INERT AIR SYSTEMS

14

Transcript of INERT AIR SYSTEMS

Page 1: INERT AIR SYSTEMS
Page 2: INERT AIR SYSTEMS

INERT AIR SYSTEMS

NOTE:- 1/2" CABINET MOUNTING HARDWARE NOT SUPPLIED WITH UNIT.- NEMA 4X RATING PRIOR TO MODIFICATION FOR THE N2 SYSTEM COMPONENTS- CONVENIENCE PACKAGE INCLUDES CABINET LIGHT AND GFI OUTLET.

N2-0- STANDARD PANEL ENCLOSURE- REGULATOR ENCLOSURE- 60" HIGH PRESSURE STAINLESS STEEL FLEX HOSE- 60W PTC HEATER INCLUDED- N2-OE-CONVENIENCE PACKAGE MODEL

REGULATOR PANEL(CLICK HERE)

- N2-1E-CONVENIENCE PACKAGE MODEL - 200W PTC HEATER INCLUDED

STEEL FLEX HOSE - 48" HIGH PRESSURE STAINLESS

- HOLDS 1 NITROGEN CYLINDER - SINGLE CYLINDER ENCLOSURE

N2-1

Page 3: INERT AIR SYSTEMS

- N2-2E - CONVENIENCE PACKAGE MODEL - 200W PTC HEATER INCLUDED

FLEX HOSE - 48" HIGH PRESSURE STAINLESS STEEL

- HOLDS 2 NITROGEN CYLINDERS - DUAL CYLINDER ENCLOSURE

N2-2

REGULATOR PANEL (CLICK HERE)

INERT AIR SYSTEMS

NOTE:- 1/2" CABINET MOUNTING HARDWARE NOT SUPPLIED WITH UNIT.- NEMA 4X RATING PRIOR TO MODIFICATION FOR THE N2 SYSTEM COMPONENTS- CONVENIENCE PACKAGE INCLUDES CABINET LIGHT AND GFI OUTLET.

Page 4: INERT AIR SYSTEMS

11.52

27.24

14.02

28.48

12.84

11.50

25.98

.56TYP

N2-0-SYSTEM

FLEX HOSE 60" SST BRASS TIP

OUTLET

BREATHER PLUG

INLET

BREATHER PLUG

Page 5: INERT AIR SYSTEMS

N2-0-SYSTEM

12

BLIZ

ZAR

D 6

0W

PTC

HEA

TER

WIRING DIAGRAM

LOW

PR

ESS

HIG

H P

RES

S

NC C NO0.2PSI

5.5PSI

RED

WH

BLK

NCCNO

RED

BLK

BLU

PG1

PS1

2

21

1

BLK

BLKAL

ARM

EN

ABLE

SW

ITC

H

REGULATOR PANEL ASSEMBLY

NOLO C NO

HINO C NC + - + - L1 N 120 N G

TRANS. TANK ALARMS

NITROGEN.STORAGEALARM

TRANS TANK STORAGE TANK

HEATER SUPPLY POWER

(VAC)(4-20mA) (4-20mA)

CABINETGROUNDSTUD.

DOORGROUND STUD

SW# 1

SW# 2

NOTES:1. ALL CONTACTS IN THE DIAGRAM ARE SHOWN WITH THE SYSTEM DE-ENERGIZED AT ATMOSPHERIC PRESSURE. SW# 12. CONTACT RED-WHT : FACTORY SET TO CLOSE AT A PRESSURE OF 0.2 PSIG OR BELOW, SENDING AN ALARM, IF MONITORED. CONTACT BLK-WHT : FACTORY SET TO CLOSE AT A PRESSURE OF 5.5 PSIG OR ABOVE, SENDING AN ALARM, IF MONITORED. SW# 2 CONTACT BLU-BLK : N.C., OPENS AT 200.0 PSIG CONTACT RED-BLK : N.O., CLOSES AT 200.0 PSIG

