INSTALLING NAECA III PRODUCT IN CONFINED LOCATIONS Brought to you by: NAECA III.
-
Upload
valerie-page -
Category
Documents
-
view
213 -
download
0
Transcript of INSTALLING NAECA III PRODUCT IN CONFINED LOCATIONS Brought to you by: NAECA III.
What is NAECA III ?
The National Appliance Energy Conservation Act of 1987 is a United States Act of Congress that regulates energy consumption of household appliances. These laws and regulations have to do with creating mandatory standards that deal with the energy efficiency. These standards were put in place to ensure that manufacturers were building products that are at the maximum energy efficiency. Since these standards have gone into effect they have positively affected both the American economy and the environment. Americans who have purchased these appliances have been saving money on their electricity bills every year. It is estimated that these savings have been greater than $300 billion.
WHAT IS NAECA III
INSTALLING NAECA III GAS PRODUCT
Gallon Capacity Pre-NAECA III NAECA IIIGas Gas
30 0.61 0.63
40 0.59 0.62
50 0.58 0.60
55 0.58 0.59
60 0.56 0.75
66 0.54 0.75
75 0.53 0.74
80 0.52 0.74
100 0.48 0.72
NAECA III GAS EF REQUIREMENTS
*Commercial water heaters are not affected*
INSTALLING NAECA III GAS PRODUCT
Gallon Capacity
Pre-NAECA III Model
Height (Inches)
Diameter (Inches)
NAECA-III Model
Height (Inches)
Diameter (Inches)
30 30 G 1” 61 1/2 16 30 G 2” 61 3/4 18
30 New 30 gal 1” foam with blanket *30 G 1”+ 61 3/4 16
30 30 G 2” 61 1/2 18 30 G 2” 61 3/4 18
40 New 40 gal under 40k Btu input 40 G 2” 62 20
40 40 G 1” 61 3/4 18 40 G 2” 62 20
40 New 40 gal 1” foam with blanket *40 G 1”+ 62 18
40 40 G 2” 61 3/4 20 40 G 2” 62 20
50 50 G 1” 60 3/4 20 50 G 1 ½” 60 3/4 21
50 50 G 2” 61 22 50 G 2” 60 3/4 22
Tall Gas Models
INSTALLING NAECA III GAS PRODUCT
Gallon Capacity
Pre-NAECA Model
Height (Inches)
Diameter (Inches)
NAECA-III Model
Height (Inches)
Diameter (Inches)
30 30 G 1” 50 18 30 G 2” 50 20
30 New 30 gal 1” foam with blanket *30 G 1”+ 50 18
40 40 G 1” 51 1/2 20 40 G 2” 51 1/2 22
40 New 40 gal 1” foam with blanket *40 G 1”+ 51 1/2 20
40 40 G 2” 51 1/2 22 40 G 2” 51 1/2 22
50 50 G 2” 53 1/4 24 50 G 2” 53 24
Short Gas Models
INSTALLING NAECA III GAS PRODUCT
Gas Replacement OptionsOriginal 40G 1”
62”Tall
18”Dia
New 40 G 2”
62”Tall
20”Dia
New 40 1” + Blk
62”Tall
18”*Dia
1” Foam insulation 2” Foam insulation1” Foam insulation+ *External Blanket
Option 1 Option 2
INSTALLING NAECA III GAS PRODUCT
Product Improvements
Minimum inlet gas pressure reduction Manifold pressure change from 5”wc to 4”wc 5”WC 4”WC
Ported ball type drain valve30% more flow for faster drainingTrue ¼ turn w/stop
INSTALLING NAECA III ELECTRIC PRODUCT
Gallons
Pre-NAECA
NAECA III
Electric Electric
30 0.93 0.95
40 0.92 0.95
50 0.90 0.95
55 0.90 0.94
66 0.88 1.98
80 0.86 1.97
120 0.81 1.92
Volume based calculation with new criteria established for larger storage capacity models – over 55 gallons
– Increase for ≤ 55 gal capacities a challenge for units already very efficient
– Increase for > 55 gal levels substantial, requiring technology change to heat pump water heaters
NAECA III Requirements
GallonCapacity
Pre-NAECAModel
Pre-NAECAHeight
Pre-NAECADiameter
NAECA IIIModel Height Diameter
30 30 Tall 46-1/2 18 30 Tall 46-1/2 19
40 40 Tall 59-1/2 18 40 Tall 60-1/4 20
50 50 Tall 54 20 50 Tall 60-1/2 22
50 50 Tall Blkt* 60-1/4 21
55 55 Tall 60-1/4 20 Discontinued – See 50 Tall
55 55 Tall 56-1/2 24
66 66 Tall 60-1/4 20-1/2 Discontinued – See Heat Pump
80 80 Tall 60-1/2 22-1/2 Discontinued – See Heat Pump
119 120 Tall 64-1/4 28 Discontinued – See Heat Pump
Tall Electric Models
INSTALLING NAECA III ELECTRIC PRODUCT
Gallon Capacity Pre-NAECA
Height (Inches)
Diameter (Inches) NAECA-III Model
Height (Inches)
Diameter (Inches)
30 30 Short/Reg 36-1/2 20-1/2 30 Short/Reg 39-3/4 2230 30 Short/Reg Blkt * 39 2040 40 Short/Reg 44 20-1/2 40 Short/Reg 50 2250 50 Short/Reg 48 22 50 Short/Reg 49-3/4 24
Short Electric Models
INSTALLING NAECA III ELECTRIC PRODUCT
INSTALLING NAECA III ELECTRIC PRODUCT
LOWBOY TOP CONNECT
Gallon Capacity Pre-NAECAHeight
(Inches)Diameter (Inches) NAECA-III Model
Gallon Capacity
Height (Inches) Diameter (Inches)
30 30 Low 30 22 30 Low 28 31-1/4 2430 30 Low Blkt* 30 20 30 Low Blkt* 28 30 2238 40 Low 31-1/4 23 40 Low 38 31-3/4 2638 40 Low Blkt* 32-1/4 24 40 Low Blkt* 38 31-3/4 2450 50 Low 34 26-1/2 Discontinued
LOWBOY SIDE CONNECT
Gallon Capacity Pre-NAECAHeight
(Inches)Diameter (Inches) NAECA-III Model
Gallon Capacity
Height (Inches) Diameter (Inches)
30 30 Low 30 22 30 Low 28 31-1/4 2430 30 Low Blkt* 28 30 2238 40 Low 30-1/2 23 40 Low 38 31-3/4 2638 40 Low Blkt* 38 31-3/4 24
Low Boy Electric Models
INSTALLING NAECA III ELECTRIC PRODUCT
Original 50 Tall
54”Tall
20”Dia
New 50 Tall
60.5”Tall
22”Dia
New 50 Tall Blkt*
60.25”Tall
21”Dia*
New 40 Tall
60 1/2”Tall
20”Dia
Option 1 Option 2 Option 3
1.75” Foam insulation 3” Foam insulation2.5” Foam insulation+ *External Blanket
40 Gallon Tank+ Mixing Valve
Electric Replacement Options
INSTALLING NAECA III ELECTRIC PRODUCT
• Standard 6/6 & 10/6– Copper upper element 4.5KW 240V– Incoloy lower element 4.5KW 240V
• Premium 10/10– Dual Incoloy elements 5.5KW 240V– Electronic thermostat replaces electromechanical
Electric Element Changes