PRODUCT NAME INERGEN® Fire Suppression System ENVIRONMENTAL IMPACT INERGEN agent is a mixture of three naturally occurring gases: nitrogen, argon, and carbon dioxide. As INERGEN agent is derived from gases present in the earth’s atmosphere, it exhibits no ozone depleting potential, does not contribute to global warming, nor does it contribute unique chemical species with extended atmospheric lifetimes. Because INERGEN agent is composed of atmospheric gases, it does not pose the problems of toxicity associated with the chemically derived Halon alternative agents. PRODUCT DESCRIPTION The INERGEN Fire Suppression System, manufactured by Ansul, is an engineered system utilizing a fixed nozzle agent distribu- tion network. The system is designed and installed in accordance with the National Fire Protection Association (NFPA) Standard 2001, ‘‘Clean Agent Fire Extinguishing Systems.’’ When properly designed, the INERGEN system will extinguish surface burning fire in Class A, B, and C hazards by lowering the oxygen content below the level that supports combustion. INERGEN agent has also been tested by FMRC for inerting capabilities. Those tests have shown that INERGEN agent, at design concentrations between 40% and 50%, has successfully inerted mixtures of propane/air, and methane/air. The system can be actuated by detection and control equipment for automatic system operation along with providing local and remote manual operation as needed. Accessories are used to provide alarms, ventilation control, door closures, or other auxiliary shutdown or functions. When INERGEN agent is discharged into a room, it introduces the proper mixture of gases that will allow a person to breathe in a reduced oxygen atmosphere. A system installation and maintenance manual is available containing information on system components and procedures concerning design, operation, inspection, maintenance, and recharge. The system is installed and serviced by authorized distributors that are trained by the manufacturer. Basic Use – The INERGEN system is partic- ularly useful for suppressing fires in hazards where an electrically non-conductive medium is essential or desirable; where clean-up of other agents present a problem; or where the INERGEN® FIRE SUPPRESSION SYSTEMS DATA SHEET hazard is normally occupied and requires a non-toxic agent. The following are typical hazards protected by INERGEN systems: Computer rooms • Subfloors Tape storage • Telecommunication/Switchgear • Vaults Process equipment All normally occupied or unoccupied elec- tronic areas where equipment is either very sensitive or irreplaceable Composition and Materials – The basic system consists of extinguishing agent stored in high strength alloy steel cylinders. Various types of actuators, either manual or auto- matic, are available for release of the agent into the hazard area. The agent is distributed and discharged into the hazard area through a network of piping and nozzles. Each nozzle is drilled with a fixed orifice designed to deliver a uniform discharge to the protected area. On large hazards, where three or more cylinders are required, a screwed or welded pipe manifold assembly is employed. The cylinder(s) is connected to the distribution piping or the manifold by means of a flexible discharge bend and check valve assembly. Additional equipment includes – Control panels, releasing devices, remote manual pull stations, corner pulleys, door closures, pressure trips, bells and alarms, and pneu- matic switches. All or some are required when designing a total system. INERGEN Agent – INERGEN agent is a mixture of three inerting (oxygen diluting) gases: 52% nitrogen, 40% argon, and 8% carbon dioxide. INERGEN gas extinguishes fire by lowering the oxygen content below the level that supports combustion. When INERGEN agent is discharged into a room, it introduces the proper mixture of gases that still allow a person to breathe in a reduced oxygen atmosphere. It actually enhances the body’s ability to assimilate oxygen. The normal atmosphere in a room contains 21% oxygen and less than 1% carbon dioxide. If the oxygen content is reduced below 15%, most ordinary combustibles will cease to burn. INERGEN agent will reduce the oxygen content to approximately 12.5% while increasing the carbon dioxide content to about 3%. The increase in the carbon dioxide content increases a person’s respiration rate and the body’s ability to absorb oxygen. Simply stated, the human body is stimulated by the carbon dioxide to breathe more deeply and rapidly to compensate for the lower oxygen content of the atmosphere. Cylinders – The cylinders are constructed, tested, and marked in accordance with applicable Dept. of Transportation (DOT) and the U.S. Bureau of Explosives specifica- tions. As a minimum, the cylinders must meet the requirements of DOT 3AA2300 or 3AA2015+. Cylinder Assembly – The cylinder assembly is of steel construction with a red standard finish. Four sizes are available to meet specific needs. Each is equipped with a pressure seat-type valve equipped with gauge. The valve is constructed of forged brass and is attached to the cylinder providing a leak tight seal. The valve also includes a safety pressure relief device which provides relief at 2900-3300 psi (20685-23167 kPA) per CGA test method. Cylinder charging pressure is 2175 psi at 70 °F (14997 kPA at 21 °C). The cylinders are shipped with a maintenance record card and shipping cap attached. The cap is attached to the threaded collar on the neck of each cylinder to protect the valve while in transit. The cylinder serial number and date of manufacture are stamped near the neck of each cylinder. Electric Actuator – Electric actuation of an agent cylinder is accomplished by an electric actuator interfaced through an AUTOPULSE® Control System. This actuator can be used in hazardous environments where the ambient temperature range is between 32 °F and 130 °F (0 °C and 54 °C). In auxiliary or override applications, a manual lever actuator can be installed on top of the actuator. Manual or Pneumatic Actuators – Three types of manual/pneumatic actuators are available for lever actuation on the cylinder valve. Manual actuation is accomplished by pulling the hand lever on the actuator. Detection System – The AUTOPULSE Control System is used where an automatic electronic control system is required to actuate the INERGEN system. This control system is used to control a single fixed fire suppression or alarm system based on inputs received from fire detection devices. The detection circuits can be configured using cross, counting, independent or priori- ty-zone (counting) concepts. The control system has been tested to the applicable FCC Rules and Regulations for Class A Computing devices. ANSUL ® SYSTEM SPECIFICATIONS

