3. Level Measurements
-
7/30/2019 Instrumentation Basics -03- Level Measurement
3/63
3-Level Measurement
Very simple systems employ external sight glasses or tubes to viewthe height of the fluid.
Others utilize floats connected to variable potentiometers or
rheostats that will change the resistance according to the amount of
motion of the float.
This signal is then inputted to transmitters that send a signal to aninstrument calibrated to read out the height or volume.
So, we have
Sight-type Instruments
Pressure-type Instruments
Electrical-type Instruments
Sonic-type Instruments
Radiation-type Instruments
-
7/30/2019 Instrumentation Basics -03- Level Measurement
4/63
Sight-type Instruments
Glass Gauges The gauges are made of glass, plastic, or acombination of the two materials must be able to withstand the
pressure in the vessel.
-
7/30/2019 Instrumentation Basics -03- Level Measurement
5/63
Sight-type Instruments
-
7/30/2019 Instrumentation Basics -03- Level Measurement
6/63
Sight-type Instruments
The pressure that the liquid exerts in the tank forces the liquid
in the sight glass to rise to the same level as the liquid in thetank.
For the pressurized tank, the upper end of the tube is
connected to the tank.
This creates an equilibrium pressure in both ends of the tube,and the liquid in the tube rises to the same level as the liquid
in the vessel.
Pressure at the base of a vessel containing liquid is directly
proportional to the height of the liquid in the vessel.
P = g H
The level of liquid inside a tank can be determined from the
pressure reading if the density of the liquid is constant.
-
7/30/2019 Instrumentation Basics -03- Level Measurement
7/63
Sight-type Instruments
There are two basic types of flat sight gauges: reflex andtransparent.
The reflex-type gauge produces a dark area where liquid is
present and a light area where vapor is present.
The reflex type gauge is normally chosen for liquids thatare colorless, clear, and nonviscous.
The transparent gauge is generally used when the liquid is
colored, viscous, and corrosive.
Sight glass gauges are installed with manual shutoff valvesat both ends so maintenance can be performed.
-
7/30/2019 Instrumentation Basics -03- Level Measurement
8/63
Sight-type Instruments
-
7/30/2019 Instrumentation Basics -03- Level Measurement
9/63
Magnetic Level Gauges
An external float chamber
connected to the tank.
The float has a magnetic
property that makes the
indicator goes up and downon a scale according to the
level in the tank.
-
7/30/2019 Instrumentation Basics -03- Level Measurement
10/63
Tape Float
A tape is connected to a float on one end and to a counterweight
on the other to keep the tape under constant tension.
The float motion makes the counterweight ride up and down a
direct-reading gauge board.
-
7/30/2019 Instrumentation Basics -03- Level Measurement
11/63
Displacers Displacer level gauges operate on Archimedes principle.
A body fully or partially immersed in a fluid is buoyed up by aforce equal to the weight of the fluid displaced.
By measuring the buoyancy force produced by a displacer, youcan determine a level value.
Displacer may used as a level transmitter for single liquid (LT), or
differential level transmitter for interface applications (LDT). For empty tank (or filled with a light liquid), there is no (or
minimum) buoyancy force Maximum weight of the displacer.
For filled tank ( or filled with heavy liquid), maximum buoyancyforce generated on the displacer Minimum weight of the
displacer.
The displacer may be top mounted inside the tank or chamberedunit.
-
7/30/2019 Instrumentation Basics -03- Level Measurement
12/63
Displacers
-
7/30/2019 Instrumentation Basics -03- Level Measurement
13/63
Displacers Installation
-
7/30/2019 Instrumentation Basics -03- Level Measurement
14/63
Displacers (LT)
-
7/30/2019 Instrumentation Basics -03- Level Measurement
15/63
Displacers (LDT)
-
7/30/2019 Instrumentation Basics -03- Level Measurement
16/63
Pressure-type Instruments
The pressure at the base of a vessel containing liquid is
directly proportional to the height of the liquid in the
vessel.
As the level in the vessel rises, the pressure exerted by
the liquid at the base of the vessel will increase linearly.
Differential Pressure (DP) capsules are the most
commonly used devices to measure the pressure at the
base of a tank.
When a DP transmitter is used for the purpose of
measuring a level, it will be called a level transmitter.
