INSTALLATION UNITARY ENERGY RECOVERY VENTILATOR …

16
PAGE 1 I - Shipping And Packing List Package 1 of 2 contains: 1 - Energy Recovery Ventilator Assembly 1 - Outdoor Fresh Air Hood w/ Filter 1 - Outdoor Exhaust Hood w/ Barometric Dampers 1 - Bag Assembly 1 - Roll of ¾" x 1 ¼" gasket 1 - 272" of 1 8 " x ½" gasket 10 - #14 Screws 10 - #10 x 1 ½" Screws 30 - #10 x ½" Gold Screws 1 - Installation Instructions Package 2 of 2 contains: 1 - Balancing Damper Assembly 1 - Platform Support Plate 2 - Side Filler Panel 2 - Door Panels 1 - Field Wiring Harness for Low Voltage with ECO 1001 economizer control board II - Shipping Damage Check unit for shipping damage. Receiving party should contact last carrier immediately if shipping damage is found. III - General These instructions are intended as a general guide and do not supersede local codes in any way. Authorities having jurisdiction should be consulted before installation. IV - Requirements When installed, the unit must be electrically wired and grounded in accordance with local codes or, in absence of local codes, with the current National Electric Code, ANSI/NFPA No. 70. V - Application Unitary Energy Recovery Ventilator (UERV) are used with 15 to 30 ton rooftop units equipped with a balancing damper assembly. These wheels conserve energy by mixing warmer air with cooler air in the following manner: Recovery Wheel Mode The Recovery Wheel mode is accomplished by two blowers providing continuous exhaust of stale indoor air and replacement by equal amount of outdoor air. Energy recovery is achieved by slowly rotating the energy recovery wheel within the cassette frame work. In winter, the UERV adsorbs heat and moisture from the exhaust air stream during one half of a complete rotation and gives them back to the cold,drier intake air supply during the other half rotation. In summer, the process is automatically reversed. Heat and moisture are absorbed from incoming fresh air supply and transferred to the exhaust air stream. This process allows outdoor air ventilation rates to be increased by factors of three or more without additional energy penalty or increase in size of heating or air conditioning systems. VI - Rigging Unit For Lifting 1. Maximum weight of unit is — 1500 Lbs. (Crated) 2. Remove crating. Then remove access panel to retrieve bag assembly. Replace access panel. 3. All panels must be in place for rigging. 4. Lifting lugs are supplied with the unit. Loosen machine bolts and rotate lifting lug 60 57 3 8 A 30 ½ MODEL# A VR036 46 5 8 VR046 52 5 8 VR062 58 7 8 CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges. WARNING Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies. MAXA-MI$ERÔ UNITARY ENERGY RECOVERY VENTILATOR MODEL VR036A15H/25H & VR046A15H/25H & VR062A15M/H/25M/H (STATIONARY) INSTALLATION INSTRUCTIONS 5257528-UAI-A-0616 / R62A-18YSDW ETL Certified per UL 1995 and CSA 22.2 Energy recovery COMPONENT certified to the AHRI Air-to-Air Energy Recovery Ventilation Equipment Certification Program in accordance with AHRI Standard 1060-2000. Actual performance in packaged equipment may vary.

Transcript of INSTALLATION UNITARY ENERGY RECOVERY VENTILATOR …

r62a-18ysdwPackage 1 of 2 contains:
1 - Energy Recovery Ventilator Assembly 1 - Outdoor Fresh Air Hood w/ Filter 1 - Outdoor Exhaust Hood w/ Barometric Dampers 1 - Bag Assembly
1 - Roll of ¾" x 1 ¼" gasket 1 - 272" of 1
8" x ½" gasket 10 - #14 Screws 10 - #10 x 1 ½" Screws 30 - #10 x ½" Gold Screws 1 - Installation Instructions
Package 2 of 2 contains:
1 - Balancing Damper Assembly 1 - Platform Support Plate 2 - Side Filler Panel 2 - Door Panels 1 - Field Wiring Harness for Low Voltage with
ECO 1001 economizer control board
II - Ship ping Dam age
Check unit for shipping damage. Receiving party should contact last carrier immediately if shipping damage is found.
III - Gen eral
These instructions are intended as a general guide and do not supersede local codes in any way. Authorities having jurisdiction should be consulted before installation.
