501 01 3403 01 10/19 INSTALLATION INSTRUCTIONS R--410A SPLIT CONDENSING UNITS CAS180/181--240/241 with RTPF These instructions must be read and understood completely before attempting installation Safety Labeling and Signal Words DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and throughout this manual and other manual that may apply to the product. DANGER -- Immediate hazards which will result in severe personal injury or death. WARNING --Hazards or unsafe practices which could result in severe personal injury or death. CAUTION -- Hazards or unsafe practices which may result in minor personal injury or product or property damage. NOTE -- Used to highlight suggestions which will result in enhanced installation, reliability, or operation. ! WARNING Signal Words in Manuals The signal word WARNING is used throughout this manual in the following manner: The signal word CAUTION is used throughout this manual in the following manner: ! CAUTION Signal Words on Product Labeling Signal words are used in combination with colors and/or pictures or product labels. SAFETY CONSIDERATIONS 2 .................. MODEL NOMENCLATURE 3 .................... INSTALLATION GUIDELINE 4 ................... Step 1 -- Plan for Unit Location 9 ................. Step 2 -- Complete Pre--Installation Checks 9 ...... Step 3 -- Prepare Unit Mounting Support 9 ........ Step 4 -- Rig and Mount Unit 10 ................... Step 5 -- Complete Refrigerant Piping 10 ........... PRE--START--UP 20 ............................. START--UP 20 .................................. OPERATING SEQUENCE 28 ..................... ROUTINE SYSTEM MAINTENANCE 29 ........... SERVICE 29 ................................... TROUBLESHOOTING 40 ........................ APPENDIX A, R--410A Quick Reference Guide 42 .. APPENDIX B, Low Ambient Option 43 ............. START--UP CHECKLIST 51 ...................... CHECK VOLTAGE BALANCE 52 ................. TABLE OF CONTENTS ! WARNING PERSONAL INJURY, AND/OR PROPERTY DAMAGE HAZARD Failure to carefully read and follow this warning could result in equipment malfunction, property damage, personal injury and/or death. Installation or repairs made by unqualified persons could result in equipment malfunction, property damage, personal injury and/or death. The information contained in this manual is intended for use by a qualified service technician familiar with safety procedures and equipped with proper tools and test instruments. Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part 1 CSA C.22.1. Specifications are subject to change without notice.

Transcript of INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with...

Page 1: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

501 01 3403 01 10/19

INSTALLATION INSTRUCTIONSR--410A SPLIT CONDENSING UNITSCAS180/181--240/241 with RTPF

These instructions must be read and understood completely before attempting installation

Safety Labeling and Signal WordsDANGER, WARNING, CAUTION, and NOTE

The signal words DANGER, WARNING,CAUTION, andNOTE are used to identify levels ofhazard seriousness. The signal word DANGER isonly used on product labels to signify an immediatehazard. The signal words WARNING, CAUTION,and NOTE will be used on product labels andthroughout this manual and other manual that mayapply to the product.

DANGER -- Immediate hazards which will result insevere personal injury or death.

WARNING --Hazards or unsafe practices whichcould result in severe personal injury or death.

CAUTION -- Hazards or unsafe practices whichmay result in minor personal injury or product orproperty damage.

NOTE -- Used to highlight suggestions which willresult in enhanced installation, reliability, oroperation.

! WARNING

Signal Words in ManualsThe signal wordWARNING is used throughoutthis manual in the following manner:

The signal word CAUTION is used throughoutthis manual in the following manner:

! CAUTIONSignal Words on Product LabelingSignal words are used in combination withcolors and/or pictures or product labels.

SAFETY CONSIDERATIONS 2. . . . . . . . . . . . . . . . . .MODEL NOMENCLATURE 3. . . . . . . . . . . . . . . . . . . .INSTALLATION GUIDELINE 4. . . . . . . . . . . . . . . . . . .Step 1 -- Plan for Unit Location 9. . . . . . . . . . . . . . . . .Step 2 -- Complete Pre--Installation Checks 9. . . . . .Step 3 -- Prepare Unit Mounting Support 9. . . . . . . .Step 4 -- Rig and Mount Unit 10. . . . . . . . . . . . . . . . . . .Step 5 -- Complete Refrigerant Piping 10. . . . . . . . . . .PRE--START--UP 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . .START--UP 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .OPERATING SEQUENCE 28. . . . . . . . . . . . . . . . . . . . .ROUTINE SYSTEM MAINTENANCE 29. . . . . . . . . . .SERVICE 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .TROUBLESHOOTING 40. . . . . . . . . . . . . . . . . . . . . . . .APPENDIX A, R--410A Quick Reference Guide 42. .APPENDIX B, Low Ambient Option 43. . . . . . . . . . . . .START--UP CHECKLIST 51. . . . . . . . . . . . . . . . . . . . . .CHECK VOLTAGE BALANCE 52. . . . . . . . . . . . . . . . .

TABLE OF CONTENTS

! WARNINGPERSONAL INJURY, AND/OR PROPERTYDAMAGE HAZARDFailure to carefully read and follow this warningcould result in equipment malfunction, propertydamage, personal injury and/or death.Installation or repairs made by unqualifiedpersons could result in equipment malfunction,property damage, personal injury and/or death.

The information contained in this manual isintended for use by a qualified service technicianfamiliar with safety procedures and equippedwith proper tools and test instruments.

Installation must conform with local buildingcodes and with the national Electrical CodeNFPA70 current edition or Canadian ElectricalCode part 1 CSA C.22.1.

Specifications are subject to change without notice.

Page 2: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

2 501 01 3403 01Specifications are subject to change without notice.

SAFETY CONSIDERATIONSImproper installation, adjustment, alteration, service,maintenance, or use can cause explosion, fire, electricalshock, or other conditions which may cause death,personal injury, or property damage. Consult a qualifiedinstaller, service agency, or your distributor or branch forinformation or assistance. The qualified installer or agencymust use factory--authorized kits or accessories whenmodifying this product. Refer to the individual instructionspackaged with the kits or accessories when installing.Follow all safety codes. Wear safety glasses, protectiveclothing, and work gloves. Use quenching cloth for brazingoperations. Have fire extinguisher available. Read theseinstructions thoroughly and follow all warnings or cautionsincluded in literature and attached to the unit. Consult localbuilding codes, the current editions of the NationalElectrical Code (NEC) NFPA 70.In Canada refer to the current editions of the CanadianElectrical Code CSA C22.1 Recognize safety information.

This is the safety--alert symbol !! When you see thissymbol on the unit and in instructions or manuals, be alertto the potential for personal injury. Understand thesesignal words; DANGER, WARNING, and CAUTION. Thesewords are used with the safety--alert symbol. DANGERidentifies the most serious hazards which will result insevere personal injury or death. WARNING signifieshazards which could result in personal injury or death.CAUTION is used to identify unsafe practices which mayresult in minor personal injury or product and propertydamage. NOTE is used to highlight suggestions which willresult in enhanced installation, reliability, or operation.

! WARNINGELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injuryor death.

Before performing service or maintenance operations onunit, always turn off main power switch to unit and installlockout tag. Unit may have more than one power switch.

! WARNINGUNIT OPERATION AND SAFETY HAZARD

Failure to follow this warning could cause personal injury,death and/or equipment damage.

R--410A systems operate at higher pressures than R--22systems. When working with R--410A systems, use onlyservice equipment and replacement components specifi-cally rated or approved for R--410A service.

! WARNINGPERSONAL INJURY AND ENVIRONMENTAL HAZARD

Failure to follow this warning could cause personal injuryor death.

Relieve pressure and recover all refrigerant before systemrepair or final unit disposal.Wear safety glasses and gloves when handling refriger-ants.Keep torches and other ignition sources away from refri-gerants and oils.

! CAUTIONCUT HAZARD

Failure to follow this caution may result in personal injury.

Sheet metal parts may have sharp edges or burrs. Usecare and wear appropriate protective clothing, safetyglasses and gloves when handling parts and servicingunits.

! CAUTIONUNIT DAMAGE HAZARD

Failure to follow this caution may cause equipment dam-age.

Ensure voltage listed on unit data plate agrees with elec-trical supply provided for the unit.

Page 3: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

3501 01 3403 01 Specifications are subject to change without notice.

MODEL NOMENCLATUREMODEL SERIES C A S 1 8 1 H A A 0 A 0 0Position Number 1 2 3 4 5 6 7 8 9 10 11 12 13C = R--410A Condensing Unit

A = Air Conditioning (Cooling Only)H = Heat Pump Type

S = Standard ASHRAE 90.1--2010 Efficiency Efficiency

180 = 15 Tons (2 circuit)181 = 15 Tons (1 circuit)240 = 20 Tons (2 circuits)241 = 20 Tons (1 circuit) Nominal Cooling Capacity

H = 208/230--3--60L = 460--3--60S = 575--3--50 VOLTAGE

A = Single CircuitB = Single Circuit w/ Low Ambient ControlD = Dual CircuitE = Dual Circuit w/ Low Ambient Control Refrigerant System Options

A = Copper / Aluminum StandardC = E--Coat Copper / Aluminum Outdoor Coil Options

0 = None1 = UnPowered C.O. Service Options

A = NoneC = Non--Fused Disconnect Electrical Options

0 = Elec--Mechanical Standard Base Unit Controls

0 = Future Use Future Use

Page 4: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

4 501 01 3403 01Specifications are subject to change without notice.

Installation GuidelineReplacement /Retrofit – R22 to R--410AReplacement/retrofit installations require change--out ofoutdoor unit, metering device, and filter driers. Change--outof indoor coil (evaporator) and interconnecting tubing isrecommended.Existing evaporator coil – If the existing evaporator coil maybe re--used, check with the coil manufacturer to verify the coilconstruction is suitable for operation with the higherpressures of R--410A. Also determine if the existing TXVvalve is compatible with R--410A, replace if necessary. Theminimum factory test pressure rating must be 250 psig (1725kPa). Existing coil will need to be purged with Nitrogen toremove as much mineral oil as possible to eliminate crosscontamination of oil.Acid test – If the existing system is being replaced becauseof a compressor electrical failure, assume acid is in system.If system is being replaced for any other reason, use anapproved acid test kit to determine acid level. If even lowlevels of acid are detected, install a 100 percent activatedalumina suction--line filter drier in addition to the replacementliquid--line filter drier. Remove the suction line filter drier assoon as possible, with a maximum of 72 hours of operation.Recommendation: Install a ball valve in the liquid line at thefilter drier locationwhen installing a suction filter in the suctionline.

Installation1. Remove the existing evaporator coil or fan coil and

install the replacement coil when appropriate.

2. Drain oil from lowpoints and traps in suction line tubingand hot gas bypass tubing if appropriate) andevaporator if they were not replaced. Removing oilfrom evaporator coil may require purging of the tubingwith dry nitrogen.

3. Unless indoor unit is equipped with a R--410Aapproved metering device, change the meteringdevice to a thermal expansion valve (TXV) designedfor R--410A.

4. Remove the existing outdoor unit. Install the newoutdoor unit according to these installationinstructions.

5. Install a new field--supplied liquid--line filter drier at theindoor coil just upstream of the TXV or fix orificemetering device.

6. If a suction line filter drier is also to be installed, installsuction line drier downstream of suction line servicevalve at condensing unit.

7. If required, install a 100% activated alumina suctionline filter drier at the outdoor unit.

8. Evacuate and charge the system according to theinstructions in this installation manual.

9. Operate the system for 10 hours. Monitor the pressuredrop across the suction line filter drier. If pressure dropexceeds 3 psig (21kPa), replace suction--line andliquid--line filter driers. Be sure to purge systemwith drynitrogen and evacuate when replacing filter driers.Continue to monitor the pressure drop acrosssuction--line filter drier. Repeat filter changes isnecessary. Never leave suction--line filter drier insystem longer than 72 hr (actual time).

NOTE: Do not use a torch to remove filter driers, use tubingcutters. Excess heat from the torch will drive the moisturecontained within the drier back out into the system.

Page 5: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

5501 01 3403 01 Specifications are subject to change without notice.

Figure 1 Unit Dimensions -- 15 Ton

CAS181CAS180

(FOR CAS180 SYSTEMS)

UNIT

StandardWeight

CornerA

CornerB

CornerC

CornerD Center of Gravity

UnitHeight

lbs. kg. lbs. kg. lbs. kg. lbs. kg. lbs. kg. X Y Z H

CAS181(RTPF) 731 332 237 107 172 78 135 61 186 84 38

[965.2]19

[482.6]17

[431.8]50 3/8[1279.2]

CAS180(RTPF) 731 332 237 107 172 78 135 61 186 84 38

[965.2]19

[482.6]17

[431.8]50 3/8[1279.2]

LEGEND: RTPF = Round Tube/Plate Fin coil

Page 6: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

6 501 01 3403 01Specifications are subject to change without notice.

Figure 2 Unit Dimensions -- 20 Ton

CAS240CAS241

(FOR CAS240 SYSTEMS)

UNIT StandardWeight

CornerA

CornerB

CornerC

CornerD Center of Gravity Unit

Height

lbs. kg. lbs. kg. lbs. kg. lbs. kg. lbs. kg. X Y Z H

CAS241(RTPF) 978 444 360 163 188 85 147 67 283 128 38

[965.2]23

[584.2]17

[431.8]50 3/8[1279.2]

CAS240(RTPF) 978 444 360 163 188 85 147 67 283 128 38

[965.2]23

[584.2]17

[431.8]50 3/8[1279.2]

LEGEND: RTPF = Round Tube/Plate Fin coil

Page 7: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

7501 01 3403 01 Specifications are subject to change without notice.

