INSTALLATION AND OPERATING MANUAL FOR TELEPAC MICROCONTROLLER Synchronizer

Transcript of INSTALLATION AND OPERATING MANUAL FOR …3.imimg.com/data3/RW/TJ/MY-681901/telepack-controller.pdf5...

IINNSSTTAALLLLAATTIIOONN AANNDD

OOPPEERRAATTIINNGG MMAANNUUAALL

FOR

TELEPAC

MICROCONTROLLER

Synchronizer

2 IInnttrroodduuccttiioonn MICROCONTROLLERS with their inherent advantages are being increasingly used in the industry. With growing shortage and escalating cost of Electrical Energy, accurate monitoring of Air Conditioner's parameters has become necessary. 'TELEPAC MICROCONTROLLER is most useful for controlling A/Cs. This instrument is able to maintain Room Temperature with an accuracy of 0.1° C by automatic measurement of Room temperature and accordingly controlling AC ON/OFF.It also protects Costly Air conditioner from ‘Unhealthy conditions’ such as over load/under load etc. by automatically cutting off supply to it. SSaalliieenntt FFeeaattuurreess 1. Fully programmable. 2. Complete protection for AC from unhealthy condition. 3. All set points programmable from keypad.. 4. Password protection for controller. 5. Different Passwords for Normal set points, Offset Set points & Alarm Configuration set point. 6. on site selection of Single Phase/Three Phase. 7. 16 char. 2 lines LCD display with back lit on controller front panel. 8. Simple 4 Key keypad for on site programming. 9. Separate alarm contacts for AC 1 fail alarm AC 2 fail alarm, power fail 10. on site selection of Single AC/Dual AC operation. 11. Automatic display of AC parameters one by one in Run Mode. 12. Status & Healthy indication by LED on front panel. 13. Alarm indication by LED on front panel. 14. Room temperature sensing by precise sensor. 15. Separate outputs for each fan and compressor. 16. Direct display of Line voltage & actual current drawn by compressor. 17. Direct display of actual room temperature. 18. Sequencing of comp. for equal run hours, Site selectable. 19. Automatic Timer mode operation if Room sensor fails. 20. All Faults Autoreset. 21. Smoke fire & D.G. sensing. 22. Fault log History.(last 10 faults) 23. Compressor hour run 4 digit display. 24. Time remaining for change over display. 25. Total hour run from installation. 26. Single Phasing/Reverse Phasing Protection in case of Three Phase Controller. 27. Communication between 15 units ( 1 Master /14 Slaves) in each zone. 28. Communication between multiple zones possible. 29. Offset Feature for On site calibration. 30. Sensor fail mode On-time & Off-Time. 31. Seperate settable on delay for compressor.

3

FRONT VIEW :

BLUE STAR TELEPAC

CPU ALARMSUPPLY1SUPPLY2

AC 1 AC 2

4

TTeecchhnniiccaall SSppeecciiffiiccaattiioonnss

Supply Voltage : 230 VAC ± 15 % for Single Phase 415 VAC ± 15% for Three Phase Separate power supplies for each AC & independent Outputs for Fan & Compressor Output Contact Rating : 25 Amps. at 230 VAC Front Panel : 1) 16 char. 2 lines LCD display with backlit. 2) 4 Key keypad for programming. 3) Power indication for each AC. 4) AC ON indication for each AC 5) Controller Healthy Indication by Blinking Green LED 6) ALARM indication by Red LED. Sensing : 1) Inbuilt Voltage & Current sensing in Power

supply unit for compressor. 2)Temperature Sensing by precise Temp.sensor. Terminals : 1) Power unit for each AC, separate o/ps for 2 Fans & Compressor.

