screws for direct connection of insulated bars or cables with lugs.Lugs
The small lugs for copper cables may be used for cables with the following cross-sectional areas ��0, �50 or �85 mm² (secure the lugs by hexagonal crimping or punching).
The small lugs for aluminium cables may be used for cables with the following cross-sectional areas �50 or �85 mm² (secure the lugs by hexagonal crimping).
Pole pitch35 mmDimensions
Bars d (mm) y �0e (mm) y 6L (mm) y �5Ø (mm) u �0
Lugs L (mm) y �5Ø (mm) u �0
Torque (Nm) �5
b
b
Dimensions
DB
�056
36
DB
�054
53
DB
�056
35D
B�0
56�9
Small lugs for copper cables.
DB
�054
77
Small lugs for aluminium cables.
DB
�056
�6
Bar.
If 500 V y U y 690 V, interphase-barrier or short or long terminal shields are mandatory.
Insulation of live partsWith short or long terminal shields.Interphase-barrier:distribution blocks, lugs, right-angle/straight/edgewise terminal extensions and
spreaders are supplied with interphase-barrierinterphase-barrier may be positioned horizontally or verticallythey may be replaced by long terminal shields.One-piece spreader: the one-piece spreader increases the pitch to correspond to
that of the upstream device and provides protection against direct contact (see page A-45).
bbv
vvb
DB
�056
37
DB
�054
5�
Terminal shields.
DB
�054
7�
Interphase-barrier. One-piece spreader.
B-�0
Interpact INS250-100 to 250 Interpact INV100 to 250 Complete source-changeover assembly INS250-100 to 250
Installation recommendationsD
B�0
5453
DB
�056
35
Front connection with accessoriesStraight terminal extensionsMaterial: tinned copper.
DB
�067
6�
Connection of two cables with lugs.
DB
�054
66
Right-angle extensionsMaterial: tinned copper.
DB
�054
67
Insulation stripping lengths and tightening torques for cables, bare bars and cables with lugs are identical to those for direct connection to devices.
SpreaderMaterial: tinned copper.
DB
�067
6�
Connection of two cables with lugs. One-piece spreader.
DB
�054
70
Separate parts.
DB
�067
63
DB
�056
�7
Pole pitch45 mmDimensions
Bars d (mm) y �0e (mm) y 6L (mm) y �5Ø (mm) 8.5
Lugs L (mm) y �5Ø (mm) 8.5
Torque (Nm) �5 (1)
(1) Tightening torque for spreader.
Spreaders, straight terminal extensions and right-angle terminal extensions are supplied with interphase-barrier.
DimensionsRight-angle terminal extensions
Spreader and straight terminal extensions
DB
�067
64
DB
�067
65
One-piece spreader 3P/4P
DB
�067
66
B-��
Installation recommendations Interpact INS250-100 to 250 Interpact INV100 to 250 Complete source-changeover assembly INS250-100 to 250
DB
�056
�7
Rear connectionThe rear connections are simply fitted to the device connection terminals. All combinations of rear connection lengths and positions are poss ble on a given switch-disconnector. The switch-disconnector is mounted on a backplate.For the connection of cables without lugs, the �-cable connectors for Interpact INS�00-�50 to INS�50 and INV�00 to �50 may be simply clipped onto the rear connections.Bars or cables with crimped lugsInterpact INS�50-�00 to INS�50 and INV�00 to �50 switch-disconnectors may be equipped with long or short rear connections, or a mix of the two. The connections may be positioned flat, on edge or at 45° angles, or any combination thereof.Material of rear connections: tinned copper.
Pole pitch35 mmDimensions
Bars d (mm) y �0e (mm) y 6L (mm) y �5Ø (mm) u 8
Lugs L (mm) y �5Ø (mm) u 8
Torque (Nm) 5 (1)
(1) Tightening torque for rear connections.
Dimensions
DB
�068
36D
B�0
5630
Bare cables (copper or aluminium)The rear connections may be equipped with �-cable connectors secured by clips.
1-cable connector Steel y 160 A Aluminium y 250 AL (mm) �0 �0S (mm²) Cu / Al �.5…95 (1) ��0…�85Torque (Nm) �� �6Distribution connector, 6 cables Cu or Al
L (mm) �5 or 30S (mm²) Cu / Al �.5…6 (1) 8…35Torque (Nm) 4 6
(1) Connection of 1.5 to 4 mm² flexible cables requires crimped or auto-crimping ferrules.
Insulation stripping lengths and tightening torques for cables, bare bars and cables with lugs are identical to those for direct connection to devices.
DB
�054
53
DB
�067
68D
B�0
6769
Connection of bars or cables with lugs.
DB
�056
�6
Bar.
DB
�054
80
Two lenghts.
DB
�068
55
Four positions.
DB
�067
73D
B�0
677�
Rear connection with bar.
B-��
Interpact INS320 to 630 Interpact INV320 to 630 Complete source-changeover assembly INS320 to 630
Installation recommendationsD
B�0
5456
DB
�067
74D
B�0
5475
1-cable connector.
DB
�054
76
2-cable connector.
DB
�056
30
Front connection of bare copper and aluminium cablesBare-cable connectors for Interpact INS/INV switch-disconnectors may be used for both copper and aluminium cables.1-cable and 2-cable connectors�-cable and �-cable connectors, made of tinned aluminium for copper and aluminium cables, are screwed to the device terminals or to right-angle terminal extensions. These connectors are supplied with interphase-barrier.
1-cable connector 2-cable connectorTorque (Nm) 3� 3�
Dimensions
DB
�068
6�
�-cable connector
DB
�077
�4
DB
�067
75
�-cable connector
DB
�077
�5
DB
�067
77
B-�3
Installation recommendations Interpact INS320 to 630 Interpact INV320 to 630 Complete source-changeover assembly INS320 to 630
DB
�056
�7
Front connection of insulated bars and cables with crimped lugsInterpact INS3�0 to 630 and INV3�0 to 630 switch-disconnectors are equipped as standard with terminals receiving snap-in nuts and M�0 screws for direct connection of bars or cables with lugs. Lugs
The small lugs for copper cables may be used for cables with the following cross-sectional areas �40 or 300 mm² (secure the lugs by hexagonal crimping or punching).
The small lugs for aluminium cables may be used for cables with the following cross-sectional areas �40 or 300 mm² (secure the lugs by hexagonal crimping).Pole pitch
45 mmDimensions
Bars d (mm) y �5e (mm) 3 y e y �0L (mm) y 3�Ø (mm) u �0
Lugs L (mm) y 3�Ø (mm) u �0
Torque (Nm) 50
b
b
Dimensions
DB
�067
80
DB
�054
53
DB
�067
79D
B�0
56�9
Small lugs for copper cables.
DB
�054
77
Small lugs for aluminium cables.
DB
�056
�6
Bar.
If 500 V y U y 690 V, interphase-barrier or short or long terminal shields are mandatory.
Insulation of live partsWith short or long terminal shields.Interphase-barrier:distribution blocks, lugs, right-angle/straight/edgewise terminal extensions and
spreaders are supplied with interphase-barrierinterphase-barrier may be positioned horizontally or verticallythey may be replaced by long terminal shields.
bbv
vvD
B�0
5637
DB
�054
5�
Terminal shields.
Interphase-barrier.
B-�4
Interpact INS320 to 630 Interpact INV320 to 630 Complete source-changeover assembly INS320 to 630
Installation recommendations
Front connection with accessoriesSpreaderMaterial: tinned copper.
Edgewise terminal extensionsMaterial: tinned copper.
Right-angle extensionsMaterial: tinned copper.Installation on upstream terminals.
DB
�067
8�
DB
�067
83
DB
�067
84
DB
�054
53
DB
�067
67D
B�0
56�6
Bar.
DB
�056
�7Pole pitch
Without spreader 45 mmWith spreader 5�.5 or 70 mmDimensions With spreader With edgewise
terminal ext.Bars d (mm) y �5 y �5
e (mm) 3 y e y �0 3 y e y �0L (mm) y 3� y 3�Ø (mm) > �0.5 > �0.5
Lugs L (mm) y 3� y 3�Ø (mm) �0.5 �0.5
Torque (Nm) 50 (1) 50 (1)
(1) Tightening torque for spreader.
Spreaders, straight terminal extensions and right-angle terminal extensions are supplied with interphase-barrier.
DimensionsEdgewise terminal extensions Right-angle terminal extensions
DB
�073
87
DB
�067
86
Spreader
DB
���5
5�
Type K8 K9 K10 K11 K12Spreader Width in mod. of 5� 5 mm 5�.5 �87.5 �35 39 �4�.5
Width in mod. of 70 mm 70 �40 �70 5�.5 �56
B-�5
Installation recommendations Interpact INS320 to 630 Interpact INV320 to 630 Complete source-changeover assembly INS320 to 630
DB
�056
�7
Rear connectionThe rear connections are simply fitted to the device connection terminals. All combinations of rear connection lengths and positions are possible on a given switch-disconnector. The switch-disconnector is mounted on a backplate.Bars or cables with crimped lugsInterpact INS3�0 to 630 and INV3�0 to 630 switch-disconnectors may be equipped with long or short rear connections, or a mix of the two. The connections may be positioned flat, on edge or at 45° angles, or any combination thereof.Material of rear connections: tinned copper.
DimensionsBars d (mm) y �5
e (mm) 3 y e y �0L (mm) y 3�Ø (mm) > �0.5
Lugs L (mm) y 3�Ø (mm) u �0.5
Torque (Nm) �0 (1)
(1) Tightening torque for rear connections.
Dimensions
DB
�068
37
Bare cables (copper or aluminium)The rear connections may be equipped with �-cable connectors secured by clips.Insulation stripping lengths and tightening torques for cables, bare bars and cables with lugs are identical to those for direct connection to devices.
DB
�054
53
DB
�067
68D
B�0
6769
Connection of bars or cables with lugs.
DB
�056
�6
Bar.
DB
�067
89
Two lenghts.
DB
�068
55
Four positions.
DB
�067
9�D
B�0
677�
Rear connection with bar.
B-�6
Interpact INS630b to 1600 Interpact INV630b to 1600
Installation recommendationsD
B�0
5483
DB
�054
87D
B�0
5490
DB
�054
9�
2-cable connector.
ConnectionsThere are many solutions to connect bars:
vertical connection adapters to connect edgewise bars, spreaders with a 95 mm pole pitch to increase the clearance between bars.
SpreadersSpreaders increase the pole pitch of a switch-disconnector for greater clearance between the bars. They are not compat ble with terminal shields.
bb
DB
�054
88
Spreaders.
Vertical connection adaptersFor connection of edgewise bars.
DB
�054
89
Vertical connection adapters.
Adapters for cables with crimped lugsCable-lug adapters are used in conjunction with vertical connection adapters.They may be used to connect one to four cables (S y 300 mm²) with crimped lugs.To ensure adequate mechanical strength, the cable-lug adapters must be secured together by spacers.
DB
�067
93
Lugs for copper cables.
DB
�054
9�
Adapters for cables with crimped lugs.
DB
�056
�7
Pole pitchWithout spreader 70 mmWith spreader 95 mmDimensions With
spreaderWith vertical connection adapters
With cable lug adapters
Bars d (mm) ��.5 y ��.5 -e (mm) 3 y e y �0 3 y e y �0 -L (mm) y 80 y 80 -Ø (mm) �� > �� -
Lugs L (mm) - - y 40Ø (mm) - - y ��
Torque (Nm) 50 (1) 50 50 (1)
(1) Tightening torque for spreader.
B-�7
Installation recommendations Interpact INS630b to 1600 Interpact INV630b to 1600
Front connection of insulated barsConnection of barsInterpact switch-disconnectors are equipped with terminals for direct connection of bars.
DB
�067
94
DB
�054
83
DB
�054
84
If 500 V y U y 690 V, interphase-barrier or short or long terminal shields are mandatory.
Insulation of live partsWith terminal shields.Interphase-barrier:interphase-barrier may be positioned horizontally or vertically,they may be replaced by long terminal shields.
bbvv
DB
�067
96
DB
�067
97
Interphase-barrier. Terminal shield.
Compatibility of terminal shields + base for connectionsBase Terminal shields Spreader Interphase-barrier
Base - YES YES NOTerminal shields YES - NO NOSpreader NO NO - YESInterphase-barrier NO NO YES -
B-�8
Interpact INS630b to 1600 Interpact INV630b to 1600
Installation recommendations
DimensionsConnection with spreaders
DB
�067
98
DB
�067
99
DB
�068
00
Spreader details
DB
�068
0�
DB
�068
0�
DB
�068
03
DB
�068
04
For 3P switch-disconnectors. For 4P switch-disconnectors.
Connection with vertical connection adapters
DB
�068
05
DB
�068
06
DB
�068
07
Connector details
Note: lines X and Y indicate the axes of symmetry of the switch-disconnector.Reference plane Z corresponds to the back of the switch-disconnector.2 connection possibilities on vertical connection adapters (21 mm between centres).Recommended connection screws: M10 class 8.8.Tightening torque: 50 Nm with contact washer.
DB
�068
08
B-�9
Installation recommendations Interpact INS630b to 1600 Interpact INV630b to 1600
Connection with vertical connection adapters
DB
�068
09
DB
�068
�0
DB
�068
��
Cable lug adapter detailD
B�0
68��
B-�0
Interpact INS2000 to 2500 Interpact INV2000 to 2500
Installation recommendationsD
B�0
5483
Front connection of insulated barsConnection of barsInterpact switch-disconnectors are equipped with terminals for direct connection of bars.
DB
�067
95D
B�0
5486
DB
�068
59
Connector for connection of edgewise bars
DB
�068
60
DB
�068
6�
If 500 V y U y 690 V, interphase-barrier are mandatory.
Insulation of live partsInterphase-barrier
DB
�068
�3
B-��
Installation recommendations Interpact INS2000 to 2500 Interpact INV2000 to 2500
DimensionsConnection with spreaders
DB
�068
�4
DB
�068
�5
DB
�068
�6
Spreader details
DB
��75
�5
DB
��75
�6
For 3P and 4P switch-disconnectors.
Connection with spreaders
DB
�073
80
DB
��75
�7
DB
��75
�8
DB
��75
�9
DB
��75
30
DB
��75
3�
Note: lines X and Y indicate the axes of symmetry of the switch-disconnector.Reference plane Z corresponds to the back of the switch-disconnector.
