International Fan Coil Unit I100-90002102[1]

36
BUILD YOUR REPUTATION ON OURS Horizontal Series FAN COIL TECHNICAL CATALOG

Transcript of International Fan Coil Unit I100-90002102[1]

Page 1: International Fan Coil Unit I100-90002102[1]

BUILD YOUR REPUTATION ON OURS

Horizontal SeriesFAN COIL TECHNICAL CATALOG

Page 2: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com2

Horizontal Series

International Environmental Corporation (IEC) works continually

to improve its products. As a result, the design and specifications

of each product may be changed without notice and may not be

as described herein. Please contact IEC for information regarding

current design and product specif ications. Statements and

other information contained herein are not express warranties

and do not form the basis of any bargain between the parties

but are merely IEC’s opinion or commendation of its products.

Manufacturer’s standard limited warranty applies.

Page 3: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

3

TAbLE OF CONTENTS

3 Table of Contents

4 Portfolio

6 Features & Benefits

7 Unit Model Key

8 Ratings & Listings

9 Air Delivery

10 Electric Heating

11 Motor Data

13 Physical Data

27 Standard Features & Options

32 Piping Packages (Typical)

33 Mechanical Specifications

Page 4: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com4

Horizontal SeriesPOrTFOLIO

CPY - Horizontal Hideaway with Plenum 200 CFM to 1200 CFMThe Horizontal Hideaway with Plenum (CPY) fan coil unit

provides the same basic features of the CHY plus a return

air plenum for above-ceiling mounting in closets, hallways

or bathroom areas. The CPY design enables the unit to be

adapted to installations requiring return air ducts or to be

used as a return-air plenum with a unit-mounted filter and

filter-rack assembly. CPY units are shipped from the factory

ready for installation with the plenum section in place. No

field fabrication is required. CPY units are designed with

interchangeable panels so that the unit may be modified on

site to accommodate a rear or bottom return. Standard CPY

units are provided with a galvanized finish.

CBY - Horizontal Telescoping Hideaway 200 CFM to 1200 CFMThe Horizontal Telescoping Hideaway (CBY) fan coil unit is

mounted fully-recessed for ceiling-recessed applications. The

CBY’s telescoping frame with hinged panel adapts to any

ceiling type and ensures exact alignment of the panel with

the ceiling. The hinged-bottom panel provides easy access

to all internal components. Standard CBY units are provided

with a galvanized finish on the cabinet and powder-coat

paint finish on the bottom-access panel.

CHY - Horizontal Hideaway 200 CFM to 1200 CFMThe Horizontal Hideaway (CHY) fan coil unit is designed

specifically to meet the many varied requirements for a

ceiling hideaway installation. The low-silhouette styling of

the CHY makes this unit ideally suited for drop-ceiling and

over-closet applications. Standard CHY units are provided

with a galvanized finish.

Page 5: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

5

POrTFOLIO, Cont’d.

CXB - Horizontal Cabinet 200 CFM to 1200 CFMThe Horizontal Cabinet (CXB) fan coil unit is designed

specifically for exposed mounting in hotels, motels,

hospitals, nursing homes, offices or other commercial

establishments. With the CXB, valuable floor space is not

required, and its slim, attractively-styled cabinet blends

with all types of decor. Since there is no requirement for

duct work or structure modifications, the CXB is ideal for

retrofit applications. Standard CXB units are provided with a

powder-coat paint finish.

BHY - Horizontal Hi-Static Hideaway 400 CFM to 1000 CFMThe Horizontal Hi-Static Hideaway (BHY) fan coil unit is

suited for above-ceiling applications with space limitations.

The BHY unit is furnished with larger diameter wheels

to achieve higher static pressures required for ductwork

applications. Standard BHY units are provided with a

galvanized finish.

BPY - Horizontal Hi-Static Hideaway with Plenum 400 CFM to 1000 CFMThe Horizontal Hi-Static Hideaway with Plenum (BPY) fan

coil unit is designed for installations requiring a return-air

plenum with a unit-mounted filter and filter-rack assembly.

The BPY plenum is constructed of galvanized steel and lined

with glass-fiber insulation. BPY units are designed with

interchangeable panels so that the unit may be modified on

site to accommodate a rear or bottom return. Standard BPY

units are provided with a galvanized finish.

Page 6: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com6

Horizontal SeriesFEATurES & bENEFITS

Application Fit• Multiple cabinet choices are available in 7 nominal

CFM sizes for application in a variety of room layouts.

o Horizontal Cabinet units (CXB) with aesthetically

pleasing cabinetry offer capacities that are ideal for

air conditioning in dormitories, small apartments,

schools and many other applications. Front supply,

bottom or rear return are available.

o Horizontal Telescoping Hideaway units with

painted access panel (CBY) allows smooth fit up

to plaster or sheet rock ceilings. Standard units

include bottom louvered return air with the filter

located in the access panel.

o Horizontal Hideaway models (CHY/BHY) units are

installed above the ceiling with or without ducted

supply air and open “soffit” return with an optional

ceiling-mounted filter-grille.

o Horizontal Hideaway models with plenum (CPY/

BPY) units are installed above the ceiling with or

without ducted supply air and ducted return air.

The return air filter is either mounted on the unit

plenum or installed in an optional ceiling filter-

grille.

Design Flexibility• Easy to use ratings program to speed up project

design.

• Standard and high capacity hydronic coils and DX coils

are available to match the heating and cooling loads of

the space.

• Optional powder-paint finish colors and grille

selections will complement most décors (exposed

units).

• CXB and CBY units ordered with optional rear return

are constructed with a solid bottom panel.

• Customizable cabinetry makes these units ideal for

renovation jobs or where special sizes are required to

fit oversized valves and control packages.

• Optional airflow configuration (front supply, bottom

supply, rear return or bottom return) to meet certain

design limitations.

• Outside air connections are available to meet

ventilation requirements and reduce field labor (CXB/

CBY/CPY/BPY).

• Wide variety of factory assembled valve packages to

meet desired controls specifications.

• Optional condensate overflow switch to address latest

building codes where required.

• Wide variety of optional insulation materials are

available to address IAQ concerns.

Ease of Installation• Factory assembled valve packages minimize piping

work at the job site (shipped loose for field mounting).

• Optional unit mounted controls, service switches and

fusing minimize the electrical work required on site.

• Units are tagged at the factory for clear identification

on job site.

• Opposite end connection units may minimize the

piping work on renovation jobs.

Ease of Service• All components are accessible by simply removing the

access panel.

• Filters can be replaced without tools or by opening the

bottom panels on exposed units.

• Blower assembly easily removed from the rear of coil

for service and cleaning.

Quality and Safety• Every unit is tested and inspected at the factory for

trouble free start-up.

• ETL and CETL listed.

• AHRI certified.

Page 7: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

7

uNIT MOdEL KEy

Y • NoneYY • None

• R • 3 Row, AAVS • 4 Row, AAV

CoilConstruction

Y • StdS • SS Wrapper

Code ItemsCode

* Consult factory for 50Hz applications.

** Note that kWs depend on voltage and unit size.

*** Standing in front of the unit, hand is determined by looking into the air supply and assigning the hand to match the location of the cooling coil connections.

Arrangement

56

CHY • Horizontal HideawayCPY • Horizontal Hideaway with PlenumCBY • Horizontal Telescoping HideawayCXB • Horizontal CabinetBHY • Horizontal Hi-Static HideawayBPY • Horizontal Hi-Static Hideaway

with Plenum

02 • 200 CFM03 • 300 CFM04 • 400 CFM06 • 600 CFM08 • 800 CFM10 • 1000 CFM12 • 1200 CFM

Two-pipe Cooling and Heating or Four-pipe Cooling

A 3 RowB • 4 RowD • 2 Row

Voltage

C • 120 VD • 208 VE • 240 VF • 277 VV • 220 V (50)*U • 240 V (50)*

Four-pipe Heating

Y • None6 • 1 Row7 • 2 Row

Voltage

C • 115-1-60

D • 208-1-60

E • 230-1-60

F • 277-1-60

V • 220-1-50*

U • 240-1-50*

Hand***

R • RightL • Left

Voltage

C • 120 VB • 24 V

D • 208 VE • 240 VF • 277 VV • 220 V (50)*

System

Manual Fan Operation

A • Standard Wall Mount (Switch Only)

Valve Cycle Control

G • 2-Pipe Heat OnlyH • 2-Pipe Cool OnlyJ • 2-Pipe Heat and Cool, MCOK • 2-Pipe Heat and Cool, ACOL • 2-Pipe Heat and Cool w/ Aux. Elec. Heat, MCOM • 2-Pipe Heat and Cool w/ Aux. Elec. Heat, ACON • 2-Pipe Cool w/ Total Elec. Heat, MCOP • 2-Pipe Cool w/ Total Elec. Heat, ACOQ • 4-Pipe Heat and Cool, MCOR • 4-Pipe Heat and Cool, ACO

Type

2 • PermanentSplit Capacitor

CHY, BHY

CPY, BPY

CBY

CXB

kW**

AY • 0.50 HY • 5.00BY • 1.00 JY • 6.00CY • 1.50 KY • 7.00DY • 2.00 LY • 8.00FY • 3.00 NY • 10.00GY • 4.00

Stages

Y • Single Stage Only

Coil Connection

Y • NoneS • Same EndO • Opposite End

NOTE: MCO controls (J, L, N, Q) not available with Standard Unit Mount Thermostat

•U • 240 V (50)*

Thermostat

4 • Basic Wall Series

P • 24 V Programmable Wall SeriesN • 24 V Non-Programmable

Wall Series

A • Horizontal Wall SeriesB • Vertical Wall Series

6

6

6

6

5

5

5

MOTOR

05C 2

SIZE

030 4

CONTROLS

07C BP

ELECTRIC HEAT

04aY YC B

VINTAGEUNIT

02Y

01C B

COILS

04Y YA Y

HAND/ARRANGEMENT

06R 5

Page 8: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com8

Horizontal SeriesrATINGS & LISTINGS

C-ETL US ListingIEC’s Horizontal Series units are

listed by ETL. The C-ETL-US listing

signifies that IEC’s fan coil units

have been examined by ETL and

are in compliance with both the

U.S. and Canadian applicable

standards.

