www.UsePhoenix.com [email protected] Toll-Free 1-800-533-7533 Owner’s Manual Phoenix 200HT Installation, Operation & Service Instructions Read and Save These Instructions The Phoenix 200HT LGR, High Capacity Dehumidifier Phoenix 200HT 4029970 Specifications subject to change without notice. TS-621 08/10 4201 Lien Rd.• Madison, WI 53704 Patented Bypass Technology High Capacity - Removes 135 pints per day at AHAM 7.2 amps - Removes over 6.5 pints/kWh. R-410A Refrigerant More Grain Depression - Drier air from an LGR finishes jobs quicker versus a conventional refrigerant dehumidifier. Focused Airflow - Patented focused outlet directs air downward across the wet surface. Motorized Impeller - 380 CFM; Faster drying and superior static pressure for ducting. Multiple Ducting Options - 12” intake, 10” exhaust. Solid State Controls - Easy to read and operate. Recessed 12” Wheels - Allows greater maneuverability on the job site and efficient storage. Rolls over obstacles with ease. MERV-11 Pleated Media Air Filter The Phoenix 200HT is one of the most effective and versatile drying devices available. The Phoenix 200HT features higher capacity and superior efficiency compared to other refrigerant dehumidifiers, removing 135 pints per day at AHAM while drawing only 7.2 amps of electricity. The 200HT also features Phoenix’s patented bypass system. At higher temperatures, where typical LGRs lose effectiveness, patented Bypass Technology helps the Phoenix 200HT continue to remove moisture, leading to faster evaporation, quicker drying, and elimination of the need to remove equipment for temperature control. www.sylvane.com 1 (800) 934-9194

Transcript of Installation, Operation & Service Instructions - Air …...3.1 Air Filter The Phoenix 200HT is...

Page 1: Installation, Operation & Service Instructions - Air …...3.1 Air Filter The Phoenix 200HT is equipped with a pleated fabric air filter that must be checked regularly. The standard

www.UsePhoenix.com • [email protected] 1-800-533-7533

Owner’s Manual — Phoenix 200HTInstallation, Operation & Service Instructions

Read and Save These Instructions

The Phoenix 200HT LGR, High Capacity Dehumidifier

Phoenix 200HT4029970Specifications subject to change without notice.

TS-621 08/10

4201LienRd.•Madison,WI53704

• Patented Bypass Technology

• High Capacity - Removes135pintsperdayatAHAM

• 7.2 amps - Removesover6.5pints/kWh.

• R-410A Refrigerant

• More Grain Depression - DrierairfromanLGRfinishesjobsquickerversusaconventionalrefrigerantdehumidifier.

• Focused Airflow - Patentedfocusedoutletdirectsairdownwardacrossthewetsurface.

• Motorized Impeller - 380CFM;Fasterdryingandsuperiorstaticpressureforducting.

• Multiple Ducting Options - 12”intake,10”exhaust.

• Solid State Controls - Easytoreadandoperate.

• Recessed 12” Wheels - Allowsgreatermaneuverabilityonthejobsiteandefficientstorage.Rollsoverobstacleswithease.

• MERV-11 Pleated Media Air Filter

ThePhoenix200HTisoneofthemosteffectiveandversatiledryingdevicesavailable.ThePhoenix200HTfeatureshighercapacityandsuperiorefficiencycomparedtootherrefrigerantdehumidifiers,removing135pintsperdayatAHAMwhiledrawingonly7.2ampsofelectricity.

The200HTalsofeaturesPhoenix’spatentedbypasssystem.Athighertemperatures,wheretypicalLGRsloseeffectiveness,patentedBypassTechnologyhelpsthePhoenix200HTcontinuetoremovemoisture,leadingtofasterevaporation,quickerdrying,andeliminationoftheneedtoremoveequipmentfortemperaturecontrol.

www.sylvane.com1 (800) 934-9194

Page 2: Installation, Operation & Service Instructions - Air …...3.1 Air Filter The Phoenix 200HT is equipped with a pleated fabric air filter that must be checked regularly. The standard

2 www.UsePhoenix.com • [email protected] 1-800-533-7533

1 SpecificationsPart No. 4029970

Power 110-120Vac,7.2amps

Water 135pints/day@AHAM(80°F,60%)Removal

Refrigerant 2lbs.2oz.R410aCharge

Blower 380CFM InternalCondensatePumpwith20’lift, 30’vinylhose

Operating 33°Fto125°FRange

Filters 16”x20”x2”PleatedMediaMERV-11

Duct Intake–12”Flex-DuctOptions Exhaust–10”Lay-Flat

Warranty Fiveyears; Firstyear100%ofPartsandLabor Second-fifthyear100%ofPartsofsealed refrigerationsystem.

