R INSTALLATION AND MAINTENANCE INSTRUCTIONS RCU 20 FOR FIGHTER 360P/1120/1220/1320 MOS GB 0627-1 511584 RCU 20 LEK

Transcript of INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate...

Page 1: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

R

INSTALLATION AND MAINTENANCE INSTRUCTIONS

RCU 20FOR FIGHTER 360P/1120/1220/1320

MOS GB 0627-1 511584RCU 20

LEK

Page 2: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation
Page 3: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

Contents 1

RCU 20

GeneralSetting table ........................................................ 2Product description .............................................. 3

InstallationAssembly .............................................................. 4Network connections ............................................ 6Digital inputs ........................................................ 7

IndicatorsIndicators on RCU 20 .......................................... 8

StartingGeneral .................................................................. 9RCU 20 configuration software .............................. 9Logging in ............................................................ 11

Web interfaceWeb browser requirements .................................. 12Menu overview .................................................... 12

Web interface – SettingsLanguage selection .............................................. 13Log ...................................................................... 13Module ................................................................ 14E-mail .................................................................. 14Network ................................................................ 14User ...................................................................... 15

Web interface – FIGHTER 360POverview page .................................................... 16Operating data .................................................... 17Operating data, extended .................................... 18Alarm/status ........................................................ 19Log ...................................................................... 19

Web interface – FIGHTER 1120/1220Overview page .................................................... 20Operating data .................................................... 21Operating data, extended .................................... 22Operating data, external units .............................. 22Alarm/status ........................................................ 23Log ...................................................................... 23

Web interface – FIGHTER 1320Overview page .................................................... 24Operating data .................................................... 25Operating data, external units .............................. 26Operating data, compressor ................................ 27Log ...................................................................... 27

Component locationsComponent locations .......................................... 28List of components .............................................. 28

MiscellaneousTechnical specifications ...................................... 29Enclosed kit .......................................................... 29

Frequently asked questionsFrequently asked questions ................................ 30

Page 4: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

General

RCU 20

2

In order to get the ultimate benefit from your RCU 20 communications unit you should readthrough these Installation and Maintenance Instructions.

Installation date

Installation engineers

MAC ID

Date __________ Signature __________________________________

To be completed when the communications unit has been installed

Page 5: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

The RCU 20 consists of a communications module,and a separate power supply unit with jack for plug-ging into a wall socket.The RCU 20 enables operations to be controlled andmonitored using a computer connected to a local net-work or via the Internet.

It is possible to connect to the RCU 20 two indepen-dent switch functions to detect external events such asa movement alarm or freezing protection.Note that all configuration of the unit requires that acomputer is connected.

General 3

RCU 20

Product description

Page 6: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

LEK

Installation

RCU 20

4

Stick the product label securely to the cover. The labelcan be placed in any orientation, depending on thelocation of the unit.Open the plastic cover by separating its two halves.The RCU 20 is placed outside the heat pump and itsbest location is mounted on a wall.Connect the communication cable in accordance withthe appropriate product description. Then continue withthe instructions under the heading “Final installation”.

FIGHTER 360PConnect the black communication cable (105) fromthe heat pump to the cable leading to the RCU 20,position (4) using the accompanying extension con-nector.Earlier versions of the FIGHTER 360P do not have thecable (105). Then connect the accompanying blackcommunication cable to the heat pump modular con-nector that is on the CPU card (34). Use the accompa-nying extension connector to connect the cable fromthe RCU 20 position (4).For communication to work, the CPU card in theFIGHTER 360P must have version number 2.00 orhigher.

34

105

34

FIGHTER 1120Connect the accompanying black communicationcable to the heat pump modular connector that is onthe CPU card (34). Use the accompanying extensionconnector to connect the cable from the RCU 20 posi-tion (4).For communication to work, the CPU card in theFIGHTER 1120 must have version number 1.03 orhigher.