2) Temperature sensor. 3) AC1 fail alarm relay o/p. 4) AC2 fail alarm relay o/p. 5) Power fail alarm relay o/p

Alarms/ Protections : 1) Over voltage protection set point user selectable. 2) Under voltage protection set point user selectable. 3) Over load protection set point user selectable. 4) Under load protection set point user selectable. 5) Automatic cut off for smoke/Fire. 6) High/low temperature alarm set point user selectable. Dimensions : 1) Controller : 245 mm X 150 mm X 60 mm 2)Power supply unit:-125mm X 68mm X168mm

5 WWOORRKKIINNGG

TELEPAC MICROCONTROLLER is provided with independent power supplies for each AC. Controller can work with any one or both power supplies.Under normal working condition at Power On,first “ TELEPAC 1 Phase controller” message is displayed which remains about 10secs. After that Healthy indication starts blinking alongwith the supply indication provided for both supplies separately. Now, depending on the Room Temperature & Set points Fan 1 will be started after Fan Startup Delay (Default 5 sec) & Compressor will be On after Cp1 Startup Delay (Default 30 sec) & after Startup Delay of Fan2 & Cp2 startup delay they will be started if required ( depending on room temperature ) This is ‘Normal Run Mode’ for the controller. In this mode display will show status of ACs showing current drawn by Compressor,voltage & room temp. In this mode ACs will be turned ON/OFF depending on Room temperature requirement & Setpoints.e.g. If Compressor Temperature cutin is set to 23°C then the AC will be ON if Room Temperature goes above 23°C & the AC will be turned OFF when Room Temperature goes below 20°C i.e. 3°C Hysterisis is provided also 0.1°C accuracy is achieved with the controller. İf by some means Room Temperature remains below set point of one compressor & above set point of other. For example Compressor1 setpoint =20°C and Compressor2 set point =25°C & Room Temperature =22°C then Compressor2 may never be turned On & may cause problem to AC hence after specified time ( Shift Interval Set in Hrs.) the Temperature Set Points of the compressors gets interchanged automatically & now compressor2 will now be in service. If a fault occurs then ALARM indication on the front panel will be ON & the fault is displayed in the fault status also fault is stored in the Fault log history For Faults such as Compressor Overload/Underload AC will be turned off automatically & restart after Delay. User can examine the parameters of AC directly on controller display. At the end of set points user can view last 10 faults occurred to the A/C.These fault can be viewed using INC key. User can Hold & examine a parameter by pressing enter key in RUN mode. For any fault occurrence temperature Cutin set points are swapped between master and slaves. Cutin set points are swapped in cyclic manner.ie. Master Slave1 Slave 2……. Slave 14 Master. Once the cutin setpoint are swapped next change/ swapping occurs only after 5 minutes.

6 KKEEYY DDEESSIIGGNNAATTIIOONNSS 1) FUN : Thıs key is used to change the controller from RUN mode to FUNCTION selection mode. 2) ENTER : When this key is pressed the parameter entered by user gets accepted by the controller. 3) INC : This key is used to increment the value of parameters. 4) DEC : This key is used to decrement the value of parameters. RRUUNN MMOODDEE PPAARRAAMMEETTEERRSS 1) Initial Message : TELEPAC 1 Phase Microcontroller. 2) Zone ID 3) Slave ID 4) Room Temperature 5) CP1 Set Point 6) CP2 Set Point 7) CP1 Amp 8) CP2 Amp 9) CP1 Volt 10) CP2 Volt 11) BALANCE CYCLE TIME 12) CP1 Hour Run 13) CP2 Hour Run 14) Fault Messages FFAAUULLTTSS//PPRROOTTEECCTTIIOONNSS 1) Power supply failure CP1/CP2 2) Under Voltage CP1/CP2 3) Over Voltage CP1/CP2 4) Under Load CP1/CP2 5) Over Load CP1/CP2 6) Room Temperature High/Low 7) Smoke fire sensing. 8) D.G. sensing 9) Room sensor fail protection. CCOONNTTRROOLLLLEERR FFUUNNCCTTIIOONNSS User can see all set points by pressing FUN key.To enter any function, you are required to first enter the password.

7 System setting: • To change any parameter user will have to enter the password . When

you press INC/DEC key ,the display will indicate will show .

Enter the system password with the help of INC/DEC key . Press the Enter key to accept the value .Now user can enter/change into any set points. If password is not correct display shows “ 0” When correct passwor is entered user can change the set points. 1.Shift Cycle Time : - The temperature set points of A/Cs will be interchanged after cycle time That change over time is user setable . This fun is used to change the set point of Cycle Time , 0240M means 240 minutes so cycle time is 240 minutes. • Press FUN key once . Display will show 2 . System Temp Set Point:-

Display shows .the temperature setpoint for the controller. Display shows

İ.e. By default the setpoint is 24c. İn that case the CP1 set point will be 24c and CP2 set point will be Sys Temp Setpt + differential.

