This manual is provided to acquaint you with the dehumidifier so that installation, operation and maintenance can proceed successfully. Ultimate satisfaction depends on the quality of installation and a thorough understanding of this equipment. The dehumidifier is built around tested engineering principles and has passed a thorough inspection for quality of workmanship and function. Installation, Operation and Maintenance Instructions 4201 Lien Rd Phone 608-237-8400 Madison, WI 53704 Toll-Free 1-800-533-7533 www.QuestProtect.com [email protected] – Read and Save These Instructions – Specifications subject to change without notice. 1 Quest 105, 155, and 205 Dual Water Removal Rates (Pints/Day) 105 pints 80˚F, 60% (AHAM) (105 Dual) 155 pints 80˚F, 60% (AHAM) (155 Dual) 205 pints 80˚F, 60% (AHAM) (205 Dual) quest Asset Protection and IAQ Solutions quest PATENTS: D570,988 8,069,681 The Quest 105 Dual provides 105 pints per day of water removal at standard rating conditions (80ºF/60%RH) while using only 4.9 amps/115V, and will effectively control humidity in areas up to 2500 sq. ft. The Quest 155 Dual provides water removal of 155 pints per day at 80ºF/60%RH using 8.0 amps/115V. The 155 conditions and controls areas up to 3600 sq. ft. The Quest 205 Dual is the largest capacity of the group. This unit removes up to 205 pints of water per day using only 13.2 amps/115V and retains the same cabinet size as the 105 and the 155. Ideally suited for structures with high ceiling applications, the Quest 205 Dual effectively controls inside environments up to 5,000 square feet. Features: Industry-leading efficiency, most efficient on the market today Plug-N-Play Patented, optimized air-to-air heat exchanger High-efficiency, long-life impeller fan Quiet operation and superior high static pressure performance Superior air filtration (MERV-11 standard) Patent Pending Dual air distribution Auto-restart after power outages Environmentally friendly R410A refrigerant TS-694 02/14

Transcript of Installation, Operation and Maintenance...

Page 1: Installation, Operation and Maintenance Instructionssunlightsupply.s3.amazonaws.com/.../product/Quest-Dual_Manual.pdf · Installation, Operation and Maintenance Instructions This

Installation, Operation and Maintenance Instructions

This manual is provided to acquaint you with the dehumidifier so that installation, operation and maintenance can proceed successfully. Ultimate satisfaction depends on the quality of installation and a thorough understanding of this equipment. The dehumidifier is built around tested engineering principles and has passed a thorough inspection for quality of workmanship and function.

Quest Dry

Installation, Operation and Maintenance Instructions

4201 Lien Rd Phone 608-237-8400Madison, WI 53704 Toll-Free 1-800-533-7533www.QuestProtect.com [email protected]

– Read and Save These Instructions –

Specifications subject to change without notice. 1

Quest 105, 155, and 205 Dual

Water Removal Rates (Pints/Day)

105 pints 80˚F, 60% (AHAM) (105 Dual)155 pints 80˚F, 60% (AHAM) (155 Dual) 205 pints 80˚F, 60% (AHAM) (205 Dual)

questAsset Protection and IAQ Solutions

quest

PATENTS: D570,988 8,069,681

The Quest 105 Dual provides 105 pints per day of water removal at standard rating conditions (80ºF/60%RH) while using only 4.9 amps/115V, and will effectively control humidity in areas up to 2500 sq. ft.

The Quest 155 Dual provides water removal of 155 pints per day at 80ºF/60%RH using 8.0 amps/115V. The 155 conditions and controls areas up to 3600 sq. ft.

The Quest 205 Dual is the largest capacity of the group. This unit removes up to 205 pints of water per day using only 13.2 amps/115V and retains the same cabinet size as the 105 and the 155. Ideally suited for structures with high ceiling applications, the Quest 205 Dual effectively controls inside environments up to 5,000 square feet.