DB
��75
3�
DB
��75
33
B-��
Use at high temperaturesInstallation recommendations
Power dissipated and resistance per poleInterpact INS 40 63 80 100 125 160
Ra ing (A) 40 63 80 �00 ��5 �60Resistance per pole (mW) 0 3 0.3 0.3 0.� 0.� 0.�Power dissipated per pole (W) 0 5 �.� �.9 � 3.� 5.�Interpact INS/INV 100 160 200 250 320 400 500 630
Ra ing (A) �00 �60 �00 �50 3�0 400 500 630Resistance per pole (mW) 0.�5 0.�5 0.�5 0.�5 0.06 0.06 0.06 0.06Power dissipated per pole (W) � 5 4 6 9.5 6.� 9.6 �5 �4Interpact INS/INV 800 1000 1250 1600 2000 2500
Ra ing (A) 800 �000 ��50 �600 �000 �500Resistance per pole (mW) 0 0�4 0.0�4 0.0�4 0.0�4 0.0�� 0.0��Power dissipated per pole (W) �6 �4 38 6� 48 75
Temperature deratingInterpact INS 40 63 80 100 125 160Front connection with bare-cable connectors or lugs
Thermal current Ith at 60 °C 40 63 80 �00 ��5 �6065 °C 40 63 80 �00 ��5 �6070 °C 40 63 80 �00 ��5 �50
Interpact INS/INV 100 160 200 250 320 400 500 630Front connection / rear connection
Thermal current Ith at 60 °C �00 �60 �00 �50 3�0 400 500 63065 °C �00 �60 �00 �50 3�0 400 500 59070 °C �00 �60 �00 �50 3�0 400 500 550
Front connection with right-angle terminal extension + bare-cable connectorsThermal current Ith at 55 °C �00 �60 �00 �50 3�0 400 500 630
60 °C �00 �60 �00 �50 3�0 400 500 59065 °C �00 �60 �00 �50 3�0 400 500 55070 °C �00 �60 �00 �40 3�0 400 500 5�0
Front connection / rear connection with ammeter or CT moduleThermal current Ith at 40 °C �00 �60 �00 �50 3�0 400 500 600
50 °C �00 �60 �00 �50 3�0 400 500 57555 °C �00 �60 �00 �50 3�0 400 500 54060 °C �00 �60 �00 �40 3�0 400 500 50565 °C �00 �60 �00 �30 3�0 400 480 48070 °C �00 �60 �00 ��0 3�0 400 450 450
Interpact INS/INV 630b 800 1000 1250 1600 2000 2500with or without term. shield
with or without term. shield
with term. shield
without term. shield
with term. shield
without term. shield
with term. shield
without term. shield
Direct connection by flat-facing bars (1)
Thermal current Ith at 40 °C 630 800 �000 ��50 ��50 �600 �600 �000 �50045 °C 630 800 �000 ��50 ��50 �570 �600 �000 �50050 °C 630 800 �000 ��50 ��50 �500 �550 �000 �50055 °C 630 800 �000 ��50 ��50 �4�0 �470 �000 �50060 °C 630 800 �000 ��50 ��50 �340 �390 �000 �50065 °C 630 800 �000 ��50 ��50 ��50 �300 �000 �50070 °C 630 800 �000 �060 ���0 �060 ���0 �000 �400
Connection by flat-facing bars via spreaders, without terminal shields (2)
Thermal current Ith at 40 °C 630 800 �000 ��50 �600 - -45 °C 630 800 �000 ��50 �600 - -50 °C 630 800 �000 ��50 �580 - -55 °C 630 800 �000 ��50 �500 - -60 °C 630 800 �000 ��50 �4�0 - -65 °C 630 800 �000 ��50 �330 - -70 °C 630 800 �000 ��40 ��40 - -
Connection of edgewise bars via vertical connection adapters or cables via vertical connection adapters with cable-lug adaptersThermal current Ith at 40 °C 630 800 �000 ��50 �600 �600 - -
45 °C 630 800 �000 ��50 �600 �600 - -50 °C 630 800 �000 ��50 �600 �600 - -55 °C 630 800 �000 ��50 �600 �600 - -60 °C 630 800 �000 ��50 �600 �600 - -65 °C 630 800 �000 ��50 �5�0 �560 - -70 °C 630 800 �000 ��50 �4�0 �450 - -
(1) INS/INV1600: 4 bars 50 x 5.(2) INS/INV1600: 3 bars 80 x 5.Note: thermal current Ith in Amps (QA).
schneider-electric.com Training
This international site allows you to access all the Schneider Electric products in just � clicksvia comprehensive range data-sheets, with direct links to:
complete library: technical documents, catalogs, FAQs, brochures…
selection guides from the e-catalog.
product discovery sites andtheir Flash animations.You will also fi nd illustrated overviews, news to which you can subscribe, the list of country contacts…
p
p
p
Training allows you to acquire the Schneider Electric expertise (installation design, work with power on, etc.) for increased effi ciencyand a guarantee of improved customer service.The training catalogue includes beginner’s courses in electrical distribution, knowledgeof MV and LV switchgear, operation and maintenance of installations, design of LV installations to give but a few examples.
TOOLS
C-�
Interpact INS/INV Dimensions and connection
Presentation 2Functions and characteristics A-1Installation recommendations B-1
Interpact INS40 to 160 C-2
Interpact INS250-100 to 630 Interpact INV100 to 630 C-5
Interpact INS250-100 to 630 Interpact INV100 to 630 C-6
Interpact INS630b to 1600 Interpact INV630b to 1600 C-10
Interpact INS2000 to 2500 Interpact INV2000 to 2500 C-12
Mechanical interlocks for direct and extended handles C-14INS40 to 630, INV�00 to 630 C-�4
Complete source changeover assembly C-15INS�50-�00 to 630, INV�00 to 630 C-�5
Installation of downstream coupling C-16INS�50-�00 to 630, INV�00 to 630 C-�6
Front-panel accessories C-17INS�50-�00 to �500, INV�00 to �500 C-�7
Parallel or series connection accessories for direct current C-18Interpact INS�50-�00 to �50 Interpact INV�00 to �50 C-�8Interpact INS3�0 to 630 Interpact INV3�0 to 630 C-�9Additional characteristics D-1Catalogue numbers E-1
C-�
Interpact INS40 to 160Dimensions and connection
DimensionsFront handle
DB
�068
�4
DB
�068
�5
DB
�068
�6
(a) Terminal shields INS40/63/80.(b) Terminal shields INS100/125/160.
Dimensions (mm)Type H H1 H2 H3 H4 H5 H6 H7 K K1 L L1 L2 P P1 P2 P3 P4 P5
INS40/63/80 ��.5 45 40 5 8� 4�.5 85 73.5 �47 � �8 46 73 90 �3 3 43 47 6�.5 79 5INS�00/��5/�60 ��.5 45 50 �00 50 �00 ��0 ��0 7 5 30 67.5 ��9 �35 �� 5 45 47 6�.5 79 5
Extended front handle
DB
�056
5�
DB
�056
50
Dimensions (mm)Type A B
(on back plate) (on rail)Min. Max. Min. Max.
INS40/63/80 ��8 5�9 ��3 5�4INS�00/��5/�60 ��8 5�9 ��3 5�4
Type e K Length of shaft
INS40/63/80 �…3 � A - 69INS�00/��5/�60 �…3 7.5 A - 69
Door or front panel cutout for front handleDirect Extended
DB
�056
5�
DB
�056
53
Dimensions (mm)Type C R K
INS40/63/80 47 9� �INS�00/��5/�60 47 �37 7.5
Note: lines X and Y indicate the axes of symmetry of the switch-disconnector.Reference plane Z corresponds to the back of the switch-disconnector.
C-3
Dimensions and connection Interpact INS40 to 160
DimensionsLateral handle
DB
�056
4�
DB
�056
4�
DB
�056
43
Dimensions (mm)Type L3 P6 P7
INS40/63/80 �09 40 66.�INS�00/��5/�60 �54 4�.5 69.3
Extended lateral handle
DB
�056
44
DB
�056
45
Dimensions (mm)Type B e P6 Length of shaftWith shaft Min. Max.
INS40/63/80 �55 396 �…3 40 B - 95INS�00/��5/�60 �00 44� �…3 4�.5 B - �40Without shaft B e P6
INS40/63/80 �0� �…3 40INS�00/��5/�60 �47 �…3 4�.5
Lateral handle for functional enclosure
DB
�056
44
DB
�056
46
Dimensions (mm)Type Enclosure length Type of shaft B e P6
INS40/63/80 550 mm Short �49 �…3 4�.5600 mm Long �74 �…3 4�.5
INS�00/��5/�60 550 mm Short �94 �…3 4�.5600 mm Long ��9 �…3 4�.5
C-4
Interpact INS40 to 160Dimensions and connection
DimensionsFront panel cutout for extended handle
DB
�056
44
Dimensions (mm)Type P6
INS40/63/80 40INS�00/��5/�60 4�.5
InstallationOn a backplate On rail
DB
�056
39
DB
�056
40
Dimensions (mm)Type C1 C2 R1 R2 ØT U
INS40/63/80 40 80 �0 36 4.5 35INS�00/��5/�60 37.5 75 ��.5 60 4.5 35
C-5
Dimensions and connection Interpact INS250-100 to 630 Interpact INV100 to 630
DimensionsFront handle
DB
�056
54
DB
�056
55
(a) Terminal shields.(b) Interphase-barrier.(c) Long terminal shields.
DB
�056
56
Dimensions (mm)Type H H1 H2 H3 H4 H5 H6 H7 H8 H9 H10 K K1 L L1 P P1 P2 P3 P4
INS�50 40 80 68 �36 8� �64 �48 �96 �66 33� ��5 �7.5 35 70 �40 ��.5 86 96 �3� �38INV�00/�50INS3�0/630 6�.5 ��3 �0�.5 �05 ��8 �36 ��5 430 ���.5 4�5 �77 ��.5 45 9�.5 �85 �6 ��0 �30 �60.4 �6�INV3�0/630
Extended front handleINS250-100 to 250 and INV100 to 250
DB
�056
57
DB
�056
58
DB
��45
54
(1) Length of shaft = A - 101.INS320 to 630 and INV320 to 630
DB
���5
5�
DB
�056
6�
(1) Length of shaft = A - 124.
DB
��80
0�
Note:Lines X and Y indicate the axes of symmetry of the switch-disconnector.Reference plane Z corresponds to the back of the switch-disconnector.
C-6
Interpact INS250-100 to 630 Interpact INV100 to 630
Dimensions and connection
Door or front panel cutout for front handleWithout escutcheon With escutcheon
DB
�056
63
DB
�056
64
DB
�056
65
Dimensions (mm) Type C6 C7 H9 L3 L4 P5 P6 R6 R7
INS/INV�00 to �50 5�.5 �03 8� 66 �3� 86 88 8� �6�INS/INV3�0 to 630 76.5 �53 ��7 86 �7� ��0 ��� �0� �0�
InstallationOn panel fixed/FC On panel fixed/RC On rail
DB
��09
��
DB
��09
�3
DB
��09
�4
Dimensions (mm)Type G G1 G2 G3 K K1 K2 ØT
INS/INV�00 to �50 50 �00 ��5 57.5 �7.5 35 70 6INS/INV3�0 to 630 75 �50 �77 88.5 ��.5 45 90 6
Front panel cutoutSwitch-disconnector equipped with a voltage-presence indicator
DB
��08
63
DB
��08
64
Dimensions (mm)Type P43 R14 R15 C22 C23 C30 T8 K3
INS/INV�00 to �50 87.� 65 �30 80 40 58.5 3� �8INS/INV3�0 to 630 ��� 86 �7� ��5.7 6�.85 97 3� ��.7
C-7
Dimensions and connection Interpact INS250-100 to 630 Interpact INV100 to 630
DimensionsLateral handle (only for INS250-100 to 250 and INV100 to 250)
DB
�056
69
DB
�056
70
Extended lateral handle (only for INS250-100 to 250 and INV100 to 250)
DB
��08
65
DB
�056
7�
Door or front panel cutout for lateral handle (only for INS250-100 to 250 and INV100 to 250)
DB
�056
73
C-8
Interpact INS250-100 to 630 Interpact INV100 to 630
Dimensions and connection
DimensionsSwitch-disconnector with ammeter module Switch-disconnector equipped with
current transformerDirect handle (INS250/INV100 to 250) Extended handle
DB
�056
74
DB
�056
75
DB
�056
76
(1) To front of direct handle.(2) To front of key.
Front panel cutoutSwitch-disconnector with ammeter module
Direct handle (INS250/INV100 to 250) Extended handle
DB
�056
77
DB
�056
78
DB
�056
79
(1) Only for INS250/INV100 to 250 with direct handle and ammeter module.
C-9
Dimensions and connection Interpact INS250-100 to 630 Interpact INV100 to 630
Installation (for INS250 direct rotary handle equipped with ammeter module or current transformer)On a backplate On rails
Fixed front connection Fixed rear connection
DB
��09
�5
DB
��09
�6
DB
��09
�7
Installation (for extended rotary handle equipped with ammeter module)On a backplate On rails
Fixed front connection Fixed rear connection
DB
��09
�8
DB
��09
�9
DB
��09
30
Dimensions (mm)Type C22 C23 C27 C28 C29 G G1 G6 G7 G8 G9 G10 G11 G12 G13
INS/INV�00 to �50 4� 8� 56.5 �87 �95 50 �00 ��5 �75 �3�.5 �90 �00 �50 �07.5 �65INS/INV3�0 to 630 63.5 ��7 56.5 �6� - 75 �50 �75 �50 �88.5 �77 �75 �50 �88.5 �77
Type H8 H9 H10 H11 H12 H13 H14 H15 H16 H17 H18 H19INS/INV�00 to �50 ��6 �8� �79.5 4�0 �97.5 446 �4� �07 �05 334 ��3 370INS/INV3�0 to 630 - - - - - - �0�.5 305 3�0.5 5��.5 ��7.5 530
Type K K1 K2 P1 P2 P3 P4 P43 P47 R14 R15 R16 R17 ØT ØT4 U(e)INS/INV�00 to �50 �7.5 35 70 8� 86 �3� �38 89 �37 48.5 97 46.5 93 6 �� y 3�INS/INV3�0 to 630 ��.5 45 90 95.5 ��0 �60.4 �6� ��� �6� 64.5 ��9 64.5 93 6 3� y 3�
C-�0
Interpact INS630b to 1600 Interpact INV630b to 1600
Dimensions and connection
DimensionsDirect front handle
3 poles 4 poles
DB
�056
86
DB
���5
88
(a) Terminal shields.(b) Interphase-barrier.
DB
�056
88
Door or front panel cutout for extended handle
DB
�056
89
DB
�056
90
Cutout for switch-disconnector cover (mm)Type A D E F G
3P �07 �99 �03 �08 ��64P �07 369 �73 �08 ��6
Cutout for switch-disconnector front (mm)Type B D E F G
3P �4� �74 90,5 95.5 �9�4P �4� 344 �60,5 95.5 �9�
Cutout for escutcheon (mm)Type C D E F G
3P �3� 330 ��0 ��3 �464P �3� 400 �90 ��3 �46
Note:Lines X and Y indicate the axes of symmetry of the switch-disconnector.Reference plane Z corresponds to the back of the switch-disconnector.
C-��
Dimensions and connection Interpact INS630b to 1600 Interpact INV630b to 1600
Extended front handle
DB
���5
89
DB
��08
97
(1) Length of shaft = A - 151.