Shift Cycle Time 240M

Sys Temp Setpt 24.0 C

Setting(*10Shiycle:024

Enter Password: 0000

8 3.CP Differential:- By default the setpoint is 24c. İn that case the CP1 set point will be 24c and CP2 set point will be Sys Temp Setpt + differential. 4. ROOM HIGH SET POINT:- Press FUN key till Display shows

• Change the Room High Set Pt with the help of INC/DEC key. Press

Enter key. 5. ROOM LOW SET POINT:- • Press FUN key till Display shows •

• Change the Room Low Set Pt with the help of INC/DEC key. Press

Enter key. 6. COMPRESSOR OVER LOAD:- This fun is used for setting the Compressor Over Current set point.

The CP Over Load is displayed in Amp. • Press FUN key till Display shows

CP Differential 2.0 C

Room High SetPt 30.0C

Room Low SetPt 18.0C

CP OL SetPt 15.0A

9 • User can change the set point of CP OL with the help of INC/DEC key.

Press Enter key to save the changes. 7. COMPRESSOR UNDER LOAD:- This fun is used for setting the Compressor Under Current.

The CP Under Load set point is displayed in Amp. • Display shows

• Use INC/DEC keys to change set points.Press Enter key at the end. 8. A/C OVER VOLTAGE:- This fun is used for setting the over voltage set point

The A/C OV is displayed in Volt.

Display shows

For single phase &

For three phase . • To change the set point of A/C OV use INC/DEC key. Press Enter key at

the end. • 9. A/C UNDER VOLTAGE:- This fun is used for setting the under voltage set point of A/C.

The A/C UV is displayed in Volt. Display shows

CP UL SetPt 3.0A

OV SetPts 260V

UV SetPts 160V

OV SetPts 460V

10 For single phase &

For three phase. To change the set point of A/C OV use INC/DEC key. Press Enter key at the end. 10. CUT IN TEMPERATURE FOR COMPRESSOR1:- This fun is used for setting the Cut in Temperature for A/C1. The set point of CP1 is displayed in °C. Press FUN key twice. Display will show • Change the set point of CP1 Temp with the help of INC/DEC key. Press

Enter key. 11 . CUT IN TEMPERATURE FOR COMPRESSOR2:- This fun is used for setting the Cut in Temperature for A/C2.

The Room Temp of CP1 is displayed in °C. Display shows

• User can change the cut in temp.set point of CP2 with the help of

INC/DEC key. Press Enter key at the end. 12. SELECTION OF SINGLE PHASE/THREE PHASE CONTROLLER: Default selection is Single Phase Controller. To change the settings,user has to enter Select Contrlr Pwd which is 15. Display shows

To select Three Phase Controller, change the setting by arrow keys to

CP1 Temp SetPts 24.0C

CP1 Temp SetPts 24.0C

UV SetPts 160V

M/C Supply Setup Single Phase

11

And press ENTER key. 13. SELECTION OF SINGLE AC/DUAL AC CONTROLLER: Default selection is Single AC Controller. To change the settings,user has to enter Select Contrlr . Display shows

To select Three Phase Controller, change the setting by arrow keys to

And press ENTER key. OFFSET FUNCTIONS: IMP NOTE: Offset functions are not visible normally. If user wants to access offset functions follow these steps. 1. First enter password =6 2. Now OFFSET functions are open & visible to user.User can change/modify them. After power ON/OFF or password is locked, again the offset functions are inaccessible & only be opened if password = 6. CCOORRRREECCTTIIOONNSS UUSSIINNGG CCOONNTTRROOLLLLEERR OOFFFFSSEETTSS

If user wants to correct any error in the displayed parameter of A/C value e.g. Current or voltage which is displayed on screen, use OFFSETTING functions in settings. There are two functions. ‘+’ will add the set offset value with parameter . ‘-‘ will substract the set offset value from the parameter on screen. The offset parameters are as follows.