Assembly

Page 7: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

Installation 5

RCU 20

FIGHTER 1220Connect the accompanying black communicationcable to the heat pump modular connector that is onthe CPU card (34). Use the accompanying extensionconnector to connect the cable from the RCU 20 posi-tion (4).For communication to work, the CPU card in theFIGHTER 1220 must have version number 1.03 orhigher.

Final installationConnect the 4-pole modular cable to the networkadapter output. Plug the network adapter into a near-by wall socket. Refit the plastic cover to the RCU 20.The heat pump must be configured, to permit commu-nication with the RCU 20. This is done via the servicemenus. Refer to the “Installation and MaintenanceInstructions” for the respective products.

Tip: Try to find a wall socket for the network adapterthat is fed from a different fuse than the fuse for theheat pump supply. The RCU 20 will then be able todetect if the heat pump shuts down.

34

FIGHTER 1320Connect the accompanying black communicationcable to the heat pump modular connector that is onthe CPU card (34). Use the accompanying extensionconnector to connect the cable from the RCU 20 posi-tion (4).For communication to work, the CPU card in theFIGHTER 1320 must have version number 1.10 orhigher.

LE

K

34

Assembly

Page 8: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

RCU 20

6

Internetuppkoppling(t ex modem)

Router alt. Hub/Switch

Dator RCU 10

Värmepump

Dator

RCU 10

Internetuppkoppling(t ex modem)

Värmepump

The RCU 20 has a connection (5) for 10/100 MbpsEthernet.Connect the unit to a network, or alternatively direct toa computer with the Ethernet cabling. For connectionto a router or a hub/switch a straight-through cablemust be used, and for direct connection to a computera crossover cable must be used.A network with the RCU 20 connected to a router orhub/switch is recommended. For connection direct toa computer with Internet connection, two networkcards are required in the computer, and it must runcontinuously in order to provide the RCU 20 access tothe Internet.Internet connection is not necessary to be able toinstall and configure the unit, but is required foraccess to the unit via the Internet.

Network connections

Internet connection

Router, alternativelyHub/Switch

Computer RCU 20 RCU 20

Computer

Heat pump Heat pump

Internet connection

Page 9: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

7

RCU 20

Installation

The RCU 20 has two digital inputs (7) (optically isolat-ed) for connection of an external signal. The inputsshall be 10 – 24 VDC for an active high signal and 0 –2 VDC for an inactive signal.

Terminal number Function24 Voltage feed (12 VDC)23 Signal ground (GND)22 Not used (NC)21 Not used (NC)20 Digital In 2+ (DI2+)19 Digital In 2- (DI2-)18 Digital In 1+ (DI1+)17 Digital In 1- (DI1-)(Digital In 1- and Digital In 2- are internally connectedtogether).

Digital inputs

Supply

Voltag

e 9-3

2 V

AC/D

C, 1

W

ART# :

0120 9

999 0

1

Mac

ID: 0

0:3

0:1

1:F

B:0

1:3

5

NETB

ITER

MO

DBU

S TCP/R

TU G

ATEW

AY

MAD

E IN S

WED

EN45:2

003

LEK

74

Page 10: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

RCU 20

8 Indicators

Not lit The RCU has no voltageSteady green RCU 20 in operation Steady orange On starting

Not lit No contact with networkSteady green 10 Mbit/s linkSteady orange 100 Mbit/s link

Not lit WaitingFlashing green TX serial channelFlashing red RX serial channelSteady orange On starting

Not lit WaitingFlashing green Ethernet trafficFlashing red Ethernet conflict

Indicators on RCU 20

Page 11: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

9

RCU 20

Starting

The RCU configuration software is a PC-based pro-gram that can be used to prepare different network-parameters in the RCU 20. The program can searchfor RCU 20 units on an Ethernet network, after whichthe IP address, network mask, gateway, DNS, etc.can be set. DHCP can also be activated in the unit.

Install by running the installation program Setup-Net-BiterConfig.exe that is on the supplied CD.

System requirements■ Pentium 133 MHz■ 5 MB free hard disk space■ Windows 95/98/ME/NT/2000/XP■ Network card (Ethernet)If a different operating system than Windows is usedthe configuration software can not be used. Then con-nect to the RCU’s preset IP address in the web brows-er and use the web interface to change the networksettings. See section “Starting” – “Logging in”.