AHRI CertificationIEC’s Horizontal Series units are

certified in compliance with

Air-Conditioning, Heating, and

Refrigeration Institute (AHRI) industry standard AHRI-440 for

room fan coil units. Approved standard ratings are tabulated

below.3061627

HEATING AND COOLING EQUIPMENT

Standard Ratings

Unit Type

Unit Cell Size

Nominal CFM

Cooling Capacity Power Input

Watts PSCTotal MBH

Sensible MBH

CHYCPYCXBCBY

02-A 200 6.0 4.4 87

03-A 300 9.0 6.3 85

04-A 400 12.1 8.8 165

06-A 600 17.3 13.0 225

08-A 800 22.6 16.2 235

10-A 1000 27.5 21.0 305

12-A 1200 32.8 25.0 435

CHYCPYCXBCBY

02-B 200 6.9 4.3 87

03-B 300 9.8 6.5 85

04-B 400 13.8 9.8 145

06-B 600 19.6 14.3 220

08-B 800 25.5 18.8 235

10-B 1000 31.0 22.0 300

12-B 1200 37.2 27.7 425

BHY

04-B 400 16.0 11.6 170

06-B 600 21.8 16.0 205

08-B 800 26.5 19.6 225

10-B 1000 37.2 27.6 355

NoTeS: 1. Ratings are based on 80°F DB and 67°F WB EAT, 45°F EWT, 10°F water temperature rise, high fan speed, motor voltage 115/1/60, and air flow under dry coil conditions.

2. For all application ratings, use IEC’s computer selection program, the quick-selection ratings provided in this catalog, or contact your local IEC representative.

3. For additional information, please consult AHRI’s website at www.ahrinet.org.

Page 9: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

9

AIr dELIvEry

Air Delivery (60 Hz)

Model Coil UnitSize

CFM@ 0.0 eSPFor Fan Speed

High Speed CFM@ eSP Indicated

Low Med High 0.05 0.10 0.15 0.20 0.25 0.30

CHY

3 Row

02 175 195 220 205 185 160 - - -03 250 295 330 300 265 225 170 - -04 220 360 510 480 450 415 370 290 -06 330 540 760 720 670 620 560 475 -08 335 590 870 840 800 760 700 620 -10 490 665 1100 1060 1010 930 845 730 -12 705 950 1425 1370 1310 1240 1160 1055 -

4 Row

02 165 190 215 200 175 140 - - -03 240 285 320 290 250 205 150 - -04 215 305 500 470 440 400 340 240 -06 295 530 745 700 650 590 525 430 -08 330 585 860 825 780 730 665 575 -10 480 655 1085 1040 970 895 800 670 -12 690 930 1400 1345 1280 1205 1115 990 -

CBYCPYCXB

3 Row

02 150 175 190 180 170 145 - - -03 215 270 300 275 250 215 165 - -04 205 275 470 445 415 380 320 250 -06 280 450 690 655 615 560 500 410 -08 335 565 835 800 760 710 650 570 -10 485 630 1045 995 940 880 805 710 -12 540 900 1300 1240 1180 1110 1025 920 840

4 Row

02 145 170 185 180 160 125 - - -03 205 260 290 270 240 195 - - -04 200 270 460 435 400 355 300 210 -06 220 440 675 635 595 535 465 355 -08 325 550 815 780 740 658 615 515 -10 475 615 1020 970 915 850 765 645 -12 530 880 1275 1215 1150 1075 980 850 815

BHY

3 Row

04 515 600 665 630 595 550 500 430 35006 545 705 830 780 725 670 610 550 48008 630 715 930 870 810 750 685 615 54010 1210 1350 1445 1360 1275 1185 1095 1000 880

4 Row

04 505 585 650 620 575 530 465 395 30006 525 680 800 750 700 640 585 520 44008 615 705 905 840 780 720 655 580 49510 1180 1315 1410 1320 1230 1140 1050 945 810

BPY

3 Row

04 485 535 570 540 505 465 420 360 28506 540 640 720 680 635 585 530 460 38508 545 660 800 750 695 640 580 515 44010 1060 1195 1295 1216 1130 1045 960 865 700

4 Row

04 420 525 555 520 485 445 390 330 -06 525 625 700 660 610 560 500 430 34008 535 645 780 725 670 615 555 485 39510 1035 1165 1260 1175 1090 1005 915 810 700

NoTeS: 1. Tabled values are standard CFM at sea level, 70°F with dry coil. 2. Ratings include factory-installed filter and/or grille, where applicable. 3. Consult factory for 50 Hz applications.

Page 10: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com10

Horizontal SeriesELECTrIC HEATING

Electric Heater Selection

Voltage kWUnit Size

02 03 04 06 08 10 12

120 V

0.5 • • - - - - -

1.0 • • • • • - -

1.5 • • • • • - -

2.0 • • • • • • •3.0 - • • • • • •

208 V

0.5 • • - - - - -

1.0 • • • • • - -

1.5 • • • • • - -

2.0 • • • • • • •3.0 - • • • • • •4.0 - - - • • • •5.0 - - - •

Note 6 • • •6.0 - - - •

Note 6•

Note 6 • •8.0 - - - - - •

Note 6•

Note 6

240 V277 V

0.5 • • - - - - -

1.0 • • • • • - -

1.5 • • • • • - -

2.0 • • • • • • •3.0 - • • • • • •4.0 - - - • • • •5.0 - - - •

Note 6 • • •6.0 - - - •

Note 6•

Note 6 • •8.0 - - - - - •

Note 6•

Note 6

10.0 - - - - - - • Note 6

NoTeS: 1. All heaters are single stage and single phase. 2. Heaters over 48 Amps are subdivided and fused. 3. Electric Heating Capacities (BTUH) = Heater kW x 3413. 4. Electric Heater Amperage = (Heater kW x 1000)/Applied

Voltage) 5. Consult factory for 50 Hz applications. 6. High and medium speed only.

Electric Resistance HeatingElectric heaters are available on IEC Horizontal Series fan coil

units for the following applications.

Total Electric HeatTotal electric heat eliminates the requirement for a boiler.

Heating and/or cooling may be available on an individual

basis throughout the year. Two-pipe chilled water is used

for cooling; and the electric heater is used for heating.

Individual room controls can be supplied for either manual

or automatic changeover.

Auxiliary Electric HeatAuxiliary electric heat is ideal for tempering room air

between seasons and during the cooling season when

chilled water is being circulated. Individual room controls

are supplied to provide electric heat only when chilled water

is being circulated. During regular heating season, heating is

provided by hot water being circulated in the system.

ConstructionThe heater coils of high-grade resistance wire are supported

by ceramic insulators on plated steel brackets. These heat

elements are suspended directly in front of the fan outlet

between the blower and the coil. High limit thermal cutouts

protect the heater in the event of air failure. There are many

special applications and control sequences for electric heat.

For special applications, please consult the factory.

Page 11: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

11

MOTOr dATA

Thermal Overload Protection and ETL ListingAll permanently lubricated split-capacitor motors furnished by IEC contain internal thermal-

overload protection. The overload automatically resets when the temperature returns to a

safe limit. Electronics Testing Laboratories, Inc. approves the motor and thermal overload

combination at locked rotor conditions only.

Motor Performance Data - CHY, CPY, CXB, CBY

Voltage Fan SpeedUnit Size 02 03 04 06 08 10 12

Nominal HP 1/30 1/30 1/12 1/12 1/6 (2) 1/12 (2) 1/6

115 V

60 Hz

1 Phase

HighAmps 0.53 0.83 1.40 1.40 2.50 2.80 5.00

Watts 87 85 165 165 235 305 435

MediumAmps 0.31 0.50 0.70 0.72 1.50 1.40 2.80

Watts 55 55 80 80 160 150 305

LowAmps 0.27 0.34 0.45 0.45 1.20 0.90 1.20

Watts 35 35 50 50 120 100 130

208 V

60 Hz

1 Phase

HighAmps 0.48 0.48 0.69 0.69 1.30 1.38 2.60

Watts 86 89 115 130 195 260 340

MediumAmps 0.29 0.29 0.43 0.47 0.69 0.94 1.33

Watts 60 60 89 100 135 190 255

LowAmps 0.15 0.15 0.22 0.24 0.47 0.46 0.94

Watts 28 28 45 48 90 90 180

230 V

60 Hz

1 Phase

HighAmps 0.48 0.48 0.69 0.69 1.30 1.38 2.60

Watts 103 106 135 155 210 290 380

MediumAmps 0.31 0.32 0.45 0.52 0.70 1.00 1.34

Watts 70 73 105 115 150 220 285

LowAmps 0.15 0.15 0.24 0.28 0.50 0.50 1.00

Watts 33 33 53 60 105 110 210

277 V

60 Hz

1 Phase

HighAmps 0.35 0.35 0.69 0.69 0.91 1.38 1.82

Watts 80 80 150 155 240 270 440

MediumAmps 0.26 0.26 0.43 0.43 0.62 0.80 1.20

Watts 64 66 110 110 160 200 300

LowAmps 0.16 0.16 0.25 0.35 0.35 0.25 0.66

Watts 40 43 60 90 90 75 175

NoTeS: 1. Total unit motor Amps and Watts are shown. 2. Consult factory for 50 Hz applications.

Page 12: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com12

Horizontal SeriesMOTOr dATA, Cont’d.

Motor Performance Data - BHY, BPY

Voltage Fan SpeedUnit Size 04 06 08 10

Nominal HP 1/8 1/8 1/8 (2) 1/8

115 V60 Hz

1 Phase

HighAmps 1.70 1.70 1.70 3.40Watts 170 205 225 355

MediumAmps 1.65 1.65 1.70 3.37Watts 160 175 195 345

LowAmps 1.45 1.45 1.45 2.95Watts 135 140 165 290

208 V60 Hz

1 Phase

HighAmps 0.76 0.76 0.76 1.52Watts 135 150 160 280

MediumAmps 0.60 0.66 0.67 1.25Watts 120 130 135 250

LowAmps 0.54 0.57 0.57 1.05Watts 105 110 110 205

230 V60 Hz

1 Phase

HighAmps 0.76 0.76 0.76 1.52Watts 150 160 170 300

MediumAmps 0.58 0.66 0.67 1.30Watts 128 145 135 260

LowAmps 0.55 0.60 0.57 1.05Watts 115 127 127 205

277 V60 Hz

1 Phase

HighAmps 0.64 0.64 0.64 1.28Watts 145 155 170 310

MediumAmps 0.45 0.48 0.54 0.95Watts 125 130 145 265

LowAmps 0.36 0.36 0.39 0.74Watts 90 90 100 195

NoTeS: 1. Total unit motor Amps and Watts are shown. 2. Consult factory for 50 Hz applications.

