description

Innerduct Seal-Off

Transcript of Innerduct Seal-Off

Page 1: Innerduct  Seal-Off

Comstar supply, INCThink Cable... Think Comstar1-866-326-6782

5 Blue Heron Drive Collegeville, PA 19426 (610) 831-5020 Fax: (610) 831-5012www.comstarsupply.com

5 Blue Heron DriveCollegeville, PA 19426Phone: 610-831-5020

Fax: 610-831-5012www.comstarsupply.com

Innerduct Seal-OffUSER GUIDE USER GUIDE USER GUIDE

®

CONDUX

© Copyright 1996, Condux International, Inc.Printed in USA

Literature Part Number: 08034314Revision Number: 1.2

Limited WarrantyCondux International, Inc. extends the following warranty to the original pur-chaser of these goods for use, subject to the qualifications indicated:

Condux International, Incorporated warrants to the original purchaser for usethat the goods or any component thereof manufactured by ConduxInternational will be free from defects in workmanship for a period of one yearfrom the date of purchase, provided such goods are installed, maintained, andused in accordance with Condux’s written instructions.

Components not manufactured by Condux International but used within theassembly provided by Condux International are subject to the warranty periodas specified by the individual manufacturer of said component, provided suchgoods are installed, maintained, and used in accordance with Condux’s andthe original manufacturer’s written instructions.

Condux’s sole liability and the purchaser’s sole remedy for a failure of goodsunder this limited warranty, and for any and all claims arising out of the pur-chase and use of the goods, shall be limited to the repair or replacement ofthe goods that do not conform to this warranty.

To obtain repair or replacement service under the limited warranty, the pur-chaser must contact the factory for a Return Material Authorization (RMA).Once obtained, send the RMA along with the defective part or goods, trans-portation prepaid, to:

Condux International, Inc.145 Kingswood RoadMankato, MN 56001

THERE ARE NO EXPRESS WARRANTIES COVERING THESE GOODSOTHER THAN AS SET FORTH ABOVE. THE IMPLIED WARRANTIES ORMERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARELIMITED IN DURATION TO ONE YEAR FROM DATE OF PURCHASE.

CONDUX ASSUMES NO LIABILITY IN CONNECTIONWITH THE INSTALLATION OR USE OF THIS PROD-UCT, EXCEPT AS STATED IN THIS LIMITED WAR-RANTY. CONDUX WILL IN NO EVENT BE LIABLEFOR INCIDENTAL OR CONSEQUENTIAL DAMAGES.

CONDUXCondux International, Inc. • P.O. Box 247 • 145 Kingswood Road • Mankato, MN 56001507-387-6576 • 800-533-2077 • FAX 507-387-1442Internet: http://www.condux.com

®

Page 2: Innerduct  Seal-Off

Comstar supply, INCThink Cable... Think Comstar1-866-326-6782

5 Blue Heron Drive Collegeville, PA 19426 (610) 831-5020 Fax: (610) 831-5012www.comstarsupply.com

5 Blue Heron DriveCollegeville, PA 19426Phone: 610-831-5020

Fax: 610-831-5012www.comstarsupply.com

1. Based upon the duct’s inner diameter, determine the correct seal-off head size (Table 1).

2. Screw the seal-off head onto the seal-off body and tighten until snug (Figure 1).

Set-Up Procedure

!WARNING: Read and understand all procedureand safety instructions before using any ConduxInnerduct Seal-Off. Failure to do so may result inpersonal injury or property damage. Save thisuser’s guide for future reference.

!WARNING: Do not exceed 15 psi of air pressure.Do not stand directly behind the Seal-Off. Seriouspersonal injury could result.

!CAUTION: Wear personal protective equipment:hard hat, safety glasses, safety shoes, and leatherwork gloves.

!WARNING: Keep the compressed air hose couplings clean of debris. Compressed air blowssurrounding debris during the installation andremoval of the air line. Serious personal injurycould result.

!CAUTION: Beware of sharp threads on the seal-offhead - wear leather work gloves when handling orpersonal injury could result.

Operating Procedure

PartNumber Description

Duct Size(in) (mm)

Duct ID Range(in) (mm)

08034300 Complete Kit

08034301 Seal-Off Body

08034310 Seal-Off Body 1 25 .93-1.19 24-30

08034311 Seal-Off Body 1 1/4 32 1.18-1.44 30-37

08034312 Seal-Off Body 1 1/2 38 1.31-1.69 33-43

08034313 Seal-Off Body 2 51 1.93-2.31 49-59

NOTE: The seal-off body comes standard with a rope adapter for 1⁄4” diameter rope.Additional adapters are available for 3⁄16”-1⁄2” diameter ropes. Consult your Condux cata-log, or see your Condux representative for more information.

1. Insert the rope or line through the rope adapter and seal-off head. Tie the rope orline to the projectile or missile.

2. Place the projectile or missile into the duct. Insert the seal-off head into the duct.

3. Twist the seal-off head and body clockwise until the head seats tightly inside theduct. Position the hose coupling for easy access.

4. Close the air flow valve by turning it until it is perpendicular to the coupling.

5. Attach the compressed air line to the seal-off’s air hose coupling. Ensure the airpressure is not over 15 psi.

6. Slowly open the seal-off’s air flow valve until the rope or line begins to feed throughthe duct. This valve also regulates the projectile or missile’s speed.

1. Close the air flow valve on the seal-off, and disconnect the compressed air line.

2. Loosen the seal-off by twisting it counterclockwise, and pull it out of the duct.

!ADVERTENCIA: Favor de leer y comprender todaslas instrucciones de operación y seguridad antesde usar el Condux Innerduct Seal-Off. Si Ud. nocomprende las instrucciones favor de consultarle asu jefe.

ADVERTENCIA

Instruccionesde Operación

Removal Procedure

Table 1: Compatibility Chart

Figure 1: Condux Innerduct Seal-Off

Rope Adapter

Seal-Off Body

Seal-Off Head

Innerduct

Air Hose Coupling

Air FlowValve