IV - Re quire ments
When installed, the unit must be electrically wired and grounded in accordance with local codes or, in absence of local codes, with the current National Electric Code, ANSI/NFPA No. 70.
V - Ap pli ca tion
Unitary Energy Recovery Ventilator (UERV) are used with 15 to 30 ton rooftop units equipped with a balancing damper assembly. These wheels conserve energy by mixing warmer air with cooler air in the following manner:
Recovery Wheel Mode
The Recovery Wheel mode is accomplished by two blowers providing continuous exhaust of stale indoor air and replacement by equal amount of outdoor air. Energy recovery is achieved by slowly rotating the energy recovery wheel within the cassette frame work. In winter, the UERV adsorbs heat and moisture from the exhaust air stream during one half of a complete rotation and gives them back to the cold,drier intake air supply during the other half rotation. In summer, the process is automatically reversed. Heat and moisture are absorbed from incoming fresh air supply and transferred to the exhaust air stream. This process allows outdoor air ventilation rates to be
increased by factors of three or more without additional energy penalty or increase in size of heating or air conditioning systems.
VI - Rig ging Unit For Lift ing
1. Maximum weight of unit is — 1500 Lbs. (Crated)
2. Remove crating. Then remove access panel to retrieve bag assembly. Replace access panel.
3. All panels must be in place for rigging.
4. Lifting lugs are supplied with the unit. Loosen machine bolts and rotate lifting lug
60
VR036 46 5 8
VR046 52 5 8
VR062 58 7 8
CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.
WARNING Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.
MAXA-MI$ERÔ UNITARY ENERGY RECOVERY VENTILATOR MODEL VR036A15H/25H & VR046A15H/25H
& VR062A15M/H/25M/H (STATIONARY)
Energy recovery COMPONENT certified to the AHRI Air-to-Air Energy Recovery Ventilation Equipment Certification Program in accordance with AHRI Standard 1060-2000. Actual performance in packaged equipment may vary.
MAXA-MI$ERÔ UNITARY ENERGY RECOVERY VENTILATOR MODEL VR036A15H/25H & VR046A15H/25H
& VR062A15M/H/25M/H (STATIONARY)
INSTALLATION INSTRUCTIONS
PAGE 2
5257528-UAI-A-0616 / R62A-18YSDW
1. Disconnect all power to the rooftop unit.
Note: Ensure that no power source is connected to the unit. If the economizer is installed and power is applied, de-energize all power sources to the unit and use Lockout - Tag-out procedures. There may be multiple power inputs to unit, so validate that all power sources are de-energized and tagged.
2. Remove the rooftop units horizontal and return air access panels. Remove and discard any hoods, power exhaust equipment or economizer. Discard. See Figure 1.
Figure 1
REMOVE FILTER ACCESS
3. Remove the return duct cover from the floor of the RTU.
4. Remove the 9 screw holding the painted outside center post between the horizontal return air openings.
5. Remove the galvanized inside center post by removing the clip and two screws on the top, and the two 3 8" head screws on the bottom. See Figures 2 and 3.
6. Install the provided balancing damper assembly into the return air section of the RTU as shown in Figure 4. Reinstall the painted outside center post as shown in Figure 5.
7. Adjusting the balancing damper for the minimum airflow requirements can be done by loosening the wingnut on the quadrant and then moving the quadrant handle to set the return dampers in place. See Figure 6.
REMOVE
REMOVE
& VR062A15M/H/25M/H (STATIONARY)
Figure 7
8. Mount the SE-ECO1001 economizer control board in the return air compartment on the balancing damper frame within reach of field wiring harness. See Figure 7.
9. Connect the communication wire and power wire located in the accessory wiring bundle in the RTU return air section to the proper terminals on the economizer control board (see SSE field harness diagram at the back of this manual). See Figure 8.
10. Route the field wiring harness through the balancing damper into the return air section of the rooftop unit, coil the excess wire inside the RTU in order to keep it clear during the installation of the UERV. See Figure 9.
11. Align the provided platform support rail with the base rail of the RTU. Attach the support rail to the upper set of pre-drilled holes using the provided #14 screws. See Figure 10.
12. Locate the two provided adaptor panels, install them in place of the horizontal access panels removed earlier using provided #10 x ½" screws. See Figure 11.
