Owner’s Manual — Phoenix 200HTInstallation, Operation & Service Instructions
Read and Save These Instructions
The Phoenix 200HT LGR, High Capacity Dehumidifier
Phoenix 200HT4029970Specifications subject to change without notice.
TS-621 08/10
4201LienRd.•Madison,WI53704
• Patented Bypass Technology
• High Capacity - Removes135pintsperdayatAHAM
• 7.2 amps - Removesover6.5pints/kWh.
• R-410A Refrigerant
• More Grain Depression - DrierairfromanLGRfinishesjobsquickerversusaconventionalrefrigerantdehumidifier.
• Focused Airflow - Patentedfocusedoutletdirectsairdownwardacrossthewetsurface.
• Motorized Impeller - 380CFM;Fasterdryingandsuperiorstaticpressureforducting.
• Multiple Ducting Options - 12”intake,10”exhaust.
• Solid State Controls - Easytoreadandoperate.
• Recessed 12” Wheels - Allowsgreatermaneuverabilityonthejobsiteandefficientstorage.Rollsoverobstacleswithease.
• MERV-11 Pleated Media Air Filter
ThePhoenix200HTisoneofthemosteffectiveandversatiledryingdevicesavailable.ThePhoenix200HTfeatureshighercapacityandsuperiorefficiencycomparedtootherrefrigerantdehumidifiers,removing135pintsperdayatAHAMwhiledrawingonly7.2ampsofelectricity.
The200HTalsofeaturesPhoenix’spatentedbypasssystem.Athighertemperatures,wheretypicalLGRsloseeffectiveness,patentedBypassTechnologyhelpsthePhoenix200HTcontinuetoremovemoisture,leadingtofasterevaporation,quickerdrying,andeliminationoftheneedtoremoveequipmentfortemperaturecontrol.
www.sylvane.com1 (800) 934-9194
![Page 2: Installation, Operation & Service Instructions - Air …...3.1 Air Filter The Phoenix 200HT is equipped with a pleated fabric air filter that must be checked regularly. The standard](https://reader033.fdocuments.us/reader033/viewer/2022053018/5f1e251852eeff55521be6ab/html5/thumbnails/2.jpg)
2 www.UsePhoenix.com • [email protected] 1-800-533-7533
1 SpecificationsPart No. 4029970
Power 110-120Vac,7.2amps
Water 135pints/day@AHAM(80°F,60%)Removal
Refrigerant 2lbs.2oz.R410aCharge
Blower 380CFM InternalCondensatePumpwith20’lift, 30’vinylhose
Operating 33°Fto125°FRange
Filters 16”x20”x2”PleatedMediaMERV-11
Duct Intake–12”Flex-DuctOptions Exhaust–10”Lay-Flat
Warranty Fiveyears; Firstyear100%ofPartsandLabor Second-fifthyear100%ofPartsofsealed refrigerationsystem.
Dimensions Width20”,Height40”,Depth23”
Weight 130lbs.
2 Operation2.1 Transporting the Phoenix 200HT ThePhoenix200HTmustalwaysbeuprightwhentransportedbyvehicle.Itmaybetippedontoitshandleandbackforloadingandmovingbyhand.
2.2 LocationNote the following precautions when locating the Phoenix 200HT:
• ItisdesignedtobeusedINDOORS ONLY.
• Ifusedinawetarea,plugitintoaGROUND FAULT INTERRUPTER.
• DO NOTusethePhoenix200HTasabenchortable.
•Itmustalwaysbeusedintheuprightposition.
• Theairinletontop&thesideoutletmustbeatleast1footfromwallsandotherobstructionstoairflow.