IP: IP address for the RCU 20SN: Network maskGW: GatewayDHCP: Dynamically assigned IP address (On/Off)Version: Software versionType: Product typeMAC: Ethernet MAC address

Search for connected unitsWhen the program starts, it will automatically searchfor an RCU 20 network connection. A list will be dis-played of all units that are found. A new search can bemade by pressing the “Scan” button.

MAC ID in hex code.

The RCU 20 has a preset IP address: 10.200.1.1. NOTE! Images and settings on the following pagesmay show some difference, depending on the brows-er, settings and the version of the RCU, as well as theheat pump configuration.

RCU 20 configuration software

General

Page 12: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

Starting

RCU 20

Changing IP settingsDouble-click on the desired unit in the list to changethe IP settings. A new window will open, in which thenew settings can be entered.

To obtain the necessary information concerning yournetwork settings, please contact your network admin-istrator.

RCU 20 configuration software

IP Address: IP address for the RCU 20Subnet mask: Network maskDefault gateway: GatewayPrimary DNS: Primary DNS (any)Secondary DNS: Secondary DNS (any)Host name: Host name for RCU 20 (any)

The preset password is ”admin”.On pressing the “Set” button the RCU 20 will restart,after which the new settings will be activated.

The new settings can be tested by opening a browserand entering the set IP address. If DHCP is activated,a new search can be made with the program to seewhich IP address has been assigned to the RCU 20.

NOTE! Only set DHCP to “On”

if a DHCP server is available on the network.

NOTE! If the password is forgotten, there is

no way to retrieve it. The RCU 10must be returned to NIBE where a

complete reset will take place.All the settings that have been made,

including user settings, will disappear.

NOTE! The password is case-sensitive, i. e.

the precise password must be enteredin respect of upper and loser case

characters.

NOTE! Only A-Z, a-z and 0-9 are permitted tobe used in the user ID and password,the symbol characters cannot be used.

10

Page 13: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

RCU 20

Start the browser (such as Internet Explorer) andenter the selected IP address in the RCU 20. If the IP address is chosen for example to be 10.2.15.21,then ”http://10.2.15.21” is entered into the browseraddress field, followed by pressing the Enter button.The following or a similar image will be displayed:

To access the product’s internal web page for the firsttime, enter “admin” into both entry fields. The pass-word will be changed later, and new users can beadded (refer to the ”Web interface – Settings” >”Users” section).

If there is a problem logging in, check that ”Caps Lock”is not activated for the keyboard.

Logging in

Starting 11

Page 14: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

RCU 20

Web interface

The web pages are optimised for Internet Explorer 6.0and Mozilla Firefox. Other browsers may also work,but the pages may appear different.The browser must support Java.If Java is not supported, the component may bedownloaded athttp://www.java.com/en/download/manual.jsp

The actual displayed images may differ somewhat,depending on the currently installed configuration.The RCU 20 has two menus, a top menu and a sidemenu. The top menu provides navigation to differentareas of the NIBE web site (requires Internet connec-tion) and resetting of the RCU 20 to another language(requires administrative or writing authority).

The side menu provides navigation in the RCU 20’sinternal web pages. The side menu has differencesdepending on which product is used together with theRCU 20.

If “Miscellaneous” is selected, a new menu appears:

Overview diagramThis page shows in a schematic way how the heatpump operates. The temperature and operational sta-tus can be read here. See the respective productdescriptions.

Operating dataThis page shows in detail how the heat pump oper-ates. A selection of the most often used measured val-ues can be read and adjusted here. See the respec-tive product descriptions.

Extended operating data/ external/ compressorFurther measured values are shown here for readingand adjustment. See the respective product descrip-tions.

Alarm/statusThis page shows whether any alarms have been acti-vated. FIGHTER 1320 does not have this page, andany activated alarms are shown on the overview pageinstead.