13. Lift the UERV at least 3' (feet), remove the nut and bolt assembly and slide the telescoping leg out of the guide. Position the stand off legs so that the foot is on the bottom of the stand and reinstall the nut and bolt assembly. Do not tighten nuts at this time as the legs will have to be adjusted once the unit is finally set in place
14. Locate provided roll of ¾" x 1 ¼" gasket material. Apply gasket down the center post of the UERV as well as over the #14 screws on the support rail. See Figures 11 and 12.
15. Remove screw from the top panel of the RTU in order to enable lifting the top panel of the RTU up at least 2".
Note: An equipment support or pressure treated 2x6x60" piece of wood should be placed under the end of the UERV to prevent roof penetration by the standoff legs.
16. Lift the UERV then move it into position in front of the horizontal return air adaptor panels.
PAGE 4
& VR062A15M/H/25M/H (STATIONARY)
DELTA PRESSURE
Figure 15
Figure 13
Figure 12
17. Lower the UERV into place against the RTU, catch the bottom of the UERV on the platform support rail. With it in place remove the bolt assembly placed in the standoff legs in Step 13 and adjust the legs on the UERV so that it is level. Insert all 4 screws into each leg so that the legs are secure and the UERV sits in a leveled position.
18. Lift the top panel of the RTU enough to slip the top flange of the UERV under it, lower the top panel over the flange then reinsert screws. See Figure 13.
19. Secure the provided side filler panels to the UERV and the adaptor panels installed in step 10 using provided screws through pre-drilled holes. See Figures 14 .
20. Check along the edges where the UERV meets the adaptor panels and where the adapter panels meet the RTU and seal where necessary. There should be no air leakage and the final UERV assembly should be weather tight. Final assembly should resemble Figure 15.
21. On the UERV open the access panel on the right side of the name plate.Connect the wiring harness to the 3 prong connector located near the bottom of this access panel on one end and the "ex-fan" and "com" connectors on the other.
22. All electrical connections must meet current National Electric Codes (NEC) and/or Canadian Electric Code (CEC). Refer closely to the wiring diagram in unit or in these instructions for proper connections. Refer to the units Nameplate for the minimum circuit ampacity and the Maximum Over Current protection size. Electrical data is listed both on the nameplates and the individual motor nameplates.
23. Connect the line voltage power to the UERV from a field installed power disconnect through provided knockout. Connect line voltage to the fused power block per wiring diagram, Figure 16 shows the control box and wiring.
FUSE BLOCK
Figure 16
PAGE 5
& VR062A15M/H/25M/H (STATIONARY)
INSTALLATION INSTRUCTIONS 5257528-UAI-A-0616 / R62A-18YSDW
24. Ground the unit with a suitable ground connection either through the supply wiring or and earth ground. Units voltage entries must be sealed weather tight after wiring is complete.
25. Restore power to the unit.
26. Start system up to verify operation.
27. Replace access panels on UERV and return air section of the RTU and secure.
28. Cleanup once UERV is operating properly, caulk open joints holes or seams to make the unit weather tight.
29. Fill out installation checklist and startup sheet in the back of these instructions.
30. Leave this manual with the owner or in an envelope inside the unit.
VIII - Operation
How It Works
The unit contains an Energy Recovery Wheel (ERW) that is a new concept in rotary air-to-air heat exchanger. Designed as a packaged unit for ease of installation and maintenance, only matching up to rooftop unit with an internal balancing damper and connection of electrical power is required to make the system operational. The concept consists of a unique rotary energy recovery wheel that rotates in and out of fresh air streams within a heavy duty, permanently installed blower cabinet that provides ready access to all internal components. The media is polymeric material that is coated and permanently bonded with a dry desiccant for total enthalpy recovery. The wheel is belt driven by PSC motor and drive belt.
When slowly rotating through counter flowing exhaust and fresh air streams the UERV adsorbs sensible heat and latent heat from the warmer air stream and transfer this total energy to the cooler air stream during the second half of its rotating cycle. Rotating at 60 revolutions per minute, the wheel provides constant flow of energy from warmer to cooler air stream. The large energy transfer surface and laminar flow through the wheel causes this constant flow of recovered energy to represent up to 85% of the difference in total energy contained within the two air streams.