Table of ContentsIntroduction................................................................1
1. Specifications........................................................2
2. Operation.............................................................2
2.1TransportingthePhoenix200HT.......................2
2.2Location.........................................................2
2.3ElectricalRequirements...................................3
2.4CondensateRemoval.......................................3
2.5Ducting...........................................................3
2.6PowerButton..................................................3
2.7PumpPurgeButton..........................................3
2.8HourMeter.....................................................3
2.9HoursButton..................................................3
2.10DefrostLight.................................................3
2.11LowPressureProtection................................3
2.12DefrostCycle................................................3
2.13TemperatureSpecificOperation......................4
3. Maintenance.........................................................4
3.1AirFilter..........................................................4
3.2Storage..........................................................4
4. Service.................................................................4
4.1TechnicalDescription.......................................4
4.2Troubleshooting...............................................5
4.3AirMoverReplacement....................................5
4.4ThermistorReplacement..................................5
4.5CondensatePumpReplacement.......................6
4.6RefrigerantCharging........................................6
4.7Compressor/CapacitorReplacement................6
4.8GravityDrainOption.........................................6
5. Wiring Diagram.....................................................7
6. Service Parts List..................................................8
7. Warranty.............................................................10
SerialNo.___________________________
PurchaseDate______/______/_____
Dealer’sName___________________________________
Read the operation and maintenance instructions carefully before using this unit. Proper adherence to these instructions is essential to obtain maximum benefit from your Phoenix 200HT dehumidifier.
•ItisdesignedtobeusedINDOORS ONLY.
•Ifusedinawetarea,plugitintoaGROUND FAULT INTERRUPTER.
•DO NOTusethePhoenix200HTasabenchortable.
•Itmustalwaysbeusedintheuprightposition.
www.sylvane.com1 (800) 934-9194
![Page 3: Installation, Operation & Service Instructions - Air …...3.1 Air Filter The Phoenix 200HT is equipped with a pleated fabric air filter that must be checked regularly. The standard](https://reader033.fdocuments.us/reader033/viewer/2022053018/5f1e251852eeff55521be6ab/html5/thumbnails/3.jpg)
www.UsePhoenix.com • [email protected] 1-800-533-7533
2.3 Electrical RequirementsThePhoenix200HTplugsintoacommongroundedoutletona15Ampcircuit.Itdraws7.2Ampsat80°F,60%RH.Ifusedinawetarea,agroundfaultinterrupter(GFI)isrequired.
Ifanextensioncordisrequired,itmusthaveaminimumof14gaugeconductorsif25feetlongorlessand12gaugeconductorsifgreaterthan25feetlong.
2.4 Condensate RemovalThePhoenix200HTisequippedwithaninternalcondensatepumptoremovethewaterthatiscondensedduringdehumidification.Thisallowsthecondensatetobepumped30’withtheattachedhose.Ifthecondensatemustbepumpedmorethan20feetabovetheunit,asecondpumpmustbeaddedtorelaythecondensate.Ifthepumpfailsandtheunitmustbeusedbeforeitcanbereplaced,thecondensatecanbedrainedbygravity(seeSec.4.9).
2.5 DuctingAdetachablerectangularexhaustcollarissuppliedthatwillallow10”roundlay-flatducttobeattachedtothePhoenix200HToutlet.
Toattachductingtoacollar,puttheplasticductendthroughthecollarcenterandrolltheductendoutwardsothatitoverlapstheoutsideofthecollar.TheductandcollarmaythenbequicklyattachedtothePhoenix200HTbysnappingthecollaroverthefourscrewsatthebloweroutlet.
2.6 Power ButtonPressthePOWERbuttontoturnthedehumidifieronoroff.Whenstartingthedehumidifierthedisplaywillshowtheaccumulatedhours.PressthePOWERbuttonagaintoturnthedehumidifieroff.Thedisplaywillalsopoweroff.
2.7 Pump Purge ButtonDuringnormaloperationthepumpautomaticallycycleseveryfourminutes.PressthePURGEbuttontoremovecondensatemanuallyfromthereservoir.Thereareseveralwaystomanuallyremovewaterfromthereservoir:
1. PressthePURGEbuttononceandthepumpwillrunfor20seconds
2. PressandholdthePURGEbuttonandthepumpwillrunforupto30seconds
3. PressthePURGEbuttonwhilethedehumidifierispoweredoffandthepumpwillrunfor30seconds.
Alwaysmanuallypurgethewaterreservoirbeforetransportorstorage.Turnoffthepowerandallowthepluggedindehumidifiertorest15minutesbeforethefinalpurge.