-
7/30/2019 Instrumentation Basics -03- Level Measurement
17/63
DP Level Transmitter
When using pressure or differential Pressure
transmitters to measure tank liquid level, determining
the liquid density is important to accurately calculate the
level for a given liquid head pressure.
Tanks may be open (vented), or they may be closed
(pressurized).
With closed tanks that may have a pressure above the
liquid that is different from atmospheric pressure, a dry
leg or wet leg system may be used to port the top-of-
tank pressure to the opposite side of a differentialpressure transmitter that is connected to the tank to
measure level.
-
7/30/2019 Instrumentation Basics -03- Level Measurement
18/63
DP Level Transmitter
If it is a dry leg, then density of vapor or noncondensing
gas in dry leg is calculated and used to correct levelmeasurement for vapor density changes.
If it is a wet leg, density of liquid in wet leg is calculated
and used to correct the liquid level measurement.
Transmitter can be mounted at minimum level, or below
minimum level.
If transmitter is mounted below minimum level, the leg to
transmitter from the lower tank connection is assumed to
have liquid in it, and its density calculated to correct theliquid level measurement.
-
7/30/2019 Instrumentation Basics -03- Level Measurement
19/63
Open Tank (Vented) or Closed Tank With Dry Leg
Assume dP cell below bottom tap
we make zero suppressioncalculation.
The span points for the dP cell
are calculated as follows
DP0% = d g
DP100% = (Lmax+d) g The DP transmitter must be
calibrated from DP0% to DP100%
Any condensation in the leg will
create an error in the level
measurement.
We can prevent condensation in most cases by doing steamtracing of the reference leg.
-
7/30/2019 Instrumentation Basics -03- Level Measurement
20/63
Closed Tank With Wet Leg
Assume the leg filled with liquid that ( w > ) to prevent theserviced liquid goes to the transmitter cell.
Assume dP cell below bottom tap
we make zero elevation calculation.
The span points for the dP
cell are calculated as follows
DP0%
= d g h w
g
DP100% = (Lmax+ d) g(hwg)
Any change in the height or
density of the wet leg fluid
influences the accuracy of the
level measurement.
-
7/30/2019 Instrumentation Basics -03- Level Measurement
21/63
Bubbler Level Measurement System
Used If the process liquid contains suspended solids or is chemically
corrosive or radioactive. It is desirable to prevent it from coming into direct contact with the
level transmitter.
A bubbler tube is immersed to the bottom of the vessel in which the
liquid level is to be measured.
A gas (called purge gas) is allowed to pass through the bubbler
tube.
Consider that the tank is empty, so, the gas will escape freely at the
end of the tube and therefore the gas pressure inside the bubbler
tube (called back pressure) will be at atmospheric pressure. As the liquid level inside the tank increases, pressure exerted by the
liquid at the base of the tank (and at the opening of the bubbler tube)
increases.
-
7/30/2019 Instrumentation Basics -03- Level Measurement
22/63
Bubbler Level Measurement System
As a result, the gas pressure in the bubbler tube will continue to
increase until it just balances the pressure of the liquid & anyexcess supply pressure will escape as bubbles through the liquid.
A level transmitter (DP cell) used to monitor this backpressure.
The bubbler tube is connected to the high-pressure side of the
transmitter, while the low pressure side is vented to atmosphere.
The output of the transmitter will be proportional to the tank level.
Note that bubbling action has to be continuous or the measurement
signal will not be accurate.
The purge supply pressure should be at least 10 psi higher than the
highest hydrostatic pressure the process will encounter. You should keep the purge rate small so no significant pressure
drop occurs in the dip tube.
The purge medium is air or nitrogen, although you can use liquids.
-
7/30/2019 Instrumentation Basics -03- Level Measurement
23/63
Bubbler Level Measurement System
-
7/30/2019 Instrumentation Basics -03- Level Measurement
24/63
Diaphragm Level Detectors
Diaphragm detectors operate by the simple principle of
detecting the pressure that the process material exerts
against the diaphragm.
The diaphragm box instrument consists of an air-filled
diaphragm that is connected to a pressure detector viaair tubing.
As the level rises above the diaphragm, the liquid head
pressure compresses the captive air inside.
A differential pressure element senses the air pressure,which is displayed as level.
-
7/30/2019 Instrumentation Basics -03- Level Measurement
25/63
Diaphragm Level Detectors
-
7/30/2019 Instrumentation Basics -03- Level Measurement
26/63
Servo Tank Gauge Its level measuring principle is based on the detection of
variations in the weight of a displacer suspended in theprocess fluid.