Page 13: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

13

PHySICAL dATA

CHY - Horizontal Hideaway

AIR VENT

1"(25) SUPPLY DUCTCOLLAR

SUPPLYAIR

MTG. HOLES

RESILIENT MOUNTING GROMMET W/ 3/8"(10) DIA. HOLES (TYP. OF 4)

CHILLED/HOT WATERSUPPLY & RETURNCONNECTIONS

A'

OPTIONAL EXTENDEDDRAIN PAN(SEE NOTE 2)

OPTIONAL DRIP LIPSHIPPED LOOSE

OPTIONAL 5/8"(16) O.D. TELL-TALEDRAIN CONNECTION, AVAILABLE ON

STANDARD AND EXTENDED DRAIN PANS

7/8"(22) O.D. CONDENSATE DRAIN

FLEXIBLE METALCONDUIT

RIGHT SIDE VIEWFRONT VIEW

TOP VIEW

6(152)

1-1/2(38)

B

A

3(76)

2-1/4(64)

1-1/8(29)

1(25)

H

E 3/4(19)

3/4(19)

16(406)

G F

17-1/2(445)

8-3/8(213)

1(25)

D'

7/8(22)

JUNCTION BOX

(REMOTE MOUNT)

(NOTE 5)

4(102)

4(102)

Unit Model

Dimensions - Inches (Millimeters) Quantity/Unit Unit Weight*A A’ B D’ e F G H Blower Motor

CHY02 21-1/4 (540) 31-1/4 (794) 16 (406) 13 (330) 18-1/4 (464) 6-1/4 (159) 8-3/4 (222) 19-3/4 (502) 1 1 36CHY03 25-1/4 (641) 36-1/4 (921) 20 (508) 14 (356) 22-1/4 (565) 6-1/4 (159) 8-3/4 (222) 23-3/4 (603) 1 1 39CHY04 31-1/4 (794) 43-1/4 (1099) 26 (660) 15 (381) 28-1/4 (718) 6-1/4 (159) 8-3/4 (222) 29-3/4 (756) 2 1 49CHY06 36-1/4 (921) 43-1/4 (1099) 31 (787) 10 (254) 33-1/4 (845) 7-1/2 (191) 10 (254) 34-3/4 (883) 2 1 59CHY08 43-1/4 (1099) 57-1/4 (1454) 38 (965) 17 (432) 40-1/4 (1022) 7-1/2 (191) 10 (254) 41-3/4 (1060) 2 1 64CHY10 57-1/4 (1454) 65-1/4 (1657) 52 (1321) 11 (279) 54-1/4 (1378) 7-1/2 (191) 10 (254) 55-3/4 (1416) 4 2 95CHY12 65-1/4 (1657) 75-1/4 (1911) 60 (1524) 13 (330) 62-1/4 (1581) 7-1/2 (191) 10 (254) 63-3/4 (1619) 4 2 107

NoTeS: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Optional drip lip not required with optional extended drain pan. 3. All dimensions are +/- 1/4" (6). 4. Product specifications are subject to change without notice. 5. Drip lip recommended. 6. Threaded fittings must be field tightened and leak tested.

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for

up to date drawings.

Page 14: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com14

Horizontal SeriesPHySICAL dATA, Cont’d.

CHY - Horizontal Hideaway with Electric Heat

RIGHT SIDE VIEWFRONT VIEW

TOP VIEW

CONTROL BOX(REMOTE MOUNT)

ELECTRIC STRIPHEATER ELEMENT

STRIP HEATERHIGH LIMIT

FLEXIBLE METALCONDUIT

7/8"(22) O.D.CONDENSATE DRAIN

OPTIONAL 5/8"(16) O.D.

TELL-TALE DRAIN CONNECTION,

AVAILABLE ON STANDARD AND

EXTENDEDDRAIN PANS

OPTIONAL DRIP LIPSHIPPED LOOSE(NOTE 5)

OPTIONAL EXTENDEDDRAIN PAN (SEE NOTE 2)

A'

CHILLED/HOT WATERSUPPLY & RETURNCONNECTIONS

RESILIENT MOUNTING GROMMETW/ 3/8"(10) DIA. HOLES (TYP. OF 4)

MTG. HOLES

AIRSUPPLY

1" SUPPLY DUCT

COLLAR

VENTAIR

6(152)

1-1/2(38)

1-1/8(29)

2-1/4(64)

AB

E

1(25)

D'

21-1/2(546)

12-3/8(314)

1(25)

G F

7/8(22)

16(406)

H3/4(19)

3/4(19)

3(76)

6 (152)STD.

5-3/8(137)STD.

Unit Model

Dimensions - Inches (Millimeters) Quantity/Unit Unit Weight*A A’ B D’ e F G H Blower Motor

CHY02 21-1/4 (540) 31-1/4 (794) 16 (406) 13 (330) 18-1/4 (464) 6-1/4 (159) 8-3/4 (222) 19-3/4 (502) 1 1 38CHY03 25-1/4 (641) 36-1/4 (921) 20 (508) 14 (356) 22-1/4 (565) 6-1/4 (159) 8-3/4 (222) 23-3/4 (603) 1 1 41CHY04 31-1/4 (794) 43-1/4 (1099) 26 (660) 15 (381) 28-1/4 (718) 6-1/4 (159) 8-3/4 (222) 29-3/4 (756) 2 1 51CHY06 36-1/4 (921) 43-1/4 (1099) 31 (787) 10 (254) 33-1/4 (845) 7-1/2 (191) 10 (254) 34-3/4 (883) 2 1 61CHY08 43-1/4 (1099) 57-1/4 (1454) 38 (965) 17 (432) 40-1/4 (1022) 7-1/2 (191) 10 (254) 41-3/4 (1060) 2 1 66CHY10 57-1/4 (1454) 65-1/4 (1657) 52 (1321) 11 (279) 54-1/4 (1378) 7-1/2 (191) 10 (254) 55-3/4 (1416) 4 2 97CHY12 65-1/4 (1657) 75-1/4 (1911) 60 (1524) 13 (330) 62-1/4 (1581) 7-1/2 (191) 10 (254) 63-3/4 (1619) 4 2 109

NoTeS: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Optional drip lip not required with optional extended drain pan. 3. All dimensions are +/- 1/4" (6). 4. Product specifications are subject to change without notice. 5. Drip lip recommended. 6. Threaded fittings must be field tightened and leak tested.

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for

up to date drawings.

Page 15: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

15

PHySICAL dATA, Cont’d.

CPY - Horizontal Hideaway with Plenum

15-1/4(387)

11-3/8(289)

FILTER REMOVAL

FILTER REMOVAL

10-1/2(267)

20(508)

19(483)

7/8(22)

FG

1(25)

1" (25) SUPPLY

DUCT COLLAR

SUPPLYAIR

3/4(19)

E

A 16(406)

1-1/2(38)

1-1/8(29) C

2-1/4(57) B 3

(76)MTG. HOLES

RESILIENT MOUNTING GROMMET W/ 3/8" (10) DIA. HOLES (TYP. OF 4) CHILLED/HOT WATER

SUPPLY & RETURNCONNECTIONS

D'

A'

OPTIONALEXTENDEDDRAIN PAN(SEE NOTE 2)

OPTIONAL DRIP LIPSHIPPED LOOSE(NOTE 5)

AIR VENT

REAR ACCESSPANEL

1"(25) FILTER

1" (25) RETURNDUCTCOLLAR

1" (25) FILTER

FILTERRETAINERCLIP

BOTTOM ACCESS

PANEL

CONDENSATE7/8" (22) O.D.

DRAIN

RETURNAIR

AIRRETURN

RIGHT SIDE VIEWFRONT VIEW

TOP VIEW

OPTIONAL 5/8" (16) O.D. TELL-TALEDRAIN CONNECTION, AVAILABLE ON

STANDARD AND EXTENDED DRAIN PANS

HREAR MTG. HOLES

JUNCTION BOX INSULATED PLENUM

1-1/2(38)

1(25)

3/4(19)

OPTIONAL REAR RETURN

3

3-1/4 (83)

4(102)

3(76)

Unit Model

Dimensions - Inches (Millimeters) Quantity/Unit Unit Weight*A A’ B C D’ e F G H Blower Motor

CPY02 21-1/4 (540) 31-1/4 (794) 16 (406) 18-1/4 (464) 13 (330) 19-3/4 (502) 6-1/4 (159) 8-3/4 (222) 15-3/8 (391) 1 1 55CPY03 25-1/4 (641) 36-1/4 (921) 20 (508) 22-1/4 (565) 14 (356) 23-3/4 (603) 6-1/4 (159) 8-3/4 (222) 19-3/8 (883) 1 1 60CPY04 31-1/4 (794) 43-1/4 (1099) 26 (660) 28-1/4 (718) 15 (381) 29-3/4 (756) 6-1/4 (159) 8-3/4 (222) 25-3/8 (645) 2 1 70CPY06 36-1/4 (921) 43-1/4 (1099) 31 (787) 33-1/4 (845) 10 (254) 34-3/4 (883) 7-1/2 (190) 10 (254) 30-3/8 (772) 2 1 82CPY08 43-1/4 (1099) 57-1/4 (1454) 38 (965) 40-1/4 (1022) 17 (432) 41-3/4 (1060) 7-1/2 (190) 10 (254) 37-3/8 (949) 2 1 95CPY10 57-1/4 (1454) 65-1/4 (1657) 52 (1321) 54-1/4 (1378) 11 (279) 55-3/4 (1416) 7-1/2 (190) 10 (254) 51-3/8 (1305) 4 2 135CPY12 65-1/4 (1657) 75-1/4 (1911) 60 (1524) 62-1/4 (1581) 13 (330) 63-3/4 (1619) 7-1/2 (190) 10 (254) 59-3/8 (1508) 4 2 154

NoTeS: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Optional drip lip not required with optional extended drain pan. 3. All dimensions are +/- 1/4" (6). 4. Product specifications are subject to change without notice. 5. Drip lip recommended. 6. Threaded fittings must be field tightened and leak tested. 7. Control box size and position may vary (consult factory).

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for

up to date drawings.

Page 16: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com16

Horizontal SeriesPHySICAL dATA, Cont’d.

CPY - Horizontal Hideaway with Plenum with Electric Heat

FRONT VIEW RIGHT SIDE VIEW

ELECTRICAL KNOCKOUTSIN TOP & BOTTOM OFCONTACTOR BOX

CONTROLBOX

STRIP HEATERHIGH LIMIT

ELEMENTSTRIP HEATERELECTRIC

3-1/4(83)

3/4(19)

RETURNAIR

INSULATED PLENUM

REAR MTG. HOLESH 1-1/2

(38)

7/8" (22) O.D.CONDENSATIONDRAIN

1" (25) FILTER

REAR ACCESS

AIR VENT

OPTIONAL DRIP LIPSHIPPED LOOSE(NOTE 5)

CHILLED/HOTWATER SUPPLY &RETURN CONNECTIONS

RESILIENT MOUNTING GROMMET W/ 3/8" (10) DIA. HOLES (TYP. OF 4)

1(25)

16(406)

3/4(19)

3/4(19)

AIRSUPPLY

1" (25)SUPPLY

DUCTCOLLAR

7/8(22)

23(584)

24(610)

10-1/2(267)

FILTER REMOVAL

11-3/8(289)

19-1/4(489)

FILTER REMOVAL

D'

A'

OPTIONAL EXTENDEDDRAIN PAN (SEE NOTE 2)

COLLARDUCT1" (25) RETURN

1" (25) FILTER

FILTERRETAINERCLIP

BOTTOM ACCESS

PANEL

AIRRETURN

OPTIONAL 5/8" (16) O.D.