Sensible and latent heat are the two components of total heat. Sensible heat is energy contained in dry air and latent heat is the energy contained within the moisture of the air. The latent heat load from the outdoor fresh air on an air conditioning system can often be two to three times that of the sensible heat load and in the winter it is a significant part of a humidification heat load.
During both the summer and winter, the UERV transfers moisture entirely in the vapor phase. This eliminates wet surfaces that retain dust and promote fungal growth as well as the need for a condensate pan and drain to carry water.
Because it is constantly rotating when in the air stream, the UERV is always being cleared by air, first in one direction then the other. Because it is always dry, dust or other particles impinging on the surface during one half cycle, are readily removed during the next half cycle.
Additional Information for Options are provided in Options Manual.
Re cov ery Mode
On a thermostat call for blower operation in heating, cooling or continuous blower, the ERW will rotate between fresh air and exhaust air streams. Both the fresh air and exhaust air blowers will also be operating to overcome the air resistance of the UERV.
Free Cool ing Mode (op tional)
The Start, Stop, Jog kit is an optional control board with temperature and/or enthalpy sensor(s) that stops the enthalpy wheel from spinning (and transferring heat) when temperature conditions are conducive for free cooling. The board will spin the wheel intermittently in 10 min off 1 min on intervals to keep dust from building up on the surface.
All units shipped with the Start, Stop, Jog option installed have the temperature and enthalpy sensors installed, and the jumper (J9) set to T(emp). A qualified tech can adjust the setting to E(nthalpy) only or Temp and Enthalpy by adjusting the jumper (J9).
The factory set points to allow for free cooling during ventilation are 40oF-70oF, but they can be field adjusted to narrow the band by adjusting two potentiometers while measuring VDC between the Com & High or Com & Low terminals (0 VDC = 40 degrees, low set point, 5 VDC = 70 degrees, high set point).
IX - Sys tem Check
1. Disconnect main power.
2. Turn thermostat to "Cont" for blower operation.
3. Restore power to unit. Observe UERV wheel rotation and both fresh air and exhaust air blowers will operating.
Note: If Low ambient kit is used the jumper between TB37-5 & TB37-6 should be removed. Also if system check out is being conducted at low ambient temperatures, technician should be aware that this kit can cause system not to operate.
4. Verify that the UERV (3) three phase blower motors are phased sequentially ensuring correct rotation and operation.
a) Disconnect power.
b) Reverse any two field power leads to the UERV.
c) Reapply power.
A - Re turn Damper Set tings
Manually adjust position of dampers. This is accomplished by loosing and tightening set screw on positioning rod.
B - Blower Speed Ad just ment
Blower speed selection is accomplished by changing the sheave setting on both fresh air and exhaust air blowers. Both blowers are factory set at "closed" for maximum airflow. To determine air flow setting, external static pressure readings will need to be read across the UERV. See Figure 15 for location to take pressure readings.
PAGE 6
& VR062A15M/H/25M/H (STATIONARY)
1. Remove plastic plugs in door panels (4 total).
2. With a manometer measure the pressure drop [Inches Of water column] across the wheel on the supply airflow side of the unit (Top). The unit’s CFM is determined by referring to Table #1. If the Cfm value is not per design adjust the motor sheave until the desired CFM is reached.
3. To adjust the exhaust airflow check the pressure on the exhaust side of the unit (Bottom), then remove the door panel to access the return air dampers installed inside the RTUs return air section. Adjustment of the damper is made by loosening the wingnut, adjusting the damper blades and then tightening the wingnut before closing the panel and measuring again.
4. Once desired the CFM is reached replace the plastic plugs in the access holes in the doors.
X - Main te nance
Motor Maintenance All motors use prelubricated sealed bearings; no further lubrication is necessary.
Mechanical Inspection Make visual inspection of dampers, linkage assemblies and UERV rotating bearings during routine maintenance. Filters should be checked periodically and cleaned when necessary. Filter is located in fresh air hoods. DO NOT replace permanent filters with throwaway type filters.
Belt Alignment Proper alignment is essential to maintain long V-Belt life. Belt alignment should be checked every time belt maintenance is performed, each time the belt is replaced, and whenever sheaves are removed or installed.
Belt Installation Always move the drive unit forward so the belt can be easily slipped into the groove without forcing them. Never force the belt into a sheave with a screw driver or wedge. You will damage the fabric and break the cords. It is recommended that the pulley center distances be offset by ¾" for proper length. This will allow the motor assembly to slide forward to remove belt and backward for belt tension.
