    MELINK INTELLI-HOOD-2 CONTROLS

    KEYPAD DISPLAYS AND AUDIBLE SOUNDS

    Typical Display

    Normal Operation

    In Normal Operation, the keypad will cycle through 4 hoods (H-1, H-2 ) displaying a

    bar graph for each hood channel indicating the fan speed of that channel.

    Clean Light Blank or Flashing Red and Green

    Clean Light should be blank at all times of Normal Operation. Clean Light will flash red

    and green if there is an Optics Fault. See Optics Fault in the Troubleshooting list

    following.

    Fault L ight Blank or Green

    In Normal Operation, fault light will be blank or green. A blank fault light indicates

    Normal Operation with no faults. A green fault light indicates that the system is

    receiving a digital input on one of the digital input terminals 25 through 33. A green fault

    light is a normal occurrence on many systems.

    Fault Light Red

    Fault light will change to red in the case of any fault. See fault codes in the

    Troubleshooting list following.

    Sounds

    Keypad is typically silent. In Normal Operation, it will beep only when buttons are

    pressed such as turning it on/off or turning lights on/off. Keypad will beep if it is

    commanded by an external input to turn on using Remote on/off function. Keypad may

    beep indicating other problems. See Troubleshooting list following.

  • 8/13/2019 IH2 Detailed Troubleshooting Guide

    2/10

    MELINK INTELLI-HOOD-2 CONTROLS

    TROUBLESHOOTING

    SYMPTOMS AND REPAIR ACTIONS

    1. Keypad appears normal, but fans are not running.

    a. Check if VFDs are running. Check VFD maximum speed and amp draw.

    b. Check if fan disconnect switch is on.

    c. Check if fan belt is adjusted for proper tension.

    2. When the Fans button is pressed, nothing happens, The keypad does not light up

    and the fans do not starta. Check programming that Hx-06 is set correctly. If there are no sensors

    programmed, then the system will not function.

    b. Check programming that the Fans button is not disabled, parameter SY-25

    c. Check programming that there are no inputs programmed for Remote

    Enable, parameters SY-04, SY-05, Hx-11.

    3. Keypad displays -E, such as H2-E

    a. -E indicates that system is in Emergency Bypass Mode. Press 100%

    Button to take the system out of Emergency Bypass Mode. Use the Fans

    Button to turn the system on in Normal Mode.

    4. Fans shut off every 10 minutes.

    a. The default timer length of the Emergency Bypass Timer is 10 minutes.

    Customer is likely using the 100% Button to turn the system on, system runs

    for 10 minutes, and then shut off. Customer then presses 100% again and

    repeats the cycle. -E indicates that system is in Emergency Bypass Mode.

    Press 100% Button to take the system out of Emergency Bypass Mode.

    Use the Fans Button to turn the system on in Normal Mode.

    5. Keypad is blank. Fans are running

    a. System is likely in fire mode. Check that the main processor has 120VAC

    power.

  • 8/13/2019 IH2 Detailed Troubleshooting Guide

    3/10

    6. Keypad is blank. Fans are not running.

    a. Press the Fans Button to turn on the fans.b. On/Off command may be by another device other than the Fans button.

    On/Off command may be from a toggle switch, water wash panel, or Building

    automation system. Refer to system setup drawings and installation

    documentation for that site.

    c. System may be disabled by another device. Refer to system setup drawings

    and installation documentation for that site.

    d. Check the VFDs for faults.

    7. Keypad shows a low temperature fault as shown by a lowercase h,

    a. Processor is reading an extremely low resistance on the temperature sensor

    circuit.

    b. Check that the number of temperature probes installed matches the number

    of temperature probes programmed.

    c. Check for a damaged component that might be causing a short on the

    temperature circuit. Sensor cables, Temperature-Ys, APU Header Boards,

    Optic Cables, and Optic Sensors are all possible causes.

    8. Keypad shows a high temperature fault as shown by uppercase H,

    a. Processor is reading an extremely high resistance on the temperature sensorcircuit.

    b. Check to see that temperature sensors are connected.

    c. Check that the number of temperature probes installed matches the number

    of temperature probes programmed.

    d. Check for a damaged component that might be causing an open loop on the

    temperature circuit. Sensor cables, Temperature-Ys, APU Header Boards,

    Optic Cables, and Optic Sensors are all possible causes.

