Transcript of INSILCOTE HV2000 Silicone coating for Insulator
Welcomes All of You
PUNE
We are Manufacturers of
* Alarm Annunciators
* Sequence of Events Recorder
* Microprocessor /PLC Based Systems.
We Represent some Foreign Companies for
* SF6 Gas Purification and Filling Units
* SF6 Gas Leak Detector and MultiParameter Analyzer
* Dew Point Meters
* Portable GIS Monitoring System
* Online GIS Monitoring System
Right Now We Introduce a New Product
INSILCOTE – RTV Silicone Rubber Coating,
From Mace Technologies, South Africa
( to be applied on Insulators in Substations.)
We are Sole Agent for this Product in India.
THE ELIMINATION OF POLLUTION FLASHOVER WITH THE
SYSTEM
INSILCOTE
IF A SUBSTATION IS SUFFERING FROM POLLUTION FLASHOVERS, WHAT ACTION SHOULD BE TAKEN?
• HAND CLEANING?• LIVE SPRAY WASHING?• INSTALL A FIXED WASHING SYSTEM?• SILICONE GREASING?• SILICONE RUBBER COATING?
LET’S EXAMINE THESE OPTIONS…..
HAND CLEANING
LIVESPRAYWASHING
ADVANTAGES:
• NO OUTAGE REQUIRED
DISADVANTAGES:
• NOT SUITED TO ALL CONTAMINANTS• NEEDS SPECIALISED EQUIPMENT• NEEDS SKILLED OPERATOR• NEEDS SOURCE OF LOW COND. WATER• FREQUENCY – NEEDS TO BE DONE OFTEN• INVOLVES RISK OF FLASHOVER FROM INCORRECT TECHNIQUE AND OVERSPRAY• DISTORTION OF FIELDS CAN CAUSE EQUIPMENT FAILURE
FIXEDSPRAYWASHINGSYSTEMS
…AND THE BIGGEST PROBLEM WITH ANYWASHING PROGRAM?….
TIMING!
• CLIMATIC VARIABLES & UNPREDICTABILITY
• MONITORING LIMITATIONS
• PRE-DEPOSITED VS. INSTANTANEOUS POLLUTION
SILICONEGREASING
ADVANTAGES:
• HYDROPHOBIC SURFACE
• CONTAMINANT ENCAPSULATION
• EXTEND MAINTENANCE INTERVAL
DISADVANTAGES:
• HIGH MATERIAL COST
• HIGH LABOUR COST
• LONG OUTAGES
• NOT FOR BULKY CONTAMINANTS
• SPENT MATERIAL DISPOSAL
• UNPLEASANT TASK
WARNING SIGN!
LEAKAGE CURRENTSARE DEGRADING THE GREASE TO A WHITE,WATER-ABSORBENTSILICA.
REPLACEMENT ISURGENTLY NEEDED.
SILICONE RUBBER COATING
GREASE IS NOW BEING LARGELY REPLACEDBY RTV SILICONE RUBBER COATINGS.
INSILCOTE HV2000 COATING FEATURES:
• EXCELLENT HYDROPHOBICITY• THE ABILITY TO TRANSFER THIS WATER- REPELLENCY TO A POLLUTION LAYER ON THE SURFACE• INHIBITS THE FORMATION OF MOIST LAYERS• LIMITS THE FLOW OF LEAKAGE CURRENTS• DUE TO IONISED CONTAMINANTS, IT PREVENTS FORMATION OF DRY BANDS
• INSILCOTE CONTAINS LOW MOLECULAR WEIGHT POLYMERS. THIS IMPARTS WATER REPELLANCY PROPERTIES TO THE POLLUTANTS WHICH GET ACCUMULATED ON THE SURFACE
• INSILCOTE HAS GOOD RESISTANCE TO ULTRA- VIOLATE RAYS AND MANY ORGANIC CHEMICALS
• IT PROVIDES GOOD SURFACE ARC RESISTANCE • USED FOR TRANSMISION LINES, SUBSTATIONS• USED FOR ALL POLLUTED AREAS LIKE CEMENT, CHEMICAL,STEEL, THERMAL POWER PLANTS
MACE TECHNOLOGIES’ INSILCOTE HV2000SILICONE RUBBER COATING HAS SERVEDFOR MORE THAN TWENTY YEARS IN THEMOST EXTREME ENVIRONMENTS.IT HAS BEEN USED IN SUBSTATIONS FROM 11kV TO 400kV AC AND 3kV TO 533kV DC.
