I&M Manual_WGZ-1

download I&M Manual_WGZ-1

of 72

Transcript of I&M Manual_WGZ-1

  • 7/24/2019 I&M Manual_WGZ-1

    1/72

    Installation, and Maintenance Manual IMM WGZC

    Group: Chiller

    Part Number: 331975201

    Effective: February 2010

    Supercedes: April 2009

    Water-Cooled Scroll Compressor Chillers

    WGZ 030CW to WGZ 200CW, Packaged Water-Cooled Chiller

    WGZ 030CA to WGZ 200CA, Chiller with Remote Condenser

    30 to 200 Tons, 105 to 700 kW

    60 Hz, R-410A

  • 7/24/2019 I&M Manual_WGZ-1

    2/72

    2 WGZ 030C through 200C IMM WGZC

    Table of Contents

    Introduction ....................................... 3Nomenclature ........................................ 3

    Installation ......................................... 4Vibration Isolators................................. 6

    Limitations of Operation ................ 11

    Water Piping .................................... 12Flow Switch ........................................ 15Glycol Solutions.................................. 15Condenser Water Piping...................... 17

    Pressure Drops................................. 17

    Refrigerant Piping........................... 20Unit with Remote Condenser .............. 20Factory-Mounted Condenser............... 25

    Dimensions ....................................... 26

    Packaged Chillers................................ 26Chillers with Remote Condenser......... 29

    Physical Data.................................... 32Packaged Chillers................................ 32Chillers with Remote Condenser......... 35Operating Limits ................................. 36Components ........................................ 37

    Wiring............................................... 38

    Unit Configuration .......................... 39

    Electrical Data ................................. 40

    Electrical Notes ................................... 53Field Wiring Diagram ......................... 55Control Panel Layout .......................... 57Motor Protection Module.................... 57

    Start-Up and Shutdown..................58Pre Start-up.......................................... 58Start-up................................................ 58Weekend or Temporary Shutdown...... 59Start-up after Temporary Shutdown.... 59Extended Shutdown ............................ 59Start-up after Extended Shutdown ...... 60

    System Maintenance .......................61General................................................ 61Electrical Terminals............................. 62Compressor Lubrication...................... 62Sightglass and Moisture Indicator....... 62Crankcase Heaters............................... 63Optional Controls................................ 63Phase/Voltage Monitor (Optional) ...... 63Hot Gas Bypass (Optional) ................. 64

    Maintenance Schedule....................65

    System Service.................................66Troubleshooting Chart ........................ 68

    Warranty Statement .......................69

    Manufactured in an ISO Certified facility

    Cover Picture: WGZ 200C, Nominal 200 ton chiller

    2009 McQuay International. Illustrations and data cover the McQuay International product at the time of publication and we reserve the right to

    make changes in design and construction at anytime without notice. The following are trademarks or registered trademarks of their respective

    companies: BACnet from ASHRAE; LONMARK, LonTalk, LONWORKS, and the LONMARK logo are managed, granted and used by LONMARK

    International under a license granted by Echelon Corporation; Compliant Scroll from Copeland Corporation; ElectroFin from AST ElectroFin Inc.;

    Modbus from Schneider Electric; FanTrol, MicroTech II, Open Choices, and SpeedTrol from McQuay International

  • 7/24/2019 I&M Manual_WGZ-1

    3/72

    IMM WGZC WGZ 030C through 200C 3

    Introduction

    General Description

    McQuay Type WGZ water chillers are designed for indoor installations and are available with

    water-cooled condensers (Model WGZ-CW), or arranged for use with remote, air-cooled or

    evaporative condensers (Model WGZ-CA). Each water-cooled unit is completely assembled andfactory wired before evacuation, charging and testing. They consist of hermetic scroll

    compressors, brazed-plate evaporators on Models WGZ 030 to 130( shell-and-tube on Models

    WGZ 150 to 200), water-cooled condenser (WGZ-CW), and complete refrigerant piping.

    Units manufactured for use with remote condensers (Models WGZ-CA) have all refrigerant

    specialties factory-mounted and connection points for refrigerant discharge and liquid lines.

    Liquid line components that are included are manual liquid line shutoff valves, charging valves,

    filter-driers, liquid line solenoid valves, sight glass/moisture indicators, and expansion valves.

    Other features include compressor crankcase heaters, and a MicroTech IImicroprocessor

    controller.

    The electrical control center includes all equipment protection and operating controls necessaryfor dependable automatic operation.

    The compressors are not fused as standard, but can be protected by optional circuit breakers or

    fuses, or can rely on a field-installed, fused disconnect switch for protection.

    Nomenclature

    W G Z 100 - C W

    Inspection

    When the equipment is received, all items should be carefully checked against the bill of lading to

    be sure of a complete shipment. All units must be carefully inspected for damage upon arrival. All

    shipping damage must be reported to the carrier and a claim must be filed with the carrier. The

    unit serial plate should be checked before unloading the unit to be sure that it agrees with the

    power supply available. Physical damage to unit after acceptance is not the responsibility of

    McQuay.

    Note: Unit lifting weights are given in the physical data tables beginning on page 5.Corner operating weights are given on page 7

    Water-Cooled

    Global

    Scroll Compressor Nominal Capacity (Tons)

    W = Water-Cooled Condenser

    A = Unit Less Condenser

    Design Vintage

  • 7/24/2019 I&M Manual_WGZ-1

    4/72

    4 WGZ 030C through 200C IMM WGZC

    Installation

    Note: Installation and maintenance are to be performed only by qualified personnelwho are familiar with local codes and regulations, and experienced with this type ofequipment.

    ! WARNING

    Avoid contact with sharp edges. Personal injury can result

    Handling

    Every model WGZ-CW water chiller with water-cooled condensers is shipped with a full

    refrigerant charge. For shipment, the charge is contained in the condenser and is isolated by

    the condenser liquid shutoff valve and the compressor discharge valve common to a pair of

    compressors.

    A holding charge of nitrogen/helium is supplied in remote condenser models, WGZ-CA and

    must be removed prior to charging with refrigerant. The operating charge must be field

    supplied and charged.

    Moving the Unit The packaged unit skid option is strongly recommended for ease ofhandling and to help prevent damage if a crane is not available for rigging at site.Properly

    designed field supplied skids or dollies are acceptable. Do not push unit along a floor without

    them. The condenserless models (AGZ-CA) are manufactured with a base suitable for movingwith rollers.

    Figure 1, Lifting the Unit

    ! WARNING

    If the unit has been damaged, allowing the refrigerant to escape, there can be danger of suffocation in the area since refrigerant will displace the air. Be sure to review Environmental Protection Agency (EPA) requirements if damage occu

    Avoid exposing an open flame to the refrigerant

    331926901 REV. 0A

    WGZ150-200CUNIT SHOWN

    SPREADER BARS MUSTBE USED FOR STABILITY

    DURING LIFTING OFALL SIZE UNITS

    RemovableLiftingBar

    (2) 2

    LiftingHoles

  • 7/24/2019 I&M Manual_WGZ-1

    5/72

    IMM WGZC WGZ 030C through 200C 5

    All moving and handling of packaged units (illustrated above) must be performed with skids

    or dollies under the unit and they should not be removed until the unit is in the final location.

    Never put the weight of the unit against the control box.

    All moving and handling of packaged units (illustrated above) must be performed with skids

    or dollies under the unit and they should not be removed until the unit is in the final location.

    Never put the weight of the unit against the control box.

    In moving, always apply pressure to the base on the skids only and not to the piping or othercomponents. A long bar will help move the unit easily. Avoid dropping the unit at the end of

    the roll.

    If the unit must be hoisted, lift the unit from the removable lifting arms factory-bolted to each

    end of the unit adjacent to the tube sheet by attaching cables or chains to the end of the arms.

    A spreader bar must be used to protect the piping, control panel and other areas of the chiller

    (see Figure 1). The arms should be removed and discarded after use.

    Do not attach slings to piping or equipment. Do notattempt to lift the unit by lifting points

    mounted on the compressors. They are for lifting only the compressor should one need to be

    removed from the unit. Move unit in the upright horizontal position at all times. Set unit

    down gently when lowering from the truck or rollers.

    Table 1, Lifting Loads

    WGZ-CW Package Units (lbs.) WGZ CA Less Condenser Units (lbs)ModelWGZ-C L1 L2 L3 L4

    ShippingWeight

    L1 L2 L3 L4ShippingWeight

    WGZ 030 606 633 599 573 2410 415 430 374 361 1580

    WGZ 035 632 646 616 603 2496 442 445 392 390 1670

    WGZ 040 639 659 630 611 2539 443 451 399 392 1685

    WGZ 045 639 667 639 612 2558 444 460 407 393 1704

    WGZ 050 655 689 664 631 2639 451 468 416 400 1735

    WGZ 055 655 698 673 632 2658 451 476 425 402 1754

    WGZ 060 655 712 688 633 2688 451 484 433 404 1771

    WGZ 070 929 874 942 1001 3746 649 595 556 606 2406

    WGZ 080 1066 927 1001 1151 4145 765 635 598 720 2717

    WGZ 090 1076 849 1059 1343 4327 806 653 623 770 2851

    WGZ 100 1059 781 1118 1515 4474 829 681 657 801 2968

    WGZ 115 1054 802 1146 1506 4508 830 710 689 805 3035

    WGZ 130 1055 828 1181 1505 4568 831 737 716 807 3091

    WGZ 150 1684 1516 1602 1780 6581 1204 1142 1184 1249 4779

    WGZ 175 1814 1528 1637 1943 6921 1245 1149 1198 1299 4891

    WGZ200 1829 1550 1677 1979 7036 1265 1178 1235 1326 5004

    See Figure 2on the following page for location of lifting points.

    Location

    WGZ chillers are designed for indoor application and must be located in an area where

    the surrounding ambient temperature is 40F (4C) or above. A good rule of thumb is toplace units where ambient temperatures are at least 5F (3C) above the leaving water

    temperature.

    Because of the electrical control devices, the units should not be exposed to the weather.

    A plastic cover over the control box is supplied as temporary protection during shipment.

    A reasonably level and sufficiently strong floor is required for the water chiller. If

    necessary, additional structural members should be provided to transfer the weight of the

    unit to the nearest beams.

  • 7/24/2019 I&M Manual_WGZ-1

    6/72

    6 WGZ 030C through 200C IMM WGZC

    Control Panel

    WaterConnections

    4

    1

    3

    2

    LB

    LF

    RB

    FRF

    Space Requirements for Connections and Servicing

    The chilled water and condenser water (on units with a water-cooled condenser) piping

    enters and leaves the unit from the right side when looking at the control panel. Left-hand

    condenser connections are an option. A clearance of at least 3 feet (1219 mm), or more if

    codes require, should be provided beyond this piping and on all other sides and ends of

    the unit for general servicing or for changing the compressors, if it ever becomes

    necessary.

    On units equipped with a water-cooled condenser (Type WGZ-CW) clearance should also

    be provided for cleaning or removal of condenser tubes on one end of the unit. The

    clearance for cleaning depends on the type of apparatus used, but can be as much as the

    length of the condenser (10 feet, 3050 mm). Tube replacement requires the tube length of

    10 feet (3050 mm) plus one to two feet of workspace. This space can often be provided

    through a doorway or other opening.

    Allow a minimum of 4-foot clearance in front of the control panel.

    Placing the UnitThe small amount of vibration normally encountered with the water chiller makes this

    unit particularly desirable for basement or ground floor installations where the unit can be

    mounted directly to the floor. The floor construction should be such that the unit will not

    affect the building structure, or transmit noise and vibration into the structure. NOTE:Springs are Model CP1E, one spring per housing.

    Vibration IsolatorsIt is recommended that isolators be used on all upper level installations or in areas where

    vibration transmission is a consideration.

    Figure 2, Isolator Locations

    Transfer the unit as indicated

    under Moving the Unit. In all

    cases, set the unit in place and

    level with a spirit level. When

    spring-type isolators are

    required, install springs runningunder the main unit supports.

    The unit should be set initially

    on shims or blocks at the listed

    spring free height. When all piping, wiring, flushing, charging, etc., is completed, the

    springs are adjusted upward to loosen the blocks or shims that are then removed.

    A rubber anti-skid pad should be used under isolators if hold-down bolts are not used.

    Installation of spring isolators requires flexible piping connections and at least three feet of

    flexible electrical conduit to avoid straining piping and transmitting vibration and noise.