Belt Tension Measure the span length (center distance between pulleys when belt is snug). Mark center of span, then apply a force (6 to 9 Lbs on new belts) perpendicular to the span large enough to deflect the belt 164" for every inch in span length.
Energy Recovery Wheel Maintenance Eight pie-shaped ERW segments, are seated on stops between the segment retainer which pivots on the wheel rim and secured to the hub and rim of wheel. Annual inspection of the self cleaning wheel is recommended. With power disconnected, remove UERV access panels (rear) and unplug [J150 and P150] (Refer to wiring diagrams in this instruction manual). Remove segment and wash with water and/or mild detergent.
To install wheel segments follow steps A through E . See Figure 17. Reverse procedure for segment removal.
A. Unlock two segment retainers (one on each side of the selected segment opening.
B. With the embedded stiffener facing the motor side, insert the nose of the segment between the hub plates.
C. Holding segment by the two outer corners, press the segment towards the center of the wheel and inwards against the spoke flanges. If hand pressure does not fully seat the segment, insert the flat tip of a screw driver between the wheel rim and outer corners of the segment and apply downward force while guiding the segment into place.
D. Close and latch each segment retainer under segment retaining catch.
E. Slowly rotate the wheel 180o. Install the second segment opposite the first for counterbalance. Rotate the two installed segment 90o to balance the wheel while the third segment is installed. Rotate the wheel 180o again to install the fourth segment. Repeat this sequence with the remaining four segments.
MAXA-MI$ERÔ UNITARY ENERGY RECOVERY VENTILATOR MODEL VR036A15H/25H & VR046A15H/25H
& VR062A15M/H/25M/H (STATIONARY)
Wheel Type
R = Rooftop Stationary O = Stand Alone Over and Under, Stationary S = Stand Alone Side by Side P = Rooftop Pivoting (036-060 & 078-150 only)
Prod uct Cat e gory
V = Ventilator
CFM*
006 = 300 to 550 011 = 600 to 1000 020 = 1100 to 1700 028 = 2200 to 2800** 1500 to 2200** 036 = 2800 to 3600 046 = 3400 to 4600 062 = 5500 to 6200** 4800 to 5600** 074 = 6000 to 8000 122 = 8000 to 13000
York Roof top Cab i net
A06 = Small Sunline ZF/ZR/XP036-072 A12 = 50" Predator ZF/ZH/ZR/XP*102-150, ZJ076-150 B12 = 42" Predator ZF/ZR/XP078-090, ZH0037-090, ZJ/ZR076-150 A15 = Large Sunline ZF180 A25 = Large Sunline ZF210-300, ZJ180-300, XP180-240 A40 = Millennium 25, 30 and 40 Ton Package
Blower Speed
H = High Speed** M = Medium Speed** V = Variable Speed L = Constant Volume
Prod uct Gen er a tion
1 = First Generation
Ad di tional Op tions
AA = No Options Installed L1 = Low Ambient Kit (LAK)* L2 = LAK & MOA* L3 = LAK & MOA & SSJ (not used on P models)* L4 = LAK & MOA & SSJ & PS (not used on P models) L5 = LAK & SSJ (not used on P models)* L6 = LAK & SSJ & PS (not used on P models) L7 = LAK & PS L8 = LAK, MOA and PS M1 = Motorized Outside Air (MOA)* M2 = MOA & SSJ (not used on P models)* M3 = MOA & SSJ & PS (PS) (not used on P models) M4 = MOA & PS S1 = Stop-Start-Job (SSJ) (not used on P models)* S2 = SSJ & PS (not used on P models) P1 = Pressure Sensor (PS)
Volt age
Duct Type
A = No Selection on Rooftop Units
* CFM is ERV wheel rating. This may vary depending on unit cabinet pressure drop.
** These CFM ranges are dependant upon blower motor selection.
Low Ambient Kit (LAK) - Defrosts wheel when low ambient temp near the exhaust blower shows possible frost up.
Start-Stop-Jog (SSJ) - provides a "free cooling" mode by stopping enthalpy wheel when temps are appropriate for free cooling.
Motorized Outside Air (MOA) damper - closes a damper on the outside air intake when the ERV is not in use.