DB
��08
96InstallationOn backplate On rail
DB
�056
94
DB
�056
95
C-��
Interpact INS2000 to 2500 Interpact INV2000 to 2500
Dimensions and connection
DimensionsDirect front handle
3 poles 4 poles
DB
�056
96
DB
�056
97
DB
�056
98
DB
�085
69
A : 50 min. / 72 max.
Door or front panel cutout for front handle
DB
�085
70
DB
�057
00
Cutout for switch-disconnector cover (mm)Type A D E F G
3P �88 �99 �03 �08 ��64P �88 369 �73 �08 ��6
Cutout without escutcheon (mm)Type B D E F G
3P ��3 �74 90,5 95.5 �9�4P ��3 344 �60,5 95.5 �9�
Cutout with escutcheon (mm)Type C D E F G
3P ��3 3�7 ��0 ���,5 �434P ��3 397 �80 ���,5 �43
Note:Lines X and Y indicate the axes of symmetry of the switch-disconnector.Reference plane Z corresponds to the back of the switch-disconnector.
C-�3
Dimensions and connection Interpact INS2000 to 2500 Interpact INV2000 to 2500
Extended front handle
DB
���5
90
DB
��77
68
(1) Length of shaft = A - 232.
DB
��08
96InstallationOn backplate
DB
�057
04
C-�4
Mechanical interlocks for direct and extended handlesINS40 to 630, INV100 to 630
Dimensions and connection
Dimensions for direct handle (INS250-100 to 630 and INV100 to 630)
DB
�057
05
DB
�057
06
Door cutout Dimensions (mm)Type A B C D E F G H K L M N P Q
INS�50 3�5 90 87.5 �75 70 �56 �06 �7.5 �95 75.5 �50 75 68 �36INV�00/�50INS3�0/630 4�6 ��5 �00 �00 9�.5 ��0 �30 ��.5 386 �00 �75 74.5 �0�.5 �05INV3�0/630D
B�0
5707
Dimensions for extended handle (INS250-100 to 630 and INV100 to 630)
DB
�057
08
DB
�057
09
Door cutout Dimensions (mm)Type A B C D E F G H P Q
min. max.INS40/80 - - - - 46 �56 �55 396 - 45 90INS�00/�60 - - - - 70 �56 ��8 5�9 - 50 �00INS�50 3�5 90 87.5 �75 70 �56 �85 600 �7.5 68 �36INV�00/�50INS3�0/630 4�6 ��5 �00 �00 9�.5 ��0 �04 600 ��.5 �0�.5 �05INV3�0/630
Note:Lines X and Y indicate the axes of symmetry of the switch-disconnector.Reference plane Z corresponds to the back of the switch-disconnector.
DB
�067
37
C-�5
Dimensions and connection Complete source changeover assemblyINS250-100 to 630, INV100 to 630
Dimensions of the complete source-changeover assembly with a direct handle
DB
�067
38
DB
�067
39
Front cutout Dimensions (mm)Type A B C D E F G H J K L
INS�50 60.4 �30.4 �95 68 �36 �3� 6�.8 �79.3 84 �56 4�INS3�0/630 8� 5 �75 395 �0�.5 �05 �55 87 383.7 ��8 ��0 64
DB
�067
40
Dimensions of the complete source-changeover assembly with an extended handle
DB
�067
4�
DB
�067
4�
Door cutout Dimensions (mm)Type A B C E K L M N P
INS�50 60.4 �30.4 �95 �36 �56 �38.5 63� 50 �00INV�00/�50INS3�0/630 8�.5 �75 395 �05 ��0 �6�.5 658 75 �50INV3�0/630
Note:Lines X and Y indicate the axes of symmetry of the switch-disconnector.Reference plane Z corresponds to the back of the switch-disconnector.
DB
�067
43
C-�6
Installation of downstream couplingINS250-100 to 630, INV100 to 630
Dimensions and connection
Dimensions
DB
�067
44
DB
�067
45
Dimensions Connection
DB
�067
46
DB
�067
48
DB
�067
47
Dimensions (mm)Type G2 G3 G28 G29 G30 G52 K1 K2 K3 K4 K8 K9 K16
INS�50 �05.5 �69 ��5.� 83.5 ��7.5 �43.5 35 35 5� �56 57.5 �57.5 �5.4INV�00/�50INS3�0/630 �4� �40.7 3�5 ��8.4 �63.4 �0�.5 45 5�.5 75 ��0 88.5 ��5.7 �6.�INV3�0/630Type L28 L29 L30 L31 L32 L33 L34 L35 L36 L37 L38 L39 L40
INS�50 3�0 8�.� 300 7�.� �6.4 ��3 �39.5 74.5 �9.5 70 ��.5 �4.9 �40INV�00/�50INS3�0/630 4�0 �05.� 400 95.� ��.� �87.5 �84.7 96.5 �4 9�.5 �6 ��.4 ��0INV3�0/630
Note:Lines X and Y indicate the axes of symme try of the switch-disconnector.Reference plane Z corresponds to the back of the switch-disconnector.
C-�7
Dimensions and connection Front-panel accessoriesINS250-100 to 2500, INV100 to 2500
Front-panel escutcheonFor switch-disconnectors
DB
�067
49
DB
�067
50
DB
�067
5�
Dimensions (mm) Type A2 D1 D2 M6 M7
INS�50 �74 3.5 6.5 ��4 �0�INV�00/�50INS3�0/630 ��5.5 3.5 6.5 �64 �5�INV3�0/630INS630b/�500 3P 346 3.5 ��.5 �57.5 �4� x 3�6.5INV630b/�500 4P 4�6 3.5 ��.5 �57.5 �4� x 396.5
For ammeter module Connection
DB
�067
5�
DB
�067
53
DB
�067
54
Front alignment (only for INS/INV250-100)
DB
�067
55
DB
�067
56
Note:Lines X and Y indicate the axes of symme try of the switch-disconnector.Reference plane Z corresponds to the back of the switch-disconnector.
C-�8
Parallel or series connection accessories for direct currentInterpact INS250-100 to 250 Interpact INV100 to 250
Dimensions and connection
With series connections3P
DB
��46
78
4P
DB
��46
80
With parallel connections3P 4P
DB
��46
79
DB
��46
8�
C-�9
Dimensions and connection Parallel or series connection accessories for direct currentInterpact INS320 to 630 Interpact INV320 to 630
With series connections3P
DB
��46
8�
4P
DB
��46
83
With parallel connections4P 3P (1)
DB
��46
84
(1) Connection to be made by customer.
schneider-electric.com The electrical installation guide
This international site allows you to access all the Schneider Electric products in just � clicksvia comprehensive range data-sheets, with direct links to:
complete library: technical documents, catalogs, FAQs, brochures…
selection guides from the e-catalog.
product discovery sites andtheir Flash animations.You will also fi nd illustrated overviews, news to which you can subscribe, the list of country contacts…
p
p
p
According to IEC 60364This guide, part of the Schneider Electric offer, is the essential tool to "guide" you any time in your business:
design offi ce, consultantcontractor, panelbuilderteacher, trainer.
Comprehensiveand concrete information on:
all the new technical solutionsall the componentsof an installation from a global
point of viewall the IEC standards modifi cationsall the fundamental
electrotechnical knowledgeall the design stages, from medium
to low voltage.
ppp
ppp
pp
p
TOOLS
D-1
Interpact INS/INV Additional characteristics
Presentation 2Functions and characteristics A-1Installation recommendations B-1Dimensions and connection C-1
Protection of switch-disconnectors D-2INS40 to INS160 by Compact NSX circuit breaker D-2INS/INV100 to INS/INV630 by Compact NSX circuit breaker D-8INS40 to INS160 by Compact NS circuit breaker D-12INS/INV100 to INS/INV630 by Compact NS circuit breaker D-14INS/INV630b to INS/INV2500 by Compact NS circuit breaker D-16INS/INV630b to INS/INV2500 by Masterpact NT and NW circuit breakers D-18INS40 to 2500 and INV100 to 2500 by fuses D-20
Characteristics of switch-disconnectors D-22INS40 to 2500 and INV100 to 2500 for direct current D-22
Catalogue numbers E-1
D-2
Additional characteristics Protection of switch-disconnectorsINS40 to INS160 by Compact NSX circuit breaker
DB
1152
19 Interpact INS switch-disconnectorsUpstream protectionBy Compact NSX
By circuit breaker 380/415 V Type/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peak
D-3
Additional characteristics Protection of switch-disconnectorsINS40 to INS160 by Compact NSX circuit breaker
INS40 INS63 INS80 INS100 INS125 INS160
NSX100B/40 NSX100B/63 NSX100B/80 NSX100B/100 - -
25 25 25 25 52 52 52 52
NSX100F/40 NSX100F/63 NSX100F/80 NSX100F/100 - - 36 36 36 36
75 75 75 75 NSX100N/40 NSX100N/63 NSX100N/80 NSX100N/100 - -
36 36 36 36 75 75 75 75
NSX100H/S/L/40 NSX100H/S/L/63 NSX100H/S/L/80 NSX100H/S/L/100 - - 36 36 36 36
75 75 75 75 NSX160B/40 NSX160B/63 NSX160B/80 NSX160B/100 NSX160B/125 NSX160B/160
25 25 25 25 25 25 52 52 52 52 52 52
NSX160F/40 NSX160F/63 NSX160F/80 NSX160F/100 NSX160F/125 NSX160F/160 25 25 25 36 36 36
52 52 52 75 75 75 NSX160N/40 NSX160N/63 NSX160N/80 NSX160N/100 NSX160N/125 NSX160N/160
25 25 25 50 50 50 52 52 52 105 105 105
NSX160H/S/L/40 NSX160H/S/L/63 NSX160H/S/L/80 NSX160H/S/L/100 NSX160H/S/L/125 NSX160H/S/L/160 25 25 25 70 70 70
52 52 52 154 154 154 - - - NSX250B/100 NSX250B/125 NSX250B/160
25 25 25 52 52 52
- - - NSX250F/100 NSX250F/125 NSX250F/160 36 36 36
75 75 75 - - - NSX250N/100 NSX250N/125 NSX250N/160
50 50 50 105 105 105
- - - NSX250H/S/L/100 NSX250H/S/L/125 NSX250H/S/L/160 70 70 70
154 154 154 NSC100N/40 NSC100N/63 NSC100N/80 NSC100N/100 - -
18 18 18 18 37 37 37 37
NG125N/40 NG125N/63 NG125N/80 NG125N/100 NG125N/125 - 25 25 25 25 25
52 52 52 52 52 NG125H/40 NG125H/63 NG125H/80 - - -
36 36 36 75 75 75
NG125L/40 NG125L/63 NG125L/80 - - - 50 50 50
105 105 105 NG160N/40 NG160N/63 NG160N/80 NG160N/100 NG160N/125 NG160N/160
30 30 30 30 30 30 63 63 63 63 63 63
D-4
Additional characteristics Protection of switch-disconnectorsINS40 to INS160 by Compact NSX circuit breaker
DB
1152
19 Interpact INS switch-disconnectorsUpstream protectionBy Compact NSX
By circuit breaker Type/maximum rating (A)440/480 V (1) Isc max. kA rms
Making capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peak
By circuit breaker Type/maximum rating (A)500/525 V Isc max. kA rms
Making capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peak
(1) Applicable for 480 NEMA.
D-5
Additional characteristics Protection of switch-disconnectorsINS40 to INS160 by Compact NSX circuit breaker
INS40 INS63 INS80 INS100 INS125 INS160
NSX100B/40 NSX100B/63 NSX100B/80 NSX100B/100 - -
20 20 20 20 40 40 40 40
NSX100F/40 NSX100F/63 NSX100F/80 NSX100F/100 - - 35 35 35 35
73 73 73 73 NSX100N/40 NSX100N/63 NSX100N/80 NSX100N/100 - -
35 35 35 35 73 73 73 73
NSX100H/S/L/40 NSX100H/S/L/63 NSX100H/S/L/80 NSX100H/S/L/100 - - 35 35 35 65
73 73 73 143 NSX160B/40 NSX160B/63 NSX160B/80 NSX160B/100 NSX160B/125 NSX160B/160
20 20 20 20 20 20 40 40 40 40 40 40
NSX160F/40 NSX160F/63 NSX160F/80 NSX160F/100 NSX160F/125 NSX160F/160 25 25 25 35 35 35
52 52 52 73 73 73 NSX160N/40 NSX160N/63 NSX160N/80 NSX160N/100 NSX160N/125 NSX160N/160
25 25 25 35 35 35 52 52 52 73 73 73
NSX160H/S/L/40 NSX160H/S/L/63 NSX160H/S/L/80 NSX160H/S/L/100 NSX160H/S/L/125 NSX160H/S/L/160 25 25 25 65 65 65
52 52 52 143 143 143 - - - NSX250B/100 NSX250B/125 NSX250B/160
20 20 20 40 40 40
- - - NSX250F/100 NSX250F/125 NSX250F/160 35 35 35
73 73 73 - - - NSX250N/100 NSX250N/125 NSX250N/160
35 35 35 73 73 73
- - - NSX250H/S/L/100 NSX250H/S/L/125 NSX250H/S/L/160 65 65 65
143 143 143 NSC100N/40 NSC100N/63 NSC100N/80 NSC100N/100 - -
18 18 18 18 37 37 37 37
NSX100B/40 NSX100B/63 NSX100B/80 NSX100B/100 - - 15 15 15 15
30 30 30 30 NSX100F/40 NSX100F/63 NSX100F/80 NSX100F/100 - -
18 18 18 18 36 36 36 36
NSX100N/40 NSX100N/63 NSX100N/80 NSX100N/100 - - 18 18 18 18
36 36 36 36 NSX100H/S/L/40 NSX100H/S/L/63 NSX100H/S/L/80 NSX100H/S/L/100 - -
25 25 25 25 53 53 53 53
NSX160B/40 NSX160B/63 NSX160B/80 NSX160B/100 NSX160B/125 NSX160B/160 15 15 15 15 15 15
30 30 30 30 30 30 NSX160F/40 NSX160F/63 NSX160F/80 NSX160F/100 NSX160F/125 NSX160F/160
15 15 15 15 22 22 30 30 30 30 46 46
NSX160N/40 NSX160N/63 NSX160N/80 NSX160N/100 NSX160N/125 NSX160N/160 15 15 15 15 22 22
30 30 30 30 46 46 NSX160H/S/L/40 NSX160H/S/L/63 NSX160H/S/L/80 NSX160H/S/L/100 NSX160H/S/L/125 NSX160H/S/L/160
15 15 15 22 22 22 30 30 30 46 46 46
- - - NSX250B/100 NSX250B/125 NSX250B/160 15 15 15
30 30 30 - - - NSX250F/100 NSX250F/125 NSX250F/160
15 22 22 30 46 46
- - - NSX250N/100 NSX250N/125 NSX250N/160 15 22 22
30 46 46 - - - NSX250H/S/L/100 NSX250H/S/L/125 NSX250H/S/L/160
22 22 22 46 46 46
NSC100N/40 NSC100N/63 NSC100N/80 NSC100N/100 - - 18 18 18 18
37 37 37 37
D-6
Additional characteristics Protection of switch-disconnectorsINS40 to INS160 by Compact NSX circuit breaker
DB
1152
19 Interpact INS switch-disconnectorsUpstream protectionBy Compact NSX
By circuit breaker 690 V Type/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peak
Upstream protection by fuseBy 500 V fuse Type aM (2)/maximum rating (A)
Isc max. kA rmsMaking capacity kA peakType gG (3)/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType gG (2)/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType BS (3)/maximum rating (A) Isc max. kA rmsMaking capacity kA peakType BS (2)/maximum rating (A) Isc max. kA rmsMaking capacity kA peak
By 690 V fuse Type aM (2)/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType gG (3)/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType gG (2)/maximum rating (A)Isc max. kA rmsMaking capacity kA peak
(2) Protection by external thermal relay obligatory. (3) Without external thermal relay.