M/C Supply Setup Three Phase

No of CPs (1-2) 1

No of CPs (1-2) 2

12 1. ROOM TEMPERATURE + OFFSET :- • Press FUN key till Display shows

• Change the set point of Room Temp - offset with the help of INC/DEC

key. Press Enter key. 2. ROOM TEMPERATURE - OFFSET :- • Press FUN key till Display shows

• Change the set point of Room Temp - offset with the help of INC/DEC

key. Press Enter key. 3. A/C1 Current + OFFSET :- • Press FUN key till Display shows

• Change the set point of A/C1 Volt + offset with the help of INC/DEC

key. Press Enter key. 4. A/C1 Current - OFFSET :- • Press FUN key till Display shows

• Change the set point of A/C1 Volt - offset with the help of INC/DEC

key. Press Enter key.

ROOM Temp.+ 0.0c

ROOM Temp.- 0.0c

CP1 Current+ 0.0A

CP1 Current- 0.0A

13 5. A/C2 Curent + OFFSET :- Press FUN key till Display shows

• Change the set point of A/C2 Volt +/- offset with the help of INC/DEC

key. Press Enter key. 6. A/C2 Curent - OFFSET :- • Press FUN key till Display shows

• Change the set point of A/C2 Volt - offset with the help of INC/DEC key.

Press Enter key. 7. A/C1 VOLTAGE + OFFSET :- • Press FUN key till Display shows

• Change the set point of A/C1 Volt + offset with the help of INC/DEC

key. Press Enter key. 8. A/C1 VOLTAGE - OFFSET :- • Press FUN key till Display shows

• Change the set point of A/C1 Volt - offset with the help of INC/DEC

key. Press Enter key.

CP1 Voltage+ 0v

CP1 Voltage- 0v

CP2 Current+ 0.0A

CP2 Current- 0.0c

14 9. A/C2 VOLTAGE + OFFSET :- Press FUN key till Display shows

• Change the set point of A/C2 Volt +/- offset with the help of INC/DEC

key. Press Enter key. 10. A/C2 VOLTAGE - OFFSET :- • Press FUN key till Display shows

• Change the set point of A/C2 Volt - offset with the help of INC/DEC key.

Press Enter key. DELAY FUNCTIONS: IMP NOTE: DELAY functions are not visible normally. If user wants to access Delay functions follow these steps. 1.First enter password = “06” 2.Now DELAY functions are open & visible to user.User can change/modify them. After power ON/OFF or password is locked, again the DELAY functions are inaccessible & can only be opened if password = 06 1.AC1 FAN ON DELAY:- It shows the fan on delay for AC1 Change the Delay of AC1 FAN ON Delay with the help of INC/DEC key. Press Enter key.

CP2 Voltage+ 0v

CP2 Voltage- 0v

AC1 FAN ON Dly 5s

15 2.AC2 FAN ON DELAY:-. It shows the fan on delay for AC2 Change the Delay of AC2 FAN ON Delay with the help of INC/DEC key. Press Enter key 3.CP1 ON DELAY:- It shows the on delay for AC1 • Change the Delay of AC1 ON Delay with the help of INC/DEC

key. Press Enter key. 4.CP2 ON DELAY:- It shows the on delay for AC2 Change the Delay of AC2 ON Delay with the help of INC/DEC key. Press Enter key. 5.CP Over load sense DELAY:- It shows the over load sense delay for ACs • Change the Delay of CP OL Sense Delay with the help of

INC/DEC key. Press Enter key

AC2 FAN ON Dly 5s

CP1 ON Dly 30s

CP2 ON Dly 35s

CP OL Sense 5s

16 6.CP Under load sense DELAY:- It shows the under load sense delay for ACs • Change the Delay of CP UL Sense Delay with the help of

INC/DEC key. Press Enter key. 7.ROOM High sense DELAY:- It shows the ROOM HIGH sense delay for ACs • Change the Delay of Room High Sense with the help of INC/DEC

key. Press Enter key. 8.ROOM LOW sense DELAY:- It shows the ROOM LOW sense delay for ACs • Change the Delay of Room low Sense with the help of INC/DEC

key. Press Enter key. 9.OVER VOLTAGE sense DELAY:- It shows the OVER VOLTAGE sense delay for ACs • Change the Delay of AC OV Sense Delay with the help of

INC/DEC key. Press Enter key.