  • 7/24/2019 I&M Manual_WGZ-1

    7/72

    IMM WGZC WGZ 030C through 200C 7

    Table 2, WGZ-CW Packaged, Mounting Weights & Vibration Mounting Location

    Unit Mounting Weights, Lbs (kg) Spring-Flex Mountings R-I-S Mountings

    Size M1 M2 M3 M4 M1 M2 M3 M4 M1 M2 M3 M4

    ID-900 ID-900 ID-900 ID-900 RP-3 RP-3 RP-3 RP-3030 625 653 618 591

    Green Green Green Green Gray Gray Gray Gray

    ID-900 ID-900 ID-900 ID-900 RP-3 RP-3 RP-3 RP-3035 651 665 635 621

    Green Green Green Green Gray Gray Gray Gray

    ID-900 ID-900 ID-900 ID-900 RP-3 RP-3 RP-3 RP-3040 662 683 653 633

    Green Green Green Green Gray Gray Gray Gray

    ID-900 ID-900 ID-900 ID-900 RP-3 RP-3 RP-3 RP-3045 662 691 662 634

    Green Green Green Green Gray Gray Gray Gray

    ID-900 ID-900 ID-900 ID-900 RP-3 RP-3 RP-3 RP-3050 683 718 692 659

    Green Green Green Green Gray Gray Gray Gray

    ID-900 ID-900 ID-900 ID-900 RP-3 RP-3 RP-3 RP-3055 683 727 702 659

    Green Green Green Green Gray Gray Gray Gray

    ID-900 ID-900 ID-900 ID-900 RP-3 RP-3 RP-3 RP-3060 682 742 717 660

    Green Green Green Green Gray Gray Gray Gray

    ID-1350 ID-1350 ID-1350 ID-1350 RP-4 RP-4 RP-4 RP-4070 964 907 978 1038Purple Purple Purple Purple Brown Brown Brown Brown

    ID-1350 ID-1350 ID-1350 ID-1350 RP-4 RP-4 RP-4 RP-4080 1106 962 1039 1195

    Purple Purple Purple Purple Brown Brown Brown Brown

    ID-1800 ID-1800 ID-1800 ID-1800 RP-4 RP-4 RP-4 RP-4090 1121 884 1103 1399

    Green Green Green Green Brown Brown Brown Brown

    ID-1800 ID-1800 ID-1800 ID-2400 RP-4 RP-4 RP-4 RP-4100 1108 817 1169 1585

    Green Green Green Gray Brick Red Brick Red Brick Red Brick Red

    ID-1800 ID-1800 ID-1800 ID-2400 RP-4 RP-4 RP-4 RP-4115 1102 839 1198 1574

    Green Green Green Gray Brick Red Brick Red Brick Red Brick Red

    ID-1800 ID-1800 ID-1800 ID-2400 RP-4 RP-4 RP-4 RP-4130 1102 865 1234 1572

    Green Green Green Gray Brick Red Brick Red Brick Red Brick Red

    ID-2400 ID-2400 ID-2400 ID-2400 RP-4 RP-4 RP-4 RP-4150 1886 1690 1794 1993

    Gray Gray Gray Gray Brick Red Brick Red Brick Red Brick Red

    ID-2400 ID-2400 ID-2400 ID-2400 RP-4 RP-4 RP-4 RP-4170 2033 1710 1835 2178

    Gray Gray Gray Gray Brick Red Brick Red Brick Red Brick Red

    ID-2400 ID-2400 ID-2400 ID-2400 RP-4 RP-4 RP-4 RP-4200 2047 1730 1877 2215

    Gray Gray Gray Gray Brick Red Brick Red- Brick Red Brick Red WR

    NOTES:

    1. ID 900 has one spring per housing.

    2. ID 1350, ID 1800, ID 2400 have two springs per housing.

  • 7/24/2019 I&M Manual_WGZ-1

    8/72

    8 WGZ 030C through 200C IMM WGZC

    Table 3, WGZ-CA, Remote Condenser, Mounting Weights & Vibration Mounting Location

    Unit Mounting Weights, Lbs Spring-Flex Mountings R-I-S Mountings

    Size M1 M2 M3 M4 M5 M6 M1 M2 M3 M4 M5 M6 M1 M2 M3 M4 M5

    ID-900 ID-900 ID-510 ID-510 RP-3 RP-3 RP-3 RP-3030 476 501 322 307 N/A N/A

    Green Green Black BlackN/A N/A

    Lime Lime Lime LimeN/A

    ID-900 ID-900 ID-510 ID-510 RP-3 RP-3 RP-3 RP-3035 511 516 337 334 N/A N/A

    Green Green Black Black

    N/A N/A

    Lime

    Lime

    Lime

    Lime

    N/A

    ID-900 ID-900 ID-510 ID-510 RP-3 RP-3 RP-3 RP-3040 511 525 344 335 N/A N/A

    Green Green Black BlackN/A N/A

    Lime Lime Lime LimeN/A

    ID-900 ID-900 ID-510 ID-510 RP-3 RP-3 RP-3 RP-3045 512 538 353 336 N/A N/A

    Green Green Black BlackN/A N/A

    Lime Lime Lime LimeN/A

    ID-900 ID-900 ID-510 ID-510 RP-3 RP-3 RP-3 RP-3050 520 549 362 342 N/A N/A

    Green Green Black BlackN/A N/A

    Lime Lime Lime LimeN/A

    ID-900 ID-900 ID-510 ID-510 RP-3 RP-3 RP-3 RP-3055 519 561 371 343 N/A N/A

    Green Green Black BlackN/A N/A

    Lime Lime Lime LimeN/A

    ID-900 ID-900 ID-510 ID-510 RP-3 RP-3 RP-3 RP-3060 519 574 380 344 N/A N/A

    Green Green Black BlackN/A N/A

    Lime Lime Lime LimeN/A

    ID-900 ID-900 ID-675 ID-900 RP3 RP3 RP3 RP3

    070 738 651 509 577 N/A N/A Green Green Purple Green N/A N/A Gray Gray Gray Gray N/A

    ID-900 ID-900 ID-675 ID-900 RP-3 RP-3 RP-3 RP-3080 884 675 532 697 N/A N/A

    Green Green Purple GreenN/A N/A

    Gray Gray Gray GrayN/A

    ID-1020 ID-1020 ID-680 ID-1020 RP-3 RP-3 RP-3 RP-3090 937 690 552 749 N/A N/A

    Black Black Red BlackN/A N/A

    Gray Gray Gray GrayN/A

    ID-1020 ID-1020 ID-680 ID-1020 RP-3 RP-3 RP-3 RP-3100 963 724 585 778 N/A N/A

    Black Black Red BlackN/A N/A

    Gray Gray Gray GrayN/A

    ID-1020 ID-1020 ID-680 ID-1020 RP-3 RP-3 RP-3 RP-3115 957. 764 621 778 N/A N/A

    Black Black Red BlackN/A N/A

    Gray Gray Gray GrayN/A

    ID-1020 ID-1020 ID-680 ID-1020 RP-3 RP-3 RP-3 RP-3130 956 804 655 779 N/A N/A

    Black Black Red BlackN/A N/A

    Gray Gray Gray GrayN/A

    ID-1020 ID-1020 ID-1020 ID-1020 ID-1020 ID-1020 RP-4 RP-4 RP-4 RP-4 RP-4 150 821 793 763 931 968 1003Black Black Black Black Black Black Brown Brown Brown Brown Brown B

    ID-1020 ID-1020 ID-1020 ID-1020 ID-1020 ID-1020 RP-4 RP-4 RP-4 RP-4 RP-4 170 863 812 750 919 986 1047

    Black Black Black Black Black Black Brown Brown Brown Brown Brown B

    ID-1020 ID-1020 ID-1020 ID-1020 ID-1020 ID-1020 RP-4 RP-4 RP-4 RP-4 RP-4 200 875 831 784 947 1000 1057

    Black Black Black Black Black Black Brown Brown Brown Brown Brown B

    NOTES:

    1. ID 510, ID 675 and ID 900 have one spring per housing.

    2. ID 680 and ID 1020 have two springs per housing.

    Table 4, WGZ-CW, Packaged, Isolator Kit Numbers

    Model Number 030-060 070-080 090 100-130 150-200Spring-Flex 332320501 332320502 332320503 332320504 332320505

    R-I-S 332325501 332325502 332325502 332325503 332325503

    Table 5, WGZ-CA, Remote Condenser, Isolator Kit Numbers

    Model Number 030-060 070-080 090-115 130 150-200

    Spring-Flex 332320506 332320507 332320508 332320509 332320510

    R-I-S 332325504 332325501 332325501 332325501 332325505

  • 7/24/2019 I&M Manual_WGZ-1

    9/72

    IMM WGZC WGZ 030C through 200C 9

    Figure 3, Spring Flex Mounting. Two-Spring

    Figure 4, Neoprene-in-Shear Mounting, RP-3

    DRAWING NUMBER 3319880

    2.50

    1.75 (R)

    .25

    MOUNTING MOLDED INDURULENE. WEATHERRESISTANT (WR)

    3.38

    4.13

    5.50

    .5 DIA.2 HOLES

    1/2-13 TAP

    LOCATING PIN TOBE INSTALLED HERE

    ALL

    DIMENSIONS ARE IN DECIMAL INCHES

  • 7/24/2019 I&M Manual_WGZ-1

    10/72

    10 WGZ 030C through 200C IMM WGZC

    Table 6, Spring Flex Mounting, One-Spring

    Table 7, Neoprene-in-Shear, RP-4

    NOTES:

    MOUNT MATERIAL TO BE DURULENE RUBBER.1.

    MOLDED STEEL AND ELASTOMER MOUNT FOR.OUTDOOR SERVICE CONDITIONS.

    . RP-4 MOUNT VERSION WITH STUD IN PLACE.

    ALL DIMENSIONS ARE IN DECIMAL INCHES

    DRAWING NUMBER 3314814

    1.13 .25APPROX.

    1.63

    .38

    DURULENEMATERIAL

    RAISED GRIP RIBS

    3.00

    3.75

    5.00

    6.25

    3.87

    .56 TYP.

    4.63

    R.28TYP.

    R.250 TYP.

    R.750 TYP.RECESSEDGRIP RIBS

    .500-13NC-2B

    R4

    R4

    VM&C

    VM&C

  • 7/24/2019 I&M Manual_WGZ-1

    11/72

    IMM WGZC WGZ 030C through 200C 11

    Limitations of Operation

    1. Maximum allowable condenser water pressure is 232 psig (1599 kPa).

    2. Maximum condenser LWT is 115F (46.1C).

    3. Maximum design saturated discharge temperature (SDT) is 140F (60C). SDT=Condensingtemperature + discharge line loss.

    4. Maximum condenser leaving water temperature is 115F (41.6C).

    5. Maximum allowable water temperature to evaporator when not operating is 100F (37.8C).

    Maximum entering water temperature for operating cycle is 90F (32.2C) (during system

    changeover from heating to cooling cycle).

    6. Minimum design leaving water temperature from the evaporator without anti-freeze protection is

    40F (4.4C).

    7. Contact your McQuay representative for operation with tower condenser water entering the chiller

    below 60F (15.6C).

    8. The maximum altitude for air-cooled condensers is 8,000 feet.9. Consult factory for ambient operation below 0F (-17.8C) for air-cooled applications.

  • 7/24/2019 I&M Manual_WGZ-1

    12/72

    12 WGZ 030C through 200C IMM WGZC

    Water Piping

    Vessel Drains at Start-upCondensers are drained of water in the factory and are shipped with the condenser drain plugs in the

    heads removed and stored in a bag in the control panel. Be sure to replace plugs prior to filling the

    vessel with fluid.

    GeneralDue to the variety of piping practices, it is advisable to follow the recommendations of local

    authorities for code compliance. They can supply the installer with the proper building and safety

    codes required for a safe and proper installation.

    Basically, the piping should be designed with a minimum number of bends and changes in elevation

    to keep system cost down and performance up. Other piping design considerations include:

    1. All piping should be installed and supported to prevent the chiller connections from bearing anystrain or weight of the system piping.

    2. Vibration eliminators to reduce vibration and noise transmission to the building.

    3. Shutoff valves to isolate the unit from the piping system during unit servicing.

    4. Manual or automatic air vent valves at the high points of the system. Drains should be placed atthe lowest points in the system.

    5. Some means of maintaining adequate system water pressure (e.g., expansion tank or regulatingvalve).

    6. Temperature and pressure indicators located within 3 feet (0.9 meters) of the inlet and outlet ofthe vessels to aid in unit servicing.

    7. A strainer or some means of removing foreign matter from the water before it enters the pump isrecommended. It should be placed far enough upstream to prevent cavitation at the pump inlet

    (consult pump manufacturer for recommendations). The use of a strainer will prolong pump life

    and thus maintain system performance.

    Important NoteA cleanable 40-mesh strainer must also be placed in the water line just prior to the inletof the evaporator on Models WGZ 030 to 130. A 20-mesh is satisfactory on Models WGZ150 to 200. This will aid in preventing foreign material from entering and decreasing theperformance of the evaporator.

    8. If the unit is used as a replacement chiller on a previously existing piping system, the systemshould be thoroughly flushed prior to unit installation. Regular water analysis and chemical

    water treatment on the evaporator and condenser is recommended immediately upon equipment

    start-up.

    9. In the event glycol is added to the water system, as an afterthought for freeze protection,recognize that the refrigerant suction pressure will be lower, cooling performance less, and

    water side pressure drop will be higher. If the percentage of glycol is large, or if propyleneglycol is used instead of ethylene glycol, the added pressure drop and loss of performance

    could be substantial. Reset the freezestat and low leaving water alarm temperatures. The

    freezestat is factory set to default at 36F (2.2C). Reset the freezestat setting to approximately

    4 to 5F (2.3 to 2.8C) below the leaving chilled water setpoint temperature. See the section

    titled Glycol Solutions for additional information concerning the use of glycol.