The displacer on level is partly immersed in the liquid.
The apparent weight is the weight of the displacer minusthe weight of the displaced product.
The hart of the servo gauge is an accurate forcetransducer that continuously measures the apparentweight of the displacer.
A weight corresponding with the apparent weight of thedisplacer on level is programmed by software settings.
In equilibrium condition, the weight of the partly immerseddisplacer balances against the weight programmed to bemeasured by the force transducer.
-
7/30/2019 Instrumentation Basics -03- Level Measurement
27/63
Servo Tank Gauge
-
7/30/2019 Instrumentation Basics -03- Level Measurement
28/63
Servo Tank Gauge
When emptying the tank, the liquid level starts moving
downwards. The force transducer will experience an increasing
weight, as upward force is no longer acting on thedisplacer.
Smart communication between the force transducer and
the servo controller will ensure that the displacer islowered.
The servo motor drives the measuring drum to unwindmeasuring wire until the displacer is partly immersed inliquid again until the measured or apparent weight
equals the programmed weight. The smart processing unit then can detect the level of
the liquid inside the tank corresponding to the drumapparent weight.
-
7/30/2019 Instrumentation Basics -03- Level Measurement
29/63
Servo Tank Gauge
-
7/30/2019 Instrumentation Basics -03- Level Measurement
30/63
Electrical-type Instruments Capacitance Probes one side of the process tank acts as one
plate and an immersion electrode is used as the other. The dielectric is either air or the material in the vessel & the
dielectric varies with the level in the vessel.
With the tank empty, the insulating medium between the twoconductors is air.
With the tank full, the insulating material is the process liquid orsolid.
As the level rises in the tank to start covering the probe, some ofthe insulating effect from air changes into that from the processmaterial, producing a change in capacitance between the sensingprobe and ground.
This capacitance is measured to provide a direct and linearmeasurement of tank level.
Noting that this type of instrument used only with NON-conductingservice to act as a dielectric between capacitance plat.
-
7/30/2019 Instrumentation Basics -03- Level Measurement
31/63
Capacitance Probes
-
7/30/2019 Instrumentation Basics -03- Level Measurement
32/63
Resistance Tapes In these devices, resistive material is spirally wound around a steel
tape & mounted vertically from top to bottom on a process tank.
The pressure of the fluid in the tank causes the resistive tape to beshort-circuited, thus changing the total resistance of the measuring
tape.
This resistance is measured by an electronic circuit and is directlyrelated to the liquid level in the tank.
-
7/30/2019 Instrumentation Basics -03- Level Measurement
33/63
Ultrasonic Type Instruments
These system consist of a transmitter mounted on top ofthe tank and receiver as well as associated electronicsequipment.
The transmitter antenna radiates the signal toward thesurface of the process liquid in the tank.
A portion is reflected back to the antenna, where it is
collected and routed to the receiver. The strength of the reflected signal is directly related to the
dielectric constant of the liquid.
The instrument measures the time that elapses betweenthe transmitted burst and the echo signal which is
proportional to distance between the transducers and thesurface of the liquid inside the tank.
-
7/30/2019 Instrumentation Basics -03- Level Measurement
34/63
Ultrasonic Type Instruments
-
7/30/2019 Instrumentation Basics -03- Level Measurement
35/63
Ultrasonic Type Instruments
Ultrasonic level measurement works on a "time of flight" principle.
Ultrasonic Level Measurement Instruments use sound waves todetermine level.
A piezoelectric crystal inside the transducer mounted on top of thetank converts electrical pulses into sound energy that travels in theform of a wave at the established frequency and at a constant speedin a given medium.
The sound waves are emitted in bursts and received back at thetransducer as echoes.
The Ultrasonic Level Measurement Instrument measures the time forthe bursts to travel down to the reflecting surface and return.
This time will be proportional to the distance from the transducer tothe surface and can be used to determine the level in the tank.
Sound waves are a form of mechanical energy that uses themolecules in the atmosphere to propagate, so, any changes in thechemical makeup of the atmosphere cause the speed of sound tovary.
-
7/30/2019 Instrumentation Basics -03- Level Measurement
36/63
Ultrasonic Type Instruments
Affected by powders, heavy vapors, surface turbulenceand foam.