    9. Keypad shows a VFD Fault, such as F3-U

    a. Check cable connections from VFD to processor

    b. Check that VFDs are on. All VFDs wired to the system must be on.

    c. Check VFDs for actual VFD faults, address the VFD faults per VFD

    documentation

    d. Check the Simplissimo programming for VFD type and addresses of the

    VFDs

    e. Check VFD enable jumper

  • 8/13/2019 IH2 Detailed Troubleshooting Guide

    4/10

    10. Keypad shows a low optic fault, F1-o,

    a. Check that optics are connected to the hood channel indicated.b. Clean optic lenses

    c. Check for obstructions such as fire suppression pipes between the Emitter

    and Receiver

    d. Increase the gain switch of the Receiver

    e. Check for a damaged component that might be causing an open loop on the

    temperature circuit. Sensor cables, Temperature-Ys, APU Header Boards,

    Optic Cables, and Optic Sensors are all possible causes.

    11. Keypad shows a high optic fault, o in the upper part of 7-segment display,

    a. Optic signal is saturated, too strong. Reduce the gain setting on the Receiver

    board.

    12. Keypad shows a temperature fault on one of the auxiliary temperature channels,

    F5-h or F6-h

    a. Temperature channel 5 is the supply temperature port. Temperature channel

    6 is the kitchen space temperature port. Connect a temperature sensor if

    applicable.

    b. Check parameter SY-07, economizer mode. Economizer mode will trigger

    processor to look for both supply and kitchen temperaturesc. Check parameter Hx-10, short cycle ratio. Short cycle hoods require a supply

    temperature sensor.

    13. Keypad shows a phone fault, F-PH

    a. Check that the telephone line (analog) is connected and that the line is

    operational

    b. Check that modem is installed on autocal board

    c. Check programming parameter SY-34

    14. Keypad display d-on when the fan button is pressed.

    a. The system is Disables and on or more outputs are programmed for MUA

    Damper. In this mode, the output is activated for 2 minutes waiting for

    something to occur which will Enable and Start the system. If the Enable and

    Start inputs do not occur in the 2 minute period, the system will shut off.

    b. Check parameters SY-04, SY-05, and HX-11 for a parameter programmed for

    Remote Enable. Provide the enable closure or un-program the setting.

  • 8/13/2019 IH2 Detailed Troubleshooting Guide

    5/10

    15. Vertical Bar graph is flashing and keypad will not shut off the fans

    a. System is in exhaust temp alarm mode.b. Press the up arrow to check temperatures. Verify temperatures are correct.

    c. Check Hood Parameter Hx04

    d. Check the number of temperature probes programmed and check actual

    number installed.

    16. Red text display of the keypad scrolls through the hoods H-1, H-2, etc, but the bar

    graph is does not light up at all.

    a. Check that parameters Hx08 is correctly programmed.

    b. Check that VFD type is correct Hx19 and Sy32

    c. If there is a situation of primary/secondary VFDs using parameters Hx08 and

    Hx09, verify that both VFDs are connected and functional.

    17. VFDs cycle on and off when system is on in normal mode.

    a. Check VFD for faults.

    b. If there is a situation of primary/secondary VFDs using parameters Hx08 and

    Hx09, verify that both VFDs are connected and functional.

    18. Keypad has a constant tone noise. Fans are at full speed.

    a. This is the optic block function. Optic Receiver is seeing zero light from theEmitter. If there optic sensors are blocked for 15 minutes, this audible alarm

    will occur. If the user presses, any button, optic fault will display on the

    keypad but the fans will not be locked at full speed. The fans will run as

    temperature-only.

    b. Remove the solid obstruction.

    19. Keypad is making a heartbeat beeping noise: continuous short beeps occurring

    about every second

    a. This beep noise is indicative of a 24V short in the hood sensor circuit. The

    beep occurs because a current limiting device is cycling processor boardpower. The processor is rebooting itself.

    b. Unplug all hood sensor cables.

    c. Plug cables in one at a time to find the problem hood sensor circuit. Then

    inspect/replace cables or sensors to fix the problem.

  • 8/13/2019 IH2 Detailed Troubleshooting Guide

    6/10

    20. Fan increases in speed when the optics are blocked but they never slow down.

    a. Check the programming of the clock. Press the Enter key to see the systemtime. If it shows 1200, A, 1 (12 midnight on Sunday), then you know that the

    processor time was not programmed. Program the clock using SY-12.

    b. After correcting the programming, make sure that the clock battery backup

    works correctly. Turn off the main power switch on the power board. Turn it

    back on. When you turn it back on, check the time again using the keypad. If

    the system time has reverted back to 12:00 midnight, then troubleshoot the

    battery of the autocal board.