    10.A preliminary leak check of the water piping should be made before filling the system.

  • 7/24/2019 I&M Manual_WGZ-1

    13/72

    IMM WGZC WGZ 030C through 200C 13

    Note: A water flow switch or pressure differential switch must be mounted in theevaporator outlet water line to signal that there is water flow before the unit will start.

    Table 8, Typical Field Evaporator Water Piping, WGZ 030 to 130AirVent

    FlowSwitch

    VibrationEliminators

    Drain

    Outlet

    Inlet

    PIsolationValves

    Strainer

    NOTE: Water piping must be supported independently from the unit.

    Figure 5, Typical Field Evaporator Water Piping, WGZ 150 to 200

    Vent

    Drain

    GateValve

    WaterStrainer

    VibrationEliminatorValved

    PressureGauge

    In

    OutProtect All Field Piping

    Against Freezing

    Flow

    VibrationEliminator

    FlowSwitch

    BalancingValve

    GateValve

    Flow

    Liquid

    Suction

    NOTE: Inlet and outlet connections may be reversed on some units. Check unit

    dimension drawing.

    System Water VolumeIt is important to have adequate water volume in the system to provide an opportunity for the chiller

    to sense a load change, adjust to the change, and then stabilize. As the expected load change

    becomes more rapid, a greater water volume is needed. The system water volume is the total

    amount of water in the evaporator, air handling equipment, and associated piping. If the water

    volume is too low, operational problems can occur including rapid compressor cycling, rapid

    loading and unloading of compressors, erratic refrigerant flow in the chiller, improper motor

    cooling, shortened equipment life and other undesirable occurrences.

    For normal comfort cooling applications where the cooling load changes relatively slowly, a

    minimum system volume of two to three minutes times the flow rate (GPM) is recommended. For

    example, if the design chiller flow rate is 120 gpm, we recommend a system volume of 240 to 360

    gallons.

    For process applications where the cooling load can change rapidly, additional system water

    volume is needed. A process example would be the quenching of hot metal objects. The load would

    be very stable until the hot metal is dipped into the water tank. Then, the load would increase

    drastically.

    Since there are many other factors that can influence performance, systems can successfully operate

    below these suggestions. However, as the water volume decreases below these guidelines, the

    possibility of problems increases.

  • 7/24/2019 I&M Manual_WGZ-1

    14/72

    14 WGZ 030C through 200C IMM WGZC

    Suction

    Circuit #1SuctionCircuit #2

    LiquidCircuit #2

    LiquidCircuit #1

    Leaving ChilledWater Sensor

    Variable Chilled Water FlowReducing chilled water flow in proportion to load can reduce total system power consumption.

    Certain restrictions apply to the amount and rate of flow change. The rate of flow change should

    be a maximum of 10 percent of the change, per minute. Do not reduce flow lower than the part

    load minimum flows listed on page 17.

    Chilled Water PipingThe system water piping must be flushed thoroughly prior to making connections to the unit

    evaporator. It is required that a 40-mesh strainer be installed in the return water line before the

    inlet to the chiller. Lay out the water piping so the chilled water circulating pump discharges into

    the evaporator inlet.

    The return water line must be piped to the evaporator inlet connection and the supply water line

    must be piped to the evaporator outlet connection. If the evaporator water is piped in the reverse

    direction, a substantial decrease in capacity and efficiency of the unit will be experienced.

    A flow switch must be installed in the horizontal piping of the supply (evaporator outlet) water

    line to prove water flow before starting the unit.

    Drain connections should be provided at all low points in the system to permit complete drainage

    of the system. Air vents should be located at the high points in the system to purge air out of the

    system. The evaporators are not equipped with vent or drain connections and provision must be

    made in the entering and leaving chilled water piping for venting and draining.

    Pressure gauges should be installed in the inlet and outlet water lines to the evaporator. Pressure

    drop through the evaporator should be measured to determine water flow from the flow/pressure

    drop curves beginning on page 18. Vibration eliminators are recommended in both the supply and

    return water lines.

    Chilled water piping should be insulated to reduce heat loss and prevent condensation. Complete

    unit and system leak tests should be performed prior to insulating the water piping. Insulation

    with a vapor barrier would be the recommended type of insulation. If the vessel is insulated, the

    vent and drain connections must extend beyond the proposed insulation thickness for

    accessibility.

    Chillers not run in the winter should have their water systems thoroughly drained if subject to

    sub-freezing temperatures. If the chiller operates year-round, or if the system is not drained forthe winter, the chilled water piping exposed to sub-freezing ambient temperatures should be

    protected against freezing by wrapping the lines with a heater cable. In addition, an adequate

    percentage of glycol should be added to the system to further protect the system during low

    ambient temperature periods. It should be noted that water piping that has been left drained is

    subject to more corrosion than if filled with water. Use of a Vapor Corrosion Inhibitor (VCI) or

    some other protection should be considered.

    Figure 6 Thermostat Well Location, WGZ 030 - 130

    The chilled water sensor is factory installed in the leaving water

    connection on the evaporator. Care should be taken not to damage

    the sensor cable or lead wires when working around the unit. It isalso advisable to check the lead wire before running the unit to be

    sure that it is firmly anchored and not rubbing on the frame or any

    other component. If the sensor is ever removed from the well for

    servicing, care must be taken to not wipe off the heat-conducting

    compound supplied in the well.

  • 7/24/2019 I&M Manual_WGZ-1

    15/72

    IMM WGZC WGZ 030C through 200C 15

    ! CAUTION

    The thermostat bulb should not be exposed to water temperatures above 125F (51.7C)since this will damage it.

    Flow SwitchA water flow switch must be mounted in the leaving evaporator and condenser water lines to

    prove adequate water flow before the unit can start. This will safeguard against slugging the

    compressors on start-up. It also serves to shut down the unit in the event that water flow is

    interrupted to guard against evaporator freeze-up.

    Factory-mounted and wired evaporator and condenser flow switches are available as an option

    If the optional factory flow switch is not supplied, a flow switch is available from McQuay under

    part number 01750330. It is a paddle type switch and adaptable to any pipe size from 1 in. (25

    mm) to 6 in. (152 mm) nominal. Certain flow rates are required to open the switch and are listed

    in Table 9. Wire from switch terminals Y and R to panel terminals 33 and 43 (chilled water) and

    41 and 53 (condenser water). There is also a set of normally closed contacts on the switch that

    could be used for an indicator light or an alarm to indicate when a no flow condition exists.

    1. Apply pipe sealing compound to only the threads of the switch and screw unit into 1 in. (25 mm)reducing tee. The flow arrow must be pointed in the correct direction.

    2. Piping should provide a straight length before and after the flow switch of at least five times thepipe diameter without any valves, elbows, or other flow restricting elements.

    ! CAUTION

    Make sure the arrow on the side of the switch is pointed in the direction of flow. The flowswitch is designed to handle the control voltage and should be connected according to thewiring diagram

    Table 9, Paddle-Type Flow Switch Flow Rates

    inch 1 1/4 1 1/2 2 2 1/2 3 4 5 6 8Pipe SizeNOTES (x) mm 32 (2) 38 (2) 51 63 (3) 76 102 (4) 127 (4) 153 (4) 204 (5)

    gpm 5.8 7.5 13.7 18.0 27.5 65.0 125.0 190.0 205.0Flow

    Lpm 1.3 1.7 3.1 4.1 6.2 14.8 28.4 43.2 46.6

    gpm 3.7 5.0 9.5 12.5 19.0 50.0 101.0 158.0 170.0

    Min.

    Adjst. NoFlow Lpm 0.8 1.1 2.2 2.8 4.3 11.4 22.9 35.9 38.6

    gpm 13.3 19.2 29.0 34.5 53.0 128.0 245.0 375.0 415.0Flow

    Lpm 3.0 4.4 6.6 7.8 12.0 29.1 55.6 85.2 94.3

    gpm 12.5 18.0 27.0 32.0 50.0 122.0 235.0 360.0 400.0

    Max.

    Adjst. No

    Flow Lpm 2.8 4.1 6.1 7.3 11.4 27.7 53.4 81.8 90.8

    NOTES:

    1. A segmented 3-inch paddle (1, 2, and 3 inches) is furnished mounted, plus a 6-inch paddle loose.

    2. Flow rates for a 2-inch paddle trimmed to fit the pipe.

    3. Flow rates for a 3-inch paddle trimmed to fit the pipe.

    4. Flow rates for a 3-inch paddle.

    5. Flow rates for a 6-inch paddle.

    Glycol Solutions

    Chiller capacity, flow rate, evaporator pressure drop, and power input for glycol solutions can becalculated using the following formulas and reference to Table 10for ethylene and Table 11for

    propylene glycol.

    1. Capacity,Capacity is reduced compared to that with plain water. To find the reduced value,multiply the chillers capacity when using water by the capacity correction factor C to find

    the chillers capacity when using glycol.

    2. Flow, To determine evaporator gpm (or T) knowing T (or gpm) and capacity:

    TablesFromGCorrectionFlowxT

    CapacityGlycolxGPMGlycol

    24

  • 7/24/2019 I&M Manual_WGZ-1

    16/72

    16 WGZ 030C through 200C IMM WGZC

    For Metric Applications -- Determine evaporator lps (or T) knowing T (or lps)

    and kW:

    TablesfromGCorrectionFlowxTx

    kWLpsGlycol

    18.4

    3. Pressure Drop, To determine glycol pressure drop through the cooler, enter the waterpressure drop graph on page 17at the actual glycol flow. Multiply the water pressure

    drop found there by P to obtain corrected glycol pressure drop.

    4. Power, To determine glycol system kW, multiply the water system kW by factor K.

    Test coolant with a clean, accurate, glycol solution hydrometer (similar to that found in

    service stations) to determine the freezing point. Obtain percent glycol from the freezing

    point found in Table 10 or Table 11. On glycol applications the supplier normally

    recommends that a minimum of 25% solution by weight be used for protection against

    corrosion or the use of additional inhibitors.

    Note: The effect of glycol in the condenser is negligible. As glycol increases intemperature, its characteristics have a tendency to mirror those of water.

    Therefore, for selection purposes, there is no derate in capacity for glycol in thecondenser.

    Table 10, Ethylene Glycol

    Freezing PointPercentGlycol F C

    C (Capacity) K (Power) G (Flow)P (Pressure

    Drop)

    10 26 -3 0.991 0.996 1.013 1.070

    20 18 -8 0.982 0.992 1.040 1.129

    30 7 -14 0.972 0.986 1.074 1.181

    40 -7 -22 0.961 0.976 1.121 1.263

    50 -28 -33 0.946 0.966 1.178 1.308

    Table 11, Propylene Glycol

    Freezing PointPercent

    Glycol F C C (Capacity) K (Power) G (Flow)

    P (Pressure

    Drop)

    10 26 -3 0.987 0.992 1.010 1.068

    20 19 -7 0.975 0.985 1.028 1.147

    30 9 -13 0.962 0.978 1.050 1.248

    40 -5 -21 0.946 0.971 1.078 1.366

    50 -27 -33 0.929 0.965 1.116 1.481

    ! CAUTION

    Do not use automotive antifreeze. Industrial glycols must be used. Automotive antifreezecontains inhibitors that causes plating on copper tubes. The type and handling of glycol usedmust be consistent with local codes.

  • 7/24/2019 I&M Manual_WGZ-1

    17/72

    IMM WGZC WGZ 030C through 200C 17

    Circuit #1Outlet

    Condenser

    Temperature

    ControlValve

    CondenserWater

    Circuit #2Outlet

    Circuit #1Inlet

    Circuit #2Inlet

    Condenser Water PipingArrange the condenser water so the water enters the bottom connection of the condenser.

    The condenser water will discharge from the top connection. Failing to arrange the

    condenser water as stated above will negatively affect the capacity and efficiency.

    Install pressure gauges in the inlet and outlet water lines to the condenser. Pressure drop

    through the condenser should be measured to determine flow on the pressure drop/flowcurves on beginning on page 17Error! Bookmark not defined.. Vibration eliminators

    are recommended in both the supply and return water lines. Install a 20-mesh strainer in

    the inlet piping to the condenser.

    Water-cooled condensers can be piped for use with cooling towers, well water, or heat

    recovery applications. Cooling tower applications should be made with consideration of

    freeze protection and scaling problems. Contact the cooling tower manufacturer for

    equipment characteristics and limitations for the specific application.

    Head pressure control must be provided if the entering condenser water can fall below

    60F. The WGZ condenser has two refrigerant circuits with a common condenser water

    circuit. This arrangement makes head pressure control with discharge pressure actuated

    control valves difficult.

    If the tower water temperature cannot be maintained at a 60F minimum, or when pond,

    lake, or well water that can fall below 60F (15C) is used as the condensing medium,

    special discharge pressure control must be used. A water recirculating system with

    recirculating pump as shown in Figure 7 is recommended. This system also has the

    advantage of maintaining tube velocity to help prevent tube fouling. The pump should

    cycle with the chiller.

