Installation InstructionsSupplement
Coaxial Venting Systemfor Vitodens 100-W, WB1A and Vitodens 200-W, WB2A boilers
5441 088 v1.0 09/2009
Safety and Installation Requirements
Please ensure that these instructions are read and understood before commencing installation. Failure to comply with the
instructions listed below can cause product/property damage, severe personal injury, and/or loss of life.
Working on the equipment
The installation, adjustment, service,and maintenance of this product mustbe done by a licensed professionalheating contractor who is qualified andexperienced in the installation, service,and maintenance of hot water boilers.There are no user serviceable parts onthe boiler, burner, or control.
Ensure main power supply toequipment, the heating system, and allexternal controls has been deactivated.Close main gas supply valve. Takeprecautions in all instances to avoidaccidental activation of power duringservice work.
Ensure that the installation
literature of other components
is referenced.
This supplement provides specific information for the installation of the Coaxial
Venting System on Vitodens 100-W, WB1A and Vitodens 200-W, WB2A series
gas-fired condensing boilers.
The venting system is tested and ULC S636 listed by Intertek. Look for the
Intertek marking shown on the left and found on each component to identify the
new ULC listed coaxial system.
Do not mix pipe, fittings, or joining methods from different vent systemmanufacturers. Do not use adhesives of any kind with this venting system.
When installing the coaxial venting
system on Vitodens 200-W, models
WB2A 44 and 60, a transition adaptor
D must be installed immediately after
the boiler vent pipe adaptor. The length
of the adaptor is not considered in the
enclosed mounting template. Move side
wall vent opening location to 11 5/8” /
295 mma above mounting bracket.
Ple
ase
file
inS
ervic
eB
ind
er
When to Use This Supplement
Before Getting Started....
A
C
B
A Reference point top edge of boilerBMounting bracketCMounting templateD Transition adaptor (WB2A 44, 60 only)E Vent opening with transition adaptora 11 5/8” / 295 mm
D
a
E
Fig. 1
IMPORTANT
Side Wall Vent Installation
Fig. 2 Standard side wall venting layout, using basic vent kit components for vent systems 60/100, 80/125 and 100/150
1
2
3 4 5 6
7
A
A
B
a
Max. wall thickness19.6” / 500 mm
2
Side Wall Venting Layouts
Layout with basic coaxial vent kit componentry
Vent pipe adaptor
Transition adaptor (110/150 >100/150) for models WB2A 44, 60
Elbow, 87° (1 per carton)
Straight pipe, 3.3 ft. / 1 m long
Vent termination (incl. wall flashings)Important!
Total length of vent termination pipe
is 31” / 787 mm. If required, the vent
termination pipe may be shortened by
max. 12” / 305 mm (min. vent
termination length is 19” / 483 mm).
Protective screen
Warning!
Protective screen MUST be installed.
Mounting clip, white (use at least 2)
Brass adaptor (see page 3)
Combustion air intake
Flue gas outlet
a Total vent length*1
*1 See page 8 “Vent Length Requirements”(Side Wall Venting).
5441088
v1.0
Side Wall Vent Installation
7
8
9
Fig. 3 Side wall venting layout, using basic vent kit components for vent systems 60/100, 80/125 and 100/150
Transition adaptor
(used for models WB2A 44, 60 only)
3
Side Wall Venting Layouts (continued)
Layout with basic coaxial vent kit componentry (continued)
Mounting clip (c/w 4” screw)
Brass adaptor (supplied) (M8 x 5/16” -18) and set of screws (#8 x 3/8”)
9 All-threaded rod (field supplied)
5441088
v1.0
Side Wall Vent Installation
4
Side Wall Venting Layouts (continued)
Layout with basic coaxial vent kit and accessory componentry
Vent pipe adaptor
Transition adaptor (110/150 >100/150) for models WB2A 44, 60
Straight pipe*1
3.3 ft. / 1 m longor1.6 ft. / 0.5 m long
Elbow, 87° (1 per carton)
Telescopic extension
Elbow, 45° (2 per carton)
Vent termination (incl. wall flashings)Important!
Total length of vent termination is
31” / 787 mm. If required, the vent
termination may be shortened by
max. 12” / 305 mm (min. vent
termination length is 19” / 483 mm).