BLIZZARD 60W PTC HEATER

REGULATOR PANEL

RUST INHIBITOR CAPSULE

FLEX HOSE 60", SST BRASS TIP

Page 6: INERT AIR SYSTEMS

16.00

22.21

13.21

61.2565.18

14.32

.56TYP

N2-1-SYSTEM

OUTLETINLET

Page 7: INERT AIR SYSTEMS

NOTES:1. ALL CONTACTS IN THE DIAGRAM ARE SHOWN WITH THE SYSTEM DE-ENERGIZED AT ATMOSPHERIC PRESSURE. SW# 12. CONTACT RED-WHT : FACTORY SET TO CLOSE AT A PRESSURE OF 0.2 PSIG OR BELOW, SENDING AN ALARM, IF MONITORED. CONTACT BLK-WHT : FACTORY SET TO CLOSE AT A PRESSURE OF 5.5 PSIG OR ABOVE, SENDING AN ALARM, IF MONITORED. SW# 2 CONTACT BLU-BLK : N.C., OPENS AT 200.0 PSIG CONTACT RED-BLK : N.O., CLOSES AT 200.0 PSIG

WIRING DIAGRAMREGULATOR PANEL ASSEMBLY

WH

T

BLK

PTC2HEATER 200 W/120 VAC

LOW

PR

ESS

HIG

H P

RES

S

NC C NO0.2PSI

5.5PSI

RED

WH

BLK

NCCNO

RED

BLK

BLU

PG1

PS1

2

21

1

BLK

BLK

NOLO C NO

HINO C NC + - + - L1 N 120 N G

TRANS. TANK ALARMS

NITROGEN.STORAGEALARM

TRANS TANK STORAGE TANK

HEATER SUPPLY POWER

(VAC)(4-20mA) (4-20mA)

ALAR

M E

NAB

LE S

WIT

CH

CABINETGROUNDSTUD.

DOORGROUND STUD

SW# 1

SW# 2

N2-1-SYSTEM

HEATER 200 W/120 VAC

FLEX HOSE, 48" SST

REGULATOR PANEL

BREATHER FILTER

RUST INHIBITOR CAPSULE

Page 8: INERT AIR SYSTEMS

24.00

30.21

73.25

13.21

15.32

77.16

74.50

.56TYP

N2-2-SYSTEM

Page 9: INERT AIR SYSTEMS

WIRING DIAGRAM

REGULATOR PANEL ASSEMBLY

WH

T

BLK

PTC2HEATER 200 W/120 VAC

LOW

PR

ESS

HIG

H P

RES

S

NC C NO0.2PSI

5.5PSI

RED

WH

BLK

NCCNO

RED

BLK

BLU

PG1

PS1

2

21

1

BLK

BLK

NOLO C NO

HINO C NC + - + - L1 N 120 N G

TRANS. TANK ALARMS

NITROGEN.STORAGEALARM

TRANS TANK STORAGE TANK

HEATER SUPPLY POWER

(VAC)(4-20mA) (4-20mA)

ALAR

M E

NAB

LE S

WIT

CH

CABINETGROUNDSTUD

DOORGROUND STUD

SW# 1

SW# 2

NOTES:1. ALL CONTACTS IN THE DIAGRAM ARE SHOWN WITH THE SYSTEM DE-ENERGIZED AT ATMOSPHERIC PRESSURE. SW# 12. CONTACT RED-WHT : FACTORY SET TO CLOSE AT A PRESSURE OF 0.2 PSIG OR BELOW, SENDING AN ALARM, IF MONITORED. CONTACT BLK-WHT : FACTORY SET TO CLOSE AT A PRESSURE OF 5.5 PSIG OR ABOVE, SENDING AN ALARM, IF MONITORED. SW# 2 CONTACT BLU-BLK : N.C., OPENS AT 200.0 PSIG CONTACT RED-BLK : N.O., CLOSES AT 200.0 PSIG

N2-2-SYSTEM

RUST INHIBITOR CAPSULE

HEATER 200W/120VAC

FLEX HOSE, 48" SST

REGULATOR PANEL

BREATHER FILTER

Page 10: INERT AIR SYSTEMS

N2-AABB N2-REGULATOR REPLACEMENT PANEL

REGULATOR PANEL

N2-PWAUKESHA N2-REGULATOR REPLACEMENT PANELR

Page 11: INERT AIR SYSTEMS

8.50

21.6923.18

10.00

4X .313

NOTES:1. ALL WIRES SIZE 12 AWG, UNLESS OTHERWISE SPECIFIED; USE AS REQUIRED. 2. 15 RING TERMINALS REQUIRED; RING TERMINALS INCLUDED AND BAGGED SEPARATELY. 3. PULL VENT PLUG UP TO ALLOW FOR ALTITUDE EQUALIZATION. ONCE NITROGEN GAS CIRCULATES THROUGH THE SYSTEM, PUSH DOWN TO CLOSE VENT PLUG. 4. WHEN PANEL IS SOLD SEPARATELY, ORDER PART NUMBER 1030-1733K FOR CONNECTION COMPONENTS.