    Figure 7, Recirculating Discharge Pressure Control System

    Pressure Drops

    The evaporator flow rates and pressure drops shown on the following page (Figure 8) are for full load

    design purposes. The maximum flow rate and pressure drop are based on a 6-degree temperature drop.

    Avoid higher flow rates with resulting lower temperature drops to prevent potential control problems

    resulting from very small control bands and limited start up/shut off temperature changes.

    The minimum flow and pressure drop is based on a full load evaporator temperature drop of 16-degrees.

    Condenser pressure drops are shown on the page following evaporator drops.

  • 7/24/2019 I&M Manual_WGZ-1

    18/72

    18 WGZ 030C through 200C IMM WGZC

    Figure 8, Evaporator Pressure Drop, WGZ 030C WGZ 200C

    Minimum Flow & PD Nominal Flow & PD Maximum Flow & PD

    Inch-Pound S.I. Inch-Pound S.I. Inch-Pound S.I.WGZ-C

    Model

    Ref

    #GPM Ft. L/S kPa GPM Ft. L/S kPa GPM Ft. L/S kPa

    WGZ030C A 45 4.7 2.8 14.1 72 11 4.5 32.9 120 27.6 7.6 82.4WGZ035C B 51.9 4.9 3.3 14.6 83 11.4 5.2 34 138.3 28.5 8.7 85.4

    WGZ040C C 61.1 5.1 3.9 15.2 97.8 11.8 6.2 35.4 163 29.7 10.3 88.8

    WGZ045C D 68.2 5.2 4.3 15.5 109.1 12.1 6.9 36.1 181.8 30.2 11.5 90.4

    WGZ050C E 76.7 5.8 4.8 17.2 122.6 13.4 7.7 40.1 204.4 33.6 12.9 100.6

    WGZ055C F 84.6 6.1 5.3 18.1 135.4 14.1 8.5 42.2 225.6 35.4 14.2 105.9

    WGZ060C G 90.8 6.6 5.7 19.7 145.2 15.6 9.2 46.5 242 39.2 15.3 117.1

    WGZ070C H 106.3 3.7 6.7 10.9 170 8.6 10.7 25.6 283.4 21.2 17.9 63.3WGZ080C I 117.5 4.3 7.4 12.8 187.9 10 11.9 29.9 313.2 25 19.8 74.9

    WGZ090C J 132.1 4.5 8.3 13.3 211.3 10.5 13.3 31.3 352.1 26.1 22.2 78.1

    WGZ100C K 146.6 4.9 9.3 14.6 234.6 11.4 14.8 34.1 391.1 28.7 24.7 85.8

    WGZ115C L 169.3 4.5 10.7 13.5 270.9 10.5 17.1 31.4 451.5 26.4 28.5 78.9

    WGZ130C M 188.1 4.2 11.9 12.6 301 9.8 19 29.5 501.6 24.7 31.6 73.9

    WGZ150C N 219.9 5.5 13.9 351.8 12.8 22.2 38.3 586.4 32.0 37

    WGZ170C O 254 7.9 16 406.3 18.5 25.6 55.3 677.2 46.4 42.7

    WGZ200C P 282.2 9.5 17.8 451.4 22 28.5 65.8 752.4 55.1 47.5

    Notes: Minimum, nominal, and maximum flows are at a 16 F, 10 F, and 6 F chilled water temperature range respectively atARI tons.

    900 1000

    CBD K

    LJIA

    EFG

    H

    0

    6

    12

    18

    24

    27

    30

    9

    21

    15

    60

    90

    40 50 60 70 80 90 100 200 300 400 500 600

    PresureDrop(ftofwater)

    Flow Rate (GPM)

    700 800

    O

    P

    N

    M

  • 7/24/2019 I&M Manual_WGZ-1

    19/72

    IMM WGZC WGZ 030C through 200C 19

    Figure 9, Condenser Pressure Drop, WGZ 030C WGZ 200C

    Minimum Flow & PD Nominal Flow & PD Maximum Flow & PD

    Inch-Pound SI Inch-Pound SI Inch-Pound SIUnit ModelRef

    #GPM Ft. L/S kPa GPM Ft. L/S kPa GPM Ft. L/S kPa

    WGZ030C A 56.1 2.4 3.5 7.2 89.7 6.3 5.7 18.8 149.5 17.4 9.4 52.0

    WGZ035C B 64.9 3.4 4.1 10.2 103.8 8.6 6.5 25.7 173.0 23.9 10.9 71.4

    WGZ040C C 76.3 2.7 4.8 8.1 122.1 6.9 7.7 20.6 203.5 19.3 12.8 57.7

    WGZ045C D 85.3 3.6 5.4 10.8 136.5 9.2 8.6 27.5 227.5 25.7 14.4 76.8

    WGZ050C E 96.4 2.9 6.1 8.7 154.2 7.5 9.7 22.4 257.0 20.7 16.2 61.9

    WGZ055C F 105.8 3.8 6.7 11.4 169.2 9.7 10.7 29.0 282.0 26.8 17.8 80.1

    WGZ060C G 113.4 4.5 7.2 13.5 181.5 11.6 11.5 34.7 302.5 32.3 19.1 96.5

    WGZ070C H 132.8 4.1 8.4 12.3 212.4 10.4 13.4 31.1 354.0 29.0 22.3 86.7

    WGZ080C I 146.8 3.7 9.3 11.1 234.9 9.5 14.8 28.4 391.5 26.5 24.7 79.2

    WGZ090C J 165.0 3.4 10.4 10.2 264 8.8 16.7 26.3 440.0 24.5 27.8 73.2WGZ100C K 183.4 3.4 11.6 10.2 293.4 8.8 18.5 26.3 489.0 24.4 30.9 72.9

    WGZ115C L 211.7 4.8 13.4 14.3 338.7 12.3 21.4 36.8 564.5 34.1 35.6 101.9

    WGZ130C M 235.1 6.1 14.8 18.2 376.2 15.5 23.7 46.3 627.0 43.1 39.6 128.8

    WGZ150C N 274.9 6.2 17.3 18.5 439.8 15.8 27.7 47.2 733.0 43.8 46.2 130.9

    WGZ170C O 317.4 5.5 20.0 16.4 507.9 14.0 32.0 41.8 846.5 38.9 53.4 116.3

    WGZ200C P 352.7 7.4 22.3 22.1 564.3 18.8 35.6 56.2 940.5 52.3 59.3 156.3

    P

    ressureDrop(ftofwater)

    Flow Rate (GPM)

  • 7/24/2019 I&M Manual_WGZ-1

    20/72

    20 WGZ 030C through 200C IMM WGZC

    Refrigerant Piping

    Unit with Remote CondenserGeneral

    Refrigerant piping, to and from the unit, should be sized and installed according to the

    latest ASHRAE Handbook. It is important that the unit piping be properly supported with

    sound and vibration isolation between tubing and hanger, and that the discharge lines be

    looped at the condenser and trapped at the compressor to prevent refrigerant and oil from

    draining into the compressors. Looping the discharge line also provides greater line

    flexibility.

    NOTE:Do not install any refrigerant piping underground.

    The discharge gas valves, liquid line solenoids, filter-driers, moisture indicators, and

    expansion valves are all factory mounted as standard equipment with the water chiller.

    For remote condenser application (WGZ-CA) such as air-cooled or evaporative

    condenser, the chillers are shipped with a nitrogen/helium holding charge. The unit is

    evacuated in the factory to 500 microns before charging with the nitrogen.

    The liquid line has a shutoff valve upstream from the liquid line solenoid valve and a

    copper tube cap to be brazed on this line after test to seal this line for shipment.

    The discharge line has a ball valve installed between the compressor and the discharge

    stub tube with a copper tube cap brazed on the line after test to seal it for shipment.

    The discharge gas valves, liquid line solenoids, filter-driers, moisture indicators, and

    expansion valves are all factory-mounted as standard equipment with the water chiller.

    ! DANGER

    Do not apply heat, such as a brazing torch, to a sealed unit, vessel, or component. Internalgases can increase the internal pressure and cause a life-threatening explosion. Open thesystem when heating. The short line between a valve and brazed end cap can be drilled to

    vent it. Note that the valve may leak and the entire unit charge may be open to the cap.

    It is important that the unit be kept tightly closed until the remote condenser is installed,

    piped to the unit and the high side evacuated.

    When the field piping has been leak tested, evacuated, and is ready to charge, the unit

    valves can be opened and the system is ready to pressure test, evacuate and charge the

    entire system together at one time.

    After the equipment is properly installed, leak tested, and evacuated, it can be charged

    with R-410A, and run at design load conditions. Add charge until the liquid line sight

    glass is clear, with no bubbles flowing to the expansion valve. Total operating charge will

    depend on the air-cooled condenser used and volume of the refrigerant piping.NOTE:On WGZ-CA units (units with remote condensers), the installer is required to record

    the refrigerant charge by stamping the total charge and the charge per circuit on the serial plate

    in the appropriate blocks provided for this purpose.

    The following discussion is intended for use as a general guide to the piping of air-cooled

    condensers.

    Discharge lines must be designed to handle oil properly and to protect the compressor from

    damage that can result from condensing liquid refrigerant in the line during shutdown. Total

    friction loss for discharge lines of 3 to 6 psi (20.7 to 41.4 kPa) is considered good design.

  • 7/24/2019 I&M Manual_WGZ-1

    21/72

    IMM WGZC WGZ 030C through 200C 21

    Careful consideration must be given for sizing each section of piping to insure that gas

    velocities are sufficient at all operating conditions to carry oil. If the velocity in a vertical

    discharge riser is too low, considerable oil can collect in the riser and the horizontal header,

    causing the compressor to lose its oil and result in damage due to lack of lubrication. When the

    compressor load is increased, the oil that had collected during reduced loads can be carried as

    a slug through the system and back to the compressor, where a sudden increase of oil

    concentration can cause liquid slugging and damage to the compressor.

    Any horizontal run of discharge piping should be pitched away from the compressor

    approximately 1/8 inch (6.4 mm) per foot (meter) or more. This is necessary to move, by

    gravity, any oil lying in the header. Oil pockets must be avoided because oil needed in the

    compressor would collect at such points and the compressor crankcase can become starved.

    It is recommended that any discharge lines coming into a horizontal discharge header rise

    above the centerline of the discharge header. This is necessary to prevent any oil or condensed

    liquid from draining to the compressor heads when the compressor is not running.

    In designing liquid lines, it is important that the liquid reach the expansion valve without flash

    gas since this gas will reduce the capacity of the valve. Because flashing can be caused by a

    pressure drop in the liquid line, the pressure losses due to friction and changes in static head

    should be kept to a minimum.

    A check valve must be installed in the liquid line in all applications where the ambient

    temperature can drop below the equipment room temperature. This prevents liquid migration

    to the condenser, helps maintain a supply of refrigerant in the liquid line for initial start-up,

    and keeps liquid line pressure high enough on off cycle to keep the expansion valve closed.

    On systems as described above, a relief valve or relief-type check valve, must be used in the

    liquid line as shown in piping systems (shown in and Its purpose is to relieve dangerous

    hydraulic pressures that could be created as cool liquid refrigerant trapped in the line between

    the check valve and the expansion or shutoff valve warms up. Install a relief device in the hot

    gas piping at the condenser coil as shown in and Figure 11. Install a discharge check valve in

    the discharge line, in a horizontal run, close to the condenser.

    Recommended Line SizingThe following tables provide recommended line sizing for the field piping. Final design

    should be based on ASHRAE design standards.

  • 7/24/2019 I&M Manual_WGZ-1

    22/72

    22 WGZ 030C through 200C IMM WGZC

    Table 12, Equivalent Feet for Fittings

    Fitting Type 7/8 1 1/8 1 3/8 1 5/8 2 1/8 2 5/8 3 1/8

    Elbows

    90Standard 2.0 2.6 3.3 4.0 5.0 6.0 7.5

    90Long Radius 1.4 1.7 2.3 2.6 3.3 4.1 5.0

    90Street 3.2 4.1 5.6 6.3 8.2 10 12

    45Standard 0.9 1.3 1.7 2.1 2.6 3.2 4.045Street 1.5 2.1 3.0 3.4 4.5 5.2 6.4

    180Bend 3.2 4.1 5.6 6.3 8.2 10 12

    Tees

    Full Size 1.4 1.7 2.3 2.6 3.3 4.1 5.0

    Reducing 2.0 2.6 3.3 4.0 5.0 6.0 7.5

    Valves

    Globe Valve, Open 22 29 38 43 55 69 84

    Gate Valve, Open 0.9 1.0 1.5 1.8 2.3 2.8 3.2

    Angle Valve, Open 9.0 12 15 18 24 29 35

    Table 13, Maximum Line Size for Oil Carry Up a Discharge Riser, R-410A

    Unit Size WGZ030

    WGZ035

    WGZ040

    WGZ045

    WGZ050

    WGZ055

    WGZ060

    WGZ070

    WGZ080

    WGZ090

    Line

    Size (in.)1 5/8 1 5/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 5/8 2 5/8

    Unit SizeWGZ

    100

    WGZ

    115

    WGZ

    130

    WGZ

    150

    WGZ

    170

    WGZ

    200

    Line

    Size (in.)2 5/8 3 1/8 3 1/8 2 5/8 3 1/8 3 1/8

    Table 14, Recommended Liquid Line Size, R-410A

    Recommended Liquid Line Size (in.)