Dimensions Width20”,Height40”,Depth23”

Weight 130lbs.

2 Operation2.1 Transporting the Phoenix 200HT ThePhoenix200HTmustalwaysbeuprightwhentransportedbyvehicle.Itmaybetippedontoitshandleandbackforloadingandmovingbyhand.

2.2 LocationNote the following precautions when locating the Phoenix 200HT:

• ItisdesignedtobeusedINDOORS ONLY.

• Ifusedinawetarea,plugitintoaGROUND FAULT INTERRUPTER.

• DO NOTusethePhoenix200HTasabenchortable.

•Itmustalwaysbeusedintheuprightposition.

• Theairinletontop&thesideoutletmustbeatleast1footfromwallsandotherobstructionstoairflow.

Table of ContentsIntroduction................................................................1

1. Specifications........................................................2

2. Operation.............................................................2

2.1TransportingthePhoenix200HT.......................2

2.2Location.........................................................2

2.3ElectricalRequirements...................................3

2.4CondensateRemoval.......................................3

2.5Ducting...........................................................3

2.6PowerButton..................................................3

2.7PumpPurgeButton..........................................3

2.8HourMeter.....................................................3

2.9HoursButton..................................................3

2.10DefrostLight.................................................3

2.11LowPressureProtection................................3

2.12DefrostCycle................................................3

2.13TemperatureSpecificOperation......................4

3. Maintenance.........................................................4

3.1AirFilter..........................................................4

3.2Storage..........................................................4

4. Service.................................................................4

4.1TechnicalDescription.......................................4

4.2Troubleshooting...............................................5

4.3AirMoverReplacement....................................5

4.4ThermistorReplacement..................................5

4.5CondensatePumpReplacement.......................6

4.6RefrigerantCharging........................................6

4.7Compressor/CapacitorReplacement................6

4.8GravityDrainOption.........................................6

5. Wiring Diagram.....................................................7

6. Service Parts List..................................................8

7. Warranty.............................................................10

SerialNo.___________________________

PurchaseDate______/______/_____

Dealer’sName___________________________________

Read the operation and maintenance instructions carefully before using this unit. Proper adherence to these instructions is essential to obtain maximum benefit from your Phoenix 200HT dehumidifier.

•ItisdesignedtobeusedINDOORS ONLY.

•Ifusedinawetarea,plugitintoaGROUND FAULT INTERRUPTER.

•DO NOTusethePhoenix200HTasabenchortable.

•Itmustalwaysbeusedintheuprightposition.

www.sylvane.com1 (800) 934-9194

Page 3: Installation, Operation & Service Instructions - Air …...3.1 Air Filter The Phoenix 200HT is equipped with a pleated fabric air filter that must be checked regularly. The standard

www.UsePhoenix.com • [email protected] 1-800-533-7533

2.3 Electrical RequirementsThePhoenix200HTplugsintoacommongroundedoutletona15Ampcircuit.Itdraws7.2Ampsat80°F,60%RH.Ifusedinawetarea,agroundfaultinterrupter(GFI)isrequired.

Ifanextensioncordisrequired,itmusthaveaminimumof14gaugeconductorsif25feetlongorlessand12gaugeconductorsifgreaterthan25feetlong.

2.4 Condensate RemovalThePhoenix200HTisequippedwithaninternalcondensatepumptoremovethewaterthatiscondensedduringdehumidification.Thisallowsthecondensatetobepumped30’withtheattachedhose.Ifthecondensatemustbepumpedmorethan20feetabovetheunit,asecondpumpmustbeaddedtorelaythecondensate.Ifthepumpfailsandtheunitmustbeusedbeforeitcanbereplaced,thecondensatecanbedrainedbygravity(seeSec.4.9).