  • 8/13/2019 IH2 Detailed Troubleshooting Guide

    7/10

    VFD TROUBLESHOOTING

    Allen Bradley Powerflex 4 VFDs

    Used On Melink Intelli-Hood

    Refer to the Powerflex 4 Quickstart manual for basic information about the VFD.

    Page 8: explains how to navigate the display and programming settings.

    Page 9, 10, 11: lists all of the display and programming parameters

    Page 11: describes the fault codes.

    In addition to the information in the Quickstart Manual, Melink Corporation suggests the following

    additional troubleshooting steps.

    Resetting the VFD and Restarting It.

    When the VFD is displaying a fault Fxxx, clear the fault by pressing the Red stop button on the face of

    the VFD. To restart the fans, shut them off and restart them. In most cases, use the Melink keypad Fans

    button to do this. In some other applications, use the water-wash panel or other switch.

    VFD does not accelerate to full speed

    Turn off the IO Processor to put drive in fire more or use programming to put the VFD in Hand Mode, ifVFD will not accelerate to the expected full speed (60Hz) check parameters P031 and P032. These

    parameters should never be changed off of their default values but sometimes they get changed. For

    example, if the motor is a 460VAC motor and somebody changes the P031 to something less than 460V,

    then the VFD will not ever output more than P031 and motor will never go full speed.

    F3: Power Loss

    Allen-Bradley Explanation:

    o Monitor the incoming AC line for low voltage or line power interruption

    Melink Explanation

    o This fault is a problem with low voltage on the input side of the VFD. The most likely time to

    see this fault is at startup of a new system. Once a system has been started and operating

    for many weeks, the fault rarely occurs.

    Check the incoming phases on the VFD to make sure that they are all at even

    voltage. Check phase-to-phase, as well as each phase to ground.

    Check that all wire terminals are tight.

    Check the circuit breaker that supplies power to the drive. Replace the breaker.

  • 8/13/2019 IH2 Detailed Troubleshooting Guide

    8/10

    F5: Overvoltage

    Allen-Bradley Explanation:o Monitor the AC line for high line voltage or transient conditions. Bus overvoltage can also

    be caused be motor regeneration. Extend the deceleration time or install dynamic brake

    option.

    Melink Explanation

    o This is the most difficult fault to troubleshoot. It has many possible causes.

    o In Intelli-hood applications, the most likely cause of this fault is motor failure. Many

    exhaust fan motors are not inverter-duty. They cannot be operated by a VFD. The

    insulation of the windings is weak, it breaks down, and the windings short together.

    Shut off the disconnect switch between the motor and the VFD.

    Restart the VFD. If the VFD runs, while disconnected from the motor, then the

    motor needs to be replaced. Make sure that the replacement motor is InverterDuty rated or Class F insulation, but these indicators really dont tell you that motor

    will truly work with a VFD.

    Tell the electrician on site to remove the wiring from the VFD and wire directly to

    the motor. If the breaker trips or motor fails in this way, then you can tell him that

    the VFD is fine.

    o If this fault occurs during deceleration of a large inertia fan, extend the deceleration time.

    Parameter P040 sets the deceleration time. By default, Intelli-hood setting is 60

    seconds. Change it to 90 to 120 seconds.

    o Another thing to try is Parameter P037 Stop Mode

    By default, Intelli-hood uses setting 1, Coast to Stop. Change to setting 0, ramp to

    stop, CF.

    o Set the minimum speed on the VFD P034 to 60 HZ. The drive will stay at full speed at all

    times. Let the VFD run at full speed in this way. This might tell us that the problem is in

    the motor. If F5 faults occur when the VFD is not decelerating, then the problem has

    nothing to do with motor regeneration.

    o High input power can cause this fault. Check voltage at the input terminals. Line reactor

    may smooth out the variances in input voltage.

    o Output Filter and/or brake resistor will reduce the feedback voltage the drive sees from the

    motor. These options are possible.

    o Melink has seen cases where a bad disconnect switch caused this fault. It is similar to a

    short in the motor windings.

    F7: Motor Overload

    Allen-Bradley Explanation:

    o An excessive motor load exists. Reduce load so drive output current does not exceed the

    current set by P033

    Melink Explanation

    o Melink recommends that the Motor Overload parameter P033 be set to the motor FLA plus

    10%. Verify that P033 is correct.

  • 8/13/2019 IH2 Detailed Troubleshooting Guide

    9/10

    o Set the display to Operating Amps (d003). Restart the fans and watch the amps to see if the

    amps go above the level set at P033.o If F7 occurs, the VFD will shut down, restart, and ramp up again. It will try to restart 5 times.