INSILCOTE HV2000 IS THE ONLY INSULATOR COATING TO HAVE PASSED ESKOM’SSEVERE APPROVAL PROCEDURE AT THEIRKOEBERG TEST STATION ON THE HARSH WEST COAST OF SOUTH AFRICA
Time Trends
Date
00:00:002004/04/01
00:00:002004/03/15
00:00:002004/03/01
00:00:002004/02/15
00:00:002004/02/01
00:00:002004/01/15
00:00:002004/01/01
00:00:002003/12/15
00:00:002003/12/01
00:00:002003/11/15
00:00:002003/11/01
00:00:002003/10/15
00:00:002003/10/01
00:00:002003/09/15
00:00:002003/09/01
00:00:002003/08/15
00:00:002003/08/01
00:00:002003/07/15
00:00:002003/07/01
00:00:002003/06/15
00:00:002003/06/01
00:00:002003/05/15
00:00:002003/05/01
Acc
.CA
(C
A)
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
INSILCOTE
HV2000
COATINGTYPE 2UNCOATED
PORCELAIN
FOURTH FLASHOVER(sample disconnected)
NO FLASHOVERS
6 Mnths 9 Mnths
ACCUMULATED COULOMB AMPERE LEAKAGE CURRENTSMEASURED AT KOEBERG TEST STATION OVER A PERIOD OF 1 YEAR
Time of day trends of the average Peak Leakage Current
Time Of Day
23:0022:0021:0020:0019:0018:0017:0016:0015:0014:0013:0012:0011:0010:0009:0008:0007:0006:0005:0004:0003:0002:0001:00
Ave
rage
Pea
k Le
akag
e C
urre
nt (m
A)
5048
46
4442
4038
36
3432
3028
2624
22
2018
1614
12
108
64
2
EPOXY RESIN
EPDM RUBBERPORCELAIN
SILICONE RUBBER
INSILCOTE COATING
AVERAGE DAILY LEAKAGE CURRENT AMPLITUDES MEASURED AT KOEBERG TEST STATION OVER A PERIOD OF ONE YEAR
(IDENTICAL INSULATORS PRODUCED FROM DIFFERENT MATERIALS)
WATER “BEADS UP” ON A SILICONE RUBBER SURFACE…
EVEN WHEN THERE IS A THICK POLLUTION LAYER!
HYDROPHOBICITY OF INSILCOTE HV2000 AFTER3 YEARS ADJACENT TO A POWER STATION AND OPEN-CAST COAL MINE
TYPICAL MAINTENANCE INTERVALS AND/ORREPLACEMENT PERIODS ARE AS FOLLOWS:
WASHING…………………2 WEEKS – 1 YEAR
GREASING………………..1 TO 2 YEARS
INSILCOTE………………….10 TO 15 YEARS
Relative costs for 10 Years : Cleaning & Greasing – INR 6.9 Crores.
Silicone Rubber coating – INR 1.1 Crores. Features of Insilcote:
• 1 Kg covers 2.35 Sq.Meter Area of insulator
• Thickness of coating is 0.3 to 0.5 mm
• Application Procedure :
1. Cleaning, Drying
2. Application of Primer by Spray Gun
3. Application of Insilcote HV2000 by Spray gun
4. After application can charge the Insulator.
Price per Kg is Rs. 6000/- , Taxes & Application Charges are Extra.
Price per Sq. Meter Area of Insulator : Rs. 2550/-
Our INSILCOTE HV 2000 IS TESTED AT
CENTRAL POWER RESEARCH INSTITUTE, BANGALORE
ELECTRICAL RESEARCH & DEVELOPMENT ASSOCIATION, VADODARA
1. Inclined Plane Tracking & Erosion Test as per IEC-60587
2. Hydrophobicity Recovery Test as per REC Spec. No. 76/2006
3. Inclined Plane Tracking & Erosion Test as per ASTMD 2302-97
4. Arc Resistance as per ASTMD 495
Our Product is Sample Tested at
1. MSETCL, Kalwa
2. ADANI Power, Mundra
3. Neyveli Lignite Corp. Ltd.
4. ESSAR Steel, Hazira
Comparative Parameters of Porcelain Insulators before and after Application of Insilcote :
Before Application After Application
1. Volume Resistivity (Ohm Cm) 1011 2.3 x 1013
2. Surface Resistivity (Ohm) 109 1.5 x 1013
3. Puncture Value (KV/mm) 30 64
TECHNICAL CHARACTERISTICS of “ INSILCOTE HV2000 ”
As Supplied – •Appearance after mixing : Light blue•Liquid Specific Gravity at 25 degC : 1.33•Viscosity : 33.5 cSt•Thickness : 0.3 to 0.5 mm•Area Coverage per Kg : 2.35 Sq. Meters•Method of Application : By Spray Guns
As Cured –• Specific Gravity at 25 degC : 1.24 • Dielectric Strength : 64kV/mm• Permittivity : 2.4• Tracking & Erosion Resistance (IEC 60587 test ) : 1A4.5 • Hydrophobicity Recovery test As per REC Spec.76/2006 : HC1-HC2• Tracking Resistance at 2.5 KV ( ASTM D2303- 97 Test) : > 480 minutes• Dry Arc Resistance ( ASTM D 495 -99) : 187.2 sec• Surface Resistivity : 1.5 x 1013 ohms• Volume Resistivity : 2.29 x 1013 ohm-meters• Loss Tangent at 50Hz : 0.0096• Dielectric Constant : 2.99• Dissipation factor : 0.010• Flammability under dry arcing. : No visible flame • Drying Time Skin over Time : 15 Minutes Cure through : 7 Hour
Customer List
1. Nuclear Power Corporation Ltd, Tarapore
2. MSETCL, Pune
3. Oil & Natural Gas Corporation Ltd, Uran
4. Delhi Metro Rail Corporation, New Delhi
5. UltraTech Cement, Raipur
6. JSW Energy Ltd, Ratnagiri
7. Indian Railways, Secunderabad
8. Mitsubhisi
Thanks All of You
Presentation at MSETCL, Head Office Meeting at Kolhapur on 23.9.2008
Presentation at GETCO, Head Office, Vadodara.
Thanks All of You