CP UL Sense 5s

ROOM HIGH Sense 5s

ROOM LOW Sense 5s

OV Sense 5s

17 10.UNDER VOLTAGE sense DELAY:- It shows the UNDER VOLTAGE sense delay for ACs • Change the Delay of AC UV Sense Delay with the help of

INC/DEC key. Press Enter key. 11. ROOM SENSOR FAIL:- In case room sensor fails, controller will be in Timer Mode. Only one A/C will be ON whose Cut in set point is less than the other.The A/C will be working with respect to the cycle on/off time set pts are given below. The cyc On / Off time set pts are displayed in minutes. • Press FUN key till Display shows

Change the cycle On / Off time set pts with the help off INC/DEC key. Press Enter key. A/C will remain ON for ON Time & OFF for OFF Time.

UV Sense 5s

Ssr Fail ON Dly 10M

Ssr Fail Off Dly 10M

18 STATUS PARAMETER:- 1. SHİFT CYCLE BALANCE TİME:- The temperature set points of A/Cs will be interchanged after cycle time That change over time is user setable . This fun is used to change the set point of Cycle Time , 0240M means 240 minutes so cycle time is 240 minutes. This function shoes the balance time for next shift cycle.

• Display shows

• Change the Delay of shift cycle balance time with the help of

INC/DEC key. Press Enter key 2. CP1 LOCK HOURS:- 3. CP2 LOCK HOURS:- 4. AC1 HOUR RUN :- This function shows for how much time AC 1 compressor is run from the time of installation. This function is for display only & user cannot modify it. Hour run counter will consider only the compressor running period not Fans. • Display shows

Shift Cycle Bal 240M

Cp1 Lock Hour 2H

Cp2 Lock Hour 2H

Cp1 Run Hour 2H

19 5. AC2 HOUR RUN :- This function shows for how much time AC 2 compressor is run from the time of installation. This function is for display only & user cannot modify it. Hour run counter will consider only the compressor running period not FANs.

• Display shows

NOTE THAT HOUR RUN COUNTER WILL BE RESET AUTOMATICALLY AFTER 9999 HOURS OF RUNNING OF COMPRESSOR. POWER CUT WILL NOT AFFECT THE COUNTER. Hysteresis FUNCTIONS: IMP NOTE: Hysteresis functions are not visible normally. If user want to access Hysteresis functions follow these steps. 1. First enter password = “06” 2. Now Hysteresis functions are open & visible to user.User can change/modify them. After power ON/OFF or password is locked, again the Hysteresis functions are inaccessible & only be opened if password = 06

If user wants to set any Hysteresis use Hysteresis functions

in settings. The Hysteresis parameters are as follows.

1. Room High Temp Hysteresis :- • Press ENT key till Display shows

• Change the Hysteresis of Room High Hysteresis with the help of

INC/DEC key. Press Enter key.

Cp2 Run Hour 2H

Room Hi Temp Hys 1.0c

20 2. Room Low Hysteresis :- • Press ENT key till Display shows

• • Change the Hysteresis of Room Low Hysteresis with the help of

INC/DEC key. Press Enter key. 3. A/C OV Cutoff Hysteresis :- Press ENT key till Display shows

• Change the Hysteresis of AC OV Cutoff Hysteresis with the help

of INC/DEC key. Press Enter key. 4. A/C UV Cutoff Hysteresis ON Delay :- • Press ENT key till Display shows

• Change the Hysteresis of AC UV CutOff Hysteresis with the help

of INC/DEC key. Press Enter key. 5. FAN1 Cutoff Hyustersis :- • Press ENT key till Display shows

• Change the Hysteresis of Fan1 Cutoff Hysteresis with the help of

INC/DEC key. Press Enter key. 6. Fan2 CutOFF Hysisteresis :- • Press ENT key till Display shows

Room Lo Temp Hys 1.0c

AC OV CutOff Hys 10V

AC UV CutOff Hys 10V

FAN1 CutOff Hys 1.0c

FAN2 CutOff Hys 1.0c

21 • Change the Hysteresis of Fan2 Cutoff Hysteresis with the help of

INC/DEC key. Press Enter key. 7. CP1 Cutoff Hysteresis :- Press ENT key till Display shows

• Change the Hysteresis of CP1 Cutoff Hysteresis with the help of

INC/DEC key. Press Enter key. 8. CP2 Cutoff Hysteresis :- • Press ENT key till Display shows