Features:

• Industry-leading efficiency, most efficient on the market today

• Plug-N-Play

• Patented, optimized air-to-air heat exchanger

• High-efficiency, long-life impeller fan

• Quiet operation and superior high static pressure performance

• Superior air filtration (MERV-11 standard)

• Patent Pending Dual air distribution

• Auto-restart after power outages

• Environmentally friendly R410A refrigerant

TS-694 02/14

Page 2: Installation, Operation and Maintenance Instructionssunlightsupply.s3.amazonaws.com/.../product/Quest-Dual_Manual.pdf · Installation, Operation and Maintenance Instructions This

questAsset Protection and IAQ Solutions

quest 1-800-533-7533

Quest 105, 155, and 205 Dual Installation, Operation and Maintenance Instructions

2www.QuestProtect.com

[email protected]

Table of Contents Safety Precautions ..................................................... 3 1. Intended Application(s) .......................................... 42. Registrations .......................................................... 43.Specifications ........................................................ 44 . Installation ........................................................... 4 4.1 Location ......................................................... 5 4.1A No Ducting ........................................... 5 4.1B Ducted Return and Supply .................... 6 4.1C Remote Area w/ Ducted Supply ............. 6 4.1D Remote Area w/ Ducted Return ............. 7 4.2 Electrical Requirements .................................. 7 4.3 Condensate (Water) Removal .......................... 85. Ducting ........................................................... 8 5.1 Supply Duct Kit .............................................. 8 5.2 Return Duct Kit ............................................... 86. Operation ........................................................... 9 6.1 Humidity Control Adjustment ......................... 9 6.2 Blower (Fan) Switch ........................................ 97. Maintenance ......................................................... 9 7.1 Air Filter ........................................................ 108. Service ......................................................... 10 8.1 Technical Description ................................... 10 8.2 Troubleshooting ............................................ 119. Service Parts List .................................................. 1210. Accessory/Replacement Parts List ....................... 1211. Optional Remote Humidity Control ................... 1312. Wiring Diagram ................................................. 14Warranty ......................................................... 15

Page 3: Installation, Operation and Maintenance Instructionssunlightsupply.s3.amazonaws.com/.../product/Quest-Dual_Manual.pdf · Installation, Operation and Maintenance Instructions This

1-800-533-7533

Quest 105, 155, and 205 Dual Installation, Operation and Maintenance Instructions

3www.QuestProtect.com

[email protected]

questAsset Protection and IAQ Solutions

quest

Safety PrecautionsRead the installation, operation and maintenance instructions carefully before installing and operating this device.ProperadherencetotheseinstructionsisessentialtoobtainmaximumbenefitfromyourQuestDual indoor air quality system.

READ AND SAVE THESE INSTRUCTIONS

•ThedeviceisdesignedtobeinstalledINDOORSINA SPACE THAT IS PROTECTED FROM RAIN AND FLOODING.

•Installtheunitwithspacetoaccessthebackorsidepanelsfor maintenance and service. DO NOT INSTALL UNIT WITH THE SERVICE PANELS INACCESSIBLE.

•Avoiddirectingthedischargeairatpeople,oroverthewater in pool areas.

•Ifusednearapoolorspa;becertainthereisNOchancethe unit could fall into the water, be splashed and that it is plugged into a GFI GROUND FAULT INTERRUPT OUTLET.

•DO NOT use the device as a bench or table.

•DONOTplacethedevicedirectlyonstructuralmembers.Provide vibration isolation in order to minimize operational vibration and/or noise.

• AdrainpanMUSTbeplacedundertheunitifinstalledabove a living area or above an area where water leakage could cause damage

Page 4: Installation, Operation and Maintenance Instructionssunlightsupply.s3.amazonaws.com/.../product/Quest-Dual_Manual.pdf · Installation, Operation and Maintenance Instructions This

questAsset Protection and IAQ Solutions

quest 1-800-533-7533

Quest 105, 155, and 205 Dual Installation, Operation and Maintenance Instructions

4www.QuestProtect.com

[email protected]

1. Intended Application for Quest DualThe Quest Dual is designed to operate in temperatures between 56° and 95°F.

Inordertoefficientlycontrolhumiditylevels,theareainwhichthedehumidifieristobeoperatedmustbefreeofwaterintrusionorexcessivefresh(outside)airinfiltration.BeforeinstallingtheQuestDual,waterintrusionandairinfiltrationproblemsshouldbeaddressedornotedincalculations.

2. RegistrationsThe Quest Dual units conform to UL STD 474.

3. Specifications

Unit: 4032270 105 Dual 4031490 155 Dual 4033060 205 Dual

Blower: (Tested with duct collars

on)

257 CFM @ 0.0" WG 206 CFM @ 0.2" WG 146 CFM @ 0.4" WG

391 CFM @ 0.0" WG 363 CFM @ 0.2" WG 337 CFM @ 0.4" WG

526 CFM @ 0.0" WG 495 CFM @ 0.2" WG 458 CFM @ 0.4" WG

Power: 530 Watts @ 80°F and 60% RH 920 Watts @ 80°F and 60% RH 1525 Watts @ 80°F and 60% RH

Supply voltage: 110-120 VAC - 1 Phase - 60 Hz. 110-120 VAC - 1 Phase - 60 Hz. 110-120 VAC - 1 Phase - 60 Hz.