TELL-TALEDRAIN

CONNECTION, AVAILABLE ON

STANDARD AND EXTENDED

DRAIN PANS

1-1/2(38) 1-1/8

(29) C

2-1/4(57) B 3

(76)A

FRONT MTG. HOLES

TOP VIEW OPTIONAL REAR RETURN

FG

5-3/8(137)STD.

6(152)STD.

Unit Model

Dimensions - Inches (Millimeters) Quantity/Unit Unit Weight*A A’ B C D’ e F G H Blower Motor

CPY02 21-1/4 (540) 31-1/4 (794) 16 (406) 18-1/4 (464) 13 (330) 19-3/4 (502) 6-1/4 (159) 8-3/4 (222) 15-3/8 (391) 1 1 57CPY03 25-1/4 (641) 36-1/4 (921) 20 (508) 22-1/4 (565) 14 (356) 23-3/4 (603) 6-1/4 (159) 8-3/4 (222) 19-3/8 (883) 1 1 62CPY04 31-1/4 (794) 43-1/4 (1099) 26 (660) 28-1/4 (718) 15 (381) 29-3/4 (756) 6-1/4 (159) 8-3/4 (222) 25-3/8 (645) 2 1 72CPY06 36-1/4 (921) 43-1/4 (1099) 31 (787) 33-1/4 (845) 13 (330) 34-3/4 (883) 7-1/2 (190) 10 (254) 30-3/8 (772) 2 1 84CPY08 43-1/4 (1099) 57-1/4 (1454) 38 (965) 40-1/4 (1022) 17 (432) 41-3/4 (1060) 7-1/2 (190) 10 (254) 37-3/8 (949) 2 1 97CPY10 57-1/4 (1454) 65-1/4 (1657) 52 (1321) 54-1/4 (1378) 11 (279) 55-3/4 (1416) 7-1/2 (190) 10 (254) 51-3/8 (1305) 4 2 137CPY12 65-1/4 (1657) 75-1/4 (1911) 60 (1524) 62-1/4 (1581) 13 (330) 63-3/4 (1619) 7-1/2 (190) 10 (254) 59-3/8 (1508) 4 2 156

NoTeS: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Optional drip lip not required with optional extended drain pan. 3. All dimensions are +/- 1/4" (6). 4. Product specifications are subject to change without notice. 5. Drip lip recommended. 6. Threaded fittings must be field tightened and leak tested. 7. Control box size and position may vary (consult factory).

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for

up to date drawings.

Page 17: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

17

PHySICAL dATA, Cont’d.

CBY - Horizontal Telescoping Hideaway

TOP VIEW

FRONT VIEW RIGHT SIDE VIEW

(TYPICAL BOTH SIDES)PARTIAL REAR VIEW

1-1/2(38)KNOCKOUT (TYPICAL)

7/8"(22)KNOCKOUT

DRAIN CONNECTION7/8"(22) O.D. CONDENSATE AIR

RETURN1"(25) FILTERAIR GRILLE &STAMPED RETURN

DUCT COLLAR1"(25) SUPPLY

F

1-1/4(32)

24(610)

1-1/2(38)

20-3/4(527)

1-1/2(38)

D

14(356)MAX.

12(305)MIN.

11-1/4(286)

A

6-1/8(156)

B C1-1/2(38) 1-1/2

(38)

CHILLED/HOT WATER SUPPLY& RETURN CONNECTION

RESILIENT MOUNTINGGROMMETS WITH 3/8"(10)DIA. HOLE (TYP. OF 4)

OPTIONAL "L" SHAPE DRIPLIP, SHIPPED LOOSE (NOTE 5)

JUNCTION BOX

26(660)

1(25)

1(25)

1-1/2(38)

20-3/4(527)

1-1/2(38)

1(25)

1(25)

E

6-1/8(156)

AIR

SUPPLY

HINGEDBOTTOM RETURN

AIR PANEL

OPTIONALDUCTEDREAR RETURN

Unit Model

Dimensions - Inches (Millimeters) Quantity/Unit Unit Weight*A B C D e F Blower Motor

CBY02 35 (889) 16 (406) 12-3/4 (324) 37 (940) 32 (813) 6 (152) 1 1 115CBY03 35 (889) 20 (508) 8-3/4 (222) 37 (940) 32 (813) 6 (152) 1 1 120CBY04 41 (1041) 26 (660) 8-3/4 (222) 43 (1092) 38 (965) 6 (152) 2 1 135CBY06 53 (1346) 31 (787) 15-3/4 (400) 55 (1397) 50 (1270) 7 (178) 2 1 150CBY08 53 (1346) 38 (965) 8-3/4 (222) 55 (1397) 50 (1270) 7 (178) 2 1 155CBY10 75 (1905) 52 (1321) 16-3/4 (425) 77 (1956) 72 (1829) 7 (178) 4 2 227CBY12 75 (1905) 60 (1524) 8-3/4 (222) 77 (1956) 72 (1829) 7 (178) 4 2 241

NoTeS: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Internal factory valve packages and drains may not align w/cabinet knockouts. 3. All dimensions are +/- 1/4" (6). 4. Product specifications are subject to change without notice. 5. Drip lip required for units with valves. 6. Threaded fittings must be field tightened and leak tested.

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for

up to date drawings.

Page 18: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com18

Horizontal SeriesPHySICAL dATA, Cont’d.

CBY - Horizontal Telescoping Hideaway with Electric Heat

TOP VIEW

FRONT VIEW RIGHT SIDE VIEW

ELECTRIC STRIPHEATER ELEMENT

STRIP HEATERHIGH LIMIT

(TYPICAL BOTH SIDES)PARTIAL REAR VIEW

1-1/2(38)KNOCKOUT

(TYPICAL)

7/8"(22)KNOCKOUT

7/8"(22) O.D. CONDENSATE

DRAIN CONNECTION

RETURNAIR

STAMPED RETURNAIR GRILLE &1"(25) FILTER

DUCT COLLAR1"(25) SUPPLY

F

1-1/4(32)

1-1/2(38)

20-3/4(527)

1-1/2(38)

D

14(356)MAX.

12(305)MIN.

11-1/4(286)

A6-1/8(156) B C

1-1/2(38)

1-1/2(38)

CHILLED/HOT WATER SUPPLY& RETURN CONNECTION

RESILIENT MOUNTINGGROMMETS WITH 3/8"(19)DIA. HOLE (TYP. OF 4)

OPTIONAL "L" SHAPE DRIPLIP, SHIPPED LOOSE (NOTE 5)

CONTROL BOX

26(660)

1(25) 1-1/2

(38)

20-3/4(527)

1-1/2(38)

1(25)

1(25)

E

6-1/8(156)

AIR

SUPPLY

HINGEDBOTTOM RETURN

AIR PANEL

24(610)

OPTIONALDUCTEDREARRETURN

1(25)

Unit Model

Dimensions - Inches (Millimeters) Quantity/Unit Unit Weight*A B C D e F Blower Motor

CBY02 35 (889) 16 (406) 12-3/4 (324) 37 (940) 32 (813) 6 (152) 1 1 117CBY03 35 (889) 20 (508) 8-3/4 (222) 37 (940) 32 (813) 6 (152) 1 1 122CBY04 41 (1041) 26 (660) 8-3/4 (222) 43 (1092) 38 (965) 6 (152) 2 1 137CBY06 53 (1346) 31 (787) 15-3/4 (400) 55 (1397) 50 (1270) 7 (178) 2 1 152CBY08 53 (1346) 38 (965) 8-3/4 (222) 55 (1397) 50 (1270) 7 (178) 2 1 157CBY10 75 (1905) 52 (1321) 16-3/4 (425) 77 (1956) 72 (1829) 7 (178) 4 2 229CBY12 75 (1905) 60 (1524) 8-3/4 (222) 77 (1956) 72 (1829) 7 (178) 4 2 243

NoTeS: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Optional drip lip not required with optional extended drain pan. 3. All dimensions are +/- 1/4" (6). 4. Product specifications are subject to change without notice. 5. Drip lip required for units with valves. 6. Threaded fittings must be field tightened and leak tested.

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for

up to date drawings.

Page 19: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

19

PHySICAL dATA, Cont’d.

CBY - Horizontal Telescoping Hideaway with Bottom Supply

FRONT VIEW

(TYPICAL BOTH SIDES)PARTIAL REAR VIEW

1-1/2(38) KNOCKOUT

(TYPICAL)

7/8"(22)KNOCKOUT

D

14"(356)MAX.

12"(305)MIN.

11-1/4(286)

A

30-3/4 (781)34(864)

RIGHT SIDE VIEW

HINGEDBOTTOM RETURN

AIR PANEL

1-1/2(38)

AIR GRILLE &AIR 1"(25) FILTER

STAMPED RETURN

7/8"(22) O.D.

RETURN

1-1/2(38)

DRAIN CONNECTION

SUPPLYAIR

STAMPED SUPPLYAIR GRILLE

E

36(914)

30-3/4(781)

1(25)

1-1/2 (38)

1(25) TOP VIEW

1(25) 1-1/2(38) JUNCTION BOX

1(25)

1-1/2 (38)

RESILIENT MOUNTING GROMMETS WITH 3/8"(10) DIA. HOLE (TYP. OF 4)

OPTIONAL "L" SHAPE DRIP LIP, SHIPPED LOOSE (NOTE 5)

CHILLED/HOT WATER SUPPLY& RETURN CONNECTION

6"(152)

1-1/2(38)

CONDENSATE

OPTIONALDUCTEDREAR RETURN

E1-1/2 (38) 1-1/2 (38)

Unit ModelDimensions - Inches (Millimeters) Quantity/Unit

Unit Weight*A D e F Blower Motor

CBY02 35 (889) 37 (940) 32 (813) 6 (152) 1 1 115CBY03 35 (889) 37 (940) 32 (813) 6 (152) 1 1 120CBY04 41 (1041) 43 (1092) 38 (965) 6 (152) 2 1 135CBY06 53 (1346) 55 (1397) 50 (1270) 7 (178) 2 1 150CBY08 53 (1346) 55 (1397) 50 (1270) 7 (178) 2 1 155CBY10 75 (1905) 77 (1956) 72 (1829) 7 (178) 4 2 227CBY12 75 (1905) 77 (1956) 72 (1829) 7 (178) 4 2 241

NoTeS: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Internal factory valve packages and drains may not align w/cabinet knockouts. 3. All dimensions are +/- 1/4" (6). 4. Product specifications are subject to change without notice. 5. Drip lip required for units with valves. 6. Threaded fittings must be field tightened and leak tested.