description

32

Transcript of Inergen 150 Bar System Specification

  • PRODUCT NAMEINERGEN Fire Suppression System

    ENVIRONMENTAL IMPACTINERGEN agent is a mixture of threenaturally occurring gases: nitrogen, argon,and carbon dioxide. As INERGEN agent isderived from gases present in the earthsatmosphere, it exhibits no ozone depletingpotential, does not contribute to globalwarming, nor does it contribute uniquechemical species with extended atmosphericlifetimes. Because INERGEN agent iscomposed of atmospheric gases, it does notpose the problems of toxicity associated withthe chemically derived Halon alternativeagents.

    PRODUCT DESCRIPTIONThe INERGEN Fire Suppression System,manufactured by Ansul, is an engineeredsystem utilizing a fixed nozzle agent distribu-tion network. The system is designed andinstalled in accordance with the National FireProtection Association (NFPA) Standard2001, Clean Agent Fire ExtinguishingSystems. When properly designed, theINERGEN system will extinguish surfaceburning fire in Class A, B, and C hazards bylowering the oxygen content below the levelthat supports combustion.INERGEN agent has also been tested byFMRC for inerting capabilities. Those testshave shown that INERGEN agent, at designconcentrations between 40% and 50%, hassuccessfully inerted mixtures of propane/air,and methane/air.The system can be actuated by detectionand control equipment for automatic systemoperation along with providing local andremote manual operation as needed.Accessories are used to provide alarms,ventilation control, door closures, or otherauxiliary shutdown or functions.When INERGEN agent is discharged into aroom, it introduces the proper mixture ofgases that will allow a person to breathe in areduced oxygen atmosphere.A system installation and maintenancemanual is available containing information onsystem components and proceduresconcerning design, operation, inspection,maintenance, and recharge.The system is installed and serviced byauthorized distributors that are trained by themanufacturer.Basic Use The INERGEN system is partic-ularly useful for suppressing fires in hazardswhere an electrically non-conductive mediumis essential or desirable; where clean-up ofother agents present a problem; or where the