Protective screen
Warning!
Protective screen MUST be installed.
Mounting clip, white (use at least 2)
Brass adaptor (M8 x 5/16” - 18) andSet of screws (#8 x 3/8”)
*1 Other lengths may be used provided thatthe maximum equivalent vent length is notexceeded. 5
441088
v1.0
Fig. 4 Side wall venting layout, using basic vent components and accessory parts for vent system 60/100, 80/125 and 100/150
2
3
4 5 6
7 8
1
3
3
6 9qP
Side Wall Vent Installation
5
Component Guide (Side Wall Venting)
Telescopic extension installation
Fig. 5 Telescopic extension
The telescopic extension is used whereminor cutting or adjustment to thelength of the vent pipe is required. Seedimension “g” in table below.
Table 1.
Boiler model ain / mm
bin / mm
cin / mm
din / mm
ein / mm
f(max.
insertion)in / mm
gin / mm
WB1A 24, 30 2.4 / 60 4 / 100 0.4 / 10 7.9 / 200 9.6 / 245 1.2 / 30 min. 10.4 / 265max. 16 / 405
WB2A 24(C), 32 3.1 / 80 5 / 125 0.4 / 10 7.9 / 200 9.6 / 245 1.2 / 30 min. 11 / 280max. 15.5 / 395
WB2A 44, 60 4/100 6 / 150 0.4 / 10 7.9 / 200 9.6 / 245 1.2 / 30 min. 11 / 280max. 15.5 / 395
5441088
v1.0
Ø b
Ø a
c
Ø a
Ø b
c
f
e
d
Fig. 6
g
Side Wall Vent Installation
6
Component Guide (Side Wall Venting) (continued)
Vent termination installation
Table 2. Dimensions
Ventsystem
ain / mm
bin / mm
60/100 4.5 / 115 27.8 / 706
80/125 5.3 / 135 29 / 736
100/150 7.3 / 185 30.8 / 783
Table 3. Wall opening information
Vent system Opening Ø
60/100 4¼” / 108 mm
80/125 5¼“ / 133 mm
100/150 63/8” / 160 mm
When installing a side wall vent systemwith the minimum equivalent ventlength (87º elbow and vent terminationshortened to 19”/483 mm) from boilerback to the outside wall, a wallthickness of at least 6”/152 mm isrequired.For walls with a thickness of less than6” / 152 mm, means must be providedto offset the boiler from the wall.See Fig. 8.
Side wall vent termination installation
1. Provide side wall opening (see Table3.) to install vent termination.
2. Slide vent termination with wallflashing 2 into opening.
3. Attach wall flashing2 to inside ofwall using the screws and plugsprovided.
4. Attach wall flashing to outside ofwall.
5. To prevent movement of venttermination inside the wall, fastenflashing to vent pipe, using two#8 x 3/8” screws.(continued on next page)
Total length of vent termination is 31” /
787 mm. If required, the vent
termination may be shortened by max.
12” / 305 mm (min. vent termination
length is 19” / 483 mm).
Potential gaps between the vent-air
intake and the surrounding construction
which may cause air, rain or flue gases
to leak into the wall or the building,
must be sealed with approved outdoor
sealant/caulking to prevent leakage of
any kind.
5441088
v1.0
Fig. 7 Coaxial vent termination for vent system 60/100, 80/125 and 100/150
b
1 23
1Vent termination2Wall flashing (inside)3Wall flashing (outside)
6”/152 mm
Offset
Fig. 8
IMPORTANT
IMPORTANT
Side Wall Vent Installation
7
Component Guide (Side Wall Venting) (continued)
Vent termination installation (continued)
6. Secure protective screen (Fig. 9)into place, using the four stainlesssteel screws and plugs provided.
The protective screen MUST be
installed.