Current Draw: 4.9 Amps 8.0 Amps 13.2 Amps

Energy Factor: 4.2 L/kWh 3.5 2.7

Operating Temp: 56°F Min - 95°F Max 56°F Min - 95°F Max 56°F Min - 95°F Max

Sized For: 2,500 Square Foot Typical 3500 Square Foot Typical 5000 Square Foot Typical

Minimum Performance @ 80°F and 60% RH:

Water Removal: Efficiency:

105 Pints/Day 8.8 Pints/kWh

155 Pints/Day 7.3 Pints/kWh

205 Pints/Day 5.7 Pints/kWh

Air Filter: MERV-11 Size: 16" x 20" x 2" MERV-11 Size: 16" x 20" x 2" MERV-11 Size: 16" x 20" x 2"

Power Cord: 10’, 110-120 VAC, Ground 10’, 110-120 VAC, Ground 10’, 110-120 VAC, Ground *This unit requires a dedicated 20A

circuit

Drain Connection: 3/4” Threaded NPT 3/4” Threaded NPT 3/4” Threaded NPT

Dimensions: Width: Height: Length: Weight:

Unit Shipping 20.25" 24" 21.75" 28.25" 38" 42" 140 lbs 160 lbs

Unit Shipping 20.25" 24" 21.75" 28.25" 38" 42" 140 lbs 160 lbs

Unit Shipping 20.25" 24" 21.75" 28.25" 38 " 42" 150 lbs 170 lbs

Page 5: Installation, Operation and Maintenance Instructionssunlightsupply.s3.amazonaws.com/.../product/Quest-Dual_Manual.pdf · Installation, Operation and Maintenance Instructions This

1-800-533-7533

Quest 105, 155, and 205 Dual Installation, Operation and Maintenance Instructions

5www.QuestProtect.com

[email protected]

questAsset Protection and IAQ Solutions

quest

4. Installation

4.1 LocationThe Quest Dual can be installed in a variety of locationstomeettheowner’sneeds;otherconsiderationsinclude:

1. Providing access to a 115 VAC power outlet (10’ power cord is provided).

2.Locatingnearafloororothersuitabledrain (8’ drain hose included).

3. Mount 4” above drain.

4. Do not install the Quest Dual with the exhaust of the unit within 1’ of a wall or obstruction. Do not place the unit near open water.

4.1A No Ducting (fig. 1)The simplest installation is to place the Quest Dual with no ducting. To ensure optimal performance, the air inletandtheoutletoftheunitmustbeatleast2’fromwallsandotherobstructionstoairflow.Recirculationof outlet air into inlet should be avoided as much as possible.

Input of Humid Air

Out put ofDehumidified Air

Front View

Page 6: Installation, Operation and Maintenance Instructionssunlightsupply.s3.amazonaws.com/.../product/Quest-Dual_Manual.pdf · Installation, Operation and Maintenance Instructions This

questAsset Protection and IAQ Solutions

quest 1-800-533-7533

Quest 105, 155, and 205 Dual Installation, Operation and Maintenance Instructions

6www.QuestProtect.com

[email protected]

4.1B Ducted Return and Supply (fig. 2)Dehumidificationperformancecanbemodifiedbyaddinganreturnand/orsupplyducttocirculateair. For optimal drying, use return duct to draw warm, moist air from near the ceiling.

4.1C Remote Area, w/ Ducted Supply (fig. 3)AsimplifiedremoteinstallationmethodthanaboveusesductingbetweentheQuestDualdischargeandthehumidroom;theQuestDualinletdrawsairfromtheroominwhichit’slocated.Thisworkswellifthereisanadequateairflowpathbetweenthetworooms;e.g.highdoorundercut,louvereddoororwallgrill.Thiseliminates the need to remote mount the humidity control.