    INERGEN FIRESUPPRESSIONSYSTEMSDATA SHEET

    hazard is normally occupied and requires anon-toxic agent.The following are typical hazards protectedby INERGEN systems: Computer rooms Subfloors Tape storage Telecommunication/Switchgear Vaults Process equipment All normally occupied or unoccupied elec-

    tronic areas where equipment is either verysensitive or irreplaceable

    Composition and Materials The basicsystem consists of extinguishing agent storedin high strength alloy steel cylinders. Varioustypes of actuators, either manual or auto-matic, are available for release of the agentinto the hazard area. The agent is distributedand discharged into the hazard area througha network of piping and nozzles. Each nozzleis drilled with a fixed orifice designed todeliver a uniform discharge to the protectedarea. On large hazards, where three or morecylinders are required, a screwed or weldedpipe manifold assembly is employed. Thecylinder(s) is connected to the distributionpiping or the manifold by means of a flexibledischarge bend and check valve assembly.Additional equipment includes Controlpanels, releasing devices, remote manualpull stations, corner pulleys, door closures,pressure trips, bells and alarms, and pneu-matic switches. All or some are requiredwhen designing a total system.INERGEN Agent INERGEN agent is amixture of three inerting (oxygen diluting)gases: 52% nitrogen, 40% argon, and 8%carbon dioxide. INERGEN gas extinguishesfire by lowering the oxygen content below thelevel that supports combustion. WhenINERGEN agent is discharged into a room, itintroduces the proper mixture of gases thatstill allow a person to breathe in a reducedoxygen atmosphere. It actually enhances thebodys ability to assimilate oxygen. Thenormal atmosphere in a room contains 21%oxygen and less than 1% carbon dioxide. Ifthe oxygen content is reduced below 15%,most ordinary combustibles will cease toburn. INERGEN agent will reduce the oxygencontent to approximately 12.5% whileincreasing the carbon dioxide content toabout 3%. The increase in the carbon dioxidecontent increases a persons respiration rateand the bodys ability to absorb oxygen.Simply stated, the human body is stimulatedby the carbon dioxide to breathe more deeplyand rapidly to compensate for the loweroxygen content of the atmosphere.

    Cylinders The cylinders are constructed,tested, and marked in accordance withapplicable Dept. of Transportation (DOT)and the U.S. Bureau of Explosives specifica-tions. As a minimum, the cylinders mustmeet the requirements of DOT 3AA2300or 3AA2015+.Cylinder Assembly The cylinder assemblyis of steel construction with a red standardfinish. Four sizes are available to meetspecific needs. Each is equipped with apressure seat-type valve equipped withgauge. The valve is constructed of forgedbrass and is attached to the cylinderproviding a leak tight seal. The valve alsoincludes a safety pressure relief devicewhich provides relief at 2900-3300 psi(20685-23167 kPA) per CGA test method.Cylinder charging pressure is 2175 psi at70 F (14997 kPA at 21 C). The cylindersare shipped with a maintenance record cardand shipping cap attached. The cap isattached to the threaded collar on the neckof each cylinder to protect the valve while intransit. The cylinder serial number and dateof manufacture are stamped near the neck ofeach cylinder.Electric Actuator Electric actuation of anagent cylinder is accomplished by anelectric actuator interfaced through anAUTOPULSE Control System. This actuatorcan be used in hazardous environmentswhere the ambient temperature range isbetween 32 F and 130 F (0 C and 54 C).In auxiliary or override applications, a manuallever actuator can be installed on top of theactuator.Manual or Pneumatic Actuators Threetypes of manual/pneumatic actuators areavailable for lever actuation on the cylindervalve. Manual actuation is accomplished bypulling the hand lever on the actuator.Detection System The AUTOPULSEControl System is used where an automaticelectronic control system is required toactuate the INERGEN system. This controlsystem is used to control a single fixed firesuppression or alarm system based oninputs received from fire detection devices.The detection circuits can be configuredusing cross, counting, independent or priori-ty-zone (counting) concepts. The controlsystem has been tested to the applicableFCC Rules and Regulations for Class AComputing devices.