Table 1 Physical Data — 60 Hz English

UNIT CAS 181 180 241 240

NOMINAL CAPACITY (tons) 15 15 20 20

OPERATING WEIGHTS (lb)

Round Tube/Plate Fin Coil (Cu/Al) 731 731 900 900

REFRIGERANT TYPE‡ R-410A

Operating Charge, Typical (lb)† 24.6 12.0 / 12.0 38.0 19.0 / 19.0

Shipping Charge (lb) 12.2 6.0 / 6.0 28.0 14.0 / 14.0

COMPRESSOR

Qty...Type 2...Scroll 2...Scroll 2...Scroll 2...Scroll

Oil Charge (oz) 60 60 / 60 110 110 / 110

CONDENSER FANS

Qty...Rpm 3...1100 3...1100 4...1100 4...1100

Motor Hp 1/4 1/4 1/4 1/4

Diameter 22 22 22 22

Nominal Airflow (Cfm Total) 9,000 9,000 12,000 12,000

Watts (Total) 970 970 1150 1150

RTPF CONDENSER COIL

Material (Tube/Fin) Cu / Al Cu / Al Cu / Al Cu / Al

Coil Type 3/8--in RTPF 3/8--in RTPF 3/8--in RTPF 3/8--in RTPFRows/Fins per inch (FPI) 2 / 17 2 / 17 2 / 17 2 / 17

Face Area (sq ft total) 47.0 47 50.0 50

CONTROLS

Pressurestat Settings (psig)

High Cutout 630 10

Cut-in 505 20

Low Cutout 54 3

Cut-in 117 5

PIPING CONNECTIONS (in. ODS)

Qty...Suction 1...13/8 2...13/8 1...15/8 2...13/8

Qty...Liquid 1...5/8 2...1/2 1...5/8 2...1/2

LEGENDRTPF — Round Tube/Plate Fin CoilODS — Outside Diameter Sweat (socket)* Unit is factory--supplied with partial charge only.† Typical operating charge with 25 ft of interconnecting piping.** Storage capacity of condenser coil with coil 80% full of liquidR--410A at 95_F.

Page 8: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

8 501 01 3403 01Specifications are subject to change without notice.

Table 2 Physical Data — 60 Hz SI

UNIT CAS 181 180 241 240

NOMINAL CAPACITY (kW) 52.7 52.7 70.3 70.3

OPERATING WEIGHT (kg)

Round Tube/Plate Fin Coil (Cu/Al) 332 332 409 409

REFRIGERANT TYPE‡ R-410A

Operating Charge, Typical (kg)† 11.1 5.4 / 5.4 17.2 8.6 / 8.6

Shipping Charge (kg) 5.4 2.7 / 2.7 12.7 6.8 / 6.8

COMPRESSOR Scroll

Qty...Type 2...Scroll 2...Scroll 2...Scroll 2...Scroll

Oil Charge (L) 1.7 1.7 / 1.7 3.2 3.2 / 3.2

CONDENSER FANS

Qty...r/s 3...18 3...18 4...18 4...18

Motor Hp NEMA 1/4 1/4 1/4 1/4

Diameter (mm) 560 560 560 560

Nominal Airflow (L/s) 4248 4248 5663 5663

Watts (Total) 970 970 1150 1150

RTPF CONDENSER COIL (Qty)

Material (Tube/Fin) Cu / Al Cu / Al Cu / Al Cu / Al

Coil Type 3/8--in RTPF 3/8--in RTPF 3/8--in RTPF 3/8--in RTPFRows/Fins per Meter (Fins/m) 1...670 1...670 2...670 2...670

Face Area (sq m total) 4.4 4.4 4.6 4.6

CONTROLS

Pressurestat Settings (kPa)

High Cutout 4347 70

Cut-in 3482 138

Low Cutout 372 21

Cut-in 807 34

PIPING CONNECTIONS (mm ODS)

Qty...Suction 1...34.9 2...34.9 1...38.7 2...34.9

Qty...Liquid 1...13.3 2...12.7 1...13.3 2...12.7

LEGENDRTPF — Round Tube/Plate FinNEMA — National Electrical Manufacturers AssociationODS — Outside Diameter Sweat (socket)‡ Unit is factory-supplied with partial charge only.† Typical operating charge with 7.62 m of interconnecting piping.

Page 9: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

9501 01 3403 01 Specifications are subject to change without notice.

Matching CAS Model To Evaporator CoilThe Model CAS181/241 is a single-circuit unit design,requiring one set of refrigeration piping. This model can beconnected to an evaporator coil with one circuit or with twocircuits (by manifolding the evaporator connections into asingle piping system).The Model CAS180/240 is a dual-circuit unit design thatrequires two sets of refrigeration piping between theoutdoor unit and the evaporator coil (or coils). This modelcan only be connected to an evaporator coil that has tworefrigeration circuits (or to two separate evaporator coils).The Model CAS180/240 CANNOT be connected to asingle-circuit evaporator coil. The Model CAS180/240CANNOT be field-converted to a single-circuit design.

Table 3 – Evaporator Coil Connections

EvaporatorCoil Connect to Model Notes

Single Circuit CAS181/241ONLY

Two Circuits

CAS181/241 Manifold evaporator circuitsinto single piping system

Or

CAS180/240 Use two separate pipingsystems

Before unpacking this new CAS model, compare theevaporator coil design to the CAS model.

Jobsite SurveyComplete the following checks before installation.1. Consult local building codes and the NEC (National

Electrical Code) ANSI/NFPA 70 for special installationrequirements.

2. Determine unit location (from project plans) or selectunit location.

3. Check for possible overhead obstructions which mayinterfere with unit lifting or rigging.

Step 1 — Plan for Unit LocationSelect a location for the unit and its support system (pad, railsor other) that provides for the minimum clearances requiredfor safety. This includes the clearance to combustiblesurfaces, unit performance and service access below, aroundand above unit as specified in unit drawings. See Figure 3.NOTE: Consider also the effect of adjacent units on airflowperformance and control box safety clearance.Do not install the outdoor unit in an area where fresh airsupply to the outdoor coil may be restricted or whenrecirculation from the condenser fan discharge is possible.Do not locate the unit in a well or next to high walls.Evaluate the path and required line length for interconnectingrefrigeration piping, including suction riser requirements(outdoor unit above indoor unit), liquid line lift (outdoor unitbelow indoor unit) and hot gas bypass line. Relocate sectionsto minimize the length of interconnecting tubing.

! CAUTIONUNIT OPERATION HAZARDFailure to follow this caution may result in improperoperation.Do not bury refrigerant piping underground.Although unit is weatherproof, avoid locations that permitwater from higher level runoff and overhangs to fall onto theunit.

Figure 3 Service Clearance Dimensional Drawing

LEFT:Min 18” (457 mm)requried for service

RIGHT:Min 18” (457 mm)requried for service

REAR:Min 18” (457 mm)requried for service

Note: Observe requirements for 39” (914 mm) operating clearance on either Left or Rear coil opening.

FRONT:42” (1067 mm)

Step 2 — Complete Pre--Installation ChecksCHECKUNIT ELECTRICAL CHARACTERISTIC—Confirmbefore installation of unit that voltage, amperage and circuitprotection requirements listed on unit data plate agree withpower supply provided.UNCRATEUNIT—Removeunit packaging except for the topskid assembly, which should be left in place until after the unitis rigged into its final location.INSPECT SHIPMENT— File a claim with shipping companyif the shipment is damaged or incomplete.

CONSIDER SYSTEM REQUIREMENTSS Consult local building codes and National Electrical

Code (NEC, U.S.A.) for special installationrequirements.

S Allow sufficient space for airflow clearance, wiring,refrigerant piping, and servicing unit. See Figure 1 and2 for unit dimensions and weight distribution data.

S Locate the unit so that the outdoor coil (condenser)airflow is unrestricted on all sides and above.

S The unit may bemounted on a level pad directly on thebase channels or mounted on raised pads at supportpoints. See Tables 1 and 2 for unit operating weights.See Figure 1 and 2 for weight distribution based onrecommended support points.

NOTE: If vibration isolators are required for a particularinstallation, use the data in Figure 1 and 2 tomake the properselection.

Step 3 — Prepare Unit Mounting SupportSlab MountProvide a level concrete slab that extends a minimum of 6 in.(150 mm) beyond unit cabinet. Install a gravel apron in front

Page 10: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

10 501 01 3403 01Specifications are subject to change without notice.

of condenser coil air inlet to prevent grass and foliage fromobstructing airflow.

Step 4 -- Rig and Mount the Unit

! CAUTIONUNIT OPERATION HAZARD

Failure to follow this caution may result in equipmentdamage.All panels must be in place when rigging. Unit is notdesigned for handling by fork truck.RIGGING— These units are designed for overhead rigging.Refer to the rigging label for preferred rigging method.Spreader bars are not required if top crating is left on the unit.All panelsmust be in placewhen rigging. As further protectionfor coil faces, plywood sheets may be placed against thesides of the unit, behind cables. Run cables to a centralsuspension point so that the angle from the horizontal is notless than 45 degrees. Raise and set the unit down carefully.If it is necessary to roll the unit into position, mount the unit onlongitudinal rails, using a minimum of 3 rollers. Apply force tothe rails, not the unit. If the unit is to be skidded into position,place it on a large pad and drag it by the pad. Do not apply anyforce to the unit.Raise from above to lift the unit from the rails or pad when unitis in its final position.After the unit is in position, remove all shipping materials andtop crating.

Step 5 — Complete Refrigerant PipingConnections

! CAUTIONUNIT OPERATION HAZARDFailure to follow this caution may result in improperoperation.Do not bury refrigerant piping underground.

! CAUTIONUNIT OPERATION HAZARDFailure to follow this caution may result in improperoperation.A refrigerant receiver is not provided with the unit. Do notinstall a receiver.PROVIDE SAFETY RELIEF — If local codes dictate anadditional safety relief device, purchase locally and installlocally. Installation will require the recovery of the factoryshipping charge before the factory tubing can be cut and thesupplemental relief device is installed.Model CAS180/240 has two separate refrigeration systems. Ifrequired, each circuit will require a field-supplied/installedsupplemental relief device.

Table 4 – Equivalent Lengths for Common Fittings (ft)

NominalTubeOD

Elbows

90 Std 90 Lrad 90 Street 45 Std 45 Street

3/8 1.3 0.8 2.2 0.6 11/2 1.4 0.9 2.3 0.7 1.15/8 1.6 1 2.5 0.8 1.33/4 1.8 1.2 2.9 0.9 1.57/8 2 1.4 3.2 0.9 1.6

11/8 2.6 1.7 4.1 1.3 2.1

13/8 3.3 2.3 5.6 1.7 3

15/8 4 2.6 6.3 2.1 3.4

21/8 5 3.3 8.2 2.6 4.5

NominalTubeOD

Tees

BranchFlow

Straight-Thru

No Reduct Reduce 25% Reduce 50%3/8 2.6 0.8 1.1 1.31/2 2.7 0.9 1.2 1.45/8 3 1 1.4 1.63/4 3.5 1.2 1.7 1.87/8 4 1.4 1.9 2

11/8 5 1.7 2.3 2.6

13/8 7 2.3 3.1 3.3

15/8 8 2.6 3.7 4

21/8 10 3.3 4.7 5

Check CAS Model with Evaporator Coil Connections —Confirm before installation of unit that the evaporator coilconnections are consistent with this CAS model. See Table3.SIZE REFRIGERANT LINES — Select the recommendedline sizes for CAS181/241 and CAS180/240 unit from theappropriate tables.Determine the linear length of interconnecting pipingrequired between the outdoor unit and indoor unit(evaporator). Consider and identify also the arrangement ofthe tubing path (quantity and type of elbows in both lines),liquid line solenoid size, filter drier and any otherrefrigeration specialties located in the liquid line. Refer tothe indoor unit installation instructions for additional detailson refrigeration specialties devices.Determine equivalent line length adjustments for path andcomponents and add to linear line lengths. See Table 4,Equivalent Lengths for Common Fittings, for usual fittingtypes. Also identify adjustments for refrigeration specialties.NOTE: Equivalent line lengths will vary based on tubediameter. Calculate equivalent line length for each pipe byadding equivalent length adjustments to linear lengths foreach pipe.Enter the appropriate table to select the recommended linesizes.

Page 11: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

11501 01 3403 01 Specifications are subject to change without notice.

Model: Line Sizes Table Quantity of LineSets

CAS181/241 5 1

CAS180/240 6 2

Liquid Lift —A liquid lift condition exists when the outdoor unit is locatedbelow the indoor (evaporator) unit and liquid flows verticallyup in a portion of the liquid line. The vertical column ofliquid reduces the available state point subcooling at theevaporator coil’s thermal expansion valve. This effectreduces the length of liquid lift (feet of elevation) that aliquid line size can accommodate. Longer linear tubelengths will also reduce the amount of liquid lift possible.Check Tables 5 (CAS181/241) and 6 (CAS180/240) formaximum liquid lift capabilities for line sizes. Reselect theliquid line tube size if necessary. If maximum available tube

size cannot provide the required lift distance on thisinstallation, relocate the outdoor unit to reduce theequivalent line length or the lift requirement.Suction Riser —A suction riser condition exists when the outdoor unit islocated above the indoor (evaporator) unit and suctionvapor must flow vertically up to return to the compressor.Oil return is a concern when the suction tube size is toolarge to produce the minimum refrigerant velocity to ensureoil return at minimum load conditions.Check Table 7 for maximum suction tube size for CAS unitsat minimum load conditions. Consider suction speed riser(reduced tube size for vertical segment only) or doublesuction riser arrangement if the recommended suction tubesize does not provide necessary minimum flowrates for thisriser.