D-7
Additional characteristics Protection of switch-disconnectorsINS40 to INS160 by Compact NSX circuit breaker
INS40 INS63 INS80 INS100 INS125 INS160
- - - NSX100B/100 - -
6 9
- - - NSX100F/100 - - 8
14 - - - NSX100N/100 - -
10 17
- - - NSX100H/S/L/100 - - 10
17 - - - NSX160B/100 NSX160B/125 NSX160B/160
6 6 6 9 9 9
- - - NSX160F/100 NSX160F/125 NSX160F/160 8 8 8
14 14 14 - - - NSX160N/100 NSX160N/125 NSX160N/160
10 10 10 17 17 17
- - - NSX160H/S/L/100 NSX160H/S/L/125 NSX160H/S/L/160 10 10 10
17 17 17 - - - NSX250B/100 NSX250B/125 NSX250B/160
6 6 6 9 9 9
- - - NSX250F/100 NSX250F/125 NSX250F/160 8 8 8
14 14 14 - - - NSX250N/100 NSX250N/125 NSX250N/160
10 10 10 17 17 17
- - - NSX250H/S/L/100 NSX250H/S/L/125 NSX250H/S/L/160 10 10 10
17 17 17 NSC100N/40 NSC100N/63 NSC100N/80 NSC100N/100 - -
18 18 18 18 37 37 37 37
125 125 125 200 200 200
100 100 100 100 100 100 220 220 220 220 220 220
32 50 50 80 100 125 100 100 100 100 100 100
120 120 120 220 220 220 100 100 100 125/160 125/160 125/160
100 100 100 100/50 100/50 100/50 220 220 220 220/105 220/105 220/105
32 50 and 32M50 63 and 32M63 80 and 63M80 100 and 63M100 125 and 100M125 80 80 80 80 80 80
176 176 176 176 176 176 125 and 100M125 125 and 100M125 125 and 100M125 160 and 100M160 160 and 100M160 160 and 100M160
80 80 80 80 80 80 176 176 176 176 176 176
- - - - - -
- - - - - -
- - - - - -
D-8
Additional characteristics Protection of switch-disconnectorsINS/INV100 to INS/INV630 by Compact NSX circuit breaker
DB
1152
20 Interpact INS switch-disconnectors INS250-100 / INV100 INS250-160 / INV160 Upstream protectionBy Compact NSX
By circuit breaker 380/415 V Type/maximum rating (A) NSX100-160-250B/100 NSX160-250B/160Isc max. kA rms 25 25Making capacity kA peak 52 52Type/maximum rating (A) NSX100-160-250F/100 NSX160-250F/160Isc max. kA rms 36 36Making capacity kA peak 75 75Type/maximum rating (A) NSX100-160-250N/100 NSX160-250N/160Isc max. kA rms 50 50Making capacity kA peak 105 105Type/maximum rating (A) NSX100-160-250H/100 NSX160-250H/160Isc max. kA rms 70 70Making capacity kA peak 154 154Type/maximum rating (A) NSX100-160-250S/100 NSX160-250S/160Isc max. kA rms 100 100Making capacity kA peak 120 120Type/maximum rating (A) NSX100-160-250L/100 NSX160-250L/160Isc max. kA rms 150 150Making capacity kA peak 330 330
By circuit breaker Type/maximum rating (A) NSX100-160-250B/100 NSX160-250B/160440/480 V (1) Isc max. kA rms 20 20
Making capacity kA peak 40 40Type/maximum rating (A) NSX100-160-250F/100 NSX160-250F/160Isc max. kA rms 35 35Making capacity kA peak 73 73Type/maximum rating (A) NSX100-160-250N/100 NSX160-250N/160Isc max. kA rms 50 50Making capacity kA peak 105 105Type/maximum rating (A) NSX100-160-250H/100 NSX160-250H/160Isc max. kA rms 65 65Making capacity kA peak 143 143Type/maximum rating (A) NSX100-160-250S/100 NSX160-250S/160Isc max. kA rms 90 90Making capacity kA peak 198 198Type/maximum rating (A) NSX100-160-250L/100 NSX160-250L/160Isc max. kA rms 130 130Making capacity kA peak 286 286
By circuit breaker 500 V Type/maximum rating (A) NSX100-160-250B/100 NSX160-250B/160Isc max. kA rms 15 15Making capacity kA peak 30 30Type/maximum rating (A) NSX100F/100 -Isc max. kA rms 25Making capacity kA peak 52Type/maximum rating (A) NSX160-250F/100 NSX160-250H/160Isc max. kA rms 30 30Making capacity kA peak 63 63Type/maximum rating (A) NSX100-160-250N/100 NSX160-250N/160Isc max. kA rms 36 36Making capacity kA peak 75 75Type/maximum rating (A) NSX100-160-250H/100 NSX160-250H/160Isc max. kA rms 50 50Making capacity kA peak 105 105Type/maximum rating (A) NSX100-160-250S/100 NSX160-250S/160Isc max. kA rms 65 65Making capacity kA peak 143 143Type/maximum rating (A) NSX100-160-250L/100 NSX160-250L/160Isc max. kA rms 70 70Making capacity kA peak 154 154
(1) Applicable for 480 NEMA.
D-9
Additional characteristics Protection of switch-disconnectorsINS/INV100 to INS/INV630 by Compact NSX circuit breaker
INS250-200 / INS/INV250 INS/INV320 INS/INV400 INS/INV500 INS/INV630 INV200
NSX250B/200 NSX250N/250 - - - -
25 25 52 52
NSX250F/200 NSX250F/250 NSX400-630F/320 NSX400-630F/400 NSX630F/500 NSX630F/630 36 36 36 36 36 36
75 75 75 75 75 75 NSX250N/200 NSX250N/250 NSX400-630N/320 NSX400-630N/400 NSX630N/500 NSX630N/630
50 50 50 50 50 50 105 105 105 105 105 105
NSX250H/200 NSX250H/250 NSX400-630H/320 NSX400-630H/400 NSX630H/500 NSX630H/630 70 70 70 70 70 70
154 154 154 154 154 154 NSX250S/200 NSX250S/250 NSX400-630S/320 NSX400-630S/400 NSX630S/500 NSX630S/630
100 100 100 100 100 100 120 120 120 120 120 120
NSX250L/200 NSX250L/250 NSX400-630L/320 NSX400-630L/400 NSX630L/500 NSX630L/630 150 150 150 150 150 150
330 330 330 330 330 330 NSX250B/200 NSX250B/250 - - - -
20 20 40 40
NSX250F/200 NSX250F/250 NSX400-630F/320 NSX400-630F/400 NSX630F/500 NSX630F/630 35 35 35 35 35 35
73 73 73 73 73 73 NSX250N/200 NSX250N/250 NSX400-630N/320 NSX400-630N/400 NSX630N/500 NSX630N/630
50 50 50 50 50 50 105 105 105 105 105 105
NSX250H/200 NSX250H/250 NSX400-630H/320 NSX400-630H/400 NSX630H/500 NSX630H/630 65 65 65 65 65 65
143 143 143 143 143 143 NSX250S/200 NSX250S/250 NSX400-630S/320 NSX400-630S/400 NSX630S/500 NSX630S/630
90 90 90 90 90 90 198 198 198 198 198 198
NSX250L/200 NSX250L/250 NSX400-630L/320 NSX400-630L/400 NSX630L/500 NSX630L/630 130 130 130 130 130 130
286 286 286 286 286 286 NSX250B/200 NSX250B/250 - - - -
15 15 30 30
- - - - - -
NSX250F/200 NSX250F/250 NSX400-630F/320 NSX400-630F/400 NSX630F/500 NSX630F/630
30 30 25 25 25 25 63 63 52 52 52 52
NSX250N/200 NSX250N/250 NSX400-630N/320 NSX400-630N/400 NSX630N/500 NSX630N/630 36 36 30 30 30 30
75 75 63 63 63 63 NSX250H/200 NSX250H/250 NSX400-630H/320 NSX400-630H/400 NSX630H/500 NSX630H/630
50 50 50 50 50 50 105 105 105 105 105 105
NSX250S/200 NSX250S/250 NSX400-630S/320 NSX400-630S/400 NSX630S/500 NSX630S/630 65 65 65 65 65 65
143 143 143 143 143 143 NSX250L/200 NSX250L/250 NSX400-630L/320 NSX400-630L/400 NSX630L/500 NSX630L/630
70 70 70 70 70 70 154 154 154 154 154 154
D-10
Additional characteristics Protection of switch-disconnectorsINS/INV100 to INS/INV630 by Compact NSX circuit breaker
DB
1152
20 Interpact INS switch-disconnectors INS250-100 / INV100 INS250-160 / INV160 Upstream protectionBy Compact NSX
By circuit breaker 525 V Type/maximum rating (A) NSX100-160-250B/100 NSX160-250B/160Isc max. kA rms 12 12Making capacity kA peak 24 24Type/maximum rating (A) NSX100-160-250F/100 NSX160-250F/160Isc max. kA rms 22 22Making capacity kA peak 47 47Type/maximum rating (A) NSX100-160-250N/100 NSX160-250N/160Isc max. kA rms 35 35Making capacity kA peak 73 73Type/maximum rating (A) NSX100-160-250H/100 NSX160-250H/160Isc max. kA rms 35 35Making capacity kA peak 73 73Type/maximum rating (A) NSX100-160-250S/100 NSX160-250S/160Isc max. kA rms 40 40Making capacity kA peak 81 81Type/maximum rating (A) NSX100-160-250L/100 NSX160-250L/160Isc max. kA rms 50 50Making capacity kA peak 105 105
By circuit breaker 690 V Type/maximum rating (A) NSX100-160-250B/100 NSX160-250B/160Isc max. kA rms 6 6Making capacity kA peak 9 9Type/maximum rating (A) NSX100-160-250F/100 NSX160-250F/160Isc max. kA rms 8 8Making capacity kA peak 14 14Type/maximum rating (A) NSX100-160-250N/100 NSX160-250N/160Isc max. kA rms 10 10Making capacity kA peak 17 17Type/maximum rating (A) NSX100-160-250H/100 NSX160-250H/160Isc max. kA rms 10 10Making capacity kA peak 17 17Type/maximum rating (A) NSX100-160-250S/100 NSX160-250S/160Isc max. kA rms 15 15Making capacity kA peak 30 30Type/maximum rating (A) NSX100-160-250L/100 NSX160-250L/160Isc max. kA rms 20 20Making capacity kA peak 40 40
Upstream protection by fuseBy 500 V fuse Type aM (2)/maximum rating (A) 315 315
Isc max. kA rms 100 100Making capacity kA peak 220 220Type gG (3)/maximum rating (A) 80 125Isc max. kA rms 100 100Making capacity kA peak 220 220Type gG (2)/maximum rating (A) 225/355 225/355Isc max. kA rms 100/50 100/50Making capacity kA peak 220/105 220/105Type BS (3)/maximum rating (A) 80 and 63M80 125 and 100M125 Isc max. kA rms 80 80Making capacity kA peak 176 176Type BS (2)/maximum rating (A) 250 and 200M250 250 and 200M250 Isc max. kA rms 80 80Making capacity kA peak 176 176
By 690 V fuse Type aM (2)/maximum rating (A) - -Isc max. kA rmsMaking capacity kA peakType gG (3)/maximum rating (A) - -Isc max. kA rmsMaking capacity kA peakType gG (2)/maximum rating (A) - -Isc max. kA rmsMaking capacity kA peak
(2) Protection by external thermal relay obligatory. (3) Without external thermal relay.
D-11
Additional characteristics Protection of switch-disconnectorsINS/INV100 to INS/INV630 by Compact NSX circuit breaker
INS250-200 / INS/INV250 INS/INV320 INS/INV400 INS/INV500 INS/INV630 INV200
NSX250B/200 NSX250B/250 - - - -
12 12 24 24
NSX250F/200 NSX250F/250 NSX400-630F/320 NSX400-630F/400 NSX630F/500 NSX630F/630 22 22 22 22 22 22
47 47 47 47 47 47 NSX250N/200 NSX250N/250 NSX400-630N/320 NSX400-630N/400 NSX630N/500 NSX630N/630
35 35 22 22 22 22 73 73 47 47 47 47
NSX250H/200 NSX250H/250 NSX400-630H/320 NSX400-630H/400 NSX630H/500 NSX630H/630 35 35 35 35 35 35
73 73 73 73 73 73 NSX250S/200 NSX250S/250 NSX400-630S/320 NSX400-630S/400 NSX630S/500 NSX630S/630
40 40 40 40 40 40 81 81 81 81 81 81
NSX250L/200 NSX250L/250 NSX400-630L/320 NSX400-630L/400 NSX630L/500 NSX630L/630 50 50 50 50 50 50
105 105 105 105 105 105 NSX250B/200 NSX250B/250 - - - -
6 6 9 9
NSX250F/200 NSX250F/250 NSX400-630F/320 NSX400-630F/400 NSX630F/500 NSX630F/630 8 8 8 8 8 8
14 14 14 14 14 14 NSX250N/200 NSX250N/250 NSX400-630N/320 NSX400-630N/400 NSX630N/500 NSX630N/630
10 10 10 10 10 10 17 17 17 17 17 17
NSX250H/200 NSX250H/250 NSX400-630H/320 NSX400-630H/400 NSX630H/500 NSX630H/630 10 10 10 10 10 10
17 17 17 17 17 17 NSX250S/200 NSX250S/250 NSX400-630S/320 NSX400-630S/400 NSX630S/500 NSX630S/630
15 15 15 15 15 15 30 30 30 30 30 30
NSX250L/200 NSX250L/250 NSX400-630L/320 NSX400-630L/400 NSX630L/500 NSX630L/630 20 20 20 20 20 20
40 40 40 40 40 40
315 315 800 800 800 800 100 100 100 100 100 100
220 220 220 220 220 220 160 200 250 315 400 500
100 100 100 100 100 100 220 220 220 220 220 220
225/355 225/355 630 630 630 500/630 100/50 100/50 50 50 50 100/50
220/105 220/105 105 105 105 220/105 160 and 100M160 200 and 100M200 250 and 200M250 315 and 200M250 400 450 and 400M450
80 80 80 80 80 80 176 176 176 176 176 176
250 and 200M250 250 and 200M250 355 and 315M355 355 and 315M355 450 and 400M450 450 and 400M450 80 80 80 80 80 80
176 176 176 176 176 176 - - - 800 800 800
100 100 100 220 220 220
- - - 315 400 500 100 100 100
220 220 220 - - - 630 630 500/630
50 50 100/50 105 105 220/105
D-12
Protection of switch-disconnectorsINS40 to INS160 by Compact NS circuit breaker
Additional characteristicsD
B11
5219
Interpact INS switch-disconnectorsUpstream protectionBy Compact NS circuit breaker
By circuit breaker 380/415 V Type/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peak
By circuit breaker Type/maximum rating (A)440/480 V (1) Isc max. kA rms
Making capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peak
By circuit breaker Type/maximum rating (A)500 V (INS40 to INS80) Isc max. kA rms500/525 V (INS100 to INS160) Making capacity kA peak
Type/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peak
By circuit breaker 690 V Type/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peak
(1) Applicable for 480 NEMA.