Input ofHumid Air

Front View

Output of Dehumidified Air

Front View

CONDITIONED SPACE

Input ofHumid Air

Output of Dehumidified Air

Page 7: Installation, Operation and Maintenance Instructionssunlightsupply.s3.amazonaws.com/.../product/Quest-Dual_Manual.pdf · Installation, Operation and Maintenance Instructions This

1-800-533-7533

Quest 105, 155, and 205 Dual Installation, Operation and Maintenance Instructions

7www.QuestProtect.com

[email protected]

questAsset Protection and IAQ Solutions

quest

WARNING! Before installing the dehumidifier in the manner described in section 4.1D (Fig. 4), call the factory for specific instructions if backdraft devices (i.e. hot waters heaters) are present in the space to be dehumidified.

4.1D In A Remote Area, Ducted Return Only (fig. 4)WhentheQuestDualislocatedinaroomseparatefromthemainareatobedehumidified,itmaybedesirable to dehumidify and/or slightly pressurize that room. Pressurization assures that open combustion devices do not backdraft. This can be prevented by installing a duct from the humid room to the Quest Dual inletandbyallowingtheQuestDualtodischargedehumidifiedairintotheroominwhichit’slocated.Anadequateairflowpathmustexistbetweenthetworoomsforthismethodtoworkproperly.

WARNING!

4.2 Electrical RequirementsThe Quest Dual plugs into a common grounded outlet on a 110-120 VAC 15-Amp circuit. Use of a ground fault circuit interrupter (GFCI) protected circuit is recommended. The unit should not be used in areas prone toflooding.

CONDITIONED SPACE

Front View

Input ofHumid Air

Output of Dehumidified Air

Page 8: Installation, Operation and Maintenance Instructionssunlightsupply.s3.amazonaws.com/.../product/Quest-Dual_Manual.pdf · Installation, Operation and Maintenance Instructions This

questAsset Protection and IAQ Solutions

quest 1-800-533-7533

Quest 105, 155, and 205 Dual Installation, Operation and Maintenance Instructions

8www.QuestProtect.com

[email protected]

CAUTION! For proper drainage, the unit must be mounted so the drain outlet is at least 4” above the floor drain, and must be fully supported under the base.

4.3 Condensate (Water) Removal Condensate drains by gravity via the drain port. Use 3/4” male NPT PVC pipe. Route drain to drain. Install a trap if possible. Take care when installing drain pipe to drain port. Use an adjustable wrench to secure the drain port. An optional condensate pump kit (4028614) may be installed if a lift is required to dispose of the condensate. To order call 1-800-533-7533.

Wheninstallingthedrainhosemakesurethefeetareextendedsuchthatthedehumidifieris21/2”offtheground. Then coil the drain hose under itself or position a spacer to lift the hose 1” off the ground after the hose has touched the ground. This procedure will create a trap that ensures your unit drains correctly. See thediagrambelowforfurthervisualclarification.

5. Ducting 5.1 Supply Duct Kit (P/N 4028607)

A factory designed supply duct kit can be purchased to accept 10” ducting to both outlets of the Quest Dual. Contact your dealer or call 1-800-533-7533 to order.

5.2 Return Duct Kit (P/N 4028610)

A factory designed return duct kit can be purchased to accept 12” ducting. Contact your dealer or call 1-800-533-7533 to order.

Page 9: Installation, Operation and Maintenance Instructionssunlightsupply.s3.amazonaws.com/.../product/Quest-Dual_Manual.pdf · Installation, Operation and Maintenance Instructions This

1-800-533-7533

Quest 105, 155, and 205 Dual Installation, Operation and Maintenance Instructions

9www.QuestProtect.com

[email protected]

questAsset Protection and IAQ Solutions

quest

6. Operation 6.1 Humidity Control Adjustment

The humidity control is an adjustable switch that closes when the relative humidity of the air in which it is located rises to the dial set point. It opens when the RH drops 4 to 6% below the set point.

Approximate Humidity Levels Per Setting

“Dry” 20% to 30% Relative Humidity

“Normal” 50% Relative Humidity (Recommended)

“Humid” 80% to 90% Relative Humidity

Thedehumidifierwillrununtiltherelativehumidity(RH)isreducedtothehumiditycontroldialsetting.

Quality humidity meters are available from the factory and are recommended to accurately monitor humidity levels. Contact your dealer or call 1-800-533-7533 to order.

6.2 Blower (Fan) Switch

Turning the blower switch to “FAN ON” will cause the unit’s internal blower to run continuously, whether the unit is dehumidifying or not. This function is desirable if the unit is used for air circulation.