Table 5 – CAS181/241 Piping Recommendations (Single-Circuit Unit)

R-410A Equivalent Length

Ft 0-38 38-75 75-113 113-150 150-188

m 0-12 12-23 23-34 34-46 46-57

Model Typ Linear ft 0-25 25-50 50-75 75-100 100-125

CAS181

Liquid Line 5/8 5/8 5/8 5/8 5/8

Max Lift 25 50 75 100 125

Suction Line 1-1/8 1-3/8 1-3/8 1-3/8 1-3/8 1-5/8

Charge (lbs) 24.3 27.5 30.6 33.7 37.8

CAS241

Liquid Line 5/8 5/8 5/8 5/8 5/8

Max Lift 25 50 71 77 63

Suction Line 1-1/8 1-3/8 1-3/8 1-3/8 1-5/8 1-5/8 1-5/8

Charge (lbs) 37.8 40.8 44.6 47.8 51.1

Legend:

Length Equiv Equivalent tubing length, including effects of refrigeration specialties devices

Typ Linear Typical linear tubing length, Feet (50% added to linear to define Equivalent Length for this table)

Liquid Line Tubing size, inches OD.

Max Lift Maximum liquid lift (indoor unit ABOVE outdoor unit only), at maximum permitted liquid line pressure drop —S Linear Length Less than 100 ft: Minimum 2.0F subcooling entering TXVS Linear Length Greater than 100 ft: Minimum 0.5F subcooling entering TXV

Suction Line Tube size, inches OD

Charge Charge Quantity, lbs. Calculated for both liquid line sizes (where applicable), but only with larger suction line size(where applicable)

NOTE: For applications with equivalent length greater than 188 ft (57 m) and/0r linear length greater than 125 ft (38 m),contact your local distributor.

Page 12: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

12 501 01 3403 01Specifications are subject to change without notice.

Table 6 – CAS180/240 Piping Recommendations (Two-Circuit Unit)

NOTE: CAS180/240 requires TWO sets of refrigeration piping

R-410A Equivalent Length

Ft 0-38 38-75 75-113 113-150 150-188

m 0-12 12-23 23-34 34-46 46-57

Model Typ Linear ft 0-25 25-50 50-75 75-100 100-125

CAS180

Liquid Line 1/2 1/2 1/2 1/2 1/2

Max Lift 25 50 75 100 125

Suction Line 7/8 11/8 11/8 11/8 11/8

Charge ea. (lbs) 11.7 13.8 15.7 17.6 19.6

CAS240

Liquid Line 1/2 1/2 1/2 5/8 1/2 5/8 1/2 5/8

Max Lift 25 50 54 75 60 99 46 95

Suction Line 11/8 11/8 11/8 11/8 13/8 13/8

Charge (lbs) AB

19.318.3

21.020.3

23.022.0

26.025.0

25.924.9

29.728.7

28.027.0

32.731.7

Legend:

Length Equiv Equivalent tubing length, including effects of refrigeration specialties devices

Typ Linear Typical linear tubing length, Feet (50% added to linear to define Equivalent Length for this table)

Liquid Line Tubing size, inches OD.

Max Lift Maximum liquid lift (indoor unit ABOVE outdoor unit only), at maximum permitted liquid line pressure drop —S Linear Length Less than 100 ft: Minimum 2.0F subcooling entering TXVS Linear Length Greater than 100 ft: Minimum 0.5F subcooling entering TXV

Suction Line Tube size, inches OD

Charge Charge Quantity, lbs. Calculated for both liquid line sizes (where applicable), but only with larger suction line size(where applicable)

NOTE: For applications with equivalent length greater than 188 ft (57 m) and/0r linear length greater than 125 ft (38 m),contact your local distributor.

Table 7 – CAS Maximum Suction Pipe Size

Model: Maximum Tube Size

CAS181/24115/8

15/8

CAS180/24015/8

15/8

Insulate Suction Lines —Apply closed-cell tubular insulation to all suction linesbetween evaporator coil connection and CAS unit’s suctionservice valve.Hot Gas Bypass —Hot gas bypass, if used, should be introduced before theevaporator. (A bypass route that also bypasses theevaporator circuit may lead to oil trapping in the evaporatorcircuit during low load conditions and then to oil slugging asevaporator load increases.) Model CAS units do notinclude a hot gas stub connection; a tee must befield-supplied and installed in the compressor dischargeline. Run a 1/2-in OD line between outdoor unit andevaporator coil inlet. Install an Auxiliary Side Connector atthe evaporator between TXV and distributor (followinstructions for the side connector part). Insulate the hotgas line.

CAS180/240: Generally only one hot gas bypass systemwill be applied on a two-circuit unit. Connect the hot gasbypass system to Circuit 1 (first-on/last-off, connected tothe evaporator coil’s bottom circuit).CAS180/240 Piping Connections —The CAS180/240’s two circuits are designated Circuit 1and Circuit 2. Circuit 1 is controlled by the thermostat’s Y1(or TC1) contact and will be the first circuit on and lastcircuit off. Circuit 2 is controlled by the thermostat’s Y2 (orTC2) contact and this circuit is always the “lag” circuit.See Fig. 4 for location of Circuit 1 and Circuit 2 servicevalves and field piping connections. Circuit 1 is on theleft-hand side of the service valve compartment; Circuit 2 ison the right.When a single piece evaporator coil with two separatecircuits is connected to a CAS180/240, the lower coil circuitshould be connected to the CAS180/240’s Circuit 1 so thatthe evaporator’s lower coil segment is first-on/last-off (toavoid re-evaporation of condensate on dry lower coilsegments).

Page 13: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

13501 01 3403 01 Specifications are subject to change without notice.

Circuit 1 Connections

Circuit 2 Connections

CKT1

CKT1

CKT2

CKT2

Figure 4 CAS180/240 Service valve Locations

Plan the Circuit 1 and Circuit 2 tubing segments carefully,mark each segment and check constantly as pipingsystems are assembled to avoid piping errors.CAS180/240 unit cannot be field-piped as asingle-circuit/tandem system.Connecting FAS to CAS180/240: The FAS fan coil insizes 15, 20 and 25 ton is a face-split coil design that alsohas its circuits designated as 1 and 2. See Fig.5. Note thatthe lower coil segment changes as the arrangement of theFAS changes. In a vertical arrangement, the FAS’s lowercoil segment is segment 2; this segment should beconnected to the CAS180/240’s Circuit 1. In a horizontalarrangement, the FAS’s lower segment is now segment 1;this segment should be connected to the CAS180/240’sCircuit 1.Note that refrigerant suction piping should be insulated.

FASArrangement

CoolingStage

FAS CoilSegment

Connect toCAS180/240

Vertical Y1Y2

21

Circuit 1Circuit 2

Horizontal Y1Y2

12

Circuit 1Circuit 2

Install Filter Drier(s) and Moisture Indicator(s) —Every unit MUST have a filter drier in the liquid line.CAS180/240 models require two filter driers (one in eachliquid line). Locate the filter drier(s) at the indoor unit, closeto the evaporator coil’s thermal expansion valve (TXV)inlets.

CAS units include one (CAS181/241) or two (CAS180/240)R--410A-duty filter drier(s), shipped in cartons attached tothe unit basepan. Remove the filter drier(s) and prepare toinstall in the liquid line(s) at the evaporator coil. Do notremove connection fitting plugs until ready to connect andbraze the filter drier into the liquid line position.

Figure 5 Typical Evaporator Coil Connections (FAS)

FIRST ON/LAST OFF = 2VERTICAL INSTALLATION

FIRST ON/LAST OFF = 1HORIZONTAL INSTALLATION

1

2

2

1

Table 8 – R--410A-duty Filter Drier(s)

Model-Size QtyLiquidLine OD

DesiccantVolume

PartNumber Ref

CAS181 1 5/8-in 30 cu. in. KH43LS087

CAS241 1 5/8-in 30 cu. in. KH43LS087

CAS180 2 1/2-in 16 cu. in. KH43LS085

CAS240 2 1/2-in 16 cu. in. KH43LS085

Installation of liquid line moisture indicating sightglass ineach circuit is recommended. Locate the sightglass(es)between the outlet of the filter drier and the TXV inlet.Refer to Table 9 for recommendations on refrigerationspecialties.

Table 9 – Refrigerant Specialties Part Numbers.

LIQUID LINESIZE (in.)

LIQUID LINESOLENOID VALVE (LLSV)

LLSVCOIL

SIGHTGLASS

FILTERDRIER

1/2 1179872 1179874 1179877provided with unit

see Table 85/8 1179873 1179874 1179878

CAS180/240 units require TWO sets of parts.

Page 14: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

14 501 01 3403 01Specifications are subject to change without notice.

Figure 6Location of Sight Glass(es) and Filter DriersTypical CAS181/241 Systems

INDOORCOIL CKT 2

AIRFLOW

INDOORCOIL CKT 1

AIRFLOW

15 DIAMSMIN 10

DIAMS8 DIAMS

MIN

TXVSENSINGBULB

EQUALIZER LINE

SIGHT GLASSA LOCATION

SIGHT GLASSESB LOCATION

TXVCKT 2

FILTER DRIERA LOCATION

FILTER DRIERS B LOCATION

FLOWTXVSENSINGBULB

TXVCKT 1

8 DIAMSMIN

15 DIAMSMIN 10

DIAMS

Single Circuit Coil Piping ConfigurationFor single compressor condensing units

Dual Circuit Coil Piping ConfigurationFor single compressor condensing units

15 DIAMSMIN 10

DIAMS8 DIAMS

MIN

INDOORCOIL CKT

AIRFLOW

TXVSENSINGBULB

EQUALIZER LINE

SIGHT GLASSA LOCATION

TXV

FILTER DRIERA LOCATION

LIQUID LINESOLENOIDVALVE

FLOW

LIQUID LINESOLENOIDVALVE

Figure 7Location of Sight Glass(es) and Filter DriersTypical CAS180/240 Systems

AIRFLOW

SUCTIONCIRCUIT 2

SUCTIONCIRCUIT 1

AIRFLOW

15 DIAMSMIN 10

DIAMS8 DIAMS

MIN

TXVSENSINGBULB

EQUALIZER LINE

SIGHT GLASSES

TXVCKT 2

FILTER DRIERS

LIQUID LINESOLENOID VALVECIRCUIT 2

FLOW

LIQUID LINESOLENOID VALVECIRCUIT 1

FLOW

TXVSENSINGBULB

TXVCKT 1

8 DIAMSMIN

15 DIAMSMIN 10

DIAMS

Dual Circuit Coil Piping ConfigurationFor two circuit condensing units

In some applications, depending on space andconvenience requirements, it may be desirable to install 2filter driers and sight glasses in a single circuit application.One filter drier and sight glass may be installed at Alocations (see Fig. 6) or 2 filter driers and sight glassesmay be installed at B locations (see Figs. 6 and 7).Select the filter drier for maximum unit capacity andminimum pressure drop. Complete the refrigerant pipingfrom the indoor unit to the outdoor unit before opening theliquid and suction lines at the outdoor unit.

Install Liquid Line Solenoid Valve —It is recommended that a solenoid valve be placed in themain liquid line (see Figs. 6 & 7) between the condensingunit and the evaporator coil. Locate the solenoid valve atthe outlet end of the liquid line, near the evaporator coilconnections, with flow direction arrow pointed at theevaporator coil. Refer to Table 9. (A liquid line solenoidvalve is required when the liquid line length exceeds 75 ft[23 m].) This valve prevents refrigerant migration (whichcauses oil dilution) to the compressor during the off cycle,at low outdoor ambient temperatures. Wire the solenoid inparallel with the compressor contactor coil (see Figs. 6 &7). This means of electrical control is referred to assolenoid drop control.Capacity Control Liquid Line Solenoid Valve: Evaporatorcapacity control via liquid solenoid valve is not recommendedfor use with CAS models.Make Piping Connections —Piping connections at the CAS unit are ball valves with stubtube extensions. Do not open the unit service valves untilall interconnecting tube brazing has been completed.The stub tube connections include 1/4-in SAE servicefittings with Schrader valve cores (see Fig. 10). Beforemaking any brazed connections to the unit service valves,remove both Schrader valve caps and cores and save forre-installation. Connect a source for nitrogen to one ofthese service fittings during tube brazing to prevent theformation of copper oxides inside the tubes at brazedjoints.

Figure 8 Typical Piping Connection Assembly

Factory High-FlowAccess Port

Service Valvewith Stem Cap

Field ServiceAccess Port(Schrader core)

SweatConnection

When connecting the field tubing to the CAS servicevalves, wrap the valves in wet rags to prevent overheatingPressure-test all joints from outdoor unit connections overto the evaporator coil, using nitrogen as pressure and withsoap-and-bubbles.When pressure-testing is completed, remove the nitrogensource at the outdoor unit service valves and re-install thetwo Schrader valve cores. Torque the cores to 2-3 in-lbs(23-34 N-cm).

Page 15: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

15501 01 3403 01 Specifications are subject to change without notice.

Evacuation/Dehydration —Evacuate and dehydrate the connected refrigerationsystem(s) (excluding the CAS unit) to 500 microns using atwo-stage vacuum pump attached to the service portsoutside the CAS service valves, following description inGTAC II, Module 4, System Dehydration.

UNIT OPERATION AND SAFETY HAZARDFailure to follow this warning could cause personalinjury, death and/or equipment damage.R--410A refrigerant systems operate at higherpressure than standard R--22 systems. Do not useR--22 service equipment or components on R--410Arefrigerant equipment.