2.8 Hour MeterThedigitalhourmeterdisplaysthecumulativeandjobtimethedehumidifierhasbeenturnedontothetenthofanhour.Thetotalandjobhoursmeasuredarestoredwhentheunitisunplugged.Theprevioustotalwillbedisplayedthenexttimetheunitisturnedon.ThejobhourscanberesetbypressingandholdingtheHOURSbuttonfor5secondswhentheunitisoperating.
2.9 HOURS ButtonPresstheHOURSbuttonwhenthedehumidifiercannotbepluggedinandthehourmeterneedstoberead.Thedigitalhourmeterwillbrieflydisplaythelastsavedcumulativetimefor10seconds.
2.10 DEFROST LightTheDEFROSTlightturnsonwhentheunitisindefrostmodeindicatingwhenthecompressorisoff.
DRYING TIP: Air’s ability to absorb moisture from wet surroundings and the Phoenix 200HT’s ability to remove moisture from that air is greatly improved at higher temperatures. We recommend that the area to be dried be heated to over 70°F if possible. Less drying time will be required and efficiency will improve.
2.11 Low Pressure ProtectionIfthelowsidepressuredropsto35PSIG,thelowpres-surecontrolopensandshutsofthecompressor.Itisanautomaticallyresetcontrol.Itsprimaryfunctionistopreventdamagetothecompressorifaleakdevelopsintherefrigerationsystem.
2.12 Defrost CycleIfthelowsiderefrigeranttemperaturedropsbelowthedefrostsetpoint,duetoexcessivefrostformationontheevaporatorcoil,thethermistoractivatesthesolidstatecontrolandthedefrostlight.Thecontrolcyclesthecompressor“off”and“on”bymonitoringthermistortemperature.Theairmoverwillcontinuetorun,causingairtoflowthroughtheevaporatorcoil.Theairwillmelttheicethatformedontheevaprator.
Whentheairtemperatureand/orhumidityincreases,theevaporatortemperaturewillriseandthethermistorwillendthedefrostcyclerestartingthecompressor.
Iftheevaporatortemperaturedoesnotreachthedesiredtemperature,thecompressorwillstartafter15minutes.Thesystemwillstartatimeddefrostcycle.Thetimeddefrostcycleensurestheunitwillcontinuetoremovewaterfromtheairincoolambientconditions.
www.sylvane.com1 (800) 934-9194
![Page 4: Installation, Operation & Service Instructions - Air …...3.1 Air Filter The Phoenix 200HT is equipped with a pleated fabric air filter that must be checked regularly. The standard](https://reader033.fdocuments.us/reader033/viewer/2022053018/5f1e251852eeff55521be6ab/html5/thumbnails/4.jpg)
4 www.UsePhoenix.com • [email protected] 1-800-533-7533
2.13 Temperature Specific OperationAbove90F–WhenthePhoenix200HTisusedinhightemperatureconditions(above90F),therefrigeranttemperatureinsidethecondenserrises.Byremovingthebypassmagnetfromthebypassopenings,additionalairflowisdirectedoverthecondenserandlessairflowisdirectedacrosstheevaporator.Theairflowdifferencesimprovethedehumidifierefficiency.
Below90F–WhenthePhoenix200HTisusedinlowtemperatureconditions(below90F),therefrigeranttemperatureinsidethecondenserlowers.Byaddingabypassmagnettothebypassopenings,additionalairflowisaddedthroughtheevaporator.Theairflowdifferenceimprovesthedehumidifierefficiency.
3 Maintenance3.1 Air FilterThePhoenix200HTisequippedwithapleatedfabricairfilterthatmustbecheckedregularly.ThestandardfilterisaMERV-11highefficiencyfilter.Operatingtheunitwithadirtyfilterwillreducethedehumidifier’scapacityandefficiencyandmaycausethecompressortocycleoffandonunnecessarilyonthedefrostcontrol.
IMPORTANT:DONOToperatetheunitwithoutthefilterorwithalesseffectivefilterastheheatexchangerandcoilsinsidetheunitcouldbecomecloggedandrequiredisassemblytoclean.