SettingsHere are various web interface and RCU function set-tings.

These menus are common to all heat pumps and aredescribed in the “Web interface – Settings” section.

FIGHTER 360P FIGHTER 1120/1220 FIGHTER 1320

Web browser requirements

Menu overview

12

Page 15: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

RCU 20

In “Settings” – “Log” are entered the desired paramet-ers, logging interval and type of log-in.The selected parameters and logging interval affectthe total log time. With several selected parametersand a a more frequent logging interval, the RCU 20memory fills up more quickly and the total log time isreduced.The logging interval defines at which intervals thelogged values shall be saved. Selectable intervals areevery 10 seconds, 30 seconds, 1, 2, 5, 10, 30 and60 minutes.The logging type can be selected from 3 differentmodes: No logging, Stop logging when the log is full orCircular logging (the oldest measured value is erasedand replaced by new when the log is full).The buttons at the bottom can be used tomark/unmark all the measured values and saveselected settings.

The log settings menu has differences depending onwhich product is used.The following illustration is from the FIGHTER 1320.Here the logged values are put on different pages,that are selected from the scrolling list. The FIGHTER1120/1220 also has its logged values placed on differ-ent pages. Otherwise, the logging settings for the dif-ferent products operate in the same way.

NOTE! The settings must be saved for

activation to take place.

To change the language used in the RCU 20, click onthe flag for the desired language in the top menu, orselect ”Settings” – “Choose language” and then clickon the desired language. To activate the selected lan-guage, click on ”Save”.

Language selection

Log

Web interface - Settings 13

Page 16: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

RCU 20

Web interface – Settings

In “Settings” – ”Miscellaneous” – “Module” informationconcerning where the module is installed can beentered. The informationen in the “Building” display isthen used when the RCU 20 sends an alarm via E-mail or as a text message.The RCU 20 can be restarted remotely by clicking on“Restart”.

Module

Here the settings for handling E-mail can be made.This is necessary for enabling the RCU 20 to sendalarms via E-mail to selected users.

E-mail

Here the basic settings for network connection can bemade. These are the same settings that can be madewith the aid of the RCU 20 configuration program.

Network

NOTE! If the RCU 20 is to be reached via theInternet it is important to configure a

firewall that will allow the reception ofincoming web traffic (port 80).

NOTE! Only set DHCP to “On”

if a DHCP server is available on the network.

14

Page 17: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

RCU 20

Web interface – Settings

NOTE!The password is case-sensitive and

only A-Z, a-z and 0-9 are permitted tobe used in the user ID and password,

which means that the symbolcharacters cannot be used.

Here takes place handling of users who shall have theright to log in to the RCU 20. Click on “Add” to add anew user. Existing user information can be edited byclicking on the names.

■ User ID: This ID is used when logging on to theRCU 20 via a browser.

■ Name: User’s name.■ E-mail: The user’s E-mail address to which alarms

are to be sent.■ Alarm receiver: Here is defined which types of

alarm the user is to receive. Several boxes can bemarked.- Prio 1: All alarms except those below.- Prio 2: Low priority alarms.- Digital inputs: Alarms from digital inputs.- Heat pump status changed: Alarm warning that

the status of the heat pump has changed. ■ User level:

- Read: The user may only look at the web site andcannot change anything.

- Write: The user may look at the web site andchange parameters on the operations pages.

- Admin: The user may look at the web site andhas full authority to change configuration andparameters.

■ Password: This password is used when logging onto the RCU 20 via a browser. The password is tobe repeated for verification.

User

15

Page 18: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

RCU 20

Web interface – FIGHTER 360P

This is the first page to be displayed after logging in. Itshows an overview with information concerning themost important parameters of the heat pump.

A Supply temperature Menu 2.0*B Return temperature Menu 2.6*C Temperature, compressor sensor Menu 1.1*D Temperature, hot water sensor Menu 1.0*E Evaporation temperature Menu 5.0*F Extract air temperature Menu 5.1*G Exhaust air temperature Menu 5.2*H Outside temperature Menu 4.0*I Operating indications

Lit lamp indicates an active function.