! WARNING

This unit is designed for use with R--410A refrigerant. Donot use any other refrigerant in this system.R--410A refrigerant is provided in pink (rose) coloredcylinders. These cylinders are available with and withoutdip tubes; cylinders with dip tubes will have a labelindicating this feature. For a cylinder with a dip tube, placethe cylinder in the upright position (access valve at the top)when removing liquid refrigerant for charging. For acylinder without a dip tube, invert the cylinder (access valveon the bottom) when removing liquid refrigerant.Because R--410A refrigerant is a blend, it is stronglyrecommended that refrigerant always be removed from thecylinder as a liquid. Admit liquid refrigerant into the systemin the discharge line. If adding refrigerant into the suctionline, use a commercial metering/expansion device at thegauge manifold; remove liquid from the cylinder, pass itthrough the metering device at the gauge set and thenpass it into the suction line as a vapor. Do not removeR--410A refrigerant from the cylinder as a vapor.Preliminary Charge —Before starting the unit, charge R-410A liquid refrigerantinto the high side of each CAS circuit through the liquidservice valve(s). The amount of refrigerant added must beat least 80% of the operating charge listed in Tables 5 or 6for LINEAR line length LESS the factory charge quantity (iffactory shipping charge has not been removed). Seeexample below.Allow high and low side pressures to equalize. If pressuresdo not equalize readily, charge R-410A vapor (usingspecial service manifold with expansion device) into thesuction line service port for the low side of system toassure charge in the evaporator. Refer to GTAC II, Module5, Charging, Recover, Recycling, and Reclamation forliquid charging procedures.

Example:CAS24060-ft (18.3 m) linear line lengthEquivalent line length 90-ft (27.4 m)Liquid Lift: 20-ft (6.1 m)Select line sizes from Table 6 (CAS180/240):Liquid 1/2 inSuction 1-1/8 in.ChargeCircuit 1: 23.0 lbs (at 75-ft linear length)Circuit 2: 22.0 lbs80% of Operating Charge:Circuit 1: 0.80 x 23.0 = 18.4 lbsCircuit 2: 0.80 x 22.0 = 17.6 lbsFactory Shipping Charge: 15 lbsField-ChargeCircuit 1: 18.4 -- 15 = 3.4 lbsCircuit 2: 17.6 -- 15 = 2.6 lbsFor linear line lengths longer than 125 ft (38 m), contactyour local distributor for system charge value.Step 1 — Install AccessoriesAccessories requiring modifications to unit wiring should becompleted now. These accessories may include WinterStart controls and Low Ambient controls. Refer to theinstructions shipped with the accessory.Step 2 — Complete Electrical Connections

ELECTRICAL SHOCK HAZARDFailure to follow this warning could result in personalinjury or death.Do not use gas piping as an electrical ground. Unitcabinet must have an uninterrupted, unbroken electricalground to minimize the possibility of personal injury if anelectrical fault should occur. This ground may consist ofelectrical wire connected to unit ground lug in controlcompartment, or conduit approved for electrical groundwhen installed in accordance with NEC (NationalElectrical Code); ANSI/NFPA 70, latest edition (inCanada, Canadian Electrical Code CSA [CanadianStandards Association] C22.1), and local electrical codes.

! WARNING

NOTE: Check all factory and field electrical connectionsfor tightness. Field-supplied wiring shall conform with thelimitations of 63F (33C) rise.Field Power Supply —If equipped with optional Powered Convenience Outlet:The power source leads to the convenience outlet’stransformer primary are not factory connected. Installermust connect these leads according to required operationof the convenience outlet. If an always-energizedconvenience outlet operation is desired, connect thesource leads to the line side of the unit-mounteddisconnect. (Check with local codes to ensure this methodis acceptable in your area.) If a de-energize via unit

Page 16: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

16 501 01 3403 01Specifications are subject to change without notice.

disconnect switch operation of the convenience outlet isdesired, connect the source leads to the load side of theunit disconnect. On a unit without a unit-mounteddisconnect, connect the source leads to compressorcontactor C and indoor fan contactor IFC pressure lugswith unit field power leads..Field power wires are connected to the unit at line-sidepressure lugs on compressor contactor C and TB1 (seewiring diagram label for control box componentarrangement) or at factory-installed option non-fuseddisconnect switch. Max wire size is #4 AWG (copper only).NOTE: TEST LEADS - Unit may be equipped with shortleads (pigtails) on the field line connection points oncontactor C or optional disconnect switch. These leads arefor factory run-test purposes only; remove and discardbefore connecting field power wires to unit connectionpoints. Make field power connections directly to lineconnection pressure lugs only.

FIRE HAZARDFailure to follow this warning could cause in personalinjury, death and/or equipment damage.Do not connect aluminum wire between disconnectswitch and condensing unit. Use only copper wire.(See Fig. 9.)

! WARNING

Figure 9 Disconnect Switch and Unit

COPPER

WIRE ONLY

ELECTRICDISCONNECT

SWITCH

ALUMINUMWIRE

Units Without Factory-Installed Disconnect —When installing units, provide a disconnect switch per NEC(National Electrical Code) of adequate size. Disconnectsizing data is provided on the unit informative plate. Locateon unit cabinet or within sight of the unit per national orlocal codes. Do not cover unit informative plate if mountingthe disconnect on the unit cabinet.Units with Factory-Installed Disconnect —The factory-installed option disconnect switch is located ina weatherproof enclosure located under the main controlbox. The manual switch handle is accessible through anopening in the access panel.All Units —All field wiring must comply with NEC and all local codes.Size wire based on MCA (Minimum Circuit Amps) on theunit informative plate. See Fig. 10 for power wiringconnections to the unit contactor and terminal block andequipment ground.

Provide a ground-fault and short-circuit over-currentprotection device (fuse or breaker) per NEC Article 440 (orlocal codes). Refer to unit informative data plate for MOCP(Maximum Over-current Protection) device size.All units except 208/230-v units are factory wired for thevoltage shown on the nameplate. If the 208/230-v unit is tobe connected to a 208-v power supply, the controltransformer must be rewired by moving the black wire withthe -in. female spade connector from the 230-vconnection and moving it to the 208-v -in. male terminalon the primary side of the transformer. Refer to unit labeldiagram for line-side information.

Figure 10 Power Wiring Connections

11 13

L1 L2 L3

C TB1

208/230-3-60460-3-60575-3-60

Units Without Disconnect Option

Units With Disconnect Option

2

4

6

1

3

5

L1

L2

L3

OptionalDisconnect

Switch

Disconnect factory test leads; discard.

FactoryWiring

Disconnectper

NEC

Affix the crankcase heater warning sticker to the unitdisconnect switch.Convenience Outlets —

ELECTRICAL OPERATION HAZARDFailure to follow this warning could result in personalinjury or death.Units with convenience outlet circuits may use multipledisconnects. Check convenience outlet for powerstatus before opening unit for service. Locate itsdisconnect switch, if appropriate, and open it. Tag-outthis switch, if necessary.

! WARNING

A non--powered convenience outlets is offered on CASmodels and provide a 125-volt GFCI (ground-faultcircuit-interrupter) duplex receptacle rated at 15-A behind ahinged waterproof access cover, located on the end panelof the unit. See Fig. 11.Non-powered type: This type requires the field installationof a general-purpose 125-volt 15-A circuit powered from a

Page 17: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

17501 01 3403 01 Specifications are subject to change without notice.

source elsewhere in the building. Observe national andlocal codes when selecting wire size, fuse or breakerrequirements and disconnect switch size and location.Route 125-v power supply conductors into the bottom ofthe utility box containing the duplex receptacle.

Figure 11 Convenience Outlet Location

ConvenienceOutletGFCI

Control BoxAccess Panel

ELECTRICAL OPERATION HAZARDFailure to follow this warning could result in personalinjury or death.Using unit-mounted convenience outlets: Units withunit-mounded convenience outlet circuits will oftenrequire that two disconnects be opened to de-energizeall power to the unit. Treat all units as electricallyenergized until the convenience outlet power is alsochecked and de-energization is confirmed. ObserveNational Electrical Code Article 210, Branch Circuits,for use of convenience outlets.

! WARNING

Installing Weatherproof Cover: A weatherproof while inuse cover for the factory installed convenience outlets isnow required by UL standards. This cover cannot befactory mounted due its depth; it must be installed at unitinstallation. For shipment, the convenience outlet iscovered with a blank cover plate.The weatherproof cover kit is shipped in the unit’s controlbox. The kit includes the hinged cover, a backing plate andgasket.DISCONNECT ALL POWER TO UNIT ANDCONVENIENCE OUTLET.Remove the blank cover plate at the convenience outlet;discard the blank cover.Loosen the two screws at the GFCI duplex outlet, untilapproximately 1/2--in (13 mm) under screw heads areexposed. Press the gasket over the screw heads. Slip thebacking plate over the screw heads at the keyhole slotsand align with the gasket; tighten the two screws until snug(do not overtighten).Mount the weatherproof cover to the backing plate asshown in Fig. 12. Remove two slot fillers in the bottom of

the cover to permit service tool cords to exit the cover.Check for full closing and latching.

Figure 12 Weatherproof Cover Installation

All Units —Voltage to compressor terminals during operation must bewithin voltage range indicated on unit nameplate. SeeTable 10. On 3-phase units, voltages between phases mustbe balanced within 2% and the current within 10%. Use theformula shown in the legend for Tables 10 and 11, Note 5to determine the percent of voltage imbalance. Operationon improper line voltage or excessive phase imbalanceconstitutes abuse and may cause damage to electricalcomponents. Such operation would invalidate anyapplicable warranty.Field Control Wiring —CAS unit control voltage is 24v. See Fig. 13 (CAS181/241)and Fig. 14 (CAS180/240) for typical field controlconnections and the unit’s label diagram for field-suppliedwiring details. Route control wires to the CAS unit throughthe opening in unit’s end panel to the connections terminalboard in the unit’s control box.Remainder of the system controls connection will varyaccording to the specific construction details of the indoorsection (air handler or packaged fan coil). Fig. 13(CAS181/241) and Fig. 14 (CAS180/240) depict typicalconnections to a FAS fan coil unit. Plan for fieldconnections carefully and install control wiring correctly perthe project plan. Additional components and supplementaltransformer accessory may be required.The CAS unit requires an external temperature controldevice. This device can be a thermostat (field-supplied) ora thermostat emulation device provided as part of athird--party Building Management System.Thermostat —Install an approved accessory thermostat according toinstallation instructions included with the accessory. Locatethe thermostat accessory on a solid wall in the conditionedspace to sense average temperature in accordance withthe thermostat installation instructions.

Page 18: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

18 501 01 3403 01Specifications are subject to change without notice.

The CAS181/241 is a single-circuit, two--stage cooling unit.Select a two—stage cooling thermostat, with or withoutsupplemental heating as needed.The CAS180/240 is a dual--circuit, two-stage cooling unit.Select a two—stage cooling thermostat, with or withoutsupplemental heating as needed.Select a thermostat cable or equivalent single leads ofdifferent colors with minimum of five leads for CAS181/241 orsix leads for CAS180/240 unit. Check the thermostatinstallation instructions for additional features which mightrequire additional conductors in the cable.For wire runs up to 50 ft. (15 m), use no. 18 AWG(American Wire Gage) insulated wire (35C minimum). For50 to 75 ft. (15 to 23 m), use no. 16 AWG insulated wire(35C minimum). For over 75 ft. (23 m), use no. 14 AWGinsulated wire (35C minimum). All wire sizes larger thanno. 18 AWG cannot be directly connected to the thermostatand will require a junction box and splice at the thermostat.

Figure 13 Typical Remote Thermostat ConnectionsCAS181/241

Note 1: Typical multi-function marking. Follow manufacturer’s configuration instructions to select Y2.Note 2: Connect only if thermostat requires 24-vac power source.Note 3: Connect W1 and W2 if supplemental heaters are installed Field Wiring

(Note 1)

(Note 2)

(Note 3)

(Note 3)

Figure 14 Typical Remote Thermostat ConnectionsCAS180/240

Note 1: Typical multi-function marking. Follow manufacturer’s configuration instructions to select Y2.Note 2: Connect only if thermostat requires 24-vac power source.Note 3: Connect W1 and W2 if supplemental heaters are installed Field Wiring

(Note 1)

(Note 2)

(Note 3)

(Note 3)

Control Circuit Wiring —Control voltage is 24 v. See Figs. 13 and 14 and the unit’slabel diagram for field--supplied wiring details. Routecontrol wires through the opening in unit’s end panel to theconnection in the unit’s control box.Control Transformer Wiring —On multi voltage units, check the transformer primarywiring connections. See Fig. 15 or refer to the unit’s labeldiagram.If the unit will be operating at 208-3-60 power, remove theblack wire (BLK) from the transformer primary connectionlabelled “230” and move it to the connection labelled “208”.See Fig. 15.

Figure 15 Control Transformer Wiring

Page 19: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

19501 01 3403 01 Specifications are subject to change without notice.

Table 10 – Unit Wire/Fuse or HACR Breaker Sizing Data

UNITSIZECAS

NOMINALPOWERSUPPLY

VOLTAGERANGE

COMPRESSOR NO C.O. or UNPWRD C.O.

No. 1 No. 2 OFM POWER SUPPLY DISCONNECT SIZE

V--Ph--Hz Min Max RLA LRA RLA LRA QtyFLA(ea) MCA

FUSE orHACRBRKR FLA LRA

181180

208/230--3--60 187 253 25.0 164 25.0 164 3 1.5 60.8/60.8 80/80 63/63 337/337

460--3--60 414 506 12.2 100 12.2 100 3 0.8 29.9 40 31 206

575--3--60 518 633 9.0 78 9.0 78 3 0.7 22.4 30 23 162

241240

208/230--3--60 187 253 30.1 225 30.1 225 4 1.5 73.7/73.7 100/100 76/76 462/462

460--3--60 414 506 16.7 114 16.7 114 4 0.8 40.8 50 42 236

575--3--60 518 633 12.2 80 12.2 80 4 0.7 30.3 40 31 168

Legend and Notes for Table 10LEGEND:BRKR --- Circuit breakerCO --- Convenient outletFLA --- Full Load AmpsLRA --- Locked Rotor AmpsMCA --- Minimum Circuit Amps

ProtectionNEC --- National Electrical CodeRLA --- Rated Load AmpsUNPWR CO --- Unpowered convenient outletNOTES:1. In compliance with NEC requirements for multimotor andcombination load equipment (refer to NEC Articles 430 and440), the overcurrent protective device for the unit shall befuse or HACR breaker. Canadian units may be fuse or cir-cuit breaker.