Cannot operate in vacuum or high pressure.
Limited temperature range
More position sensitive than other technologies
-
7/30/2019 Instrumentation Basics -03- Level Measurement
37/63
Ultrasonic Type Instruments
-
7/30/2019 Instrumentation Basics -03- Level Measurement
38/63
Radar And Microwaves Instrument
Radar and Microwavesinstruments are similar to the Sonic-type, but
have advantage that they dont affected by the molecules in theatmosphere to propagate unlike the sonic-type.
Both radar signals and microwaves travel at the speed of light, but aredistinguished by their frequencies and by their power levels.
The transmitter is a microwave oscillator and directional antenna (aparabolic dish, horn-type antenna or rod antenna).
The receiver consists of an antenna, a high gain, a pulse-decodingcircuit, and an output circuit.
Microwave signals are absorbed almost entirely by water and tovarying degrees by water-based liquids or by products that have ahigh moisture content.
Microwave signals cannot penetrate metals but are reflected by them,so metal storage tanks or hoppers must have a detector window thatis transparent to the microwave signals.
-
7/30/2019 Instrumentation Basics -03- Level Measurement
39/63
Radar And Microwaves Instrument
-
7/30/2019 Instrumentation Basics -03- Level Measurement
40/63
Radar And Microwaves Instrument
-
7/30/2019 Instrumentation Basics -03- Level Measurement
41/63
Radar And Microwaves Instrument
There are two types of radar level instruments: noncontact and
guided wave. In the noncontact type the output electromagnetic energy of the
radar antenna is very weak, typically about 1 mW.
On the return to the instrument, this weak signal loses more
energy.
Liquid turbulence and some foams can further complicate the
measurement by scattering or absorbing the radar pulse.
The guided-wave radar unit can overcome these problems by
using pulses of electromagnetic energy that are transmitted down
the probe tube. The wave guided offers a highly efficient path for the signal to
travel down to reach the surface of the liquid and then bounce
back to the receiver.
-
7/30/2019 Instrumentation Basics -03- Level Measurement
42/63
Radar And Microwaves Instrument
-
7/30/2019 Instrumentation Basics -03- Level Measurement
43/63
Nuclear Level Measurement
Nuclear radiation systems have the ability to see through tank walls,
and thus they can be mounted on the outside of process equipment. Suitable for liquid or solid material detection.
Composed of a radioactive source material and a radiation detector,the two are mounted across the diameter of a storage vessel foreither solid or liquid material.
The product to be measured is attenuating the radiation coming from
the radioactive source and according to the height of the product inthe vessel, more or less of the original radiation is reaching thedetector.
This measuring signal is then transferred to an output signal whichdirectly correlates to the actual Level of the product.
Two typical nuclear level instruments:
Using a single low-level gamma-ray source on one side of theprocess vessel and a radiation detector on the other side of thetank.
Using several gamma sources at different heights on the tank.
-
7/30/2019 Instrumentation Basics -03- Level Measurement
44/63
Nuclear Level Measurement
-
7/30/2019 Instrumentation Basics -03- Level Measurement
45/63
Level Measurement Errors
Over ranging Damage to the D/P Cell
Faulty Sensing Lines
Loss of Loop Electrical Power
Connections: with an incorrectly connected DP cell theindicated level would go down while the true tank level
increases.
Extra weighted displacer: The sludge formed on thedisplacer makes faulty indication of the level.
Blocked bubbler tube: gives higher level reading thanthe present one.
-
7/30/2019 Instrumentation Basics -03- Level Measurement
46/63
Level Switches
A level switch is a device that senses the level of a liquid
in a process tank.
They are also used to control valves or pumps in order to
maintain fluid level at a set value or to prevent tanks from
being overfilled.
Level switch can be
Float type switch.
Ultrasonic type switch.
Rotating Paddle type switch.
Displacer type switch.
Capacitance type switch.
-
7/30/2019 Instrumentation Basics -03- Level Measurement
47/63
Float Type Switch The buoyant force is the operating principle of float level switch.
Floats should always be lighter than the minimum expectedspecific gravity of the process fluid.
As the level rises and falls, the float tilts up and down, thus openingand closing its electric contact.
The free length of the cable determines the actuation level.
In most cases, magnetic coupling transfers the float motion to theelectric contact or indicator mechanism.
The switch itself can be mercury or snap-action type switch.