D-13
Additional characteristics Protection of switch-disconnectorsINS40 to INS160 by Compact NS circuit breaker
INS40 INS63 INS80 INS100 INS125 INS160
NS100N/40 NS100N/63 NS100N/80 NS100N/100 - -
36 36 36 36 75 75 75 75
NS100SX-H-L/40 NS100SX-H-L/63 NS100SX-H-L/80 NS100SX-H-L/100 - - 36 36 36 50/70
75 75 75 105/54 NS160N-SX/40 NS160N-SX/63 NS160N-SX/80 NS160-250N/100 NS160-250N/125 NS160-250N/160
25 25 25 36 36 36 52 52 52 75 75 75
NS160H-L/40 NS160H-L/63 NS160H-L/80 NS160-250SX-H-L/100 NS160-250SX-H-L/125 NS160-250SX-H-L/160 25 25 25 50/70 50/70 50/70
52 52 52 105/154 105/154 105/154 NSC100N/40 NSC100N/63 NSC100N/80 NSC100N/100 - -
18 18 18 18 37 37 37 37
NG125N/40 NG125N/63 NG125N/80 NG125N/100 NG125N/125 - 25 25 25 25 25
52 52 52 52 52 NG125H/40 NG125H/63 NG125H/80 - - -
36 36 36 75 75 75
NG125L/40 NG125L/63 NG125L/80 - - - 50 50 50
105 105 105 NSA160N/40 NSA160N/63 NSA160N/80 NSA160N/100 NSA160N/125 NSA160N/160
30 30 30 30 30 30 63 63 63 63 63 63
NS100N/40 NS100N/63 NS100N/80 NS100N/100 - - 35 35 35 35
73 73 73 73 NS100SX-H-L/40 NS100SX-H-L/63 NS100SX-H-L/80 NS100SX-H-L/100 - -
35 35 35 35/65 73 73 73 73/143
NS160N/40 NS160N/63 NS160N/80 NS160-250N/100 NS160-250N/125 NS160-250N/160 25 25 25 35 35 35
52 52 52 73 73 73 NS160H-L/40 NS160H-L/63 NS160H-L/80 NS160-250SX-H-L/100 NS160-250SX-H-L/125 NS160-250SX-H-L/160
25 25 25 35/65 35/65 35/65 52 52 52 73/143 73/143 73/143
NSC100N/40 NSC100N/63 NSC100N/80 NSC100N/100 - - 18 18 18 18
37 37 37 37 NS100N/40 NS100N/63 NS100N/80 NS100N/100 - -
18 18 18 18 36 36 36 36
NS100SX-H-L/40 NS100SX-H-L/63 NS100SX-H-L/80 NS100SX-H-L/100 - - 18-25 18-25 18-25 35-100
36-53 36-53 36-53 73-220 NS160N/40 NS160N/63 NS160N/80 NS160-250N/100 NS160-250N/125 NS160-250N/160
15 15 15 22 22 22 30 30 30 46 46 46
NS160SX-H-L/40 NS160SX-H-L/63 NS160SX-H-L/80 NS160-250SX-H-L/100 NS160-250SX-H-L/125 NS160-250SX-H-L/160 15 15 15 22 22 22
30 30 30 46 46 46 NSC100N/40 NSC100N/63 NSC100N/80 NSC100N/100 - -
10 10 10 10 17 17 17 17
- - - NS100N/100 - - 8
14 - - - NS100SX-H-L/100
10-75 17-165
- - - NS160-250N/100 NS160-250N/125 NS160-250N/160 8 8 8
14 14 14 - - - NS160-250SX-H-L/100 NS160-250SX-H-L/125 NS160-250SX-H-L/160
10-20 10-20 10-20 17-40 17-40 17-40
D-14
Protection of switch-disconnectorsINS/INV100 to INS/INV630 by Compact NS circuit breaker
Additional characteristicsD
B11
5220
Interpact INS switch-disconnectors INS250-100 / INV100 INS250-160 / INV160 Upstream protectionBy Compact NS circuit breaker
By circuit breaker 380/415 V Type/maximum rating (A) NS100-160-250N/100 NS160-250N/160Isc max. kA rms 36 36Making capacity kA peak 75 75Type/maximum rating (A) NS100-160-250SX/100 NS160-250SX/160Isc max. kA rms 50 50Making capacity kA peak 105 105Type/maximum rating (A) NS100-160-250H/100 NS160-250H/160Isc max. kA rms 70 70Making capacity kA peak 154 154Type/maximum rating (A) NS100-160-250L/100 NS160-250L/160Isc max. kA rms 150 150Making capacity kA peak 330 330
By circuit breaker Type/maximum rating (A) NS100-160-250N/100 NS160-250N/160440/480 V (1) Isc max. kA rms 35 35
Making capacity kA peak 73 73Type/maximum rating (A) NS100-160-250SX NS160-250SXIsc max. kA rms 50 50Making capacity kA peak 105 105Type/maximum rating (A) NS100-160-250H/100 NS160-250H/160Isc max. kA rms 65 65Making capacity kA peak 143 143Type/maximum rating (A) NS100-160-250L/100 NS160-250L/160Isc max. kA rms 130 130Making capacity kA peak 286 286
By circuit breaker 500 V Type/maximum rating (A) NS100-160-250N/100 NS160-250N/160Isc max. kA rms 25-30-30 30Making capacity kA peak 53-63-63 63Type/maximum rating (A) NS100-160-250SX/100 NS160-250SX/160Isc max. kA rms 36 36Making capacity kA peak 75 75Type/maximum rating (A) NS100-160-250H/100 NS160-250H/160Isc max. kA rms 50 50Making capacity kA peak 105 105Type/maximum rating (A) NS100-160-250L/100 NS160-250L/160Isc max. kA rms 100-70-70 70Making capacity kA peak 220-154-154 154
By circuit breaker 525 V Type/maximum rating (A) NS100-160-250N/100 NS160-250N/160Isc max. kA rms 22 22Making capacity kA peak 46 46Type/maximum rating (A) NS100-160-250SX/100 NS160-250SX/160Isc max. kA rms 35 35Making capacity kA peak 73 73Type/maximum rating (A) NS100-160-250H/100 NS160-250H/160Isc max. kA rms 35 35Making capacity kA peak 73 73Type/maximum rating (A) NS100-160-250L/100 NS160-250L/160Isc max. kA rms 100-50-50 50Making capacity kA peak 220-105-105 105
By circuit breaker 690 V Type/maximum rating (A) NS100-160-250N/100 NS160-250N/160Isc max. kA rms 8 8Making capacity kA peak 14 14Type/maximum rating (A) NS100-160-250SX/100 NS160-250SX/160Isc max. kA rms 10 10Making capacity kA peak 17 17Type/maximum rating (A) NS100-160-250H/100 NS160-250H/160Isc max. kA rms 10 10Making capacity kA peak 17 17Type/maximum rating (A) NS100-160-250L/100 NS160-250L/160Isc max. kA rms 75-20-20 20Making capacity kA peak 165-40-40 40
(1) Applicable for 480 NEMA.
D-15
Additional characteristics Protection of switch-disconnectorsINS/INV100 to INS/INV630 by Compact NS circuit breaker
INS250-200 / INS/INV250 INS/INV320 INS/INV400 INS/INV500 INS/INV630 INV200
NS250N/200 NS250N/250 NS400-630N/320 NS400-630N/400 NS630N/500 NS630N/630
36 36 50 50 50 50 75 75 105 105 105 105
NS250SX/200 NS250SX/250 - - - - 50 50
105 105 NS250H/200 NS250H/250 NS400-630H/320 NS400-630H/400 NS630H/500 NS630H/630
70 70 70 70 70 70 154 154 154 154 154 154
NS250L/200 NS250L/250 NS400-630L/320 NS400-630L/400 NS630L/500 NS630L/630 150 150 150 150 150 150
330 330 330 330 330 330 NS250N/200 NS250N/250 NS400-630N/320 NS400-630N/400 NS630N/500 NS630N/630
35 35 42 42 42 42 73 73 88 88 88 88
NS250SX/200 NS250SX/250 - - - - 50 50
105 105 NS250H/200 NS250H/250 NS400-630H/320 NS400-630H/400 NS630H/500 NS630H/630
65 65 65 65 65 65 143 143 143 143 143 143
NS250L/200 NS250L/250 NS400-630L/320 NS400-630L/400 NS630L/500 NS630L/630 130 130 130 130 130 130
286 286 286 286 286 286 NS250N/200 NS250N/250 NS400-630N/320 NS400-630N/400 NS630N/500 NS630N/630
30 30 30 30 30 30 63 63 63 63 63 63
NS250SX/200 NS250SX/250 - - - - 36 36
75 75 NS250H/200 NS250H/250 NS400-630H/320 NS400-630H/400 NS630H/500 NS630H/630
50 50 50 50 50 50 105 105 105 105 105 105
NS250L/200 NS250L/250 NS400-630L/320 NS400-630L/400 NS630L/500 NS630L/630 70 70 100-70 100-70 70 70
154 154 220-154 220-154 154 154 NS250N/200 NS250N/250 NS400-630N/320 NS400-630N/400 NS630N/500 NS630N/630
22 22 22 22 22 22 46 46 46 46 46 46
NS250SX/200 NS250SX/250 - - - - 35 35
73 73 NS250H/200 NS250H/250 NS400-630H/320 NS400-630H/400 NS630H/500 NS630H/630
35 35 35 35 35 35 73 73 73 73 73 73
NS250L/200 NS250L/250 NS400-630L/320 NS400-630L/400 NS630L/500 NS630L/630 50 50 100-50 100-50 50 50
105 105 220-105 220-105 105 105 NS250N/200 NS250N/250 NS400-630N/320 NS400-630N/400 NS630N/500 NS630N/630
8 8 10 10 10 10 14 14 17 17 17 17
NS250SX/200 NS250SX/250 - - - - 10 10
17 17 NS250H/200 NS250H/250 NS400-630H/320 NS400-630H/400 NS630H/500 NS630H/630
10 10 20 20 20 20 17 17 40 40 42 42
NS250L/200 NS250L/250 NS400-630L/320 NS400-630L/400 NS630L/500 NS630L/630 20 20 75-35 75-35 35 35
40 40 165-73 165-73 73 73
D-16
Protection of switch-disconnectorsINS/INV630b to INS/INV2500 by Compact NS circuit breaker
Additional characteristicsD
B11
5221
Interpact INS switch-disconnectorsUpstream protectionBy Compact NS circuit breaker
By circuit breaker 380/415 V Type/maximum rating (A) Isc max. kA rmsMaking capacity kA peakType/maximum rating (A) Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peak
By circuit breaker Type/maximum rating (A) 440/480 V (1) Isc max. kA rms
Making capacity kA peakType/maximum rating (A) Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peak
By circuit breaker Type/maximum rating (A) 500/525 V Isc max. kA rms
Making capacity kA peakType/maximum rating (A) Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peak
By circuit breaker Type/maximum rating (A)690 V Isc max. kA rms
Making capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peak
By Masterpact NT H1 circuit breakerBy circuit breaker Type/maximum rating (A)220/690 V Isc max. kA rms
Making capacity kA peakBy Masterpact NT H2 circuit breaker
By circuit breaker Type/maximum rating (A)220/690 V Isc max. kA rms
Making capacity kA peakBy Masterpact NT L1 circuit breaker
By circuit breaker Type/maximum rating (A)220/525 V Isc max. kA rms Making capacity kA peakBy circuit breaker Type/maximum rating (A)690 V Isc max. kA rms
Making capacity kA peak(1) Applicable for 480 NEMA.