* Equivalent menu number in FIGHTER 360P

Overview diagram

C

D

HG IFE

A B

16

Page 19: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

RCU 20

Web interface – FIGHTER 360P

The change in value presumes that the user haslogged in with writing or administration authority.

Operating data for several measured values is shownin table format for easy viewing.M1.0 shows that the equivalent menu in FIGHTER360P is 1.0.At S86 the status for the component numbered 86 inFIGHTER 360P’s component list is shown.To change a value, click on ”arrow down” and select avalue from the scrolling list, confirm with ”Set”. After afew seconds the change is confirmed by FIGHTER360P and the relevant value is updated.

Operating data

17

Page 20: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

RCU 20

Web interface – FIGHTER 360P

In this form the heat regulation parameters can bechanged by clicking on ”arrow down” and selecting avalue from the scrolling list, confirming thereafter with”Set”.Note that the selected RCU offset heating curve isadded to the heat pump’s internal offset heatingcurve.

The change in value presumes that the user haslogged in with writing or administration authority.

Operating data, extended

18

Page 21: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

RCU 20

Web interface – FIGHTER 360P

This form shows the common alarms that the heatpump has indicated.External alarm inputs DI1 and DI2 are not concernedwith the heat pump functions but are self-defined func-tions, e.g. movement alarm and freezing protection.

Factory settingsClick on the “Factory settings” button to reset all set-tings in the FIGHTER 360P to their original states.

RestartingClick on the “Restart FIGHTER 360” button to restartthe FIGHTER 360P.

Alarm/statusHere the log files that are in the RCU 20 can befetched. The parameter log contains selected loggedvalues (see the “Web interface – Settings” > “Log”section).The alarm log contains all the alarms that have beenindicated and a number of temperatures registered atthe time of each alarm.The log files can be cleaned out by clicking on the“Clean log file” button for the appropriate log.

The log files are in CSV format, which is a standardformat that can be imported into several kinds of cal-culation program for further processing.

Log

19

Page 22: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

RCU 20

Web interface – FIGHTER 1120/122020

This is the first page to be displayed after logging in. Itshows an overview with information concerning themost important parameters of the heat pump.

A Communication indicationsGreen lamp indicates functioning communica-tions.Red lamp indicates communication error.

B Operating indicationsLit lamp indicates an active function.

C Operational informationHere the status is shown of the functions that areactivated in the heat pump.

Overview diagram

C

BA

Page 23: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

RCU 20

Web interface – FIGHTER 1120/1220 21

Operating data for several measured values is shownin table format for easy viewing.M1.0 shows that the equivalent menu in FIGHTER1120/1220 is 1.0.Note that the selected RCU offset heating curve isadded to the heat pump’s internal offset heatingcurve.To change a value, click on ”arrow down” and select avalue from the scrolling list, confirm with ”Set”. After afew seconds the change is confirmed by the heatpump and the relevant value is updated.

The change in value presumes that the user haslogged in with writing or administration authority.

Operating data

Page 24: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

RCU 20

Web interface – FIGHTER 1120/122022

In this form the heat regulation parameters can bechanged by clicking on ”arrow down” and selecting avalue from the scrolling list, confirming thereafter with”Set”.

The change in value presumes that the user haslogged in with writing or administration authority.

Operating data, extended

In this form the external unit parameters can bechanged by clicking on ”arrow down” and selecting avalue from the scrolling list, confirming thereafter with”Set”.

The change in value presumes that the user haslogged in with writing or administration authority.

Operating data, external units

Page 25: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

RCU 20

Web interface – FIGHTER 1120/1220 23

This form shows the common alarms that the heatpump has indicated.External alarm inputs DI1 and DI2 are not concernedwith the heat pump functions but are self-defined func-tions, e.g. movement alarm and freezing protection.Alarm resetting takes place from the form “Operatingdata, extended”.