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for

up to date drawings.

Page 20: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com20

Horizontal SeriesPHySICAL dATA, Cont’d.

CBY - Horizontal Telescoping Hideaway with Bottom Supply with Electric Heat

FRONT VIEW

(TYPICAL BOTH SIDES)PARTIAL REAR VIEW

1-1/2(38) KNOCKOUT (TYPICAL)7/8"(22) KNOCKOUT

D

14"(356)MAX.

12"(305)MIN.

11-1/4(286)

A1-1/2(38) E 1-1/2

(38)

30-3/4(781)

34(864)

RIGHT SIDE VIEW

HINGEDBOTTOM RETURN

AIR PANEL

1-1/2(38)

STAMPED RETURNAIR GRILLE &1"(25) FILTER

AIRRETURN

1-1/2(38)

SUPPLYAIR

STAMPED SUPPLYAIR GRILLE

E

36(914)

30-3/4(781)

1(25)

1-1/2(38)

1(25)

1-1/2(38)

TOP VIEW

1(25)1-1/2(38)

1(25)

1-1/2(38)

RESILIENT MOUNTINGGROMMETS WITH 3/8"(10) DIA. HOLE (TYP. OF 4)

OPTIONAL "L" SHAPE DRIP LIP, SHIPPED LOOSE (NOTE 5)

CHILLED/HOT WATER SUPPLY & RETURN CONNECTION

6"(152)

STRIP HEATERHIGH LIMIT HEATER ELEMENT

ELECTRIC STRIPCONTROL BOX

7/8"(22) O.D. CONDENSATEDRAIN CONNECTION

*DRAWING NOT TO SCALE*

OPTIONALDUCTEDREAR RETURN

Unit ModelDimensions - Inches (Millimeters) Quantity/Unit

Unit Weight*A D e Blower Motor

CBY02 35 (889) 37 (940) 32 (813) 1 1 117CBY03 35 (889) 37 (940) 32 (813) 1 1 122CBY04 41 (1041) 43 (1092) 38 (965) 2 1 137CBY06 53 (1346) 55 (1397) 50 (1270) 2 1 152CBY08 53 (1346) 55 (1397) 50 (1270) 2 1 157CBY10 75 (1905) 77 (1956) 72 (1829) 4 2 229CBY12 75 (1905) 77 (1956) 72 (1829) 4 2 243

NoTeS: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Internal factory valve packages and drains may not align w/cabinet knockouts. 3. All dimensions are +/- 1/4" (6). 4. Product specifications are subject to change without notice. 5. Drip lip required for units with valves. 6. Threaded fittings must be field tightened and leak tested.

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for

up to date drawings.

Page 21: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

21

PHySICAL dATA, Cont’d.

CXB - Horizontal Cabinet

SUPPLYAIR

APPROX.REF.

1-1/2(38)

RETURNAIR

7/8" (22) O.D. CONDENSATEDRAIN CONNECTION

AIRVENT

RESILIENT MOUNTINGGROMMETS WITH 3/8" (10)DIA. HOLE (TYP. OF 4)

2(51)

2(51)

2(51)

SUPPLY AIR GRILLESTANDARD STAMPED

OPTIONAL "L" SHAPEDDRIP LIP, SHIPPEDLOOSE (NOTE 5)

CHILLED/HOT WATERSUPPLY & RETURN

CONNECTIONS

STAMPED RETURNAIR GRILLE &1" (25) FILTER

RIGHT SIDE VIEWFRONT VIEW

TOP VIEW

REMOVABLE HINGEDR.A./ACCESS

PANEL

18(457)

Ø7/8" (22) KNOCKOUT(TYP. OF 2)

Ø1-1/2"(38) KNOCKOUT(TYP. OF 5)

PARTIAL REAR VIEW(TYPICAL BOTH SIDES)

2(51)

CONTROL BOX

5-3/4(146)

AIRRETURN

1" (25) FILTERAIR GRILLE &STAMPED RETURNOPTIONAL

OPTIONAL

LOCATION

STANDARD

C B C

E

A

FG

3 1/2(89)

23-1/2(597)

Unit ModelDimensions - Inches (Millimeters) Quantity/Unit Unit

Weight*A B C e F G Blower MotorCXB02 38 (965) 17-1/8 (435) 10-7/16 (265) 34 (864) 5-3/4 (146) 11 (279) 1 1 98CXB03 42 (1067) 21-1/2 (546) 10-1/4 (260) 38 (965) 5-3/4 (146) 11 (279) 1 1 118CXB04 48 (1219) 25-7/8 (657) 11-1/16 (281) 44 (1118) 5-3/4 (146) 11 (279) 2 1 126CXB06 53 (1346) 34-5/8 (879) 9-3/16 (233) 49 (1245) 6-3/4 (171) 12 (305) 2 1 168CXB08 60 (1524) 39 (991) 10-1/2 (267) 56 (1422) 6-3/4 (171) 12 (305) 2 1 176CXB10 74 (1880) 52-1/8 (1324) 10-15/16 (262) 70 (1778) 6-3/4 (171) 12 (305) 4 2 215CXB12 82 (2083) 60-7/8 (1546) 10-9/16 (268) 78 (1981) 6-3/4 (171) 12 (305) 4 2 245

NoTeS: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Internal factory valve packages and drains may not align w/cabinet knockouts. 3. All dimensions are +/- 1/4" (6). 4. Product specifications are subject to change without notice. 5. Drip lip required for units with valves. 6. Threaded fittings must be field tightened and leak tested.

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for

up to date drawings.

Page 22: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com22

Horizontal SeriesPHySICAL dATA, Cont’d.

CXB - Horizontal Cabinet with optional Electric Heat

SUPPLYAIR

APPROX.REF.

1-1/2(38)

RETURNAIR

7/8" (22) O.D.

DRAIN CONNECTION

AIR VENT

RESILIENT MOUNTINGGROMMETS WITH 3/8" (10)DIA. HOLE (TYP. OF 4)

2(51)

2(51)

2(51)

SUPPLY AIR GRILLESTANDARD STAMPED

OPTIONAL "L" SHAPEDDRIP LIP, SHIPPEDLOOSE

CHILLED/HOT WATERSUPPLY & RETURN

CONNECTIONS

STAMPED RETURNAIR GRILLE &1" (25) FILTER

ELECTRIC STRIPHEATER ELEMENT

RIGHT SIDE VIEWFRONT VIEW

TOP VIEW

REMOVABLE HINGEDR.A./ACCESS

PANEL

18(457)

Ø7/8" (22) KNOCKOUT(TYP. OF 2)

Ø1-1/2"(38) KNOCKOUT(TYP. OF 5)

PARTIAL REAR VIEW(TYPICAL BOTH SIDES)

2(51)

5-3/4(146)

1" (25) FILTERAIR GRILLE &STAMPED RETURN

OPTIONAL

OPTIONAL

STANDARD

C B C

E

A

FG

3-1/2(89)

(NOTE 5)

23-1/2(597)

CONDENSATE

AIRRETURNOPTIONAL

LOCATION

CONTROL BOX

Unit ModelDimensions - Inches (Millimeters) Quantity/Unit Unit

Weight*A B C e F G Blower MotorCXB02 38 (965) 17-1/8 (435) 10-7/16 (265) 34 (864) 5-3/4 (146) 11 (279) 1 1 100CXB03 42 (1067) 21-1/2 (546) 10-1/4 (260) 38 (965) 5-3/4 (146) 11 (279) 1 1 120CXB04 48 (1219) 25-7/8 (657) 11-1/16 (281) 44 (1118) 5-3/4 (146) 11 (279) 2 1 128CXB06 53 (1346) 34-5/8 (879) 9-3/16 (233) 49 (1245) 6-3/4 (171) 12 (305) 2 1 170CXB08 60 (1524) 39 (991) 10-1/2 (267) 56 (1422) 6-3/4 (171) 12 (305) 2 1 178CXB10 74 (1880) 52-1/8 (1324) 10-15/16 (262) 70 (1778) 6-3/4 (171) 12 (305) 4 2 217CXB12 82 (2083) 60-7/8 (1546) 10-9/16 (268) 78 (1981) 6-3/4 (171) 12 (305) 4 2 247

NoTeS: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Internal factory valve packages and drains may not align w/cabinet knockouts. 3. All dimensions are +/- 1/4" (6). 4. Product specifications are subject to change without notice. 5. Drip lip required for units with valves. 6. Threaded fittings must be field tightened and leak tested.

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for

up to date drawings.

Page 23: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

23

PHySICAL dATA, Cont’d.

BHY - Horizontal Hi-Static Hideaway

11-1/4(286)

19-3/4(502)

8-3/8(213)7/8

(22)

FG

1(25)

AIR VENT

1"(25) SUPPLY

DUCT COLLAR

SUPPLYAIR

E 3/4(19)

H

G

A

16(406)

1-1/2(38)

6(152)

1-1/8(29)

E

2-1/4(57)

B 3(76)

A

1(25)

MTG. HOLES

RESILIENT MOUNTING GROMMET W/ 3/8"(10) DIA. HOLES (TYP. OF 4)

CHILLED/HOT WATERSUPPLY & RETURNCONNECTIONS

D'OPTIONAL EXTENDED DRAIN PAN (SEE NOTE 2)

OPTIONAL DRIP LIPSHIPPED LOOSE(NOTE 5)

OPTIONAL 5/8"(16) O.D.

TELL-TALE DRAIN CONNECTION,

AVAILABLE ON STANDARD AND

EXTENDED DRAIN PANS

JUNCTION BOX (REMOTE MOUNT)

RIGHT SIDE VIEWFRONT VIEW

TOP VIEW

7/8"(22) O.D. CONDENSATE DRAIN

FLEXIBLE METAL CONDUIT

A'

*DRAWING NOT TO SCALE*

3/4(19)

4(102)

4(102)

Unit Model

Dimensions - Inches (Millimeters) Quantity/Unit Unit Weight*A A’ B D’ e F G H Blower Motor

BHY04 31-1/4 (794) 43-1/4 (1099) 26 (660) 15 (381) 28-1/4 (718) 6-1/4 (159) 8-3/4 (222) 29-3/4 (756) 2 1 62BHY06 36-1/4 (921) 43-1/4 (1099) 31 (787) 10 (254) 33-1/4 (845) 7-1/2 (191) 10 (254) 34-3/4 (883) 2 1 73BHY08 43-1/4 (1099) 57-1/4 (1454) 38 (965) 17 (432) 40-1/4 (1022) 7-1/2 (191) 10 (254) 41-3/4 (1060) 2 1 82BHY10 57-1/4 (1454) 65-1/4 (1657) 52 (1321) 11 (279) 54-1/4 (1378) 7-1/2 (191) 10 (254) 55-3/4 (1416) 4 2 128

NoTeS: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Optional drip lip not required with optional extended drain pan. 3. All dimensions are +/- 1/4" (6). 4. Product specifications are subject to change without notice. 5. Drip lip recommended. 6. Threaded fittings must be field tightened and leak tested.