SHEET 1 OF 2

Page 12: INERT AIR SYSTEMS

WIRING DIAGRAM

NOLO C NO

HI NO C NC + - + - L1 N 120 N G

TRANS. TANK ALARMS

NITROGEN STORAGEALARM

TRANS. TANK STOR. TANK HEATER SUPPLY POWER

(VAC)(4-20mA) (4-20mA)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

LOW PRESS

HIGH PRESS

NOCNC5.5PSI

5.5PSI

RED GR

BLK

NCCNO

RED

BLK

BLU

PG1

PS1

2

21

1

BLK

BLK

NO

CN

C

5

6

4

2

1

3

.25PSI

.25PSI

GR

ALAR

M E

NAB

LE S

WIT

CH

SW# 1

SW# 2

SW# 3

NOTES:1. ALL CONTACTS IN THE DIAGRAM ARE SHOWN WITH THE SYSTEM DE-ENERGIZED AT ATMOSPHERIC PRESSURE. SW# 1CONTACT 1-2 : CLOSES AT 0.25 PSIG & ABOVE.CONTACT 1-3 : CLOSES AT A PRESSURE OF 0.25 PSIG OR BELOW, SENDING AN ALARM, IF MONITORED. SW# 2CONTACT 6-4 : CLOSES AT 5.5 PSIG & BELOW.CONTACT 6-5 : CLOSES AT A PRESSURE OF 5.5 PSIG OR ABOVE, SENDING AN ALARM, IF MONITORED. SW# 3CONTACT BLU-BLK : N.C., OPENS AT 200.0 PSIGCONTACT RED-BLK : N.O., CLOSES AT 200.0 PSIG

12

BLIZ

ZAR

D 6

0W

PTC

HEA

TER

SHEET 2 OF 2

Page 13: INERT AIR SYSTEMS

16.00

11.00

13.00

5.50

18.00

3X .375

NOTES:1. ALL WIRES SIZE 12 AWG, UNLESS OTHERWISE SPECIFIED; USE AS REQUIRED.2. 15 RING TERMINALS REQUIRED; RING TERMINALS INCLUDED AND BAGGED SEPARATELY.3. PULL VENT PLUG UP TO ALLOW FOR ALTITUDE EQUALIZATION. ONCE NITROGEN GAS CIRCULATES THROUGH THE SYSTEM, PUSH DOWN TO CLOSE VENT PLUG.4. REGULATOR SET TO CONTROL PRESSURE AT 0.5 PSI.

SHEET 1 OF 2

Page 14: INERT AIR SYSTEMS

WIRING DIAGRAM

NCCNOR

ED

BLK

BLU

PSI

2

21

1

BLK

BLK

NOLO

CN

OHI

NO

CN

C+

-+

-L1

N120

NG

TRAN

S. TANK

ALARM

SN

ITRO

GEN

.STOR

AGE

ALARM

TRAN

S TANK

STOR

-TANK

H

EATERSU

PPLY POW

ER(VAC

)(4-20m

A)(4-20m

A)

12

34

56

78

910

1112

1314

15

WH

T

BLK

NATURALCONVECTION60W PTCHEATER

SW# 3

LOW PRESS

HIGH PRESS

NOCNC8.5PSI

8.5PSI

PG1

NO

CN

C

564

2

1

3

.25PSI.25PSI

SW# 1

SW# 2

WHT

BLK

RED

WHT

NOTES:1. ALL CONTACTS IN THE DIAGRAM ARE SHOWN WITH THE SYSTEM DE-ENERGIZED AT ATMOSPHERIC PRESSURE.SW# 1CONTACT 1-2 : CLOSES AT 0.25 PSIG & ABOVE.CONTACT 1-3 : CLOSES AT A PRESSURE OF 0.25 PSIG OR BELOW, SENDING AN ALARM, IF MONITORED.SW# 2CONTACT 6-4 : CLOSES AT 8.5 PSIG & BELOW.CONTACT 6-5 : CLOSES AT A PRESSURE OF 8.5 PSIG OR ABOVE, SENDING AN ALARM, IF MONITORED.SW# 3CONTACT BLU-BLK : N.C., OPENS AT 200.0 PSIGCONTACT RED-BLK : N.O., CLOSES AT 200.0 PSIG

ALAR

M E

NAB

LE S

WIT

CH

CO

NN

ECTO

RSHEET 2 OF 2