Intelligent Line Monitoring and Disturbance Management Ryan Kelso/Justin Stroupe July 24, 2018

Transcript of Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for...

Page 1: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

Intelligent Line Monitoring and Disturbance Management Ryan Kelso/Justin Stroupe July 24, 2018

Page 2: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

New Braunfels Utilities Overview

¾41,373 Electric Meters ¾99.5% AMI (Itron Network Solutions) ¾160 sq. mi. Electric Territory ¾619 miles Primary OH ¾285 miles Primary UG ¾40 Distribution Feeders ¾20 miles of 138kV transmission ¾24/7 Control Center Operations

2

Page 3: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

The Desire

¾Enhance visibility of the distribution system ¾Improve system resiliency ¾Reduce outage duration - SAIDI ¾Lower outage frequency - SAIFI

¾Leverage existing AMI communications network to connect grid-edge devices

3

Page 4: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

Existing Tools

¾Fault Indicators (flashing lights) ¾Milsoft Outage Management System ¾Itron Network Solutions AMI ¾Intelligent substation relays

4

Page 5: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

The Solution: Sentient

$100+ million invested in developing and delivering

sensing technology

Proven technology ≈ 60,000 intelligent sensors shipped. Serving 8 of top 10 largest utilities in North America

Highest fidelity oscillography on the

market (>7,800 samples/second)

Multiple communications options

5

Page 6: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

MM3: Sentient Core Sensing Solution Overhead Feeder Monitoring System

¾ Continuously sampling, 130 Sample/cycle Current and E-field capture

¾ GPS for location and precision timing

¾ MM3 supports multiple communications options: Itron, L+G, and LTE technology

¾ Patented power harvesting technology requires no servicing or maintenance for the life of the product

6

Page 7: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

MM3 Intelligent Sensor

¾ Easy installation ¾ Local annunciation:

daylight-visible LED ¾ Embedded fault detection

algorithms: ¾Fixed Trip, Auto-range, Rate

of Change (di/dT) ¾ Inrush restraint, Loss Of

Source ¾ Event Details: ¾Fault magnitude, related

hi-res waveform

7

Page 8: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

Ample Software Foundation for Sentient’s Grid Analytics System (GAS)

¾ Complete sensor management ¾ Multiple DNP masters – directly connect to devices ¾ Analytics Software: ¾ Interval Logging - Current and Conductor Temperature per

phase ¾ Fault Location along the feeder and on what phase ¾ Phase Identification ¾ E-Field – monitors reverse flow of current ¾ Disturbance Management (Momentary/Incidents) –

Waveforms ¾ Easy to integrate ¾ APIs for historian integration ¾ Role level security

8

Page 9: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

Pilot Approach: 9 Sensors

¾Deployed 3 sets of sensors on 2 distribution feeders

¾Deployed at 2 substation feeder exits and 1 feeder midpoint

¾Developed ROI measurement ¾Value of Lost Load +

Operational Cost per SAIDI Minute

¾ Focused on disturbance management

9

Page 10: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

Disturbance Management what is a disturbance?

¾ A disturbance is a small and momentary change in current/e-field waveforms.

¾ Characteristics of a disturbance are: ¾ Disturbances usually do not cause a

sustained power interrupt ¾ Magnitude is usually 1-5 times normal

current (faults can cause > 15 times increase in current)

¾ Duration usually lasts less than 5 cycles (5 – 80 milliseconds)

¾ Distortions: 1st to 50 harmonic content (Sentient can detect up to 31st harmonic in underground solution)

10

Page 11: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

Pilot Results: Disturbance Management Trees grow into lines Control Center sees elevated

disturbance counts

Electric Ops finds tree

making contact with

B&C phase, trims

trees to prevent

outage, disturbances

return to normal

Avoided SAIDI: 2.66 min.

Avoided Cost: $16,770

11

Page 12: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

Change in workflow

Operator

receives fault

data from

Sensors

Runs fault

location tool

in OMS

Provides

operations

with

predicted

location of

fault

Operations

makes repairs

and reports

back results

for ROI

Calculation

Operator sees

fault

If fault data is

available

provide

prediction of

fault

Operations

will make

decision on

whether to

run out circuit

No report

usually

provided

12

Page 13: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

Calculating ROI

Avoided Costs(ROI) =

Value of Lost Load (VOLL) +

Operational Cost Per SAIDI Minute(OCPSM)

13

Page 14: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

Pilot Results

¾Delivered 2.66 SAIDI minute reduction through disturbance management ¾$16,770 in VOLL+OCPSM savings ¾SAIFI reduction

¾Communication through AMI network worked as designed

14

Page 15: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

Phase 2: 60 Sensors

¾Deployed 20 sets of sensors on 18 distribution feeders ¾Deployed on feeders with old

relays that did not report fault amplitude ¾Positioned at midpoint of circuit

15

Page 16: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

Benefits: Phase Identification

¾Identifies phase miss-match and reports detected phase

16

Page 17: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

Benefits: Phase Balancing

¾ Allow decision making based on facts not estimates

¾ Planning, load flow, dynamic loading application data

17

Page 18: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

Benefits: Disturbance Monitoring

18

Page 19: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

Benefits: Fault Detection ¾ Enables waveform capture, storage and analysis ¾ Precisely determine boundaries of disturbance using patent-pending algorithm ¾ Supports automatic or manual retrieval of waveforms ¾ Foundational component for disturbance analysis and event categorization ¾ Capture momentary and transient events for further analysis ¾ Instrument-class, sampling rate, “Oscilloscope on the wire”. True 130 samples/cycle.

19

Page 20: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

Benefits: Fault Locating 20

Page 21: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

Benefits: Temperature Monitoring

21

Page 22: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

Success

Predicted Location Actual Location

Fault Waveform

22

Page 23: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

Success

Faulted Element:

Broken Insulator

Cause: Lightning

Avoided SAIDI: 2.66 min.

Avoided Cost: $28,329.81

23

Page 24: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

Success

Issue Fixed on 7/20 – Disturbance counts fall off

24

Page 25: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

Phase 3: 66 Sensors

¾Currently deploying 22 sets of sensors ¾Deploying at feeder substation

exits to maximize coverage for disturbance management

25

Page 26: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

Results 26

Page 27: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

Results

27

Page 28: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

Results

28

Page 29: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

Results

¾Avoided SAIDI: 5.32 Minutes ¾Avoided Costs: $45,100.30 ¾Avoided Interruptions: 1,760 ¾SAIFI Reduction: 0.04 ¾Improved System Resiliency ¾Improved Customer Experience

29

Page 30: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

Lessons Learned

¾Deployment at substation feeder exit yields maximum disturbance management coverage ¾Get it in the hands of System

Operators early ¾Develop metrics, track and brag on

success – resulted in increased buy-in

30

Page 31: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

Future Plans

Continue deployment of MM3

Q3 2018: Pilot ZM1 “Low

Amp” Line Monitor

Q4 2018: Pilot UM3+ UG

Line Monitor

Q4 2018: Launch NBU

UAV Program

31

Page 32: Intelligent Line Monitoring and Disturbance Management€¦ · Ample Software Foundation for Sentient’s Grid Analytics System (GAS) ¾Complete sensor management ¾Multiple DNP masters

Questions? 32