    If it gets F7 fault 5 times in a row, it will fault to F033 and stop restarting.

    o Check the fan rotation direction. A fan spinning backwards will have higher amp draw than

    forward rotation. Reverse direction by switching any 2 phase on the output of the VFD. You

    can switch the phase at the VFD output terminals or at the motor.

    Note that if this is a bypass VFD, check direction both in drive mode and in bypass

    mode. Check direction in drive mode first. Correct drive mode if necessary. Then

    check bypass mode. If the direction is wrong in bypass mode, switch any two phase

    on the input side of the bypass.

    o Slow down the fan to get the Operating Amps under the FLA of the motor. Adjust the

    pulley on the fan or reduce the maximum speed of the VFD. Use parameter P035 to reduce

    the maximum speed of the VFD.

    Keep in mind that the minimum operating speed of the VFD should be kept above

    18Hz. For example, the minimum speed of Intelli-hood is 40%, then P35 should be

    kept above 45 Hz.

    o Adjust S-Curve parameter A083.

    Typically Melink sets this to 20%. Change to 30 or 40%. This extends the

    acceleration time, but makes acceleration smoother and reduces the maximum amp

    draw.

    o Adjust Start Boost Parameter, A084 or S-Curve parameter A083.

    Typically Melink sets this to 1 30.0 VT. Change to setting 2 or 3.

    F12: Hardware Overcurrent

    Allen-Bradley Explanation:

    o Check Programming. Check for excess load, improper DC boost setting, DC brake volts set

    too high or other causes of excess current

    Melink Explanation

    o This is a short on the output side of the VFD.

    o Usually we see this when there is a short on the output side of the VFD. There could be a

    motor failure. Another common cause is a short in the disconnect switch on the roof.

    Check the wiring in the disconnect switch. After a heavy rain or after a hood cleaning

    process, water in the disconnect switch can be the root cause.

    o F12 can also be a short in the motor.

    o Disconnect the output wiring at the VFD. Restart the VFD. If the VFD runs and outputvoltage on the terminals is verified to be correct, then the problem is on the output side for

    the VFD.

    o Check that VFD is the correct HP for the motor.

    o Check parameter , A089, current limit. It should be 1.5xDrive rated current. See page of the

    Quickstart manual for the Drive Rated Current

    o Adjust Start Boost Parameter, A084 or S-Curve parameter A083. See F7 Fault

  • 8/13/2019 IH2 Detailed Troubleshooting Guide

    10/10

    F13: Ground Fault

    Allen-Bradley Explanation:

    o Check the motor and external wiring to the drive output terminals for a grounded condition.

    Melink Explanation

    o This is a short on the output side of the VFD.

    o Another common cause is a short in the disconnect switch on the roof. Check the wiring in

    the disconnect switch. After a heavy rain or after a hood cleaning process, water in the

    disconnect switch can be the root cause.

    o F13 can also be a short in the motor.

    o Disconnect the output wiring at the VFD. Restart the VFD. If the VFD runs and output

    voltage on the terminals is verified to be correct, then the problem is on the output side for

    the VFD.o Melink suggests contractor to bypass or replace the disconnect switch.

    o Melink suggests replacement of the motor.

    o Melink suggests replacement of the wiring between the VFD and motor. Wiring can be

    damaged by conduit that is not deburred completely.

    o We have had one case of F13 fault that was drive defect. It is very rare. Jeremy has seen

    F13 that occurred at a site but did not occur when the VFD was returned to the plant and

    tested in the RMA test area. The drive was sent back to the site, reinstalled, and then the

    VFD faulted again on F13. A New VFD on site did not give F13. Our only conclusion is that

    the fault is related to heat. VFD would warm up and trip on F13 fault.

    F33: Auto Restart Fault

    Allen-Bradley Explanation:

    o Correct the cause of the fault and manually clear.

    Melink Explanation

    o Check the fault history parameters.

    d007 is the previous fault. It will be 33

    d008 is the fault that occurred prior to the fault in d007. This is the cause of the

    fault F033 fault. Check d008 and refer to that fault for tips to repair the problem.

    d009 is the fault prior to the d008 fault.

    F100 Fault on Powerflex 400 VFDsThere is a bug in some PF400 VFDs where if the VFD clock exceeds 10000 hours, the VFD will trip on

    F100.

    1. Check parameters d310, d312, and d316. If any of these are 9999 or more, then theinternal timer on the VFD needs to be reset to zero.

    2. To reset the VFD timer to zero, go to parameter A195. Change the value to 2, save it.Then cycle power at the breaker. Leave the power off long enough for the VFD to gocompletely blank. And then turn the power back on.