Turning the blower switch to “FAN AUTO” will cause the unit’s internal blower to run only while the unit is dehumidifying.

7. Maintenance WARNING! NOTE: Do not operate the unit without the filter or with a less effective

filter. The heat exchange coils inside the unit could become clogged and require disassembly to clean.

4031882

Page 10: Installation, Operation and Maintenance Instructionssunlightsupply.s3.amazonaws.com/.../product/Quest-Dual_Manual.pdf · Installation, Operation and Maintenance Instructions This

questAsset Protection and IAQ Solutions

quest 1-800-533-7533

Quest 105, 155, and 205 Dual Installation, Operation and Maintenance Instructions

10www.QuestProtect.com

[email protected]

7.1 Air FilterTheQuestDualshipswithastandardMERV11efficientpleatedfabricfilter.Thisshouldbecheckedeverysixmonths.Thepleatedfabricfiltercangenerallybevacuumedcleanseveraltimesbeforeneedingreplacement.Operatingtheunitwithadirtyfilterwillreducedehumidifiercapacityandefficiencyandmaycausethecompressortocycleonandoffunnecessarily.Replacementfilterscanbeorderedfromyourdealeror by calling 1-800-533-7533.

8. Service WARNING! Servicing the Quest Dual with its high pressure refrigerant system and

high voltage circuitry presents a health hazard which could result in death, serious bodily injury, and/or property damage. Only qualified service people should service this unit.

8.1 Technical Description

The Quest Dual uses a refrigeration system similar to an air conditioner’s to remove heat and moisture from incoming air, and add heat to the air that is discharged. Hot, high pressure refrigerant gas is routed from the compressor to the condenser coil. The refrigerant is cooled and condensed by giving up its heat to the airthatisabouttobedischargedfromtheunit.Therefrigerantliquidthenpassesthroughafilter/drierandcapillary tubing which cause the refrigerant pressure and temperature to drop. It next enters the evaporator coil where it absorbs heat from the incoming air and evaporates.

Theevaporatoroperatesinafloodedcondition,whichmeansthatalltheevaporatortubescontainliquidrefrigerantduringnormaloperation.Afloodedevaporatorshouldmaintainconstantpressureandtemperature across the entire coil, from inlet to outlet. The mixture of gas and liquid refrigerant enter the accumulator after leaving the evaporator coil. The accumulator prevents any liquid refrigerant from reaching the compressor. The compressor evacuates the cool refrigerant gas from the accumulator and compresses it to a high pressure and temperature gas to repeat the process.

Quest Dual refrigeration system

Page 11: Installation, Operation and Maintenance Instructionssunlightsupply.s3.amazonaws.com/.../product/Quest-Dual_Manual.pdf · Installation, Operation and Maintenance Instructions This

1-800-533-7533

Quest 105, 155, and 205 Dual Installation, Operation and Maintenance Instructions

11www.QuestProtect.com

[email protected]

questAsset Protection and IAQ Solutions

quest

8.2 Troubleshooting

FOR THE END USER:

If the unit does not work properly, please check the following:

— Is the unit unplugged?

— Is power to outlet on? (check switch, if applicable)

— Is circuit breaker tripped?

— Is humidity control set? (turn to “ON”)

—Isairflowrestricted?(checkairfilterandgrill)

If none of the above, call dealer or 1-800-533-7533.

FOR THE HVAC PROFESSIONAL:

No dehumidification. Neither blower, nor compressor run with fan switch AUTO.

1. Unit unplugged or no power to outlet, circuit breaker tripped.

2. Humidity control set to “Humid” setting.

3. Loose connection in internal wiring.

4. Humidity control is defective.

No dehumidification. Compressor does not run but blower runs with fan switch AUTO and humidity control turned to ON.

1. Defrost thermostat open, ambient temperature too low.

2. Loose connection in compressor circuit.

3. Defective compressor overload.

4. Defective compressor or compressor run capacitor.

Blower runs with fan switch AUTO but compressor cycles on & off.

1. Low ambient temperature and/or humidity causing unit to cycle through defrost mode.

2. Defrost thermostat defective.

3. Defective compressor overload.

4. Defective compressor.

Page 12: Installation, Operation and Maintenance Instructionssunlightsupply.s3.amazonaws.com/.../product/Quest-Dual_Manual.pdf · Installation, Operation and Maintenance Instructions This

questAsset Protection and IAQ Solutions

quest 1-800-533-7533

Quest 105, 155, and 205 Dual Installation, Operation and Maintenance Instructions

12www.QuestProtect.com

[email protected]

• Blower does not run with fan switch in either position. Compressor runs briefly but cycles on and off.