2. The MCA values are calculated in accordance with TheNEC. Article 440.

3. Motor RLA and LRA values are established in accordancewith Underwriters’ Laboratories (UL). Standard 1995.

4. The 575---v units are UL, Canada--- listed only.5. Unbalanced 3-Phase Supply VoltageNever operate a motor where a phase imbalance in supplyvoltage is greater than 2%. Use the following formula to de-termine the percentage of voltage imbalance.

Example: Supply voltage is 230-3-60

% Voltage Imbalance = 100 xmax voltage deviation from average voltage

average voltage

AB = 224 vBC = 231 vAC = 226 v

Average Voltage =(224 + 231 + 226)

=681

3 3

= 227

Determine maximum deviation from average voltage.(AB) 227 – 224 = 3 v(BC) 231 – 227 = 4 v(AC) 227 – 226 = 1 vMaximum deviation is 4 v.Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x4

227

= 1.76%

This amount of phase imbalance is satisfactory as it is below themaximum allowable 2%.IMPORTANT: If the supply voltage phase imbalance is more than 2%,contact your local electric utility company immediately.

Page 20: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

20 501 01 3403 01Specifications are subject to change without notice.

PRE-START-UP

IMPORTANT: Before beginning Pre-Start-Up orStart-Up, review Start-Up Checklist at the back of thisbook. The Checklist assures proper start-up of a unitand provides a record of unit condition, applicationrequirements, system information, and operation atinitial start-up.

UNIT DAMAGE HAZARDFailure to follow this caution may result in equipmentdamage.Do not attempt to start the condensing unit, evenmomentarily, until the following steps have beencompleted. Compressor damage may result.

CAUTION!

System Check1.The electrical power source must agree with the unit’s

nameplate rating.2.Check all air handler(s) and other equipment auxiliary

components. Consult the manufacturer’s instructionsregarding any other equipment connected to thecondensing unit. If the unit has field-installed accessories,be sure all are properly installed and correctly wired. Ifused, the airflow switch must be properly installed.

3.Check tightness of all electrical connections.4.Be sure liquid line and low side of the system are

properly leak checked and dehydrated.5.Be sure the unit is properly charged. See “Preliminary

Charge”, below.6.Open the liquid line and suction line service valves.7.The crankcase heater must be firmly attached to the

compressor crankcase. Be sure the crankcase is warm(heater must be on for 24 hours before startingcompressor).

Turn On Crankcase Heater —Turn on the crankcase heater for 24 hours before startingthe unit to be sure all the refrigerant is out of the oil. Toenergize the crankcase heater, proceed as follows:1.Set the space thermostat set point above the space

temperature so there is no demand for cooling.2.Close the field disconnect.Preliminary Charge —Before starting the unit, charge liquid refrigerant into the highside of the system through the liquid service valve. Theamount of refrigerant added must be at least 80% of theoperating charge listed in the Physical Data table (Tables 1through 2. Allow high and low side pressures to equalizebefore starting compressor. If pressures do not equalizereadily, charge vapor on low side of system to assure chargein the evaporator. Refer to GTAC II, Module 5, Charging,Recover, Recycling, and Reclamation for liquid chargingprocedures.

UNIT DAMAGE HAZARDFailure to follow this caution may result in equipmentdamage.Prior to starting compressor, a preliminary charge ofrefrigerant must be added to avoid possible compressordamage.

CAUTION!

START-UPCAS Units: T:he compressor crankcase heater must be onfor 24 hours before start-up. After the heater has been onfor 24 hours, the unit can be started. If no time elapsedsince the preliminary charge step was completed, it isunnecessary to wait the 24-hour period.

Preliminary Checks1.Check that electric power supply agrees with unit

nameplate data.2.Verify that the compressor crankcase heater is securely

in place.3.Check that the compressor crankcase heater has been

on at least 24 hours.4.Re--check for leaks using the procedure outlined in the

Pre-Start-Up section, Leak Test and Dehydration. If anyleaks are detected, repair as required. Evacuate anddehydrate as described in the Leak Test andDehydration section.

5.Ensure that the preliminary charge has been added asdescribed in the Pre-Start-Up section, PreliminaryCharge.

6.All internal wiring connections must be tight, and allbarriers and covers must be in place.

NOTE: The CAS units are factory charged with therequired amount of oil. If recharging in required, useEmkarate RL 32-3MAF for the CAS units.Compressor Rotation —On 3--phase units with scroll compressors, it is important tobe certain that the compressor is rotating in the properdirection. CAS units are equipped with a Comfort AlertDiagnostic Module (CADM). Alert Code 7 indicates reversepower phasing.To correct phase order:1.Turn off power to the unit, tag disconnect.2.Reverse any two of the unit power leads.3.Reapply power to the compressor, verify correct

pressures.To verify the compressor is rotating in the properdirection:1.Connect service gages to the suction and liquid pressure

fittings.2.Energize the compressor.3.The suction pressure should drop and the liquid pressure

should rise, as is normal on any start--up.

Page 21: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

21501 01 3403 01 Specifications are subject to change without notice.

Compressor Overload —This overload interrupts power to the compressor wheneither the current or internal motor winding temperaturebecomes excessive, and automatically resets when theinternal temperature drops to a safe level. This overloadmay require up to 60 minutes (or longer) to reset. If theinternal overload is suspected of being open, disconnectthe electrical power to the unit and check the circuitthrough the overload with an ohmmeter or continuity tester.Advanced Scroll Temperature Protection (ASTP) —A label located above the terminal box identifies CopelandScroll compressor models that contain this technology. SeeFig. 16. Advanced Scroll Temperature Protection (ASTP) is aform of internal discharge temperature protection, thatunloads the scroll compressor when the internal temperaturereaches approximately 149_C (300_F). At this temperature,an internal bi--metal disk valve opens and causes the scrollelements to separate, which stops compression. Suctionand discharge pressures balance while the motor continuesto run. The longer the compressor runs unloaded, the longerit must cool before the bi--metal disk resets. See Fig. 17.

Figure 16 Advanced Scroll Temperature Protection Label

Figure 17Recommended Minimum Cool Down TimeAfter Compressor is Stopped

0102030405060708090

100110120

0 10 20 30 40 60 70 80 9050

Compressor Unloaded Run Time (Minutes)*

*Times are approximate.NOTE: Various factors, including high humidity, high ambient temperature, and the presence of a sound blanket will increase cool-down times.

Rec

omm

ende

d C

oolin

g Ti

me*

(Min

utes

)

To manually reset ASTP, the compressor should bestopped and allowed to cool. If the compressor is notstopped, the motor will run until the motor protector trips,which occurs up to 90 minutes later. Advanced ScrollTemperature Protection will reset automatically before themotor protector resets, which may take up to 2 hours.

Start UnitSet the space thermostat to a set point above spacetemperature so that there is no demand for cooling. Closethe CAS disconnect switch. Only the crankcase heater willbe energized.Reset the space thermostat below ambient so that a call forcooling is ensured.

UNIT DAMAGE HAZARDFailure to follow this caution may result in equipmentdamage.Never charge liquid into the low-pressure side ofsystem. Do not overcharge. During charging or removalof refrigerant, be sure indoor-fan system is operating.Ensure both outdoor fan motors are running; bypass anyMotormaster function.

CAUTION!

Adjust Refrigerant Charge —The unit must be charged in Cooling mode only. Refer toCooling Charging Charts, Fig. 19 through Fig. 22. Forapplications with line lengths greater than 125 ft, contact yourdistributor. Vary refrigerant until the conditions of the chart aremet. Note that the charging charts are different from the typenormally used. The charts are based on charging the units tothe correct subcooling for the various operating conditions.Accurate pressure gage and temperature sensing device arerequired. Connect the pressure gage to the service port onthe liquid line service valve. Mount the temperature sensingdevice on the liquid line close to the liquid line service valve,and insulate it so that outdoor ambient temperature does notaffect the reading. Indoor airflow must be within the unit’snormal operating range. Operate the unit for a minimum of 15minutes. Ensure that pressure and temperature readingshave stabilized. Plot the liquid pressure and temperature onchart and add or reduce the charge to meet the curve. Adjustthe charge to conform with the charging chart, using theliquid pressure and temperature to read the chart.CAS241 Check Compressor Oil Level —After adjusting the refrigerant charge, allow the unit to runfully loaded for 20 minutes. Stop the compressors andcheck the oil level. Oil level should be 1/3 to 1/2 up on thesight glass (see Fig. 18).

Figure 18 Recommended Oil Level -- CAS241

1/3 (MIN)1/2 (MAX)

Page 22: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

22 501 01 3403 01Specifications are subject to change without notice.

IMPORTANT: Oil level should only be checkedwhen the compressors are off.

Add oil only if necessary to bring the oil into view in thesight glass. If oil is added, run the circuit for an additional10 minutes, then stop and check oil level. If the levelremains low, check the piping system for proper design foroil return; also, check the system for leaks. If checking theoil level with unit running in part load, let unit run one hour,then run at full load for 10 minutes. If oil does not return toacceptable sight glass levels, check for correct suctionpiping and line sizing.

Final Checks —Ensure that all safety controls are operating, control panelcovers are on, and the service panels are in place.

Page 23: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

23501 01 3403 01 Specifications are subject to change without notice.

Figure 19 CAS181 Charging Chart -- Single Circuit

15 TON CHARGING CHART R--410A ALL CONDENSER FANS OPERATING

15 TONNE TABLEAU DE CHARGE R--410ATOUTES LES SOUFFLERIES DE CONDENSATION EN FONCTIONNEMENT

Figure 20 CAS241 Charging Chart -- Single Circuit

20 TON CHARGING CHART R--410A ALL CONDENSER FANS OPERATING

15 TONNE TABLEAU DE CHARGE R--410ATOUTES LES SOUFFLERIES DE CONDENSATION EN FONCTIONNEMENT

Page 24: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

24 501 01 3403 01Specifications are subject to change without notice.

Figure 21 CAS180 Charging Chart -- Dual Circuit

15 TON CHARGING CHART R--410A ALL CONDENSER FANS OPERATING

15 TONNE TABLEAU DE CHARGE R--410ATOUTES LES SOUFFLERIES DE CONDENSATION EN FONCTIONNEMENT

15 TON CHARGING CHART R--410A ALL CONDENSER FANS OPERATING

15 TONNE TABLEAU DE CHARGE R--410ATOUTES LES SOUFFLERIES DE CONDENSATION EN FONCTIONNEMENT

Page 25: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

25501 01 3403 01 Specifications are subject to change without notice.

(CIRCUIT 1)

(CIRCUIT 2)

Figure 22 CAS240 Charging Chart -- Dual Circuit

20 TON CHARGING CHART R--410A ALL CONDENSER FANS OPERATING

20 TONNE TABLEAU DE CHARGE R--410ATOUTES LES SOUFFLERIES DE CONDENSATION EN FONCTIONNEMENT

20 TON CHARGING CHART R--410A ALL CONDENSER FANS OPERATING

20 TONNE TABLEAU DE CHARGE R--410ATOUTES LES SOUFFLERIES DE CONDENSATION EN FONCTIONNEMENT

Page 26: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

26 501 01 3403 01Specifications are subject to change without notice.

Figure 23 Typical CAS181/241 Wiring Diagram (15 Ton 230v Tandem Unit Shown)

Page 27: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

27501 01 3403 01 Specifications are subject to change without notice.

Figure 24 Typical CAS180/240 Wiring Diagram (15 Ton 230v Dual Unit Shown)

Page 28: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

28 501 01 3403 01Specifications are subject to change without notice.

OPERATING SEQUENCEBase Unit ControlsIndoor (Supply) Fan —The indoor fan contactor (IFC) is remotely located at the fancoil or fan section. If the thermostat fan operation is selectedas Continuous, the IFC is energized and the indoor (supply)fan motor runs continuously. If the thermostat fan operation isselected as Automatic, the IFC will be energized on a call forCooling; indoor (supply) fan motor runs. When thermostat callfor Cooling is satisfied, the IFC is de-energized and indoor(supply) fan motor stops.Cooling, Unit Without Economizer —CAS181/241 (Single Circuit)On a thermostat call for Cooling, IFC will be energized andindoor (supply) fan motor runs. Thermostat output Y1 isenergized; terminal Y1 at CAS181/241 unit receives 24-v.24-v received at CADM1 terminal Y. If anti-recycle timedelay period has not expired, CADM1 relay will remainopen, de-energizing Solenoid Valve Relay (SVR) andpreventing compressor start. When safety pressureswitches are closed and CADM1 time delay expires,CADM1 relay closes, SVR and compressor contactor C1are energized; liquid line solenoid valve LLSV opens, alloutdoor fan motors start and Compressor 1 starts.On a thermostat calling for Stage 2 Cooling, thermostatoutput Y2 is energized; terminal Y2 at CAS181/241 unitreceives 24-v. 24-v received at CADM2 terminal Y. Ifanti-recycle time delay period has not expired, CADM2relay will remain open, preventing Compressor 2 start.When safety pressure switches are closed and CADM2time delay expires, CADM2 relay closes, compressorcontactor C2 is energized; Compressor 2 starts.As space cooling load is satisfied, thermostat outputs Y2and Y1 are de--energized, removing 24-v at CAS181/241terminals Y2 and Y1. Compressor 2 stops on Y2 opening.CADM2 begins its three-minute anti-recycle time delay. OnY1 opening, Compressor 1 stops, all outdoor fan motorsstop and SVR relay is de-energized. Liquid line solenoidvalve is de-energized and valve closes. CADM1 begins itsthree-minute anti-recycle time delay.CAS180/240 (Two Circuit)On a thermostat call for Cooling, IFC will be energized andindoor (supply) fan motor runs. Thermostat output Y1 isenergized; terminal Y1 at CAS180/240 unit receives 24-v.24-v received at CADM1 terminal Y. If anti-recycle timedelay period has not expired, CADM1 relay will remainopen, de-energizing Solenoid Valve Relay 1 (SVR1) andpreventing compressor start. When safety pressureswitches are closed and CADM1 time delay expires,CADM1 relay closes, SVR1 and compressor contactor C1are energized; liquid line solenoid valve LLSV1 opens, alloutdoor fan motors start and Circuit 1 compressor starts.