Pressure Sensor (PS) - Analog differential pressure gauge (Magnahelic) shows pressure drop across the wheel in Inches of Water.
PAGE 8
0.83 0.89
0.95 1.01
SCFM
TABLE #1
P R
E S
S U
R E
D R
O P
(i n
R36 Series 1000 RPM 900 RPM 800 RPM 700 RPM
VR036 Se ries
0.52 0.57
0.62 0.67
0.71 0.76
0.81 0.86
0.91 0.96
1.00 1.05
1.38 1.35 1.29
0.98 0.93
0.85 0.78
0.75 0.69
0.65
0.57
0.48
0.37
0.22
0.00
0.20
0.40
0.60
0.80
1.00
1.20
1.40
1.60
2200 2400 2600 2800 3000 3200 3400 3600 3800 4000 4200 4400 4600
SCFM
TABLE #1
P R
E S
S U
R E
D R
O P
(i n
.o f
W .C
.)
R46 Series 1000 RP M 900 RP M 800 RP M
VR046 Se ries
& VR062A15M/H/25M/H (STATIONARY)
0.81 0.84 0.87 0.91 0.94 0.98 1.01 1.04
1.89 1.82
1.75 1.65
SCFM
TABLE #1
P R
E S
S U
R E
D R
O P
(i n
VR062 Se ries
& VR062A15M/H/25M/H (STATIONARY)
PAGE 10
Notes: 1. Remove jumper to install field optional low ambient switch. 2. Step-down transformer assembly for 460/575 volt units. 3. Selective voltage terminal for proper unit voltage 4. Optional low ambient switch. 5. Optional motorized intake damper. 6. Optional Stop, Start and Jog control (Climate Smart). 7. For energy management systems connect +24v to "G" and common 24v to "C". 8. Optional motorized exhaust damper. 9. Optional wheel rotation sensor. 10. Optional smoke detector.
COMPONENT CODE
A131 Fixed Relay Board B26 Motor, Exhaust Air B27 Motor, Intake Air B28 Motor, Desiccant Wheel B30 Motor, Damper Intake (Optional) B31 Motor, Damper Exhaust (Optional) C23 Capacitor, Wheel Motor F29 Fuse J48 Jack, Control Box (Intake Air) J50 Jack, Control Box (Wheel) J51 Jack, Control Box (Exhaust Air) J56 Jack, Control Box (Damper) J148 Jack, Intake Air Motor Harness J150 Jack, Wheel Motor Harness J151 Jack, Exhaust Air Motor Harness
P153 Plug, Field Harness P160 Plug, Damper Intake Motor Harness P161 Plug, Damper Exhaust Motor Harness RS-1 Rotation Sensor (Optional) S26 Switch, Low Ambient (Optional) S51 Switch, Door S52 Switch, Damper Intake S53 Switch, Damper Exhaust SD Smoke Detector (Optional) SSJ Climate Smart Board (Optional) T27 Transformer, Control T28 Transformer, Step-down (Optional) TB37 Terminal Block (Low Voltage) TB39 Terminal Block (Monitoring) WHL Relay, Wheel Motor
J152 Jack, Transformer (High Voltage) J153 Jack, Field Harness J160 Jack, Damper Intake Motor Harness J161 Jack, Damper Exhaust Motor Harness K163 Contactor, Exhaust Air Motor K164 Contactor, Intake Air Motor MPD-1 Missing Pulse Detector Board (Optional) P48 Plug, Intake Air Motor Harness P50 Plug, Wheel Motor Harness P51 Plug, Exhaust Air Motor Harness P56 Plug, Damper Motor Harness P148 Plug, Intake Air Motor P150 Plug, Wheel Motor P151 Plug, Exhaust Air Motor P152 Plug, Transformer (High Voltage)
WIRE COLOR CODE
WT White YL Yellow
ERV UNIT WIR ING DIAGRAM
: s
& VR062A15M/H/25M/H (STATIONARY)
5257528-UAI-A-0616 / R62A-18YSDW
In order for the ERV to operate with maximum effectiveness the Smart Equipment Control (SEC) must have the latest 3.1 (or greater) firmware installed. In order to determine the version of firmware present within the control follow the menu steps below.