Alarm/statusHere the log files that are in the RCU 20 can befetched. The parameter log contains selected loggedvalues (see the “Web interface – Settings” > “Log”section).The alarm log contains all the alarms that have beenindicated and a number of temperatures registered atthe time of each alarm.The log files can be cleaned out by clicking on the“Clean log file” button for the appropriate log.

The log files are in CSV format, which is a standardformat that can be imported into several kinds of cal-culation program for further processing.

Log

Page 26: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

RCU 20

Web interface – FIGHTER 1320

This is the first page to be displayed after logging in. Itshows an overview with information concerning themost important parameters of the heat pump.

A Lists installed units. Click on a unit to see theassociated operating information. A red markerindicates which unit is being shown.

B Operating indicationsShows operating conditions for installed units.Green background indicates when the compres-sor is operational. Red background indicatesalarm.

C Alarm indicationsD Operational information

Here the status is shown of the functions that areactivated in the heat pump.

Overview diagram

B C

D

A

24

Page 27: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

RCU 20

Web interface – FIGHTER 1320

Operating data for several measured values is shownin table format for easy viewing.M1.0 shows that the equivalent menu in FIGHTER1320 is 1.0.Note that the selected RCU offset heating curve isadded to the heat pump’s internal offset heatingcurve.To change a value, click on ”arrow down” and select avalue from the scrolling list, confirm with ”Set”. After afew seconds the change is confirmed by the heatpump and the relevant value is updated.

The change in value presumes that the user haslogged in with writing or administration authority.

Operating data

25

Page 28: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

RCU 20

Web interface – FIGHTER 1320

In this form the external unit parameters can bechanged by clicking on ”arrow down” and selecting avalue from the scrolling list, confirming thereafter with”Set”.

The change in value presumes that the user haslogged in with writing or administration authority.

Operating data, external units

26

Page 29: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

RCU 20

Web interface – FIGHTER 1320

In this form the compressor parameters can bechanged by clicking on ”arrow down” and selecting avalue from the scrolling list, confirming thereafter with”Set”. Switch between different heat pumps in the sys-tem by using the scroll list at the top left.

The change in value presumes that the user haslogged in with writing or administration authority.

Operating data, compressor

Here the log files that are in the RCU 20 can befetched. The parameter log contains selected loggedvalues (see the “Web interface – Settings” > “Log”section).The alarm log contains all the alarms that have beenindicated and a number of temperatures registered atthe time of each alarm.The log files can be cleaned out by clicking on the“Clean log file” button for the appropriate log.

The log files are in CSV format, which is a standardformat that can be imported into several kinds of cal-culation program for further processing.

Log

27

Page 30: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

RCU 20

Component locations28

1 Communications module4 Communication port to FIGHTER5 Network connections7 Connection of external contact function8 Label with MAC ID

List of components

A

LEK

4 71

8

5

Page 31: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

RCU 20

Miscellaneous 29

Technical specifications

Operating temperature range 0 – 60 °C

Rating 230 V, 50 Hz, 3 VA

CE certification In accordance with EN 50 081-2:1993 and EN 61 000-6-2:1999

Ethernet connection 10Base-T or 100Base-TX (IEEE 802.3). RJ45 contact.

CD with RCU configuration software

Extension connector

Power supply adapter

Label for placing on thecover

Cabling for heat pump, 0.5 m

Enclosed kit

LEK

LEK

LEK

LEK

Page 32: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

RCU 20

What do you have to think about to get to the website from the Internet?In most cases where on has a fixed connection to theInternet there is some kind of firewall to protect the net-work. To access a unit inside a firewall, it must be con-figured to let desired traffic through. To gain access tothe web site in the RCU 20 from the Internet, port 80(HTTP/web) must open in the firewall and be guided tothe RCU unit on the inside.

How do I connect an RCU with a cable directly to acomputer, without connecting it to a network?Ethernet networks can have two types of cable: straight-through or crossover. A straight-through cable is usedbetween the computer <-> network equipment. Acrossover cable is used between a computer <-> anoth-er computer or for network equipment <-> networkequipment. The RCU 20 is counted as a computer andshall therefore have a crossover cable if it is connecteddirectly to another computer.