3.2 StorageTherearetwoissuestoconsiderwhenthePhoenix200HTisstoredbetweenuses.Bothpertaintothewatertrappedintheunit:damagecausedbyfreezingorbiologicalgrowth.Theeffectofthetrappedwatercanbegreatlyreducedifprecautionsaretakentoremoveasmuchaspossiblebeforestorage.
1. Usethepumppurgeswitch(seeSec.2.7)toreducethewaterlevelinthereservoir.
2. Stretchthehoseflattodrainitcompletely.Raiseoneendaboveyourheadandspooltodrainwateroutoftheotherend.
Iftheunitwillnotbeexposedtofreezingtemperatures,analternativetoreducebiologicalgrowthistoflushtheunitwithabio-fungicidethatisapprovedforusewithcopper,aluminumandpolyethylene.Toflush:
1. Runthehosetoadrain.
2. Plugintheunitbutdonotturniton.
3. Removetheairfilter.Slowlypouraquartofthechemicalthroughtheheatexchanger
4. Holdinthepumppurgeswitchtoreducethewaterlevelinthereservoir.
5. Flushwithwater.
4 Service
CAUTION: Servicing the Phoenix 200HT with its high pressure refrigerant system and high voltage circuitry presents a health hazard which could result in death, serious bodily injury, and/or property damage. Only qualified service people should service this unit.
4.1 Technical DescriptionThePhoenix200HTusesarefrigerationsystemsimilartoanairconditioner’storemoveheatandmoisturefromincomingair,andtoaddheattotheairthatisdischarged(seeFig.2).
Hot,highpressurerefrigerantgasisroutedfromthecompressortothecondensercoil(seeFigure2).Therefrigerantiscooledandcondensedbygivingupitsheattotheairthatisabouttobedischargedfromtheunit.Therefrigerantliquidthenpassesthroughafilter/drierandcapillarytubingwhichcausetherefrigerantpressureandtemperaturetodrop.Itnextenterstheevaporatorcoilwhereitabsorbsheatfromtheincomingairandevaporates.
Theevaporatoroperatesinafloodedcondition,whichmeansthatalltheevaporatortubescontainliquidrefrigerantduringnormaloperation.Afloodedevaporatorshouldmaintainconstantpressureandtemperatureacrosstheentirecoil,frominlettooutlet.
Themixtureofgasandliquidrefrigerantentertheaccumulatorafterleavingtheevaporatorcoil.Theaccumulatorpreventsanyliquidrefrigerantfromreaching
Figure 2: Refrigeration system
www.sylvane.com1 (800) 934-9194
![Page 5: Installation, Operation & Service Instructions - Air …...3.1 Air Filter The Phoenix 200HT is equipped with a pleated fabric air filter that must be checked regularly. The standard](https://reader033.fdocuments.us/reader033/viewer/2022053018/5f1e251852eeff55521be6ab/html5/thumbnails/5.jpg)
www.UsePhoenix.com • [email protected] 1-800-533-7533
thecompressor.Thecompressorevacuatesthecoolrefrigerantgasfromtheaccumulatorandcompressesittoahighpressureandtemperaturetorepeattheprocess.
4.2 TroubleshootingNo dehumidification, neither hour meter display nor compressor run and POWER button does not turn ON.
1. Unitunpluggedornopowertooutlet
2. Defectivecontrolboard
3. Looseconnectionininternalwiring
No dehumidification, neither hour meter display nor compressor run with POWER button ON.
1. Defectivecontrolboard
2. Looseconnectionininternalwiring
Some dehumidification, air mover runs continuously but compressor only runs sporadically.
1. Unitisindefrostcycle,DEFROSTlighton
2. Defrostthermistordefectiveorloose
3. Looseconnectionincompressorcircuit
4. Defectivecompressoroverload
5. Defectivecompressor
6. Lowrefrigerantcharge
7. Defrostthermistordetachedfromcoil
8.Looseconnectiontolowpressureswitch.
No dehumidification, air mover runs but compressor does not.