• Change the Hysteresis of CP2 Cutoff Hysteresis with the help of

INC/DEC key. Press Enter key. NetWork functions IMP NOTE: NetWork functions are not visible normally. If user wants to access NetWork functions follow these steps. 4. First enter password = “06” 2. Now NetWork functions are open & visible to user.User can change/modify them. After power ON/OFF or password is locked, again the NetWork functions are inaccessible & only be opened if password = 06

If user wants to set IP Adderess of unit or unit No it will change over NETWORK Settings. The Network parameters are as follows. 1. ZONE İD :- • Press ENT key till Display shows

CP1 CutOff Hys 3.0c

CP2 CutOff Hys 3.0c

Zone ID(1-15) 1

22 • Change the zone ID with the help of INC/DEC key. Press Enter

key. 2. UNIT ID :- • Press ENT key till Display shows

• Change the unit ID with the help of INC/DEC key. Press Enter key.

3. Reset Unit ID :- Press ENT key till Display shows

• Reset the unit id with the help of INC/DEC key. Press Enter key. 4. Selection of MASTER/SLAVE :- • Press ENT key till Display shows

• Select MASTER/SLAVE with the help of INC/DEC key. Press

Enter key. 5. TOTAL ZONE UNITS :-

THE NUMBERS OF UNITS CONNECTED IN THE ZONE SHOULD BE SELECTED

• Press ENT key till Display shows

• Change the NO OF ZONE UNITS with the help of INC/DEC key.

Press Enter key.

Reset Unit ID NO

Unit ID(1-15)1

MASTER/SLAVEMASTER

TOTAL ZONE UNITS 1

23 6. BAUD RATE :- Press ENT key till Display shows

• Change the BAUD RATE with the help of INC/DEC key. Press

Enter key. 7.UNIT SYNCRONIZATION PERIOD:- Password FUNCTIONS: IMP NOTE: Password functions are not visible normally. If user wants to access Password functions follow these steps. 6. First enter password = “06” 2. Now Password functions are open & visible to user.User can change/modify them. After power ON/OFF or password is locked, again the Password functions are inaccessible & only be opened if password = 06

If user wants to set any Password use Password functions in settings. The Password parameters are as follows. 1. System Settings :- • Press ENT key till Display shows

• Change the System Setting Password with the help of INC/DEC

key. Press Enter key.

BAUD RATE 9600

Unıt Sync Period10M

System Settings 6

24 2. Offset Settings :-

• Press ENT key till Display shows

• Change the Offset Settings Password with the help of INC/DEC

key. Press Enter key. 3. Delay Setting :- Press ENT key till Display shows

• Change the Delay Setting Password with the help of INC/DEC

key. Press Enter key. 4. Status Parameter :- • Press ENT key till Display shows

• Change the Status Parameter with the help of INC/DEC key.

Press Enter key. 5. Control Parameter :- Press ENT key till Display shows

• Change the Control Parameter with the help of INC/DEC key.

Press Enter key.

Delay Settings 6

Offset Settings 6

Status Parameter 6

Control Parameter 6

25 6. Network Settings :- • Press ENT key till Display shows

• Change the Network Settings with the help of INC/DEC key. • Press Enter key. 7. Password Setting :- Press ENT key till Display shows

• Change the Password Setting with the help of INC/DEC key.

Press Enter key. 8. Fault History :- • Press ENT key till Display shows

• Change the Fautl History with the help of INC/DEC key. Press

Enter key. 9. Fault Reset :- • Press ENT key till Display shows

• Change the Fautl reset the help of INC/DEC key. Press Enter

key.

Network Settings 6

Password Settings 6

Fault History 5

Fault Reset 6

26 10. DEBUG WINDOW :- • Press ENT key till Display shows

• Change the Debug Window byINC/DEC . Press Enter key. Fault History Function:- In This function resent ten fault are store. Fault Reset :- Using this function the faults can be reset. DEBUG WINDOW:- Thıs function shows the status of the units connected in the network. The display shows as follows Exit Function: Using this function the user can exit from the function menu to Run mode. PASSWORD :- Now password is of 4 digits & default factory set password will be “06”. If user wish to change the password,he has to enter first this default password & then by going into password function he can enter his own password.Now next time the controller will give access to password entered by user OR the factory set password which is 06. To view/change the offset set points, user has to enter the correct Offset Password which is 06 (Factory set).

DEBUG WINDOW 5

Unit Connection Slave 01 NO