7. Connect vent termination from insideand route toward boiler with min. 3ºdownward slope.
Table 4. Dimensions
Model Vent system a b c
WB1A-24, -30 60/100 12” / 305 mm 7.5” / 190mm 9.5” / 241 mm
WB2A-24(C), -32 80/125 12” / 305 mm 6.7” / 170mm 9.5” / 241 mm
WB2A-44, -60 100/150 12” / 305 mm 4.7” / 120mm 9.5” / 241 mm
5441088
v1.0
Fig. 9 Protective screen, side view for vent systems 60/100, 80/125 and 100/150
6
IMPORTANT
Fig.10 Protective screen, front view
Vertical Vent Installation (Coaxial)
Fig. 11 Equivalent vent length calculation
*1
8
Vent Length Requirements (Side Wall Venting)
Maximum vent length
Table 5.
Vent system
Boiler model 60/100 80/125 100/150
WB1A 24, 30 20 ft. / 6 m (see Fig. 11) 26 ft. / 8 m*1 (see Fig. 12) 33 ft. / 10 m*2 (see Fig. 12)
WB2A 24(C), 32 n.a. 20 ft. / 6 m (see Fig. 11) 26 ft. / 8 m*3 (see Fig. 13)
WB2A 44, 60 n.a. n.a. 20 ft. / 6 m (see Fig. 11)
*1If used with increasers 60/100 to 80/125. *2 If used with increasers 60/100 to 100/150. *3 If used with increasers 80/125 to 100/150.
87º elbowVent pipe (3.3 ft. / 1 m)Vent pipe (1.6 ft. / 0.5 m)Vent termination
*1 First elbow not included in equivalent
vent calculation.
� For maximum equivalent vent lengthon all models see tables 5. and 6.,and Figs. 11, 12 and 13.
�Do not exceed the maximum ventlength.
�Do not use more than five elbows(87º or 45º) within one vent system(first elbow is included in count).
� First 87º elbow on boiler is notincluded in equivalent vent lengthcalculation.
Table 6.
Type of fitting Equivalentlength
87º elbow/87º inspection tee
1.6 ft. / 0.5 m
45º elbow 1 ft. / 0.3 m
Equivalent vent length calculation
example
2 x 87º elbow 3.2 ft. / 1 m. . . . . . . . . . . . . . . . . . . . . . . .
2 x vent pipe (1 m) 6.6 ft. / 2 m. . . . . . . . . . . . . .
1 x vent pipe (0.5 m) 1.6 ft. / 0.5 m. . . . . . .
1 x vent termination 2.4 ft. / 0.73 m. . . . .
Total equivalent length13.8 ft. / 4.23 m
First elbow not included in equivalent
vent calculation.
Always include vent termination length
in calculations.
5441088
v1.0
IMPORTANT
Vertical Vent Installation (Coaxial)
9
Vent Length Requirements (Side Wall Venting) (continued)
Maximum vent length with increasers (Vitodens 100-W, WB1A boiler)
Maximum vent length with increaser (Vitodens 200-W, WB2A boiler)
Minimum vent length
The minimum equivalent vent length for all models is 19” / 483
mm (length of the vent termination when cut to the minimum
permissible length). Please note that the first 87º elbow on boiler
is not included in equivalent length calculation.
5441088
v1.0
a
Coaxial increaserfor system 60/100 to 100/150
Coaxial increaserfor system 60/100 to 80/125
Fig. 12 Vitodens 100-W boiler with increasers
a
Coaxial increaser for system80/125 to 100/150
Fig. 13 Vitodens 200-W boiler with increaser
Vertical Vent Installation (Coaxial)
10
Vertical Venting Layouts
Layout of vertical vent system with accessories
Please note that there is no basic vent kit available for this vertical vent system.
Select from the vertical vent components below as required. Do not exceed maximum equivalent vent length.
Vent pipe adaptor
Elbow, 87° (1 per carton)
Telescopic extension
Straight pipe
3.3 ft./1 m or1.6 ft./0.5 m
Elbow, 87° (1 per carton)
Elbow, 45° (2 per carton)
Vent termination
Never shorten vertical vent
termination.
IMPORTANT
Mounting clip (c/w 4” screw)
Wall band (c/w vent termination, notshown)_
Brass adaptor (c/w set of screws)
Roof flashing and storm collar (fieldsupplied)
Use other anchoring/support system
components as required.
Ensure that the venting system isproperly supported; the Vitodens100-W and 200-W boilers are notdesigned to support the weight of theventing system.