1. Badconnectionincompressorcircuit
2. Safetyfloatswitchclosed,checkpumpreservoir
3. Defectivecompressorcapacitor
4. Defectivecompressoroverload
5. Defectivecompressor
6. Defectivecontrolboard
7. Lowrefrigerantcharge
8.Looseconnectiontolowpressureswitch.
Air mover does not run. Compressor runs briefly but cycles on and off.
1. Looseconnectioninblowercircuit
2. Obstructionpreventsimpellerrotation
3. Defectiveairmover
4. Defectivecontrolboard.
Unit removes some water but not as much as expected.1. Airtemperatureand/orhumidityhavedropped2. Humiditymeterand/orthermometerusedareoutof
calibration3. Unithasentereddefrostcycle
4. Airfilterdirty5. Defectivedefrostthermistor6. Lowrefrigerantcharge7. Airleaksuchasloosefrontcover8. Defectivecompressor
9. Restrictiveexhaustorinletducting
10.Defrostthermistordetachedfromcoil
Unit runs but does not pump water.1. Hosekinkedorplugged2. Pumpmotordefective3. Pumpcheckvalveplugged4. Badconnectioninpumpcircuit5. Hosedisconnectedinternally6. Defectivecontrolboard
Unit pumps water automatically but not when PURGE button is pushed.
1.BadconnectioninPURGEbuttoncircuit
2.Defectivecontrolboard
Evaporator coil frosted continuously, low dehumidifying capacity.
1.Defrostthermistorlooseordefective
2.Lowrefrigerantcharge
Compressor runs with POWER button OFF.
1.Defectivecontrolboard
2.Upperhousingnotsealedtotower
No hour meter display when the HOURS button is pressed.
1. Batterychargeislow.Replacebattery
2. Defectivecontrolboard
4.3 Air Mover ReplacementTheblowerhasaPSCmotorandinternalthermaloverloadprotection.Ifdefective,thecompleteassemblymustbereplaced.
1. Unplugpowercord
2. Removethefrontcover
3. Removethe5screwsattachingblowerinletring
4. Removethe4screwsmountingimpellertoundersideofbaseplate
5. Disconnecttheblowerleads
6. Reassemblethenewblowerusingtheaboveprocedureinreverse
4.4 Thermistor ReplacementThedefrostthermistorisattachedtotherefrigerantsuctionlinebetweentheaccumulatorandtheevaporator.
www.sylvane.com1 (800) 934-9194
![Page 6: Installation, Operation & Service Instructions - Air …...3.1 Air Filter The Phoenix 200HT is equipped with a pleated fabric air filter that must be checked regularly. The standard](https://reader033.fdocuments.us/reader033/viewer/2022053018/5f1e251852eeff55521be6ab/html5/thumbnails/6.jpg)
6 www.UsePhoenix.com • [email protected] 1-800-533-7533
Toreplacethermistor:
1. Unplugthedehumidifier
2. Removethefrontcover
3. Removealuminumtape
4. Removecontrolpanel
5. Removerightpanelscrews,viewedfromfront,attachingfrontfilterbracket,andevaporator
6. Removecontrolboard
7. Detachthermistorfromcontrolboardjumper,(EVAP)
8. Reassemblethermistoranddehumidifierusingtheaboveprocedureinreverse
4.5 Condensate Pump ReplacementTheinternalcondensatepumpremoveswaterthatcollectsinthereservoir.
Toreplacethecondensatepump:
1. Unplugtheunit
2. Removetherearskidplate
3. Unplugthepumpwiresfromthewireharness
4. Removethecondensatehoseandthescrewattachingthepumpbrackettothebase
5. Replacethepump,hose,wiring,bolts,andcoverinthereverseorder
4.6 Refrigerant ChargingIftherefrigerantchargeislostduetoserviceoraleak,anewchargemustbeaccuratelyweighedin.Ifanyoftheoldchargeisleftinthesystem,itmustberemovedbeforeweighinginthenewcharge.Refertotheunitnameplateforthecorrectchargeweightandrefrigeranttype.
4.7 Compressor/Capacitor ReplacementThiscompressorisequippedwithatwoterminalexternaloverload,runcapacitor,butnostartcapacitor.