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for

up to date drawings.

Page 24: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com24

Horizontal Series

BHY - Horizontal Hi-Static Hideaway with Electric Heat

TOP VIEW

FRONT VIEWRIGHT SIDE VIEW

STRIP HEATER

CONDUITFLEXIBLE METAL

7/8"(22) O.D. CONDENSATE DRAIN

OPTIONAL 5/8"(16) O.D.

TELL-TALEDRAIN

CONNECTION,AVAILABLE

ON STANDARD AND EXTENDED

DRAIN PANS

OPTIONAL DRIP LIP (NOTE 5) SHIPPED LOOSE

DRAIN PAN (SEE NOTE 2)OPTIONAL EXTENDED

D'

CHILLED/HOT WATER SUPPLY & RETURN CONNECTIONS

W/ 3/8"(10) DIA. HOLES (TYP. OF 4)RESILIENT MOUNTING GROMMET

MTG. HOLES

1(25)

A

3(76)B2-1/4

(57)

E1-1/8(29)

6(152)

1-1/2(38)

16(406)

A

G

H

3/4(19)

E

AIRSUPPLY

VENTAIR

G F

12-3/8(314)

23-3/4(603)1

(25)

1"(25) SUPPLY

DUCT COLLAR

7/8(22)

11-1/4(286)

A'

3/4(19)

CONTROL BOX(REMOTE MOUNT)

6(152)STD.

5-3/8(137)STD.

Unit Model

Dimensions - Inches (Millimeters) Quantity/Unit Unit Weight*A A’ B D’ e F G H Blower Motor

BHY04 31-1/4 (794) 43-1/4 (1099) 26 (660) 15 (381) 28-1/4 (718) 6-1/4 (159) 8-3/4 (222) 29-3/4 (756) 2 1 64BHY06 36-1/4 (921) 43-1/4 (1099) 31 (787) 10 (254) 33-1/4 (845) 7-1/2 (191) 10 (254) 34-3/4 (883) 2 1 75BHY08 43-1/4 (1099) 57-1/4 (1454) 38 (965) 17 (432) 40-1/4 (1022) 7-1/2 (191) 10 (254) 41-3/4 (1060) 2 1 84BHY10 57-1/4 (1454) 65-1/4 (1657) 52 (1321) 11 (279) 54-1/4 (1378) 7-1/2 (191) 10 (254) 55-3/4 (1416) 4 2 130

NoTeS: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Optional drip lip not required with optional extended drain pan. 3. All dimensions are +/- 1/4" (6). 4. Product specifications are subject to change without notice. 5. Drip lip recommended. 6. Threaded fittings must be field tightened and leak tested.

PHySICAL dATA, Cont’d.

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for

up to date drawings.

Page 25: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

25

PHySICAL dATA, Cont’d.

BPY - Horizontal Hi-Static Hideaway with Plenum

TOP VIEW

FRONT VIEW RIGHT SIDE VIEW

RETURNAIR

AIRRETURN

1(25)REAR MTG. HOLES

H

2(51)

DRAIN

7/8"(22) O.D.CONDENSATE

BOTTOM ACCESS

PANELCLIPRETAINERFILTER

1"(25) FILTER

1"(25) RETURNDUCTCOLLAR

1"(25) FILTER

PANELACCESSREAR

AIR VENT

1/2(13)

OPTIONAL 5/8"(16) O.D. TELL-TALEDRAIN CONNECTION, AVAILABLE ONSTANDARD AND EXTENDED DRAIN PANS

SHIPPED LOOSE

OPTIONAL DRIP LIP

OPTIONALEXTENDEDDRAIN PAN (SEE NOTE 2)

D'

CONNECTIONSSUPPLY & RETURNCHILLED/HOT WATERW/ 3/8"(10) DIA. HOLES (TYP. OF 4)

RESILIENT MOUNTING GROMMET

MTG. HOLES

1(25)

A

3(76)B2-1/4

(57)

C1-1/8(29)

1-1/2(38)

16(406)A

E3/4(19)C

AIRSUPPLY

1"(25) SUPPLY

DUCTCOLLAR

G F

7/8(22)

21-1/2(546)

22-1/2(572)

PLENUM HANGER CLIPS (SEE NOTE 4)

FILTERREMOVAL

REMOVALFILTER

13-15/16(354)

12-3/4(324)

INSULATED PLENUMJUNCTION BOX

18(457)

3 (76)

A'

(NOTE 6)

OPTIONAL REAR RETURN

3/4(19)

4(102)

3(76)

Unit Model

Dimensions - Inches (Millimeters) Quantity/Unit Unit Weight*A A’ B C D’ e F G H Blower Motor

BPY04 31-1/4 (794) 43-1/4 (1099) 26 (660) 28-1/4 (718) 15 (381) 29-3/4 (756) 6-1/4 (159) 8-3/4 (223) 30-1/4 (768) 2 1 84BPY06 36-1/4 (921) 43-1/4 (1099) 34 (787) 33-1/4 (845) 10 (254) 34-3/4 (883) 7-1/2 (190) 10 (254) 35-1/4 (895) 2 1 97BPY08 43-1/4 (1099) 57-1/4 (1454) 38 (965) 40-1/4 (1022) 17 (432) 41-3/4 (1060) 7-1/2 (190) 10 (254) 42-1/4 (1073) 2 1 110BPY10 57-1/4 (1454) 65-1/4 (1657) 52 (1321) 54-1/4 (1378) 11(279) 55-3/4 (1416) 7-1/2 (190) 10 (254) 56-1/4 (1429) 4 2 163

NoTeS: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Optional drip lip not required with optional extended drain pan. 3. All dimensions are +/- 1/4" (6). 4. Plenum hanger clip location may vary depending on unit accessories. 5. Product specifications are subject to change without notice. 6. Drip lip recommended. 7. Control box size and position may vary (consult factory). 8. Threaded fittings must be field tightened and leak tested.

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for

up to date drawings.

Page 26: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com26

Horizontal Series

BPY - Horizontal Hi-Static Hideaway with Plenum with Electric Heat

TOP VIEW

FRONT VIEW RIGHT SIDE VIEW

MAX.

CONTACTOR BOXIN TOP & BOTTOM OFELECTRICAL KNOCKOUTS

CONTROLBOX

STANDARD AND EXTENDED

ELEMENTSTRIP HEATERELECTRIC

3 (76)CLIPS (SEE NOTE 4)PLENUM HANGER

(SEE NOTE 2)DRAIN PAN

3/4(19)

RETURNAIR

AIRRETURN

INSULATED PLENUM

1(25)REAR MTG. HOLES

H

2(51)

DRAIN

7/8"(22) O.D.CONDENSATE

BOTTOM ACCESS PANEL FILTERRETAINERCLIP

1"(25) FILTER

1"(25) RETURNDUCTCOLLAR

1"(25) FILTER PANELACCESSREAR

AIR VENT

1/2(13)

CONNECTION,AVAILABLE ONTELL-TALE DRAINOPTIONAL 5/8"(16) O.D.

SHIPPED LOOSE

OPTIONAL DRIP LIP

EXTENDEDOPTIONAL

A'

D'

CONNECTIONSSUPPLY & RETURNCHILLED/HOT WATERW/ 3/8"(10) DIA. HOLES (TYP. OF 4)

RESILIENT MOUNTING GROMMET

MTG. HOLES

1(25)

A

3(76)B2-1/4

(57)

C1-1/8(29)

16(406)A

E3/4(19)

3/4(19)

AIRSUPPLY

1"(25) SUPPLY

DUCT COLLAR

G F

7/8(22)

25-1/2(648)

26-1/2(673)

FILTERREMOVAL

REMOVALFILTER

12-3/4(324)

13-15/16(354)

22(559)

DRAIN PANS

1-1/2(38)

(NOTE 6)

OPTIONAL REAR RETURN

5-3/8(137)STD.

6(152)STD.

Unit Model

Dimensions - Inches (Millimeters) Quantity/Unit Unit Weight*A A’ B C D’ e F G H Blower Motor

BPY04 31-1/4 (794) 43-1/4 (1099) 26 (660) 28-1/4 (718) 15 (381) 29-3/4 (756) 6-1/4 (159) 8-3/4 (223) 30-1/4 (768) 2 1 86BPY06 36-1/4 (921) 43-1/4 (1099) 34 (787) 33-1/4 (845) 10 (254) 34-3/4 (883) 7-1/2 (190) 10 (254) 35-1/4 (895) 2 1 99BPY08 43-1/4 (1099) 57-1/4 (1454) 38 (965) 40-1/4 (1022) 17 (432) 41-3/4 (1060) 7-1/2 (190) 10 (254) 42-1/4 (1073) 2 1 112BPY10 57-1/4 (1454) 65-1/4 (1657) 52 (1321) 54-1/4 (1378) 11 (279) 55-3/4 (1416) 7-1/2 (190) 10 (254) 56-1/4 (1429) 4 2 165

NoTeS: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Optional drip lip not required with optional extended drain pan. 3. All dimensions are +/- 1/4" (6). 4. Plenum hanger clip location may vary depending on unit accessories. 5. Product specifications are subject to change without notice. 6. Drip lip recommended. 7. Control box size and position may vary (consult factory). 8. Threaded fittings must be field tightened and leak tested.

PHySICAL dATA, Cont’d.

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IeC web site for

up to date drawings.