1. Loose connection in blower circuit.

2. Obstruction prevents impeller rotation.

3. Defective blower.

4. Defective blower switch.

• Evaporator coil frosted continuously, low dehumidifying capacity.1. Dirtyairfilterorairflowrestricted.

2. Defrost thermostat loose or defective.

3. Low refrigerant charge.

If none of the above has fixed the issue, call technical support at 1-800-533-7533.

9. Service Parts List

10. Accessory/Replacement Parts List4021475 MERV 11 Filter (16”x20”x2”)

4027420 MERV 11 Filters 4-Pack

4027424 MERV 11 Filters 12-Pack

4028614 Pump Kit

4028616 Caster Kit

4028607 Supply Duct Kit (includes two 10” collars)

Part No Description

4031086-02 Evaporator Coil E-Coat 4025741 (105, 155) Thermostat Defrost Control 4032229 (205) Thermostat Defrost Control 4032226 (105) Compressor Replacement Kit 4032225 (155) Compressor Replacement Kit 4032224 (205) Compressor Replacement Kit 4029568 (105) Compressor Overload 4029714 (155) Compressor Overload 4031574 (205) Compressor Overload 4032196 (105) Impeller 4026657 (155) Impeller 4031089 (205) Impeller

Part No Description

4021469 (105, 155) Humidistat 4027172 (205) Humidistat 4033031-02 (105) Blower Capacitor, Run, 5MFD, 370V 4033031-07 (155) Blower Capacitor, Run, 15 MFD, 370V 4033031-08 (205) Blower Capacitor, Run, 20 MFD, 370V 4033032-03 (105) Compressor Capacitor, Run, 35 MFD, 370V 4033032-05 (155, 205) Compressor Capacitor, Run, 45 MFD, 370V

Page 13: Installation, Operation and Maintenance Instructionssunlightsupply.s3.amazonaws.com/.../product/Quest-Dual_Manual.pdf · Installation, Operation and Maintenance Instructions This

1-800-533-7533

Quest 105, 155, and 205 Dual Installation, Operation and Maintenance Instructions

13www.QuestProtect.com

[email protected]

questAsset Protection and IAQ Solutions

quest

4026969 10” Flex Duct 25’

4022126 10” Flex Insulated Duct 25’

4028610 Return Duct Kit (includes one 12” collar)

4024750 12” Flex Duct 25’

4028366 12” Flex Insulated Duct 25’

4020175 Remote Dehumidistat

To order, contact your dealer or call 1-800-533-7533.

11. Quest Dual Optional Remote Humidity Control

CAUTION! This should only be performed by a qualified electrician.

A 120 VAC remote humidity control is available from the factory. This replaces the factory mounted humidity controlonthecabinetofthedehumidifier,andallowsyoutoaccuratelysensethehumidityinanareaotherthantheonewherethedehumidifierislocated.

4020175

Page 14: Installation, Operation and Maintenance Instructionssunlightsupply.s3.amazonaws.com/.../product/Quest-Dual_Manual.pdf · Installation, Operation and Maintenance Instructions This

questAsset Protection and IAQ Solutions

quest 1-800-533-7533

Quest 105, 155, and 205 Dual Installation, Operation and Maintenance Instructions

14www.QuestProtect.com

[email protected]

4027461B

BLK-1 WHT-2

VIO-4 BLK-9 BLU-10

GRN-12BRN-11

BLK-

8

ORG-

13

BLK-14 BLK-15

YEL-5

RED-6GRN-7

GRN - 3

12. Wiring Diagram

1Ph60Hz

24Vac

BLOWERRELAY COIL

COMPRESSORRELAY COIL

14 13

10

WH

T-4

RE

D-1

PN

K-3

BLU-7

GRN-5

24V

XFMRYEL-6 YEL-2

BLOWERRELAY RUN

CAPACITOR

RELAY

COMPRESSOR

6

VIO

-84

5 9

1

5 9

BL

K-2

BLK-10

BRN-3

BLOWER

BLK-1 BLU-2

T-STATDEFROST

RUNCAPACITOR

RED-6

YEL-5

R

S3BLK-11

GRN-4

GRN-4

BLK-1 WHT-5115V/220V

COMPRESSOR

4032179A

BLK-3 WHT-6

AB

BABLK-7

COM

COM24V

BLOWERSWITCH

FAN ON

LINE NEUTRAL

HUMIDISTAT

105, 155 Dual

205 Dual

Page 15: Installation, Operation and Maintenance Instructionssunlightsupply.s3.amazonaws.com/.../product/Quest-Dual_Manual.pdf · Installation, Operation and Maintenance Instructions This