    Up to Up to Up to Up to Up to

    Unit Model

    WGZ-CB

    Connection

    Size at Unit(in.) 50 Equiv. Ft 75 Equiv. Ft 100 Equiv. Ft 125 Equiv. Ft 150 Equiv. Ft

    WGZ 030 7/8" 7/8 " 7/8 " 7/8 " 7/8 " 7/8 "

    WGZ 035 7/8" 7/8 " 7/8 " 7/8 " 7/8 " 1 1/8 "

    WGZ 040 7/8" 7/8 " 7/8 " 7/8 " 1 1/8 " 1 1/8 "

    WGZ 045 7/8" 7/8 " 7/8 " 7/8 " 1 1/8 " 1 1/8 "

    WGZ 050 7/8" 7/8 " 7/8 " 7/8 " 1 1/8 " 1 1/8 "

    WGZ 055 7/8" 7/8 " 7/8 " 1 1/8 1 1/8 " 1 1/8 "

    WGZ 060 7/8" 7/8 7/8 " 1 1/8 " 1 1/8 " 1 1/8 "

    WGZ 070 1 1/8 1 1/8 1 1/8 " 1 1/8 " 1 1/8 " 1 1/8

    WGZ 080 1 1/8 1 1/8 " 1 1/8 " 1 1/8 1 1/8 1 1/8

    WGZ 090 1 1/8 1 1/8 " 1 1/8 " 1 1/8 1 1/8 1 1/8

    WGZ 100 1 1/8 1 1/8 " 1 1/8 " 1 1/8 1 1/8 1 1/8WGZ 115 1 1/8 1 1/8 " 1 1/8 " 1 1/8 1 3/8 1 3/8

    WGZ 130 1 1/8 1 1/8 " 1 3/8 1 1/8 1 3/8 1 3/8

    WGZ 150 1 3/8 1 3/8 1 1/8 " 1 3/8 1 3/8 1 3/8

    WGZ 170 1 3/8 1 3/8 1 1/8 " 1 3/8 1 3/8 1 3/8

    WGZ-200 1 3/8 1 3/8 1 1/8 " 1 3/8 1 3/8 1 3/8

  • 7/24/2019 I&M Manual_WGZ-1

    23/72

    IMM WGZC WGZ 030C through 200C 23

    Table 15, Recommended Horizontal or Downflow Discharge Line Size, R-410A

    Recommended Discharge Line Sizes

    Up to Up to Up to Up to Up toUnit Model

    AGZ-CB

    Connection

    Size

    At Unit 50 Equiv. Ft 75 Equiv. Ft 100 Equiv. Ft 125 Equiv. Ft 150 Equiv. Ft

    WGZ 030 1 3/8" 1 1/8" 1 1/8" 1 1/8" 1 1/8" 1 1/8"

    WGZ 035 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8"

    WGZ 040 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8"WGZ 045 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8"

    WGZ 050 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8"

    WGZ 055 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8"

    WGZ 060 1 3/8" 1 3/8" 1 5/8 1 5/8 1 5/8 1 5/8

    WGZ 070 1 3/8" 1 3/8" 1 5/8 1 5/8 1 5/8 1 5/8

    WGZ 080 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8

    WGZ 090 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8

    WGZ 100 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8

    WGZ 115 1 5/8 1 5/8 1 5/8 2 1/8" 2 1/8" 2 1/8"

    WGZ 130 1 5/8 1 5/8 2 1/8" 2 1/8" 2 1/8" 2 1/8"

    WGZ 150 2 1/8" 2 1/8" 2 1/8" 2 1/8" 2 1/8" 2 1/8"

    WGZ 170 2 1/8" 2 1/8" 2 1/8" 2 1/8" 2 1/8" 2 1/8"

    WGZ 200 2 1/8" 2 1/8" 2 1/8" 2 1/8" 2 1/8" 2 5/8"

    Typical Arrangements

    Figure 10 illustrates a typical piping arrangement involving a remote air-cooled condenser

    located at a higher elevation than the compressor and receiver. This arrangement is commonly

    encountered when the air-cooled condenser is on a roof and the compressor and receiver are on

    grade level or in a basement equipment room.

    Notice, in both illustrations, that the hot gas line is looped at the bottom and top of the vertical

    run. This is done to prevent oil and condensed refrigerant from flowing back into thecompressor and causing damage. The highest point in the discharge line should always be

    above the highest point in the condenser coil. It is advisable to include a purging vent at this

    point to extract non-condensables from the system.

    Figure 11 illustrates another very common application where the air-cooled condenser is

    located on essentially the same level as the compressor and receiver. The discharge line piping

    in this case is not too critical. The principal problem encountered with this arrangement is that

    there is frequently insufficient vertical distance to allow free drainage of liquid refrigerant

    from the condenser coil to the receiver.

    The receiver is used when it is desired to have refrigerant storage capacity, in addition to the

    pumpdown capability of the condenser.

  • 7/24/2019 I&M Manual_WGZ-1

    24/72

    24 WGZ 030C through 200C IMM WGZC

    Condenser

    Relief Valve

    Check Valve

    Purge Valve

    Discharge Line

    Loop

    Receiver

    ReceiverBypass

    ToEvap.

    PreferredSubcoolerHook-up

    Relief Valve(Vent to Outdoorsor to Condenser Sideof Liquid LineCheck Valve)

    Pitch

    CheckValve

    Subcooler

    Condenser

    Relief Valve

    Check Valve

    Purge Valve

    Relief Valve(Vent to Outdoorsor to Condenser Sideof Liquid LineCheck Valve)

    Pitch

    CheckValve

    Discharge Line

    Receiver

    ReceiverBypass

    ToEvap.

    PreferredSubcoolerHook-up

    CheckValve

    Subcooler

    Figure 10, Condenser Above Compressor and Optional Receiver Installation

    Figure 11, Condenser and Compressor on Same Level, Optional Receiver

    Installation

    The receiver shown is optional and not used on many installations. It is bypassed during

    normal operation.

  • 7/24/2019 I&M Manual_WGZ-1

    25/72

    IMM WGZC WGZ 030C through 200C 25

    Factory-Mounted CondenserUnits with the standard water-cooled, factory-mounted condenser are provided with

    complete refrigerant piping and full operating refrigerant charge at the factory.

    There is a remote possibility on water-cooled units utilizing low temperature pond or

    river water as a condensing medium, and if the water valves leak, that the condenser and

    liquid line refrigerant temperature could drop below the equipment room temperature on

    the off cycle. This problem only arises during periods when cold water continues tocirculate through the condenser and the unit remains off due to satisfied cooling load.

    If this condition occurs:

    1. Cycle the condenser pump off with the unit.

    2. Check the liquid line solenoid valve for proper operation.

    Relief Valve Piping

    The ANSI/ASHRAE Standard 15, Safety Standard for Refrigeration Systems, specifies

    that pressure relief valves on vessels containing Group 1 refrigerant (R-410a) shall

    discharge to the atmosphere at a location not less than 15 feet (4.6 meters) above the

    adjoining ground level and not less than 20 feet (6.1 meters) from any window,

    ventilation opening or exit in any building. The piping must be provided with a rain capat the outside terminating point and with a drain at the low point on the vent piping to

    prevent water buildup on the atmospheric side of the relief valve. Also, a flexible pipe

    section should be installed in the line to eliminate any piping stress on the relief valve(s).

    The size of the discharge pipe from the pressure relief valve should not be less than the

    size of the pressure relief outlet. When two or more vessels are piped together, the

    common header and piping to the atmosphere should not be less than the sum of the area

    of each of the lines connected to the header.

    NOTE: Fittings should be provided to permit vent piping to be easilydisconnected for inspection or replacement of the relief valve.

    Figure 12, Relief Valve Piping

  • 7/24/2019 I&M Manual_WGZ-1

    26/72

    26 WGZ 030C through 200C IMM WGZC

    Dimensions

    Packaged Chillers

    Figure 13, WGZ 030CW through WGZ 060CW

    CHILLER WATER CONNECTIONSIZE (NOM) VICTAULIC

    CONDENSER WATER

    CONNECTION SIZE(NOM) VICTAULIC

    CENTER OF GRAVITYWGZ MODELNUMBER

    IN (MM) A IN (MM) X Y Z

    WGZ030C 2.5 (64) 107.4 (2728) 4 (102) 59.2 22.4 14.1

    WGZ035C 2.5 (64) 108.4 (2753) 4 (102) 59.9 22.8 14.2

    WGZ040C 2.5 (64) 109.8 (2789) 4 (102) 59.6 22.8 14.2

    WGZ045C 2.5 (64) 111.5 (2832 4 (102) 59.2 22.9 14.2

    WGZ050C 2.5 (64) 113.3 (2878) 4 (102) 59.0 23.3 14.2

    WGZ055C 2.5 (64) 115.0 (2921) 4 (102) 58.7 23.4 14.2

    WGZ060C 2.5 (64) 116.7 (2965) 4 (102) 58.0 23.6 14.3

    CONDENSER

    INLET

    121.13075

    9.7246

    134.63419

    3.8

    REF.98 " X "

    " Y "

    3.9100

    .875 DIA MOUNTING HOLES (4)

    INLET

    OUTLET

    OUTLET

    RELIEF VALVES

    MICROTECH II USER INTERFACE

    VENT

    DRAIN

    CIRCUIT 1CIRCUIT 2

    30.1763

    32.8832

    " Z "

    " Y "

    23.5597

    2.051

    20.0508

    29.0737

    13.3338

    32.0813

    8.0204

    14.0354

    29.2742

    44.91139

    12.4314

    63.41609

    40.01016

    EVAPORATOR

    REMOVABLEDISC. HANDLE

    REMOVE BRKT.FOR SHIPPING

    ONLYPOWER

    CONNECTIONS

    CONTROLCONNECTION

    .88 KNOCKOUTSON OPPOSITE SIDE

    .88 KNOCKOUTS

    "A"

    CONTROL BOX

    WATERCONNECTIONS

    L1 / M1 L2 / M2

    L3 / M3L4 / M4

    WGZ030C-060CPac kaged Unit

    331929701

  • 7/24/2019 I&M Manual_WGZ-1

    27/72

    IMM WGZC WGZ 030C through 200C 27

    Figure 14, WGZ 070CW through WGZ 130CW

    MAXIMUM OVERALL

    DIMENSIONSIN (MM) CENTER OF GRAVITYWGZ MODELNUMBER

    L W H

    CHILLERWATER

    CONNECTIONIN(MM)

    VICTAULIC

    SIZE (NOM)

    A

    CONDENSERWATER

    CONNECTIONIN(MM)

    VICTAULIC

    SIZE (NOM)

    T

    X Y Z

    WGZ070C143.3(3639)

    35.0(889)

    65.5(1664)

    3 (76)114.9(2918)

    4 (102)8.0

    (203)62.4 28.6 15.0

    WGZ080C149.6(3799)

    35.0(889)

    65.5(1664)

    3 (76)115.3(2930)

    4 (102)14.3(363)

    64.8 29.3 15.1

    WGZ090C149.4(3795)

    35.0(889)

    65.5(1664)

    3 (76)117.1(2975)

    4 (102)14.1(359)

    67.7 29.6 16.1

    WGZ100C149.4

    (3795)

    35.0

    (889)

    65.5

    (1664)

    3 (76)118.0

    (2997)

    4 (102)14.1

    (359)

    69.7 29.9 17.1

    WGZ115C149.4(3795)

    35.0(889)

    65.5(1664)

    3 (76)121.6(3088)

    4 (102)14.1(359)

    68.8 30.2 17.1

    WGZ130C149.4(3795)

    35.0(889)

    65.5(1664)

    3 (76)124.7(3167)

    4 (102)14.1(359)

    67.8 30.4 17.1

    CONDENSER

    121.13075"T"

    14.2361

    "L"

    "A"

    " X "

    4.0102

    .875 DIA MOUNTING HOLES (4)

    INLET

    INLET

    OUTLET

    OUTLET

    EVAPORATOR

    RELIEF VALVES

    MICROTECH II USER INTERFACE

    VENT

    DRAIN

    CIRCUIT 2 CIRCUIT 1

    29.0737

    13.0330

    32.3821

    "W"

    " Y "

    " Z "

    23.5597

    2.051

    10.0253

    17.9454

    32.8834

    57.6

    1462

    14.5369

    20.0508

    "H"

    32.0813

    40.01016

    40.21021

    REMOVABLEDISC. HANDLE REMOVE BRKT.

    FOR SHIPPINGONLY

    POWERCONNECTIONS

    CONTROLCONNECTION

    .88 KNOCKOUTSON OPPOSITE SIDE

    .88 KNOCKOUTS

    CONTROL BOX

    WATERCONNECTIONS

    L1 / M1 L2 / M2

    L3 / M3L4 / M4

    WGZ070-130CWPackaged Chiller

    331929801

  • 7/24/2019 I&M Manual_WGZ-1

    28/72

    28 WGZ 030C through 200C IMM WGZC

    Figure 15, WGZ 150CW through WGZ 200CW

    CHILLER WATERCONNECTION SIZE(NOM) VICTAULIC

    CONDENSER WATERCONNECTION SIZE(NOM) VICTAULIC

    CENTER OF GRAVITYWGZ MODELNUMBER

    IN (MM) IN (MM) X Y Z

    WGZ150C 8 (203) 5 (127) 68.7 38.6 14.9

    WGZ170C 8 (203) 5 (127) 66.3 38.3 15.0

    WGZ200C 8 (203) 5 (127) 66.6 38.7 15.1

    CONDENSER

    EVAPORATOROUTLET

    10.9276

    145.13685

    14.2361

    170.24322

    " X "

    " Y "

    4.0

    102

    INLET

    OUTLET

    EVAPORATORINLET

    RELIEF VALVES

    MICROTECH II USER INTERFACE

    VENT

    VENT

    DRAINDRAIN

    29.0737

    13.3337

    33.8859

    36.5

    T.B.D.927

    77.71973

    " Z "

    23.5597

    2.051

    15.5394

    17.0432

    9.6243

    18.3464

    36.9

    EVAP

    INLET/OUTLET

    938

    32.0813

    5.0127

    40.01016

    41.21046

    .875 DIA MOUNTING HOLES (4)

    .88 KNOCKOUT

    REMOVABLEDISC HANDLE

    REMOVE BRKT.FOR SHIPPING

    ONLY

    CONTROLCONNECTION

    .88 KNOCKOUTSON OPPOSITE SIDE

    POWERCONNECTIONS

    23.5596

    77.21961

    1.334

    CIRCUIT 1CIRCUIT 2

    WGZ150CW-200CWPackaged Chiller

    331929901

  • 7/24/2019 I&M Manual_WGZ-1

    29/72

    IMM WGZC WGZ 030C through 200C 29

    Chillers with Remote Condenser

    Figure 16, WGZ 030CA through WGZ 060CA

    CHILLER WATER CONNECTIONSIZE (NOM) VICTAULIC

    CONDENSER WATER

    CONNECTION SIZE(NOM) VICTAULIC

    CENTER OF GRAVITYWGZ MODEL

    NUMBER

    IN (MM) A IN (MM) X Y Z

    WGZ030CA 2.5 (64) 21.6 (550) 4 (102) 67.3 22.8 13.3

    WGZ035CA 2.5 (64) 20.6 (523) 4 (102) 68.3 23.8 13.4

    WGZ040CA 2.5 (64) 19.2 (488) 4 (102) 67.9 23.9 13.5

    WGZ045CA 2.5 (64) 17.5 (444) 4 (102) 67.3 24.0 13.5

    WGZ050CA 2.5 (64) 15.8 (400) 4 (102) 67.2 24.5 13.5

    WGZ055CA 2.5 (64) 14.0 (356) 4 (102) 66.6 24.6 13.5

    WGZ060CA 2.5 (64) 12.3 (312) 4 (102) 66.1 24.7 13.6

    WGZ030-060CAREMOTE CONDENSER UNIT

    331929711

    " X "

    " Y "

    137.03480

    12.3312

    6.0152

    20.2512

    MICROTECH II USER INTERFACE

    CIRCUIT 1CIRCUIT 2

    1.38 DISCHARGECONNECTIONS

    .88 LIQUIDCONNECTIONS

    30.3770

    " Z "

    23.5597

    2.051

    30.0762

    2.051

    20.0508

    34.0864

    40.01016

    6.0152

    6.0151

    16.5419

    60.01524

    EVAPORATOR

    REMOVABLEDISC. HANDLE REMOVE BRKT.

    FOR SHIPPING

    ONLY

    POWERCONNECTIONS

    CONTROLCONNECTION

    .88 KNOCKOUTSON OPPOSITE SIDE

    .88 KNOCKOUTS

    ISOLATOR HOLES (4)

    OUTLET

    INLET

    LIQUIDCONNECTIONS

    EVAP. ANDDISCHARGECONNECTIONS

    25.9657

    41.51054

    " A "

    27.4696

    38.2971 87.9

    223498.82509

    11.4289

    10.4263

    OUTLET

    INLET

  • 7/24/2019 I&M Manual_WGZ-1

    30/72

    30 WGZ 030C through 200C IMM WGZC

    Figure 17, WGZ 070CA through WGZ 130CA

    CHILLER WATERCONNECTION SIZE

    (NOM) VICTAULIC

    COND.

    WATERCONN. SIZE

    VICTAULIC

    REFRIGERANTPIPING

    CONNECTION SIZE

    CENTER OF GRAVITY(IN.)

    WGZMODEL

    NUMBER

    IN (MM) A IN (MM) B DISC. C LIQ.

    T

    LEFTOVERHANG

    X Y Z

    WGZ070C 3 (76) 14.1 (359) 4 (102) 1.38 OD 1.13 OD N/A 71.5 29.3 14.9

    WGZ080C 3 (76) 13.7 (348) 4 (102) 1.62 OD 1.13 OD 6.3 (161) 74.9 30.1 15.0

    WGZ090C 3 (76) 11.9 (303) 4 (102) 1.62 OD 1.13 OD 6.6 (167) 75.7 30.4 15.1

    WGZ100C 3 (76) 11.0 (280) 4 (102) 1.62 OD 1.13 OD 6.6 (167) 75.2 30.6 15.2

    WGZ115C 3 (76) 7.5 (190) 4 (102) 1.62 OD 1.13 OD 6.6 (167) 73.8 30.8 15.2

    WGZ130C 3 (76) 4.4 (111) 4 (102) 1.62 OD 1.13 OD 6.6 (167) 72.6 30.9 15.3

    " T "

    " Y "

    " X "

    137.03480

    12.3312

    6.0152

    23.2588

    MICROTECH II USER INTERFACECIRCUIT 1CIRCUIT 2

    DISCHARGE CONNECTIONS "B"

    LIQUID CONNECTIONS "C"

    32.3821

    23.5597

    2.051

    30.0762

    2.051" Z "

    20.0508

    34.0864

    40.01016

    6.0152

    60.01524

    4.0

    101

    15.5394

    EVAPORATOR

    REMOVABLEDISC. HANDLE

    REMOVE BRKFOR SHIPPIN

    ONLYPOWER

    CONNECTIONS

    CONTROLCONNECTION

    .88 KNOCKOUTSON OPPOSITE SIDE

    .88 KNOCKOUTS

    ISOLATOR HOLES (4)

    OUTLET

    INLET

    LIQUID

    CONNECTIONS

    EVAP. ANDDISCHARGECONNECTIONS

    52.01322

    18.5469

    27.3694

    "A "

    13.3338

    12.4.253166.35

    38.2971

    89.22266

    98.82509

    OUTLET

    INLET

    WGZ070-130CAUnit less condenser

    331929811

    1.533

    5.2413

    1.533

    2.051

    30.0

    762

    2.051

    %%c.75

    ISOLATOR HOLES IN THEBOTTOM OF THE BASE

    19

    CONTROL BOX

    CIRCUIT 1CIRCUIT 2

    L1 L2

    L3L4

    M1 M2

    M3M4

    EVAP WATERCONNECTIONS

  • 7/24/2019 I&M Manual_WGZ-1

    31/72

    IMM WGZC WGZ 030C through 200C 31

    Figure 18, WGZ 150CA through WGZ 200CA

    CHILLER WATERCONNECTION SIZE

    (NOM) VICTAULIC

    CENTER OF GRAVITYWGZ MODELNUMBER

    IN (MM) X Y Z

    WGZ150C 8 (203) 79.1 43.2 15.3

    WGZ170C 8 (203) 80.1 43.6 15.4

    WGZ200C 8 (203) 79.7 44.0 15.4

    " Y "

    " X "

    154.03912

    2.051

    MICROTECH IIUSER INTERFACE

    CIRCUIT 1CIRCUIT 2

    WGZ150-200CAREMOTE CONDENSER UNIT

    331929911

    2.051

    30.0762

    2.051

    " Z "

    5.0127

    12.0

    305

    35.5902

    3.076

    75.01905

    12.0305

    34.0864

    40.01016

    4.0101

    5.0127

    REMOVABLEDISC. HANDLE

    REMOVE BRKT.FOR SHIPPING

    ONLY

    CONTROLCONNECTION

    .88 KNOCKOUTSON OPPOSITE SIDE

    .88 KNOCKOUTSISOLATOR HOLES (6)

    POWERCONNECTIONS

    (QTY 3)

    LIQUIDCONNECTIONS

    106.52705

    33.9862

    42.11069 119.3

    3030

    34.2867

    24.9631

    74.71898

    17.4443

    6.0152

    23.2588

    OUTLETINLET

    1.62 O.D. DISCHARGECONNECTIONS

    1.38 O.D. LIQUIDCONNECTIONS

    CIRCUIT 1 CIRCUIT 2

    2.360 7.9

    200

    14.5368

    13.4340

    3.690

    EVAPORATORINLET/OUTLET

    DISCHARGECIRCUIT 1 DISCHARGE

    CIRCUIT 2

    21.0533

    30.0762

    2.051

    2.051

    21.0533

    58.01473

    54.01372

    .75

    ISOLATOR HOLES IN THEBOTTOM OF THE BASE

    19

    CONTROL BOX

    CIRCUIT 1CIRCUIT 2

    L1 L2

    L3L4

    M1 M3

    M4M6

    M2

    M5

  • 7/24/2019 I&M Manual_WGZ-1

    32/72

    32 WGZ 030C through 200C IMM WGZC

    Physical Data

    Packaged Chillers

    Table 16, WGZ 030CW WGZ 055CW

    WGZ UNIT SIZE 30 35 40 45 50 55

    Unit capacity @ ARI tons, (kW) 30.0 (105.5) 34.6 (121.7) 40.7 (143.1) 45.5 (160.0) 51.4 (180.8) 56.4 (198.4)

    No. Circuits 2 2 2 2 2 2

    COMPRESSORS

    Nominal Tons 7.5 7.5 9 9 10 10 12 12 13 13 13 15

    Number Per Circuit 2 2 2 2 2 2 2 2 2 2 2 2

    CAPACITY REDUCTION STEPS - PERCENT OF COMPRESSOR DISPLACEMENT

    Staging, Circuit #1 in Lead 25 / 50 / 75 / 100 25 / 50 / 75 / 100 25 / 50 / 75 / 100 25 / 50 / 75 / 100 25 / 50 / 75 / 100 23 / 50 / 73 / 100

    Staging, Circuit #2 in Lead 25 / 50 / 75 / 100 25 / 50 / 75 / 100 25 / 50 / 75 / 100 25 / 50 / 75 / 100 25 / 50 / 75 / 100 27 / 50 / 77 / 100

    Oil Charge per Compressor oz., (l) 85 (2.5) 110 (3.3) 110 (3.3) 110 (3.3) 110 (3.3) 110 (3.3)

    CONDENSER

    Number 1 1 1 1 1 1

    No. Refrigerant Circuits 2 2 2 2 2 2

    Diameter, in., (mm) 10 (254) 10 (254) 10 (254) 10 (254) 10 (254) 10 (254)

    Tube Length, in., (mm) 120 (3048) 120 (3048) 120 (3048) 120 (3048) 120 (3048) 120 (3048)

    Design W.P.PSIG, (kPa):

    Refrigerant Side 500 (3447) 500 (3447) 500 (3447) 500 (3447) 500 (3447) 500 (3447)

    Water Side 232 (1599) 232 (1599) 232 (1599) 232 (1599) 232 (1599) 232 (1599)

    Pump-Out Capacity, lb., (kg) (3) 245.8 (111.7) 245.8 (111.7) 228.2 (103.7) 228.2 (103.7) 205.4 (93.4) 205.4 (93.4)

    Conn.In & Out, in, (mm) Victaulic 4 (102) 4 (102) 4 (102) 4 (102) 4 (102) 4 (102)

    Relief Valve, Flare In., (mm) (15.9) (15.9) (15.9) (15.9) (15.9) (15.9)

    Purge Valve, Flare In., (mm) (12.7) (12.7) (12.7) (12.7) (12.7) (12.7)

    Vent & Drain, in. (mm) NPT (6.4) (6.4) (6.4) (6.4) (6.4) (6.4)

    Liquid Subcooling Integral Integral Integral Integral Integral Integral

    EVAPORATOR, BRAZED-PLATENumber 1 1 1 1 1 1

    No. Refrigerant Circuits 2 2 2 2 2 2

    Water Volume, gallons, (l) 1.9 (7.1) 2.2 (8.3) 2.4 (9.1) 2.9 (11.0) 3.4 (12.8) 3.7 (14.0)

    Refrig. Side D.W.P. Psig, (kPa) 450 (3102) 450 (3102) 450 (3102) 450 (3102) 450 (3102) 450 (3102)

    Water Side D.W.P,. psig, (kPa) 653 (4500) 653 (4500) 653 (4500) 653 (4500) 653 (4500) 653 (4500)

    Conn. In & Out, in. (mm) Victaulic 2.5 (65) 2.5 (65) 2.5 (65) 2.5 (65) 2.5 (65) 2.5 (65)

    Relief Valve, Flare in., (mm) (15.9) (15.9) (15.9) (15.9) (15.9) (15.9)

    Vent & Drain Field Field Field Field Field Field

    UNIT DIMENSIONS

    Length In., (mm) 136.0 (3455) 136.0 (3455) 136.0 (3455) 136.0 (3455) 136.0 (3455) 136.0 (3455)

    Width In., (mm) 32.8 (832) 32.8 (832) 32.8 (832) 32.8 (832) 32.8 (832) 32.8 (832)

    Height In., (mm) 63.4 (1609) 63.4 (1609) 63.4 (1609) 63.4 (1609) 63.4 (1609) 63.4 (1609)

    UNIT WEIGHTS

    Operating Weight, lb., (kg) 2486 (1128) 2572 (1167) 2631 (1193) 2650 (1202) 2752 (1248) 2771 (1257)

    Shipping Weight, lb., (kg) 2410 (1093) 2496 (1132) 2539 (1152) 2558 (1160) 2639 (1197) 2658 (1206)

    Cir # 1,Opn. Charge, lb.,(kg) R410a 45 (20.5) 45 (20.5) 47 (21.4) 47 (21.4) 47 (21.4) 50 (22.7)

    Cir # 2,Opn. Charge, lb.,(kg) R410a 45 (20.5) 45 (20.5) 47 (21.4) 47 (21.4) 47 (21.4) 50 (22.7)

    Notes:

    1. Certified in accordance with ARI Standard 550/590-2003.2. 90% Full R-410a at 90F (32C) per unit.

  • 7/24/2019 I&M Manual_WGZ-1

    33/72

    IMM WGZC WGZ 030C through 200C 33

    Table 17, WGZ060CW - WGZ100CW

    WGZ UNIT SIZE 60 70 80 90 100

    Unit capacity @ ARI tons, (kW) (1) 60.5 (212.8) 70.8 (249.0) 78.3 (275.4) 88.0 (309.5) 97.8 (344.0)

    No. Circuits 2 2 2 2 2

    COMPRESSORS

    Nominal Tons 15 15 15/20 15/20 20 20 20 26 26 26

    Number per Circuit4 2 2 2 2 2 2 2 2 2 2

    CAPACITY REDUCTION STEPS - PERCENT OF COMPRESSOR DISPLACEMENT

    Staging, 4 Stages, Circuit #1 in Lead 25 / 50 / 75 / 100 22 / 50 / 72 / 100 25 / 50 / 75 / 100 25 / 50 / 75 / 100 25 / 50 / 75 / 100

    Staging, 4 Stages, Circuit #2 in Lead 25 / 50 / 75 / 100 22 / 50 / 72 / 100 25 / 50 / 75 / 100 25 / 50 / 75 / 100 25 / 50 / 75 / 100

    Oil Charge, per compressor oz. (l) 110 (3.3)110 (3.3)158 (4.7)

    110 (3.3)158 (4.7)

    158 (4.7)158(4.7)

    230(6.8)

    230 (6.8)

    CONDENSER

    Number 1 1 1 1 1

    No. Refrigerant Circuits 2 2 2 2 2

    Diameter, in. (mm) 10 (254) 14 (356) 14 (356) 14 (356) 14 (356)

    Tube Length, in. (mm) 120 (3048) 120 (3048) 120 (3048) 120 (3048) 120 (3048)

    Design W.P., psig (kPa):

    Refrigerant Side 500 (3447) 500 (3447) 500 (3447) 500 (3447) 500 (3447)

    Water Side 232 (1599) 232 (1599) 232 (1599) 232 (1599) 232 (1599)

    No. of Passes 2 2 2 2 2

    Pump-Out Capacity lb., (kg) (3) 205.4 (93.4) 415.1 (188.7) 397.5 (180.7) 371.1 (168.7) 344.7 (156.7)

    Conn. In & Out, in., (mm) Victaulic 4 (102) 4 (102) 4 (102) 4 (102) 4 (102)

    Relief Valve, Flare in., (mm) (15.9) (15.9) (15.9) (15.9) (15.9)

    Purge Valve, Flare in. (mm) (12.7) (12.7) (12.7) (12.7) (12.7)

    Vent & Drain, in. (mm) NPT (6.4) (6.4) (6.4) (6.4) (6.4)

    Liquid Subcooling Integral Integral Integral Integral Integral

    EVAPORATOR, BRAZED-PLATE

    Number 1 1 1 1 1

    No. Refrigerant Circuits 2 2 2 2 2

    Water Volume, gallons (l) 4.2 (15.9) 6.4 (24.3) 6.6 (24.9) 7.5 (28.4) 8.0 (30.2)Refrigerant Side D.W.P., psig, (kPa) 450 (3102) 450 (3102) 450 (3102) 450 (3102) 450 (3102)

    Water Side D.W.P., psig, (kPa) 653 (4500) 653 (4500) 653 (4500) 653 (4500) 653 (4500)

    Conn. In & Out, in. (mm) Victaulic 2.5 (65) 3 (76) 3 (76) 3 (76) 3 (76)

    Relief Valve, Flare in., (mm) (15.9) (15.9) (15.9) (15.9) (15.9)

    Vent & Drain Field Field Field Field Field

    UNIT DIMENSIONS

    Length, in. (mm) 136.0 (3455) 143.3 (3639) 149.6 (3799) 149.4 (3795) 149.4 (3795)

    Width, in. (mm) 32.8 (832) 35.0 (889) 35.0 (889) 35.0 (889) 35.0 (889)

    Height, in. (mm) 63.4 (1609) 65.5 (1664) 65.5 (1664) 65.5 (1664) 65.5 (1664)

    UNIT WEIGHTS

    Operating Wt, lb., (kg) 2801 (1271) 3887 (1763) 4302 (1951) 4507 (2044) 4678 (2122)

    Shipping Wt, lb. (kg) 2688 (1219) 3746 (1699) 4145 (1880) 4327 (1963) 4474 (2029)

    Cir # 1,Opn. Charge, lb, (kg) R410a 50 (22.7) 74 (34.1) 80 (36.4) 80 (36.4) 90 (40.9)

    Cir # 2,Opn. Charge, lb.,(kg) R410a 50 (22.7) 74 (34.1) 80 (36.4) 80 (36.4) 90 (40.9)

    Notes:

    1. Certified in accordance with ARI Standard 550/590-2003.-2. Units WGZ030 to 130 have two parallel compressors per circuit. Units WGZ150 to 200 have three parallel compressors per circuit.3. 90% Full R-410a at 90F (32C) per unit.

  • 7/24/2019 I&M Manual_WGZ-1

    34/72

    34 WGZ 030C through 200C IMM WGZC

    Table 18, WGZ115CW - WGZ200CW

    WGZ UNIT SIZE 115 130 150 170 200

    Unit capacity @ ARI. tons, (kW) (1) 112.9 (397.1) 125.4 (441.0) 146.6 (515.6) 169.3 (595.4) 188.1 (661.5)

    No. Circuits 2 2 2 2 2

    COMPRESSORS

    Nominal Tons 26/30 26/30 30 30 26 26 26 30 30 30

    Number Per Circuit 2 2 2 2 3 3 3 3 3 3

    CAPACITY REDUCTION STEPS - PERCENT OF COMPRESSOR DISPLACEMENT

    Staging, 4 Stages, Circuit #1 in Lead 22 / 50 / 72 / 100 25 / 50 / 75 / 10017 / 33 / 50 / 67

    / 83 / 10015 / 33 / 48 / 67 /

    81 / 10017 / 33 / 50 / 67 /

    83 / 100

    Staging, 4 Stages, Circuit #2 in Lead 22 / 50 / 72 / 100 25 / 50 / 75 / 10017 / 33 / 50 / 67

    83 / 10019 / 33 / 52 / 67

    86 /10017 / 33 / 50 / 67 /

    83 / 100

    Oil Charge, per compressor oz. (l)230 (6.8 )/213 (6.3)

    230 (6.8 )/213 (6.3)

    213 (6.3) 230 (6.8) 230 (6.8) 213 (6.3) 213 (6.3)

    CONDENSER

    Number 1 1 1 1 1

    No. Refrigerant Circuits 2 2 2 2 2

    Diameter, in. (mm) 14 (356) 14 (356) 16 (406.4) 16 (406.4) 16 (406.4)

    Tube Length, in. (mm) 120 (3048) 120 (3048) 144 (3658) 144 (3658) 144 (3658)

    Design W.P., psig (kPa):

    Refrigerant Side 500 (3447) 500 (3447) 500 (3447) 500 (3447) 500 (3447)

    Water Side 232 (1599) 232 (1599) 232 (1599) 232 (1599) 232 (1599)

    Pump-Out Capacity lb., (kg) (3) 344.7 (156.7) 344.7 (156.7) 572.3 (260.1) 508.9 (231.3) 508.9 (231.3)

    Water Conn In & Out, in., (mm) (4) 4 (102) 4 (102) 5 (127) 5 (127) 5 (127)

    Relief Valve, Flare in., (mm) (15.9) (15.9) (15.9) (15.9) (15.9)

    Purge Valve, Flare in. (mm) (12.7) (12.7) (12.7) (12.7) (12.7)

    Vent & Drain, in. (mm) FPT 6.4) 6.4) 6.4) 6.4) 6.4)

    Liquid Subcooling Integral Integral Integral Integral Integral

    EVAPORATOR, BRAZED-PLATE SHELL-AND-TUBE

    Number 1 1 1 1 1

    No. Refrigerant Circuits 2 2 2 2 2Water Volume, gallons (l) 8.5 (32.1) 10.5 (39.7) 57.6 (218.0) 56.9 (215.4) 56.9 (215.4)

    Refrigerant Side D.W.P., psig, (kPa) 450 (3102) 450 (3102) 450 (3102) 450 (3102) 450 (3102)

    Water Side D.W.P., psig, (kPa) 653 (4500) 653 (4500) 150 (1034) 150 (1034) 150 (1034)

    Water Conn.In & Out, in. (mm) Victaulic 3 (76) 3 (76) 8 (203) 8 (203) 8 (203)

    Relief Valve, Flare in., (mm) (15.9) (15.9)

    Drain & Vent size, in. (mm) Field Field (12.7) (12.7) (12.7)

    UNIT DIMENSIONS

    Length, in. (mm) 149.4 (3795) 149.4 (3795) 170.2 (4322) 170.2 (4322) 170.2 (4322)

    Width, in. (mm) 35.0 (889) 35.0 (889) 36.5 (927) 36.5 (927) 36.5 (927)

    Height, in. (mm) 65.5 (1664) 65.5 (1664) 77.7 (1973) 77.7 (1973) 77.7 (1973)

    UNIT WEIGHTS

    Operating Wt, lb., (kg) 4712 (2137) 4772 (2165) 7370 (3343) 7758 (3519) 7873 (3571)Shipping Wt, lb. (kg) 4508 (2045) 4568 (2072) 6581 (2985) 6921 (3139) 7036 (3192)

    Cir #1, Op. Charge, lb., (kg) R-410a 100 (45.5) 100 (45.5) 150 (68.2) 150 (68.2) 150 (68.2)

    Cir #2, Op. Charge, lb., (kg) R-410a 100 (45.5) 100 (45.5) 150 (68.2) 150 (68.2) 150 (68.2)

    Notes:

    1. Certified in accordance with ARI Standard 550/590-2003.2. Units WGZ030 to 130 have two parallel compressors per circuit, units WGZ150 to 200 have three parallel compressors per circuit.3. 90% Full R-410a at 90F (32C) per unit.