IMPORTANT
Fig. 14 General vertical venting layout for vent systems 60/100, 80/125 and 100/150
1
2
4
3 4
8 + qP
5
4
6
4
6
4 8
7
8
Vertical Vent Installation (Coaxial)Vertical Vent Installation (Coaxial)
11
Vertical Venting Layouts (continued)
General installation examples
Ensure that the venting system is
properly supported; the Vitodens 100-W
and Vitodens 200-W boilers are not
designed to support the weight of the
venting system.
5441088
v1.0
Fig. 15 Sloped roof installation Fig. 16 Flat roof installation Fig. 17 Sloped roof installation with offset
IMPORTANT
Vertical Vent Installation (Coaxial)
12
Component Guide (Vertical Venting)
Telescopic extension installation
Fig. 18 Telescopic extension
The telescopic extension is used whereminor cutting or adjustment to thelength of the vent pipe is required. Seedimension “g” in table below.
Table 7.
Boiler model ain / mm
bin / mm
cin / mm
din / mm
ein / mm
f(max.
insertion)in / mm
gin / mm
WB1A 24, 30 2.4 / 60 4 / 100 0.4 / 10 7.9 / 200 9.6 / 245 1.2 / 30 min. 10.4 / 265max. 16 / 405
W2A 24(C), 32 3.1 / 80 5 / 125 0.4 / 10 7.9 / 200 9.6 / 245 1.2 / 30 min. 11/ 280max. 15.5 / 395
WB2A 44, 60 4/100 6 / 150 0.4 / 10 7.9 / 200 9.6 / 245 1.2 / 30 min. 11/ 280max. 15.5 / 395
5441088
v1.0
Ø b
Ø a
c
d
Ø a
Ø b
c
f
e
Fig. 19
g
Vertical Vent Installation (Coaxial)
13
Component Guide (Vertical Venting) (continued)
Vent termination installation
Fig. 20 Vent termination
ACombustion air intake
B Flue gas outlet
Øb
c
g
Øa
d
f
e
A A
B B
Table 8. Wall opening information
Vent system Opening Ø
60/100 4¼” / 108 mm
80/125 5¼“ / 133 mm
100/150 63/8” / 160 mm
Vertical vent termination installation
The vertical vent termination must not
be shortened outside the roof,
otherwise the overall length will be
shorter than required.
1. Install the vent termination for slopedor flat roof collars in accordance withthe manufacturer’s instructions.
2. The vent termination should beplaced from above on the sloped orflat roof collar.
3. Connect vent pipe from below.
Table 9. Dimensions, vent system
Boiler model a(in / mm)
b(in / mm)
c(in / mm)
d(in / mm)
e(in / mm)
f(in / mm)
g(in / mm)
WB1A 24WB1A 30
2.4 / 60 4 / 100 0.4 / 10 1.6 / 40 23 / 585 18.1 / 460 50.4 / 1280
WB2A 24(C)WB2A 32
3 / 80 5 / 125 0.4 / 10 2.2 / 57 18.7 / 476 22.8 / 580 53.3 / 1354
WB2A 44WB2A 60
4 / 100 6 / 150 0.4 / 10 n.a. 31.3 / 795 22.8 / 580 68.3 / 1735
5441088
v1.0
IMPORTANT
Vertical Vent Installation (Coaxial)
14
Vent Length Requirements (Vertical Venting)
Maximum vent length
Table 10. Vitodens 100-W
Boiler model WB1A 24 30
a (max. length)60/100 vent system ft./m 33/10 33/10
Do not exceed the maximum vent length.
Table 11. Vitodens 200-W
Boiler model WB2A 24C 24 32 44 60
a (max. length)80/125 vent system100/150 vent system
ft./mft./m
33/10--
33/10--
27/8--
--33/10
--20/6
Do not exceed the maximum vent length.
5441088
v1.0
Fig. 21 Vent length “a”
a
Vertical Vent Installation (Coaxial)
15
Vent Length Requirements (Vertical Venting) (continued)
Maximum vent length with increasers
Table 12. Maximum vertical vent length
(Vitodens 100-W, WB1A)
ModelNo.
WB1A 24, 30
Systemvent size
80/125*1 100/150*2
Max. ventlength
39.4 ft.12 m
46 ft.14 m
*1If used with increasers 60/100 to 80/125.