2.5 DuctingAdetachablerectangularexhaustcollarissuppliedthatwillallow10”roundlay-flatducttobeattachedtothePhoenix200HToutlet.

Toattachductingtoacollar,puttheplasticductendthroughthecollarcenterandrolltheductendoutwardsothatitoverlapstheoutsideofthecollar.TheductandcollarmaythenbequicklyattachedtothePhoenix200HTbysnappingthecollaroverthefourscrewsatthebloweroutlet.

2.6 Power ButtonPressthePOWERbuttontoturnthedehumidifieronoroff.Whenstartingthedehumidifierthedisplaywillshowtheaccumulatedhours.PressthePOWERbuttonagaintoturnthedehumidifieroff.Thedisplaywillalsopoweroff.

2.7 Pump Purge ButtonDuringnormaloperationthepumpautomaticallycycleseveryfourminutes.PressthePURGEbuttontoremovecondensatemanuallyfromthereservoir.Thereareseveralwaystomanuallyremovewaterfromthereservoir:

1. PressthePURGEbuttononceandthepumpwillrunfor20seconds

2. PressandholdthePURGEbuttonandthepumpwillrunforupto30seconds

3. PressthePURGEbuttonwhilethedehumidifierispoweredoffandthepumpwillrunfor30seconds.

Alwaysmanuallypurgethewaterreservoirbeforetransportorstorage.Turnoffthepowerandallowthepluggedindehumidifiertorest15minutesbeforethefinalpurge.

2.8 Hour MeterThedigitalhourmeterdisplaysthecumulativeandjobtimethedehumidifierhasbeenturnedontothetenthofanhour.Thetotalandjobhoursmeasuredarestoredwhentheunitisunplugged.Theprevioustotalwillbedisplayedthenexttimetheunitisturnedon.ThejobhourscanberesetbypressingandholdingtheHOURSbuttonfor5secondswhentheunitisoperating.

2.9 HOURS ButtonPresstheHOURSbuttonwhenthedehumidifiercannotbepluggedinandthehourmeterneedstoberead.Thedigitalhourmeterwillbrieflydisplaythelastsavedcumulativetimefor10seconds.

2.10 DEFROST LightTheDEFROSTlightturnsonwhentheunitisindefrostmodeindicatingwhenthecompressorisoff.

DRYING TIP: Air’s ability to absorb moisture from wet surroundings and the Phoenix 200HT’s ability to remove moisture from that air is greatly improved at higher temperatures. We recommend that the area to be dried be heated to over 70°F if possible. Less drying time will be required and efficiency will improve.

2.11 Low Pressure ProtectionIfthelowsidepressuredropsto35PSIG,thelowpres-surecontrolopensandshutsofthecompressor.Itisanautomaticallyresetcontrol.Itsprimaryfunctionistopreventdamagetothecompressorifaleakdevelopsintherefrigerationsystem.

2.12 Defrost CycleIfthelowsiderefrigeranttemperaturedropsbelowthedefrostsetpoint,duetoexcessivefrostformationontheevaporatorcoil,thethermistoractivatesthesolidstatecontrolandthedefrostlight.Thecontrolcyclesthecompressor“off”and“on”bymonitoringthermistortemperature.Theairmoverwillcontinuetorun,causingairtoflowthroughtheevaporatorcoil.Theairwillmelttheicethatformedontheevaprator.

Whentheairtemperatureand/orhumidityincreases,theevaporatortemperaturewillriseandthethermistorwillendthedefrostcyclerestartingthecompressor.

Iftheevaporatortemperaturedoesnotreachthedesiredtemperature,thecompressorwillstartafter15minutes.Thesystemwillstartatimeddefrostcycle.Thetimeddefrostcycleensurestheunitwillcontinuetoremovewaterfromtheairincoolambientconditions.

www.sylvane.com1 (800) 934-9194

Page 4: Installation, Operation & Service Instructions - Air …...3.1 Air Filter The Phoenix 200HT is equipped with a pleated fabric air filter that must be checked regularly. The standard

4 www.UsePhoenix.com • [email protected] 1-800-533-7533

2.13 Temperature Specific OperationAbove90F–WhenthePhoenix200HTisusedinhightemperatureconditions(above90F),therefrigeranttemperatureinsidethecondenserrises.Byremovingthebypassmagnetfromthebypassopenings,additionalairflowisdirectedoverthecondenserandlessairflowisdirectedacrosstheevaporator.Theairflowdifferencesimprovethedehumidifierefficiency.