Page 27: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

27

STANdArd FEATurES & OPTIONS

Features And options StandardFactory

Installed option

Field Installed option

Factory Special Quote

Air Flow ArrangementFront Supply/Rear Return (CHY, BHY) X – – –Front Supply/Rear or Bottom Return (CPY, BPY, CBY, CXB) X (Bottom) X (Rear) – –Coils2 Rows 2-Pipe (CHY, CPY, CBY, CXB) – X – –3 Rows 2-Pipe (CHY, BHY, CPY, BPY, CBY, CXB) X – – –4 Rows 2-Pipe (CHY, BHY, CPY, BPY, CBY, CXB) – X – –3/1, 3/2, 4/1 Rows 4-Pipe (CHY, BHY, CPY, BPY, CBY, CXB) – X – –Manual Air Vent X – – –Automatic Air Vent – X – –DX Coils – X – –Steam Coils – X – XConnectionRight or Left (Same End) X – – –Right or Left (Opposite End) – X – –Drain PanGalvanized Internally Coated with 2-part closed Cell Foam X – – –Stainless Steel Externally Coated – X – –Drip Lip (recommended with motorized valves) – – X –Extended Drain Pans (CHY, CPY, BHY, BPY) – X – –Secondary Drain Connection – X – vFin MaterialAluminum with Galvanized End Sheets X – – –Copper with Stainless End Sheets & Bottom Coil Baffle – X – XNichrome Wire Strip electric Heater (Total and Auxiliary) – X – –Filters1" Throwaway non-woven synthetic filter X – – –1" Permanent – X – –1" Pleated MERV 8 – X – –Insulation1/2" Standard Fiberglass X – – –1/2" Premium IAQ Fiberglass – X – X1/2" Foil Face – X – –1/4" Closed Cell – X – –Motor TypePSC Motors with Quick Connect Plug X – – –Motor Voltage120/1/60 3-Speed X – – –208/230/277/1/60 3-Speed (Optional Voltage) – X – –Supply/Return Air GrillesLouvered Stamped Supply Grille (CXB) X – – –

Double Deflection, Aluminum Finish Supply Grille – X (CXB X (CHY, CPY, CBY)

X (CHY, CPY, CBY)

Double Deflection, Integral Supply Grille - painted – X (CXB) – –Stamped Return Grille (CBY, CXB) X – – –

Hinged Bar-Type, Aluminum-finish Return Grille with Throwaway Filter - F.O. – – X (CHY, CPY, CBY)

X (CHY, CPY, CBY)

ControlsService Switch with Lockout Tabs – X – –Single Point Power Connection – X – –Incoming Power Fusing – X – –24 V Controls – X – –Condensate Overflow Switch – X – –3-Speed Switch X – X –Thermostats – – X –Custom Control (DDC) – X – X

Page 28: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com28

Horizontal SeriesSTANdArd FEATurES & OPTIONS, Cont’d.

As detailed in the table on page 29, we offer a control

for most of the customer needs. Additional controls and

devices are available to meet even the most demanding

operating logic.

Three-speed Fan ControlAll of our basic control schemes utilize a 2- or 3-speed

switch to modulate the cooling output, to maximize the

percentage of latent heat removal, and to further minimize

the sound level when maximum cooling or heating

performance is not required.

Low Voltage Control (24 V)A low voltage control is available with all of our control

schemes.

Condensate High Level SwitchThis switch shuts down the unit when the water level in the

drain pan reaches an unsafe level. Building code changes in

much of the country now require this type of device.

Service SwitchesWe offer concealed service switches for use by maintenance

and service personnel to shut off the power while working

on the unit.

FusingWe offer incoming power fusing for all units as well as

blower motor and control sub-fusing for units that use

electric heat. The blower motor and control sub-fusing

(single power source wiring) is required when single source

power with electric heat is specified.

Control Packages

Horizontal Wall Series 155

Wall Series 4039 Vertical Wall Series 155

24 V Programmable and Non-Programmable

Digital Series

Page 29: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

29

STANdArd FEATurES & OPTIONS, Cont’d.

Control Package Applications

Unit Type Control option System Type Changeover

TypeWall Series

4039

Vertical and Horizontal Wall

Series155

24 V Programmable and Non-Programmable

Digital Series– Manual Fan Manual1 None – – –

2-PipeValve Cycle*

Heat Only None

Cool Only None

Heat/CoolManual –

Automatic

Heat/Cool with Auxiliary Electric Heat

Manual –Automatic

Cool with Total Electric Heat

Manual –Automatic

4-Pipe Heat/CoolManual –

Automatic

NoTe: 1. Fan switch only; no thermostat.

Thermostat Features

All listed controls include fan switching.Control Type1

Wall Series 4039 Vertical and Horizontal Wall Series 155 24 V Digital Series

24 V, 115 V, 208 V, 240 V, 277 V 24 V onlyRemote Wall Mounted

Manual Fan Switch Operation

Auto Fan Speed Control N/A N/A

Continuous 3-Speed Fan

Cycling Fan N/A N/A

O.A. Damper Signal N/A

Remote Temperature Sensor N/A Opt OptAdjustable Operating Range Kit

Touch Pad/Digital Display N/A N/A

Local Temperature Set-Back N/A N/A

Water Temperature Purge Cycle N/A N/A

Pipe Sensor N/A N/A

NoTeS: 1. Control packages with valve cycle control are continuous fan operation only. 2. All wall-mount control packages are shipped loose for field installation. (Boxes, tile rings, plaster rings, etc. are not provided.) 3. Aquastats are included in control packages, as required.

Control Options• 24 V control packages• Unit-mounted fan switches (Special Quote)• Single power source wiring (motor/control fusing)• Incoming power fusing• Service switches

• Minimum room temperature thermostats (Special Quote)• Low voltage remote shutdown relays (Special Quote)• Fan and valve cycle applications (Special Quote)• Thermostats available with large letter print for handicap

applications (Special Quote)• DX coil applications

Page 30: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com30

Horizontal SeriesSTANdArd FEATurES & OPTIONS, Cont’d.

Supply Air Grilles

Unit Size Nominal CFMRecommended

Grille Size - Inches (Millimeters)

02 200 16" x 6" (406 x 152)

03 300 20" x 6" (508 x 152)

04 400 26" x 6" (660 x 152)

06 600 30" x 6" (762 x 152)

08 800 38" x 6" (965 x 152)

10 1000 52" x 6" (1320 x 152)

12 1200 60" x 6" (1524 x 152)

NoTeS: 1. Refer to Physical Data, pages 13 through 26 for actual unit supply air opening dimensions.

2. Field-furnished duct transitions may be required.

Return Air Filter Grilles

Unit Size Nominal CFMRecommended

Grille Size - Inches (Millimeters)

02 200 24" x 10" (610 x 254)

03 300 28" x 10" (711 x 254)

04 400 32" x 10" (813 x 254)

06 600 42" x 10" (1067 x 254)

08 800 42" x 10" (1067 x 254)

10 1000 54" x 10" (1372 x 254)

12 1200 64" x 10" (1626 x 254)

NoTeS: 1. Refer to Physical Data, pages 13 through 26 for actual unit return air opening dimensions.

2. Field-furnished duct transitions may be required.

optional Double-deflection, Integral Supply Grille Painted to Match Color of Unit

optional Double Deflection, Aluminum-finish Supply Grille (optional special ship separate for models CHY, CPY, CBY, BHY,

and BPY. Consult factory for details.)optional Hinged, Bar-type, Aluminum-finish Return Grille

with Throwaway Filter (optional special ship separate for models CHY, CPY, CBY, BHY,

and BPY. Consult factory for details.)

Page 31: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

31

STANdArd FEATurES & OPTIONS, Cont’d.

Nominal Filter SizesAll cabinet model units (except CH and BH) have non-woven synthetic throwaway filters furnished as standard equipment.

Cleanable and pleated filters are optional.

Unit Size

Nominal one-Inch Filter Size - Inches (Millimeters)

CHY (Note 1) CPY

CBY Bottom Return

Stamped

CBY Rear Return

Stamped

CXB Bottom Return

Stamped

CXB Rear Return

Stamped

CXB Rear Return

Ducted

02 10" x 24"(254 x 610)

10" x 18" (254 x 457)

10" x 28"(254 x 711)

7" x 21"(178 x 533)

10" x 23-1/2"(254 x 597)

8" x 23-1/2"(203 x 597)

8" x 23-1/2"(203 x 597)

03 10" x 28"(254 x 711)

10" x 22" (254 x 559)

10" x 28"(254 x 711)

7" x 21"(178 x 533)

10" x 28"(254 x 711)

8" x 28"(203 x 711)

8" x 28"(203 x 711)

04 10" x 32"(254 x 813)

10" x 28" (254 x 711)

10" x 33"(254 x 838)

7" x 27"(178 x 533)

10" x 32-1/2"(254 x 826)

8" x 32-1/2"(203 x 826)

8" x 32-1/2" (203 x 826)

06 10" x 42"(254 x 1067)

10" x 33" (254 x 838)

10" x 45"(254 x 1143)

7" x 38"(178 x 965)

10" x 37"(254 x 940)

8" x 37"(203 x 940)

8" x 37"(203 x 940)

08 10" x 42"(254 x 1067)

10" x 40" (254 x 1016)

10" x 45"(254 x 1626)

7" x 38"(178 x 965)

10" x 41"(254 x 1041)

8" x 41"(203 x 1041)

8" x 41"(203 x 1041)

10 10" x 54"(254 x 1372)

10" x 54" (254 x 1372)

10" x 62"(254 x 1575)

7" x 52"(178 x 1321)

10" x 54-1/2"(254 x 1384)

8" x 54-1/2"(203 x 1384)

8" x 54-1/2"(203 x 1384)

12 10" x 64" (254 x 1626)

10" x 62" (254 x 1575)

10" x 62"(254 x 1575)

7" x 52"(178 x 1321)

10" x 63"(254 x 1600)

8" x 63" (203 x 1600)

8" x 63"(203 x 1600)

Unit Size

Nominal one-Inch Filter Size - Inches (Millimeters)

BHY(Note 1)

BPYBottom Return

with Heat

BPYBottom Return without Heat

BPYRear Return

with Heat

BPY Bottom Return without Heat

04 10" x 32"(254 x 813)

16-3/4" x 28"(425 x 711)

12-3/4" x 28"(324 x 711)

12-3/4" x 28"(324 x 711)

12-3/4" x 28"(324 x 711)

06 10" x 42"(254 x 1067)

16-3/4" x 33"(425 x 838)

12-3/4" x 33"(324 x 838)

12-3/4" x 33"(324 x 838)

12-3/4" x 33"(324 x 838)

08 10" x 42"(254 x 1067)

16-3/4" x 40"(425 x 1016)

12-3/4" x 40"(324 x 1016)

12-3/4" x 40"(324 x 1016)

12-3/4" x 40"(324 x 1016)

10 10" x 54"(254 x 1372)

16-3/4" x 54"(425 x 1372)

12-3/4" x 54"(324 x 1372)

12-3/4" x 54"(324 x 1372)

12-3/4" x 54"(324 x 1372)

NoTeS: 1. Filter sizes for the CH and BH models are recommended filter sizes only. No filter is factory provided with these models. 2. Sizes shown are nominal ordering sizes.

Page 32: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com32

Horizontal SeriesPIPING PACKAGES (TyPICAL)

Two-way Motorized Control ValveIn a two-way motorized control valve package, the motor

drives the valve open, and a spring returns the valve to a

normally closed position. No water flows with the unit off.

The standard supply connection from the coil will accept

a swaged copper fitting for field brazing. As an option, this

connection may be factory furnished with a union. When a

swage is necessary, it becomes part of the valve package.