*2If used with increasers 60/100 to 100/150
Table 13. Maximum vertical vent length
(Vitodens 200-W, WB2A)
ModelNo.
WB2A 24C, WB2 32
Systemvent size
100/150*1 100/150*1
Max.ventlength (a)
39.4 ft.12 m
33 ft.10 m
*1If used with increasers 80/125 to 100/150.
5441088
v1.0
a
Coaxial increaserfor system 60/100 to 100/150
Coaxial increaserfor system 60/100 to 80/125
Fig. 22 Vent length “a”
Vertical Vent Installation (Coaxial)
16
Vent Length Requirements (Vertical Venting) (continued)
Equivalent vent calculation examples
Table 14.
Type of fitting Equivalentlength
87º elbow/87º inspection tee
1.6 ft. / 0.5 m
45º elbow 1 ft. / 0.3 m
Always include vent termination length
in calculations.
Equivalent vent length calculation
example
Vitodens 100-W, WB1A 30 andVitodens 200-W, WB2A 32(vent system 60/100) (see Fig. 23)
2 x 87º elbow 3.3 ft. / 1 m. . . . . . . . . . . . . . . . . . . . . . . .
2 x 45º elbow 2 ft. / 0.6 m. . . . . . . . . . . . . . . . . . . . . . . .
3 x vent pipe (0.5 m) 4.8 ft. / 1.5 m. . . . . . .
1 x vent pipe (1 m) 3.3 ft. / 1 m. . . . . . . . . . . . . .
1 x sliding coupling 0.8 ft. / 0.25 m. . . . . . .
1 x vent termination 3.9 ft. / 1.2 m. . . . . . . .
Total equivalent length18.1 ft. / 5.55 m
5441088
v1.0
Fig. 23 Equivalent vent length calculation, example
IMPORTANT
Componentry
17
Componentry
Table 15.
Vent system size Dimensions [in. / mm]
a b c
60/100 2.4 / 60 4 / 100 1.6 / 40
80/125 3 / 80 5 / 125 1.6 / 40
100/150 4 / 100 6 / 150 1.6 / 40
When cutting straight pipes to length,
debur and clean pipes.
Table 16.
Vent system size Dimensions [in./mm]
a b c
60/100 2.4/60 4/100 1.6/40
80/125 3/80 5/125 1.6/40
100/150 4/100 6/150 1.6/40
When cutting straight pipes to length,
debur and clean pipes.
Table 17.
Vent system size Dimensions [in./mm]
a b c d e
60/100 2.4/60 4/100 1.2/31 4.5/113 4/100
80/125 3/80 5/125 1.2/31 5/128 4.3/110
100/150 4/100 6/150 1.2/31 5.2/133 4.5/115
5441088
v1.0
Straight pipe (0.5 m)(can be cut to length if required)
c
Øb
Øa
19.7“ / 500 mm
Fig. 24
IMPORTANT
39.4”/1000 mm
Straight pipe (1 m)(can be cut to length if required)
c
Øb
Øa
Fig. 25
IMPORTANT
Elbow (87º)
Ø bØ a
88°
c
e
d
Fig. 26
Componentry
18
Componentry (continued)
Table 18.
Vent system size Dimensions [in./mm]
a b c d e
60/100 2.4/60 4/100 1.6/40 1.2/31 2.4/60
80/125 3/80 5/125 1.8/45 1.2/31 2.5/63
100/150 4.3/110 6/150 3.8/97 2/50 5/128
Table 19.
Vent system size Dimensions [in./mm]
a b c d e f
60/100 2.4/60 4/100 2/50 5/125 4/100 6/150
80/125 3.1/80 5/125 2/50 4.3/110 4/100 6/150
100/150 2.4/60 6/150 2/50 4.3/110 3.1/80 5/125
Table 20.
Vent system size Dimensions [in./mm]
a b c
60/100 2.4/60 4/100 min. 10.4/265max. 16/405
80/125 3.1/80 5/125 min. 11/280max. 15.5/395
100/150 2.4/60 6/150 min. 11/280max. 15.5/395
Table 21.