The float, which contains an annular magnet, rises or falls withliquid level and is guided by the tube.
The switch assembly can be either inserted directly into the tank orside-mounted in a separate chamber.
The side-mounted switches are completely sealed and well suitedfor heavy duty industrial applications
-
7/30/2019 Instrumentation Basics -03- Level Measurement
48/63
Float Type Switch
Top mounted switch (directly in the tank)
-
7/30/2019 Instrumentation Basics -03- Level Measurement
49/63
Float Type Switch
Side-mounted
-
7/30/2019 Instrumentation Basics -03- Level Measurement
50/63
Displacer Type Switch
A displacer remains partially or completely submerged.
The apparent weight of the displacer is reduced as it
becomes covered by more liquid.
When the weight drops below the spring tension, the
switch is actuated.
Displacer switches are more reliable than regular floats
on turbulent, frothy, or foamy applications.
-
7/30/2019 Instrumentation Basics -03- Level Measurement
51/63
Displacer Type Switch
-
7/30/2019 Instrumentation Basics -03- Level Measurement
52/63
Ultrasonic Level Switches Echo transmitter-type level switches contain transmitter and receiver
units.
The transmitter generates pulses in the ultrasonic range, which thereceiver detects.
The transmitter and receiver can be located in the same probe or onopposite sides of the tank
Sound waves are easily transmitted across a transducer gap in thepresence of a liquid medium, but are severely attenuated when the
gap is dry. The level switch will be actuated when the sound beam is
interrupted .
This type of switch is effective for both solid and liquid materialapplications.
Noting that the probes of Ultrasonic switch installation has two
types. Contact type probe: which the probe itself is inserted inside the
tank and surrounded by the media.
Non-Contact type probe: the probe is installed externally of thetank.
-
7/30/2019 Instrumentation Basics -03- Level Measurement
53/63
Ultrasonic Level Switches
-
7/30/2019 Instrumentation Basics -03- Level Measurement
54/63
Ultrasonic Level Switches
-
7/30/2019 Instrumentation Basics -03- Level Measurement
55/63
Ultrasonic Level Switches
-
7/30/2019 Instrumentation Basics -03- Level Measurement
56/63
Nuclear Level Switch The radioactive source and the radiation detector are
mounted across the diameter of a storage vessel for
either solid or liquid material.
Any height of material beyond the level of the
source/detector arrangement will attenuate the strengthof radiation reaching the detector.
This decrease in radiation at the detector can
provide a switch contact for measurement, alarm point,
or even control of the vessel level.
l l S i h
-
7/30/2019 Instrumentation Basics -03- Level Measurement
57/63
Nuclear Level Switch
R i P ddl T S i h
-
7/30/2019 Instrumentation Basics -03- Level Measurement
58/63
Rotating Paddle Type Switch
Used to detect the presence or absence of solids in a
process tank.
A Synchronous motor keeps the paddle in motion at very
low speed when no solids are present, there is very low
torque on the motor
drive.
When the level in the tank rises to the paddle, torque is
applied to the motor drive and the paddle stops.
The level instrument detects the torque and actuates a
switch or set of switches.
R i P ddl T S i h
-
7/30/2019 Instrumentation Basics -03- Level Measurement
59/63
Rotating Paddle Type Switch
C i T S i h
-
7/30/2019 Instrumentation Basics -03- Level Measurement
60/63
Capacitance Type Switches
As media rises and falls in the tank, the
amount of capacitance developed between
the sensing probe and the ground also rises
and falls.
This change in capacitance is sensed by theelectronic circuitry.
At the predefined set point, the electronic
circuit gives the alarm or trip signal.
C i T S i h
-
7/30/2019 Instrumentation Basics -03- Level Measurement
61/63
Capacitance Type Switches
Th l l l i h
-
7/30/2019 Instrumentation Basics -03- Level Measurement
62/63
Thermal level switch
The sensor head employs two temperature sensors with
a constant heating source physically attached to one ofthe temperature sensors.
The second temperature sensor is isolated from the
heating source and provides compensation for changing
process temperatures. The probe operates by sensing the thermal conductivity
of the product surrounding the probe.
All liquids that form an interface will have a difference in
thermal conductivity that can be sensed.
Th l l l i h
-
7/30/2019 Instrumentation Basics -03- Level Measurement
63/63
Thermal level switch