Status> Scroll down to "Update"> Enter> View Version
If a firmware update is required be sure to perform a backup of the units factory settings if updating the firmware. The procedure below outlines the backup and restore functions of the SE units control board. Once the procedures outlined in the document, the following set points will have been changed to the status shown below.
I - Set Points
Set Points Sta tus BACOid Economizer En able ON 29747 Power Ex haust En able ON 29787 Non-Mod u lat ing Power Ex haust ON 29503
These settings can be accessed within the RTU- SE UCB menu. Please refer to the RTU's SE "Quick Start" guide for menu navigation using the onboard LCD display, joystick and enter/cancel buttons. Please see the following pages for instructions on how to navigate the Smart Control (SE) menus and setting up the control to operate with an ERV.
II - SE Procedures to Backup / Restore
1. Once the packaged unit is powered up the 120 second startup delay begins. Once the delay expires there may or may not be a "Start Up" delay displayed. To cancel the second time delay press the "Cancel" button for six seconds. See Figure 1.
Startup Figure 1
Update Figure 2
Backup Figure 3
2. Once the control is out of time delay mode, press the Joystick down through the following menus: Status> Alarms> Summary> Commission> Controller> Update, Push ENTER (See Figure 2)
3. Once the screen and cursor are on "Update". Press Enter and scroll through the menus until the screen and cursor displays "Backup". If an USB flash drive is present or is inserted into the on board USB port, pressing enter when "Backup" is displayed the backup will begin sending factory defaults and other settings to the USB flash drive. See Figure 3.
4. Once the backup is performed (Screen shows BCFG 100%) the 3.1 or greater version of the controls firmware can be loaded. Please see the details on the following pages on how to perform the firmware updates.
III– SE Procedures to Update
Updating the program in the SE control by USB if required.
WARNING! In order for the ERV to properly operate with the SE control version 3.1.0.0.0128 or greater must be installed. Load the appropriate files to a clean USB Flash Drive as indicated in the prior five steps.
(Files located on UPGNET>UST and Technical Services Center>Tech Services Software Updates)
PAGE 14
INSTALLATION INSTRUCTIONS
& VR062A15M/H/25M/H (STATIONARY)
5257528-UAI-A-0616 / R62A-18YSDW
1. Place USB Flash Drive into USB port on controller (Note: Please be sure a backup to a USB drive before updating the firmware).
Screen will read: USB WAIT
Then: USB OK
2. Press Joy Stick down
Screen will read: Status >Alarms
3. Press Joy Stick lever down four times until the screen below appears. If the Update screen is scrolled past you return by pressing the joy stick lever up until the Update screen appears.
Screen will read: Contrler (Controller) >Update
Enter & Cancel Buttons Figure 6
>View Ver Figure 7
Screen will read: >View Ver (Version) Load Firm Backup
5. Toggle Joy stick down so the arrow is next to >Load Firm
6. Press ENTER
Screen shows software versions present on the USB Flash Drive, such as >1.0.0.1101.secusb.pkg, 3.0.0.1072.secusb.pkg or other versions that have been loaded onto the USB Flash Drive. Scroll up or down to view firmware versions on the drive. Select the desired firmware file (3.1.0.0128 version in this example).
7. Press ENTER Screen will read:
Confirm?
& VR062A15M/H/25M/H (STATIONARY)
5257528-UAI-A-0616 / R62A-18YSDW
Screen will read FWU WAIT then the program will load.
This could take up to 10 minutes or more. The screen contents will change several times during the update so be patient…
Wait until base screen reappears. Re-programming is complete for the firmware. Now that the new firmware is loaded it is time to restore the backup data from earlier step. Scrol l to : Status> Alarms> Summary> Commission> Controller> Update> View Version> Load Firmware> Backup> Restore press Enter and the screen will request the user indicate which restore file to use. The backup files should be named after the units serial number. Scroll to the appropriate units serial number on the screen and press Enter. The restore should only take 15-20 seconds. Once the restore is complete the SE unit control will reboot. Note: If updating a version "H" board it may require two firmware updates to take place. Please verify the active version of firmware after updating.
If the unit does not reboot, restart cycle power to the unit and wait again for re-boot start-up.
If loading more than one file, example upgrading CDR unit from version 1, you should cycle power after loading the first file and again after the last file is complete.