On a thermostat calling for Stage 2 Cooling, thermostatoutput Y2 is energized; terminal Y2 at CAS180/240 unitreceives 24-v. 24-v received at CADM2 terminal Y. Ifanti-recycle time delay period has not expired, CADM2relay will remain open, de-energizing Solenoid Valve Relay2 (SVR2) and preventing compressor start. When safetypressure switches are closed and CADM2 time delayexpires, CADM2 relay closes, SVR2 and compressorcontactor C2 are energized; liquid line solenoid valveLLSV2 opens and Circuit 2 compressor starts.As space cooling load is satisfied, thermostat outputs Y2and Y1 are de--energized, removing 24-v at CAS180/240terminals Y2 and Y1. Circuit 2 compressor stops on Y2opening; SVR2 is de-energized and LLSV2 closes. CADM2begins its three-minute anti-recycle time delay. On Y1opening, Circuit 1 compressor stops, all outdoor fan motorsstop and SVR1 relay is de-energized. Liquid line solenoidvalve LLSV1 is de-energized and valve closes. CADM1begins its three-minute anti-recycle time delay.All UnitsIf either the Low Pressure Switch or High Pressure Switchopens while thermostat output Y1 or Y2 remain energized,the compressor contactor is de-energized, the compressorstops and liquid line solenoid is de-energized (valvecloses). CADM initiates a TRIP event (cooling demandsensed at CADM terminal Y but no current is measured atT1, T2, T3 motor sensors); CADM relay opens and REDLED is illuminated. TRIP condition maintains lockout ofcompressor operation until CADM is manually reset. ResetCADM by cycling unit main power.Complete system shutdown may be caused by loss of mainpower, open compressor internal overload, openlow-pressure or high-pressure switch, or a fault detected bythe CADM logic. Compressor operation without coolingmay indicate the compressor’s ASTP feature is active;disconnect unit power and allow compressor to cool. SeeService section for further details.Cooling, Unit With Economizer —Refer to fan coil unit installation instructions andeconomizer accessory installation instructions for operatingsequences when system is equipped with accessoryeconomizer.Heating —Refer to fan coil unit installation instructions and accessoryheating device installation instructions for operatingsequences in heating mode.

Page 29: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

29501 01 3403 01 Specifications are subject to change without notice.

ROUTINE SYSTEM MAINTENANCEThese items should be part of a routine maintenanceprogram, to be checked every month or two, until a specificschedule for each can be identified for this installation:Quarterly Inspection (and 30 days after initial start) —Indoor sectionS Condenser coil cleanliness checked.

S Return air filter replacement

S Outdoor hood inlet filters cleaned

S Belt tension checked

S Belt condition checked

S Pulley alignment checked

S Fan shaft bearing locking collar tightness checked

S Condensate drain checked

Seasonal Maintenance —These items should be checked at the beginning of eachseason (or more often if local conditions and usage patternsdictate):Air ConditioningS Condenser fan motor mounting bolts tightness

S Compressor mounting bolts

S Condenser fan blade positioning

S Control box cleanliness and wiring condition

S Wire terminal tightness

S Refrigerant charge level

S Evaporator coil cleaning

S Evaporator blower motor amperage

HeatingS Power wire connections

S Fuses ready

S Manual-reset limit switch is closed

Economizer or Outside Air DamperS Inlet filters condition

S Check damper travel (economizer)

S Check gear and dampers for debris and dirt

SERVICERefrigeration System

EQUIPMENT DAMAGE HAZARDFailure to follow this caution may result in damage toequipment.This system uses R--410A refrigerant which has higherpressures than R-22 and other refrigerants. No otherrefrigerant may be used in this system. Gage set,hoses, and recovery system must be designed tohandle R--410A. If you are unsure consult theequipment manufacturer.

CAUTION!

Compressor Oil —

EQUIPMENT DAMAGE HAZARDFailure to follow this caution may result in damage toequipment.The compressor in a R--410A system uses a polyolester(POE) oil. This oil is extremely hygroscopic, meaning itabsorbs water readily. POE oils can absorb 15 times asmuch water as other oils designed for HCFC and CFCrefrigerants. Take all necessary precautions to avoidexposure of the oil to the atmosphere.

CAUTION!

Servicing Systems on Roofs With Synthetic Materials —POE (polyolester) compressor lubricants are known to causelong term damage to some synthetic roofing materials.Exposure, even if immediately cleaned up, may causeembrittlement (leading to cracking) to occur in one year ormore. When performing any service which may risk exposureof compressor oil to the roof, take appropriate precautions toprotect roofing. Procedures which risk oil leakage include butare not limited to compressor replacement, repairingrefrigerants leaks, replacing refrigerant components such asfilter drier, pressure switch, metering device, coil,accumulator, or reversing valve.Synthetic Roof Precautionary Procedure:1.Cover extended roof working area with an impermeable

polyethylene (plastic) drop cloth or tarp. Cover anapproximate 10 x 10 ft (3.3 x 3.3 m) area.

2.Cover area in front of the unit service panel with a terrycloth shop towel to absorb lubricant spills and preventrun-offs, and protect drop cloth from tears caused bytools or components.

3.Place terry cloth shop towel inside unit immediately undercomponent(s) to be serviced and prevent lubricantrun-offs through the louvered openings in the base pan.

4.Perform required service.5.Remove and dispose of any oil contaminated material

per local codes.Liquid Line Filter Drier —The factory-provided filter drier is specifically designed tooperate with R--410A. Replace the filter drier withfactory-authorized components only with a filter drier withdesiccant made from 100% molecular sieve grade XH-11.

Page 30: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

30 501 01 3403 01Specifications are subject to change without notice.

Filter drier must be replaced whenever the refrigerantsystem is opened.When removing a filter drier, use a tubing cutter to cut thedrier from the system. Do not unsweat a filter drier fromthe system. Heat from unsweating will release moistureand contaminants from drier into system.Field Refrigerant Access Ports —Field service access to refrigerant pressures is through theaccess ports located at the service valves (see Fig 4).These ports are -in SAE Flare couplings with Schradercheck valves and service caps. Use these ports to admitnitrogen to the field tubing during brazing, to evacuate thetubing and evaporator coil, to admit initial refrigerantcharge into the low-side of the system and when checkingand adjusting the system refrigerant charge. When serviceactivities are completed, ensure the service caps are inplace and secure; check for leaks. If the Schrader checkvalve must be removed and re-installed, tighten to 2-3in-lbs (23-34 N-cm).

Factory High-Flow Access Ports —There are two additional access ports in the system - onthe suction tube between the compressor and the suctionservice valve and on the liquid tube near the liquid servicevalve (see Figs 28 and 29). These are brass fittings withblack plastic caps. The hose connection fittings arestandard -in SAE Male Flare couplings.The brass fittings are two-piece High Flow valves, with areceptacle base brazed to the tubing and an integralspring-closed check valve core screwed into the base.(See Fig. 25) This check valve is permanently assembledinto this core body and cannot be serviced separately;replace the entire core body if necessary. Service tools areavailable from RCD that allow the replacement of the checkvalve core without having to recover the entire systemrefrigerant charge. Apply compressor refrigerant oil to thecheck valve core’s bottom o-ring. Install the fitting bodywith 96 -10 in-lbs (1085 23 N-cm) of torque; do notovertighten.

Figure 25 CoreMax Access Port Assembly

1/2-20 UNF RH

30

0.596

SEAT CORE

WASHER DEPRESSOR PER ARI 720+ .01/ -.035FROM FACE OF BODY

7/16-20 UNF RH

O-RING

45

1/2" HEX

This surface provides a metal to metal seal whentorqued into the seat. Appropriate handling isrequired to not scratch or dent the surface.

(Part No. 1173177

⅝ Hex .47

Page 31: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

31501 01 3403 01 Specifications are subject to change without notice.

Comfort Alert Diagnostic ModuleThe Comfort Alert Diagnostic Module (CADM) monitors andanalyzes data from the Copeland Scroll three-phasecompressor and the thermostat demand. The CADM alsoprovides a 3-minute anti-recycle time delay to compressorcycling. Each compressor has a separate CADM module.The CADM detects causes for electrical and system relatedfailures without any sensors. Flashing LEDs communicatethe Alert codes to guide service technicians in accuratelyand quickly troubleshooting the system and determiningroot cause for the failure.Inputs to the CADM include 24-vac power, thermostat Y1or Y2, compressor contactor coil (common side) andcompressor power leads (from the compressor contactor).

Input Terminal Voltage

ControlPower R 24-V

ControlCommon C 24-V

Cooling Y 24-V

ContactorCoil P 24-V

Line A T1 Line

Line B T2 Line

Line C T3 Line

Control of the compressor contactor coil is through anormally-closed (power on the module) contact betweenterminals P and C.Communications of status and alert conditions is throughthree LEDs located on the top edge of the module housing(see Fig. 26): POWER (green), ALERT (yellow), and TRIP(red).The POWER LED indicates the presence of control powerto the CADM.The ALERT LED indicates an abnormal condition exists inthe system through a flash code. The ALERT LED will blinka number of times consecutively, pause and the repeat theprocess. The number of blinks, defined in Table 11,correlates to a particular abnormal condition;troubleshooting tips are provided for each Alert code.Reset of the ALERT may be automatic or manual. If thefault condition causing the Alert is self-corrected, the Alertcode will be removed and the CADM will automaticallyreset and allow the system to restart normally. Manualreset requires that main power to the CAS unit be recycledafter the cause for the Alert condition has been detectedand corrected.

Figure 26 CAD/M Housing/LED Locations

POWER(GRN)

ALERT(YEL)

TRIP(RED)

The TRIP LED indicates either a time-delay period iscurrently active (RED LED is blinking) or the module haslocked out the compressor (RED LED is on steady). Alockout condition will occur when the CADM detects athermostat demand at input Y but there is no power at thecompressor line terminals T1 or T2 or T3. This lockout canoccur due to a safety switch (LPS or HPS) opening andde-energizing the compressor contactor, thecompressor-motor internal overload opens, or otherinternal power interruption has occurred. Reset of the TRIPLED requires that unit main power be recycled after theloss of power to the compressor condition has beendetected and corrected.Simultaneous Blinking of YELLOW and RED LEDsindicates control power input to the CADM is low. Checkcontrol circuit transformer and wiring.Troubleshooting the CADM Wiring – Flashing LEDs alsoindicate wiring problems to the CADM. See Table 12 fordiscussion of additional LED flash codes andtroubleshooting instructions.

Page 32: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

32 501 01 3403 01Specifications are subject to change without notice.

Table 11 – LED Status CodesStatus LED Status LED Description Status LED Troubleshooting Information

Green “POWER” Module has power Supply voltage is present at module terminals

Red “TRIP”LED On Solid

Thermostat demand signal Y ispresent, but the compressor isnot running.

1. Compressor protector is open

2. Condensing unit power disconnect is open

3. Compressor circuit breaker or fuse(s) is open

4. Broken supply wires or connector is not making contact

5. Compressor power wires not routed through Comfort Alert

6. Compressor contactor has failed open

Red “TRIP” LEDFlashing

The anti-short cycle timer (3 minutes) in module is preventing compressor restart.

Module locks out compressor when compressor damaging ALERT code appears.Lockout ALERT codes are noted in the Status LED Description.During a compressor lock out, 24VAC power must be removed from module to manually reset.

Yellow “ALERT”LED On Solid

A short circuit or over currentcondition exists on PROTterminal.

1. Compressor contactor coil shorted

2. Electrical load too high for PROT circuit (maximum 1 Amp)

3. 24 V AC wired directly to PROT terminal

Yellow “ALERT”Flash Code 2

System Pressure TripDischarge pressure out of limitsor compressor overload (if nohigh pressure switch in system)LOCKOUT

1. High head pressure

2. Condenser coil poor air circulation (dirty, blocked, damaged)

3. Condenser fan is not running

4. If low pressure switch is open: Refer to Code 3 for troubleshooting

Yellow “ALERT”Flash Code 3

Short CyclingCompressor is running onlybriefly (four consecutive cyclesof less than three minutes each)LOCKOUT

1. If low pressure switch is open:

a. Low refrigerant charge

b. Evaporator blower is not running

c. Evaporator coil is frozen

d. Faulty metering device

e. Condenser coil is dirty

f. Liquid line restriction (filter drier blocked if present)

2. If high pressure switch is open, go to Flash Code 2 information

3. Intermittent thermostat demand signal

4. System or control board defective

Yellow “ALERT”Flash Code 4

Locked RotorLOCKOUT

1. Low line voltage to compressor

2. Excessive liquid refrigerant in compressor

3. Compressor bearings are seized

Yellow “ALERT”Flash Code 5

Open Circuit 1. Condensing unit power disconnect is open

2. Compressor circuit breaker or fuses are open

3. Compressor contactor has failed open

4. High pressure switch is open and requires manual reset

5. Broken supply wires or connector is not making contact

6. Unusually long compressor protector reset time due to extremeambient temperature

7. Compressor windings are damaged

Yellow “ALERT”Flash Code 6

Missing PhaseLOCKOUT

1. Compressor fuse is open on one phase

2. Broken wire or connector on one phase

3. Compressor motor winding is damaged

4. Utility supply has dropped one phase

Yellow “ALERT”Flash Code 7

Reverse PhaseLOCKOUT

1. Compressor running backward due to supply phase reversal

Yellow “ALERT”Flash Code 8

Welded ContactorCompressor always runs

1. Compressor contactor has failed closed

2. Thermostat demand signal not connected to module

Yellow “ALERT”Flash Code 9

Low VoltageControl circuit < 18VAC

1. Control circuit transformer is overloaded

2. Low line voltage to compressor

Page 33: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

33501 01 3403 01 Specifications are subject to change without notice.