Below90F–WhenthePhoenix200HTisusedinlowtemperatureconditions(below90F),therefrigeranttemperatureinsidethecondenserlowers.Byaddingabypassmagnettothebypassopenings,additionalairflowisaddedthroughtheevaporator.Theairflowdifferenceimprovesthedehumidifierefficiency.

3 Maintenance3.1 Air FilterThePhoenix200HTisequippedwithapleatedfabricairfilterthatmustbecheckedregularly.ThestandardfilterisaMERV-11highefficiencyfilter.Operatingtheunitwithadirtyfilterwillreducethedehumidifier’scapacityandefficiencyandmaycausethecompressortocycleoffandonunnecessarilyonthedefrostcontrol.

IMPORTANT:DONOToperatetheunitwithoutthefilterorwithalesseffectivefilterastheheatexchangerandcoilsinsidetheunitcouldbecomecloggedandrequiredisassemblytoclean.

3.2 StorageTherearetwoissuestoconsiderwhenthePhoenix200HTisstoredbetweenuses.Bothpertaintothewatertrappedintheunit:damagecausedbyfreezingorbiologicalgrowth.Theeffectofthetrappedwatercanbegreatlyreducedifprecautionsaretakentoremoveasmuchaspossiblebeforestorage.

1. Usethepumppurgeswitch(seeSec.2.7)toreducethewaterlevelinthereservoir.

2. Stretchthehoseflattodrainitcompletely.Raiseoneendaboveyourheadandspooltodrainwateroutoftheotherend.

Iftheunitwillnotbeexposedtofreezingtemperatures,analternativetoreducebiologicalgrowthistoflushtheunitwithabio-fungicidethatisapprovedforusewithcopper,aluminumandpolyethylene.Toflush:

1. Runthehosetoadrain.

2. Plugintheunitbutdonotturniton.

3. Removetheairfilter.Slowlypouraquartofthechemicalthroughtheheatexchanger

4. Holdinthepumppurgeswitchtoreducethewaterlevelinthereservoir.

5. Flushwithwater.

4 Service

CAUTION: Servicing the Phoenix 200HT with its high pressure refrigerant system and high voltage circuitry presents a health hazard which could result in death, serious bodily injury, and/or property damage. Only qualified service people should service this unit.

4.1 Technical DescriptionThePhoenix200HTusesarefrigerationsystemsimilartoanairconditioner’storemoveheatandmoisturefromincomingair,andtoaddheattotheairthatisdischarged(seeFig.2).

Hot,highpressurerefrigerantgasisroutedfromthecompressortothecondensercoil(seeFigure2).Therefrigerantiscooledandcondensedbygivingupitsheattotheairthatisabouttobedischargedfromtheunit.Therefrigerantliquidthenpassesthroughafilter/drierandcapillarytubingwhichcausetherefrigerantpressureandtemperaturetodrop.Itnextenterstheevaporatorcoilwhereitabsorbsheatfromtheincomingairandevaporates.

Theevaporatoroperatesinafloodedcondition,whichmeansthatalltheevaporatortubescontainliquidrefrigerantduringnormaloperation.Afloodedevaporatorshouldmaintainconstantpressureandtemperatureacrosstheentirecoil,frominlettooutlet.

Themixtureofgasandliquidrefrigerantentertheaccumulatorafterleavingtheevaporatorcoil.Theaccumulatorpreventsanyliquidrefrigerantfromreaching

Figure 2: Refrigeration system

www.sylvane.com1 (800) 934-9194

Page 5: Installation, Operation & Service Instructions - Air …...3.1 Air Filter The Phoenix 200HT is equipped with a pleated fabric air filter that must be checked regularly. The standard

www.UsePhoenix.com • [email protected] 1-800-533-7533

thecompressor.Thecompressorevacuatesthecoolrefrigerantgasfromtheaccumulatorandcompressesittoahighpressureandtemperaturetorepeattheprocess.