It is a good practice to conduct a "RE-LEARN" from within the menu after the file(s) have been upgraded if the function of the unit does not appear to be normal. Status> Alarms> Summary> Commission> Controller>
IV - SE Procedures to Setup Operation for ERV
In order for the SE unit controller, SE economizer control and ERV to operate proper ly the fo l lowing changes/settings will need to be performed within the SE unit control.
1. Scroll through menus by pressing down on joystick: Status> Alarms> Summary> Commission> Econ> Economizer Enable- Make sure this is set to "Yes"
ERV-En Figure 11
Econ-En Figure 10
2. Scroll through menus by pressing down on joystick: Status> Alarms> Summary> Commission> PowerEx> ERV Enable- Make sure this is set to "Yes"
3. The economizer minimum setting must be set at 50% or greater. Status> Alarms> Summary> Commission> PowerEx> ERV Enable- Make sure this is set to "Yes"
4. Once the ERV is set to "Enable" the ERV will operate any time the unit is in the occupied mode. The ERV, if equipped with pivoting wheel, will rotate the wheel out of the air stream anytime the packaged units economizer enters the free cooling mode. In order to test for proper operation the unit must see a call for cooling (24 vac on the Y1 terminal) and an outdoor temperature of 55oF or less. If the outdoor ambient temperature is above 55oF the unit may not enter free cooling. If the ambient temperature is above 55oF the packaged unit can be forced into free cooling mode by doing the following:
5. Scroll through menus by pressing down on joystick: Status> Alarms> Summary> Commission> Controller> Update> Details, under details press Enter then scroll to the Service menu heading, press Enter then scroll to Inputs> NetworkInputs, scroll to NetOAT and change it to a setting well below the 55oF default by toggling the joystick left or right to increase/decrease the value, then pressing Enter to store the new value. If the setting is now 30oF for example the unit should go into free cooling mode within a few minutes of the change. Note: Once the NetOAT is forced to a temperature below 55oF it will remain at the forced value for 15 minutes and revert back to default settings.
For additional details on navigating, changing and operating the SE unit control board please refer to the SE (Smart Equipment) Controls Quick Start Guide (Document # 1136326-USG-C-0216) that is shipped with the packaged unit.
START UP INFORMATION SHEET
In com ing Volt age L1-L2 L1-L3 L2-L3
Run ning Volt age L1-L2 L 1-L3 L2-L3
Sec ond ary Volt age C (black) to G (green) Volts*
C (black) to W (white) Volts*
* With thermostat calling.
AMPERAGE - UERV MOTORS
In take Mo tor: Nom i nal HP Rated Amps Run ning Amps
Ex haust Mo tor: Nom i nal HP Rated Amps Run ning Amps
Wheel Mo tor: Nom i nal HP Rated Amps Run ning Amps
AIRFLOW
In take De sign CFM Pres sure Drop Cal cu lated CFM
Ex haust De sign CFM Pres sure Drop Cal cu lated CFM
Amb. db Temp Re turn Air db Temp* Tem pered Air db Temp*
Amb. wb Temp Re turn Air wb Temp* Tem pered Air wbTemp*
* Measure after 15 minutes of run time
INSTALLATION CHECK LIST
In stall ing Con trac tor Start Up Me chanic
q Inspect the unit for transit damage and report any damage on the carrier's freight bill.
q Check model number to insure it matches the job requirements.
q Install field accessories and unit adapter panels as required. Follow accessory and unit installation manuals.
q Verify field wiring, including the wiring to any accessories.
q Check all multi-tap transformers, to insure they are set to the proper incoming voltage.
q Verify correct belt tension, as well as the belt/pulley alignment. Tighten if needed.
q Prior to energizing the unit, inspect all the electrical connections.
q Power the unit. Bump the motor contactor to check rotation. Three phase motors are synchronized at the factory. If blower motor fans are running backwards, de-energize power to the unit, then swap two of the three incoming electrical lines to obtain proper phasing. Re-check.
q Perform all start up procedures outlined in the installation manual shipped with the unit.
q Fill in the Start Up Information as outlined on the opposite side of this sheet.
q Provide owner with information packet. Explain the thermostat and unit operation.
York International Corporation 5005 York Drive
Norman, OK 73069
Subject to change without notice. Printed in U.S.A. Copyright © 2016 by Johnson Controls, Inc. All rights reserved.
5257528-UAI-A-0616 / R62A-18YSDW Supersedes: None