Table 12 – CADM Troubleshooting

Miswired Module Indication Recommended Troubleshooting Action

Green LED is not on,module does not power up

Determine if both R and C module terminals are connected. Verify voltage in present at module’s Rand C terminals.NOTE: The CADM requires a constant nominal 24VAC power supply. The wiring to the module’s Rand C terminals must be directly from the control transformer. The module cannot receive its powerfrom another device that will interrupt the 24VAC power supply. See the CAS Wiring Diagram(s)(Fig. 27 and Fig. 28).

Green LED Intermittent,module powers up onlywhen compressor runs

Determine if R and Y terminals are wired in reverse. Verify module’s R and C terminals have aconstant source. See “NOTE” above for details on R and C wiring.

TRIP LED is on but systemand compressor check OK

Verify Y terminal is wired properly per the CAS wiring diagram (see Fig. 27 and Fig. 28). Verifyvoltage at contactor coil falls below 0.5VAC when off. Verify 24VAQC is present across Y and Cwhen thermostat demand signal is present. If not, R and C are reverse wired.

TRIP LED and ALERT LEDflashing together

Verify R and C terminals are supplied with 19-28VAC.

ALERT Flash Code 3(Compressor Short Cycling)displayed incorrectly

Verify Y terminal is connected to 24VAC at contactor coil. Verify voltage at contactor coil falls below0.5VAC when off.

ALERT Flash Code 5 or 6(Open Circuit, Missing Phase)displayed incorrectly

Check that compressor T1 and T3 wires are through module’s current sensing holes. Verify Yterminal is connected to 24VAC at contactor coil. Verify voltage at contactor coil falls below 0.5VACwhen off.

Alert Flash Code *(Welded Contactor)displayed incorrectly

Determine if module’s Y terminal is connected. Verify Y terminal is connected to 24VAC at contactorcoil. Verify 24VAC is present across Y and C when thermostat demand signal is present. If not, Rand C are reverse wired. Verify voltage at contactor coil falls below 0.5VAC when off.

Compressor ProtectionCompressor Overtemperature Protection (IP) —A thermostat installed on the compressor motor windingreacts to excessively high winding temperatures and shutsoff the compressor.Crankcase Heater —The heater minimizes absorption of liquid refrigerant by oilin the crankcase during brief or extended shutdownperiods. The heater is wired to cycle with the compressor;the heater is off when compressor is running, and on whencompressor is off.The crankcase heater will operate as long as the powercircuit is energized. The main disconnect must be on toenergize the crankcase heater.

IMPORTANT: Never open any switch or disconnectthat energizes the crankcase heater unless unit isbeing serviced or is to be shut down for a prolongedperiod. After a prolonged shutdown on a service job,energize the crankcase heater for 24 hours beforestarting the compressor.

Advanced Scroll Temperature Protection (ASTP) —See “Advanced Scroll Temperature Protection (ASTP)”.Low-Pressure Switch —The CAS low-pressure switch is stem-mounted on thesuction line. Switches are all fixed, non-adjustable type.High--Pressure Switch —The high--pressure switch is stem mounted on thedischarge line. The switch is a fixed, non-adjustable type.

Outdoor Fans —Each fan is supported by a formed-wire mount bolted to thefan deck and covered with a wire guard. Fan motors havepermanently lubricated bearings.1.Shut off unit power supply. Install lockout tag.2.Remove outdoor fan assembly (grille, motor, and fan).3.Loosen fan hub setscrews.4.Adjust fan height as shown in Fig. 27.5.Tighten setscrews to 84 in--lbs (949 N--cm).6.Replace outdoor fan assembly.

Figure 27 Outdoor Fan Blade Position

3.6 mm +0/0/-0.8

Lubrication —Fan Motors: The fan motors have sealed bearings. Noprovisions are made for lubrication.Compressor: The compressor has its own oil supply. Lossof oil due to a leak in the system should be the only reasonfor adding oil after the system has been in operation.

Page 34: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

34 501 01 3403 01Specifications are subject to change without notice.

Figure 28 CAS180 Cabinet

Condenser Fans/Motors

ServiceValves

Access Panel -Control Box &Compressors

Figure 29 CAS180 Piping

Page 35: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

35501 01 3403 01 Specifications are subject to change without notice.

Figure 30 CAS181 Compressor Assembly (Rear View)

Equalization

LPS

Oil Equalizer Line

Figure 31 CAS180 Compressor Assembly (Rear View)

Page 36: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

36 501 01 3403 01Specifications are subject to change without notice.

Figure 32 CAS240 Cabinet

Condenser Fans/Motors

ServiceValves

Access Panel -Control Box &Compressors

Figure 33 CAS240 Piping

CKT2

CKT2

CKT1

CKT1

HPS

LPS

HPS

LPS

Page 37: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

37501 01 3403 01 Specifications are subject to change without notice.

Figure 34 CAS241 Compressor Assembly (Rear View)

Figure 35 CAS240 Compressor Assembly (Rear View)

Page 38: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

38 501 01 3403 01Specifications are subject to change without notice.

Coil Type IdentificationCAS units are available with different coil types. Cleaningmethods differ for each type so identifying the coil type isimportant. Unit model number and appearance can identifythe coil type.Model number designation: See Model Nomenclature onpage 3 for general unit model number format. Position 9indicates the coil type and coating.Round--Tube Plate--Fin (RTPF) Type —This construction uses a series of small diameter copperhairpin tubes running horizontally with vertical plate fins.The plate fins may be aluminum (standard) or copper(optional). Various optional coatings are also available.These coils may be one--row or two--row.

Figure 36 Pivot and Support Top Cover

Routine Cleaning of Round-Tube Plate Fin (RTPF) Coils—Periodic cleaning with environmentally sound coil cleaner isessential to extend the life of RTPF coils. Cleaner asdescribed below.Coil cleaning should be part of the unit’s regularlyscheduled maintenance procedures to ensure long life ofthe coil. Failure to clean the coils may result in reduceddurability in the environment.Avoid the use of:S coil brighteners

S acid cleaning prior to painting

S high pressure washers

S poor quality water for cleaning

S water rinse coil with low velocity spray nozzle

Use a coil cleaner that is non−flammable, hypoallergenic,non−bacterial, and a USDA accepted biodegradable agentthat will not harm the coil or surrounding components suchas electrical wiring, painted metal surfaces, or insulation.Use of non−recommended coil cleaners is stronglydiscouraged since coil and unit durability could be affected.

Coil Cleaner Application Equipment —S 21/2 gallon garden sprayer

S water rinse with low velocity spray nozzle

UNIT DAMAGE HAZARDFailure to follow this caution may result in corrosion anddamage to the unit.Harsh chemicals, household bleach or acid or basiccleaners should not be used to clean outdoor or indoorcoils or any kind. These cleaners can be very difficult torinse out of the coil and can accelerate corrosion at thefin/tube interface where dissimilar materials are incontact. If there is dirt below the surface of the coil usethe FAST environmentally sound coil cleaner asdescribed above.

CAUTION!

UNIT RELIABILITY HAZARDFailure to follow this caution may result in reduced unitperformance.High velocity water from a pressure washer, gardenhose, or compressed air should never be used to clean acoil. The force of the water or air jet will bend the finedges and increase airside pressure drop.

CAUTION!

Coil Cleaner Application Instructions:NOTE: Proper eye protection such as safety glasses isrecommended during mixing and application.1.Turn off unit power.2.Remove screws holding rear corner post and top cover in

place. Pivot top cover up 12 to 18 inches (305 to 457mm) and support with a rigid support. See Fig. 36.

3.Remove all surface loaded fibers and dirt with a vacuumcleaner. If a vacuum cleaner is not available, a softnon-metallic bristle brush may be used. In either case,the tool should be applied in the direction of the fins.Coil surfaces can be easily damaged (fin edges can beeasily bent over and damage to the coating of aprotected coil) if the tool is applied across the fins.

NOTE: Use of a water stream, such as a garden hose,against surface loaded coil will drive the fibers and dirt intothe coil, making cleaning efforts more difficult. Surfaceloaded fibers must be completely removed prior to usinglow velocity clean water rinse.4.Using a low velocity garden hose thoroughly wet finned

surfaces with clean water. Be careful not to bend thefins.

5.Mix coil cleaner in a 21/2 gallon garden sprayeraccording to the instructions included with the cleaner.The optimum solution temperature is 100F (38C).

NOTE: Do NOT USE water in excess of 130F (54C), asthe enzymatic activity will be destroyed.6.Thoroughly apply environmentally sound coil cleaner

solution to all coil surfaces including the finned area,tube sheets and coil headers.

Page 39: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

39501 01 3403 01 Specifications are subject to change without notice.

7.Hold garden sprayer nozzle close to finned areas andapply cleaner with a vertical, up-and-down motion.Avoid spraying in horizontal pattern to minimizepotential for fin damage.

8.Ensure cleaner thoroughly penetrates deep into finnedareas.

9.Interior and exterior finned areas must be thoroughlycleaned.

10. Finned surfaces should remain wet with cleaningsolution for 10 minutes.

11. Ensure surfaces are not allowed to dry before rinsing.Reapply cleaner as needed to ensure 10-minutesaturation is achieved.

12. Thoroughly rinse all surfaces with low velocity cleanwater using downward rinsing motion of water spraynozzle. Protect fins from damage from the spraynozzle.

13. Replace top cover and rear corner posts.

FASTENER TORQUE VALUESTable 13 – Torque Values

Compressor mounting bolts 65--75 in–lbs(734–847 N–cm)

Condenser fan motor mounting bolts 20 2 in–lbs(226 23 N–cm)

Condenser fan hub setscrew 84 2 in–lbs(949 136 N–cm)

High-flow service port 96 10 in–lbs(1085 23 N–cm)

Schrader-type service check valve 2–3 in–lbs(23–34 N–cm)

Compressor oil sightglass thread 330 31 in–lbs(23–34 N–cm)

Compressor to Compressor rail torque 120–168 in–lbs(1356–1898 N–cm)

Compressor rail to base pan torque 70 5 in–lbs(791 57 N–cm)

Page 40: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

40 501 01 3403 01Specifications are subject to change without notice.

TROUBLESHOOTING

PROBLEM SOLUTION

COMPRESSOR DOES NOT RUN

Contactor Open

1. Power off. 1. Restore power.

2. Fuses blown in field power circuit. 2. After finding cause and correcting, replace with correct size fuse.

3. No control power. 3. Check control transformer primary connections and circuit breaker.

4. Thermostat circuit open. 4. Check thermostat setting.

5. Safety device lockout circuit active. 5. Reset lockout circuit.

6. Low-pressure switch open. 6. Check for refrigerant undercharge, obstruction of indoor airflow. Makesure liquid line solenoid valve(s) is open.

7. High-pressure switch open. 7. Check for refrigerant overcharge, obstruction of outdoor airflow, air in system.Be sure outdoor fans are operating correctly.

8. Compressor overtemperature switch open. 8. Check for open condition. Allow for reset. Replace if defective.

9. Loose electrical connections. 9. Tighten all connections.

10. Compressor stuck. 10. See compressor service literature.

Contactor Closed

1. Compressor leads loose. 1. Check connections.

2. Motor windings open. 2. See compressor service literature.

3. Single phasing. 3. Check for blown fuse. Check for loose connection at compressor terminal.

COMPRESSOR STOPS ON HIGH-PRESSURE SWITCH

Outdoor Fan On

1. High-pressure switch faulty. 1. Replace switch.

2. Reversed fan rotation. 2. Confirm rotation, correct if necessary.

3. Airflow restricted. 3. Remove obstruction.

4. Air recirculating. 4. Clear airflow area.

5. Noncondensables in system. 5. Recover refrigerant and recharge as required.

6. Refrigerant overcharge. 6. Recover refrigerant as required.

7. Line voltage incorrect. 7. Consult power company.

8. Refrigerant system restrictions. 8. Check or replace filter drier, expansion valve, etc.

Outdoor Fan Off

1. Fan slips on shaft. 1. Tighten fan hub setscrews.

2. Motor not running. 2. Check power and capacitor.

3. Motor bearings stuck. 3. Replace bearings.

4. Motor overload open. 4. Check overload rating. Check for fan blade obstruction.

5. Motor burned out. 5. Replace motor.

Page 41: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

41501 01 3403 01 Specifications are subject to change without notice.

TROUBLESHOOTING (cont)

PROBLEM SOLUTION

COMPRESSOR CYCLES ON LOW-PRESSURE SWITCH

Indoor-Air Fan Running

1. Liquid line solenoid valve(s) fails to open. 1. Check liquid line solenoid valve(s) for proper operation. Replace if necessary.