4.2 TroubleshootingNo dehumidification, neither hour meter display nor compressor run and POWER button does not turn ON.

1. Unitunpluggedornopowertooutlet

2. Defectivecontrolboard

3. Looseconnectionininternalwiring

No dehumidification, neither hour meter display nor compressor run with POWER button ON.

1. Defectivecontrolboard

2. Looseconnectionininternalwiring

Some dehumidification, air mover runs continuously but compressor only runs sporadically.

1. Unitisindefrostcycle,DEFROSTlighton

2. Defrostthermistordefectiveorloose

3. Looseconnectionincompressorcircuit

4. Defectivecompressoroverload

5. Defectivecompressor

6. Lowrefrigerantcharge

7. Defrostthermistordetachedfromcoil

8.Looseconnectiontolowpressureswitch.

No dehumidification, air mover runs but compressor does not.

1. Badconnectionincompressorcircuit

2. Safetyfloatswitchclosed,checkpumpreservoir

3. Defectivecompressorcapacitor

4. Defectivecompressoroverload

5. Defectivecompressor

6. Defectivecontrolboard

7. Lowrefrigerantcharge

8.Looseconnectiontolowpressureswitch.

Air mover does not run. Compressor runs briefly but cycles on and off.

1. Looseconnectioninblowercircuit

2. Obstructionpreventsimpellerrotation

3. Defectiveairmover

4. Defectivecontrolboard.

Unit removes some water but not as much as expected.1. Airtemperatureand/orhumidityhavedropped2. Humiditymeterand/orthermometerusedareoutof

calibration3. Unithasentereddefrostcycle

4. Airfilterdirty5. Defectivedefrostthermistor6. Lowrefrigerantcharge7. Airleaksuchasloosefrontcover8. Defectivecompressor

9. Restrictiveexhaustorinletducting

10.Defrostthermistordetachedfromcoil

Unit runs but does not pump water.1. Hosekinkedorplugged2. Pumpmotordefective3. Pumpcheckvalveplugged4. Badconnectioninpumpcircuit5. Hosedisconnectedinternally6. Defectivecontrolboard

Unit pumps water automatically but not when PURGE button is pushed.

1.BadconnectioninPURGEbuttoncircuit

2.Defectivecontrolboard

Evaporator coil frosted continuously, low dehumidifying capacity.

1.Defrostthermistorlooseordefective

2.Lowrefrigerantcharge

Compressor runs with POWER button OFF.

1.Defectivecontrolboard

2.Upperhousingnotsealedtotower

No hour meter display when the HOURS button is pressed.

1. Batterychargeislow.Replacebattery

2. Defectivecontrolboard

4.3 Air Mover ReplacementTheblowerhasaPSCmotorandinternalthermaloverloadprotection.Ifdefective,thecompleteassemblymustbereplaced.

1. Unplugpowercord

2. Removethefrontcover

3. Removethe5screwsattachingblowerinletring

4. Removethe4screwsmountingimpellertoundersideofbaseplate

5. Disconnecttheblowerleads

6. Reassemblethenewblowerusingtheaboveprocedureinreverse

4.4 Thermistor ReplacementThedefrostthermistorisattachedtotherefrigerantsuctionlinebetweentheaccumulatorandtheevaporator.

www.sylvane.com1 (800) 934-9194

Page 6: Installation, Operation & Service Instructions - Air …...3.1 Air Filter The Phoenix 200HT is equipped with a pleated fabric air filter that must be checked regularly. The standard

6 www.UsePhoenix.com • [email protected] 1-800-533-7533

Toreplacethermistor:

1. Unplugthedehumidifier

2. Removethefrontcover

3. Removealuminumtape

4. Removecontrolpanel

5. Removerightpanelscrews,viewedfromfront,attachingfrontfilterbracket,andevaporator

6. Removecontrolboard

7. Detachthermistorfromcontrolboardjumper,(EVAP)

8. Reassemblethermistoranddehumidifierusingtheaboveprocedureinreverse

4.5 Condensate Pump ReplacementTheinternalcondensatepumpremoveswaterthatcollectsinthereservoir.

Toreplacethecondensatepump:

1. Unplugtheunit

2. Removetherearskidplate

3. Unplugthepumpwiresfromthewireharness

4. Removethecondensatehoseandthescrewattachingthepumpbrackettothebase

5. Replacethepump,hose,wiring,bolts,andcoverinthereverseorder

4.6 Refrigerant ChargingIftherefrigerantchargeislostduetoserviceoraleak,anewchargemustbeaccuratelyweighedin.Ifanyoftheoldchargeisleftinthesystem,itmustberemovedbeforeweighinginthenewcharge.Refertotheunitnameplateforthecorrectchargeweightandrefrigeranttype.