Can the RCU 20 become infected with a virus?No. Viruses are generally always written to infect com-puters that run Microsoft Windows, or occasionallyLinux. A virus is written for a particular operating systemor processor and can only infect the type of platform forwhich it is written. An RCU 20 does not have the sametype of processor as an everyday computer, nor can ittherefore become infected.

What does ”JAVA support in a browser” mean?To be able to run a program written in JAVA on a com-puter, it must have a JVM (Java Virtual Machine)installed. A JAVA applet on a web site requires that thebrowser can use this JVM to be able to run the applet.Most current browsers can manage this but there is notalways a JVM installed in the computer. In these casesa JVM must be downloaded and installed for everythingto work. JVMs for many different operating systems canbe downloaded from: www.java.com.

Two log-in windows are displayed, why?Unfortunately web browsers are often not perfectly inte-grated with the JVM that is installed in the computer. Inpractice the JVM (that runs the JAVA applets) does notunderstand that the browser has already put up a log-inwindow, and therefore puts up another one when aJAVA applet is to be run, for safety’s sake. This willhopefully be solved in future versions of browsers andJVMs.

What does ”Network mask” mean?An IP address is composed of 32 bits and the networkmask defines how many bits are used for the networkaddress. The remaining bits identify the computer onthe network. The net mask looks the same as an IPaddress, e.g. 255.255.0.0 or 255.255.255.0.

What is a ”default Gateway”?So that computers that are on separate networks (differ-ent sub-networks) are able to communicate with eachother, routers are needed between the networks to“bridge” the traffic. Default gateway is the name of therouter that is to be used to reach the computers that arenot on the local network. This router then sends theinformation on to the destination or the nearest routerthat it knows about.

Which browsers work together with an RCU?The web pages are optimised for Internet Explorer andMozilla Firefox. Other browsers should work well, butthe pages may look different.

What is the format of the log files?The log files in the RCU are of CSV type. This is a usualformat for log files and is supported by such programsas Microsoft Excel.

Frequently asked questions30

Page 33: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

31

RCU 20

Page 34: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

RCU 20

32

Page 35: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

RCU 20

Page 36: INSTALLATION AND MAINTENANCE INSTRUCTIONS R RCU 20 · General RCU 20 2 In order to get the ultimate benefit from your RCU 20 communications unit you should read through these Installation

NIBE ABSWEDEN

R

Tel: +46 - (0)433 - 73 000Fax: +46 - (0)433 - 73 190E-mail: [email protected]

Box 14Järnvägsgatan 40SE-285 21 MARKARYD

PL

DE

NL

DK

FI

Vølund VarmeteknikFilial af NIBE AB

Brogårdsvej 7, 6920 Videbæk

Tel: 97 17 20 33Fax: 97 17 29 33E-mail: [email protected]

NIBE – HaatoValimotie 27

01510 Vantaa

Puh: 09 - 274 697 0Fax: 09 - 274 697 40E-mail: [email protected]

GBNIBE Energy Systems Ltd. Tel: 08 45 095 1200

Fax: 08 45 095 1201E-mail: [email protected]

NIBE Systemtechnik GmbHAm Reiherpfahl 3

D-29223 Celle

Tel: 05141/7546-0Fax: 05141/7546-99E-mail: [email protected]

NIBE Energietechniek B.V.Postbus 2

4797 ZG WILLEMSTAD NB

Tel: 0168 477722Fax: 0168 476998E-mail: [email protected]

NONIBE AB

Jerikoveien 20 1067 Oslo

Tel: 22 90 66 00Fax: 22 90 66 09E-mail: [email protected]

NIBE-BIAWAR Sp. z o. o.Aleja Jana Pawła II 5715-703 BIAŁYSTOK

Tel: 085 662 84 90Fax: 085 662 84 14E-mail: [email protected]

CZNIBE CZ

V Zavetri 1478/6CZ-170 00 Prague 7

Tel: 0266 791 796Fax: 0266 791 796E-mail: [email protected]