D-17
Additional characteristics Protection of switch-disconnectorsINS/INV630b to INS/INV2500 by Compact NS circuit breaker
INS/INV630b INS/INV800 INS/INV1000 INS/INV1250 INS/INV1600 INS/INV2000 INS/INV2500
NS630bN/630 NS800N/800 NS1000N/1000 NS1250N/1250 NS1600N - NS1600bN/1600 NS2000N/2000 NS2500N/2500
35 35 35 35 35 50 50 75 75 75 75 75 105 105
NS630bH/630 NS800H/800 NS1000H/1000 NS1250H/1250 NS1600H - NS1600bH/1600 NS2000H/2000 NS2500H/2500 35 35 35 35 35 50 50
75 75 75 75 75 105 105 NS630bL/630 NS800L/800 NS1000L/1000 - - - -
150 150 150 330 330 330
NS630bN/630 NS800N/800 NS1000N/1000 NS1250N/1250 NS1600N - NS1600bN/1600 NS2000N/2000 NS2500N/2500 35 35 35 35 35 50 50
75 75 75 75 75 105 105 NS630bH/630 NS800H/800 NS1000H/1000 NS1250H/1250 NS1600H - NS1600bH/1600 NS2000H/2000 NS2500H/2500
35 35 35 35 35 50 50 75 75 75 75 75 105 105
NS630bL/630 NS800L/800 NS1000L/1000 - - - - 130 130 130
286 286 286 NS630bN/630 NS800N/800 NS1000N/1000 NS1250N/1250 NS1600N - NS1600bN/1600 NS2000N/2000 NS2500N/2500
35 35 35 35 35 50 50 75 75 75 75 75 105 105
NS630bH/630 NS800H/800 NS1000H/1000 NS1250H/1250 NS1600H - NS1600bH/1600 NS2000H/2000 NS2500H/2500 35 35 35 35 35 50 50
75 75 75 75 75 105 105 NS630bL/630 NS800L/800 NS1000L/1000 - - - -
100 100 100 220 220 220
NS630bN/630 NS800N/800 NS1000N/1000 NS1250N/1250 NS1600bN/1600 NS2000N/2000 NS2500N/2500 30 30 30 30 30 50 50
63 63 63 63 63 105 105 NS630bH/630 NS800H/800 NS1000H/1000 NS1250H/1250 NS1600bH/1600 NS2000H/2000 NS2500H/2500
35 35 35 35 35 50 50 75 75 75 75 75 105 105
NS630bL/630 NS800L/800 NS1000L/1000 - - - - 25 25 25
53 53 53
NT06H1/630 NT08H1/800 NT10H1/1000 NT12H1/1250 NT16H1/1600 - - 35 35 35 35 35
75 75 75 75 75
NT06H2/630 NT08H2/800 NT10H2/1000 NT12H2/1250 NT16H2/1600 - - 35 35 35 35 35
75 75 75 75 75
NT06L1/630 NT08L1/800 NT10L1/1000 NT12L1/1250 NT16L1/1600 - - 100 100 100 100 100
220 220 220 220 220 NT06L1/630 NT08L1/800 NT10L1/1000 NT12L1/1250 NT16L1/1600 - - 25 25 25 25 25
53 53 53 53 53
D-18
Protection of switch-disconnectorsINS/INV630b to INS/INV2500 by Masterpact NT and NW circuit breakers
Additional characteristicsD
B11
5222
Interpact INS switch-disconnectorsUpstream protectionBy Masterpact NW N1- H1- H2- H3 circuit breaker
By circuit breaker Type/maximum rating (A)220/440-480 V (1) Isc max. kA rms
Making capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peak
By circuit breaker Type/maximum rating (A)500/525 V Isc max. kA rms
Making capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peakType/maximum rating (A)Isc max. kA rmsMaking capacity kA peak
By circuit breaker Type/maximum rating (A)690 V Isc max. kA rms
Making capacity kA peakType/maximum rating (A)Isc max. kA rms DIN OFF / DIN ONMaking capacity kA peak DIN OFF / DIN ONType/maximum rating (A)Isc max. kA rms DIN OFF / DIN ONMaking capacity kA peak DIN OFF / DIN ONType/maximum rating (A)Isc max. kA rms DIN OFF / DIN ONMaking capacity kA peak DIN OFF / DIN ON
By Masterpact NW L1 circuit breakerBy circuit breaker Type/maximum rating (A)220/690 V Isc max. kA rms
Making capacity kA peakBy fuse
By fuse 500 V Type aM (2) / max. rating (A)Isc max. kA rmsMaking capacity kA peakType gG (3) / max. ra ing (A)Isc max. kA rmsMaking capacity kA peakType gG (2) / max. rating (A)Isc max. kA rms
Making capacity kA peakType BS (3) / max. rating (A)Isc max. kA rms
Making capacity kA peakType BS (2) / max. ra ing (A)Isc max. kA rms
Making capacity kA peakBy fuse 690 V Type aM (2) / max. rating (A)
Isc max. kA rmsMaking capacity kA peakType gG (3) / max. ra ing (A)Isc max. kA rms
Making capacity kA peakType gG (2) / max. ra ing (A)Isc max. kA rms
Making capacity kA peak(1) Applicable for 480 NEMA.(2) Mandatory protection by an external thermal relay.(3) No external thermal relay.
D-19
Additional characteristics Protection of switch-disconnectorsINS/INV630b to INS/INV2500 by Masterpact NT and NW circuit breakers
INS/INV630b INS/INV800 INS/INV1000 INS/INV1250 INS/INV1600 INS/INV2000 INS/INV2500
NW08N1/630 NW08N1/800 NW10N1/1000 NW12N1/1250 NW16N1/1600 - -
35 35 35 35 35 75 75 75 75 75
NW08H1/630 NW08H1/800 NW10H1/1000 NW12H1/1250 NW16H1/1600 NW20H1/2000 NW25H1/2500 35 35 35 35 35 50 50
75 75 75 75 75 105 105 NW08H2/630 NW08H2/800 NW10H2/1000 NW12H2/1250 NW16H2/1600 NW20H2/2000 NW25H2/2500
35 35 35 35 35 50 50 75 75 75 75 75 105 105
- - - - - NW20H3/2000 NW25H3/2500 50 50
105 105 NW08N1/630 NW08N1/800 NW10N1/1000 NW12N1/1250 NW16N1/1600 - -
35 35 35 35 35 75 75 75 75 75
NW08H1/630 NW08H1/800 NW10H1/1000 NW12H1/1250 NW16H1/1600 NW20H1/2000 NW25H1/2500 35 35 35 35 35 50 50
75 75 75 75 75 105 105 NW08H2/630 NW08H2/800 NW10H2/1000 NW12H2/1250 NW16H2/1600 NW20H2/2000 NW25H2/2500
35 35 35 35 35 50 50 75 75 75 75 75 105 105
- - - - - NW20H3/2000 NW25H3/2500 50 50
105 105 NW08N1/630 NW08N1/800 NW10N1/1000 NW12N1/1250 NW16N1/1600 - - 35 35 35 35 35
75 75 75 75 75 NW08H1/630 NW08H1/800 NW10H1/1000 NW12H1/1250 NW16H1/1600 NW20H1/2000 NW25H1/2500
35 35 35 35 35 50 50 75 75 75 75 75 105 105
NW08H2/630 NW08H2/800 NW10H2/1000 NW12H2/1250 NW16H2/1600 NW20H2/2000 NW25H2/2500 35 35 35 35 35 50 50
75 75 75 75 75 105 105 - - - - - NW20H3/2000 NW25H3/2500
50 50 105 105
NW08L1/630 NW08L1/800 NW10L1/1000 NW12L1/1250 NW16L1/1600 NW20L1/2000 -
35 35 35 35 35 50 75 75 75 75 75 105
1000/1250 1000/1250 1000/1250 1000/1250 1000/1250 - -
100 100 100 100 100 220 220 220 220 220
500 630 800 1000 1000/1250 - - 100 100 100 80 80/50
220 220 220 176 176/105 1000/1250 1000/1250 1000/1250 1000/1250 1000/1250 - -
80/50 80/50 80/50 80/50 80/50 176/105 176/105 176/105 176/105 176/105
500 630 800 1000 1000/1250 - - 80 80 80 80 80/50
176 176 176 176 176/105 1000/1250 1000/1250 1000/1250 1000/1250 1000/1250 - -
80/50 80/50 80/50 80/50 80/50 176/105 176/105 176/105 176/105 176/105
1000/1250 1000/1250 1000/1250 1000/1250 1000/1250 - - 100 100 100 100 100
220 220 220 220 220 500 630 800 1000 1000/1250 - -
100 100 100 80 80/50 220 220 220 176 176/105
1000/1250 1000/1250 1000/1250 1000/1250 1000/1250 - - 80/50 80/50 80/50 80/50 80/50
176/105 176/105 176/105 176/105 176/105
D-20
Protection of switch-disconnectorsINS40 to 2500 and INV100 to 2500 by fuses
Additional characteristicsD
B11
5722
Interpact INS switch-disconnectors INS40 INS63 INS80Upstream protection
By fuse 500 V Type aM (1) / max. rating (A) 125 125 125Isc max. kA rms 100 100 100Making capacity kA peak 220 220 220Type gG (2) / max. rating (A) 32 50 63Isc max. kA rms 100 100 100Making capacity kA peak 220 220 220Type gG (1) / max. rating (A) 100 100 100Isc max. kA rms 100 100 100Making capacity kA peak 220 220 220Type BS (2) / max. rating (A) 32 50 & 32M50 63 & 32M63 Isc max. kA rms 80 80 80Making capacity kA peak 176 176 176Type BS (1) / max. rating (A) 125 & 100M125 125 & 100M125 125 & 100M125 Isc max. kA rms 80 80 80Making capacity kA peak 176 176 176
(1) Mandatory protection by an external thermal relay.(2) No external thermal relay.
Interpact INS switch-disconnectors INS/INV400 INS/INV500 INS/INV630Upstream protection
By fuse 500 V Type aM (1) / max. rating (A) 800 800 800Isc max. kA rms 100 100 100Making capacity kA peak 220 220 220Type gG (2) / max. rating (A) 315 400 500Isc max. kA rms 100 100 100Making capacity kA peak 220 220 220Type gG (1) / max. rating (A) 630 630 500/630Isc max. kA rms 50 50 100/50Making capacity kA peak 105 105 220/105Type BS (2) / max. rating (A) 315 & 200M315 400 500Isc max. kA rms 80 80 80Making capacity kA peak 176 176 176Type BS (1) / max. rating (A) 355 & 315M355 450 & 400M450 450 & 400M450Isc max. kA rms 80 80 80Making capacity kA peak 176 176 176
By fuse 690 V Type aM (1) / max. rating (A) 800 800 800Isc max. kA rms 100 100 100Making capacity kA peak 220 220 220Type gG (2) / max. rating (A) 315 400 500Isc max. kA rms 100 100 100Making capacity kA peak 220 220 220Type gG (1) / max. rating (A) 630 630 500/630Isc max. kA rms 50 50 100/50Making capacity kA peak 105 105 220/105
(1) Mandatory protection by an external thermal relay.(2) No external thermal relay.
D-21
Additional characteristics Protection of switch-disconnectorsINS40 to 2500 and INV100 to 2500 by fuses
INS100 INS125 INS160 INS250-100 INS250-160 INS250-200 INS/INV250 INS/INV320 INV100 INV160 INV200
200 200 200 315 315 315 315 800 100 100 100 100 100 100 100 100
220 220 220 220 220 220 220 220 80 100 125 80 125 160 200 250
100 100 100 100 100 100 100 100 220 220 220 220 220 220 220 220
125/160 125/160 125/160 225/355 225/355 225/355 225/355 630 100/50 100/50 100/50 100/50 100/50 100/50 100/50 50
220/105 220/105 220/105 220/105 220/105 220/105 220/105 105 80 & 63M80 100 & 63M100 125 & 100M125 80 & 63M80 125 & 100M125 160 & 100M160 200 & 100M200 250 & 200M250
80 80 80 80 80 80 80 80 176 176 176 176 176 176 176 176
160 & 100M160 160 & 100M160 160 & 100M160 250 & 200M250 250 & 200M250 250 & 200M250 250 & 200M250 355 & 315M355 80 80 80 80 80 80 80 80
176 176 176 176 176 176 176 176
INS/INV630b INS/INV800 INS/INV1000 INS/INV1250 INS/INV1600 INS/INV2000 INS/INV2500
1000/1250 1000/1250 1000/1250 1000/1250 1000/1250 - - 100 100 100 100 100
220 220 220 220 220 500 630 800 1000 1000/1250 - -
100 100 100 80 80/50 220 220 220 176 176/105
1000/1250 1000/1250 1000/1250 1000/1250 1000/1250 - - 80/50 80/50 80/50 80/50 80/50
176/105 176/105 176/105 176/105 176/105 500 630 800 1000 1000/1250 - -
80 80 80 80 80/50 176 176 176 176 176/105
1000/1250 1000/1250 1000/1250 1000/1250 1000/1250 - - 80/50 80/50 80/50 80/50 80/50
176/105 176/105 176/105 176/105 176/105 1000/1250 1000/1250 1000/1250 1000/1250 1000/1250 - -
100 100 100 100 100 220 220 220 220 220
500 630 800 1000 1000/1250 - - 100 100 100 80 80/50
220 220 220 176 176/105 1000/1250 1000/1250 1000/1250 1000/1250 1000/1250 - -
80/50 80/50 80/50 80/50 80/50 176/105 176/105 176/105 176/105 176/105
D-22
Characteristics of switch-disconnectorsINS40 to 2500 and INV100 to 2500 for direct current
Additional characteristics
Parallel connection of polesMaximum permissible current at 60 °C
Rating (A) In max 3P parallel In max 4P parallelINS 40 96 128
63 151 20280 192 256
INS/INV 100 240 320125 300 400160 384 512200 480 640250 600 800320 768 1024400 960 1280500 1200 1600630 1512 2016800 1920 25601000 2400 32001250 3000 40001600 3840 51202000 4800 64002500 6000 8000
This international site allows you to access all the Schneider Electric products in just � clicksvia comprehensive range data-sheets, with direct links to:
complete library: technical documents, catalogs, FAQs, brochures…
selection guides from the e-catalog.
product discovery sites andtheir Flash animations.You will also fi nd illustrated overviews, news to which you can subscribe, the list of country contacts…
p
p
p
These technical guides help you comply with installation standards and rules i.e.: the electrical installation guide, the protection guide, the switchboard implementation guide,the technical bookletsand the co-ordination tables all form genuine reference tools for the design of high performance electrical installations.For example, the LV protectionco-ordination guide - discrimination and cascading - optimises choiceof protection and connection devices while also increasing markedly continuity of supplyin the installations.
schneider-electric.com The technical guide
TOOLS
E-�
Interpact INS/INV Catalogue numbers
Presentation 2Functions and characteristics A-1Installation recommendations B-1Dimensions and connection C-1Additional characteristics D-1
INS40 to 160 E-2Complete fixed/FC device and accessories E-�Accessories E-3
INS250-100 to 630 E-5Complete fixed/FC device and accessories E-5
INV100 to 630 E-6Complete fixed/FC device and specific accessories E-6
INS250-100 to 250 and INV100 to 250 E-7Accessories E-7
INS320 to 630 and INV320 to 630 E-10Accessories E-�0
INS630b to 2500 E-12Complete fixed/FC device and accessories E-1�
INS630b to 2500 and INV630b to 2500 E-14Accessories E-�4
INSE80 (40 to 80 A) molded case switch UL489/ CSA C22-2 N° 5.2 E-16Complete fixed/FC device and accessories E-16
INSJ400 (250 to 400 A) molded case switch UL489/ CSA C22-2 N° 5.2 E-18Complete fixed/FC device and accessories E-18
E-�
INS40 to 160 Complete fixed/FC device and accessories
Catalogue numbers
Interpact INS40 to 160 standard version with black handle
E33
365
4 3P 4PInterpact INS40 28900 28901Interpact INS63 28902 28903Interpact INS80 28904 28905
E33
366
3P 4PInterpact INS�00 28908 28909Interpact INS��5 28910 28911Interpact INS�60 28912 28913
Interpact INS40 to 160 with red handle and yellow front
E33
365
4 3P 4PInterpact INS40 28916 28917Interpact INS63 28918 28919Interpact INS80 28920 28921
E33
366
3P 4PInterpact INS�00 28924 28925Interpact INS��5 28926 28927Interpact INS�60 28928 28929
Individual enclosuresIP55 heavy-duty sheetmetal enclosure
E90
49� For INS40 to INS�60 with extended standard rotary handle 31208
For INS40 to INS�60 with extended red handle on yellow front 31209
IP55 heavy-duty insulating enclosure
DB
��75
66
For INS40 to INS�60 with extended standard rotary handle 28967For INS40 to INS�60 with extended red handle on yellow front 28968
Connection accessoriesDistribloc distribution block (for bare cables)
E33
404
INS40 to ��5 ��5 A, �� outgoing spring terminals (7 x 4 mm² + 3 x 6 mm² 04045+ � x �0 mm²) + � outgoing tunnel terminal (35 mm²) (1)
4 prefabricated connections ��5 A, 35 mm², l = ��0 mm (1) 04047INS�00 to �60 �60 A, �� outgoing spring terminals (7 x 4 mm² + 3 x 6 mm² 04046
+ � x �0 mm²) + � outgoing tunnel terminal (35 mm²) wi h4 prefabricated connections (1)
Multi-stage distribution block (for bare cables)
DB
��75
34
INS40 to ��5 40 A, 4 x �3 holes (�� x �0 mm² + � x �6 mm²) (1) 13508�00 A, 4 x 7 holes (3 x �0 mm² + 3 x �6 mm² + � x �5 mm²) (1) 13510��5 A, 4 x �3 holes (5 x �0 mm² + 5 x �6 mm� + � x �5 mm² + � x 35 mm²) (1) 13512��5 A, 4 x �7 holes (7 x �0 mm² + 7 x �6 mm² + � x �5 mm² + � x 35 mm²) (1) 13514Additional neutral bar 40 A, L = 89 mm (1) 13516
�00 A, L = 6� mm (1) 13515��5 A, L = �07 mm (1) 13517��5 A, L = �34 mm (1) 13518
(1) Product sold by MGA.