The isolation, or ball, valve in the return piping is shipped

loose for field installation.

(Ships Separate)

2-way ValveCoil

Air Vent

SwageS

R

S

R BallValve

BallValve

Two-way Motorized Control Valve with ChangeoverIn a two-way motorized changeover control valve package,

the motor drives the valve open, and a spring returns the

valve to a normally closed position. No water flows through

the coil with the unit off. The aquastat bypass line allows

a small amount of water to flow from the supply to the

return piping when the control valve is closed. The strap-

on aquastat senses whether the flowing water is cold or

hot and switches a contact closed to provide automatic

summer/winter changeover (ACO) for the system.

S

R

S

Swage

2-way ValveAquastat BleedBypass Line

A

Aquastat

R

Coil

Air Vent

Swage

BallValve

BallValve

Three-way Motorized Control ValveIn a three-way motorized control valve package, a diverting

valve controls water flow to the coil. When the unit is off,

water bypasses the coil and flows directly to the system

return. A balancing valve may be specified in the bypass line

to permit equal flow balancing.

OptionalBalance Valve

S

Swage

3-way Valve

R

Coil

Air Vent

SwageA

Aquastat

S

R BallValve

BallValve

NoTeS: 1. Please note that project specifications for system pressure, pressure drop limitations and flow rate should be checked prior to selecting specific components or the valve package size.

2. The supply and return piping connections of the factory-provided valve package are either swaged for field brazing (standard) or union fitted (optional) for connection to the coil.

3. Consult IEC’s Valve Packages and Piping Components manual or your local representative for detailed piping and valve application information. Factory-provided valve packages are assembled, brazed, wired electrically and dry-fit to the coil connections before shipping. Field brazing to the coil completes the installation. Some applications dictate shipping isolation valves loose.

Page 33: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

33

MECHANICAL SPECIFICATIONS

GENERAL DESCRIPTION – HORIZONTAL FAN COIL UNITSCHY – Horizontal Hideaway CBY – Horizontal Telescoping Hideaway CPY – Horizontal Hideaway with Plenum CXB – Horizontal Cabinet BHY – Horizontal Hi-Static Hideaway BPY – Horizontal Hi-Static Hideaway with Plenum

PART 11.1 SUMMARY

This section includes fan coil units and accessories.

1.2 SYSTEM DESCRIPTION

Horizontal Fan Coil Units, 2-pipe, 4-pipe, or 2-pipe with electric heat, concealed or exposed cabinets that are horizontally mounted.

1.3 QUALITY ASSURANCE

Coils shall be tested in accordance with AHRI Standard 440-2008. Each coil shall be factory tested for leakage at 300 psig air pressure with coil submerged in water. Insulation and adhesive shall meet NFPA-90A requirements for flame spread and smoke generation.

Base or “standard” units shall be ETL certified.

1.4 DELIVERY, STORAGE AND HANDLING

Unit shall be handled and stored in accordance with the manufacturer’s instructions.

PART 2 – PRODUCTS2.1 MANUFACTURER

A. Basis of design shall be fan coils by International Environment Corporation.

2.2 CONFIGURATION

A. General:

Factory assembled horizontal fan coil units complete with fan, motor, drain pan, and all required wiring, piping and controls.

B. CHY, BHY Horizontal Hideaway Units:

1. Cabinet shall be made of heavy gauge galvanized steel.

2. The interior surfaces shall be lined with 1/2" thick standard fiberglass (1/2" thick Premium IAQ fiberglass, 1/2" foil face, or 1/4" closed cell) insulation.

3. Units shall be supplied with a ducted collar for supply duct connection.

4. Units shall have a galvanized (or stainless steel) drain pan extending the entire width of the coil (with second drain con nection).

5. Galvanized drain pans shall be internally coated with 2-part closed cell foam insulation.

C. CPY, BPY Horizontal Hideaway with Plenum Units:

1. Units shall be constructed of heavy gauge galvanized steel.

2. The interior surfaces shall be lined with 1/2" thick standard fiberglass (1/2" thick Premium IAQ fiberglass, 1/2" foil face, or 1/4" closed cell) insulation.

3. A heavy gauge plenum shall enclose the blower/motor assembly with bottom or rear return.

4. Units shall be supplied with a ducted collar for supply duct connection.

5. Units shall have a galvanized (or stainless steel) drain pan extending the entire width of the coil (with second drain con nection).

6. Galvanized drain pans shall be internally coated with a 2-part closed cell foam insulation.

Page 34: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com34

Horizontal SeriesMECHANICAL SPECIFICATIONS, Cont’d.

7. Units shall have non-woven synthetic throwaway (permanent or pleated) filters.

D. CXB Horizontal Cabinet Units:

1. Units shall be constructed of heavy gauge galvanized steel.

2. The interior surfaces shall be lined with 1/2" thick standard fiberglass (1/2" thick Premium IAQ fiberglass, 1/2" foil face, or 1/4" closed cell) insulation.

3. Cabinet shall be painted with an Arctic White powder-coat finish.

4. The unit shall have a stamped (double deflection, aluminum finish or steel construction factory installed and painted to match cabinet) discharge grille.

5. The unit shall have removable bottom access panel with stamped return air grille, filter rack, and non-woven synthetic throwaway (permanent or pleated) filter or optional ducted rear return cabinet with a solid bottom access panel.

6. Panel shall be fastened with tamper proof quarter-turn fasteners.

7. Units shall have a galvanized (or stainless steel) drain pan extending the entire width of the coil (with second drain con nection).

8. Galvanized drain pans shall be internally coated with a 2-part closed cell foam insulation.

E. CBY Horizontal Telescoping Hideaway Units:

1. Units shall be constructed of heavy gauge galvanized steel.

2. The interior surfaces shall be lined with 1/2" thick standard fiberglass (1/2" thick Premium

IAQ fiberglass, 1/2" foil face, or 1/4" closed cell) insulation.

3. Unit shall have an adjustable height, hinged return air ceiling panel with non-woven synthetic throwaway, (permanent, or pleated) filter.

4. Panel shall be painted with an Arctic White powder-coat finish.

5. Units shall have a galvanized (or stainless steel) drain pan extending the entire width of the coil (with second drain con nection).

6. Galvanized drain pans shall be externally coated with a 2-part closed cell foam insulation.

2.3 CERTIFICATION

A. Safety:

Units shall be listed by Electronics Testing Laboratories, Inc. with the ETL listing indicating the units comply with the minimum requirements of the U.S. and Canadian national product safety standard, UL 1995/CSA C22.2 No. 236.

B. Capacities:

Coil capacities are tested in accordance with AHRI Standard 440-2008.

2.3.1 MATERIALS

A. Coils:

All coils shall have 1/2" copper tubes, manual (or automatic) air vents, and aluminum fins, 10 fins per inch spacing. Coil fins shall be mechanically bonded to copper tubes. 0.500" O.D. copper tubes must comply with ASTM B-75. Fin thickness shall be 0.0045" and tube thickness shall be 0.016". All coils shall be leak tested with air at 300 psig under water.

1. For installation in a 2-pipe system, unit shall be equipped with:

a. 3-row (or 4-row) coil as shown on equipment drawings

b. 2 ball valves

c. 1 motorized control valve

Page 35: International Fan Coil Unit I100-90002102[1]

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

35

MECHANICAL SPECIFICATIONS, Cont’d.

2. For installation in a 4-pipe system, unit shall be equipped with:

a. 3/1, 3/2 or 4/1 row-split coil, as shown on equipment drawings

b. 4 ball valves

c. 2 motorized control valves

B. Fans:

1. Fans shall be direct-drive, double-width fan wheels with forward-curved blades.

2. Blower wheels shall be statically and dynamically balanced.

3. Scrolls and fan wheels shall be constructed of galvanized steel.

4. Shall be easily removable.

C. Fan Speed and Temperature Control:

3 (high, medium, low) speed control, (off, on, auto), (wall or unit) (auto or manual) thermostat.

D. Motors:

1. Motors shall be 3-speed, single phase, 60 Hz permanent split capacitor type for 115 V (208 V, 230 V, or 277 V) permanently lubricated, with sleeve bearings.

2. Motors shall be connected with quick connect electrical plugs.

3. Motors shall have thermal overload protection with automatic reset.

E. Controls and Safeties:

1. Controls:

Unit shall be furnished with a 3-speed, 4-position fan switch on a wall plate for field installation.

2. Safeties:

Unit fan motor shall be equipped with integral motor protection.

F. Operating Characteristics:

1. A 2-pipe system shall be capable of providing heating or cooling as determined by the operating mode of the central water supply system.

2. A 4-pipe system shall be capable of providing heating and cooling on demand.

G. Electrical Requirements:

1. Standard unit shall operate on 115 V (208 V, 230 V or 277 V), single phase, 60 Hz electrical power, and all exposed wiring shall be in flexible conduit.

H. Option and Accessories:

1. Unit shall be equipped with nichrome wire strip electric heaters for total or auxiliary electric heat as specified on the equipment schedule.

a. Heaters shall be protected by an automatic reset safety cutout switch and a fusible link.

b. Heater capacity shall be as specified on the equipment schedule.

c. Heaters shall be single phase, 120 V (208 V, 240 V or 277 V) volts as specified on the equipment schedule.

d. For total electric heat, unit controls shall include a sequenced heating and cooling thermostat in lieu of the heating/cooling thermostat and automatic changeover device.

e. For auxiliary electric heat, unit controls shall include an aquastat to verify system mode.

f. A junction box and fuse shall be factory furnished and installed to protect the motor and control circuit when electric heaters are installed.

2. Service switch shall be factory installed.

3. Units shall be equipped with 24 V controls.

4. Units shall be equipped with high level condensate switch.

5. A hinged, bar type aluminum return air grille with filter holder shall be furnished for field installation.

6. Discharge air grille with double deflection, aluminum construction shall be furnished for field installation as shown on equipment schedule. Aluminum grilles shall have a natural anodized finish.

Page 36: International Fan Coil Unit I100-90002102[1]

IEC Catalog Part #: I100-90002102

CA-020 Revision 3

©2010 International Environmental Corporation (IEC)

IEC is a subsidiary of LSB Industries, Inc.

NYSE symbol LXU; www.lsb-okc.com

P.O. Box 2598Oklahoma City, OK 73101-2598

p: 405.605.5000f: 405.605.5001

www.iec-okc.com

The USGBC Member logo is a trademark owned by the U.S. Green Building Council and is used by permission. The logo signifies only that IEC is a USGBC member. USGBC does not review, certify, or endorse the products or services offered by its members.

IEC is dedicated to the environment and for its part, IEC has elected to use recycled materials whenever possible for printed sales materials.