Vent system size Dimensions [in./mm]
a b
60/100 7.1/180 8.7/220
80/125 7.1/180 8.7/220
100/150 7.1/180 8.7/220
5441088
v1.0
Ø bØ a
c
43-45°
e d
Elbow (45°) (2 per carton)
Fig. 27
Increaser
Ø f
Ø bØ a
c
d
Ø e
Fig. 28
Telescopic extension
c
ab
Fig. 29
Wall flashing
Fig. 30
ba
Componentry
19
Componentry (continued)
Total length of vent termination pipe
is 31”/787 mm. If required, the vent
termination pipe may be shortened by
max. 12”/305 mm (min. vent
termination length is 19”/483 mm).
Table 22.
Vent system size Dimensions [in./mm]
a b c d
60/100 2.4/60 4/100 23.6/600 27.8/706
80/125 3/80 5/125 23.6/600 29/736
100/150 4/100 6/150 23.6/600 30.8/738
Table 23.
Boiler model Dimensions [in./mm]
a b c d e f g
WB2B80, 105 4.3/110 6/150 1.3/40 2/50 5.5/140 4.3/100 6/150
5441088
v1.0
Horizontal vent termination
Øa
Øb
c
d
front view,
not to scale
Fig. 31
IMPORTANT
b
aDimensions
a 12” / 405mmb 9.5” / 241mm
Protective screen
for side wall venting installations only
Fig. 32
Ø bØ a
c
e
d
Transition Adaptor 110>150
Fig. 33
fg
ØØ
Componentry
20
Componentry (continued)
Table 24. Dimensions, vertical vent termination
Boiler model a(in/mm)
b(in/mm)
c(in/mm)
d(in/mm)
e(in/mm)
f(in/mm)
g(in/mm)
WB1A 24, 30 2.4/60 4/100 0.4/10 1.6/40 23/585 18.1/460
50.4/1280
WB2A 24(C), 32 3/80 5/125 0.4/10 2.2/57 18.7/476
22.8/580
53.3/1354
WB2A 44, 60 4/100 6/150 0.4/10 n.a. 31.3/795
22.8/580
68.3/1735
Wall band
for installation on inside wall or ceiling(c/w vertical vent termination)
Table 25.
Vent system size Dimensions[in./mm]
a b
60/100 4/100 8.5/215
80/125 4.3/110 8.5/215
100/150 6/150 8.5/215
Mounting clip, white
for installation on inside wall or ceiling
Table 26.
Vent system size Dimensions[in./mm]
a
60/100 4/100
80/125 5/125
100/150 6/150
Brass adaptor
(c/w set of 20 #8 x 3/8” screws)
5441088
v1.0
Øb
c
g
Øa
d
f
e
A A
B B
Vertical vent termination
Fig. 34
a
b
Fig. 35
a
Fig. 36
5/16”-18
M8
Fig. 37
Componentry
21
Componentry (continued)
Basic vent kit components (Side Wall Vent System only)
Basic components
Vent pipe adaptor
(comes preinstalled on all
models)
Elbow, 87º
Straight pipe,
3.3 ft. / 1 m*1
Vent termination
(c/w wall flashings)
Protective screen
(c/w brass adaptor and set(c/w brass adaptor and set
of screws)
Mounting clip*2
Brass adaptor
(c/w set of 20 #8 x 3/8”
screws)
Vent accessories
Accessory components
Straight pipe,
1.6 ft. / 0.5 m*1
Elbow (45º)
(2 per carton)
Telescopic extension
Vent inspection tee/
Elbow (87º)
Straight tee (for system
60/100 only)
Coaxial increaser
(for system 60/100 to
80/125)
Coaxial increaser (for sys-
tem 80/125 to 100/150)
Coaxial increaser (for sys-
tem 60/100 to 100/150)
Joint lubricant
*1When ordering the straight pipe separately, order with
mounting clip and brass adaptor.*2When ordering mounting clip separately, order with
brass adaptor.5441088
v1.0
For replacement purposes or project-specific requirements,
individual parts can be ordered fromViessmann. Refer to the table
for an outline of basic vent kit componentry that can be orderedseparately.
For project-specific requirements, individual accessory parts can
be ordered from Viessmann. Refer to the table for an outline of
accessory parts available.
Componentry
22
5441088
v1.0
Componentry
23
5441088
v1.0
Componentry