E-3
Catalogue numbers INS40 to 160Accessories
Connection accessories (cont.)Connectors for bare Cu or Al cables
DB
��75
59 Snap-on INS�00 to �60 S y 95 mm² Set of 3 28947Set of 4 28948
DB
��75
60
Distribution connector for INS40 to 80 Set of 3 190963 rigid cables up to �6 mm² or Set of 4 190913 flexible cables up to 10 mm²
DB
��75
6�
Distribution connector for INS�00 to �60 Set of 3 289494 rigid cables up to �5 mm² or Set of 4 289504 flexible cables up to 16 mm²
DB
��75
6�
Crimp lugs for copper cablesFor 95 mm² cables with interphase barriers
INS�00 to �60 Set of 3 28951Set of 4 28952
Terminal shrouds
DB
��75
9�
INS40 to 80 3P/4P Set of � 28955INS�00 to �60 3P/4P Set of � 28956
Terminal shields
DB
��75
93
INS40 to 80 3P/4P Set of � 28957INS�00 to �60 3P/4P Set of � 28958
Interphase barriers
E88
893
INS�00 to �60 3P/4P Set of 6 28959
Electrical auxiliaries Auxiliary contacts
DB
��75
63
� OF / CAF / CAO (standard) INS40 to �60 29450� OF / CAF / CAO (low level) INS40 to �60 29452
Rotary handlesAccessories for conversion to extended rotary handles
E33
405
Front control Black handle INS40 to �60 28941Red handle on yellow front INS40 to �60 28942
E5�
0��
Lateral control Black handle INS40 to �60 28943Red handle on yellow front INS40 to �60 (1) 28944
Lateral control on G, GX or PRAGMA F functional enclosure
Black handle INS40 to �60 28945
Red handle on yellow front INS40 to �60 (1) 28946
(1) For red/yellow switch versions only.
E-4
INS40 to 160 (cont.)
Accessories (cont.)
Catalogue numbers
Locking and interlockingHandle locking
DB
��75
64
Ø
By � to 3 padlocks (OFF position), hasp dia. 5 to 8 mm, or by lead seals Built-in
Interlocking for extended rotary handles
DB
�077
�0
Mechanical 28953
Spare parts
DB
��75
65
Black handle 28962Red handle (1) 28963
(1) For red/yellow switch versions only.
E-5
Catalogue numbers INS250-100 to 630 Complete fixed/FC device and accessories
Interpact INS250 to 630 standard version with black handle
E50
995
3P 4PInterpact INS�50-�00A 31100 31101Interpact INS�50-�60A 31104 31105Interpact INS�50-�00A 31102 31103Interpact INS�50 31106 31107
E50
996
3P 4PInterpact INS3�0 31108 31109Interpact INS400 31110 31111Interpact INS500 31112 31113Interpact INS630 31114 31115
Interpact INS250 to 630 with red handle and yellow front
E50
995
3P 4PInterpact INS�50-�00A 31120 31121Interpact INS�50-�60A 31124 31125Interpact INS�50-�00A 31122 31123Interpact INS�50 31126 31127
E50
996
3P 4PInterpact INS3�0 31128 31129Interpact INS400 31130 31131Interpact INS500 31132 31133Interpact INS630 31134 31135
Source changeover systemsComplete assembly
E89
638
3P 4PWith Interpact INS�50-�00A 31140 31141With Interpact INS�50-�60A 31144 31145With Interpact INS�50-�00A 31142 31143With Interpact INS�50 31146 31147With Interpact INS3�0 31148 31149With Interpact INS400 31150 31151With Interpact INS500 31152 31153With Interpact INS630 31154 31155
Downstream coupling accessories
E50
998
3P 4PFor Interpact INS�50 29358 29359Long downstream 3P/4P terminal shields (set of �) 29324For Interpact INS3�0 to 630 32619 32620Long downstream 3P/4P terminal shields (set of �) 32583
Individual enclosuresIP55 heavy-duty sheetmetal enclosure
E90
49�
For INS�50-�00 to �50 with extended standard rotary handle 31210For INS�50-�00 to �50 with extended red rotary handle on yellow front 31211For INS3�0 to 630 with extended standard rotary handle 31212For INS3�0 to 630 with extended red rotary handle on yellow front 31213
IP55 heavy-duty insulating enclosure
E3�
4�9
For INS�50-�00 to �50 with extended standard rotary handle 31204For INS�50-�00 to �50 with extended red rotary handle on yellow front 31205For INS3�0 to 630 with extended standard rotary handle 31206For INS3�0 to 630 with extended red rotary handle on yellow front 31207
E-6
INV100 to 630Complete fixed/FC device and specific accessories
Catalogue numbers
Interpact INV100 to 630 standard version with black handle
E5�
00�
3P 4PInterpact INV�00 31160 31161Interpact INV�60 31164 31165Interpact INV�00 31162 31163Interpact INV�50 31166 31167
E5�
00�
3P 4PInterpact INV3�0 31168 31169Interpact INV400 31170 31171Interpact INV500 31172 31173Interpact INV630 31174 31175
Interpact INV100 to 630 with red handle and yellow front
E5�
00�
3P 4PInterpact INV�00 31180 31181Interpact INV�60 31184 31185Interpact INV�00 31182 31183Interpact INV�50 31186 31187
E5�
00�
3P 4PInterpact INV3�0 31188 31189Interpact INV400 31190 31191Interpact INV500 31192 31193Interpact INV630 31194 31195
Individual enclosuresIP55 heavy-duty insulating enclosure
DB
��75
66
For INV�00 to �50 with extended standard rotary handle 31204For INV�00 to �50 with extended red rotary handle on yellow front 31205For INV3�0 to 630 with extended standard rotary handle 31206For INV3�0 to 630 with extended red rotary handle on yellow front 31207
Combination with Compact NS devices for "tarif jaune / tarif vert"
E89
64�
¿5 8
INV�00 to �50 combination with NS�50 31066INV3�0 to 630 combination with NS�50 31067Front alignment base for INV3�0 to 630 combination with NS�50 31064INV3�0 to 630 combination with NS400/630 31068
E89
64�
Flexible connection assembly for vertical INV�00 to �50 with horizontal NS�50 04443Flexible connection assembly for vertical INV�00 to �50 with horizontal Vigi NS�50 04444Flexible connection assembly for vertical INV3�0 to 630 with horizontal NS�50/400/630 04445Flexible connection assembly for vertical INV3�0 to 630 with horizontal Vigi NS�50/400/630 04446Flexible connection assembly for vertical INV�00 to �50 with horizontal NS�50 31069Flexible connection assembly for vertical INV3�0 to 400 with horizontal NS�50 31092Flexible connection assembly for vertical INV�00 to �50 with vertical NS�50 beside 31071Flexible connection assembly for vertical INV3�0 to 630 with vertical NS400/630 beside 31072Flexible connection assembly for vertical INV3�0 to 630 with vertical NS�50 beside 31093
(1) Product sold by MGA and valid for new Prisma Plus only.(2) Product sold by MGA suitable for old Prisma range.
E-7
Catalogue numbers INS250-100 to 250 and INV100 to 250Accessories
Connection accessoriesRear connections
DB
��75
67
Short (� pair) 29235Long (� pair) 29236
Bare cable connectors
DB
��75
68
Snap-on, for cables: Steel: �.5 to 95 mm² ; y �60 A Set of 3 29242Set of 4 29243
Aluminium: �5 to 95 mm² ; y �50 A Set of 3 29227Set of 4 29228
Aluminium: ��0 to �85 mm² ; y �50 A Set of 3 29259Set of 4 29260
DB
��75
69
Tab connector for voltage tap on �85 mm² bare cable connector Set of � 29348Clip for bare cable connector Set of �0 29241Distribu ion connector for six �.5 to 35 mm² cables with interphase barriers Set of 3 29248
Set of 4 29249
Polybloc distribution block (for bare cables)
DB
�074
4�
DB
�074
43
�60 A For 6 cables (�0 mm²) per pole �P 04031�50 A For 9 cables (6 x �0 mm² + 3 x �6 mm²) per pole 3P 04033
4P 04034Additives blocks of � x 35 mm² per pole 3P 04155
4P 04156
Terminal extensions (supplied with 2 or 3 interphase barriers)
DB
��75
70
Right-angle terminal extensions Set of 3 29261Set of 4 29262
DB
��75
7�
Straight terminal extensions Set of 3 29263Set of 4 29264
Spreaders (for upstream or downstream connection)
DB
��75
7� Separate for each pole 3P 3P 31563
4P 4P 31564
E5�
006 One-piece 3/4 P 3/4P 31061
Front alignment base for one-piece spreader
3/4 P 3/4P 31064
Crimp lugs for copper cables (supplied with 2 or 3 interphase barriers)
DB
��75
73
For ��0 mm² cables Set of 3 29252Set of 4 29256
For �50 mm² cables Set of 3 29253Set of 4 29257
For cable �85 mm² cables Set of 3 29254Set of 4 29258
Crimp lugs for aluminium cables (supplied with 2 or 3 interphase barriers)
DB
��75
74
For �50 mm² cables Set of 3 29504Set of 4 29505
For �85 mm² cables Set of 3 29506Set of 4 29507
Terminal shields
DB
�074
44
Short 3/4 P Set of � 29322Long 3/4 P Set of � 29324
Interphase barriers
DB
�0�9
4�
Set of 6 29329
(1) Product sold by MGA.
E-8
INS250-100 to 250 and INV100 to 250 (cont.)
Accessories (cont.)
Catalogue numbers
Special connection accessories for INS250-100 to 250DC and INV100 to 250DC
DB
�085
56
Terminal extensions for series or parallel connection of two poles (*) � terminal ext. 29498(*) Series connection of: 2 poles = 1 terminal extension
3 poles = 2 terminal extensions4 poles = 3 terminal extensions
Parallel connection of: 2 poles = 2 terminal extensions3 poles = set of 2 terminal extensions (29499)4 poles = 4 terminal extensions
DB
�085
57
Terminal extensions for parallel connection of three poles Set of � terminal extensions
29499
4P terminal shields for series connection of poles Set of � 294964P terminal shields for parallel connection of poles (�P/4P) Set of � 29497
Electrical auxiliariesAuxiliary contacts (changeover type)
DB
��75
63
OF or CAM (early make or break) 29450Low level OF or CAM (early make or break) 29452
Indication and measurement modulesAmmeter module (4P)
E5�
008
A 1
8
Adaptation kit (compulsory for devices with direct front handles) 31081Rating (A) �00 29456
�50 30556�50 31566
Current transformer module and voltage output (4P)
E5�
009 Rating (A) �00 29462
�50 30562�50 31570
Current transformer module (4P)
E5�
009
Rating (A) �00 29458�50 30558�50 31568
Voltage presence indicator
DB
�05�
70
Rating (A) �50 29325
Rotary handlesExtended front control
E33
405
For INS�50 with standard rotary handle 31050For INS�50 with red handle on yellow front (1) 31051For complete source changeover assembly 31055
Lateral control
E89
607
Direct lateral control for INS and INV250Lateral support 31054+ standard lateral control assembly 31057or + red and yellow lateral control assembly (1) 31058Extended lateral control for INS and INV250
Standard lateral control assembly 31057Red and yellow lateral control assembly (1) 31058
(1) For red/yellow switch versions only.
E-9
Catalogue numbers INS250-100 to 250 and INV100 to 250 (cont.)
Accessories (cont.)
Locking and interlocking for INS/INV and source changeover systemsLocking for INS/INV
E5�
0��
Handle locking by � to 3 padlocks (in OFF position) Built-inBy keylock Keylocking device 31087
+ Ronis �35�B.500 keylock 41940or + Profalux KS5 B�4 D4Z keylock 42888
Locking for INS complete source changeover assembly
DB
�077
��
Handle locking by � to 3 padlocks (in OFF position) Built-inBy keylock Keylocking device 31097
+ Ronis �35�B.500 keylock 41940or + Profalux KS5 B�4 D4Z keylock 42888
Interlocking with key (2 keylocks / 1 key)
DB
�0�5
49
By � keylocks INS�50 keylocking device � x 31087INS3�0-600 keylocking device � x 31088+ Ronis �35�B.500 keylock 41950or + Profalux KS5 B�4 D4Z keylock 42878
Interlocking for INS/INV with direct or extended rotary handle
DB
��75
85
Mechanical interlocking for INS�50 31073
Installation accessoriesFront panel escutcheons
DB
��75
86
For INS/INV 31079For ammeter module, IP40 29318
Lead seal accessories29375
Spare parts12 snap-in nuts for fixed/FC(M8) 30554100 identification labels 29314Bag of screws 29312Black handle 31082Red handle (1) 31083Viewport for INV�00/�60/�50 31089
(1) For red/yellow switch versions only.
E-�0
INS320 to 630 and INV320 to 630 Accessories
Catalogue numbers
Connection accessoriesRear connections
DB
��75
67
Short (� pair) 32475Long (� pair) 32476
Bare cable connectors
E��
040 For � cable, 35 mm² to 300 mm² Set of 3 32479
Set of 4 32480For � cables, 35 mm² to �40 mm² Set of 3 32481
E��
04� Set of 4 32482
Tab connector for voltage tap on bare cable connector Set of � 29348
Terminal extensions (supplied with 2 or 3 interphase barriers)
DB
��75
70
Right-angle terminal extensions Set of 3 32484Set of 4 32485
E��
�76
Edgewise terminal extensions Set of 3 32486Set of 4 32487
Spreaders (for upstream or downstream connection)
DB
��75
7�
One-piece 5�.5 mm 3P 324904P 32491
70 mm 3P 324924P 32493
Crimp lugs for copper cables (supplied with 2 or 3 interphase barriers)
DB
��75
73
For �40 mm² cables Set of 3 32500Set of 4 32501
For 300 mm² cables Set of 3 32502Set of 4 32503
Crimp lugs for aluminium cables (supplied with 2 or 3 interphase barriers)
DB
��75
74
For �40 mm² cables Set of 3 32504Set of 4 32505
For 300 mm² cables Set of 3 32506Set of 4 32507
Terminal shields
E5�
007
Short 3/4P Set of � 32563Long 3/4P Set of � 32565Long for 5�.5 mm spreader (supplied with insulating plate) 3/4P Set of � 32583
Interphase barriers
E89
6��
Set of 6 32570
Special connection accessories for INS/INV320 to 630DC
DB
�085
66
Terminal extensions for series or parallel connection of two poles (*) � terminal ext. 32868(*) Series connection of: 2 poles = 1 terminal extension
3 poles = 2 terminal extensions4 poles = 3 terminal extensions
Parallel connection of: 2 poles = 2 terminal extensions4 poles = 4 terminal extensions
4P terminal shields for series connection of poles Set of � 328664P terminal shields for parallel connection of poles Set of � 32867
E-��
Catalogue numbers INS320 to 630 and INV320 to 630 (cont.)