4.8 Gravity Drain OptionIfthecondensatepumpfailsandcannotbereplacedimmediately,thePhoenix200HTcanbeusedbydrainingbygravity.
1. Unplugtheunitandremovethefrontcover.
2. Pushtheplasticplugontherightside(seeFig.4)outfrominsidetheunit.
3. Locatetheheavyvinylhosethatconnectsthedrainpantothecondensatepump.Pulltheendoutofthepump.
4. Removetiewrapholdingdraintubetosuctionline.
5. Pushthatendofthevinylhosethroughtheholeintherightside.
6. Connectagardenhoseandrunittoadrain.Keep
thehoseasflattotheflooraspossibletoavoidairpocketsthatwouldhinderdraining.Placingtheunitonsomethingabovethefloorwillalsoimprovedraining.
www.sylvane.com1 (800) 934-9194
![Page 7: Installation, Operation & Service Instructions - Air …...3.1 Air Filter The Phoenix 200HT is equipped with a pleated fabric air filter that must be checked regularly. The standard](https://reader033.fdocuments.us/reader033/viewer/2022053018/5f1e251852eeff55521be6ab/html5/thumbnails/7.jpg)
www.UsePhoenix.com • [email protected] 1-800-533-7533
5 Wiring Diagram
LLC Therma-Stor
www.sylvane.com1 (800) 934-9194
![Page 8: Installation, Operation & Service Instructions - Air …...3.1 Air Filter The Phoenix 200HT is equipped with a pleated fabric air filter that must be checked regularly. The standard](https://reader033.fdocuments.us/reader033/viewer/2022053018/5f1e251852eeff55521be6ab/html5/thumbnails/8.jpg)
8 www.UsePhoenix.com • [email protected] 1-800-533-7533
Specifications subject to change without notice.
6 Service PartsItem Description Qty Part No.
1 TopCover 1 4028583
2 TopCoverHinge 2 4027267
3 Wheel12”Gray 2 4026304
4 CotterPin3/32” 1 1284404
5 AirFilter1.75x15.5x19.5 1 4021475
6 HosePlastic0.56IDx24 1 4029894
7 HosePlastic0.38ID 1 4021909
8 HosePlastic0.25IDx33 1 4024916
9 CouplingBody0.25Tube 1 4024910
10 CouplingInsert0.38Tube 1 4023080
11 ControlBoard 1 4030083
12 CapacitorCompressor 45mfd 370V1 4026687
13 CapacitorImpeller15mfd 370V 1 4025224
14 Thermistor 1 4027278
15 BatteryAA 1 1912500
16 Cord115V25’ 1 4025078
17 TOS,8.2KBTU,R410A 1 4029182
18 OverloadCompressor 1 4029183
19 EvaporatorCoil 1 4028565
20 CondenserCoil 1 4028566
21 CondensatePump 1 4023649
22 FanMotorizedImpeller 1 4026657
23 InletRing 1 4028564
24 WireDuctCollar 1 4028593
25 FilterDrier(notshown) 1 4029510
26 WireHarness(notshown) 1 4030084
27 Handle 1 4026094
28 BoltM10-1.5X35 2 1177792
29 WasherM10X30 2 4025517
30 HexLockNutM10-1.5 2 1223780
1
3,4
6
7,8,9,10
11,15
16
17,18
19
20
2122
23
24
27,28,29,30
5
12
13
14
2
www.sylvane.com1 (800) 934-9194
![Page 9: Installation, Operation & Service Instructions - Air …...3.1 Air Filter The Phoenix 200HT is equipped with a pleated fabric air filter that must be checked regularly. The standard](https://reader033.fdocuments.us/reader033/viewer/2022053018/5f1e251852eeff55521be6ab/html5/thumbnails/9.jpg)
www.UsePhoenix.com • [email protected] 1-800-533-7533
Thispageintentionallyleftblank.
www.sylvane.com1 (800) 934-9194
![Page 10: Installation, Operation & Service Instructions - Air …...3.1 Air Filter The Phoenix 200HT is equipped with a pleated fabric air filter that must be checked regularly. The standard](https://reader033.fdocuments.us/reader033/viewer/2022053018/5f1e251852eeff55521be6ab/html5/thumbnails/10.jpg)
10 www.UsePhoenix.com • [email protected] 1-800-533-7533
Phoenix 200HT Dehumidifier Limited Warranty
Warrantor:
Therma-StorLLC4201LienRdMadison,WI537041-800-533-7533
Who Is Covered:Thiswarrantyextendsonlytotheoriginalend-userofthePhoenix200HTdehumidifier,andmaynotbeassignedortransferred.