1-800-533-7533

Quest 105, 155, and 205 Dual Installation, Operation and Maintenance Instructions

15www.QuestProtect.com

[email protected]

questAsset Protection and IAQ Solutions

quest

Quest Dual Dehumidifier Limited Warranty WARRANTOR:

Therma-Stor LLC 4201 Lien Rd Madison, WI 53704 Telephone: 1-800-533-7533

WHO IS COVERED: Thiswarrantyextendsonlytotheoriginalend-useroftheQuestDualdehumidifier,andmay not be assigned or transferred.

FIRSTYEARWARRANTY:Therma-StorLLCwarrantsthat,forone(1)yeartheQuestDualdehumidifierwilloperate free from any defects in materials and workmanship, or Therma-Stor LLC will, at its option, repair or replace the defective part(s), free of any charge.

SECOND THROUGH FIFTH YEAR WARRANTY:Therma-StorLLCfurtherwarrantsthatforaperiodoffive(5)years,thecondenser,evaporator,andcompressoroftheQuestDualdehumidifierwilloperatefreeofanydefects in material or workmanship, or Therma-Stor LLC, at its option, will repair or replace the defective part(s), provided that all labor and transportation charges for the part(s) shall be borne by the end-user.

END-USER RESPONSIBILITIES: Warranty service must be performed by a Servicer authorized by Therma-Stor LLC. If the end-user is unable to locate or obtain warranty service from an authorized Servicer, he should call Therma-Stor LLC at the above number and ask for the Therma-Stor LLC Service Department, which will then arrange for covered warranty service. Warranty service will be performed during normal working hours.

The End-user must present proof of purchase (lease) upon request, by use of the warranty card or other reasonable and reliable means. The end-user is responsible for normal care. This warranty does not cover any defect, malfunction, etc. resulting from misuse, abuse, lack of normal care, corrosion, freezing, tampering, modification,unauthorizedorimproperrepairorinstallation,accident,actsofnatureoranyothercausebeyond Therma-Stor LLC's reasonable control.

LIMITATIONS AND EXCLUSIONS: IfanyQuestDualDehumidifierpartisrepairedorreplaced,thenewpart shall be warranted for only the remainder of the original warranty period applicable thereto (but all warrantyperiodswillbeextendedbytheperiodoftime,ifany,thattheQuestDualDehumidifierisoutofservice while awaiting covered warranty service).

UPON THE EXPIRATION OF THE WRITTEN WARRANTY APPLICABLE TO THE Quest Dual DEHUMIDIFIER OR ANY PART THEREOF, ALL OTHER WARRANTIES IMPLIED BY LAW, INCLUDING MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, SHALL ALSO EXPIRE. ALL WARRANTIES MADE BY THERMA-STOR LLC ARE SET FORTH HEREIN, AND NO CLAIM MAY BE MADE AGAINST THERMA-STOR LLC BASED ON ANY ORAL WARRANTY. IN NO EVENT SHALL THERMA-STOR LLC, IN CONNECTION WITH THE SALE, INSTALLATION, USE, REPAIR OR REPLACEMENT OF ANY Quest Dual DEHUMIDIFIER OR PART THEREOF BE LIABLE UNDER ANY LEGAL THEORY FOR ANY SPECIAL, INDIRECT OR CONSEQUENTIAL DAMAGES INCLUDING WITHOUT LIMITATION WATER DAMAGE (THE END-USER SHOULD TAKE PRECAUTIONS AGAINST SAME), LOST PROFITS, DELAY, OR LOSS OF USE OR DAMAGE TO ANY REAL OR PERSONAL PROPERTY.

Some states do not allow limitations on how long an implied warranty lasts, and some do not allow the exclusion or limitation of incidental or consequential damages, so one or both of these limitation may not apply to you.

LEGAL RIGHTS:Thiswarrantygivesyouspecificlegalrights,andyoumayalsohaveotherrightswhichvaryfrom state to state.