Accessories (cont.)
Electrical auxiliariesAuxiliary contacts (changeover type)
DB
��75
63
OF or CAM (early make or break) 29450OF or CAM low level (early make or break) 29452
Indication and measurement modulesAmmeter module (4P)
E5�
008
A 2
4
Rating (A) 400 32656600 32856
Current transformer module (4P)
E5�
009
Rating (A) 400 32658600 32858
Voltage presence indicatorRating (A) 630 32566
Rotary handlesExtended front control
E89
6�7
For INS3�0/400/630 with standard rotary handle 31052For INS3�0/400/630 with red handle on yellow front (1) 31053For complete source changeover assembly 31055
Locking and interlocking for INS/INV and source changeover systemsLocking for INS/INV
E89
6�8
Handle locking by � to 3 padlocks (in OFF position) Built-inBy keylock Keylocking device 31088
+ Ronis �35�B.500 keylock 41940or + Profalux KS5 B�4 D4Z keylock 42888
Locking for INS complete source changeover assembly
DB
�077
��
Handle locking by � to 3 padlocks (in OFF position) Built-inBy keylock Keylocking device 31097
+ Ronis �35�B.500 keylock 41940or + Profalux KS5 B�4 D4Z keylock 42888
Interlocking with key (2 keylocks / 1 key)
DB
�0�5
49
By � keylocks INS�50 keylocking device � x 31087INS3�0-600 keylocking device � x 31088+ Ronis �35�B.500 keylock 41950or + Profalux KS5 B�4 D4Z keylock 42878
Interlocking for INS/INV with direct or extended rotary handle
E89
6�4
Mechanical interlocking for INS3�0/400/630 31074
Installation accessoriesFront panel escutcheons
E�8
59�
For INS/INV 31080For ammeter module, IP40 29318
Lead seal accessories29375
Spare parts�00 labels 29314Bag of screws 32552Black handle 31084Red handle (1) 31085Viewport for INV3�0/400/630 31090
(1) For red/yellow switch versions only.
DB
�05�
70
E-��
INS630b to 2500 Complete fixed/FC device and accessories
Catalogue numbers
Interpact INS630b to 2500 standard version with black handle
E88
699
3P 4PInterpact INS630b 31342 31343Interpact INS800 31330 31331Interpact INS�000 31332 31333Interpact INS��50 31334 31335Interpact INS�600 31336 31337
E89
6�3
Interpact INS�000 31338 31339Interpact INS�500 31340 31341
Interpact INS630b to 1600 with red handle and yellow front
E88
699
3P 4PInterpact INS630b 31356 31357Interpact INS800 31344 31345Interpact INS�000 31346 31347Interpact INS��50 31348 31349Interpact INS�600 31350 31351
E-�3
Catalogue numbers INV630b to 2500Complete fixed/FC device and specific accessories
Interpact INV630b to 2500 standard version with black handle
E89
639
3P 4PInterpact INV630b 31370 31371Interpact INV800 31358 31359Interpact INV�000 31360 31361Interpact INV��50 31362 31363Interpact INV�600 31364 31365
E89
640
Interpact INV�000 31366 31367Interpact INV�500 31368 31369
Interpact INV630b to 1600 with red handle and yellow front
E89
639
3P 4PInterpact INV630b 31387 31388Interpact INV800 31372 31373Interpact INV�000 31374 31375Interpact INV��50 31376 31377Interpact INV�600 31378 31379
Combination with Compact NS devices (for "tarif vert")
E89
6�9
3P 4PINV630b/�000/��50 combination wi h 31385 31386NS800/�000/��50
E-�4
INS630b to 2500 and INV630b to 2500Accessories
Catalogue numbers
Connection accessoriesVertical connection adapters
E88
70�
INS/INV630b-�600 3P Set of 3 313014P Set of 4 31302
Cable lug adapters
E88
70�
INS/INV630b-�600 3P Set of 3 336444P Set of 4 33645
Spreaders
E88
703
INS/INV630b-�600 3P Set of 3 313054P Set of 4 31306
DB
�085
58
Connector for direct connection (edgewise or flat) to INS2000/2500 31310
Special connection accessories for INS/INV 630b to INS 1600 DC
DB
�085
59
Terminal extensions for series connection for DC INS630b/�600 31320
Insulation accessoriesBase for terminal shield (not compatible with interphase barriers)
E88
704
INS/INV630b-�600 3P 313074P 31308
Terminal shield
E88
705
INS/INV630b-�600 3P 336284P 33629
Interphase barriers (not compatible with terminal shield and base)
E89
6�5
INS/INV630b-�600 4P Set of 6 31315INS/INV�000/�500 4P Set of 6 31319
Electrical auxiliariesAuxiliary contacts (changeover type) INS/INV630b-2500
DB
��75
63
OF or CAM (early make or break) 29450OF or CAM low level (early make or break) 29452
Extended front control
E88
708
INS/INV630b-�500 For standard rotary handle 31288INS/INV630b-�600 For red handle on yellow front (1) 31289
(1) For red/yellow switch versions only.
E-�5
Catalogue numbers INS630b to 2500 and INV630b to 2500 (cont.)
Accessories (cont.)
Locking and interlockingLocking for INS/INV630b to 2500
E89
6�0
Handle locking by � to 3 padlocks (in OFF position) Built-inBy keylock Keylocking device 31291
+ Ronis �35�B.500 keylock 41940or + Profalux KS5 B�4 D4Z keylock 42888
Interlocking for INS/INV630b to 2500
E89
6�6
By keylock Keylocking device � x 31291+ Ronis �35�B.500 keylock (� keylocks / � key) 41950or + Profalux KS5 B�4 D4Z keylock (� keylocks / � key) 42878
Installation accessoriesEscutcheon
E88
707
INS630b-�500 3P/4P 31295
Lead seal accessories31316
Spare parts
E88
709
INS/INV630b-�600 Black handle 31296Red handle (1) 31297
INS/INV�000-�500 Black handle 31298
E88
700
Viewport for INV630b/�500 3P 312934P 31294
(1) For red/yellow switch versions only.
E-�6
INSE80 (40 to 80 A) molded case switch UL489/CSA C22-2 N° 5.2Complete fixed/FC device and accessories
Catalogue numbers
Interpact INSE80 (40 to 80 A) standard version with black handle
DB
��47
37
3P 4PInterpact INSE80 40 A 28994 28995
60 A 28996 2899780 A 28998 28999
Individual enclosuresIP55 heavy-duty sheetmetal enclosure (1)
E90
49�
For INSE80-40 A to INSE80-80 A with extended standard rotary handle 31208For INSE80-40 A to INSE80-80 A with extended red handle on yellow front 31209
IP55 heavy-duty insulating enclosure (1)
E3�
4�9
For INSE80-40 A to INSE80-80 A with extended standard rotary handle 28967For INSE80-40 A to INSE80-80 A with extended red handle on yellow front 28968
Connection accessoriesDistribloc distribution block (for bare cables)
E33
404
INSE80-40 A toINSE80-80 A (1)
�60 A, �� outgoing spring terminals (7 x 4 mm² + 3 x 6 mm² (2) 07106+ � x �0 mm²) + � outgoing tunnel terminal (�5 mm²) with prefabricated connections
Multi-stage distribution block (for bare cables)
DB
��75
34
INSE80-40 A to ��5 A, 4 x �0 holes (5 x �0 mm² + 4 x �6 mm² + � x 35 mm²) (2) 13512INSE80-80 A (1) ��5 A, 4 x �7 holes (8 x �0 mm² + 8 x �6 mm² + � x 35 mm²) (2) 13514
Connectors for bare Cu or Al cables
DB
��75
59
Snap-on INSE80-40 A to INSE80-80 A Set of 3 28947�.5 to 95 mm² Set of 4 28948�� AWG to 3/0 AWG C4/AL
DB
��75
6�
Distribution connector for INSE80-40 A to INSE80-80 A (1) Set of 3 289494 rigid cables up to �5 mm² or Set of 4 289504 flexible cables up to 16 mm²
Crimp lugs for copper cables (1)
DB
��75
6�
For 95 mm² cables with interphase barriers
INSE80-40 A to INSE80-80 A Set of 3 28951Set of 4 28952
Terminal shrouds
DB
��75
9�
INSE80-40 A to INSE80-80 A 3P/4P Set of � 28956
Terminal shields
DB
��75
93
INSE80-40 A to INSE80-80 A 3P/4P Set of � 28958
(1) Not UL Listed.(2) Product sold by MGA.
E-�7
Catalogue numbers INSE80 (40 to 80 A) molded case switch UL489/CSA C22-2 N° 5.2Complete fixed/FC device and accessories (cont.)
Connection accessories (cont.)Interphase barriers
E88
893
INSE80-40 A to INSE80-80 A 3P/4P Set of 6 28959
Electrical auxiliaries Auxiliary contacts
DB
��75
63
� OF / CAF / CAO (standard) INSE80-40 A to INSE80-80 A 29450� OF / CAF / CAO (low level) INSE80-40 A to INSE80-80 A 29452
Rotary handlesAccessories for conversion to extended rotary handles
E33
405
Front control Black handle INSE80-40 A to INSE80-80 A 28941Red handle on yellow front INSE80-40 A to INSE80-80 A 28942
Lateral control Black handle INSE80-40 A to INSE80-80 A 28943
DB
��47
38
Red handle on yellow front INSE80-40 A to INSE80-80 A 28944+ red handle (2) 28963
Lateral control on G, GX or PRAGMA F functional enclosure
Black handle INSE80-40 A to INSE80-80 A 28945Red handle on yellow front (2) INSE80-40 A to INSE80-80 A 28946
Locking and interlockingHandle locking
DB
��75
64
Ø
By � to 3 padlocks (OFF position), hasp dia. 5 to 8 mm, or by lead seals Built-in
Interlocking for extended rotary handles
DB
�077
�0
Mechanical (1) 28953
Spare parts
DB
��75
65
N
Black handle 28962Red handle (2) 28963
(1) Not UL listed.(2) For red/yellow switch versions only.
E-�8
Catalogue numbers
Interpact INSJ400 (250 A to 400 A) standard version with black handle
DB
��47
39
3P 4PInterpact INSJ400-�50 A 31118 31119Interpact INSJ400-400 A 31136 31137
Individual enclosuresIP55 heavy-duty sheetmetal enclosure (1)
E90
49�
For INSJ400-�50 to 400 A with extended standard rotary handle 31212For INSJ400-�50 to 400 A with extended red rotary handle on yellow front 31213
IP55 heavy-duty insulating enclosure (1)
DB
��75
66
For INSJ400-�50 to 400 A with extended standard rotary handle 31206For INSJ400-�50 to 400 A with extended red rotary handle on yellow front 31207
Connection accessoriesRear connections
DB
��75
67
Short (� pair) 32475Long (� pair) 32476
Bare cable connectors
DB
��75
87
For � cable, 35 mm² to 300 mm² Set of 3 32479Set of 4 32480
For � cables, 35 mm² to �40 mm² Set of 3 32481
DB
��75
88
Set of 4 32482Tab connector for voltage tap on bare cable connector Set of � 29348
Terminal extensions (supplied with 2 or 3 interphase barriers)
DB
��75
70
Right-angle terminal extensions Set of 3 32484Set of 4 32485
Edgewise terminal extensions Set of 3 32486
DB
��75
89
Set of 4 32487
Spreaders (for upstream or downstream connection)
DB
��75
7�
One-piece 5�.5 mm 3P 324904P 32491
70 mm 3P 324924P 32493
Crimp lugs for copper cables (supplied with 2 or 3 interphase barriers) (1)
DB
��75
73
For �40 mm² cables Set of 3 32500Set of 4 32501
For 300 mm² cables Set of 3 32502Set of 4 32503
Crimp lugs for aluminium cables (supplied with 2 or 3 interphase barriers) (1)
DB
��75
74
For �40 mm² cables Set of 3 32504Set of 4 32505
For 300 mm² cables Set of 3 32506Set of 4 32507
(1) Not UL Listed.
INSJ400 (250 to 400 A) molded case switch UL489/ CSA C22-2 N° 5.2Complete fixed/FC device and accessories
E-19
Catalogue numbers
Connection accessories (cont.)Terminal shields
DB
1074
44
DB
1074
45
Short 3/4P Set of 2 32563Long 3/4P Set of 2 32565Long for 52.5 mm spreader (supplied with insulating plate) 3/4P Set of 2 32583
Interphase barriers
E89
622
Set of 6 32570
Electrical auxiliariesAuxiliary contacts (changeover type)
DB
1175
63
OF or CAM (early make or break) 29450OF or CAM low level (early make or break) 29452
Rotary handlesExtended front control
E89
617
For INSJ400-250 to 400 A with standard rotary handle 31052For INSJ400-250 to 400 A with red handle on yellow front + red handle (1) 31053
31085
Locking and interlocking and source changeover systemsLocking
E89
618
Handle locking by 1 to 3 padlocks (in OFF position) Built-inBy keylock Keylocking device 31088
+ Ronis 1351B.500 keylock 41940or + Profalux KS5 B24 D4Z keylock 42888
Interlocking with key (2 keylocks / 1 key)
DB
1015
49
By 2 keylocks INSJ400-250 to 400 A keylocking device 2 x 31088+ Ronis 1351B.500 keylock 41950or + Profalux KS5 B24 D4Z keylock 42878
Interlocking with direct or extended rotary handle
E89
624
Mechanical interlocking for INSJ400-250 to 400 A 31074
Installation accessoriesFront panel escutcheons
DB
1147
40
31080
Lead seal accessories29375
Spare parts100 labels 29314Bag of screws 32552Black handle 31084Red handle 31085
(1) For red/yellow switch versions only.
INSJ400 (250 to 400 A) molded case switch UL489/ CSA C22-2 N° 5.2Complete fixed/FC device and accessories
E-20
Notes
Schneider Electric Industries SAS35, rue Joseph Monier92500 Rueil-MalmaisonFrance
http://www.schneider-electric.com http://www.schneider-electric.co
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.
This document has been printed on ecological paper .
Design: Schneider ElectricPhotos: Schneider ElectricPrinted: Centre impression - made in France
10-2008LVPED208015EN
AR
T836
823
© 2
008
- Sch
neid
er E
lect
ric -
All
right
s re
serv
ed
308E0000.indd 2 13/11/2008 10:45:22