    ANSUL SYSTEMSPECIFICATIONS

  • Nozzles Nozzles are designed to direct thedischarge of INERGEN agent using thestored pressure from the cylinders. Ten sizesof nozzles are available. The system designspecifies the nozzle and orifice size to beused for proper flow rate and distribution pat-tern. The nozzle selection depends on thehazard and location to be protected.Pressure Reducer The pressure reduceris required in the distribution piping to restrictthe flow of INERGEN agent, thus reducingthe agent pressure down stream of thereducer. The pressure reducer contains astainless steel orifice plate which is drilled tothe specific size hole required based on thehydraulic calculation. The orifice plate pro-vides readily visible orifice identification. Thepressure reducer is available in nine sizes:1/2 in., 3/4 in., 1 in., 1 1/4 in., 1 1/2 in., 2 in.,2 1/2 in., 3 in., and 4 in. NPT.Pipe and Fittings The system manifoldmust be constructed of Schedule 80 or 160piping and class 2000 or 3000 lb. iron fit-tings, threaded or welded. The distributionpiping down stream from the orifice unionmust be constructed of a minimum ofSchedule 40 piping with class 300 malleableiron threaded fittings or welded steel fittings.All piping must be black iron of the followingtype and grade: ASTM A-53 seamless orelectric resistance welded, grade A or B, orASTM A-106 grade A, B, or C. Do not useASTM A-120, ASTM A-53 type F or ordi-nary cast iron pipe or fittings.Limitations The INERGEN system mustbe designed and installed within the guide-lines of the manufacturers design, installa-tion, operation, inspection, recharge, andmaintenance manual. The ambient temper-ature limitations are 32 F to 130 F (0 Cto 54 C). All AUTOPULSE Control Systemsare designed for indoor applications and fortemperature ranges between 32 F and120 F (0 C and 49 C).TECHNICAL DATAApplicable Standards: The INERGENsystem complies with NFPA Standard 2001,Standard for Clean Agent Fire ExtinguishingSystems, and EPA Program SNAP,Significant New Alternate Policy.Agent is listed and approved by UnderwritersLaboratories, Inc. (UL) and Factory MutualResearch Corporation (FMRC).INSTALLATIONSAll system components and accessoriesmust be installed by personnel trained by themanufacturer. All installations must be per-formed according to the guidelines stated inthe manufacturers design, installation,operation, inspection, recharge, andmaintenance manual.

    AVAILABILITY AND COSTAvailability INERGEN Systems are soldand serviced through a network of indepen-dent distributors located in most states andmany foreign countries.Cost Cost varies with type of systemspecified, size, and design.

    PRODUCT WARRANTYWarranty The components of the fire sup-pression system supplied by Ansul Inc.(Ansul) are warranted to you as the originalpurchaser for one year from the date of deliv-ery against defects in workmanship andmaterial. Ansul will replace or repair anyAnsul supplied components, which, in itsopinion, are defective and have not beentampered with or subjected to misuse,abuse, or exposed to highly corrosive condi-tions provided that written notice of thealleged defect shall have been given toAnsul within 30 days after discovery thereofand prior to the expiration of one year afterdelivery, and further provided that if Ansul soinstructs, such article or part thereof ispromptly returned to Ansul with shippingcharges prepaid.Disclaimer of Warranty and Limitation ofDamage The warranty described above isthe only one given by Ansul concerning thissystem. ANSUL MAKES NO OTHERWARRANTIES OF ANY KIND, WHETHEREXPRESS OR IMPLIED, INCLUDING THEWARRANTIES OF MERCHANTABILITYAND FITNESS FOR PARTICULARPURPOSE. ANSULS MAXIMUM RESPON-SIBILITY FOR ANY CLAIMS WHETHER INCONTRACT, TORT, NEGLIGENCE,BREACH OF WARRANTY, OR STRICTLIABILITY SHALL BE LIMITED TO THEPURCHASE PRICE OF THE SYSTEM.UNDER NO CIRCUMSTANCES SHALLANSUL BE RESPONSIBLE FOR SPECIAL,CONSEQUENTIAL, OR INCIDENTALDAMAGES OF ANY KIND. Ansul does notassume or authorize any other person toassume for it any additional liability inconnection with the sale of this system.For repairs, parts, and service of the Ansulfire suppression system, contact a localAnsul representative, or Ansul Incorporated,Marinette, WI 54143-2542,800-TO-ANSUL (862-6785).FALSE DISCHARGE WARRANTYSubject to the conditions set forth below,Ansul will, as purchasers sole remedy,replace INERGEN gas and pay reasonablecosts to recharge the INERGEN/Detectionand Control System where, in Ansuls opin-ion, the discharge has occurred due to adefect in the material or workmanship of theproducts provided by Ansul. This warranty isextended only to the original purchaser of theINERGEN/Detection and Control System andonly for a period of one year from the date ofinstallation of the INERGEN/Detection andControl System.Ansul will only replace INERGEN gas andpay reasonable costs to recharge theINERGEN/Detection and Control Systemwhere the discharge occurs due to a defectin the material or workmanship of theproducts provided by Ansul. For example,Ansul will not be responsible for dischargesdue to faulty maintenance or installation orservice, intentional acts by the owner or thirdparties, or circumstances over which Ansulhas no control. Ansul will not be responsiblefor discharges of the INERGEN/Detectionand Control System which occur if theINERGEN/Detection and Control System,as initially installed, has been altered ormodified.

    This warranty shall be effective only if theoriginal purchaser maintains a semi-annualservice agreement for the INERGEN/Detection and Control System with anAuthorized Ansul Distributor from the date ofinstallation. This warranty covers only thoseINERGEN/Detection and Control Systemspurchased from Ansul or its AuthorizedDistributors and only those INERGEN/Detection and Control Systems which incor-porate and use only hardware and compo-nents, including detection and controldevices manufactured, sold, or approved byAnsul. This warranty may not be assigned ortransferred to others.Ansul Product Services Department must benotified within three days of the discharge ofthe INERGEN/Detection and Control Systemand must approve the cost of INERGEN gasand recharge service in advance.Except as provided above, ANSUL MAKESNO WARRANTIES OF ANY KIND,WHETHER EXPRESSED OR IMPLIED,INCLUDING THE WARRANTIES OFMERCHANTABILITY AND FITNESS FOR APARTICULAR PURPOSE, UNDER NOCIRCUMSTANCE SHALL ANSUL HAVEANY LIABILITY FOR CONSEQUENTIAL,INCIDENTAL, SPECIAL OR SIMILARDAMAGES. ANSUL SHALL HAVE NOLIABILITY FOR ANY DAMAGES DUE TODELAY IN RECHARGING THEINERGEN/DETECTION AND CONTROLSYSTEM. ANSULS MAXIMUM LIABILITYFOR DIRECT DAMAGES IS LIMITED TOTHE REPLACEMENT OF INERGEN GASAND REASONABLE COSTS TORECHARGE THE INERGEN/DETECTIONAND CONTROL SYSTEM.This warranty is not effective unless AnsulForm No. F-9346 is completed and returnedto Ansul within 10 days of the commissioningof the INERGEN/Detection and ControlSystem.

    MAINTENANCEMaintenance is a vital step in the perfor-mance of a fire suppression system. Assuch, it must be performed by an authorizedAnsul distributor in accordance with NFPA2001 and the manufacturers design, installa-tion, recharge, and maintenance manual.When replacing components on the Ansulsystem, use only Ansul approved parts.

    TECHNICAL SERVICESFor information on the proper design andinstallation, contact a local authorizedINERGEN System distributor. The Ansulapplications engineering department is alsoavailable to answer design and installationquestions. Call 800-TO-ANSUL (862-6785).

    ANSUL, AUTOPULSE and INERGEN are registeredtrademarks.