2. Filter drier plugged. 2. Replace filter drier.

3. Expansion valve power head defective. 3. Replace power head.

4. Low refrigerant charge. 4. Add charge. Check low-pressure switch setting.

Airflow Restricted

1. Coil iced up. 1. Check refrigerant charge.

2. Coil dirty. 2. Clean coil fins.

3. Air filters dirty. 3. Clean or replace filters.

4. Dampers closed. 4. Check damper operation and position.

Indoor-Air Fan Stopped

1. Electrical connections loose. 1. Tighten all connections.

2. Fan relay defective. 2. Replace relay.

3. Motor overload open. 3. Power supply.

4. Motor defective. 4. Replace motor.

5. Fan belt broken or slipping. 5. Replace or tighten belt.

COMPRESSOR RUNNING BUT COOLING INSUFFICIENT

Suction Pressure Low

1. Refrigerant charge low. 1. Add refrigerant.

2. Head pressure low. 2. Check refrigerant charge. Check outdoor-air fan thermostat settings.

3. Air filters dirty. 3. Clean or replace filters.

4. Expansion valve power head defective. 4. Replace power head.

5. Indoor coil partially iced. 5. Check low-pressure setting.

6. Indoor airflow restricted. 6. Remove obstruction.

Suction Pressure High

1. Unloaders not functioning 1. Check unloader adjustments. Check unloader setting.

2. Heat load excessive. 2. Check for open doors or windows in vicinity of fan coil.

UNIT OPERATES TOO LONG OR CONTINUOUSLY

1. Low refrigerant charge. 1. Add refrigerant.

2. Control contacts fused. 2. Replace control.

3. Air in system. 3. Purge and evacuate system.

4. Partially plugged expansion valve or filter drier. 4. Clean or replace.

SYSTEM IS NOISY

1. Piping vibration. 1. Support piping as required.

2. Compressor noisy. 2. Replace compressor if bearings are worn.

COMPRESSOR LOSES OIL

1. Leak in system. 1. Repair leak.

2. Crankcase heaters not energized during shutdown. 2. Check wiring and relays. Check heater and replace if defective.

3. Improper interconnecting piping design. 3. Check piping for oil return. Replace if necessary.

FROSTED SUCTION LINE

Expansion valve admitting excess refrigerant. Adjust expansion valve.

HOT LIQUID LINE

1. Shortage of refrigerant due to leak. 1. Repair leak and recharge.

2. Expansion valve opens too wide. 2. Adjust expansion valve.

FROSTED LIQUID LINE

1. Restricted filter drier. 1. Remove restriction or replace.

2. Liquid line solenoid valve partially closed. 2. Replace valve.

Page 42: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

42 501 01 3403 01Specifications are subject to change without notice.

APPENDIX AAir Conditioner & Heat Pump with R--410A—Quick Reference GuideS R--410A refrigerant operates at 50 percent to 70 percenthigher pressures than R-22. Be sure that servicingequipment and replacement components are designed tooperate with R--410A.

S R--410A refrigerant cylinders are rose colored.

S Recovery cylinder service pressure rating must be 400psig, DOT 4BA400 or DOT BW400.

S R--410A systems should be charged with liquid refrigerant.Use a commercial type metering device in the manifoldhose when charging into suction line with compressoroperating.

S Manifold sets should be 700 psig high side and 180 psiglow side with 550 psig low-side retard.

S Use hoses with 700 psig service pressure rating.

S Leak detectors should be designed to detect HFCrefrigerant.

S R--410A, as with other HFCs, is only compatible with POEoils.

S Vacuum pumps will not remove moisture from oil.

S Use only factory specified liquid-line filter driers with ratedworking pressures greater than 600 psig.

S Do not install a suction-line filter drier in liquid-line.

S POE oils absorb moisture rapidly. Do not expose oil toatmosphere.

S POE oils may cause damage to certain plastics androofing materials.

S Wrap all filter driers and service valves with wet cloth whenbrazing.

S A factory approved, liquid-line filter drier is required onevery unit.

S Do not use an R-22 TXV.

S If indoor unit is equipped with a TXV, it must be changed toa R--410A TXV.

S Never open system to atmosphere while it is under avacuum.

S When system must be opened for service, recoverrefrigerant, break vacuum with dry nitrogen beforeopening system.

S Always replace filter drier after opening system for service.

S Do not vent R--410A into the atmosphere.

S Do not use capillary tube coils.

S Observe all warnings, cautions, and bold text.

S All R--410A heat pumps must have indoor TXV.

S Do not leave R--410A suction line driers in place for morethan 72 hours.

Page 43: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

43501 01 3403 01 Specifications are subject to change without notice.

APPENDIX BLow Ambient Option — Factory InstalledUnits with the factory installed low ambient option areequipped with a MotormasterR solid--state head pressurecontrol which regulates fan speed. A temperature sensor,mounted on circuit 1 of the outdoor coil (see Figs. 37 and38) controls the speed of approved outdoor fan motors inorder to maintain a constant head pressure in the outdoorcoil. The control maintains the appropriate head pressureat low ambient temperatures down to --20_F (--28_C).Wind baffles are required to prevent wind cross currentsfrom causing abnormally low condensing temperatures.S Use 20--gauge sheet metal to fabricate wind baffles (seeFig. 40--43 and Table 14) and mounting brackets.

NOTE: Mounting brackets are for use on 15 ton modelunits only.S Install the wind baffles as show in Fig. 39--42.

Operation —Fan on/off control in cooling--only units (CAS181/241,CAS180/240) is provided by an outdoor fan relay (OFR).In cooling mode, fan motor speed of outdoor motors OFM1and OFM3 is regulated by the speed control temperaturesensor on outdoor coil 1 for a minimum coil condensingtemperature of approximately 100_F (38_C) at higheroutdoor ambient temperature and 80_F (27_C) at lowerambient. Additionally, outdoor fan motor OFM2 and OFM4are turned on/off by the low ambient temperature switch,LAS, operating the low ambient relay (LAR). The LAScontrol temperatures are open 42_F +/-- 5_F, close 57_F+/-- 5_F (open 5.5_C +/-- 2.8_C, close 13.9_C +/-- 2.8_C).To override the speed control for full fan speed operationduring service or maintenance, either:

a. remove sensor and place in hot water >120_F (>49_C), or

b. rewire to bypass control by connecting speedcontrol input and output power wires.

Troubleshooting —OBSERVATION POSSIBLE REMEDYFans won’t start All fans:

Check power & wiringCheck outdoor fan relay (OFR)OFM1, OFM3 only:Check speed control sensor locationCheck speed sensor resistanceOFM2, OFM4 only:Check low ambient switch (LAS)Check low ambient relay (LAR)

Cooling -- Center outdoorfans (OFM2, OFM4) offbelow approximately 60_F(16_C) outdoor ambient.

Normal operation

Cooling -- Center outdoorfans (OFM2, OFM4) noton above approximately60_F (16_C) outdoorambient

Check low ambient switch (LAS)Check low ambient relay (LAR)

Cooling -- Slow fan speedfor outer fans (OFM1,OFM3) at start or duringlow outdoor ambient

Normal operation

Cooling -- Slow fan speedfor outer fans (OFM1,OFM3) above 85_F(29_F) outdoor ambient(should be full speed)

Check speed control sensor locationCheck speed control sensorresistanceCheck fan motor capacitor

Cooling -- motor currentinto speed control isgreater than motornameplate FLA

Normal operationUp to 30% higher A at partial speedat low ambient

Speed Control Sensor Resistance —TEMPERATURE RESISTANCE

_F +/--2_F_ _C +/--1C Ohms, nominal--22 --30 88350--4 --20 4848514 --10 2765032 0 1632550 10 995068 20 624577 25 500086 30 4028104 40 2663122 50 1801140 60 1244158 70 876

Page 44: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

44 501 01 3403 01Specifications are subject to change without notice.

Figure 37 Motormaster Sensor Location:CAS181 & CAS180

MotormasterSensor -Attach to Circuit 1 coil only.

508 mm (20 in)for Single Circuit254 mm (10 in)for Dual Circuit

Figure 38 Motormaster Sensor Location:CAS241 & CAS240

Motormaster Sensor - Must be positionedon Vapor Stub of Circuit 1 coil only.

Table 14 – Wind Baffle Dimension

DIMENSIONS -- INCHESUNIT BAFFLE A B C D E F G H J

CAS180/181(RTPF)

LEFT SIDE 10 3/4 11 1/2 12 1/4 43 1/8 4 1/4 13 1/4 22 1/4 31 1/4 40 1/4BACK 80 1/4 81 81 3/4 43 1/8 8 3/8 18 27 1/4 40 --

RIGHT SIDE 38 3/4 39 1/2 40 1/4 43 1/8 8 3/8 18 27 1/4 40 --

FRONT 27 27 3/4 28 1/2 43 1/8 3 3/4 12 3/4 21 3/4 30 3/4 39 3/4

CAS240/241(RTPF)

LEFT SIDE 32 7/8 33 5/8 34 3/8 43 1/8 4 1/4 13 1/4 22 1/4 31 1/4 40 1/4BACK 47 3/4 48 1/2 49 1/4 43 1/8 4 1/4 13 1/4 22 1/4 31 1/4 40 1/4

RIGHT SIDE 61 1/8 61 7/8 62 5/8 43 1/8 3 3/4 12 3/4 21 3/4 30 3/4 39 3/4FRONT 20 1/8 20 7/8 21 5/8 43 1/8 3 3/4 12 3/4 21 3/4 30 3/4 39 3/4

DIMENSIONS -- MMUNIT BAFFLE A B C D E F G H J

CAS180/181(RTPF)

LEFT SIDE 272 291 310 1095 108 337 565 794 1022

BACK 2037 2056 2075 1095 212 457 694 1015 --

RIGHT SIDE 983 1002 1021 1095 212 457 694 1015 --

FRONT 684 704 723 1095 95 324 552 781 1010

CAS240/241(RTPF)

LEFT SIDE 834 853 872 1095 108 337 565 794 1022

BACK 1214 1233 1252 1095 108 337 565 794 1022

RIGHT SIDE 1551 1570 1589 1095 95 324 552 781 1010

FRONT 510 530 549 1095 95 324 552 781 1010

Page 45: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

45501 01 3403 01 Specifications are subject to change without notice.

Figure 39 Wind Baffles -- Fabrication

Page 46: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

46 501 01 3403 01Specifications are subject to change without notice.

Figure 40 15 Ton Wind Baffle Brackets -- Fabrication

Page 47: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

47501 01 3403 01 Specifications are subject to change without notice.

Figure 41 Wind Baffle Installation -- 15 Ton Units

RIG

HT

BA

CK

LEFT

FRO

NT

BO

TTO

MB

RA

CK

ET

TOP

BR

AC

KE

TS

Page 48: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

48 501 01 3403 01Specifications are subject to change without notice.

Figure 42 Wind Baffle Installation -- 20 Ton Units

RIG

HT

BA

CK

LEFT

FRO

NT

Page 49: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

49501 01 3403 01 Specifications are subject to change without notice.

Page 50: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

50 501 01 3403 01Specifications are subject to change without notice.

Copyright 2019 International Comfort ProductsLewisburg, TN 37091 USA Replaces: 501 01 3403 00

10-19

Page 51: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

51501 01 3403 01 Specifications are subject to change without notice.

START-UP CHECKLISTI. PRELIMINARY INFORMATION

OUTDOOR: MODEL NO. SERIAL NO.INDOOR: AIRHANDLER MANUFACTURER

MODEL NO. SERIAL NO.ADDITIONAL ACCESSORIES

II. PRE-START-UPOUTDOOR UNITIS THERE ANY SHIPPING DAMAGE? (Y/N)IF SO, WHERE:

WILL THIS DAMAGE PREVENT UNIT START-UP? (Y/N)CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT? (Y/N)HAS THE GROUND WIRE BEEN CONNECTED? (Y/N)HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY? (Y/N)ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? (Y/N)

CONTROLSARE THERMOSTAT AND INDOOR FAN CONTROL WIRING CONNECTIONS MADE AND CHECKED?

(Y/N)

ARE ALL WIRING TERMINALS (including main power supply) TIGHT? (Y/N)HAS CRANKCASE HEATER BEEN ENERGIZED FOR 24 HOURS? (Y/N)

INDOOR UNITHAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE? (Y/N)ARE PROPER AIR FILTERS IN PLACE? (Y/N)HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT? (Y/N)DO THE FAN BELTS HAVE PROPER TENSION? (Y/N)HAS CORRECT FAN ROTATION BEEN CONFIRMED? (Y/N)

PIPINGARE LIQUID LINE SOLENOID VALVES LOCATED AT THE INDOOR COILS AS REQUIRED? (Y/N)HAVE LEAK CHECKS BEEN MADE AT COMPRESSOR, OUTDOOR AND INDOOR COILS,TXVs (Thermostatic Expansion Valves), SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGSWITH A LEAK DETECTOR? (Y/N)

LOCATE, REPAIR, AND REPORT ANY LEAKS.HAVE LIQUID LINE SERVICE VALVES BEEN OPENED? (Y/N)HAVE SUCTION SERVICE VALVES BEEN OPENED? (Y/N)

Page 52: INSTALLATION INSTRUCTIONS - Carrier...Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part

52 501 01 3403 01Specifications are subject to change without notice.

CHECK VOLTAGE IMBALANCELINE-TO-LINE VOLTS: AB V AC BC V(AB + AC + BC)/3 = AVERAGE VOLTAGE = VMAXIMUM DEVIATION FROM AVERAGE VOLTAGE = VVOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) =IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!CALL LOCAL POWER COMPANY FOR ASSISTANCE.

CHECK INDOOR UNIT FAN SPEED AND RECORD.CHECK OUTDOOR UNIT FAN SPEED AND RECORD.AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:

SUCTION PRESSURE CIR 1: CIR 2:SUCTION LINE TEMP CIR 1: CIR 2:LIQUID PRESSURE CIR 1: CIR 2:LIQUID LINE TEMP CIR 1: CIR 2:ENTERING OUTDOOR UNIT AIR TEMPLEAVING OUTDOOR UNIT AIR TEMPINDOOR UNIT ENTERING-AIR DB (dry bulb) TEMPINDOOR UNIT ENTERING-AIR WB (wet bulb) TEMPINDOOR UNIT LEAVING-AIR DB TEMPINDOOR UNIT LEAVING-AIR WB TEMP

COMPRESSOR 1 AMPS (L1/L2/L3) / /COMPRESSOR 2 AMPS (L1/L2/L3) / /

NOTES: