Installation and Operation Manual Sirios LED Emergency ... · Sirios LED front view Sirios LED...
Transcript of Installation and Operation Manual Sirios LED Emergency ... · Sirios LED front view Sirios LED...
Installation and Operation Manual
Sirios LED Emergency Lighting
3
Table of Contents
Installation - Maintenance
General Information
1. Safety information
2. Scope of Operation
3. General product information
4. Order codes
Installation instructions
5. Step by step mounting instructions
6. Connections and wiring
7. Light Distribution
Operating Instructions
8. Mains Operation
9. Emergency Operation
10. Autotest Operation
11. Dimensions
SAFETY INSTRUCTIONS
Ÿ The device shall only be used for its intended purpose and in undamaged and �awless condition
Ÿ Only genuine Eaton spare parts may be used for replacement and repair
Ÿ Observe the national safety rules and regulations to prevent accidents as well as the safety instructions included in these instruction lea�et
.......................................................................... 5
.......................................................................... 5
.......................................................................... 5
.......................................................................... 6
.......................................................................... 7
.......................................................................... 7
.......................................................................... 6
.......................................................................... 4
.......................................................................... 7
.......................................................................... 7
.......................................................................... 5
.......................................................................... 6
Sirios-LED Emergency Lighting www.eaton.com
A
C
230VAC
B230VAC
D
G:
G:
Y:
Y:
OK
TESTDK
SLO
HR
VC
EE
LT
Sirios LED Emergency Lighting - Installation / Maintenance
4 Sirios-LED Emergency Lighting www.eaton.com
Sirios LED Emergency Lighting - General Information
1. Safety Information
Observe the national safety rules and regulations to prevent accidents as well as the safety instructions included in these instruction lea�et.
2. Scope of OperationSirios LED is range of emergency lights with low pro�le, designed and equipped with technical solutions and accessories for a wide range of applications such as of�ces, restaurants, hotels, hospitals and general commercial applications
The range of accessories includes a recessed base forinstallation to walls and false ceilings and an IP65 weatherproof kit.
Sirios LED front view
Sirios LED emergency lights are suitable for both antipanic and up to 30m viewing distance exit sign applications.
3. General Product Information
0%
12h
IP420+40 C
0+5 C
1h 100%
12h24h charge for optimal operation
recyclable parts complying with WEEE directive
designed for indoor use (for outdoor applications use IP65 kit)
temperature range 0 0+5 C to +40 C
class II
Light Source:24 white LED 1.5W
Materials:White polycarbonate base and re�ectorClear polycarbonate diffuser
Operation:Maintained & Non-Maintained (user selectable)Autonomy 1h up to 3hFunctional test integrated into the diffuserInhibition and Rest ModeAutotest & slave modelsavailable
Installation:Wall and Ceiling Installation kit for recessed wall and ceilingBase for quick mounting(accessory)Panel, double-sided printed for reporting security (optional)Protection Kit IP65 foroutdoor use
Applications:Schools, universities, publicadministration, commercialenvironments
O-SLEDO-SLED-3HO-SLED-ATO-SLED-AT-3HO-SLED-MAINS
Sirios LED 2hours self-containedSirios LED 3hours self-containedSirios LED 1hour AutotestSirios LED 3hours AutotestSirios LED Mains
Order code Description
Accessories
O-SLED-STRIPEO-S-WB O-S-RB O-S-IP171-000-032 171-000-035
Led stripe accessory for Sirios LEDWall mounting baseRecessed baseWeatherproof baseVertical metal base (O-MP41)Horizontal metal base (O-PU41)
Order code Description
4. Order codes
Sirios LED order codes
5Sirios-LED Emergency Lighting www.eaton.com
13
Sirios LED Emergency Lighting - Installation instructions
click
click
1 2
3 4
5
6 7
8
10
11
12
7. Light Distribution
By changing the orientation of the LEDstrip you can adjust andchoose the light distribution of Sirios LED
5. Step by step Mounting Instructions
L1LN
230VAC !
6. Connections & wiring
Summary
Led position
Application
Exit Sign Antipanic Escape Route
Open (Λ)
Closed (ΙΙ)
Best*
Good
Best**
Good
Good
Best***
* Better uniformity on sign** Bigger covering area,*** Longer distance in smaller heights, lower illuminance diversity along the route path
Open position (Λ) suggested application for Escape Route, up to 9,5m in 4m height
Closed position (II) suggested application for Anti-panic
6
B+
/ A-
click
click
Sirios-LED Emergency Lighting www.eaton.com
Sirios LED Emergency Lighting - Operating instructions
EX500B+ A-
1-2,5
SWITCH
9. Emergency Operation
Telecommand wiring
Inhibition wiring
TLU500B+ A-
10. Autotest Operation
Telecommand operation
Sirios LED
11. Dimensions
121mm
359mm
168m
m
336mm
56m
m
384mm
192m
m
171mm
361mm
59m
m
358mm
60m
m
357mm
159m
m
153mm
Sirios recessed base
Sirios weatherproof base
8. Mains Operation
Maintained operation
Functional test, every week (7x24h)
Duration test, every 10 weeks (70x24h)
Autotest indications
Manual test
LNL1
S1
LNL1
S1 L1
S1
ECO operation
S2MAX
ECO
S2
ONLY @ MAINS
{
C6
SBSA
1-2,5
A-
B+
SBSA
Maintain:
A-
B+
G:
G:
Y:
Y:
OK
TEST
Max = 50mA (100%)Eco = 33mA (66%)
1-2,5
A-
B+
7Sirios-LED Emergency Lighting www.eaton.com
Eaton is a registered trademark.
All other trademarks are property of their respective owners.
Cooper Univel S.A.Thessalonikis 8860100 Katerini, Greece
© 2014 EatonAll Rights ReservedPrinted in EUPublication No. 1-05-250 (R2)August 2014
Eaton Industries ManufacturingElectrical Sector EMEARoute de la Longeraie 71110 Morges, SwitzerlandEaton.eu