  • 7/24/2019 I&M Manual_WGZ-1

    35/72

    IMM WGZC WGZ 030C through 200C 35

    Chillers with Remote CondenserTable 19, WGZ030CA - WGZ055CAWGZ UNIT SIZE 30 35 40 45 50 55

    Tons, (kW), 44F LWT, 125F SDT 26.6 (93.5) 30.5 (107.3) 35.2 (123.8) 39.8 (139.9) 45.8 (161.0) 50.3 (176.8)

    No. Circuits 2 2 2 2 2 2

    COMPRESSORS

    Nominal Tons 7.5 7.5 9 9 10 10 12 12 13 13 13 15

    Number per Circuit 2 2 2 2 2 2 2 2 2 2 2 2

    Staging, Circuit #1 in Lead 25 / 50 / 75 / 100 25 / 50 / 75 / 100 25 / 50 / 75 / 100 25 / 50 / 75 / 100 25 / 50 / 75 / 100 23 / 50 / 73 / 10

    Staging, Circuit #2 in Lead 25 / 50 / 75 / 100 25 / 50 / 75 / 100 25 / 50 / 75 / 100 25 / 50 / 75 / 100 25 / 50 / 75 / 100 27 / 50 / 77 / 10

    Oil Charge, per comp. oz, (l) 85 (2.5) 110 (3.3) 110 (3.3) 110 (3.3) 110 (3.3) 110 (3.3)

    EVAPORATOR, BRAZED PLATE

    No. Refrigerant Circuits 2 2 2 2 2 2

    Water Volume, gallons, (l) 1.9 (7.1) 2.2 (8.3) 2.4 (9.1) 2.9 (11.0) 3.4 (12.8) 3.7 (14.0)

    Refrig. Side D.W.P. Psig, (kPa) 450 (3102) 450 (3102) 450 (3102) 450 (3102) 450 (3102) 450 (3102)

    Water Side D.W.P. Psig, (kPa) 653 (4500) 653 (4500) 653 (4500) 653 (4500) 653 (4500) 653 (4500)

    Inlet & Outlet, in., (mm) (1) 2.5 (65) 2.5 (65) 2.5 (65) 2.5 (65) 2.5 (65) 2.5 (65)

    Relief Valve, Flare in., (mm) (15.9) (15.9) (15.9) (15.9) (15.9) (15.9)

    Drain & Vent Field Field Field Field Field Field

    UNIT DIMENSIONS

    Length In., (mm) 137.0 (3480) 137.0 (3480) 137.0 (3480) 137.0 (3480) 137.0 (3480) 137.0 (3480)

    Width In., (mm) 34.0 (864) 34.0 (864) 34.0 (864) 34.0 (864) 34.0 (864) 34.0 (864)

    Height In., (mm) 60.0 (1524) 60.0 (1524) 60.0 (1524) 60.0 (1524) 60.0 (1524) 60.0 (1524)

    UNIT WEIGHTS

    Operating Weight, lb., (kg) 1606 (728) 1698 (770) 1715 (778) 1738 (788) 1773 (804) 1795 (814)

    Shipping Weight, lb., (kg) 1580 (717) 1670 (758) 1685 (764) 1704 (773) 1735 (787) 1754 (796)

    Table 20, WGZ060CA - WGZ100CAWGZ UNIT SIZE 60 70 80 90 100

    Tons, (kW) 44F LWT, 125F SDT 53.9 (189.5) 61.3 (215.7) 68.6 (242.0) 77.7 (273.3) 86.6 (304.5)

    No. Circuits 2 2 2 2 2

    COMPRESSORS

    Nominal Tons 15 15 15/20 15/20 20 20 20 26 26 26Number Per Circuit 2 2 2 2 2 2 2 2 2 2

    Staging, Circuit #1 in Lead 25 / 50 / 75 / 100 22 / 50 / 72 / 100 25 / 50 / 75 / 100 25 / 50 / 75 / 100 25 / 50 / 75 / 100

    Staging, Circuit #2 in Lead 25 / 50 / 75 / 100 22 / 50 / 72 / 100 25 / 50 / 75 / 100 25 / 50 / 75 / 100 25 / 50 / 75 / 100

    Oil Charge, per compressor oz. (l) 110 (3.3) 110 (3.3) 158 (4.7) 158 (4.7) 230 230 (6.8)

    EVAPORATOR, BRAZED PLATE

    No. Refrigerant Circuits 2 2 2 2 2

    Water Volume, gallons (l) 4.2 (15.9) 6.4 (24.3) 6.6 (24.9) 7.5 (28.4) 8.0 (30.2)

    Refrigerant Side D.W.P., psig, (kPa) 450 (3102) 450 (3102) 450 (3102) 450 (3102) 450 (3102)

    Water Side D.W.P., psig, (kPa) 653 (4500) 653 (4500) 653 (4500) 653 (4500) 653 (4500)

    Inlet & Outlet, in. (mm) (2) 2.5 (63) 3 (76) 3 (76) 3 (76) 3 (76)

    Relief Valve, Flare in., (mm) (15.9) (15.9) (15.9) (15.9) (15.9)

    Drain & Vent Field Field Field Field Field

    UNIT DIMENSIONS

    Length, in. (mm) 137.0 (3480) 137.0 (3480) 137.0 (3480) 137.0 (3480) 137.0 (3480)Width, in. (mm) 34.0 (864) 34.0 (864) 34.0 (864) 34.0 (864) 34.0 (864)

    Height, in. (mm) 60.0 (1524) 60.0 (1524) 60.0 (1524) 60.0 (1524) 60.0 (1524)

    UNIT WEIGHTS

    Operating Wt, lb., (kg) 1816 (824) 2474 (1122) 2787 (1264) 2928 (1328) 3050 (1383)

    Shipping Wt, lb. (kg) 1771 (803) 2406 (1091) 2717 (1232) 2851 (1293) 2968 (1346)

    Notes:1. Condenser and field piping not included.

  • 7/24/2019 I&M Manual_WGZ-1

    36/72

    36 WGZ 030C through 200C IMM WGZC

    Table 21, WGZ115CA WGZ200CA

    WGZ UNIT SIZE 115 130 150 170 200

    Tons, (kW)44F LWT, 125F SDT 100.1 (352.2) 111.4 (391.7) 129.9 (456.8) 150.2 (528.3) 170.6 (599.8)

    No. Circuits 2 2 2 2 2

    COMPRESSORS

    Nominal Tons 26/30 26/30 30 30 26 26 26 30 30 30

    Number Per Circuit 2 2 2 2 3 3 3 3 3 3

    Staging, Circuit #1 in Lead 22 / 50 / 72 / 100 25 / 50 / 75 / 100 17 / 33 / 50 / 67 /83 / 100

    15 / 33 / 48 / 67 /81 / 100

    17 / 33 / 50 / 67 /83 / 100

    Staging, Circuit #2 in Lead 22 / 50 / 72 / 100 25 / 50 / 75 / 10017 / 33 / 50 / 67 /

    83 / 10019 / 33 / 52 / 67 /

    86 / 10017 / 33 / 50 / 67 /

    83 / 100

    Oil Charge, per compressor oz. (l)230 (6.8 )213 (6.3)

    213 (6.3) 230 (6.8) 230 (6.8) 213 (6.3) 213 (6.3)

    EVAPORATOR, BRAZED PLATE------------------------------------------------ SHELL-AND-TUBE

    No. Refrigerant Circuits 2 2 2 2 2

    Water Volume, gallons (l) 8.5 (32.1) 10.5 (39.7) 57.6 (218.0) 56.9 (215.4) 56.9 (215.4)

    Refrigerant Side D.W.P., psig, 450 (3102) 450 (3102) 450 (3102) 450 (3102) 450 (3102)

    Water Side D.W.P., psig, (kPa) 653 (4500) 653 (4500) 150 (1034) 150 (1034) 150 (1034)

    Water Connections:

    In & Out, in. (mm), victaulic 3 (76) 3 (76) 8 (203) 8 (203) 8 (203)

    Relief Valve, Flare in., (mm) (15.9) (15.9) (15.9) (15.9) (15.9)

    Drain & Vent Field Field (12.7) (12.7) (12.7)

    UNIT DIMENSIONS

    Length, in. (mm) 137.0 (3480) 137.0 (3480) 154.0 (3912) 154.0 (3912) 154.0 (3912)

    Width, in. (mm) 34.0 (864) 34.0 (864) 34.0 (864) 34.0 (864) 34.0 (864)

    Height, in. (mm) 60.0 (1524) 60.0 (1524) 75.0 (1905) 75.0 (1905) 75.0 (1905)

    UNIT WEIGHTS

    Operating Wt, lb., (kg) 3120 (1415) 3194 (1449) 5279 (2395) 5385 (2443) 5498 (2494)

    Shipping Wt, lb. (kg) 3035 (1377) 3091 (1402) 4779 (2168) 4891 (2219) 5004 (2270)

    Notes:1. Condenser and field piping not included

    Operating Limits

    Equipment room temperature limits, operating or standby: 32F to 104F (0C to 40C) Maximum allowable condenser water pressure is 232 psig (1599 kPa).

    Maximum design saturated discharge temperature is 140F (60C).

    Maximum allowable water temperature to evaporator in a non-operating cycle is 100F (37.8C).

    Maximum entering water temperature for operating cycle is 90F (32.2C) (during system changeover

    from heating to cooling cycle).

    Minimum leaving water temperature from the evaporator without freeze protection is 40F (4.4C).

    Minimum entering tower condenser water temperature is 60F (15.6C).

    Maximum condenser leaving water temperature is 115F (46.1C)

    For remote air-cooled condensers, the temperature difference between the saturated discharge temperature

    and the outside air temperature (TD) must be between 15 and 35 degrees F and the saturated dischargetemperature cannot exceed 135F.

  • 7/24/2019 I&M Manual_WGZ-1

    37/72

    IMM WGZC WGZ 030C through 200C 37

    Components

    Figure 19, Compressor Locations

    4 2 3 1

    Circuit 2 Circuit 1Control Panel

    EvaporatorEvaporator andCondenserConnections

    NOTE: Models WGZ 150 to 200 add a #5 compressor to circuit #1 and a #6 compressor to

    circuit #2.

    Table 22, Major Components

    System #1 System #2 Expansion ValveWGZ-C

    Unit

    SizeComp. #1 Comp. #3 Comp. #2 Comp. #4

    Evap.

    Vessel

    Size

    Cond.

    Vessel

    Size System #1 System #2

    30 ZP90KCE ZP90KCE ZP90KCE ZP90KCE ACH130-90DQ C1010-47 OZE-20-GA-BP15 OZE-20-GA-BP15

    35 ZP103KCE ZP103KCE ZP103KCE ZP103KCE ACH130-102DQ C1010-47 OZE-20-GA-BP15 OZE-20-GA-BP15

    40 ZP120KCE ZP120KCE ZP120KCE ZP120KCE ACH130118DQ C1010-57 OZE-20-GA-BP15 OZE-20-GA-BP15

    45 ZP137KCE ZP137KCE ZP137KCE ZP137KCE ACH130-138DQ C1010-57 OZE-25-GA-BP15 OZE-25-GA-BP15

    50 ZP154KCE ZP154KCE ZP154KCE ZP154KCE ACH130-158DQ C1010-70 OZE-25-GA-BP15 OZE-25-GA-BP15

    55 ZP154KCE ZP154KCE ZP182KCE ZP182KCE ACH130-178DQ C1010-70 OZE-25-GA-BP15 OZE-35-GA-BP15

    60 ZP182KCE ZP182KCE ZP182KCE ZP182KCE ACH130-198DQ C1010-70 OZE-35-GA-BP15 OZE-35-GA-BP15

    70 ZP182KCE ZP235KCE ZP182KCE ZP235KCE ACH250-122DQ C1410-88 OZE-35-GA-BP15 OZE-35-GA-BP15

    80 ZP235KCE ZP235KCE ZP235KCE ZP235KCE ACH350-126DQ C1410-98 OZE-50-GA-BP15 OZE-50-GA-BP15

    90 ZP235KCE ZP235KCE ZP295KCE ZP295KCE ACH350-142DQ C1410-113 OZE-50-GA-BP15 OZE-50-GA-BP15

    100 ZP295KCE ZP295KCE ZP295KCE ZP295KCE ACH350-152DQ C1410-128 OZE-50-GA-BP15 OZE-50-GA-BP15

    115 ZP295KCE ZP385KCE ZP295KCE ZP385KCE ACH350-182DQ C1410-128 OZE-60-GA-BP15 OZE-60-GA-BP15

    130 ZP385KCE ZP385KCE ZP385KCE ZP385KCE ACH350-210DQ C1410-128 OZE-60-GA-BP15 OZE-60-GA-BP15

    150 (3) ZP295KCE (3) ZP295KCE EV34191111/9NS C1612-156 SEHI100-30-S SEHI100-30-S

    170 (3) ZP295KCE (3) ZP385KCE EV34191212/7NS C1612-186 SEHI100-30-S SEHI100-30-S

    200 (3) ZP385KCE (3) ZP385KCE EV34191212/7NS C1612-186 SEHI100-30-S SEHI100-30-S

  • 7/24/2019 I&M Manual_WGZ-1

    38/72

    WGZ 030C through 200C IMM WGZC

    Wiring

    Field Wiring, Power

    The WGZ C vintage chillers are supplied standard with compressor contactors and power terminal block,

    designed for multi-point power supply to the unit, no compressor circuit breakers. Available options are:

    Single-point connection to power block with compressor circuit breakers

    Single-point connection to disconnect switch with compressor circuit breakersHigh short circuit current rating with single-point disconnect switch

    Multi-point connection to disconnect switch, no compressor circuit breakers

    A factory installed control circuit transformer is standard. Optionally, a field-installed control power source

    can be wired to the unit.

    Wiring and conduit selections must comply with the National Electrical Code and/or local requirements.

    An open fuse indicates a short, ground, or overload. Before replacing a fuse or restarting a compressor, the

    trouble must be found and corrected. Tables in the Electrical Data section (page 40) give specific

    information on recommended wire sizes.

    Unit power inlet wiring must enter the control box through the right