4.7 Compressor/Capacitor ReplacementThiscompressorisequippedwithatwoterminalexternaloverload,runcapacitor,butnostartcapacitor.

4.8 Gravity Drain OptionIfthecondensatepumpfailsandcannotbereplacedimmediately,thePhoenix200HTcanbeusedbydrainingbygravity.

1. Unplugtheunitandremovethefrontcover.

2. Pushtheplasticplugontherightside(seeFig.4)outfrominsidetheunit.

3. Locatetheheavyvinylhosethatconnectsthedrainpantothecondensatepump.Pulltheendoutofthepump.

4. Removetiewrapholdingdraintubetosuctionline.

5. Pushthatendofthevinylhosethroughtheholeintherightside.

6. Connectagardenhoseandrunittoadrain.Keep

thehoseasflattotheflooraspossibletoavoidairpocketsthatwouldhinderdraining.Placingtheunitonsomethingabovethefloorwillalsoimprovedraining.

www.sylvane.com1 (800) 934-9194

Page 7: Installation, Operation & Service Instructions - Air …...3.1 Air Filter The Phoenix 200HT is equipped with a pleated fabric air filter that must be checked regularly. The standard

www.UsePhoenix.com • [email protected] 1-800-533-7533

5 Wiring Diagram

LLC Therma-Stor

www.sylvane.com1 (800) 934-9194

Page 8: Installation, Operation & Service Instructions - Air …...3.1 Air Filter The Phoenix 200HT is equipped with a pleated fabric air filter that must be checked regularly. The standard

8 www.UsePhoenix.com • [email protected] 1-800-533-7533

Specifications subject to change without notice.

6 Service PartsItem Description Qty Part No.

1 TopCover 1 4028583

2 TopCoverHinge 2 4027267

3 Wheel12”Gray 2 4026304

4 CotterPin3/32” 1 1284404

5 AirFilter1.75x15.5x19.5 1 4021475

6 HosePlastic0.56IDx24 1 4029894

7 HosePlastic0.38ID 1 4021909

8 HosePlastic0.25IDx33 1 4024916

9 CouplingBody0.25Tube 1 4024910

10 CouplingInsert0.38Tube 1 4023080

11 ControlBoard 1 4030083

12 CapacitorCompressor 45mfd 370V1 4026687

13 CapacitorImpeller15mfd 370V 1 4025224

14 Thermistor 1 4027278

15 BatteryAA 1 1912500

16 Cord115V25’ 1 4025078

17 TOS,8.2KBTU,R410A 1 4029182

18 OverloadCompressor 1 4029183

19 EvaporatorCoil 1 4028565

20 CondenserCoil 1 4028566

21 CondensatePump 1 4023649

22 FanMotorizedImpeller 1 4026657

23 InletRing 1 4028564

24 WireDuctCollar 1 4028593

25 FilterDrier(notshown) 1 4029510

26 WireHarness(notshown) 1 4030084

27 Handle 1 4026094

28 BoltM10-1.5X35 2 1177792

29 WasherM10X30 2 4025517

30 HexLockNutM10-1.5 2 1223780

1

3,4

6

7,8,9,10

11,15

16

17,18

19

20

2122

23

24

27,28,29,30

5

12

13

14

2

www.sylvane.com1 (800) 934-9194

Page 9: Installation, Operation & Service Instructions - Air …...3.1 Air Filter The Phoenix 200HT is equipped with a pleated fabric air filter that must be checked regularly. The standard

www.UsePhoenix.com • [email protected] 1-800-533-7533

Thispageintentionallyleftblank.

www.sylvane.com1 (800) 934-9194

Page 10: Installation, Operation & Service Instructions - Air …...3.1 Air Filter The Phoenix 200HT is equipped with a pleated fabric air filter that must be checked regularly. The standard

10 www.UsePhoenix.com • [email protected] 1-800-533-7533

Phoenix 200HT Dehumidifier Limited Warranty

Warrantor:

Therma-StorLLC4201LienRdMadison,WI537041-800-533-7533

Who Is Covered:Thiswarrantyextendsonlytotheoriginalend-userofthePhoenix200HTdehumidifier,andmaynotbeassignedortransferred.

First Year Warranty:Therma-Storwarrantsthat,forone(1)yearthePhoenix200HTdehumidifierwilloperatefreefromanydefectsinmaterialsandworkmanship,orTherma-Storwill,atitsoption,repairorreplacethedefectivepart(s),freeofanycharge.

Second Through Fifth Year Warranty:Therma-Storfurtherwarrantsthatforaperiodoffive(5)years,thecondenser,evaporator,andcompressorofthePhoenix200HTdehumidifierwilloperatefreeofanydefectsinmaterialorworkmanship,orTherma-Stor,atitsoption,willrepairorreplacethedefectivepart(s),providedthatalllaborandtransportationchargesforthepart(s)shallbebornebytheend-user.

End-User Responsibilities:WarrantyservicemustbeperformedbyaServicerauthorizedbyTherma-Stor.Iftheend-userisunabletolocateorobtainwarrantyservicefromanauthorizedServicer,heshouldcallTherma-StorattheabovenumberandaskfortheTherma-StorServiceDepartment.,whichwillthenarrangeforcoveredwarrantyservice.Warrantyservicewillbeperformedduringnormalworkinghours.

Theend-usermustpresentproofofpurchase(lease)uponrequest,byreasonableandreliablemeans.Theend-userisresponsiblefornormalcare.Thiswarrantydoesnotcoveranydefect,malfunction,etc.resultingfrommisuse,abuse,lackofnormalcare,corrosion,freezing,tampering,modification,unauthorizedorimproperrepairorinstallation,accident,actsofnatureoranyothercausebeyondTherma-Stor’reasonablecontrol.

Limitations and Exclusions:IfanyPhoenix200HTDehumidifierpartisrepairedorreplaced,thenewpartshallbewarrantedforonlytheremainderoftheoriginalwarrantyperiodapplicablethereto(butallwarrantyperiodswillbeextendedbytheperiodoftime,ifany,thatthePhoenix200HTDehumidifierisoutofservicewhileawaitingcoveredwarrantyservice).

UPONTHEEXPIRATIONOFTHEWRITTENWARRANTYAPPLICABLETOTHEPhoenix200HTDEHUMIDIFIERORANYPARTTHEREOF,ALLOTHERWARRANTIESIMPLIEDBYLAW,INCLUDINGMERCHANTABILITYANDFITNESSFORAPARTICULARPURPOSE,SHALLALSOEXPIRE.ALLWARRANTIESMADEBYTherma-StorARESETFORTHHEREIN,ANDNOCLAIMMAYBEMADEAGAINSTTherma-StorBASEDONANYORALWARRANTY.INNOEVENTSHALLTherma-Stor,INCONNECTIONWITHTHESALE,INSTALLATION,USE,REPAIRORREPLACEMENTOFANYPhoenix200HTDEHUMIDIFIERORPARTTHEREOFBELIABLEUNDERANYLEGALTHEORYFORANYSPECIAL,INDIRECTORCONSEQUENTIALDAMAGESINCLUDINGWITHOUTLIMITATIONWATERDAMAGE(THEEND-USERSHOULDTAKEPRECAUTIONSAGAINSTSAME),LOSTPROFITS,DELAY,ORLOSSOFUSEORDAMAGETOANYREALORPERSONALPROPERTY.

Somestatesdonotallowlimitationsonhowlonganimpliedwarrantylasts,andsomedonotallowtheexclusionorlimitationofincidentalorconsequentialdamages,sooneorbothoftheselimitationmaynotapplytoyou.

Legal Rights:Thiswarrantygivesyouspecificlegalrights,andyoumayalsohaveotherrightswhichvaryfromstatetostate.

www.sylvane.com1 (800) 934-9194