First Year Warranty:Therma-Storwarrantsthat,forone(1)yearthePhoenix200HTdehumidifierwilloperatefreefromanydefectsinmaterialsandworkmanship,orTherma-Storwill,atitsoption,repairorreplacethedefectivepart(s),freeofanycharge.
Second Through Fifth Year Warranty:Therma-Storfurtherwarrantsthatforaperiodoffive(5)years,thecondenser,evaporator,andcompressorofthePhoenix200HTdehumidifierwilloperatefreeofanydefectsinmaterialorworkmanship,orTherma-Stor,atitsoption,willrepairorreplacethedefectivepart(s),providedthatalllaborandtransportationchargesforthepart(s)shallbebornebytheend-user.
End-User Responsibilities:WarrantyservicemustbeperformedbyaServicerauthorizedbyTherma-Stor.Iftheend-userisunabletolocateorobtainwarrantyservicefromanauthorizedServicer,heshouldcallTherma-StorattheabovenumberandaskfortheTherma-StorServiceDepartment.,whichwillthenarrangeforcoveredwarrantyservice.Warrantyservicewillbeperformedduringnormalworkinghours.
Theend-usermustpresentproofofpurchase(lease)uponrequest,byreasonableandreliablemeans.Theend-userisresponsiblefornormalcare.Thiswarrantydoesnotcoveranydefect,malfunction,etc.resultingfrommisuse,abuse,lackofnormalcare,corrosion,freezing,tampering,modification,unauthorizedorimproperrepairorinstallation,accident,actsofnatureoranyothercausebeyondTherma-Stor’reasonablecontrol.
Limitations and Exclusions:IfanyPhoenix200HTDehumidifierpartisrepairedorreplaced,thenewpartshallbewarrantedforonlytheremainderoftheoriginalwarrantyperiodapplicablethereto(butallwarrantyperiodswillbeextendedbytheperiodoftime,ifany,thatthePhoenix200HTDehumidifierisoutofservicewhileawaitingcoveredwarrantyservice).
UPONTHEEXPIRATIONOFTHEWRITTENWARRANTYAPPLICABLETOTHEPhoenix200HTDEHUMIDIFIERORANYPARTTHEREOF,ALLOTHERWARRANTIESIMPLIEDBYLAW,INCLUDINGMERCHANTABILITYANDFITNESSFORAPARTICULARPURPOSE,SHALLALSOEXPIRE.ALLWARRANTIESMADEBYTherma-StorARESETFORTHHEREIN,ANDNOCLAIMMAYBEMADEAGAINSTTherma-StorBASEDONANYORALWARRANTY.INNOEVENTSHALLTherma-Stor,INCONNECTIONWITHTHESALE,INSTALLATION,USE,REPAIRORREPLACEMENTOFANYPhoenix200HTDEHUMIDIFIERORPARTTHEREOFBELIABLEUNDERANYLEGALTHEORYFORANYSPECIAL,INDIRECTORCONSEQUENTIALDAMAGESINCLUDINGWITHOUTLIMITATIONWATERDAMAGE(THEEND-USERSHOULDTAKEPRECAUTIONSAGAINSTSAME),LOSTPROFITS,DELAY,ORLOSSOFUSEORDAMAGETOANYREALORPERSONALPROPERTY.
Somestatesdonotallowlimitationsonhowlonganimpliedwarrantylasts,andsomedonotallowtheexclusionorlimitationofincidentalorconsequentialdamages,sooneorbothoftheselimitationmaynotapplytoyou.
Legal Rights:Thiswarrantygivesyouspecificlegalrights,andyoumayalsohaveotherrightswhichvaryfromstatetostate.
www.sylvane.com1 (800) 934-9194